Nique Nteriors
Nique Nteriors
UNIQUE
INTERIORS
ON THE
ALSO:
www.sfpe.org 1
viewpoint
Sunderland Joins
Universityof Maryland The SFPE Corporate 100 Program was founded in
1976 to strengthen the relationship between industry
Dr. Peter B. Sunderland has joined the Department of Fire Protec- and the fire protection engineering community.
tion Engineering, University of Maryland, as Assistant Professor. He Membership in the program recognizes those who
support the objectives of SFPE and have a genuine
was previously at the National Center for Microgravity Research at the concern for the safety of life and property from fire.
NASA Glenn Research Center in Cleveland, OH.
BENEFACTORS
FM Global Corporation
Professor Sunderland’s degrees are from Cornell University (B.S.), Koffel Associates, Inc.
the University of Massachusetts (M.S.), and the University of Michigan Rolf Jensen & Associates, Inc.
SimplexGrinnell
(Ph.D.). His research interests are in combustion and fire protection.
His specializations include soot formation, microgravity combustion, PATRONS
laminar diffusion flames, oxygen-enhanced combustion, and experi- Code Consultants, Inc.
Gage-Babcock & Associates, Inc.
mental methods in combustion. Hughes Associates, Inc.
For more information visit National Fire Protection Association
The Reliable Automatic Sprinkler Company
www.eng.umd.edu. Schirmer Engineering Corporation
Specified Technologies, Inc.
Tyco Fire and Building Products, Inc.
MEMBERS
NIST Provides Fire Resistance Data Altronix Corporation
on WTC Floor Systems Ansul, Inc.
Arup Fire
Four fire resistance tests conducted on composite concrete-steel Automatic Fire Alarm Association
trussed floor systems typical of those used in the World Trade Center Cybor Fire Protection Company
Edwards Systems Technology
(WTC) towers showed the test structures were able to withstand stan- Fike Corporation
dard fire conditions for between one and two hours, according to the GE Global Asset Protection Services
Harrington Group, Inc.
National Institute of Standards and Technology (NIST). HSB Professional Loss Control
James W. Nolan Company (Emeritus)
Marsh Risk Consulting
The 1968 New York City building code – the code the towers were National Fire Sprinkler Association
intended but not required to meet when they were built – required a Nuclear Energy Institute
two-hour fire rating for the floor system. The Protectowire Co., Inc.
Reliable Fire Equipment Company
TVA Fire and Lifesafety, Inc.
Shyam Sunder, lead investigator, explains that the tests provide Underwriters Laboratories, Inc.
Wheelock, Inc.
only a means for evaluating the relative fire resistance rating of the Williams Fire & Hazard Control, Inc.
floor systems under standard fire conditions and according to ac-
SMALL BUSINESS MEMBERS
cepted test procedures. Sunder cautions, “These tests alone cannot
Beall & Associates, Inc.
be used to determine the actual performance of the floor systems in Bourgeois & Associates, Inc.
the collapse of the towers. However, they are already providing valu- Davidson and Associates
Demers Associates, Inc.
able insight into the role that the floors may have played in causing Fire Consulting Associates, Inc.
the inward bowing of the perimeter columns minutes Fire Suppression Systems Association
Futrell Fire Consult and Design, Inc.
before both buildings collapsed.” Gagnon Engineering, Inc.
More information visit Grainger Consulting, Inc.
J.M Cholin Consultants, Inc.
http://wtc.nist.gov. Poole Fire Protection Engineering, Inc.
Risk Logic, Inc.
Risk Technologies LLC
Slicer and Associates, LLC
S.S. Dannaway & Associates, Inc.
The Code Consortium, Inc.
Worcester Polytechnic Institute
M
take a trip back in time to the Wild West,
any of the largest and most unique buildings in the the Roman Empire, or medieval Europe.
world are located on the Las Vegas Strip. The interi- Fantasy abounds, and to create these
fantasies, the interiors of the facilities are
ors of these facilities gives one the impression of transformed to achieve the desired illu-
being somewhere else and/or in a different time. sion.
The interiors of these facilities contain
ically, the burner exposes the sample for 150 kilowatts. Due to the three-quarter The flame-spread index is a numerical
very short periods of time. pound (0.34 kg) wood crib used as an rating applied to tested materials. It is a
The results from these tests are only ignition source, with an approximate calculated value based on the relation-
applicable to very small, transient expo- peak heat release rate of 18 kW, these ship between the distance the flame
sure ignition conditions. tests may be considered small-scale. front extends within the test chamber
and the respective time it took to reach
UL 1975 The Steiner Tunnel Test that distance. A material with a Class A
In the late 1980s, The Society of Plas- This test is known by several designa- flame-spread rating has been tested with
tics Industry, Inc., and Underwriters Lab- tions, including ASTM E-84, NFPA 255, a flame-spread index of 25 or less. Mate-
oratories (UL) developed testing criteria and UL 723. As described in the NFPA rials receiving a flame-spread index
for foam plastics intended for use in ex- Fire Protection Handbook,3 this test was greater than 25 and up to 75 are as-
hibit booths, on film production stages, originally developed at Underwriters signed a Class B flame-spread rating.
and for decorative objects.2 Decorative Laboratories in the 1920s, and the cur- Class C materials have a flame-spread
objects include such objects as man- rent physical design was completed in index greater than 75 and up to 200. For
nequins, murals, and signs. The amount 1948. all classes, the smoke-developed index
of exposed foam plastic is dependent on This test was developed as a basis to is limited to a maximum of 450.
the proposed use and should be tested compare the surface-burning character- One of the most important concepts
at the same thickness and density as the istics of materials that form the exposed to be aware of when using the Steiner
expected application. The size of the ex- interior finishes of walls and ceilings in a Tunnel test method is that the burning
pected application should be limited to building. Reinforced-cement board is characteristics of thin combustible mate-
the size intended by the test. Larger ap- used to establish the zero value, with rials can be affected by the properties of
plications should be tested in accor- red oak flooring being assigned a rating their substrate. The lid of the furnace
dance with a larger-scale test. of 100. All other tested materials are constitutes the substrate for thin materi-
Foam plastics in exhibit booths and compared with these two values. The als tested in the tunnel. This lid is a non-
film production are allowed to have a peak heat release rate of the gas burners combustible refractory liner. As such, re-
maximum heat-release rate of 100 kilo- used as the ignition source is approxi- sults obtained from this test method may
watts. Decorative objects are limited to mately 88 kW. be quite misleading when no substrate,
or a combustible substrate, is expected orientation, its actual installation, and a Upon a cursory review of these guide-
for the proposed installation. In addi- moderate fire exposure condition. For lines, they may appear more conservative
tion, the ASTM E-84 test standard speci- certain applications, newer versions of than the allowable percentage limita-
fies that the material be tested in the codes and standards allow this test as a tions. Consider a 100,000 sq. ft. (9,000 m2)
manner in which it is to be used. There- substitute for ASTM E-84. casino with the entire allowable percent-
fore, one often-misunderstood require- Other full-scale fire tests such as large age installed in one location. As such,
ment is that this test standard expects a open corner tests (FM 4880 or UL 1040) the Clark County guidelines take a
substrate to be included when thin com- or nonstandard full-scale fire tests that somewhat different approach than the
bustible materials tested in this manner replicate end-use conditions are also allowable percentage option by limiting
are installed within a building. used to provide a more accurate mea- the size of each item and requiring suffi-
Since its inception, ASTM E-84 has sure of fire performance of wall and cient separation between adjacent items
been used to evaluate all interior finish ceiling materials. to consider each such item a separate
materials. Over the years, it has been fuel package.
recognized that the results of the test ORGANIZING THE APPROACH
method may not be indicative of real-life Decorative Wall Applications
fire performance. For example, the There are many ways to organize fire Wall-type applications can include
NFPA 101 Handbook4 discusses tests protection approaches for unique interi- murals, tapestries, pictures, signs, or
conducted at the Fire Research Labora- ors. One way is to break the features other features that are affixed to or sus-
tory of the University of California at into similar concepts that are already ad- pended from facility walls. Draperies
Berkeley and sponsored by the Ameri- dressed in codes and standards. This ap- and other decorative aspects installed in
can Textile Manufacturers’ Institute in proach is outlined in Clark County’s a vertical plane may also be included.
late 1985. This testing demonstrated that Guidelines for Unique Interiors.5 One way to think about wall-type ap-
flame-spread measurements alone might These guidelines consider of the fol- plications is to consider when a picture
not reliably predict the fire behavior of lowing unique interior design elements: becomes a wall. A picture or sign can
textile wall and ceiling coverings. • Trim generally be hung on a wall without
• Wall Applications concern of a fire hazard. As the picture
Room-Corner Tests • Ceiling Applications or sign gets larger, the potential hazard
Over the last 30 years, various room- • Artificial Plants and Statues increases. At a point, the hazard may
corner fire tests have been used and • Decorative Structures within even overwhelm the building’s fire pro-
standardized. One example is the 30-lb Buildings tection systems.
