Descripción de dimensiones Unidad de Tratamiento de Aire

Uploaded by

Mariano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views7 pages

Hoja Tecnica Uta

Descripción de dimensiones Unidad de Tratamiento de Aire

Uploaded by

Mariano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Modelbox CLCF PU (EN 1886)

- Casing Strength: D1
- Air Leakage (-400/+700): L1
- Filter Bypass: F9
- Thermal Transmittance: T2
- Thermal Bridging: TB2
TRANE participates in the ECC
programme for Air Handling Units
(AHU); check ongoing validity of
certificate online
www.eurovent-certification.com or
using www.certiflash.com.
SFP 1.1 W/l/s = 1.1 kW/m3/s
calculated using EN BS 13779
standards.
Designed at mid-point filter status, wet
coil condition.
fs-Pref W./S. 0.91/0.83

Offer N° 23-0005 Rel. 3.3.1.38 25-02-2022-


User villalba AHU1000/0360/824.716
Client AHU Mondelez Arg Date 16-02-2024
Unit reference UMA-1 - FINAL - HORIZONTAL City Buenos Aires
Project AHU Mondelez Arg
Serial number AHU Mondelez Arg
SUPPLY AIRFLOW m³/h 20000 RETURN AIRFLOW // m³/h

UNIT TYPE - CLCF 7.5 - Comfort


Insulation Polyurethane Foam (40 kg/m3) Panel thickness mm: 50
Roof Absent Panel internal side Painted Galvanised Steel
Type of roof Absent Panel external side Painted Galvanised Steel
Absent/No Roof Coil conn cabinet Absent
Support With baseframe Door type With hinges
Damper class Standard: Class 2 EN1751 Screw and bolts Galvanised Steel (standard)
Drain pan material Stainless Steel AISI 304 Packing type: Plastic Wrapping
Internal frame Galvanised Steel Eyes bolts Present

Inspection side (supply air Left Connection side (supply air Left
flow on back) flow on back)

Width mm 1923 Height + basement mm 1614 + 100


Length mm 4570 Total weight kg 1352

SUPPLY SIDE

Section 1 LENGTH: (mm) 1805 Weight :(kg) 549


Section accessories

CLCFWin Rel. 3.3.1.38 25-02-2022 1/7


AHU1000/0360/824.716
16-02-2024-Offer N°23-0005/A
Intake Section
Only hole dimensions 410x1813 mm .
Airflow 20000 m³/h
Actuator absent
With external flexible connection
Total pressure drop section 0 Pa

MATERIAL DIMENSIONS N. EFFICIENCY


Soft Bag Filter Synthetic 592 x 592 x 48 mm 6 G4 EN779 coarse 60% DP CL(Pa) 68+102
fiber 287 x 592 x 48 mm 3 F8 EN779 (E) ePM1 85% DP MP(Pa) 102+153
Synthetic 592 x 592 x 535 mm 6 Des. Temp. 24.0 °C DP DT(Pa) 136+204
fiber 287 x 592 x 535 mm 3 Vtunnel 2.01 m/s

The filters efficiency is according the ISO16890


Filter frame Stainless Steel AISI 304
Side removal
With Magnehelic gauge
With pressure switch
With light and switch 230V
With marine window

TUBES Cu/0.40 TYPE 40x34.6 CAPAC. (kW) 100.0 FLUID Water

Cooling coil FINS Al/0.11 DIM (mm) 1440x1570 EAT/RH (°C-%) 24.0-50 FLOW. (Kg/h) 17144
FRAME Zn/1.5 ROWS (n) 4 LAT/RH (°C-%) 11.6-100 EWT/LW 6/11
T (°C)
CONN.Ø. 2" F.SPACE (mm) 2 Vtunnel 2.01 DP (kPa) 37
VOL. (lt) 57.1 CIRCUITS (n) 18 DP tot/dry (Pa) 116/89
FTA (mm) 1760
Sens./Tot. 0.85

Cu-Al-FeZn P40AR 4R-36T-1570A-2.0pa 18C 2"


Total pressure drop section 116 Pa

Section 2 LENGTH: (mm) 2765 Weight :(kg) 803


Section accessories

FAN TYPE Plug fan AIRFLOW 20000 m³/h


Supply Fan SIZE NPL900S4CL1 EXTERNAL STATIC PRESSURE 300 Pa
TOTAL STATIC PRESSURE 678 Pa
RPM/FREQ. 804 rpm / 41.9 Hz
ABSORBED POWER 5.2 kW
EFFICIENCY STATIC/TOTAL 73/77 %
In duct sound power: (dBA) 80.1
Octave in duct power level
F [Hz] 63 125 250 500 1000 2000 4000 8000
Supply [dB] 78 87 84 84 81 78 71 66
SL490*290-DM2360*1810
GR2-2*6-2*6-2*6-2*6

With electronic air flow measurement device


With protection on drive (second door)
With safety door microswitch
With inspection window
With differential pressure switch
With light and switch 230V
Rubber insulators
CLCFWin Rel. 3.3.1.38 25-02-2022 2/7
AHU1000/0360/824.716
16-02-2024-Offer N°23-0005/A
With flexible connection on fan

CLCFWin Rel. 3.3.1.38 25-02-2022 3/7


AHU1000/0360/824.716
16-02-2024-Offer N°23-0005/A
PROTECTION IP 55 RPM 960
Motor IE2 INSULATION CLASS F POWER SUPPLY 400V/3ph/50Hz
POLES N. 6 STARTING TYPE Direct
INSTALLED POWER 7.5 kW RATED AMPS (A) 17
MAX AMPS (A) 110.5
MOTOR 50 Hz POWER INPUT: (kW) 6.22
SFPv (SFPe): (W/l/s) 1.1
With installed inverter IP20
With Electrical Isolator wired
Motor thermal protection PTC

