VOLTAGE MONITORING RELAY             ACCURACY
VMR 13              Class 1.0 (Standard)
                                                               OUTPUT SPECIFICATION :
                                                               Relay                                         2 nos.
                                                               Relay Type                                    1 C/O (NO-C-NC)
                                                                                                             1st Relay 10A, 230V AC
                                                               Rating
                                                                                                             2nd Relay 5A, 230V AC
                                                               AUXILIARY SUPPLY :
                                                               Supply voltage                                230V AC, ±20%,50Hz
                                                               Power consumption
                                                               (VA RATING)
                                                               ENVIRONMENT CONDITION :
                                                               Operating Temp.                               0°C to 55°C
                                                               Relative HumidityUP to 95% RH
    PV = Process Value                                                          (non-condensing)
    SV = Set Value                                             Protection Level IP-65 (Front side) As per IS/IEC
                                                               (As per request) 60529 : 2001
               TECHNICAL SPECIFICATION                         NETWORK CONNECTION :
FEATURES :                                                     3Ø-3W/3Ø-4W/1Ø-2W
Protection Available
   Over Voltage              Asymmetry                                                      MECHANICAL INSTALLATION
   Under Voltage            Phase Loss
                                                                                                                                      Panel Cutout
   Over Frequency           Phase Sequence                          Outline Dimension (mm)
                                                                                                                                      Dimension (mm)
   Under Frequency
4 digit bright LED display, Auto/ Manual/ ZVR Reset Option
                                                                                               VMR 13
Network Selection 3Ø-3W/3Ø-4W/1Ø-2W
Time parameter: Power on delay, Trip delay                     96
                                                                       2405
                                                                      L1 L2 L3        OV UV AS PS PL
                                                                                                                                  92
                  Recovery time ( Auto Reset )                       R1 R2
                                                                                              RESET
INPUT SPECIFICATION :                                                                                                                         92
                                                                                                             3
                                                                                 96                                    42
Direct Voltage AC       50 to 300V AC (L - N) 3Ø-4W/1Ø-2W
                        85 to 520V AC (L - L) 3Ø-3W
Frequency               45.0 Hz to 65.0 Hz
Resolution              0.1 Volt
                                                                                                      TERMINAL CONNECTION
Accuracy                Class 1.0
DISPLAY AND KEY :                                                                                                           15
                                                                20           19           18            17        16             14    13      12      11
Display                 4 digit, 1line, 7 seg, 0.8” RED LED     D+ D-
                                                                                                Reset
                                                                                                                                 VL1 VL2 VL3 N
Keys                    SET/ENT, INC, DEC/RST                   MODBUS
                                                                                                                                  System:
GENERAL SPECIFICATION :                                                               Range                                       3Ph-4W/3Ph-3W/1Ph-2W
                                                                    CAT III           Voltage (L-L) : 85-520V AC                  Accuracy Class: 1.0
Dimension (mm)          96 (H) x 96 (W) x 42 (D) mm                                           (L-N) : 50-300V AC
                                                                Made in India
Panel Cutout            92 (H) x 92 (W) mm                                                                                        www.multispanindia.com
                                                                230V AC               !
Trip Setting            Under Voltage : 85-520V AC 3Ø-3W        50Hz, 4VA
                                  50-300V AC 3Ø-4W/1Ø-2W                                                         Relay-1                     Relay-2
                        Over Voltage : 85-550V AC 3Ø-3W                                                 NO         C     NC             NO     C     NC
                                                                L                N
                                  50-330V AC 3Ø4W/1Ø2W
                        Under Frequency : 45.0 Hz To 65.0 Hz    1                2         3            4          5        6    7      8       9     10
                        Over Frequency : 45.0 Hz To 65.0 Hz
                        Phase Asymmetry : 2-30%
Time Parameter          Power ON Delay Time : 0 To 99 Sec.
                        Trip delay Time : 0 To 999 Sec.
                        Recovery Time : 0 To 99 Sec.
                      KEY OPERATION                                                          MAINTENANCE
              FUNCTION                        PRESS KEY               1. The equipment should be cleaned regularly to avoid
                     OPERATOR MODE                                       blockage of ventilating parts.
To enter in parameter setting                     SET                 2. Clean the equipment with a clean soft cloth. Do not use
                                                  ENT For 5 sec          isopropyl alcohol or any other cleaning agent.
 To view individual phase voltage                    OR               3. Fusible resistor must not be replaced by operator.