(14 kg) wood crib room-corner test (UL- Paintings hung on walls are typically
1715) used in many U.S. codes. Other Trim Items considered decorative materials. If the
examples include NFPA 265, which was By its very nature, trim is limited in painting is removed from its frame and
developed specifically to address the size and quantity. Features that can be adhered to gypsum wallboard with a
flammability of textile wall coverings, classified as trim typically do not consti- noncombustible adhesive, its potential
and NFPA 286, which was developed to tute sufficient fire hazard to be a con- to burn is reduced, since thin materials
address interior wall and ceiling finish cern. When trim exceeds reasonable tend to take on the burning characteris-
materials. limitations, a greater level of protection tics of the substrate to which they are
These NFPA tests were developed to becomes necessary. The challenge is de- adhered. Eliminating one surface of a
provide additional engineering data termining what constitutes “reasonable” thin material will typically (and some-
such as heat release rate and smoke pro- limitations? times significantly) reduce that material’s
duction as well as providing a visual ob- Trim can include baseboards, chair ability to exhibit significant flame
servation of the extent of burning. These rails, crown mouldings, door/window spread. Additional considerations are
tests use a gas-fired burner placed in a frames, and handrails. The length of the material’s proximity to ignition
corner of the room with a heat output these trim items is not limited, but Clark sources and automatic fire sprinkler sys-
that replicates the fire growth of the 30- County typically limits the height/width tem effectiveness. For example, the
lb (14 kg) wood crib exposure. The to six inches (150 mm). Beyond this, higher up a wall a mural is located, the
burner produces a 40 kW heat output these trim items are considered farther it should be from most significant
for the first five minutes to simulate a wall/ceiling finish. ignition sources and the closer it will be
small fuel package, such as a wastebas- Some codes and standards allow a to sprinklers.
ket. For the following 10 minutes of the small percentage of the walls and ceil- An additional constraint is the size of
15-minute test, the heat output is in- ings to have decorative combustible fea- a mural. When exposed to fire, large
creased to 150 kW (or 160 kW, depend- tures that are considered trim. As such, murals may delaminate, and burning
ing on the test) to simulate a larger fuel these items are less regulated than if scraps of material may fall down to ig-
package, such as a chair. One of the fail- they were classified as building materi- nite one or more fires that exceed the
ure criteria is if flashover occurs. See the als. To allow decorative combustible fea- intent of the sprinkler design and over-
article in this issue on page 16 for addi- tures up to the percentage of the wall or whelm the sprinkler system.
tional information. ceiling area specified by code has been On the Strip, there are several hand-
These tests provide a more appropri- taken into account in the Clark County painted murals adhered to facility walls.
ate evaluation with respect to material guidelines. Many of these have been tested in ac-
not representative of the use of the material in realistic situa- Therefore, all carpets and rugs sold in they United States5 must
tions.3 The same can also be said about thin materials, which of- meet the “methenamine pill” test (ASTM D 2859), which ensures
ten give low FSI values mainly due to insufficient material in the that flame spread will be minimal.
test method to permit flame spread to be assessed properly. An Most codes also regulate interior floor finish (in occupancies
understanding of some of these limitations has caused the codes where fire risk needs to be especially minimized) to be tested
to consider alternatives, either as replacements for the Steiner with the flooring radiant panel (ASTM E 648, NFPA 253, Figure 3)
tunnel or as additional options (see section on heat release). and require a “critical radiant flux” for ignition in excess of 4.5
kW/m2 (Class I) or 2.2 kW/m2 (Class II). In the flooring radiant
FLOOR FINISH TEST METHODS panel, the floor finish (such as a carpet) is exposed to an incident
heat flux from an angled gas-fired radiant panel, with a maxi-
Different challenges face interior floor finish than other inte- mum heat flux of approximately 11 kW/m2 at the farthest end
rior finish because heat and smoke rise in a fire. Thus, floor fin- from the igniter. The test method assesses the critical incident
ish is involved either as the initial material ignited in a fire or as flux (which is measured by comparing the distance between the
an additional fuel once a fire has become uncontrolled. Conse- igniter and the point where flame propagation stops to a calibra-
quently, fire safety requirements typically need to ensure that in- tion curve) required for continued
terior floor finish is relatively difficult to ignite and is not capable flame propagation.
of slowly spreading flame from the compartment of fire origin to This approach (even if it is based
a different one. on old-fashioned tests) is quite suit-
The Steiner tunnel cannot assess ignitability, and its fuel able for interior floor finish. Some ap-
source is not appropriate to assess slow flame spread. Experi- plications, typically in the transporta-
ence has shown that many flooring materials (traditional floor tion vehicle arena, also require
finishes such as wood flooring or resilient materials) will not ig- flooring materials to meet one of a va-
nite unless exposed to an ignition source of well over > 1 riety of smoke obscuration require-
kW/m2, but that some carpet-like or loose-fill materials may ig- ments, often based on a static smoke
nite at such low heat fluxes. A study of precision of the flooring chamber box, either with a traditional
radiant panel test method found carpets with critical radiant heat radiant heater (ASTM E 662) or with a
fluxes well under 2 kW/m2.4 conical heater (ISO 5659-2, IMO Fire
Test Procedures Code part 2, also Figure 3: Flooring
known as ASTM E 1995 and NFPA Radiant Panel Test
270). Apparatus (ASTM E 648)
Of course, the key question to ask in any fire is “how big is the
fire?”, and the answer lies in the rate of heat release.6, 7, 8, 9, 10, 11 A
burning product will spread a fire to nearby products only if it
gives off enough heat to ignite them. Moreover, the heat has to
be released fast enough not to be dissipated or lost while travel-
ing through the cold air surrounding any product that is not on
fire. Therefore, heat-release rate dominates fire hazard, and it has
been shown to be much more important than ease of ignition,
smoke toxicity, or flame spread in controlling the time available
for potential victims of a fire to escape.
The above concepts are now applied to fire testing of interior
(wall and ceiling) finish, and all U.S. codes use a room-corner test
for the purpose. The use of the room-corner test can be an alterna-
tive to the Steiner tunnel test (for most interior finish materials) or
Figure 4: Room-
Corner Fire Test
ROOM-CORNER TEST
Research was conducted very high heat-release rates (but not quite enough for
to look into issues associ- flashover) should probably be classified separately from materi-
ated with room-corner test- als that have low peak rates of heat release rate.
ing.12, 13, 14 As a result, two ad- NFPA 265 is a somewhat less severe variation of NFPA 286,
ditional important criteria which is applied exclusively to textile wall coverings (and ex-
required by the codes are panded vinyl wall coverings). In NFPA 265 and NFPA 286, iden-
that the flame spread does tical test rooms and identical gas burners are used. There are
not reach any of the extrem- three main differences, however, in the ignition sources used
ities of the test sample and for both tests: 1) in NFPA 265, the burner is placed 51 mm away
that the total smoke release from each of the walls, as opposed to flush against the walls as
cannot exceed 1,000 m2 in NFPA 286 (but it is placed in the same corner as in NFPA
over the entire 15-minute 286); 2) in NFPA 265, after the first 5 minutes at 40 kW, the
test period. burner intensity is raised to 150 kW, as opposed to 160 kW in
If all criteria are met, the NFPA 286; and 3) smoke release measurements using NFPA 265
material is suitable for use in are not required in the codes. It is likely that, eventually, textile
all applications where the wall coverings will be required to be treated similarly to other
codes require a material to interior finish.
