98015 Series Solenoid Poppet Valve
98015 Series Solenoid Poppet Valve
Technical features
Medium: Port size: Ambient/Media temperature: Materials:
Neutral or aggressive, gaseous G1/4, G1/4 NAMUR, -40 ... +60°C (-40 ... +140°F) Body: Aluminium anodized
fluids which do not damage the 1/4 NPT, 1/4 NPT NAMUR, -25 ... +60°C (-13 ... +140°F) (suitable for high humidity,
product or affect the function (e.g. G1/2, G1/2 NAMUR, (SIL version) sulphuric, sodium chloride or
compressed air, nitrogen). Based 1/2 NPT, 1/2 NPT NAMUR Depending on solenoid system. ammonia environments),
on ISO 8573-1-2010 classification NAMUR Interface with integrated Air supply must be dry enough to brass 2.0401 (Ms 58),
1-2-3. recirculation from the exhaust air to avoid ice formation at temperatures stainless steel 1.4404 (316 L)
Operation: the acutator sping chamber below +2°C (35°F). Seals: NBR
Direct solenoid operated Flow direction: For outdoor installations all
poppet valve Optional connections must be protected Flow conversion:
Operating pressure: Mounting position: against the penetration of moisture Cv US Gallon/min (water) =
0 ... 10 bar (0 ... 145 psi) Any, but preferably with solenoid and a solenoid with IP66 protection l/min (air) x 0,001
Orifice: vertical must be used! Kv m³/h (water) =
8 mm l/min (air) x 0,000906
Technical data
Seals: NBR -40 ... +60°C (-40 ... +140°F) / IEC 61508: -25 ... +60°C (-13 ... +140°F). Housing: Aluminium anodized
Symbol Port size Flow (l/min) *1) Flow (l/min) *2) Operating pressure Drawing Model *3)
1, 3 2 (3) 1»2 2»3 1»2 2»3 (bar) (psi) No.
2 3 G1/4, G1/2 G1/4 NAMUR 1100 1300 2900 3400 0 ... 10 0 ... 145 1 9801505
12 10 1/4 NPT, 1/2 NPT 1/4 NPT NAMUR 1100 1300 2900 3400 0 ... 10 0 ... 145 1 9801515
1 3
1 3 1 3
12 2 10 12 2 10
Housing: Brass
1 3 1 3
Symbol Port size Flow (l/min) *1) Flow (l/min) *2) Operating pressure Drawing Model *3)
12 2 10 12 2 10 1»2 2»3 1»2 2»3 (bar) (psi) No.
12 2 10 12 2 10 G1/2 1200 1300 3100 3400 0 ... 10 0 ... 145 2 9801655
1 3 1 3 1/2 NPT 1200 1300 3100 3400 0 ... 10 0 ... 145 2 9801665
1 3 1 3
12 *1) Inlet12
2 10 pressure2 610
bar (87 psi), outlet pressure 5 bar (72 psi)
*2) Inlet pressure 10 bar (145 psi), outlet pressure 0 bar (0 psi)
*3) When ordering please indicate solenoid, voltage and current Modele (frequency).
1 3 1 3
12 2 10 12 2 10
1 3 1 3
Our policy is one of continued research and development. We therefore reserve the right to amend, 11/18
without notice, the specifications given in this document. (2004 - 5146e) © 2014 Norgren GmbH en 5.4.369.01
98015 series, 3/2
Direct solenoid actuated poppet valve
Our policy is one of continued research and development. We therefore reserve the right to amend,
en 5.4.369.02 without notice, the specifications given in this document. (2004 - 5146e) © 2014 Norgren GmbH 11/18
98015 series, 3/2
Direct solenoid actuated poppet valve
Solenoids
Power Rated current Protection Ex-Protection Temperature Electrical Drawing Circuit Model
consumption class (ATEX-Category) Ambient/ connection diagram
24 V d.c. 230 V a.c. 24 V d.c. 230 V a.c. IP/NEMA Media
(W) (VA) (mA) (mA) (°C) No. No.