Intake Section ALUMINUM PROFILE DAMPER


Damper - 1 off insp.side shaft dimensions 610x1813 mm .
Airflow 20000 m³/h
Motorisable (linkage not incl.)
Actuator absent
With external flexible connection
With blade gasket (Leakage Class 2 according to EN1751)
Total pressure drop section 9 Pa

CLCFWin Rel. 3.3.1.38 25-02-2022 4/7


AHU1000/0360/824.716
16-02-2024-Offer N°23-0005/A
AHU sound levels Octave band (dB/Hz)
Tot. dB(A) 63 125 250 500 1000 2000 4000 8000
Sound power level supply inlet 77 66 79 56 72 76 58 44 35
Sound power level supply outlet 86 73 89 88 84 81 77 68 64
Sound power level return inlet
Sound power level return outlet
Airborne sound power 64 68 59 65 55 53 30 26

- before installing the unit, read the IOM -


unit is designed at 0 m on sea level, and with air density 1,2 kg/m3
- make the electrical wiring following the drawing inside of the motor power box or on motor label
- to avoid electrical motors overload, do not start the unit without filters or other component or without ducts or with door
open
- the unit has been designed with the required external static pressure and considering a status of filters: with plant
pressure drop less then the required, with different status of filters and without proper control, the airflow and the sound
power will be more than the indicated
- the cross flow recuperator has been designed in order to resist to the indicated differential pressure between the
plates. Do not exceed this value enslaving properly dampers or other interception devices. RHW and PHE are not
airtight devices and leakage between flows always occurs. Exact value can depends on static pressure and unit
configuration; to avoid contamination, the pressures on the fresh air side shall be higher than on the return air side
- performance data of the heat recuperator are considered for counterflow of air; in case both flows are in same
direction, performance data could be substantially different from those
-If footprint of PHE section or of other sections exceed 2300 mm x 2400 mm, a special transport could be necessary.
Please contact the factory
- unit is designed for a maximum air temperature of 55°C
- depending on supply air temperature and outdoor condition, condensate on profiles can occur
- if water temperature entering the coil is below 1°C, freezing of coil fins can occur
- link the fan working to intercepting devices, as dampers or similar, avoiding fan working with those devices closed
- filter frame “side removable” could cause filter bypass due to not perfect airtight between filter cells
- if unit is provide of roof in kit, it will be provide separately, to mount on site by customer
- standard painted panel skin color RAL9002 --
if the door length is <= 360 mm, also if selected, the inspection window will not be provided and door could be
removable
- in some cases the inspection window could be partially occluded by components or components frame
- calculate sound pressure levels are indicative only. It corresponds to: free filed hemispheric sound radiation from the
unit casing, the inlet and outlet opening. Other sources, acoustic character of the room, air flow noise, duct connection
and vibration can influence the sound pressure in dependence. In practise, therefore measured values on site may be
different from the calculation ones
- unit has been designed in wet condition
- unit weight does not include water/refrigerant and control (if provided)
- tolerance on sound levels are: - airborne level : +/-3 Db; duct level : +/-5 Db @ 63-125 Hz
and +/-3 Db @ 250-8000 Hz
- due to the gasket between sections, the total length of the unit will be around mm.5+ longer for each break point
- in case unit is provided of flat roof, it will be mm.20 out all around the unit
- in case unit is provided of sloped roof, it will be mm.100 out all around the unit
- due to bigger heater and bends, the steam coil finned area will be light reduced respect what indicated, with
consequent increase of the air velocity thought it
-based on dimensions mentioned in datasheet, a special transport could be required
- for FC units, it's possible to install the inspection doors only at the bottom
This technical sheet and the attached drawing is the only document reporting the air handling unit construction features,
also if not in conformity with offer or other requests/documents sent to us, including mechanical specifications, technical
description or similar.
For general construction features not indicated in it, refer to available documentation.

CLCFWin Rel. 3.3.1.38 25-02-2022 5/7


AHU1000/0360/824.716
16-02-2024-Offer N°23-0005/A
Eurovent Summer Application

ALGHERO FERTILIA (Italy)


Design dry-bulb temp. 34.8 °C
Design dew-point temp. 16.4 °C
Design wet bulb temp. 22.2 °C

Ecodesign
Manufacturer TRANE
Unit model CLCF 7.5
Typology NRVU;UVU
SFPint / SFPint limit 2016 [W/(m³/s)]
SFPint / SFPint limit 2018 [W/(m³/s)] 153 / 230
Type of HRS -
Thermal efficiency of heat recovery [%] -
Class of casing leakage at -400 Pa / +400 Pa L1(M) / L1(M)
Maximum internal leakage rate [%] L1(M)
Supply
Nominal flow rate [m³/s] 5.56
Type of drive for var. speed scheduled inst. of var. speed
Effective electric power input [Kw] 6.2
Face velocity [m/s] 2.01
Nominal external pressure [Pa] 300
Internal pressure drop of ventilation components [Pa] 93
Static efficiency of fan [%] 60.6
Energy consumption of the filters (kWh/annum) D
Internet address for disassembly instructions

AHU doesn't fall under Ecodesign

CLCFWin Rel. 3.3.1.38 25-02-2022 6/7


AHU1000/0360/824.716
16-02-2024-Offer N°23-0005/A
150 410 610 150

1614

1714
100
1805 2765
4570

DISCONNECTING
SWITCH
55

55
1813

1813

1923
55

55

AHU Mondelez Arg


UMA-1 - FINAL - HORIZONTAL

CLCF 7.5
AHU Mondelez Arg
DO NOT SCALE villalba 16-02-2024