Figure 5. Flame in Room- be tested by the Steiner tun-
Corner Test nel and where Class A, B, or ANALYSIS OF TEST METHODS
C requirements exist. In
practice, it is rare for a material to spread flame to the extremi- Now that the actual tests used have been presented, it is im-
ties of the test sample and still not cause flashover, since that portant to discuss the validity of the test methods and whether
would mean that the flame would reach the edge of the door improvements should be put in place. One obvious improve-
and stop without exiting the doorway (one of the criteria for ment which would permit a much more logical approach to us-
flashover). This means that any material that does not cause ing fire safety engineering methods would be to apply a test
flashover and releases < 1,000 m2 of smoke is considered equiv- method based on heat release for testing interior floor finish
alent to a Class A material. In fact, it is likely that materials with (such as the cone calorimeter, a bench-scale test, e.g., for exam-
ple, ASTM E 1354, NFPA 271, ISO 5660).
In fact, two ASTM guides and one NFPA guide addressing
fire hazard assessment, ASTM E 2280 (for healthcare occupan-
cies), ASTM E 2067 (for rail cars), and NFPA 555 (on potential
for flashover), all recommend the use of the cone calorimeter
to assess heat and smoke release of interior floor finish, at in-
cident heat fluxes of 25-30 kW/m2. However, it is true that the
combination of the methenamine pill test and the flooring ra-
diant panel test is sufficient to eliminate the vast majority of
“bad actors.” Thus, the methods being used are fairly ade-
quate for a prescriptive fire safety approach that does not dis-
criminate against materials. The additional smoke release test-
ing (used mostly in transportation environments) is not of
very high value, but it may serve to eliminate some poor per-
forming materials.
There continues to be controversy with regard to smoke re-
lease testing of interior wall and ceiling finish. In a field that
continues to be dominated by the Steiner tunnel test (despite its
well-known inadequacies for testing some materials) the ques-
80
70 SwRI (10)
Eurefic (28)
60 SBI (30)
Percentage of Total
30
20
10
0
Early Flashover Adequate Heat, Adequate Heat,
Low Smoke High Smoke
Figure 6. Room Corner Testing, Heat & Smoke Release
1500 2000
Actually 5771
1800
1250 Pk RHR
1400
1000
1200
750 1000
800
500
600
400
250
200
0 0
0 200 400 600 800 1000 1200 0 25 50 75 100 125 150 175 200
Steiner Tunnel SDI FSI in Steiner Tunnel
Figure 7. Smoke Release of Interior Finish Figure 8. Rate of Heat Release vs Flame Spread
tion arises: Is it necessary to test for test. However, the codes allow the NFPA corner test as unacceptable.
smoke release in the room-corner test, or 286 room-corner test results based on the • 14 materials had an FSI of 25 or less
is it enough to just develop low heat re- premise that materials that do not cause (i.e., Class A) in the Steiner tunnel and
lease products? flashover (or high smoke release) in the released less than 400 kW in the room-
Figure 615 shows that of five series of room-corner test are known to also have corner test. Both tests classify them as
tests conducted in room-corner tests, sys- flame spread indices of < 200 and smoke Class A.
tematically some 10% of the materials (10 developed indices of less than 450 in the • 2 materials had an FSI of > 25 and <
of the 84) give low heat release but unac- Steiner tunnel test. 75 (i.e., Class B) in the Steiner tunnel and
ceptably high smoke release. So the im- These provisions work well to a point released less than 400 kW in the room-
portance of assessing smoke release of but need refinement. The Steiner tunnel corner test. The Steiner tunnel test classi-
interior wall and ceiling finish in a large- test is likely to give falsely favorable re- fies them as Class B and the room-corner
scale test is clear. Code writers then saw sults (in fact, this happens often with ma- test as Class A.
that both flame spread and smoke re- terials that melt and drip and with materi- • 2 materials had an FSI of 25 or less
lease (or heat release and smoke release) als that are thin films) but it rarely gives (i.e., Class A) in the Steiner tunnel and
must be assessed to adequately regulate falsely unfavorable results (meaning that a released more than 400 kW but did not
the fire performance of interior wall and high flame-spread index, or FSI, is almost cause flashover in the room corner test.
ceiling finish materials, whatever test always indicative of a material with Both tests classify them as Class A.
method is used. mediocre or poor fire performance). The • 2 materials had an FSI of 200 or less
Thus, a smoke-release criterion room-corner test results are potentially (i.e., Class C) in the Steiner tunnel and al-
needed to be added to fire testing using much more suitable to classification of most caused flashover in the room-cor-
the room-corner test (such as NFPA 286), materials, because the heat release rate ner test. The Steiner tunnel test classifies
for which heat release only used to be history is obtained in the test. However, them as Class C and the room-corner test
measured, while both flame spread and the fact that the heat release rate history is as Class A.
smoke release have always been re- not used for code classification purposes In conclusion, fire testing of interior
quired in the Steiner tunnel test. The data results in some inconsistencies occurring finish is probably adequate to eliminate
in Figure 712, 13, 14 shows that this problem when comparing results from both tests. the poorest performers (both in terms of
can be resolved (and has now made its Therefore, it would be important to use heat release, or flame spread, and smoke
way into codes) by using equivalent cri- the heat release rate history in the room- release). However, in terms of maximiz-
teria in both tests, since materials with corner test in conjunction with testing ing the usefulness of current research
very high smoke-developed index (SDI) whether flashover does or does not occur. and to accommodate modern building
are also likely to have a very high total Figure 8 (based on a survey of pub- materials, the Steiner tunnel test falls
smoke release (TSR) in the room-corner lished data developed for this work) short. In applying a variety of new and
test, which is how the 1,000 m2 pass-fail shows the comparative fire performance specific tests, the full capabilities of the
criterion was developed. of 25 materials tested in the Steiner tun- room-corner test, including the actual
In light of steady research, it becomes nel and in the room-corner, and illus- heat release rates measured, could be in-
clear that for all of its traditional merits, trates the problem: corporated into engineering, and im-
the approach of codes to testing interior • 5 materials had an FSI of 200 or less provements in that area would be wel-
wall and ceiling finish is a slightly flawed (i.e., Class A, B, or C) in the Steiner tun- come. ▲
concept. Clearly the room-corner test is a nel but caused flashover in the room
much more accurate way of assessing corner test. The Steiner tunnel test clas- Marcelo Hirschler is with GBH Interna-
fire performance than the Steiner tunnel sifies them as acceptable and the room- tional.
REFERENCES Consumption Measurements,” Fire and Proceedings – Fire and Materials Conf.,
Materials, 1980, 4, pp. 61-65. Feb. 22-23, 1999, Interscience
1 NFPA 5000, “Building Construction and Communications, London, UK, pp. 83-94.
7 Babrauskas, V., and Grayson, S.J., Eds.,
Safety Code,” National Fire Protection Heat Release in Fires, Elsevier, London, 13 Hirschler, M.M., and Janssens, M.L.,
Association, Quincy, MA, 2003. UK, 1992. “Smoke Obscuration Measurements in the
2 International Building Code, NFPA 265 Room-Corner Test,”
8 Hirschler, M.M., “Heat Release from
International Code Council, Falls Church, Proceedings – Fire and Materials Conf.,
Plastic Materials,” Heat Release in Fires,
VA, 2003. Feb. 22-23, 1999, Interscience
Elsevier, London, UK, Eds. Babrauskas, V.
