Pressure
Compact differential pressure switch
Models DC, DCC
                                                                                                                                  WIKA data sheet PV 35.40
                                                                                                                     Process Compact Series
 Applications
■ Pressure monitoring and control of processes
■ Safety-critical applications in general process instrumen-
  tation, especially in the chemical and petrochemical indus-
  tries, oil and gas industries, power generation incl. nuclear
  power plants, water/wastewater industries, mining
■ For gaseous,liquid and aggressive media, also in
  aggressive ambience
■ Filter and level monitoring
 Special features
■ No power supply needed for switching of electrical loads
■ Robust switch enclosure from aluminium alloy or stainless
    steel 316L, IP66, NEMA 4X
■ Setting ranges from 0 ... 160 mbar to 0 ... 40 bar with high
    static and high one-sided pressure up to 250 bar
■ Ex ia version available
■ 1 set point, SPDT or DPDT, high switching power up to                                       Differential pressure switch, model DC
    AC 250 V, 15 A
Description
These high-quality pressure switches have been developed                                     All wetted materials are from stainless steel as a standard.
especially for safety-critical applications. The high quality of                             For applications with special requirements on the wetted
the products and manufacturing in accordance with ISO 9001                                   parts, a version with Monel is available.
ensure reliable monitoring of your plant. In production, the
switches are traced by quality assurance software at every                                   By using a diaphragm measuring system, the model DC
step and subsequently are 100 % tested.                                                      differential pressure switch is extremely robust and guaran-
                                                                                             tees optimal operating characteristics and the highest
In order to ensure as flexible operation as possible,                                        measuring performances, with repeatability lower than 1 %
the pressure switches are fitted with micro switches,                                        of span.
which enable the switching of an electrical load of up to
AC 250 V, 20 A directly.                                                                     The process connection with a centre distance of 54 mm
For lower switching power ratings, such as for PLC appli-                                    lower mount allows an easy and comfortable mounting of a
cations, argon gas-filled micro switches with gold-plated                                    standard valve manifold.
contacts can be selected.
 WIKA data sheet PV 35.40 ∙ 03/2021                                                                                                              Page 1 of 6
Data sheets showing similar products:
Compact differential pressure switch, flameproof enclosure Ex d; models DE, DEC; see data sheet PV 35.41
Standard version                                                             Ignition protection type (option)
                                                                             ■ Ex ia I Ma (mines), only available for model DC with stain-
Measuring system                                                                 less steel switch enclosure
Double diaphragm with transmission shaft, without sealing                    ■ Ex ia IIC T6/T4 1) Ga (gas)
elements                                                                     ■ Ex ia IIIC T85/T135 1) Da (dust)
                                                                             1) The temperature class is related to the ambient temperature range. See the type exami-
Switch enclosure                                                                nation certificate for further details.
■ Aluminium alloy, copper-free, epoxy resin coated
                                                                             Safety-related maximum values
■ Stainless steel 316L (only available for model DC)
                                                                             (only for optional Ex ia versions)
Tamper-proof                                                                  Maximum values
Laser-engraved product label from stainless steel                             Voltage Ui                              DC 30 V
                                                                              Current li                              100 mA
Ingress protection
IP66 per EN/lEC 60529, NEMA 4X                                                Power Pi                                0.75 W
                                                                              Internal capacitance Ci                 0 μF
Permissible temperature                                                       Internal inductance Li                  0 mH
Ambient     Tamb: -30 ... +85 °C
Medium      T M:  -30 ... +85 °C
Switch contact
Micro switches with fixed dead band
■ 1 x SPDT (single pole double throw)
■ 1 x DPDT (double pole double throw)
The DPDT function is realised with 2 simultaneously trigger-
ing SPDT micro switches within 2 % of the span.
 Contact version                                                            Electrical rating (resistive load)                                   Suitable for
                                                                            AC               DC                                                  Ex ia option
 A       1 x SPDT, silver                                                   250 V, 15 A      24 V, 2 A, 125 V, 0.5 A, 220 V, 0.25 A              No
 B       1 x SPDT, silver, hermetically sealed, argon gas filling   2)      250 V, 15 A      24 V, 2 A, 220 V, 0.5 A                             Yes
 C       1 x SPDT, gold-plated, hermetically sealed, argon gas filling 2)   125 V, 1 A       24 V, 0.5 A                                         Yes
 G       1 x DPDT, silver                                                   250 V, 1 A       24 V, 0.5 A                                         No
2) Permissible ambient temperature range: -30 ... +70 °C
Set point adjustment                                                         Example
The set point can be specified by the customer or factory-set                Setting range: 0 ... 10 bar with one switch contact
within the setting range. Subsequent adjustment of the set                   Repeatability: 1 % of 10 bar = 0.1 bar
point on site is made using the adjustment screw, which is                   Dead band: (see table setting ranges)
covered by the access cover plate with lead seal option.                     2 x repeatability + dead band = 2 x 0.1 bar + 0.3 bar = 0.5 bar
                                                                             Rising pressure: Adjust set point between 0.5 ...10 bar.
