241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
POWER SUPPLY
▪ AC 100-240V Wide-range Input
▪ Width only 32mm
▪ Efficiency up to 94.3%
▪ Excellent Partial Load Efficiency
▪ 20% Output Power Reserves (PowerBoost)
▪ Easy Fuse Breaking – 3 times nominal current for 12ms
▪ Safe HiccupPLUS Overload Mode
▪ Active Power Factor Correction (PFC)
▪ Minimal Inrush Current Surge
▪ Full Power Between -25°C and +60°C
▪ DC OK Relay Contact
▪ 3 Year Warranty
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 1/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
INDEX
Page Page
1. Intended Use .....................................................................3 20. Regulatory Product Compliance ......................................20
2. Installation Instructions .....................................................3 21. Physical Dimensions and Weight .....................................21
3. AC-Input.............................................................................5 22. Accessories ......................................................................22
4. DC-Input ............................................................................6 22.1. ZM10.WALL - Wall/Panel Mount Bracket ............. 22
5. Input Inrush Current ..........................................................7 22.2. YR2.DIODE - Redundancy Module ........................ 23
6. Output ...............................................................................8 22.3. YR20.242 - Redundancy Module .......................... 23
7. Hold-up Time ...................................................................10 22.4. YR20.246 - Redundancy Module with Automated
8. DC OK Relay Contact ........................................................10 Load Sharing.......................................................... 23
9. Efficiency and Power Losses ............................................11 22.5. UF20.241 Buffer Module ...................................... 24
10. Functional Diagram..........................................................12 23. Application Notes ............................................................25
11. Front Side and User Elements..........................................12 23.1. Peak Current Capability ........................................ 25
12. Connection Terminals ......................................................13 23.2. Charging of Batteries ............................................ 26
13. Lifetime Expectancy .........................................................14 23.3. Series Operation ................................................... 26
14. MTBF ...............................................................................14 23.4. Parallel Use to Increase Output Power................. 26
15. EMC .................................................................................15 23.5. Parallel Use for Redundancy ................................ 27
16. Environment ....................................................................16 23.6. Operation on Two Phases..................................... 29
17. Safety and Protection Features .......................................17 23.7. Use in a Tightly Sealed Enclosure ......................... 29
18. Dielectric Strength ...........................................................18 23.8. Mounting Orientations ......................................... 30
19. Approved, Fulfilled or Tested Standards..........................19
The information given in this document is correct to the best of our knowledge and experience at the time of publication. If not expressly
agreed otherwise, this information does not represent a warranty in the legal sense of the word. As the state of our knowledge and
experience is constantly changing, the information in this data sheet is subject to revision. We therefore kindly ask you to always use the
latest issue of this document (available under www.pulspower.com).
No part of this document may be reproduced or utilized in any form without our prior permission in writing.
Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse.
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 2/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
1. INTENDED USE
This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control, process control,
monitoring, measurement, Audio/Video, information or communication equipment or the like.
Do not use this device in equipment, where malfunctioning may cause severe personal injury or threaten human life without additional
appropriate safety devices, that are suited for the end-application.
If this device is used in a manner outside of its specification, the protection provided by the device may be impaired.
2. INSTALLATION INSTRUCTIONS
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 3/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side. Increase the 5mm to
15mm in case the adjacent device is a heat source. When the device is permanently loaded with less than 50%, the 5mm can be reduced
to zero.
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without additional protection device. If an
external fuse is utilized, do not use circuit breakers smaller than 6A B- or C-Characteristic to avoid a nuisance tripping of the circuit
breaker.
The maximum surrounding air temperature is +70°C. The operational temperature is the same as the ambient or surrounding air
temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
(Except CP5.242)
Installation Instructions for Hazardous Location Areas
The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II Category 3 (Zone 2) environments.
Classification: ATEX: EPS 19 ATEX 1 201 X, II 3G Ex ec nC IIC T4 Gc / IECEx EPS 19.0078X
WARNING EXPLOSION HAZARDS!
Installation in standard mounting orientation with the input terminals on the bottom of the unit. For non-standard mounting
orientations a reduction of output current is required.
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or the area is known to be non-
hazardous.
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the requirements of the
EN 60079-0.
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 4/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
3. AC-INPUT
The device is suitable to be supplied from TN, TT or IT mains networks with AC voltage. For suitable DC supply voltages see chapter 4.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Rated Input
POUT input range max.
500ms Voltage
Shut -dow n
Turn-on
Output - 5%
Overshoot
Voltage
VIN
Start-up Rise
delay Time
85V 264V 300Vac
Fig. 3-3 Input current vs. output current at 24V output Fig. 3-4 Power factor vs. output current at 24V output
voltage voltage
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 5/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
4. DC-INPUT
The device is suitable to be supplied from a DC input voltage. Use a battery or a similar DC source. A supply from the intermediate DC-
bus of a frequency converter is not recommended and can cause a malfunction or damage the unit.