Communications, London, UK, pp. 179-
3 Belles, D.W., Fisher, F.L., and Williamson, and Grayson, S.J., Eds., pp. 375-422, 1992.
198.
R.B., “How well does the ASTM E-84 pre- 9 Babrauskas, V., and Peacock, R.D., “Heat
dict fire performance of textile wallcover- 14 Janssens, M.L., Dillon, S.E., and Hirschler,
Release Rate: The Single Most Important
ings?” Fire Journal, 82(1), pp. 24-30, 74 M.M., “Using the Cone Calorimeter as a
Variable in Fire Hazard,” Fire Safety
(1988). Screening Tool for the NFPA 265 and
Journal, 1992, 18, pp. 255-72.
NFPA 286 Room Test Procedures,”
4 Lawson, J.R., “Fire tests and flooring 10 Hirschler, M.M., “Use of Heat Release Rate Proceedings – Fire and Materials Conf.,
materials,” Proc. 2nd Fire and Materials to Predict Whether Individual Furnishings Jan. 22-24, 2001, Interscience
Conf., Sept. 22-23, 1992, Interscience Would Cause Self-Propagating Fires,” Fire Communications, London, UK, pp. 529-
Communications, London, UK, pp. 253- Safety Journal, 32, 273-296 (1999). 540.
262.
11 Hirschler, M.M., “Flammability and Fire 15 Hirschler, M.M., “Fire Performance of
5 16 CFR 1630, Code of Federal Performance of Polymers,” Organic Polymers, Thermal
Regulations, Chapter II, Consumer Comprehensive Desk Reference of Polymer Decomposition, and Chemical
Product Safety Commission, Part 1630, Characterization and Analysis, Robert Composition,” American Chemical Society
Standard for the Surface Flammability of Brady, Ed. Amer. Chem. Soc., Washington, Preprints, August 2000 National Meeting,
Carpets and Rugs (FF 1-70). DC, 2003, pp. 700-738. Symposium on Fire and Polymers, Symp.
6 Huggett, C., “Estimation of Rate of Heat 12 Finley, G., Janssens, M.L., and Hirschler, Chair: G.L. Nelson and C. Wilkie,
Release by Means of Oxygen M.M., “Room Fire Testing – Recent Washington, DC.
Experiences and Implications,”
level.24 Once the fire flashed over the exterior windows located in each eleva- oped to flashover conditions on the new
side station, it quickly enveloped the tor lobby. The fire did not reach the 29th furniture being stored in the ballroom as
deli restaurant, feeding on the com- floor because of an architectural detail well as on the textile wall material and
bustible interior finishes and furnishings that deflected the flame out and away foam-insulated movable partitions lining
in the restaurant. The deli restaurant from the lobby windows. the walls of the ballroom. The com-
then flashed over, and the fire spread The Las Vegas Hilton Hotel fire and bustible ceiling in the foyer also con-
into and along the length of the casino, other less-publicized fires involving tex- tributed to the fire development.
which was roughly the size of a football tile materials motivated the textile indus- With the exception of the Las Vegas
field. The fire was confined to the casino try to sponsor research at the University Hilton Hotel fire leading to the develop-
level, but 85 people died as a result of of California, Berkeley, to evaluate how ment of the room fire test method for
this fire, with approximately 68 of the well the tunnel test predicts the perfor- textile wall coverings, the hotel fires of
victims located on the upper floors of mance of textile wall coverings.26 As a the 1980s did not inspire significant
the high-rise portion of the building result of this research project, a room changes to interior finish requirements
above the casino. fire test method for textile wall coverings in the building regulations. Instead,
Three months after the MGM Grand was developed. This room fire test these fires motivated the widespread use
Hotel fire, the Las Vegas Hilton Hotel25 method was adopted as UBC Standard of automatic sprinkler protection in
suffered a devastating fire that killed 8 42-2 in 1988 and is also currently desig- high-rise hotels and other residential
people. This fire started in the 8th floor nated as NFPA 265, which is referenced and commercial buildings where sprin-
elevator lobby in the east wing of the by the Life Safety Code and the Interna- kler protection had not traditionally
30-story building. The walls and ceiling tional Building Code. been installed.
of this elevator lobby, as well as all the The fire at the DuPont Plaza Hotel27 in The fire at the Station nightclub in
other elevator lobbies on floors served San Juan, Puerto Rico, occurred on De- West Warwick, Rhode Island, in Febru-
by these elevators, were lined with a cember 31, 1986. This fire, which ary 2003 provides the latest extreme ex-
textile carpet material. The fire in the 8th claimed the lives of 99 people located in ample of the role of interior finish in fire
floor elevator lobby developed to the hotel’s casino, started in a ballroom development. This fire, which claimed
flashover, then spread from the 8th floor located across a covered foyer from the the lives of 100 victims and injured hun-
to the 28th floor of the building via the casino. The fire in the ballroom devel- dreds more, spread very quickly, pri-
semblies that can- The section of lining material directly behind the ignition
not yet be modeled source will be the first to ignite. The flame on this section then
accurately, such as may spread vertically and beneath the ceiling, as indicated by
melting, dripping, the orange arrows in Figure 2, as well as laterally and down-
delamination, and ward, as indicated by the black arrows in Figure 2. In general,
Xf2
warping. the upward flame spread and spread beneath a ceiling are
Consider the sce- known as wind-aided spread because the flame is spreading in
nario depicted in the same direction as the buoyant flow of gases. This wind-
Figure 2, which is aided spread is generally much faster than the lateral and
Xf1 Xp2 representative of downward spread because of the larger sections of wall and
the scenario used in ceiling being heated by the advancing flame front.
most room fire Flame spread on a fuel surface can be considered as a se-
Xfo Xp1
tests. The walls quence of ignitions, as illustrated in Figure 3. An exposure fire
and/or ceiling of an or the flame from a segment of the material that is already burn-
Xpo
enclosure are lined ing imposes a heat flux on a fuel element that has not yet ig-
with a combustible nited. The temperature of this fuel surface element increases
Figure 3. Conceptual illustration of flame interior finish mate- under the imposed heat flux. When a fuel element reaches its
spread as a sequence of ignitions. rial. A section of the ignition temperature, the flame spreads to that fuel element,
lining material is and it begins to burn. With this fuel element now burning, the
subjected to an imposed heat flux from an ignition source fire, flame grows longer and imposes a heat flux on the next fuel
which is normally selected to represent a typical incidental fire, surface element. Some materials, such as thin combustible sur-
such as a small trash receptacle fire.34 Such ignition sources are face coatings or materials adhered to noncombustible sub-
normally selected to realistically challenge the lining materials strates, burn out relatively quickly once ignited. Other materials,
but not overwhelm the performance of the lining materials. In such as some wood products, char and consequently have a
room fire tests, such ignition sources are typically located near burning rate that decreases with time. Under some exposure
the corner of two walls because this represents a realistic “worst- conditions, such materials may not burn with sufficient intensity
case” ignition scenario, as noted in the 1950 FM room fire tests. long enough to ignite subsequent fuel elements.
