Cp5e481 4
Cp5e481 4
481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
POWER SUPPLY
AC 100-240V Wide-range Input
Width only 32mm
Efficiency up to 93.5%
Excellent partial load efficiency
20% Output power reserves (PowerBoost)
Easy fuse breaking – 3 times nominal current for 12ms
Safe HiccupPLUS overload mode
Active power factor correction (PFC)
Minimal inrush current surge
Full power between -25°C and +60°C
DC-OK relay contact
3 Year warranty
Class I Div 2
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 1/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
INDEX
Page Page
1. Intended Use ........................................................... 3 19. Approved, Fulfilled or Tested Standards ............. 19
2. Installation Instructions .......................................... 3 20. Regulatory Product Compliance........................... 20
3. AC-Input .................................................................. 5 21. Physical Dimensions and Weight.......................... 21
4. DC-Input .................................................................. 6 22. Accessories ............................................................ 22
5. Input Inrush Current ............................................... 7 22.1. ZM10.WALL - Wall/Panel Mount Bracket ....22
6. Output ..................................................................... 8 22.2. YR2.DIODE - Redundancy Module ...............23
7. Hold-up Time......................................................... 10 22.3. UF20.481 Buffer Module ..............................23
8. DC-OK Relay Contact ............................................ 10 23. Application Notes ................................................. 24
9. Efficiency and Power Losses.................................. 11 23.1. Peak Current Capability ...............................24
10. Functional Diagram............................................... 12 23.2. Charging of Batteries ...................................25
11. Front Side and User Elements ............................... 12 23.3. Series Operation ...........................................25
12. Connection Terminals ........................................... 13 23.4. Parallel Use to Increase Output Power ........25
13. Lifetime Expectancy .............................................. 14 23.5. Parallel Use for Redundancy ........................26
14. MTBF ...................................................................... 14 23.6. Operation on Two Phases ............................27
15. EMC ....................................................................... 15 23.7. Use in a Tightly Sealed Enclosure ................27
16. Environment .......................................................... 16 23.8. Mounting Orientations ................................28
17. Safety and Protection Features ............................ 17
18. Dielectric Strength ................................................ 18
The information given in this document is correct to the best of our knowledge and experience at the time of
publication. If not expressly agreed otherwise, this information does not represent a warranty in the legal sense of the
word. As the state of our knowledge and experience is constantly changing, the information in this data sheet is
subject to revision. We therefore kindly ask you to always use the latest issue of this document (available under
www.pulspower.com).
No part of this document may be reproduced or utilized in any form without our prior permission in writing.
Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as
domestic refuse.
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 2/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
1. INTENDED USE
This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control,
process control, monitoring, measurement, Audio/Video, information or communication equipment or the like.
Do not use this device in equipment, where malfunctioning may cause severe personal injury or threaten human life
without additional appropriate safety devices, that are suited for the end-application.
If this device is used in a manner outside of its specification, the protection provided by the device may be impaired.
2. INSTALLATION INSTRUCTIONS
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 3/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side.
Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device is permanently loaded with
less than 50%, the 5mm can be reduced to zero.
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without additional
protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A B- or C-Characteristic to
avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C. The operational temperature is the same as the ambient or
surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
(only CP5.481)
Installation Instructions for Hazardous Location Areas
The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II Category 3 (Zone 2)
environments.
Classification: ATEX: EPS 19 ATEX 1 201 X, II 3G Ex ec nC IIC T4 Gc / IECEx EPS 19.0078X
WARNING EXPLOSION HAZARDS!
Installation in standard mounting orientation with the input terminals on the bottom of the unit. For non-standard
mounting orientations a reduction of output current is required.
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or the area is
known to be non-hazardous.
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the
requirements of the EN 60079-0.
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 4/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
3. AC-INPUT
The device is suitable to be supplied from TN, TT or IT mains networks with AC voltage. For suitable DC supply voltages
see chapter 4.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Rated Input
POUT input range max.
500ms Voltage
Shut-down
Turn-on
Output - 5%
Overshoot
Voltage
VIN
Start-up Rise
delay Time
85V 264V 300Vac
Fig. 3-3 Input current vs. output current at Fig. 3-4 Power factor vs. output current at
24V output voltage 24V output voltage
Power Factor, typ.