Connect +pole to L, –pole to N and the PE terminal to an earth wire or to the machine ground.
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 6/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
Fig. 5-1 Typical turn-on behaviour at nominal load, Fig. 5-2 Typical turn-on behaviour at nominal load,
120Vac input and 25°C ambient 230Vac input and 25°C ambient
Input Input
voltage voltage
200V/DIV 200V/DIV
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 7/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
6. OUTPUT
The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage.
The output is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large capacitors, such as EDLCs
(electric double layer capacitors or “UltraCaps”) with a capacitance > 0.3F are connected to the output, the unit might charge the
capacitor in an intermittent mode.
The output is electronically protected against overload, no-load and short-circuits. In case of a protection event, audible noise may
occur.
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 8/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
Fig. 6-1 Output voltage vs. output current, typ. Fig. 6-2 Dynamic output current capability, typ.
Output
Current
Normal Normal
operation Short -circuit operation
9A
t
0
1s 9s 1s 9s 1s 9s
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 9/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
7. HOLD-UP TIME
The hold-up time is the time during which a power supply’s output voltage remains within specification following the loss of input
power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several seconds. The green DC OK LED is
also on during this time.
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
Hold-up Time
90ms a) 24V 2.5A typ. c) 24V 5A typ. Zero Transition
b) 24V 2.5A min. d) 24V 5A min.
Input
75 a Voltage
60 b
45
30
c - 5%
d
Output
Voltage
15
Input Voltage Hold-up Time
0
90 120 155 190 230Vac
8. DC OK RELAY CONTACT
This feature monitors the output voltage on the output terminals of a running power supply.
Contact closes As soon as the output voltage reaches typ. 90% of the adjusted output voltage level.
Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored.
Switching hysteresis Typically 0.7V
Contact ratings Maximal 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load
Minimal permissible load: 1mA at 5Vdc
Isolation voltage See dielectric strength table in chapter 18.
VOUT = VADJ
< >
1ms 1...4ms 100ms
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 10/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
Fig. 9-1 Efficiency vs. output current at 24V, typ. Fig. 9-2 Losses vs. output current at 24V, typ.
Efficiency Power Losses
95% 12W
(c) (a)
(a) 100Vac
94 10 (b) 120Vac (b)
(b)
93 (c) 230Vac
(a) (c)
92 8
91 (a) 100Vac
6
90 (b) 120Vac
4
(c) 230Vac
89
88 2
Output Current Output Current
87 0
1 2 3 4 5 6A 0 1 2 3 4 5 6A
Fig. 9-3 Efficiency vs. input voltage at 24V, 5A, typ. Fig. 9-4 Losses vs. input voltage at 24V, 5A, typ.
Efficiency Power Losses
95% 11W
94 10
93 9
92 8
91 7
90 6
Input Voltage Input Voltage
89 5
100 120 180 230 264Vac 100 120 180 230 264Vac
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 11/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
L +
Input Fuse
Input Filter PFC Power Output +
N Input Rectifier Converter Converter Filter
Inrush Current Limiter -
-
Output
Voltage VOUT
Regulator
B Output Terminals
Two identical + poles and two
identical - poles
+ Positive output
– Negative output
(return)
D DC OK LED (green)
On, when the output voltage is
>90% of the adjusted output
voltage
E DC OK Relay Contact
The DC OK relay contact is
synchronized with the DC OK
LED. See chapter 8 for details.
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 12/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
Daisy chaining:
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current through one
terminal pin does not exceed 25A or 15A for the CP5.241-S2. If the current is higher, use a separate distribution terminal block as shown
in Fig. 12-2.
Fig. 12-1 Daisy chaining of outputs Fig. 12-2 Using distribution terminals
Distribution
Power Power Terminals
Supply Supply Power Power
Supply Supply
+ + - - + + - - Load
+ + - - + + - - Load
Output Output + -
Output Output + -
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 13/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
14. MTBF
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it cannot be determined if the failed unit
has been running for 50 000h or only for 100h.
For these types of units the MTTF (Mean Time To Failure) value is the same value as the MTBF value.
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 14/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
15. EMC
The EMC behavior of the device is designed for applications in industrial environment as well as in residential, commercial and light
industry environments.
The device is investigated according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4.
