CSD PRV 2300
CSD PRV 2300
Q RG
Quick Reference Guide
This QRG will help you step-by-step installation, operation and programming
procedure. Please go through all the instructions carefully prior to implementing.
R37QRG000132
Our products and batteries must not be disposed of as household waste. For disposing
batteries it is necessary to observe the local national/international directives.
By disposing of these products correctly you will help to save valuable resources and prevent
any potential negative effects on human health and the environment.
Introduction
In the family of protection relay, CSDPR-V2-300 is numeric multi powered Over-current
relay specially designed for ring main units & feeder protection. It combines the following
functions in one unit:
u Over current, Short Circuit, Earth Fault & Earth Fault High set protection
u DEFT & Inverse characteristics for O/C and E/F individually selected for
phase & earth fault
u Wide operating ranges of the auxiliary supply voltage (AC/DC)
u Remote trip *
u Switch on to fault (SOTF) protection
u Remote protection block input DI*
u Potential pulse output for direct triggering the circuit breaker coil
u Potential free alarm contacts available
u Unbalance/ Asymmetric protection
u Circuit breaker failure protection
u Harmonic blocking (via DFT Filter) to avoid any unwanted tripping
u Two sets of setting groups
u Last 5 Fault and 10 Event record with Time stamp
u RS-485 Modbus
u USB port for PC / Laptop interface
Design
Relay will get energized from any of the following available sources:
u Aux. supply
u CT current
u Internal battery
u USB port
Relay will operate its trip contacts only when CT current is present or Aux. supply is available,
with other power sources, only the relay display/HMI will be available.
In the absence of Aux supply/Battery voltage/USB, LCD will get energized, if CT current is
10% of rated current or above. Trip coil will be operated, if CT current in single phase is at
least 20% of rated current or 15% of rated current in three phases. Relay is not powered from
Earth CT, so for earth fault protection, phase current is mandatory.
02
Front Interface of the Relay
CSDPR-
V2
R M U P R O T E C T I O N RE LAY
See Description B
L1 L2 L3 E PICKUP TRIP TCS CBFP
MHT Ready /
MHT Ready LED
See Description A ON READY/HLTHY
Up Scroll /
Decrement Key ENTER
Down Scroll /
Increment Key
Enter Key
RESET
Description A : This key is used to ON the LCD when available source is Aux Supply, CT current or USB port)
Description B : This key is used to ON the LCD when available source is only Battery.
03
Conn. Diagram (TCS Model) * In TCS model : Remote Trip & Remote Block DI will not be available.
L1 Aux-P Aux-N
L2 A13 A14
L3
A1 COM
DO-4
A2 NO
Latch
Aux Supply A3 COM
P1 S1 E1 DO-3
A4 NO
IL1
E2 A5
P2 S2 COM
DO-2
A6 NO Operates with
P1 S1 E3 A7 COM only Aux supply
IL2 DO-1 A8
E4 NO
P2 S2
DI-2
* CB Open A9
P1 S1 E5 A10 DI-(Comm)
* CB Close
IL3 A11 DI-1
E6
P2 S2
TF+ B1
Flag Indicator
E7 TF- B2
Ie
E8 TC- B3
Trip Coil
TC+ B4
E9
A
E10 B8
B7 B RS 485
B6
L1 Aux-P Aux-N
L2 A13 A14
L3
A1 COM
DO-4
A2 NO
Latch
Aux Supply A3 COM
P1 S1 E1 DO-3
A4 NO
IL1
E2 A5
P2 S2 COM
DO-2
A6 NO Operates with
P1 S1 E3 A7 COM only Aux supply
IL2 DO-1 A8
E4 NO
P2 S2
* Remote Block A9 DI-2
P1 S1 E5 A10 DI-(Comm)
IL3 * Remote Trip A11 DI-1
E6
P2 S2
TF+ B1
Flag Indicator
E7 TF- B2
Ie
E8 TC- B3
Trip Coil
TC+ B4
E9
A
E10 B8
B7 B RS 485
B6
NOTE: While doing the HV test, don`t connect the MHT terminal (C4-C5),
as internal capacitor bank could be in charged state & it can harm the circuitry.
04
Dimension Details (All the dim. are in mm) Side View
Front View
128.0
110.0 118.0
158.0
167.8
158.0
167.8
* ordering based
05
Back Terminal view (TCS model)
DI-Common
06
Photograph shown here for have an idea only
Battery changing Procedure
07
Technical Data
Front Port: CSE protocol with CSE LIVELINK on mini USB cable type A/A
General Data
Measuring Input
Rated data Rated current I N (1A)
Frequency F N: 50/60 Hz
Measurement Measurement of Phase / Earth current starts from 5%
08
Thermal Withstand Capacity
Thermal withstand Continuously 2.5A
capacity 10s 15A
for In=1A 1s 80A
Accuracy
09
Inverse Graph Representation
Inverse Time characteristics
10
How to do Settings
Two group of Protection Setting are available in CSDPR-V2 relay. User can select
One Group as Active Group. For setting below are simple steps for configuration:
Default Password for settings : “ 4-Times Enter Key”
Default First Screen
MAIN DEFAULT SCREEN PAGE:
The very first Screen of the HMI shows the Measured Primary Current for all the
phases based on CT ratio.
