Current Protection Relay TRIP SETTING:

CPR 19 Under Current 0.00 to CTR


Over Current 0.00 to CTR
Short Circut 1 - 9 Scale
Lock Rotor Point 0.5 to 9.0 Scale
Asymmetry 5 - 60%

TIME PARAMETER:
Power On Delay 0 to 99 Sec
Initial Time Delay 0 to 99 Sec
Reset Time 0 to 99 Sec

OUTPUT SPECIFICATION:
Relay 2 Nos
1st Relay ( NO - C - NC )
Relay Type nd
2 Relay ( NO - C )
1st Relay 10Amp, 250V AC
Rating nd
2 Relay 5 Amp, 250V AC
FEATURES
ENVIRONMENTAL CONDITION:
User Selectable Trip Time
Working Temperature 0 to 55°C
Auto/Manual/ZVR Reset Function Storage Temperature 0 to 55°C
True RMS Measurement Relative Humidity 95 % RH Non-Condensing
Protection Available Protection Level IP-65 (Front side As per
(As Per request) IS/IEC 60529 : 2001)
Over/Under Current Short Circuit
Single Phase Prevention Asymmetry TERMINAL CONNECTION
Lock Rotor Point
N
TECHNICAL SPECIFICATION L3
L2 LOAD
INPUT: L1

Current AC
20 19 18 17 16 15 14 13 12 11
Primary CT Ratio 5 to 9999 Amp selectable S1 S2 S1 S2 S1 S2 C NO
Relay-2
L1 L2 L3

Secondary Current AC 0.1 to 5 Amp


Relay-1
Burden < 0.2VA L N NO C NC

Overload Up to 6A continuous 1 2 3 4 5 6 7 8 9 10

Frequency 45.0 to 65.0 Hz #

DISPLAY AND KEYS:


Display 3 Digit, 3 Line 7 Seg 0.56”,
RED LED KEY OPERATION
Keys SET, RST, INC, DEC
Operator Mode
DIMENSION:
Size (mm) 96 (H) X 96 (W) X 54 (D) mm To Enter In Parameter Setting Mode SET

Panel Cutout (mm) 92 (H) X 92 (W) mm To Reset The Relay Contact manually after RST
Tripping
AUXILIARY SUPPLY: Parameter Setting Mode
Supply Voltage 100 to 270V AC/DC, 50/60Hz Edited Parameter Value to be Set, And Move SET

Power Consumption to the Next Step


4VA @ 230 AC MAX
To Increment Parameter Value

To Decrement Parameter Value


MECHANICAL INSTALLATION MAINTENANCE
1. The equipment should be cleaned regularly to avoid
CPR 19
blockage of ventilating parts.
R1 2. Clean the equipment with a clean soft cloth. Do not use
isopropyl alcohol or any other cleaning agent.

90.50
3. Fusible resistor must not be replaced by operator.
96

! SAFETY PRECAUTION
SET RST

All safety related codifications, symbols and instructions


2.50 54.00
96 that appear in this operating manual or on the equipment
must be strictly followed to ensure the safety of the operating
FRONT VIEW RIGHT SIDE VIEW personnel as well as the instrument.
All dimensions are in mm
Panel Cutout If all the equipment is not handled in a manner specified
by the manufacturer, it might impair the protection provided
by the equipment.

Read complete instructions prior to installation


and operation of the unit.
92

WARNING : Risk of electric shock.

92
WARNING GUIDELINES

WARNING : Risk of electric shock.


