IOM1359
IOM1359
Trailblazer®
Air-Cooled Scroll Chillers
Model AGZ, F-Vintage
30 to 245 Tons (100 to 860 kW)
R-32 Refrigerant
60 Hz
Table of Contents
Nomenclature
WARNING - flammable refrigerant
present
No. Description
1 A = Air-Cooled
2 G = Global WARNING - A2L low-burning
velocity refrigerant present
3 Z = Scroll Compressor
4 Number of Fans
5 Design Vintage
6 Compressor Code
Installation Inspection
Check all items carefully against the bill of lading. Inspect
all units for damage upon arrival. Report shipping damage
Operating Limits and file a claim with the carrier. Check the unit nameplate
before unloading, making certain it matches with the power
Table 1: Operating/Standby Limits supply available. Daikin Applied is not responsible for physical
damage after the unit leaves the factory.
Maximum standby ambient temperature 130°F (54°C)
Maximum operating ambient temperature 105°F (41°C)
Maximum operating ambient temperature with Lifting Guidance
optional high ambient package (see information 125°F (52°C) Daikin Applied equipment is designed to withstand the loads of
under High Ambient Operation)
the lifting and rigging process resulting from ASME Standard
Minimum operating ambient temperature P30.1 - Planning for Load Handling Activities or equivalent.
32°F (0°C)
(standard control)
Lifting guidance is intended for installations of newly delivered
Minimum operating ambient temperature (with equipment. If moving previously installed equipment for re-
-4°F (-20°C)
optional low-ambient control)
location or disposal, consideration should be given to unit
40°F to 70°F condition. Equipment should also be drained as unit weight
Leaving chilled water temperature
(4°C to 21°C)
and center of gravity values do not reflect the addition of water
Leaving chilled fluid temperatures (with glycol) - for lifting.
Note that in cases of high ambient temperature,
the lowest leaving water temperature settings 15°F to 70°F
may be outside of the chiller operating (-9°C to 21°C)
DANGER
envelope; consult Daikin Tools to ensure chiller Improper rigging, lifting, or moving of a unit can result in unit
is capable of the required lift. damage, property damage, severe personal injury or death.
Operating chilled water delta-T range
6°F to 20°F See the as-designed, certified dimensioned drawings included
(3.3°C to 11.1°C) in the job submittal for the weights and center of gravity of the
Maximum evaporator operating inlet fluid
81°F (27°C)
unit. If the drawings are not available, consult the local Daikin
temperature Applied sales office for assistance.
Maximum evaporator non-operating inlet fluid
temperature
100°F (38°C) Installation is to be performed only by qualified personnel who
are familiar with local codes and regulations, and experienced
with this type of equipment. Lifting equipment and mechanisms
Nameplates must be determined by the Lifting Director per the current
version of ASME Standard P30.1 or equivalent and must be
The unit nameplate is located on the exterior of the Unit Power suited for the load capacity.
Panel. Both the Model No. and Serial No. are located on the
Daikin Applied is not a licensed nor certified rigging specialist.
unit nameplate; the Serial No. is unique to the unit. These
Therefore it is the customer’s responsibility to consult a
numbers should be used to identify the unit for service, parts,
certified rigging contractor to rig, lift, and move components
or warranty questions. This plate also has the unit refrigerant
and subcomponents properly and safely as needed.
charge and electrical ratings. Evaporator data plate is under
insulation and contains the serial number. Compressor CAUTION
nameplate is located on each compressor and gives pertinent
electrical information. Forklifts may not be used to lift or move Trailblazer units as
the method may result in unit damage.
WARNING
Installation is to be performed by qualified personnel who are CAUTION
familiar with local codes and regulations. When around sharp edges, wear appropriate Personal
Protective Equipment (PPE), such as gloves, protective
CAUTION clothing, foot wear, eye protection, etc. to prevent personal
injury.
When around sharp edges, wear appropriate Personal
Protective Equipment (PPE), such as gloves, protective
clothing, foot wear, eye protection etc. to prevent personal
injury.
WARNING
The lifting angle must not go beyond 30 degrees from vertical
or the unit can become unstable which may result in unit
damage, property damage, severe personal injury, or death.