L1 : 0000.0 A
L2 : 0000.0 A
<Menu 1>
(EDIT/VIEW PARAMETERS)
# EDIT/VIEW #
Press Key <GROUP SELECT > : For Active Group Selection of Parameter
<PROTECTION > : Protection Related Parameter Menu
<COLDLOAD PRT > : Cold Load Protection Menu
<FAULT RECORD > : Fault Record Menu
<EVENT RECORD > : Event Record Menu
<DO ASSGNMNT > : Programmable Relay Assignment Menu
By using <DO RESET > : Programmable Relay Reset Menu
the <TRIP TYPE > : Trip Type
scroll keys <RST TRIP CNT > : Reset Trip count Menu
<DISPLAY OPTN > : Display Options Menu
select the
<BATTRY STATS > : Battery Status Menu
desired
<TRIP TEST > : Output Trip Test Menu
menu and
<COMMN SETTNG > : Communication RS485 Menu
press <LOAD DEFAULT > : Load Default Menu
ENTER. <EDIT RTC > : Clock Setting Menu
<CHNGE PSWORD > : Password Change Menu
< FACTORY MODE > : Factory Setting Menu
* <RELAY VERSON > : Relay Version Menu
← BACK
Note : - * Menu Model Dependent FACTORY MODE Setting are not for the users.
11
From Menu-1:
On selecting GROUP SELECT by pressing ENTER
key, user can change the active group by using # GROUP SELECT #
ENTER and then scroll key.
ACTIVE-GRP : GRP1
Press Enter and If the user selects the YES option ←BACK
then it will ask to enter the correct password or else to
go to the previous menu by selecting the other
options by pressing ENTER key.
From Menu-1:
# PROTECTION #
O n s e l e c t i n g CTRatio : 0001 : CT Ratio for primary current display
PROTECTION by
pressing ENTER key.
Frequency : 50Hz : Frequency characteristic
User can see the list of all PhaseCh : DEFT : Phase over-current trip characteristic
the protection setting EarthCh : DEFT : Earth over-current trip characteristic
parameter by using the
scroll keys. l> : 0.20xIn : Over-current Pickup
ti> : 0.01 : TMS Over-current Setting
Press ENTER to select t> : 0.1s : DEFT Trip Time
the desired Parameter &
use SCROLL keys to l>> : 0.5xIn : Short Circuit Protection
Edit the selected one. t>> : 0.03 : DEFT Trip timing for SC Protection
Ie> : 0.05xIn : Earth Over-current Pickup
If the user change any of
the setting, It is required tie> : 0.01 : Inverse Trip Time
to save the changes by te> : 0.05s : DEFT Trip Time
pressing ENTER key Ie>> : 0.01xIn : Earth High-set Pickup
and than selecting YES
option, after that entering te>> : 0.05 : DEFT Trip timing Earth High
the correct password to SOFTpk : DISABLE : SOTF pickup setting
save the setting or else Unbalnc : 5% : Unbalance
to go to the previous
menu by selecting the tUnblnc : 0.50s : Unbalance DEFT Trip Time
other options & by CBFP : YES : CBFP Supervision Time
pressing ENTER key. tCBFP : 0.15s : CBFP Supervision Time
td_TCS : 2.00s : TCS Trip Time
←BACK
12
From Menu-1:
On selecting COLD LOAD PRT by pressing ENTER
key, User can see the list of all the parameter by using the #COLD-LOAD-SET#
scroll keys.
Press ENTER to select the desired Parameter & use ColdLdPrt : DISABLE
SCROLL keys to Edit the selected one. tCldLoad : 00.10s
If the user change any of the setting, It is required to save
←BACK
the changes by pressing ENTER key and than selecting
YES option, after that entering the correct password to
save the setting or else to go to the previous menu by
selecting the other options & by pressing ENTER key.