16,9 — 703 — IP65 (with — -25 ... +60 Connector 3 10 0800
connector) Media: +80 DIN EN
175301-803,
Form A *4)
— 17,3 — 75 IP65 (with — -25 ... +50 Connector 4 13 3803
connector) Media:+80 DIN EN
175301-803,
Form A *4)
8,9 — 369 — IP65 — -25...+90 Terminals, cable 7 11 4120
Media:+110 gland
Pg 13,5
— 10,0 — 43 IP65 — -25...+90 Terminals, cable 7 14 4121
Media:+110 gland
Pg 13,5
8,9 — 369 — IP67 — -25...+90 3 m cable, 7 11 4122
Media:+110 encapsulated in
EP resin
— 10,0 — 43 IP67 — -25...+90 3 m cable, 7 14 4123
Media:+110 encapsulated in
EP resin
8,9 — 369 — IP66 (with II 2G Ex eb mb IIC T4/T5 Gb T4: -40 ... +65 M20 x 1,5 *4) 5 12 4270
cable gland) T5: -40 ... +55
II 2D Ex tb IIIC T130°C Db -40 ... +65
— 10,0 — 43 IP66 (with II 2G Ex eb mb IIC T4/T5 Gb T4: -40 ... +65 M20 x 1,5 *4) 5 15 4271
cable gland) T5: -40 ... +55
II 2D Ex tb IIIC T130°C Db -40 ... +65
8,9 — 369 — IP66 (with II 2G Ex db mb IIC T4/T6 Gb T4: -40 ... +70 1/2 NPT *4) 6 16 4670
cable gland) II 2G Ex eb mb IIC T4/T6 Gb T6: -40 ... +40
II 2D Ex tb IIIC T130°C Db -40 ... +70
— 10,0 — 43 IP66 (with II 2G Ex db mb IIC T4/T6 Gb T4: -40 ... +70 1/2 NPT *4) 6 17 4671
cable gland) II 2G Ex eb mb IIC T4/T6 Gb T6: -40 ... +40
II 2D Ex tb IIIC T130°C Db -40 ... +70
8,9 — 369 — IP66 (with II 2G Ex db mb IIC T4/T6 Gb T4: -40 ... +70 M20 x 1,5 *4) 6 16 4672
cable gland) II 2G Ex eb mb IIC T4/T6 Gb T6: -40 ... +40
II 2D Ex tb IIIC T130°C Db -40 ... +70
— 10,0 — 43 IP66 (with II 2G Ex db mb IIC T4/T6 Gb T4: -40 ... +70 M20 x 1,5 *4) 6 17 4673
cable gland) II 2G Ex eb mb IIC T4/T6 Gb T6: -40 ... +40
II 2D Ex tb IIIC T130°C Db -40 ... +70
8,9 — 369 — IP66 (with II 2G Ex db mb IIC T4 Gb T4: -40 ... +50 M20 x 1,5 *4) 8 12 4872
cable gland) II 2G Ex eb mb IIC T4 Gb
II 2D Ex tb IIIC T110°C Db -40 ... +50
— 10,0 — 43 IP66 (with II 2G Ex db mb IIC T4 Gb T4: -40 ... +50 M20 x 1,5 *4) 8 15 4873
cable gland) II 2G Ex eb mb IIC T4 Gb
II 2D Ex tb IIIC T110°C Db -40 ... +50
Standard voltages (±10%) 24 V d.c., 230 V a.c., other voltages on request. Design according to VDE 0580, EN 50014/50028. 100% duty cycle.
*4) Connector/cable gland is not scope of delivery, see table »Accessories«
Attention: The protection class for coil series 46xx and 48xx is determined by the choice of cable gland.
Example: if an ATEX-certified cable gland is used that has Ex d type of protection, the solenoid will have the protection class Ex db mb; if a cable gland with
Ex e type of proteciton is used, the solenoid will have protection class Ex eb mb.