EMC Immunity
Electrostatic discharge EN 61000-4-2 Contact discharge 8kV Criterion A
Air discharge 15kV Criterion A
Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines 4kV Criterion A
Output lines 2kV Criterion A
DC OK signal (coupling clamp) 2kV Criterion A
Surge voltage on input EN 61000-4-5 L→N 2kV Criterion A
L → PE, N → PE 4kV Criterion A
Surge voltage on output EN 61000-4-5 +→- 1kV Criterion A
+ / - → PE 2kV Criterion A
Surge voltage on DC OK EN 61000-4-5 DC OK signal → PE 1kV Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 20V Criterion A
Mains voltage dips EN 61000-4-11 0% of 100Vac 0Vac, 20ms Criterion A
40% of 100Vac 40Vac, 200ms Criterion C
70% of 100Vac 70Vac, 500ms Criterion A
0% of 200Vac 0Vac, 20ms Criterion A
40% of 200Vac 80Vac, 200ms, <4A Criterion A
40% of 200Vac 80Vac, 200ms, >4A Criterion C
70% of 200Vac 140Vac, 500ms Criterion A
Voltage interruptions EN 61000-4-11 0% of 200Vac (=0V) 5000ms Criterion C
Powerful transients VDE 0160 Over entire load range 750V, 0.3ms Criterion A
Performance criterions:
A: The device shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. The device may shut-down and restarts by itself. No damage or hazards for the device will occur.
EMC Emission
Conducted emission EN 55011, EN 55032, FCC Part 15, CISPR 11, CISPR 32 Class B
input lines
Conducted emission IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 Limits for local DC power networks
output lines fulfilled
Radiated emission EN 55011, EN 55032 Class B
Harmonic input current (PFC) EN 61000-3-2 Fulfilled for Class A equipment
Voltage fluctuations, flicker EN 61000-3-3 Fulfilled, tested with constant
current loads, non pulsing
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause undesired operation.
Switching Frequencies
PFC converter 30kHz to 140kHz Input voltage and output load dependent
Main converter 60kHz to 140kHz Output load dependent
Auxiliary converter 30kHz to 60kHz Output load dependent
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 15/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
16. ENVIRONMENT
Operational temperature -25°C to +70°C Operational temperature is the same as the ambient or
surrounding temperature and is defined as the air
temperature 2cm below the unit.
Storage temperature -40°C to +85°C For storage and transportation
Output derating 3W/K Between +60°C and +70°C
0.33A/1000m or 5K/1000m For altitudes >2000m, see Fig. 16-2
The derating is not hardware controlled. The user has to take this into consideration to stay below the
derated current limits in order not to overload the unit.
Humidity 5 to 95% r.h. According to IEC 60068-2-30
Atmospheric pressure 110-54kPa See Fig. 16-2 for details
Altitude Up to 5000m See Fig. 16-2 for details
Over-voltage category III According to IEC 60664-1 for altitudes up to 2000m
II According to IEC 60664-1, for altitudes above 2000m
Degree of pollution 2 According to IEC 62477-1, not conductive
Vibration sinusoidal 2-17.8Hz: ±1.6mm; According to IEC 60068-2-6
17.8-500Hz: 2g
2 hours / axis
Shock 30g 6ms, 20g 11ms According to IEC 60068-2-27
3 bumps per direction, 18 bumps in
total
Shock and vibration is tested in combination with DIN rails according to EN 60715 with a height of
15mm and a thickness of 1.3mm and standard orientation.
Audible noise Some audible noise may be emitted from the power supply during no load, overload or short circuit.
Fig. 16-1 Output current vs. ambient temp. Fig. 16-2 Output current vs. altitude
(Inom 5A; Iout with PowerBoost = 6A)
0
Altitude 0m 2000m 5000m
-25 0 45 60 70°C
AP*) 110kPa 80kPa 54kPa
Ambient Temperature *) Atmospheric pressure
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 16/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 17/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
settings
Earth, PE Output B*)
C + When testing input to DC OK ensure that the maximal voltage between DC OK and the output is not
exceeded (column D). We recommend connecting DC OK pins and the output pins together when
- performing the test.
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 18/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 19/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 20/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
All dimensions in mm
All dimensions in mm
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 21/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
22. ACCESSORIES
Fig. 22-1 Isometric view Fig. 22-2 Isometric view- Fig. 22-3 Isometric view
Fig. 22-5 Hole pattern for wall mounting Fig. 22-6 Wall/panel mounting,
Fig. 22-4 Wall/panel mounting, front view
side view
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 22/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 23/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
The UF20.241 buffer module is a supplementary device for DC 24V power supplies. It delivers power to bridge
typical mains failures or extends the hold-up time after the AC power is turned off.
When the power supply provides a sufficient voltage, the buffer module stores energy in the integrated
electrolytic capacitors. When the mains voltage is lost, the stored energy is released to the DC-bus in a
regulated process.
The buffer module can be added in parallel to the load circuit at any given point and does not require any
control wiring.
One buffer module can deliver 20A additional current and can be added in parallel to increase the output
ampacity or the hold-up time.