 To Scroll & Hold Page                        SET                                    INSTALLATION GUIDELINES
                                              ENT    +
 To reset the relay contact in                                       1) Do not allow pieces of metal, wire clippings, or fine
 manual mode after tripping                                             metallic fillings from installation to enter the product or
                PARAMETER SETTING MODE                                  else it may lead to a safety hazard that may in turn
                                                                        endanger life or cause electrical shock to the operator.
It is used to set parameter value      SET
and to be save & exit from menu        ENT                           2) Circuit breaker or mains switch must be installed
                                                                         between power source and supply terminal to facilitate
To increment value in parameter
                                                                         power ‘ON’ or ‘OFF’ function. However this mains switch
setting
                                                                         or circuit breaker must be installed at convenient place
To decrement value in parameter                                          normally accessible to the operator.
setting
                                                                     3) Use and store the instrument within the specified ambient
                                                                        temperature and humidity ranges as mentioned in this
                       DISPLAY PAGE                                     manual.
    3Ø-4W                   3Ø-3W                   1Ø-2W
   1) Voltage L1-N       1) Voltage L1-L2       1) Voltage L1-N          !               SAFETY PRECAUTION
       2405                 4155                    2405                  All safety related codifications, symbols and instructions that
      L1 L2 L3             L1 L2 L3                 L1 L2 L3         appear in this operating manual or on the equipment must be
      R1 R2                R1 R2                    R1 R2            strictly followed to ensure the safety of the operating personnel
                                                                     as well as the instrument.
   2) Voltage L2-N       2) Voltage L2-L3       2) Frequency
                                                                         If all the equipment is not handled in a manner specified by
       2415                 4005                      505             the manufacturer, it might impair the protection provided by the
                                                                      equipment.
      L1 L2 L3             L1 L2 L3                 L1 L2 L3
      R1 R2                R1 R2                    R1 R2
                                                                                  Read complete instructions prior to installation
   3) Voltage L3-N       3) Voltage L3-L1                                         and operation of the unit.
       2500                 4305                                                 WARNING : Risk of electric shock.
      L1 L2 L3             L1 L2 L3
      R1 R2                R1 R2
                                                                                        WARNING GUIDELINES
   4) Frequency          4) Frequency
                                                                                WARNING : Risk of electric shock.
         500                  500
      L1 L2 L3             L1 L2 L3                                  1) To prevent the risk of electric shock, power supply to the
                                                                        equipment must be kept OFF while doing the wiring
      R1 R2                R1 R2
                                                                        arrangement. Do not touch the terminals while power is
                                                                        being supplied.
                                                                     2) To reduce electro magnetic interference, use wire with
               MECHANICAL INSTALLATION                                  adequate rating and twists of the same of equal size shall
                                                                        be made with shortest connection.
1) To install the instrument on a DIN rail, raise the clamp at the
   back of the instrument and place it on the rail. Now release      3. Cable used for connection to power source, must have a
   the clamp, so the instrument fits on the DIN rail.                   cross section of 1mm or greater. These wires should have
2) Ensure proper fitting of the instrument by pulling it outwards.      insulations capacity made of at least 1.5kV.
3) To remove the instrument raise the clamp to release it from       4) A better anti-noise effect can be expected by using
   the DIN rail.                                                        standard power supply cable for the instrument.
4) The equipment in its installed state must not come in
   close proximity to any heating source, caustic vapors, oil
   steam, or other unwanted process byproducts.
5) Do not connect anything to unused terminals.