Approvals
Model Approvals Datasheet
ATEX IECEx
42xx KEMA 98 ATEX 4452 X IECEx KEM 09.0068X 7.1.580
46xx PTB 02 ATEX 2085 X IECEx PTB 11.0094X 7.1.585
48xx EPS 18 ATEX 1 019 IECEx EPS 18.0013 7.1.590
Our policy is one of continued research and development. We therefore reserve the right to amend,
11/18 without notice, the specifications given in this document. (2004 - 5146e) © 2014 Norgren GmbH en 5.4.369.03
98015 series, 3/2
Direct solenoid actuated poppet valve
Solenoids
Power Rated current Protection Ex-Protection Temperature Electrical Drawing Circuit Model
consumption class (ATEX-Category) Ambient/ connection diagram
24 V d.c. 120 V a.c. 24 V d.c. 120 V a.c. IP/NEMA Media
(W) (VA) (mA) (mA) (°C) No. No.
8,9 — 369 — 4x Cl. I, Div. 1, Gr. A - D -20 ... +60 Flying leads 9 10 3824
Cl. II/III, Div. 1, Gr. E - G length 460 mm
T3C (160°C)
— 9,5 — 84 4x Cl. I, Div. 1, Gr. A - D -20 ... +60 Flying leads 9 13 3825
Cl. II/III, Div. 1, Gr. E - G length 460 mm
T3C (160°C)
13,6 — 567 — 4x Cl. I, Div. 1, Gr. A - D -20 ... +60 Flying leads 9 10 3826
Cl. II/III, Div. 1, Gr. E - G length 460 mm
T3C (160°C)
— 15,7 — 130 4x Cl. I, Div. 1, Gr. A - D -20 ... +60 Flying leads 9 13 3827
Cl. II/III, Div. 1, Gr. E - G length 460 mm
T3C (160°C)
Standard voltages (±10%) 24 V d.c., 120 V a.c., other voltages on request. Design according to VDE 0580, EN 50014/50028. 100% duty cycle.
Approvals
Model Approvals Datasheet
FM
382x CSA-LR 57643-6 7.1.575
Example: 0000000427002400-04
(Coil: 4270; Voltage: 24V DC; Approval: TR-CU 012)
Accessories
Accessories
Cable gland
Connector
Protection class Ex e, Ex d
DIN EN 175301-803
Plastic, nickel plated brass/
stainless steel
Page 10
Ambient
For Cable Ø Protection temperatur
solenoid Thread (mm) Material class (ATEX) limitation *1) Model
42xx M20 x 1,5 7,0 … 12,0 Plastic II 2G Ex e / II 2D Ex t See table 0589735
42xx M20 x 1,5 10,0 … 14,0 Plastic II 2G Ex e / II 2D Ex t See table 0589736 0570275, form A
42xx M20 x 1,5 6,0 … 12,0 Plastic II 2G Ex e / II 2D Ex t See table 0589737 More connectors see datasheet 7.1.507
42xx M20 x 1,5 5,0 … 10,0 Plastic II 2G Ex e / II 2D Ex t See table 0589739
46xx M20 x 1,5 5,0 … 8,0 Nickel plated brass II 2G Ex e / II 2D Ex t - 0588819
46xx M20 x 1,5 10,0 … 14,0 Nickel plated brass II 2G Ex d / II 2D Ex t - 0588851
46xx 1/2 NPT 7,5 … 11,9 Nickel plated brass II 2G Ex d / II 2D Ex t - 0588925
46xx, 48xx M20 x 1,5 9,0 … 13,0 Stainless steel 1.4571 II 2G Ex e / II 2D Ex t - 0589385
46xx, 48xx M20 x 1,5 7,0 … 12,0 Stainless steel 1.4404 II 2G Ex d / II 2D Ex t - 0589395
46xx, 48xx M20 x 1,5 10,0 … 14,0 Stainless steel 1.4404 II 2G Ex d / II 2D Ex t - 0589387
*1) The limitation of the temperature range to the mentioned range is due to the self-heating of the solenoid.