Input Current, typ.
1.5A (a) 1.0
(b)
1.25 0.95
a) 100Vac (a)
1.0 b) 120Vac (b)
c) 230Vac 0.9
0.75 (c)
0.5 0.85
(a) 100Vac,
(c) (b) 120Vac,
0.25 0.8
Output Current (c) 230Vac
0 Output Current
0.25 0.5 1.0 1.5 2.0 2.5 3A 0.75
0.5 1.0 1.5 2.0 2.5 3A
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 5/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
4. DC-INPUT
The device is suitable to be supplied from a DC input voltage. Use a battery or a similar DC source. A supply from the
intermediate DC-bus of a frequency converter is not recommended and can cause a malfunction or damage the unit.
Connect +pole to L, –pole to N and the PE terminal to an earth wire or to the machine ground.
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 6/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
Fig. 5-1 Typical turn-on behaviour at nominal Fig. 5-2 Typical turn-on behaviour at nominal
load, 120Vac input and 25°C ambient load, 230Vac input and 25°C ambient
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 7/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
6. OUTPUT
The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage.
The output is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large
capacitors, such as EDLCs (electric double layer capacitors or “UltraCaps”) with a capacitance > 0.1F are connected to
the output, the unit might charge the capacitor in an intermittent mode.
The output is electronically protected against overload, no-load and short-circuits. In case of a protection event,
audible noise may occur.
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 8/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
Fig. 6-1 Output voltage vs. output current, Fig. 6-2 Dynamic output current capability,
typ. typ.
Output
Current
Normal Short -circuit Normal
operation operation
5A
t
0
1s 9s 1s 9s 1s 9s
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 9/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
7. HOLD-UP TIME
The hold-up time is the time during which a power supply’s output voltage remains within specification following the
loss of input power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several
seconds. The green DC-OK LED is also on during this time.
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
Hold-up Time
90ms a) 48V 1.25A typ. c) 48V 2.5A typ. Zero Transition
b) 48V 1.25A min. d) 48V 2.5A min.
Input
75 a Voltage
60 b
45
30
c - 5%
d
Output
Voltage
15
Input Voltage Hold-up Time
0
90 120 155 190 230Vac
Contact closes As soon as the output voltage reaches typ. 90% of the adjusted output voltage level.
Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored.
Switching hysteresis Typically 2V
Contact ratings Maximal 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load
Minimal permissible load: 1mA at 5Vdc
Isolation voltage See dielectric strength table in chapter 18.
VOUT = VADJ
< >
1ms 1...4ms 100ms
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 10/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
Fig. 9-1 Efficiency vs. output current at 48V, Fig. 9-2 Losses vs. output current at 48V, typ.
typ.
Fig. 9-3 Efficiency vs. input voltage at 48V, Fig. 9-4 Losses vs. input voltage at 48V, 2.5A,
2.5A, typ. typ.
Efficiency Power Losses
94% 11W
93 10
92 9
91 8
90 7
89 6
Input Voltage Input Voltage
88 5
100 120 180 230 264Vac 100 120 180 230 264Vac
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 11/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
L +
Input Fuse
Input Filter Output +
N Input Rectifier
PFC
Converter
Power
Converter Filter
Inrush Current Limiter -
-
Output
Voltage VOUT
Regulator
CP5.481 CP5.481-S1-C1
A Input Terminals
N, L Line input
PE (Protective
Earth) input
B Output Terminals
Two identical + poles and two identical - poles
+ Positive output
– Negative output
(return)
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 12/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
Daisy chaining:
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block as
shown in Fig. 12-2.
Fig. 12-1 Daisy chaining of outputs Fig. 12-2 Using distribution terminals
Distribution
Power Power Terminals
Supply Supply Power Power
Supply Supply
+ + - - + + - - Load
+ + - - + + - - Load
Output Output + -
Output Output + -
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 13/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
14. MTBF
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h
means that statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not
be determined if the failed unit has been running for 50 000h or only for 100h.
For these types of units the MTTF (Mean Time To Failure) value is the same value as the MTBF value.
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 14/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
15. EMC
The EMC behavior of the device is designed for applications in industrial environment as well as in residential,
commercial and light industry environments.
The device is investigated according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4.