Repeatability of the set point                                               Falling pressure: Adjust set point between 0 ... 9.5 bar.
≤ 1 % of span
                                                                             Process connection
Please specify:                                                              Stainless steel, lower mount (LM)
Set point, switching direction for the contact, e.g.:                        ■ ¼ NPT female (standard)
Set point: 5 bar, rising                                                     ■ ½ NPT, G ½ A, G ¼ A male via adapter
                                                                             ■ ½ NPT, G ¼ female via adapter
For optimal performance we suggest to adjust the set point                   ■ M20 x 1.5 male via adapter
between 25 ... 75 % of the setting range.
 WIKA data sheet PV 35.40 ∙ 03/2021                                                                                                                     Page 2 of 6
Electrical connection                                                         For cable connections to the internal terminal block use wire
■ ½ NPT female (standard)                                                     cross-sections between 0.5 ... 2.5 mm2.
■ ¾ NPT, M20 x 1.5, G ½, G ¾ female                                           For the grounding cable connection to the protective conduc-
■ Cable gland non-armoured, nickel-plated brass                               tor screws use max. 2.5 mm2 for the internal screw and max.
■ Cable gland non-armoured, stainless steel (AISI 304)                        4 mm2 for the external screw.
■ Cable gland armoured, nickel-plated brass
■ Cable gland armoured, stainless steel (AISI 304)                            Dielectric strength
■ MIL connector, 7-pin, DTL 5015                                              Safety class I (IEC 61298-2: 2008)
Wetted parts, model DC
 Setting range                Stainless steel version                  NACE version (option) 1)          Monel version (option)
                              Diaphragm               Process con-     Diaphragm        Process con-     Diaphragm         Process
                                                      nection                           nection                            connection
 0 ... 160 mbar               AISI 316                AISI 316L        Monel® 400       AISI 316L        Monel® 400
 0 ... 250 mbar
 0 ... 400 mbar
 0 ... 600 mbar
 0 ... 1 bar
 0 ... 2.5 bar
 0 ... 4 bar                  AISI 304
 0 ... 6 bar
 0 ... 10 bar
 0 ... 16 bar                 Inconel® 718                             Inconel® 718                      -
 0 ... 25 bar
 0 ... 40 bar
1) NACE compliant to MR 0175, ISO 15156 and MR 0103
Wetted parts, model DCC
 Setting range                Diaphragm                 Process con-
                                                        nection
 0 ... 160 mbar               Inconel® 718              Aluminium alloy
                                                        (EN AW-5082 per
 0 ... 250 mbar
                                                        EN 573-3)
 0 ... 400 mbar
 0 ... 600 mbar
 0 ... 1 bar
 0 ... 1.6 bar
 0 ... 2.5 bar
 0 ... 4 bar
 0 ... 6 bar
Sealing material for all models and versions: NBR
Mounting
■ Mounting fixture from stainless steel (AISI 304)
■ Option: Mounting bracket for 2" pipe mounting (AISI 304)
Weight
■ approx. 5.4 kg, switch enclosure aluminium alloy
■ approx. 5.9 kg, switch enclosure stainless steel
 WIKA data sheet PV 35.40 ∙ 03/2021                                                                                             Page 3 of 6
Setting range, model DC
 Δp-cell                    Setting range              Fixed dead band                     Static / One-sided pressure
                                                       for contact version
                            in bar                     1 contact        1 contact          in bar
                                                       A, B, C          G
                                                       in mbar          in mbar
 L                          0 ... 0.16                 ≤6               ≤ 12               ≤ 40, ≤ 100 or ≤ 160
                            0 ...0.25                  ≤8               ≤ 20
 H                          0 ... 0.4                  ≤ 20             ≤ 40
                            0 ... 0.6                  ≤ 25             ≤ 50
                            0 ... 1                    ≤ 40             ≤ 80
                            0 ... 2.5                  ≤ 70             ≤ 170              ≤ 40, ≤ 100, ≤ 160 or ≤ 250
                            0 ... 4                    ≤ 120            ≤ 200
                            0 ... 6                    ≤ 180            ≤ 250
                            0 ... 10                   ≤ 300            ≤ 400
                            0 ... 16                   ≤ 480            ≤ 600
                            0 ... 25                   ≤ 700            ≤ 1,000
 V                          0 ... 40                   ≤ 1,200          ≤ 1,800            ≤ 40, ≤ 100 or ≤ 160
Other available setting ranges:
■ -40 ... +120 mbar, -60 ... +190 mbar, -200 ... +200 mbar, -300 ... +300 mbar, -500 ... +500 mbar
■ -1.25 ... +1.25 bar, -2 ... +2 bar, -3 ... +3 bar, -5 ... +5 bar, -8 ... +8 bar, -12.5 ... +12.5 bar
Setting range, model DCC 1)
 Δp-cell                    Setting range              Fixed dead band                    Static / One-sided pressure
                                                       for contact version