From Menu-1:
On selecting FAULT RECORD, by pressing ENTER # FAULT RECORD #
key, Fault no. screen will appears. By using ENTER & <FAULT NUMBER>
Scroll keys select the desired Fault no. for its details. To <ERASE FAULTS>
go to the previous menu press BACK key. ←BACK
From Menu-1:
On selecting EVENT RECORD, by pressing ENTER # EVENT RECORD #
key, Event no. screen will appears. By using ENTER & <SELECTION>
Scroll keys select the desired Event no. for its details. To <EVENT NUMBER>
go to the previous menu press BACK key. <ERASE EVENTS>
←BACK
From Menu-1:
On selecting DO ASSGNMNT by pressing ENTER key,
# DO ASSGNMNT #
User can see the list of all the parameter by using the
scroll keys. Press ENTER to select the desired
I> : DISABLED
Parameter & use SCROLL keys to Edit the selected I>> : DISABLED
one. If the user change any of the setting, It is required to Ie> : DISABLED
save the changes by pressing ENTER key and than Ie>> : DISABLED
selecting YES option, after that entering the correct Unbaln : DISABLED
password to save the setting or else to go to the previous CBFP : DISABLED
menu by selecting the other options & by pressing TCS : DISABLED
ENTER key. AllFlt : DISABLED
SOTF : DISABLED
←BACK
13
From Menu-1:
On selecting TRIP TYPE by pressing ENTER key, User
can see the list of parameter by using the scroll keys. # TRIP TYPE #
Press ENTER to select the desired Parameter & use TripO/P : TRIP-COIL
SCROLL keys to Edit the selected one. ←BACK
From Menu-1:
On selecting RST TRIP CNT by pressing ENTER key,
User can Reset the Trip count by selecting the YES Reset Count....?
option or else comes out from the menu by selecting the YES NO CANCEL
other option.
From Menu-1:
On selecting DISPLAY OPTN by pressing ENTER key, # DISPLAY-OPTION #
User can see the list of parameter by using the scroll MODE : AUTO OFF
keys. ←BACK
Press ENTER to select the desired Parameter & use
SCROLL keys to Edit the selected one.
From Menu-1:
# BATTERY STATUS #
On selecting BATTRY STATS by pressing ENTER BATTERY : OK
key, User can see the status of the Battery, whether it
←BACK
is OK or NOT.
From Menu-1:
On selecting TRIP TEST by pressing ENTER key, # TRIP TEST #
User can see the list of parameter by using the scroll
keys. LED/DO TEST
Press ENTER to select the desired Parameter & use BREAKER TEST
SCROLL keys to perform the test.
LATCH RESET
If the user selects any of the option it will ask to ←BACK
continue the Test, If the user selects the YES option
then Right/Left key are required to press to perform
the Test, else select other option and press enter to go
to the previous menu .
14
From Menu-1:
On selecting COMMN SETTING by pressing ENTER
key, User can see the list of all the parameter by using the # COMMN SETNG #
scroll keys. SLAVE ADD : 01
Press ENTER to select the desired Parameter & use BAUDRATE : 9600
SCROLL keys to Edit the selected one.
PARITY : NONE
If the user change any of the setting, It is required to save ←BACK
the changes by pressing ENTER key and than selecting
YES option, after that entering the correct password to
save the setting or else to go to the previous menu by
selecting the other options & by pressing ENTER key.
From Menu-1:
LOAD DEFAULT
On selecting LOAD DEFAULT menu by pressing
ENTER key, User will ask to Enter the correct password.
Enter Passwrd
If the user enter the correct password, the default values
of the relays will restored.
Saving .........
From Menu-1:
On selecting EDIT RTC Menu, user can set the Date, # EDIT RTC #
Month Year Day, Hour, Minute, Second by using the HOUR : 11
S c r o l l k e y s .
MIN : 26
Press ENTER to select the desired Parameter & use
SCROLL keys to Edit the selected one. SEC : 59
DATE : 23
If the user change any of the setting, It is required to save MONTH : 08
the changes by pressing ENTER key and than selecting YEAR : 2019
YES option after that entering the correct password to
save the setting or else to go to the previous menu by ←BACK
selecting the other options & by pressing ENTER key.
From Menu-1:
Enter Passwrd
On selecting CHNGE PSWORD Menu by pressing the
ENTER key, user will ask to enter the password. If the
New PASSWORD
user entered the correct password the next screen will
ask to Enter the New Password after that re-enter the Re-PASSWORD
password for confirmation. If the password changed
successfully, it will flash password change message.
SUCCESSFUL .!
PASSWD CHGD
From RELAY VERSION MENU: CSDPR-V2-300-D
On selecting RELAY VERSION Menu, by pressing
Enter key, it will show the screen. -L/H-P-T
Ver:V1.0.00.02
User can see the relay information by using the scroll DN:220819
keys. To go to the previous menu press BACK key. ←BACK
15
Trouble Shooting Points
Digital outputs are Aux Supply is not connected Two Digital outputs (Relays)
not operating work only in presence of
Auxiliary supply. To recheck
the Digital output operation,
Go to Trip Test Menu, Enter in
the <LED/RLY TST> option &
test the Relays.
16