CAUTION
Lifting mechanisms must not make contact with the unit
beyond the lifting bracket. Extreme care must be used when
rigging the unit to prevent damage to the control panels, unit
handles, unit piping, and unit frame.
Lifting Points
Lifting points are predetermined by design. When lifting,
all factory installed lifting brackets must be used. Figure 3
illustrates typical 8 point lifting configuration, with four lifting
points on each side of the unit. The unit must remain level
throughout the entire lifting event. Level is defined as one end
being no more than 0.25” per foot of unit length to the opposite
end.
WARNING
Be aware that the center of gravity may not necessarily be in
the geometric center of the unit. No additional items can be
added to a lift with the unit as it may affect the center of gravity
and cause unit damage, property damage, or severe personal
injury or death. Refer to as-designed, certified drawings for
weight, center of gravity location and details specific to unit
configuration.
Figure 3: Lifting Points Locations 6. Long term storage in humid environments may cause
condensate corrosion on steel surfaces. Consider adding
a desiccant material to alleviate corrosion concerns.
When the unit is being tied down for transit, the maximum
allowable attachment angle from the vertical is 30 degrees in
the opposite direction of lifting. Shimming of the unit under the
lifting brackets or tie-down points must be used to ensure even
contact along the length of the base rail.
CAUTION
If the temperature of where the chiller is located is expected to
exceed 130°F (54.4°C), then the refrigerant must be removed.
It is necessary to observe some precautions during storage.
• Do not keep the machine near a heat source and/or open
flame.
• Humid environments may cause condensate corrosion on
steel surfaces. Consider adding a desiccant material to
alleviate corrosion concerns.
• For units previously installed, ensure water has been
drained from the unit or sufficient glycol has been added if
ambient temperature may be lower than 40°F (4.4°C).
For additional tasks required, contact a Daikin Applied service
Transit and Temporary Storage representative.
If the unit is stored for an intermediate period before installation
or moved to a different location, take these additional
precautions:
1. Support the unit well along the length of the base rail.
2. Level the unit (no twists or uneven ground surface).
3. Provide proper drainage around the unit to prevent
flooding of the equipment.
4. Provide adequate protection from vandalism, mechanical
contact, etc.
5. Securely close the doors and lock the handles.
Mounting
The inside of the base rail is open to allow access for
securing mounting bolts, etc. Refer to the as-built submittal
drawings provided by a Daikin Applied sales representative for
configuration-specific details.
All compressor bolts, rubber grommets, and fasteners should
be left in place on the base plate as shown in Figure 5. None of
these fasteners are considered to be ‘temporary shipping bolts.
Operational Spacing Requirements
Sufficient clearance must be maintained between the unit
Figure 5: Compressor Base Plate Mounting and adjacent walls or other units to allow the required unit
air flow to reach the coils. Failure to do so will result in a
capacity reduction and an increase in power consumption.
No obstructions are allowed above the unit at any height. The
clearance requirements shown are a general guideline and
cannot account for all scenarios. Such factors as prevailing
winds, additional equipment within the space, design outdoor
air temperature, and numerous other factors may require more
clearance than what is shown. Additional clearances may be
required under certain circumstances.
CAUTION
Unit performance may be impacted if the operational
clearance is not sufficient.
Water Flow Limitations Water systems should be cleaned and flushed prior to chiller
installation. Water testing and treatment should be verified
during initial chiller installation/commissioning and maintained
Constant Evaporator Flow on a continuous basis by water treatment professionals (see
The evaporator flow rates and pressure drops shown on page Limited Product Warranty).
16 for various system designs. The maximum flow rate and
pressure drop are based on a 6°F temperature drop. Flow CAUTION
rates above the maximum values will result in unacceptable The improper use of detergents, chemicals, and additives
pressure drops and can cause excessive erosion, potentially in the chiller system water may adversely affect chiller
leading to failure. performance and potentially lead to repair costs not covered
The minimum flow and pressure drop is based on a full load by warranty. Any decision to use these products is at the
evaporator temperature drop of 20°F. Evaporator flow rates discretion of the owner/occupant/operator/user as such they
below the minimum values can result in laminar flow causing assume full liability/responsibility for any damage that may
low pressure alarms, scaling and poor temperature control. occur due to their use.
