LGE MULTI V 5 Specification Data
ARUM300LTE5
 Multi V 5 Combination Outdoor Unit
 1xARUM120LTE5; 1xARUM180LTE5
 Type Air Source Heat Pump & Heat Recovery                                                          LG participates in the ECP programme
                                                                                                    for EUROVENT AC. Check ongoing
 Colour Warm Grey NL503K/Dawn Grey NL507K                                                           validity of certification:
                                                                                                    www.eurovent-certification.com
 Power Supply , V, Hz      3, 380-415, 50
  Performance                                                                                             Features
                            Cooling                    kW                     84.0                                              High sided shell, hermetically sealed inverter scroll
  Nominal Capacity
                            Heating                    kW                     84.0                                              High pressure oil return
                            Cooling                    kW                    18.49                                              Vapour injection
  Power Input
                            Heating                    kW                    16.97                        Compressor            Advanced wear-resistance PEEK bearing material
                                                                                                                                Real time oil level monitoring sensor
  Efficiency                                                                                                                    Automatic oil balancing between dual compressors
  EER                       Rated                                    4.54                                                       Over compression protection
  COP                       Rated                                    4.95                                                       Anti-corrosion Ocean Black Fin
  SEER                      Rated                                    8.81                                 Heat exchanger
                                                                                                                                Variable heat path control
  SCOP                      Rated                                    4.54                                 Outdoor fan           Biomimetic patterns on blades to reduce noise level
Design Data                                                                                                                     Dual sensing (temperature and humidity)
                                                       mm
                                                   (1240×1690×760)×1                                                            Advanced smart load control
Dimension (WxHxD)                                                                                                               Cooling comfort function during cooling mode
                                                    (930×1690×760)×1
Net weight                                 Kg          300x1; 215×1                                       System control        Defrost control for continuous heating
Number of maximum connectable indoor units                 49(60)                                         and monitoring        Night quiet operation mode
                  Liquid              mm(inch)           19.05(3/4)                                                             Automatic refrigerant charging
Piping for Heat                                                                                                                 Active refrigerant monitoring & control
                  Low Pressure Gas    mm(inch)           34.9(1-3/8)
Recovery                                                                                                                        Automatic fault diagnosis
                  High Pressure Gas   mm(inch)          28.58(1-1/8)
Piping for Heat Liquid                mm(inch)           19.05(3/4)                                       BMS connectivity      LonWorks, BACnet and Modbus
Pump              Gas                 mm(inch)           34.9(1-3/8)                                      Monitoring cycle      LGMV/Mobile LGMV (Android smartphone)
Sound Pressure Cooling                  dB(A)               63.1                                                                Multi V VRF indoor unit range
Level             Heating               dB(A)               64.1                                          Compatible            AHU Communication kit
Sound Power Cooling                     dB(A)               93.0                                          indoor units          ERV DX
Level             Heating               dB(A)               96.0                                                                Hydro kit
                  Name                                     R410A
                  Precharged Quantity      Kg               25.5                                          Operation Limits
Refrigerant       GWP                                      2087.5
                  T-CO2 eq.                                 53.2
                  Control                  Electronic Expansion Valve
Minimum circuit current                   (A)               68.2
Total over current                        (A)                75
Maximum fuse current                      (A)                80
                  Cooling                 (A)           30.20-27.65
Running current
                  Heating                 (A)           33.50-30.67
Acceptable voltage range                  (V)             342-456
Communication cable (VCTF-SB)         No.×mm2            2Cx1.0~1.5
NOTES:
1. This product contains Fluorinated Greenhouse Gases (R410A).
2. Wiring cable size must comply with the applicable local national codes.
3. For refrigerant pipe size, refer to the LATS drawing.
4. Nominal performances are carried out with concealed ducted indoor units at
   following rated conditions in compliance with EN14511:
    Cooling: Indoor temp. 27°C DB / 19°C WB; Outdoor temp. 35°C DB / 24°C WB.                            Typical Dual Frame Configuration
    Heating: Indoor temp. 20°C DB / 15°C WB; Outdoor temp. 7°C DB / 6°C WB.
    Interconnecting piping length of 7.5m. Elevation difference (ODU~IDU) of zero.
5. Sound pressure level is measured at rated conditions in the anechoic rooms in
   compliance with ISO 3745 standard.
6. Sound power level is measured at rated conditions in the reverberation rooms in
   compliance with ISO 3741 standard.
7. Sound data of combination model is calculated from sound data of individual units.
8. The maximum connectable indoor units in brackets are for combination ratio of
   160~200%. The recommended maximum ratio is 130%.
9. Large capacity unit is usually configured as the master unit and the small ones as
                                                                                                                See installation manual for minimum spacing between frames
   the slave units.
For continual product development, LG reserves the right to change specifications without notice.
LG Electronics Air Conditioning and Energy Solutions.
Multi V 5 Sep-2019
                                                                                                                                                                                        1
LGE MULTI V 5 Specification
For continual product development, LG reserves the right to change specifications without notice.
LG Electronics Air Conditioning and Energy Solutions.
Multi V 5 Sep-2019                                                                                  2
LGE MULTI V 5 Specification
For continual product development, LG reserves the right to change specifications without notice.
LG Electronics Air Conditioning and Energy Solutions.
Multi V 5 Sep-2019                                                                                  3