For Ambient temperatur limitation solenoid 42xx
solenoid 0589735 & 0589736 *2) 0589737 0589739 *2)
T4 & Dust Ex: -35 ... +65°C T4 & Dust Ex: -40 ... +62°C T4 & Dust Ex: -40 ... 65°C
422x/427x
T5: -35 ... +55°C T5: -40 ... +55°C T5: -40 ... +55°C
*2) Tested for the lower level of mechanical risk (4 joule), an additional protection against impacts might be needed.
Our policy is one of continued research and development. We therefore reserve the right to amend,
en 5.4.369.04 without notice, the specifications given in this document. (2004 - 5146e) © 2014 Norgren GmbH 11/18
98015 series, 3/2
Direct solenoid actuated poppet valve
Accessories
Silencer *6) Silencer Silencer Exhaust guard *7) Add-on manual override *8)
(Stainless steel) *6) (Brass) *6) without detent with detent
M/S2 (G1/4) 0014613 (G1/4) T40C2800 (G1/4) 0613422 (G1/4, 1/4 NPT) 0600205 0601765
C/S2 (1/4 NPT) 0613678 (1/4 NPT) MS002A (1/4 NPT) 0613423 (G1/2, 1/2 NPT)
M/S4 (G1/2) 0014813 (G 1/2) T40C4800 (G 1/2)
C/S4 (1/2 NPT) 0613679 (1/2 NPT) MS004A (1/2 NPT)
Manual override
Using the manual override with detent cancels the SIL-approva!. The manual override is meant to be used for system testing.
NAMUR accessories (G1/4 only)
Throttle control plate *9) Flange plate Yoke Mounting plate Quick exhaust module *10)
4040239 0612790 (NAMUR single connection 0540593 (Pipe mounting use in 0613453 (90°) 4050218
plate) combination with 0612790 )
0612791 (NAMUR-rip use in
combination with 0612790)
*9) The throttle control plate 4040239 has a minimum flow rate for safety reason.
*10) Technical details see catalogue page en 5.4.820.
Drawings Dimensions in mm
Projection/First angle
Valves
Weight: Aluminium eloxiert: 0,7 kg
1
1
(6.5)
3 3
3
~ 135
3 3
M5
24
72
2
12
G1/4
47
1 2
29,6
1
13
17.5 32 19 35 7,5
4,5
50 60
Our policy is one of continued research and development. We therefore reserve the right to amend,
11/18 without notice, the specifications given in this document. (2004 - 5146e) © 2014 Norgren GmbH en 5.4.369.05
98015 series, 3/2
Direct solenoid actuated poppet valve
Drawings Dimensions in mm
Projection/First angle
Valves
Weight: Stainless steel: 0,9 kg, Brass: 0,9 kg
2
43 1
5,5
~ 126
3
3
2
15
72
2
48
1
29,5
1
31,5
16
30 19 37
4,5
60
9,5
19 19
8,5
ø12 36
Solenoids
Weight: 0,27 kg Weight: 0,32 kg
3 4
86,5 96,5
53,5 63,5
1
49 1 59
17
22
40,5
40,5
43
48
28
43
43
28
34
27
27
Our policy is one of continued research and development. We therefore reserve the right to amend,
en 5.4.369.06 without notice, the specifications given in this document. (2004 - 5146e) © 2014 Norgren GmbH 11/18
98015 series, 3/2
Direct solenoid actuated poppet valve
2 70,5 2
107
40,5
41,5
64,5
53
27
20
3 3
10
59
14,5
42
54,5
56
29 43
122
Weight: 1,2 kg
7 Weight: 0,5 kg / 0,7 kg 8
2 68 2
41
42
18,5
45
43
53
15 + 1
3
61
30,5
56
110
28 35
113
2 Ø 16 (with spacer tube)
3 M20 x 1,5 or 1/2 NPT
4 Flying leads AWG 18 (460 mm long)
Weight: 0,5 kg
9 5 With cable gland, Pg 13,5
2
1/2 NPT
40,5
84
63 2
33,5
43
26 4
Our policy is one of continued research and development. We therefore reserve the right to amend,
11/18 without notice, the specifications given in this document. (2004 - 5146e) © 2014 Norgren GmbH en 5.4.369.07
98015 series, 3/2
Direct solenoid actuated poppet valve
Circuit diagrams
10 11 12 13