There is also a set of switch contacts on the switch that can Condenser Coil Options and Coating
be used for an indicator light or an alarm to indicate when a
“no flow” condition exists. Freeze protect any flow switch that Considerations
is installed outdoors. Differential pressure switches are not The standard coils on the Trailblazer chiller are an all aluminum
recommended for outdoor installation. They can freeze and not alloy microchannel design with a series of flat tubes containing
indicate a no-flow conditions. multiple, parallel flow microchannels layered between the
refrigerant manifolds. The microchannel coils are designed
Glycol Solutions to withstand 1000+ hour acidified synthetic sea water fog
(SWAAT) test (ASTM G85-02) at 120°F (49°C) with 0% fin loss
The use of glycol may impact system performance depending
and develop no leaks.
on its concentration and should be considered during initial
system design. When glycol is added to the chilled water Epoxy coating is a water-based extremely flexible and durable
system for freeze protection, recognize that the refrigerant polymer coating uniformly applied to all coil surfaces through
suction pressure will be lower, cooling performance less, a multi-step, submerged electrostatic coating process. Epoxy
and water side pressure drop will be higher. The reduction coated coils provide a 10,000+ hour salt spray resistance per
in performance depends upon the glycol concentration and ASTM B117-90, applied to both the coil and the coil headers.
temperature. The epoxy coated coils also receive a UV-resistant urethane
top-coat to provide superior resistance to degradation from
Test coolant with a clean, accurate glycol refractometer to
direct sunlight. This coil coating option provides the best overall
determine the freezing point.
protection against corrosive marine, industrial or combined
CAUTION atmospheric contamination to provide extended longevity.
The installed glycol level must align with the rated glycol
Table 9: Coil/Coating Selection Matrix
percentage indicated on the submitted chiller technical data
sheet. Failure to adhere to the rated glycol percentage may Combined
Non- Unpolluted
Coil Option Industrial3 Marine-
Corrosive1 Marine2
result in unit damage and loss of unit warranty. Industrial4
Standard +++ - - -
Microchannel
CAUTION Epoxy Coated +++ +++ +++ ++
Coils
Do not use an automotive-grade antifreeze. Industrial
grade glycols must be used. Automotive antifreeze contains NOTE: 1. Non-corrosive environments may be estimated
by the appearance of existing equipment in the
inhibitors which will cause plating on the copper tubes within
immediate area where the chiller is to be placed.
the chiller evaporator. The type and handling of glycol used
must be consistent with local codes. 2. Marine environments should take into
consideration proximity to the shore as well as
prevailing wind direction.
Low Ambient Operation
3. Industrial contaminants may be general or
Compressor staging is adaptively determined by system load, localized, based on the immediate source of
ambient air temperature, and other inputs to the MicroTech contamination (i.e. diesel fumes due to proximity to a
unit control. The standard minimum ambient temperature is loading dock).
32°F (0°C). A low ambient option with fan VFD allows operation 4. Combined marine-industrial are influenced by
down to -4°F (-20°C). The minimum ambient temperature proximity to shore, prevailing winds, general and local
is based on still conditions where the wind is not greater sources of contamination.
than 5 mph. Greater wind velocities will result in reduced
discharge pressure, increasing the minimum operating
ambient temperature. Field installed louvers are available and
recommended to help allow the chiller to operate effectively
down to the ambient temperature for which it was designed.