EMC Immunity
Electrostatic discharge EN 61000-4-2 Contact discharge 8kV Criterion A
Air discharge 15kV Criterion A
Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines 4kV Criterion A
Output lines 2kV Criterion A
DC-OK signal (coupling clamp) 2kV Criterion A
Surge voltage on input EN 61000-4-5 LN 2kV Criterion A
L PE, N PE 4kV Criterion A
Surge voltage on output EN 61000-4-5 +- 1kV Criterion A
+ / - PE 2kV Criterion A
Surge voltage on DC-OK EN 61000-4-5 DC-OK signal PE 1kV Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 20V Criterion A
Mains voltage dips EN 61000-4-11 0% of 100Vac 0Vac, 20ms Criterion A
40% of 100Vac 40Vac, 200ms Criterion C
70% of 100Vac 70Vac, 500ms Criterion A
0% of 200Vac 0Vac, 20ms Criterion A
40% of 200Vac 80Vac, 200ms, <2A Criterion A
40% of 200Vac 80Vac, 200ms, >2A Criterion C
70% of 200Vac 140Vac, 500ms Criterion A
Voltage interruptions EN 61000-4-11 0% of 200Vac (=0V) 5000ms Criterion C
Powerful transients VDE 0160 Over entire load range 750V, 0.3ms Criterion A
Performance criterions:
A: The device shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. The device may shut-down and restarts by itself. No damage or hazards for the device will occur.
EMC Emission
Conducted emission EN 55011, EN 55032, FCC Part 15, CISPR 11, CISPR 32 Class B
input lines
Conducted emission IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 Limits for local DC power
output lines networks fulfilled
Radiated emission EN 55011, EN 55032 Class B
Harmonic input current (PFC) EN 61000-3-2 Fulfilled for Class A equipment
Voltage fluctuations, flicker EN 61000-3-3 Fulfilled, tested with constant
current loads, no pulsing
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Switching Frequencies
PFC converter 30kHz to 140kHz Input voltage and output load dependent
Main converter 60kHz to 140kHz Output load dependent
Auxiliary converter 30kHz to 60kHz Output load dependent
DC-OK relay converter 18kHz to 25kHz Output voltage dependent
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 15/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
16. ENVIRONMENT
Operational temperature -25°C to +70°C Operational temperature is the same as the ambient
or surrounding temperature and is defined as the air
temperature 2cm below the unit.
Storage temperature -40°C to +85°C For storage and transportation
Output derating 3W/K Between +60°C and +70°C
0.167A/1000m or 5K/1000m For altitudes >2000m, see Fig. 16-2
The derating is not hardware controlled. The user has to take this into consideration to
stay below the derated current limits in order not to overload the unit.
Humidity 5 to 95% r.h. According to IEC 60068-2-30
Atmospheric pressure 110-54kPa See Fig. 16-2 for details
Altitude Up to 5000m See Fig. 16-2 for details
Over-voltage category III According to IEC 60664-1 for altitudes up to 2000m
II According to IEC 60664-1, for altitudes above 2000m
Degree of pollution 2 According to IEC 62368-1, not conductive
Vibration sinusoidal 2-17.8Hz: ±1.6mm; According to IEC 60068-2-6
17.8-500Hz: 2g
2 hours / axis
Shock 30g 6ms, 20g 11ms According to IEC 60068-2-27
3 bumps per direction, 18
bumps in total
Shock and vibration is tested in combination with DIN rails according to EN 60715 with a
height of 15mm and a thickness of 1.3mm and standard orientation.
Audible noise Some audible noise may be emitted from the power supply during no load, overload or
short circuit.
Fig. 16-1 Output current vs. ambient temp. Fig. 16-2 Output current vs. altitude
(Inom 2.5A; Iout with PowerBoost = 3A)
0
Altitude 0m 2000m 5000m
-25 0 45 60 70°C
AP*) 110kPa 80kPa 54kPa
Ambient Temperature *) Atmospheric pressure
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 16/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 17/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
current settings
Earth, PE Output B*)
C + When testing input to DC-OK ensure that the maximal voltage between DC-OK and
the output is not exceeded (column D). We recommend connecting DC-OK pins and
- the output pins together when performing the test.