14 15 16 17
T T
Accessories Dimensions in mm
Projection/First angle
Silencer Exhaust guard
Model: M/S2, M/S4, C/S2 & C/S4 Model: 0613422 & 0613423
C C
G G
øD
øD
B
Our policy is one of continued research and development. We therefore reserve the right to amend,
en 5.4.369.08 without notice, the specifications given in this document. (2004 - 5146e) © 2014 Norgren GmbH 11/18
98015 series, 3/2
Direct solenoid actuated poppet valve
B
G
C
32
NAMUR quick exhaust module for a better
M5 2
kv-value by exhaust see data sheet 5.4.820
3 (4)
1
1 Coding stud threaded
2 8 mm deep
19 25,5 M5 (4x) 32
16 9
3 (4)
19
25,5
3
12
G1/4
35
19
12
41
12
16
24
60
11,5
30
16
2 1 2
12 12
34,5
104
20
ø 9,5 19
7
ø 5,5 G1/4 M5
24 20
12
29
19
2 3 (4)
12
10
ø9 27 21 1
ø 14,5
16
32
55
43,5
3 2
12
55
Our policy is one of continued research and development. We therefore reserve the right to amend,
11/18 without notice, the specifications given in this document. (2004 - 5146e) © 2014 Norgren GmbH en 5.4.369.09
98015 series, 3/2
Direct solenoid actuated poppet valve
45
32
9,5
12
M5
5,5
50
41
12
41
76 4
5,5
5 20
8
25
12
12
5
11
M5
7,5
60°
1 1
15,5
15,5
2 2
24 ~ 33 5
G1/8 8 30
G3/8
21
1 2
3
43
42
G1/4
2
80
ø 5.5
1
24
M5
3
12
ø 15.5
ø 19.5
M5
3
4 M5 27.5 7.5 3
32
1.3 55
1 Flanged surface NAMUR or externally mounted valve
2 Flanged surface NAMUR actuator
3 Push-in threaded piece after plate mounting
(to secure correct position)
4 8 mm deep
5 Flow regulator assembly
Warning
These products are intended for use in industrial compressed air and event of such failure.
fluid systems only. Do not use these products where pressures and System designers must provide a warning to end users in the system
temperatures can exceed those listed under »Technical features/data«. instructional manual if protection against a failure mode cannot be
Before using these products with fluids other than those specified, adequately provided.
for non-industrial applications, life-support systems, or other System designers and end users are cautioned to review specific
applications not within published specifications, consult warnings found in instruction sheets packed and shipped with
IMI Precision Engineering, Norgren GmbH. these products.
Through misuse, age, or malfunction, components used in fluid
power systems can fail in various modes. Functional safety (SIL):
The system designer is warned to consider the failure modes of all Suitable for certain applications can only be evaluated through
component parts used in fluid power systems and to provide adequate examination of each safety-related overall system with regard to the
safeguards to prevent personal injury or damage to equipment in the requirements of IEC 61508/61511.
Diese
en Produkte sind ausschließlich inOur
5.4.369.10
policy is one
Druckluft- undof continued researchzu
Fluidsystemen and development. We therefore
sichtigen reserve the right to
und ausreichende amend,
Sicherheitsvorkehrungen zu treffen, um
without notice, the specifications given in this document. (2004 - 5146e) © 2014 Norgren GmbH 11/18
verwenden. Sie sind dort einzusetzen, wo die unter »Technische Merk- Verletzungen von Personen sowie Beschädigungen der Geräte im
male/-Daten« aufgeführten Werte nicht überschritten werden. Falle einer solchen Störung zu verhindern.