INSTALLATION GUIDELINES 1. To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while doing the wiring
1. This equipment, being built-in-type, normally becomes a arrangement. Do not touch the terminals while power is
part of main control panel and in such case the terminals being supplied.
do not remain accessible to the end user after installation 2. To reduce electromagnetic interference, use wire with
and internal wiring. adequate rating and twists of the same of equal size shall
2. Do not allow pieces of metal, wire clippings, or fine metallic be made with shortest connection.
fillings from installation to enter the product or else it may
3. Cable used for connection to power source, must have a
lead to a safety hazard that may in turn endanger life or 2
cross section of 1mm or greater. These wires should have
cause electrical shock to the operator.
insulations capacity made of at least 1.5kV.
3. Circuit breaker or mains switch must be installed between
power source and supply terminal to facilitate power ‘ON’ or 4. A better anti-noise effect can be expected by using
‘OFF’ function. However this mains switch or circuit breaker standard power supply cable for the instrument.
must be installed at convenient place normally accessible to
the operator.
4. Use and store the instrument within the specified ambient
temperature and humidity ranges as mentioned in this
manual.

MECHANICAL INSTALLATION GUIDELINES

1. Prepare the panel cutout with proper dimensions as shown


above.
2. Fit the unit into the panel with the help of clamp given.
3. The equipment in its installed state must not come in close
proximity to any heating source, caustic vapors, oils steam,
or other unwanted process byproducts.
4. Use the specified size of crimp terminal (M3.5 screws) to
wire the terminal block. Tightening the screws on the
terminal block using the tightening torque of the range of
0.5 N.m.
5. Do not connect anything to unused terminals.
Lock Rotor Point
CONTROL FUNCTION
Power On:- 5 Sec Lock Rotor Point:- 2.0
Initial Time Delay:- 5 Sec Over Current Value:- 2.0A
Under Current Lock Rotor Point:- Enable
Over Current:- Disable Relay Fault:- OFF
Power On:- 5 Sec Under Current:- 3.0A Reset Mode:- Auto
Reset Time:- 5 Sec
Initial Time Delay:- 5 Sec Under Current time:- 5 Sec
Relay Fault:- OFF Case-1
Under Current:- Enable
Reset Mode:- Auto
Reset Time:- 5 Sec
5A
R,Y Phase

Lock Rotor Point


4A
R,B Phase

B Phase

Current
3.0A 3A

Y Phase
2.0A 2A

1.0A
0 5 10 15 20 25 30
TIME
ON
0 5 10 15 20 25 30 35 40 Relay
OFF OFF

ON ON
Power ITD TRP
OFF OFF OFF Time ON
Under Under
Power Current Current
ON ITD Delay Reset ITD TRP
Delay
Case-2

Asymmetry 5A B Phase

Power On:- 5 Sec Asymmetry Percentage:- 50% 4A


Initial Time Delay:- 5 Sec Asymmetry Time:- 5 Sec R,Y Phase
Asymmetry:- Enable Relay Fault:- OFF
Current

Reset Mode:- Auto 3A

Reset Time:- 5 Sec


2A

3.0A
R,Y Phase
0 5 10 15 20 25 30
2.0A TIME
ON
1.5A Relay
OFF OFF
B Phase
1.0A
Power ITD TRP
Time ON

0 5 10 15 20 25 30 35 40 Time
(Second)

OFF
ON
OFF
ON
OFF
NOTES
Under Under
Power
ON
ITD Balance
Delay
Reset ITD Balance TRP
Delay
Reset Mode:
1) If Reset Mode Selected is Manual, then the Fault
will Reset Manually by pressing the Reset key on
the instrument.
2) If Reset Mode Selected is Auto, then the Relay will
be reset after Selected Reset time once the healthy
condition achieved.
3) If Reset Mode Selected As ZVR (Zero Value Reset),then
the Relay will be reset after Selected Reset time once
the healthy condition achieved OR Zero Value reached.

Relay Fault:
1) If Relay fault selected is “off” than Relay will turn
“off” when fault is achieved, otherwise Relay will
remain turn “on”.