Upward flame spread on a fuel surface generally requires two
conditions to occur:
1. The flame from the currently burning area of the fuel sur-
face must extend beyond the burning area to expose the
adjacent area to a heat flux high enough to ignite the adja-
cent area; and
To satisfy the first condition, the heat release rate per unit
area of the burning fuel must be high enough to cause the
flame to extend beyond the burning area. In general, the length
of a flame along a vertical burning surface will be proportional
to its heat release rate per unit width,35 which in turn is propor-
tional to the heat release rate per unit area. This can be ex-
pressed as:
( ) ( )
n n
x f = k f Q˙ ′ = k f Q˙ ′′x p (1)
(Q˙ ′′)
n
(2)
kf 1− n
>1
x p
Expressed differently, this also establishes the minimum heat- burning duration for the second condition would be the period
release rate per unit area for upward or wind-aided flame of time during which the heat release-rate per unit area causes
spread to occur: the flame length to exceed the pyrolysis zone length. In general,
1/ n the burning duration can be evaluated as:
x1p− n (3)
Q′′ >
˙
Q′′ m ′′∆Hc m ′′L (4)
kf tb = = =
′′ , p ( ∆Hc / L) q˙net
Q˙ ′′ q˙net ′′ , p
For example, Cleary and Quintiere36 have suggested that
kf =0.01 m2/kW and n=1 can be used to represent the flame where Q′′ is the energy content of the fuel surface per unit
length relationship, with a linear relationship between the flame area (kJ/m2), Q˙ ′′ is the average heat-release rate per unit area
length and the pyrolysis length. Based on these values, a heat (kW/m2), m ′′ is the combustible mass per unit area (kg/m2), L is
release rate per unit area of Q˙ ′′ ≥ 100 kW/m2 would be needed the effective heat of gasification of the combustible mass
for upward flame spread to occur. Tu and Quintiere37 have ′′ , p is the net heat flux to the fuel surface
(kJ/kg), and q˙net
also suggested that kf =0.067 m5/3/kW2/3 and n=2/3 are appropri- (kW/m2) in the pyrolysis zone. For thermally thick surfaces, the
ate values to represent this flame-length relationship. Based time to ignition is generally represented, for a constant net heat
on these values, the minimum heat-release rate per unit area flux at the fuel surface, as:
needed for upward flame spread would be Q˙ ′′ ≥ 58 x p kW/m2. 2
Note that this value is a function of the pyrolysis zone length, π ∆T (5)
tig = kρc ig
with larger heat-release rates per unit area needed to sustain up- 4 ′′ , f
q˙net
ward flame spread for longer pyrolysis zone lengths. This is one
reason why some fires may burn out after spreading some dis- where the product kρc is the thermal inertia of the solid sur-
tance up a wall. These relations are shown in Figure 4. face ((kW/m2K)2s), ∆Tigis the difference between the ignition
To satisfy the second condition, the burning duration, tb , of the temperature and the initial surface temperature (K), and q˙net ′′ , f
burning region must be greater than the ignition time, ti g , of the is the net heat flux to the fuel surface in the flame region
exposed region. More specifically, the burning duration should be (kW/m2). In general, the net heat flux terms in Equations 4 and
evaluated as the period of time that the burning region burns at a 5 will not be equal to each other, but for this discussion they are
rate sufficient to achieve the first condition. In other words, the assumed to be proportional to each other, i.e., q˙net ′′ , f = χ p q˙net
′′ , p .
In general, the net heat flux in the pyrolysis zone is expected to
be greater than the net heat flux in the flame zone, in which case
the proportionality factor, χ p , will have a value of less than one.
The burning duration expressed by Equation 4 can be equated
with the ignition time expressed by Equation 5 to determine the
minimum flame heat flux needed to cause ignition before burn-
out occurs. After some manipulation, this can be expressed as:
′′ , f >
q˙net
(
π kρc∆Tig
2
) (6)
4 χ p ( m ′′L)
Equation 6 would be difficult to evaluate quantitatively, par-
ticularly since the value of the proportionality factor is not
known. Nonetheless, Equation 6 is useful for a number of
reasons. First, it demonstrates that there is expected to be a
minimum heat flux for flame spread for materials where fuel
burnout is significant. Thus, it is important that such materials
be tested under exposure conditions sufficient to exceed this
minimum heat flux; otherwise, anomalous test results can oc-
cur when compared with actual field performance. This be-
havior has been observed for textile wall coverings, as noted
above. Second, Equation 6 shows how different material prop-
erties are expected to influence the minimum heat flux for
flame spread. Higher thermal inertias and larger ignition tem-
peratures would be expected to increase the minimum heat
flux for flame spread, while more fuel per unit area would be
expected to lower it. Third, Equation 6 demonstrates the criti-
cal nature of flame spread, where a slight change in the heat
flux or in the combustible mass per unit area (e.g., another
coat of paint) can spell the difference between burnout and
flame propagation. Finally, Equation 6 also shows that pre-
heating of a fuel surface will tend to decrease the minimum
heat flux for flame spread by decreasing the temperature rise
needed to ignite the surface.
The relatively simple theoretical fluence flame spread on wall and ceiling ber of complex interrelated processes,
analysis presented here has identified a finishes include: even for relatively simple geometries,
number of material properties and envi- • The heat flux imposed on the fuel homogeneous fuels, and well-character-
ronmental conditions that are expected surface by an exposure fire. This will in- ized exposure conditions. It is for this
to influence flame spread on interior fluence the burning rate and the size of reason that individual fire tests of inte-
wall and ceiling finishes. The material the fuel area first ignited, and conse- rior finish materials may not be able to
properties include: quently the flame length extending from characterize their performance under a
• The thermal inertia of the material. this area and exposing adjacent fuel ele- full range of field-use conditions.
As shown in Equation 5, the thermal in- ments. By influencing the burning rate
ertia of a material is directly proportional of the fuel, this parameter also influ- PROPOSED EVALUATION
to the ignition time. Low-density materi- ences the burning duration of this area. METHODOLOGY
als tend to also have low thermal con- Ironically, a higher imposed heat flux
ductivities and consequently have very may cause earlier burnout that a lower In 1978, Williamson and coworkers34
low thermal inertias. This is the primary heat flux and consequently not cause suggested that “a standard room fire test
reason why flame spread can be very flame spread under some conditions that could be used both as a development
rapid on exposed foam plastic products. a lower heat does. tool and a performance evaluation
• The ignition temperature of the ma- • The heat flux imposed by burning method until such time as a series of
terial. Although Equation 5 shows that surface flames on adjacent fuel ele- smaller, less expensive tests has been
the time to ignition varies with the ments. This will influence the time to ig- proven. Even then, new materials and
square of the ignition temperature rise, nition of these adjacent fuel surface ele- systems which are different in principle
ignition temperatures for most building ments and consequently the speed of from those already validated for small-
materials fall within a relatively small flame spread. scale fire tests would still require the
range, so differences in ignition temper- • The gas temperatures within the en- full-scale test to show the applicability
atures among materials do not affect closure. The accumulation of hot gases of small-scale tests.” This is similar in
flame spread nearly as much as the or- beneath the ceiling as a result of a fire concept to the evaluation methodology
der of magnitude differences in thermal causes preheating of the fuel surfaces in proposed here.
inertia do. contact with the hot gases. As these sur- The evaluation methodology pro-
• The combustible mass per unit area faces heat up, the temperature rise posed here includes a preliminary
of the material. This parameter is most needed to cause ignition decreases, re- screening/qualification step, followed by
significant for relatively thin coatings sulting in shorter ignition times and a more detailed analysis step. In the
and materials on noncombustible sub- lower minimum heat fluxes for fire screening/qualification step, the flamma-
strates, such as painted or unpainted pa- spread. This effect will be most pro- bility characteristics of a material are
per facers on gypsum wallboard or tex- nounced for materials that are good in- evaluated using a quantitative small-
tile wall coverings adhered to gypsum sulators, such as foam plastics and other scale fire test method, such as the Cone
wallboard, but is also important for ma- low-density materials, because their Calorimeter or the FM Fire Propagation
terials that tend to char. Such materials good insulating qualities will result in Apparatus. One of three outcomes will
are more likely to burn out locally and higher gas temperatures as well as occur, depending on the performance of
not spread a fire than materials with higher surface temperatures than more the material in the bench-scale test.