                                                                                                                               Page -1
             PARAMETER SETTING                                   Password 11 : To Enable / Disable parameter
                                                                               (Over Voltage, Under Voltage,over
                                                                                Frequency,Under Frequency,
                                                                                Asymmetry,Phass loss, Phase
                          Press SET key
                          for 5 sec
                                                                                sequence)
                                                                 Password 37 : To set Power on delay time, Trip delay
                                                                               Time,Relay Fault Mode, Reset mode,
                                                                               network selectiom
                            pass          Password
                                                                      Relay-1 Settings             Press SET key
            Press   SET
                          key                                                                      for 5 sec
                                11          Enter Password 11
            Press   SET
                          key                                                                           pasS         Password
                                OV        Over Voltage                           Press     SET
                                                                                                  key
            Press   SET
                          key                                                                                          Enter Password 73
                                                                                                         73
                            eNBL          (Enable/Disable)                       Press     SET
                                                                                                  key
            Press   SET
                          key                                                                                   If over voltage is enable
                                UV        (Under Voltage)         If Over                              OVR1          (Over Voltage Of Relay 1)
                                                                 Voltage
                                                                is Disable       Press     SET
                                                                                                  key
            Press   SET
                          key
                                                                                                                     (Over Voltage value)
                            eNBL          (Enable/Disable)                                              280          (85-550V For 3Ø-3W )
            Press   SET
                          key                                                    Press    SET
                                                                                                 key                 (50-330V For 3Ø-4W/1Ø-2W )
                                                                                                               If under voltage is enable
                                OF        (Over Frequency)
                                                                 If Under
                                                                                                       uVR1          (Under Voltage of Relay 1)
            Press   SET
                          key                                    Voltage         Press     SET
                                                                                                  key
                                                                is Disable
                            eNBL          (Enable/Disable)
            Press         key
                                                                                                        210         (Under Voltage Value)
                    SET
                                                                                                                    (85-520V For 3Ø-3W )
                                                                                                                    (50-300V For 3Ø-4W/1Ø-2W )
                                                                                 Press     SET
                                                                                                  key
                                UF        (Under Frequency)
                                                                                                               If Over Frequency is Enable
            Press   SET
                          key                                                                          OFR1          (Over Frequency of Relay 1)
                                                                  If Over
                            eNBL          (Enable/Disable)
                                                                Frequency
                                                                                 Press     SET
                                                                                                  key
                                                                is Disable
            Press   SET
                          key
                                                                                                        550          (Over Frequency Value)
                                                                                                                      (45.0-65.0 Hz)
                                as        (Asymmetry)
IF 1Ø-2W                                                                         Press     SET
                                                                                                  key
 Selected   Press   SET
                          key                                                                                  If Under Frequency is Enable
                                                                                                       UFR1          (Under Frequency Of Relay 1)
                            eNBL          (Enable/Disable)       If Under
                                                                Frequency
            Press   SET   key                                   is Disable
                                                                                 Press     SET
                                                                                                  key
                                                                                                        4SS          (Under Frequency value)
                                pL        (Phase loss)                                                                (45.0-65.0 Hz)
                                                                                Press    SET
                                                                                                 key           IF 3Ø-4W/3Ø-3W Selected
            Press   SET
                          key
                                                                      If                                        If Asymmetry is Enable
                                                                Asymmetry                              ASR1          (Asymmetry Of Relay 1)
                            eNBL          (Enable/Disable)       is Disable
                                                                     or          Press     SET
                                                                                                  key
            Press   SET
                          key                                   IF 1Ø-2W
                                                                   Selected
                                                                                                         20          (Asymmetry Percentage)
                                ps        (Phase Sequence)                                                           (2 - 30%)
IF 1Ø-2W
Selected    Press   SET
                          key
                                                                                                 Press   SET    key for save & exit
                            eNBL          (Enable/Disable)
                     Press      SET   key for save & exit
 Password 73 : Relay 1 Settings                                                                                                 paSs          Password                Press SET key
                                                                                                                                                                      for 5 sec
 Password 97 : Relay 2 Settings                                                                        Press     SET
                                                                                                                         key
              ( Relay -1 & Relay -2 Settings : To Set                                                                              37               Enter Password 37
              Trip Value Of Over Voltage, Under                                                        Press     SET
                                                                                                                         key
              Voltage, Over Frequency, Under                                                                                    PODL              (Power On Delay Time)
              Frequency, Asymmetry Percentage )                                                        Press     SET
                                                                                                                         key
                                                                                                                                    5              (0-99 Sec.)
       Relay-2 Settings          Press SET key
                                 for 5 sec                                                             Press     SET
                                                                                                                         key
                                                                                                                                  TDL         (Trip Delay Time)
                                                                                                       Press     SET
                                                                                                                         key
                                      pASs         Password                                                                         S         (0-999 Sec.)
                  Press   SET
                                key                                                                    Press     SET
                                                                                                                         key
                                        97           Enter Password 97                                                          Rest          (Reset mode)
                                                                                                       Press     SET
                                                                                                                         key
                  Press   SET
                                key
                                                   (Relay - 2 Mode)
                                                                                                                                autO
                                        r2m                                                            Press     SET
                                                                                                                         key                  (Auto / Manual / ZVR Reset)
                                                                                                                                          If Auto/ ZVR Reset mode select
                  Press   SET
                                key
                                                                                     If Manual                                  rECt          (Recovery time)
                                        R 1        (Relay -1 / Relay -2)                               Press     SET
                                                                                                                         key
                                                                                    Reset mode
                  Press   SET
                                key           If R 2 is Selected                       select
                                                                                                                                    5         (0 to 99 sec.)