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 24/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
Fig. 23-1 10Apeak current for 50ms , typ. Fig. 23-2 25Apeak current for 5ms , typ.
(2x the nominal current) (5x the nominal current)
24V Output
Output Voltage
24V Voltage
25A 14V
16V
10A
Output
0A Current
1ms/DIV Output
10ms/DIV 0A Current
24V
10ms/DIV Please note: The DC OK relay triggers when the voltage dips more
than 10% for longer than 1ms.
Peak current voltage dips Typically from 24V to 16V At 10A for 50ms and resistive load
Typically from 24V to 16.5V At 25A for 2ms and resistive load
Typically from 24V to 14V At 25A for 5ms and resistive load
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 25/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
Unit A
23.3. SERIES OPERATION Input
+
Devices of the same type can be connected in series for higher output voltages. It is
possible to connect as many units in series as needed, providing the sum of the output -
Output
voltage does not exceed 150Vdc. Voltages with a potential above 60Vdc must be installed +
with a protection against touching. Unit B
Load
Input
Avoid return voltage (e.g. from a decelerating motor or battery) which is applied to the + -
output terminals.
-
Keep an installation clearance of 15mm (left / right) between two power supplies and Output
avoid installing the power supplies on top of each other. Do not use power supplies in
series in mounting orientations other than the standard mounting orientation.
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple devices.
Unit A
23.4. PARALLEL USE TO INCREASE OUTPUT POWER Input
+
Devises can be paralleled to increase the output power. The output voltage shall be
adjusted to the same value (±100mV) with the same load conditions on all devices, or the -
Output
devices can be left with the factory settings. +
Unit B
The ambient temperature is not allowed to exceed +40°C. Load
Input
If more than three devices are connected in parallel, a fuse or circuit breaker with a rating + -
of 10A is required on each output. Alternatively, a diode or redundancy module can also
-
be utilized. Output
Energize all devices at the same time. It also might be necessary to cycle the input power
(turn-off for at least five seconds), if the output was in overload or short circuits and the required output current is higher than the
current of one unit.
Keep an installation clearance of 15mm (left / right) between two devices and avoid installing devices on top of each other. Do not use
devices in parallel in mounting orientations other than the standard mounting orientation or in any other condition where a reduction of
the output current is required (e.g. altitude).
Pay attention that leakage current, EMI, inrush current will increase when using multiple devices.
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 26/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
N+1 Redundancy:
Redundant systems for a higher power demand are usually built in a N+1 method. E.g. four devices, each rated for 5A are paralleled to
build a 15A redundant system.
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple devices.
Keep an installation clearance of 15mm (left / right) between two devices and avoid installing the devices on top of each other.
Do not use devices in parallel in mounting orientations other than the standard mounting orientation or in any other condition, where a
reduction of the output current is required.
For N+1 redundancy the ambient temperature is not allowed to exceed +40°C.
Wiring examples:
Fig. 23-4 1+1 Redundant configuration for 5A load current with a dual redundancy Fig. 23-5 1+1 Redundant configuration with active load share for 5A load current
module with a dual redundancy module
Failure
Monitor
+ + - - + - + - + + - - + + - - + + - - - - + + Load
Output Output 1 2 Share
Output Input Input Output Input Input
24V,5A 24V,5A
24V,5A 1 2 24V,5A Warning
Load Share o
DC- o DC- o OK o
DC- o DC- o
OK OK OK o OK o o
o YR20.242 o Redudnadcy
Redundancy OK o
Power Module Power Power Power Failure
Supply Supply Supply Supply YR20.246 Monitor
Redundancy
Module
Input Output Input Input Input Output
L N PE - + L N PE L N PE L N PE - +
5A max.
Load 5A
opt ional
Load
I I
I I
opt ional
L L
N
N
PE
PE
Note: A YR2.DIODE can also be used instead of a YR20.242
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 27/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
Fig. 23-6 N+1 Redundant configuration for 15A load current with multiple power supplies and redundancy modules
Failure
Monitor
+ + - - + - + - + + - - + + - - + - + - + + - -
Output Input Input Output Output Input Input Output
24V,5A 1 2 24V,5A 24V,5A 1 2 24V,5A
I I I I
L
N
PE
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 28/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
L2 DC
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 29/30
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series 24V, 5A, 120W, SINGLE PHASE INPUT
0
INPUT +45 +60 +70°C
Ambient Temperature
OUTPUT 0
+30 +60 +70°C
Ambient Temperature
0
+25 +60 +70°C
Ambient Temperature
3.5A
INPUT
0
+25 +60 +70°C
Ambient Temperature
Supply
3.5A
Pow er
INPUT
0
+25 +60 +70°C
Ambient Temperature
Oct. 2023 / Rev. 1.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 30/30