more combustible mass per unit area. conductive materials will. These outcomes include:
• The ratio between the heat of com- Based on this analysis, it should be • the material will be screened from
bustion and the heat of gasification apparent that flame spread on interior any further consideration if it exhibits
(∆Hc / L) of the material. As demon- wall and ceiling finishes involves a num- flammability characteristics recognized
strated in Equation 4, this “combustibil-
ity ratio” is directly proportional to the
heat-release rate per unit area of a mate-
rial and consequently has an influence Good performance – Intermediate performance Poor performance –
on the flame length as well as on the to- product qualified – further testing required product screened
tal heat-release rate of the fire, which
will have an influence on the preheating Low heat release rate per Intermediate heat release High heat release rate
of fuel surfaces as well as the potential unit area (e.g., rate per unit area per unit area (e.g.,
for flame extension beyond the room of Q˙ ′′ < 65 kw / m 2 ) or Q˙ ′′ > 200 kw / m 2 )
Time to ignition similar
origin. or to burning duration or
• The heat of gasification of a mater- or
ial. While this property individually is Time to ignition much Burning characteristics Time to ignition much
not as significant as the “combustibility greater than burning that cannot be evaluated less than burning
ratio,” it does have an influence on the duration in small-scale tests duration
burning duration and consequently on (e.g., tig > 2 × tb ) (e.g., tig < 0.5tb )
the minimum heat flux for flame spread,
as demonstrated by Equation 6.
The environmental parameters that in- Figure 4. General concept for flammability testing and evaluation.
By Randy Laymon The Steiner tunnel is a furnace cham- board. Red oak propagates flames to the
Underwriters Laboratories Inc. ber that measures flame spread and end of the tunnel in 5 minutes 30 sec-
smoke development. Its prominence in onds ± 15 seconds and generates a
INTRODUCTION the fire protection community was based flame-spread index of approximately 90.
on its ability to provide cost-effective, A smoke-developed index of 100 is as-
istics of interior finish within these struc- 723,1 Test for Surface Burning Charac- EARLY HISTORY AND DEVELOPMENT
tures has played a major role in many of teristics of Building Materials, as well as
these losses, prior to the middle of the ASTM E-842 and NFPA 255.3 The initial version of the tunnel fur-
20th century, fire protection of buildings nace was developed in 1922 when Mr.
focused primarily on: 1) the prevention SUMMARY OF TEST METHOD Steiner, an engineer in UL’s Fire Protec-
of fire occurrence, 2) early detection and tion Department, assessed the effective-
warning, 3) automatic or manual extin- The Steiner tunnel is used to assess ness of a “fireproof” paint. The proto-
guishment, and 4) confinement with the comparative surface-burning charac- type test method consisted of a long
fire-resistant structural components, such teristics of building material samples wooden bench measuring approxi-
as floors, ceilings, walls and partitions, with the exposed area measuring 18 in. mately 18 in. (460 mm) in width and
columns, roofs, and doors. (460 mm) wide by 24 ft. (7.3 m) long, up depth and 16 ft. (4.9 meters) long with a
The occurrence of major fires in indi- to a thickness of approximately 5-6 in. noncombustible top. The interior of the
vidual buildings, distinguished by the (125-150 mm). The test is conducted tunnel was coated with the paint under
rapid flame spread of interior finish mate- with the sample mounted in the “ceil- investigation and ignited with a given
rials, aroused public concern and demon- ing” position of an enclosed tunnel fur- quantity of wood at one end. The extent
strated the need to address and regulate nace measuring 18 in. (460 mm) wide of the spread of flame was compared
the burning characteristics of these mate- by 12 in. (300 mm) deep by 25 ft. long with an unpainted replica, and the flame
rials. Specific material characteristics of (7.6 m). A nominal 5000 Btu/min. (88 retardancy of the coating was thus
concern included the spread of flame kW), 4-1/2 ft. (1.4 m) flame provides an evaluated.
and the amount of heat generated and ignition source to the underside of the In the late 1920s, the development of
smoke developed. This led to the re- mounted specimen for a 10-minute du- pressure-impregnated fire-retardant lum-
search and development of various test- ration. A controlled inlet draft of 240 feet ber, in conjunction with further research
ing protocols, most of which were small, per minute (1.2 meters/second) facili- at UL, led to modifications to the test
laboratory-scale tests. However, based on tates horizontal flame propagation method in which the test sample formed
work conducted by Albert J. Steiner at throughout the test. A light and photo- the top of a 36 in. (91 mm) wide by 13
Underwriters Laboratories Inc., from the electric cell mounted in the exhaust duct in. (330 mm) deep by 23 ft. (7.0 m) long
early 1920s through the 1940s, the 25 ft. record smoke obscuration during the chamber. The use of untreated red oak
(7.6 m) long Steiner tunnel emerged as test. Flame-spread and smoke-devel- and maple flooring in this investigation
the predominant method to characterize oped indices are reported in comparison was a major factor in the selection of red
and regulate the surface-burning charac- with calibration materials of red oak oak as one of the calibration materials
teristics of interior finish materials. lumber and inorganic reinforced cement for the test method.
255 in 1955. It was adopted by ANSI in promoting more-consistent results by thereby increasing the flame spread in-
1963 as American National Standard A2.5. various laboratories. Recently, a more dex; or the material may sag or drop to
Although the tunnel test provides for comprehensive approach toward the the furnace floor, which may impede
a Classification protocol and is recog- standardization of mounting practices further flame propagation.
nized by standards-developing organiza- has led to the development of ASTM • Thermoplastic materials may be dif-
tions, it does not establish limitations for E2231, Standard Practice for Specimen ficult to evaluate in this as well as other
building codes. The intent of the test Preparation and Mounting of Pipe and standardized fire test procedures and re-
method is to provide a tool for those Duct Insulation Materials to Assess Sur- quire careful interpretation of the test re-
with the responsibility of regulating ma- face-Burning Characteristics. Similar sults. These materials tend to melt and
terials used as interior finish in build- practices for other material types are drip to the floor of the furnace, and may
ings. Widespread reliance on the tunnel currently being considered under the generate potentially misleadingly low
test method by the regulatory commu- ASTM standard-development process. flame-spread values.
nity as an acceptable criterion to assess • Some research has indicated that
interior finish and other materials has ADVANTAGES AND LIMITATIONS some types of thermosetting cellular
been in place for decades. Factors that plastics yielding low flame-spread val-
have contributed to this reliance include: • Certain relationships have been ob- ues may generate flameover conditions
• Support by standards-developing served between Steiner tunnel test re- during certain large-scale room test sce-
organizations, including UL, ASTM, and sults and performance of some materials narios, when utilizing igniting sources of
NFPA. during building fires.2 sufficient heat flux levels.4
• The test method utilizes a large • The test method provides for a real- No single test method provides the to-
sample size and an ignition source rep- istic fire scenario by presenting a sample tal information necessary to completely
resentative of a moderately developed of sufficient size to allow for progressive evaluate the potential for fire develop-
fire scenario. surface burning over a large exposed ment in a building, yet each makes
• The ability of the test method to area. some contribution to the total body of
characterize both high and low flame • A wide range of materials may be knowledge required. The Steiner tunnel
spread materials. tested, including composite construc- test method is the most extensively used
• Research that demonstrates a rela- tions, coatings, faced products, loose-fill and referenced test method to assess
tionship between tunnel test results and materials, sandwich panels, and many flammability of interior finish materials.
certain large-scale test protocols.4 others. UL currently classifies over thirty The results form a basic element in reg-
Interior finish requirements are cur- different product types in accordance ulation of these materials by providing
rently defined in Chapter 8 of the Inter- with the test method. an identification system for inspection
national Building Code 5 and Chapter 10 • The test method provides a means and enforcement authorities. ▲
of NFPA 5000, Building Construction to discriminate products yielding a wide
and Safety Code.6 Interior finishes are range of flame-spread and smoke-devel- Randy Laymon with Underwriters
grouped in the following classes in ac- oped characteristics, allowing for the de- Laboratories Inc.
cordance with their flame-spread and velopment of codes and standards.
smoke-developed indices. • Some research conducted has REFERENCES
Class A: Flame Spread 0-25; Smoke demonstrated useful relationships be-
Developed 0-450. tween Steiner tunnel flame-spread val- 1 UL723, Test for Surface-Burning
Class B: Flame Spread 26-75; Smoke ues and fire performance of materials in Characteristics of Building Materials,
Developed 0-450. large-scale corner configurations using a Underwriters Laboratories, Inc.,
Class C: Flame Spread 76-200; Smoke 20-pound ignition source wood crib.4 Northbrook, IL, 2001.