2) If Relay fault selected is “on” then Relay will turn


“on” when fault is achieved, otherwise Relay will
remain turn “off”.
FAULT MESSAGE

Under Current fault Message Single Phase Prevention Fault


1) Unc in R Phase 1) SPP in R Phase
R R Phase Fault
Fault in R phase
R S P P Single Phase Prevention
U N C Under Current 0 0 0 R - Phase Voltage Value
2 8 7 R phase Current Value 2) SPP in Y Phase 3) SPP in B Phase
2) Unc in Y Phase 3) Unc in B Phase Y B
Y B S P P S P P
U N C U N C 0 0 0 0 0 0
2 7 2 2 6 3 Lock Rotor Point
4) Unc in RY Phase 5) Unc in YB Phase 1) LRP in R Phase R R Phase Fault
R Y Y B L R P Lock Rotor Point
U N C U N C 5 0 0 Phase Current Value
2 7 0 2 6 0 2) LRP in Y Phase 3) LRP in B Phase
6) Unc in RB Phase 7) Unc in RYB Phase
Y B
R B R Y B L R P L R P
U N C U N C 5 0 0 5 0 0
2 5 5 2 5 5
Asymmetry Fault Message
1) AS in R Phase
R B Fault Between R & B Phase
a s Asymmetry
5 5 Unbalance Percentage
Between R & B Phase
2) AS in Y Phase 3) AS in B Phase
R y Y B
a s a s
5 9 5 7
4) AS in RYB Phase

R Y B
a s
5 5
»
Password = 29 » Single Phase Prevention (SPP)
Short Circuit, Lock Rotor Point,
Power Fault Memory
Asymmetry Current

Long Press SET Key to enter into Password

PARAMETER SETTING

P A S Enter Password = 19 P A S Enter Password = 29

1 9 2 9
Press SET Key Press SET Key
p O N Power on S P P Single Phase Prevention
T I M Time
5 (0-99 Sec) E N B (Enable / Disable)
Press SET Key Press SET Key
If Enable
I T D Initial Delay
S P P Single Phase Prevention
T I M Time If
T I M Time
5 (0-99 sec) Disable (0 to 999 Sec )
5
Press SET Key Press SET Key
U N C Under Current
S C Short Circuit

E N B (Enable/Disable)
E N B (Enable / Disable)
Press SET Key Press SET Key
If Enable If Enable
U N C Under Current
S C Short Circuit
If
V A L Value
Disable S C L Scale
If (0.00-CTR)
Disable 2 0 0 2 ( 1-9 )
Press SET Key Press SET Key
U N C Under Current
L R P Lock Rotor Point
T I M Delay Time
5 (0-999 Sec)
E N B (Enable / Disable)
Press SET Key Press SET Key
If Enable
O V C Over Current
L R P Lock Rotor Point
If S C L Scale
E N B (Enable/Disable) Disable
2 0 ( 0.5 - 9.0 )
Press SET Key Press SET Key
If Enable
O V C Over Current a s Asymmetry
V A L Value
If Disable

5 0 0 (0.00-CTR) e n b (Enable / Disable)


Press SET Key Press SET Key
If Enable
O V C Over Current
a s Asymmetry
T R P Trip on
P E R Percentage
T I M ( Time/Curve )
If 2 0 ( 5-60% )
If Press SET Key If
Curve Disable Press SET Key
Time
O V C Over Current O V C Over Current
T I M Delay Time C R V Curve Value a s Asymmetry
5 (0-999 Sec) 5 0 C (2.5C/5.0C/ t I m Delay Time
10C )
5 ( 0-999 Sec )
Press SET Key

Press SET key to Save & exit Press SET key to Save & exit
P A S Enter Password = 39

3 9
Press SET Key
C T R C.T. Ratio

5 ( 5-9999A )

Press SET key to Save & exit

PARAMETER SETTING
Press & Key
P
R A
S ST Reset
m O D Mode Together
M 2A 9N Manual/Auto/ZVR (Zero Value
Press SET Key Reset)
If Reset Mode is Auto/ZVR
P
r A
s S t Reset
If Reset
Mode
T I M Time
is Manual 2 95 ( 0-99 Sec )
Press SET Key

R
P LA YS Relay 1
F L T Fault
O2 N9 On/Off
Press SET Key
R
P LA 2S Relay 2
F L T Fault
O2 N9 On/Off
Press SET Key
p
P f
A m
S Power Fault Memory

2 s
y e 9 Yes/No

Press SET key to Save & exit