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 18/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 19/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 20/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
All dimensions in mm
All dimensions in mm
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 21/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
22. ACCESSORIES
Fig. 22-1 Isometric view Fig. 22-2 Isometric view Fig. 22-3 Isometric view
Fig. 22-4 Wall/panel mounting, front Fig. 22-5 Hole pattern for wall Fig. 22-6 Wall/panel mounting,
view mounting side view
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 22/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
The UF20.481 buffer module is a supplementary device for DC 48V power supplies. It delivers
power to bridge typical mains failures or extends the hold-up time after the AC power is turned
off.
When the power supply provides a sufficient voltage, the buffer module stores energy in the
integrated electrolytic capacitors. When the mains voltage is lost, the stored energy is released to
the DC-bus in a regulated process.
The buffer module can be added in parallel to the load circuit at any given point and does not
require any control wiring.
One buffer module can deliver 20A additional current and can be added in parallel to increase
the output ampacity or the hold-up time.
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 23/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
Fig. 23-1 5A peak current for 50ms , typ. Fig. 23-2 12.5A peak current for 5ms , typ.
(2x the nominal current) (5x the nominal current)
Peak current voltage dips Typically from 48V to 32V At 5A for 50ms and resistive load
Typically from 48V to 41V At 12.5A for 2ms and resistive load
Typically from 48V to 34V At 12.5A for 5ms and resistive load
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 24/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
Devises can be paralleled to increase the output power. The output voltage
+
shall be adjusted to the same value (±100mV) with the same load conditions on -
Output
all devices, or the devices can be left with the factory settings. +
The ambient temperature is not allowed to exceed +40°C. Unit B
Load
Input
If more than three devices are connected in parallel, a fuse or circuit breaker + -
with a rating of 6A is required on each output. Alternatively, a diode or
redundancy module can also be utilized. -
Output
Energize all devices at the same time. It also might be necessary to cycle the
input power (turn-off for at least five seconds), if the output was in overload or short circuits and the required output
current is higher than the current of one unit.
Keep an installation clearance of 15mm (left / right) between two devices and avoid installing devices on top of each
other. Do not use devices in parallel in mounting orientations other than the standard mounting orientation or in any
other condition where a reduction of the output current is required (e.g. altitude).
Pay attention that leakage current, EMI, inrush current will increase when using multiple devices.
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 25/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
N+1 Redundancy:
Redundant systems for a higher power demand are usually built in a N+1 method. E.g. four devices, each rated for
2.5A are paralleled to build a 7.5A redundant system.
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple devices.
Keep an installation clearance of 15mm (left / right) between two devices and avoid installing the devices on top of
each other.
Do not use devices in parallel in mounting orientations other than the standard mounting orientation or in any other
condition, where a reduction of the output current is required.
For N+1 redundancy the ambient temperature is not allowed to exceed +40°C.
Wiring examples:
Fig. 23-4 Fig. 23-5
1+1 Redundant configuration for 2.5A load N+1 Redundant configuration for 7.5A load current with
current with a dual redundancy module multiple power supplies and redundancy modules
Failure
Failure Monitor
Monitor
+ + - - + - + - + + - - + + - - + - + - + + - -
+ + - - + - + - + + - - Output Input Input Output Output Input Input Output
Output Input Input Output 48V, 2.5A 1 2 48V, 2.5A 48V, 2.5A 1 2 48V, 2.5A
48V, 2.5A 1 2 48V, 2.5A
optional
optional
I I I I
I I
L
L
N
N
PE
PE
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 26/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 27/28
www.pulspower.com Phone +49 89 9278 0 Germany
CP5.481, CP5.481-S1-C1
CP-Series 48V, 2.5A, 120W, SINGLE PHASE INPUT
0
INPUT +45 +60 +70°C
Ambient Temperature
OUTPUT 0
+30 +60 +70°C
Ambient Temperature
0
+25 +60 +70°C
Ambient Temperature
1.5A
Power
INPUT
0
+25 +60 +70°C
Ambient Temperature
1.5A
Supply
Power
INPUT
0
+25 +60 +70°C
Ambient Temperature
Jun. 2023 / Rev. 1.5 DS-CP5.481-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 48V, 2.5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. 28/28
www.pulspower.com Phone +49 89 9278 0 Germany