Developed 0-450. • The horizontal specimen orientation 2 ASTM E-84, Standard Test Method for
Prior to 1960, the tunnel test method places some limitation on the type of Surface-Burning Characteristics of
was used primarily for the evaluation of material that can be realistically Building Materials, American Society for
the surface-burning characteristics of ho- mounted. Depending on the particular Testing and Materials, West
mogenous compositions of ceiling and material being tested, specimens requir- Conshohocken, PA, 2003.
wall finishes, such as acoustical tiles, ing additional support may yield low 3 NFPA 255, Standard Method of Test for
wall coverings, coatings, and various flame-spread values due to the support- Surface-Burning Characteristics of
types of decorative paneling. Through ing material restricting flame propaga- Building Materials, National Fire Protection
inclusion of the Guide to Mounting tion or high-flame spread values be- Association, Inc., Quincy, MA, 2000.
Methods Appendix in the late 1960s, the cause the additional support retains the 4 “Flammability Studies of Cellular Plastics
method was expanded to include the specimen in the ceiling position rather and Other Building Materials Used For
evaluation of composites and assem- than allowing the specimen to fall away Interior Finishes,” Underwriters
blies. Sample mounting techniques can from the area of flame impingement. Laboratories Inc., Northbrook, IL, 1975
have a significant influence on the fire- • Some materials, such as faced com- 5 International Building Code, International
performance indices developed by the posite samples, may delaminate during Code Council, Falls Church, VA, 2003.
test method. While the Appendix is not testing, which may result in one of two 6 NFPA 5000, Building Construction and
considered a mandatory part of the stan- possible responses: the material may ex- Safety Code, National Fire Protection
dard, the Guide has proven useful in pose two or more surfaces to the flame, Association, Quincy, MA, 2003.
Publications Catalog
The Code Official’s Guide to Performance-Based Evaluation of Fire Safety
Design Review In a comprehensive treatment of the subject unavailable else-
The use of performance-based design is becoming more where, this book describes in detail the applications of hazard
prevalent as new performance-based codes and guidelines and risk analysis to fire safety, going on to developing and
are developed and adopted. This can create challenges for applying quantification methods. It also gives an explanation
enforcement officials or other stakeholders if they do not in quantitative terms of improvements in fire safety in associa-
have a strong background in performance-based design or if tion with the costs that are expended in their achievement.
their resources are already stretched thin. This guide identifies Furthermore, a quantitative approach is applied to major fire
the types of items that an enforcement official should con- and explosion disasters to demonstrate crucial faults and
sider when reviewing a performance-based design. The con- events. ISBN 0-471-49382-1, 462 pages.
cepts identified in this guide are applicable to performance- $136 SFPE Members/$160 Nonmembers
based fire protection designs that are prepared to meet
performance-based codes, designs that are prepared as equiv-
alencies to prescriptive-based code requirements, and designs
that are intended to meet objectives that exceed those con-
Performance-Based Building Design Concepts:
tained in a code or standard (e.g., business interruption, pro- A Companion Document to the ICC PC
tection of contents, etc.) ISBN 1-58001-202-7, 113 pages. This companion document to the ICC Performance Code for
Buildings and Facilities (ICC PC) leads the reader along a
$40.00 SFPE Members/$49.00 Nonmembers
path from a discussion of the origins of performance-based
building codes and the background behind the ICC PC to dis-
cussion of the basics of performance design. It was designed
SFPE Engineering Guide to Fire Exposures to to assist the reader in learning more about performance, ap-
Structural Elements plying performance concepts appropriately, and knowing
Designing fire resistance of structures in a performance envi- what to look for in the review of designs that have been de-
ronment is a three-step process: defining the fire boundary veloped using the ICC PC.
conditions that the structure will be exposed to, and deter-
mining its thermal and then structural response. SFPE’s The ten chapters cover history and overview, regulatory sys-
newest engineering guide provides the information necessary tems, understanding administrative issues, risk characteriza-
to the fire protection engineer to aid in the first important step tion and performance concepts, fire, structural design, pedes-
of this process: estimating the fire boundary conditions. De- trian movement and safety, building envelope, maintaining
sign methods, their limitations, and examples of their applica- building performance throughout a building’s life cycle, and
tion are provided for fully developed exposure fires and for prospects for the future. ISBN 1-58001-182-9, 300 pages.
fire plumes, the two fire exposures of most importance in the $70.00 SFPE Members/$87.00 Nonmembers
design of structures for fire, 146 pages.
$40.00 SFPE Members/$80 Nonmembers
A Balanced Approach
W hat is the relation-
ship between a fire
detection and
alarm system and the interior
finish of a space? Fire protec-
In this article, interior finish is used as
a variable; see how fire detection and
alarm systems must change to maintain
Class B (flame spread 26-75; smoke de-
veloped 0-450)1. Class A (flame spread
0-25; smoke developed 0-450) materials
balance when some other system (inte- are required in Assembly occupancies
tion is not any one system rior finish) changes. Though the link is while Class C (flame spread 76-200;
not a strong one, it is useful to demon- smoke developed 0-450) materials are
but a balance between many strate how different systems interact with permitted in one- and two-family
systems and concepts. This each other. How does a fire detection dwelling units.
article looks at the role of fire and alarm system affect the selection of
interior finishes? What effect does inte- The restrictions on interior finish are
detection and alarm systems rior finish have on the design of a fire based, in part, on:
as a part of a balanced fire detection and alarm system? • the expected/permitted occupant
protection system. From an load
BALANCED PREVENTION AND • occupant mobility
analysis point of view, when PROTECTION • the maximum permitted travel dis-
one facet of fire protection tance
changes, the performance of Model building and fire codes contain • the degree of compartmentation
specific limitations on interior finish. • the presence or lack of automatic
other systems may be affect- Some occupancies or use groups are suppression systems
ed. From a design perspec- permitted to have combustible interior • the presence or lack of automatic
finishes with higher flame spread and detection and alarm systems
tive, if the expected perfor- smoke production characteristics than The above list can be transformed,
mance of one system other occupancies or use groups. For placing any one of the bullet items at
changes, then others may be example, the 2000 International Build- the top as the dependent variable. For
ing Code (IBC) restricts the flame spread example:
required to change in order to and smoke production ratings of interior The requirements for fire detection
maintain the expected level of finish used in the egress components of and alarm in a building are based, in
prevention or protection. unsprinklered apartment buildings to part, on:
Control Control
Control
Heat-Energy Source-Fuel
Fuel
Source(s) Interactions
Manage Fire Manage Exposed
• the flame spread and smoke poten- automatic suppression, fire detection The relationships and interdependen-
tial of the interior finish and alarm system improvements by cies among these various parts of bal-
• the expected/permitted occupant themselves are not likely to permit anced fire protection are complex.