                                              If over voltage is enable
    If Over                           OVR2         (Over Voltage Of Relay-2)                           Press     SET     key
   Voltage
  is Disable      Press   SET
                                key                                                                                             RFM           (Relay Fault Mode)
                                                                                                       Press     SET     key
                                      280          (Over Voltage Value)                                                            ON         (ON/OFF)
                                                   (85-550V For 3Ø-3W )
                                                                                                       Press     SET     key
                  Press   SET
                                key                (50-330V For 3Ø-4W/1Ø-2W )
                                              If Under Voltage is Enable                                                        pFFM          (Power Fail Fault memory)
                                      OVR2         (Under Voltage of Relay-2)                          Press     SET     key
   If Under
   Voltage        Press   SET
                                key                                                                                               yes         (Yes/No)
  is Disable                                                                                           Press     SET     key
                                      280          (Under Voltage Value)                                                                      (Network selection)
                                                   (85-520V For 3Ø-3W )
                  Press   SET   key                (50-300V For 3Ø-4W/1Ø-2W)                           Press     SET
                                                                                                                         key
                                              If Over Frequency is Enable                                                       3p4W          (3Ø-3W/3Ø-4W/1Ø-2W )
                                      OFR2         (Over Frequency of Relay-2)
                                                                                                                          Press     SET   key for save & exit
    If Over
  Frequency       Press   SET
                                key
  Is Disable
                                      450          (Over Frequency Value)                                              FAULT MESSAGE
                                                   (45.0-60.0 Hz)                                                                                   ◘ OverVoltage in Relay 1
                  Press   SET
                                key                                                         OVR1
                                                                                            L1 L2 L3     OV
                                                                                                                                   4006
                                                                                                                                  L1 L2 L3    OV     VL1L2(3Ø-3W) or VL1(3Ø-4W)
                                              If Under Frequency is Enable                                             Scroll
                                                                                            R1 R2                                 R1 R2              Over Voltage Value=400.6V
   If Under
                                      UFR2         (Under Frequency of Relay-2)             UVR2                                  2205              ◘ Under Voltage in Relay 2
                                                                                           L1 L2 L3      UV                       L1 L2 L3    UV      VL2L3(3Ø-3W) or VL2(3Ø-4W)
  Frequency       Press   SET
                                key
  is Disable
                                                                                           R1 R2                                  R1 R2               Under Voltage Value=220.5V
                                      550          (Under Frequency Value)                  OfR2                                    525              ◘ Over Frequency Fault in Relay 2
                                                   (45.0-65.0 Hz)                          L1 L2 L3      OF                       L1 L2 L3    OF     ◘ Over Frequency
                  Press   SET
                                key       IF 3Ø-4W/3Ø-3W Selected
                                                                                           R1 R2                                  R1 R2                Value=52.5 Hz
       If                                     If Asymmetry is Enable                        UfR1                                    495              ◘ Under
                                                                                                                                                           Frequency Fault in Relay 1
 Asymmetry                                                                                 L1 L2 L3      UF                       L1 L2 L3   UF      ◘ UnderFrequency
  is Disable                          ASR2         (Asymmetry Percentage                   R1 R2                                  R1 R2               Value=49.5 Hz
      or          Press   SET
                                key                Of Relay -2)
                                                                                                                                                     ◘ Asymmentry  Voltage
  IF 1Ø-2W                                                                                  ASR1
                                                                                           L1 L2 L3
                                                                                                                                      20
                                                                                                                                  L1 L2 L3             between y & B Phase in Relay 1
   Selected
                                        2O         (Asymmetry Percentage)                  R1 R2
                                                                                                         AS
                                                                                                                                  R1 R2
                                                                                                                                              AS
                                                                                                                                                     ◘ Asymmentry Percentage
                                                   (2-30%)                                                                                             = 20 %
                                                                                                         L1 L2 L3        PL                          ◘ L1
                                                                                                 PL                                                         - Phase loss
                                                                                                         R1 R2
                                Press   SET   key for save & exit
                                                                                                         L1 L2 L3        PS                          ◘ Phase   sequence Fault
                                                                                                 Ps      R1 R2
NOTE :-                                                                                  Note : LED Status-            blinking LED LED on             LED off
- If R2M ( Relay-2 mode ) is selected as R1 ( Relay-1 ), all the setting          Specifications are subject to change, since development is a continuous process,
  done for Relay-1 will be automatically set for Relay-2.                                     So for more updated operating information and Support,
- If Reset Mode Selected As ZVR ( Zero Value Reset ), then the Relay will                    Please contact our Helpline: 9081078681/9081078683 or
  be reset after Selected Reset time once the healthy condition achieved                           Email at service@multispanindia.com Ver:1202
  OR Zero Value reached.
                                                                                                                                                                             Page -2