                            in bar                     1 contact        1 contact         in bar
                                                       A, B, C          G
                                                       in mbar          in mbar
 L                          0 ... 0.25                 ≤5               ≤ 10              ≤ 25
 H                          0 ... 1                    ≤ 30             ≤ 50
                            0 ... 1.6                  ≤ 50             ≤ 110
                            0 ... 2.5                  ≤ 80             ≤ 170
                            0 ... 4                    ≤ 120            ≤ 200
                            0 ... 6                    ≤ 120            ≤ 200
1) For clean gas or non-condensing vapour only
Other setting ranges on request.
Other Versions                                                      Assembly
■ Ex ia version                                                     ■ Valve manifold for differential pressure measuring
■ Cleaned for oxygen service                                          instruments, models IV30, IV31 and IV50 und IV51
■ Drying of wetted parts                                              see data sheet AC 09.23
■ Offshore version 2)                                               ■ Diaphragm seals, see website
■ NACE compliant to MR 0175, ISO 15156 and MR 0103 2)               ■ Differential pressure gauge
■ Wetted parts from Monel
2) WIKA recommends argon gas-filled contact versions
3) Only available for model DC
 WIKA data sheet PV 35.40 ∙ 03/2021                                                                                      Page 4 of 6
Approvals
 Logo             Description                                          Country
                  EU declaration of conformity                         European Community
                  ■ Pressure equipment directive
                  ■  Low voltage directive
                  ■ RoHS directive
                  ■ ATEX directive 1) (option)
                     IM1
                     II 1 GD
                  IECEx 1) (option)                                    IECEx member states
                     Ex ia I Ma
                       Ex ia IIC T6/T4 2) Ga
                       Ex ia IIIC T85/T135 2) Da
                  EAC (option)                                         Eurasian Economic
                  Hazardous areas                                      Community
                  Ex-Ukraine (option)                                  Ukraine
                  Hazardous areas
                  CCC (option)                                         China
                  Hazardous areas
                  KOSHA (option)                                       South Korea
                  Hazardous areas
1) Double marking ATEX and IECEx on the same product label
2) The temperature class is related to the ambient temperature range
Manufacturer‘s information and certifications
 Logo             Description
                  SIL 2 rating (option), per IEC 61508
                  Functional safety
                  Only available with contact version B or C
Certificates (option)
■ 2.2 test report per EN 10204
■ 3.1 inspection certificate per EN 10204
Approvals and certificates, see website
 WIKA data sheet PV 35.40 ∙ 03/2021                                                   Page 5 of 6
             Dimensions in mm
              Switch enclosure: Aluminium alloy                                                                   Switch enclosure: Stainless steel 316L
             Legend
             A     ⊖ Process connection                                   C     Electrical connection
             B     ⊕ Process connection                                   V     Vent
             Assembly examples
              Direct mounting with valve manifold                                                                 Mounting via capillary to diaphragm seals
             Ordering information
             Model / Static - One-sided pressure / Δp-cell / Switch enclosure / Contact version / Setting range / Process connection /
             Electrical connection / Options
             © 12/2010 WIKA Alexander Wiegand SE & Co. KG, all rights reserved.
             The specifications given in this document represent the state of engineering at the time of publishing.
             We reserve the right to make modifications to the specifications and materials.
03/2021 EN
              WIKA data sheet PV 35.40 ∙ 03/2021                                                                                                              Page 6 of 6
                                                                                                                                  WIKA Alexander Wiegand SE & Co. KG
                                                                                                                                  Alexander-Wiegand-Straße 30
                                                                                                                                  63911 Klingenberg/Germany
                                                                                                                                  Tel.   +49 9372 132-0
                                                                                                                                  Fax    +49 9372 132-406
                                                                                                                                  info@wika.de