load changes in interior finish, particularly in Codes typically contain one or two sim-
• occupant mobility egress paths. However, by improving ple, reliable, proven combinations of
• the maximum permitted travel dis- fire detection and several other facets of systems to achieve a fire safety objec-
tance protection, such as decreased travel dis- tive. Other possible solutions may also
• the degree of compartmentation tance, reduced occupant load, more be possible, but may incorporate more
• the presence or lack of automatic than two egress paths from a space, and complex combinations and relation-
suppression systems improved containment of fire and ships. NFPA 550, Guide to the Fire
smoke, it may be possible to use some Safety Concepts Tree, is a useful tool for
Building and fire codes specify certain combustible finishes. For instance, it examining these relationships and their
combinations of the various systems may be acceptable to use wood panel- weighted impact on fire safety.2 The Fire
necessary to meet the objective of the ing as a wainscoting in limited horizon- Safety Concepts Tree is an event tree us-
code. For example, in the 2000 IBC, As- tal exit access corridors. Or in rooms ing logical AND and OR gates to relate
sembly occupancies are permitted to (not part of the egress system) that various combinations of subevents that
have Class B interior finish in egress might normally require Class B or better lead to the top level successful event.
components when sprinkler protection interior finish, supplementary fire detec- Figure 1 is the top level of the Fire
is provided. When there is no sprinkler tion that closes fire and smoke doors Safety Concepts Tree.
protection, the interior finish is limited and initiates smoke control may allow Note that the top-level Fire Safety
to Class A. The code does not list any the use of Class C finishes. Objective is connected by an OR gate
similar tradeoffs for interior finish (circle with a plus sign in it) to the
when an automatic fire detection and subevents Prevent Fire Ignition and
alarm system is incorporated. A per- Manage Fire Impact. If probabilities
formance based analysis/design may are calculated or designated for the
permit greater latitude in combining subevents, then the OR gate dic-
various degrees of each protection or tates that the probabilities be added
prevention system. Unlike complete together to determine the probabil-
Manage exposed
Go to
A
Go to
Figure 2. Manage Exposed Branch of the Fire Safety Concepts Tree A
ity of the parent event. That is why the that success is also dependent on other events that might contain detection
OR gate symbol is a circle with a plus events taking place. For instance, fire subevents are shown in green.
sign in it. In other parts of the Fire Safety protection engineers regularly Manage
Concepts Tree AND gates (circle with an Fire Impact, by Moving the Exposed. In PERFORMANCE EFFECTS
X or a dot in it) require all subevents to addition to detecting the fire, it must be
occur. Thus, the probabilities are multi- signaled to occupants and emergency Interior finish has several direct effects
plied to determine the probability of the forces, adequate egress means must be on the design and performance of fire
top-level event. provided, and a safe destination is also alarm systems. The most obvious is on
The entire Fire Safety Concepts Tree is needed. the selection and performance of audi-
too large to reproduce in this short arti- Fire detection is also a part of several ble signals. Building materials such as
cle. However, examination of the re- other Fire Safety Concepts Tree events, glass, carpet, and acoustical tiles are
mainder of the tree shows that paths though not specifically listed. For ex- tested to determine their sound absorp-
containing events related to interior fin- ample, instead of Moving the Exposed, a tion coefficients at different frequencies.3
ish fall under both the Prevent Fire Igni- design might include the event Defend A particular drop ceiling panel may have
tion event and the Manage Fire event. Exposed in Place. (See Figure 2.) One a relatively flat absorption curve. That is,
Fire detection events are found only un- element required to accomplish this is its absorption coefficients are about the
der paths leading to Manage Fire Im- to maintain a tenable environment. In same for low, middle, and high frequen-
pact. In Figure 1, the red event boxes the Fire Safety Concepts Tree, this cies. Sound that is not absorbed is re-
contain paths that eventually lead down event is titled Maintain Essential Envi- flected back into the room or space. Ma-
to a detection event box. The yellow ronment. The tree does not show terials such as glass and gypsum board
events contain paths that relate to inte- subevents required for that event. In tend to have higher absorption coeffi-
rior finish. The purple box leads to both some cases, it is useful to add addi- cients at the lower frequencies and
fire detection and interior finish events. tional subevents to understand what is lower absorption at the higher frequen-
The Fire Safety Concepts Tree explic- required for an event to be successful. cies. Thus, they tend to reflect more of
itly lists three Detect Fire events that lead One subpath might include fire detec- the high-frequency sound. Carpeting
upwards in the tree to the Manage Fire tion AND closing dampers. Another and some acoustical tiles absorb high
Impact event box. However, they all subpath might be fire detection AND frequencies much more efficiently than
connect through AND gates. This means pressurization of a space. In Figure 2, lower frequencies.
B R A I N T E A S E R
Sales
Offices
HEADQUARTERS
Yahtzee® is a game played with five six-sided dice. Players take turns TERRY TANKER Publisher
rolling the dice, trying to get certain combinations of 1s, 2s, 3s, etc. Players 1300 East 9th Street
Cleveland, OH 44114-1503
may roll the dice up to three times during each turn and are permitted to 216.696.7000, ext. 9721
set aside any subset of the five dice after each roll. fax 216.696.3432
ttanker@penton.com
A player rolls the following combination on the first roll: 2, 2, 3, 4, 5. If
NORTHEAST
the player keeps the 2, 3, 4 & 5, what is the probability of obtaining a TOM CORCORAN District Manager
“large straight” (the numbers of all five dice fall in a consecutive sequence) 929 Copes Lane
in the two remaining rolls? West Chestor, PA 19380
610.429.9848
fax 610.429.1120
Solution to last issue’s brainteaser tomcorcoran@penton.com
Substitute a unique integer from 1 to 9 for each different letter in the NORTH CENTRAL
subtraction problem below. JOE DAHLHEIMER District Manager
1300 East 9th Street
FI RE Cleveland, OH 44114-1503
-HE A T 216.696.7000, ext. 9279
OUT fax 216.696.3432
jdahlheimer@penton.com
There are at least three solutions:
CENTRAL / WEST
2598 AMY COLLINS District Manager
-1834 3240 Shadyview Lane North
Plymouth, MN 55447
764 763.404.3829
fax 763.404.3830
6198 acollins@penton.com
-5824
SOUTHEAST
374
TOM GRAVES District Manager
9126 1180 Pin Oak Court
-8673 Cumming, GA 30041
770.205.1870
453 fax 770.205.1872
tgraves@penton.com
B
eginning with the publication funding to analyze the building failures of a sound business plan to attract fund-
of the SFPE Handbook of Fire that occurred on September 11, 2001, ing to support fire research.
Protection Engineering and this funding increase may be only SFPE has also directly supported re-
continuing with the publication of per- temporary. search through its Educational and Sci-
formance-based codes and several Fire protection engineering is the entific Foundation. The Educational and
engineering design guides, the fire bridge between fire research and the Scientific Foundation has historically
protection engineering profession has built environment. A fundamental tenet supported a number of fire research pro-
matured tremendously over the past of engineering is to do the best job pos- jects, typically conducted at academic in-
decade-and-a-half. Underpinning this sible with the information that is avail- stitutions. Funding for this support has
advancement is a foundation of fire able, and despite declining research pro- come from contributions from SFPE
research. However, a great deal of this ductivity, fire protection engineers will members and chapters. Additionally, the
research was conducted in the 1950s continue to apply the knowledge avail- Foundation is currently exploring mech-
through the mid-1980s. While quality able to protect people and property anisms to expand its support.
research continues, significantly less from fire. When faced with a less-than- While relatively modest in magnitude,
funding is available to support this total understanding in an area of prac- the Educational and Scientific Founda-
research, and hence, much less is tice, engineers typically compensate by tion made valuable contributions since its
being conducted now than before. building in conservatism. This excess 1979 inception, and this support has the
Before proceeding further, it is useful conservatism translates into higher de- potential to grow. A sound foundation of
to define the term “research” as used sign costs, which are ultimately passed fire research allows fire protection engi-
here. “Research” refers to a scientific in- on to the public through higher overall neers to provide the best possible service
vestigation which has results that can be costs of products and services. With an to the public, clients, and employers.