Evaporator Evaporator Model Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate
Part
GPM DP ft. l/s DP kPa GPM DP ft. l/s DP kPa GPM DP ft. l/s DP kPa
Number
332955701 ACK240DQ-58AH 36.0 1.3 2.3 4.0 72.0 7.2 4.5 21.6 144.0 32.7 9.1 97.9
332955702 ACK240DQ-66AH 42.0 1.6 2.6 4.7 84.0 7.8 5.3 23.4 168.0 34.4 10.6 102.8
332955703 ACK240DQ-78AH 54.0 2.2 3.4 6.6 108.0 9.7 6.8 29.0 216.0 40.7 13.6 121.6
332955704 ACK240DQ-86AH 60.0 2.4 3.8 7.2 120.0 10.0 7.6 30.0 240.0 41.1 15.1 122.9
332955705 ACK240DQ-98AH 66.0 2.5 4.2 7.4 132.0 9.6 8.3 28.8 264.0 38.0 16.7 113.6
332955706 ACK240DQ-106AH 72.0 2.7 4.5 8.0 144.0 10.0 9.1 29.8 288.0 38.5 18.2 114.9
332955707 ACK240DQ-114AH 66.0 2.1 4.2 6.4 132.0 7.5 8.3 22.5 264.0 28.1 16.7 84.0
332955708 ACK240DQ-122AH 78.0 2.7 4.9 8.1 156.0 9.3 9.8 27.7 312.0 33.9 19.7 101.4
332955710 ACK240DQ-138AH 84.0 2.8 5.3 8.4 168.0 8.9 10.6 26.5 336.0 30.7 21.2 91.9
332955711 ACK240DQ-142AH 90.0 3.1 5.7 9.2 180.0 9.6 11.4 28.7 360.0 33.1 22.7 98.9
332955712 ACK240DQ-154AH 96.0 3.2 6.1 9.6 192.0 9.6 12.1 28.8 360.0 28.5 22.7 85.1
332955713 ACK240DQ-170AH 108.0 3.6 6.8 10.9 216.0 10.3 13.6 30.8 360.0 24.0 22.7 71.6
332955714 ACK240DQ-194AH 120.0 4.0 7.6 11.8 240.0 10.5 15.1 31.3 360.0 19.5 22.7 58.3
332955715 ACK240DQ-210AH 138.0 4.6 8.7 13.8 276.0 11.8 17.4 35.4 360.0 17.5 22.7 52.3
NOTE: Exceeding max flow rates can cause erosion damage to the evaporator.
Each channel count has its own maximum flow rate, and the frame itself has an maximum flow rate of 360 GPM.
Evaporator Evaporator Model Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate
Part
GPM DP ft. l/s DP kPa GPM DP ft. l/s DP kPa GPM DP ft. l/s DP kPa
Number
332956501 ACK502-DQ-162 150.0 2.9 9.5 8.7 300.0 11.2 18.9 33.4 501.0 30.7 31.6 91.7
332956503 ACK502-DQ-190 168.0 3.3 10.6 9.8 336.0 11.1 21.2 33.0 528.0 25.4 33.3 76.0
332956504 ACK502-DQ-206 192.0 4.0 12.1 11.8 384.0 12.6 24.2 37.8 528.0 22.3 33.3 66.6
332956505 ACK502-DQ-234 204.0 4.2 12.9 12.5 408.0 12.1 25.7 36.2 528.0 18.5 33.3 55.3
332956506 ACK502-DQ-254 216.0 4.5 13.6 13.4 432.0 12.2 27.3 36.6 528.0 16.7 33.3 50.0
NOTE: Exceeding max flow rates can cause erosion damage to the evaporator.
Each channel count has its own maximum flow rate, and the frame itself has an maximum flow rate of 360 GPM.
Evaporator Evaporator Model Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate
Part
GPM DP ft. l/s DP kPa GPM DP ft. l/s DP kPa GPM DP ft. l/s DP kPa
Number
332956402 ACH1000DQ-166AH 240.0 3.8 15.1 11.3 480.0 13.4 30.3 40.2 801.6 35.6 50.6 106.3
332956452
332956403 ACH1000DQ-178AH 264.0 4.0 16.7 12.0 528.0 14.2 33.3 42.4 881.0 37.3 55.6 111.4
332956453
332956404 ACH1000DQ-182AH 276.0 4.2 17.4 12.6 552.0 14.8 34.8 44.2 881.0 35.7 55.6 106.8
332956454
NOTE: Exceeding max flow rates can cause erosion damage to the evaporator.
Each channel count has its own maximum flow rate, and the frame itself has an maximum flow rate of 360 GPM.
Electrical Data Power wiring connections to the chiller may be done with
either copper or aluminum wiring, provided the wire size and
count fit in the chiller lugs provided. All wiring must be done in
accordance with applicable local and national codes, including
Electrical Connection NECA/AA 10402012, Standard for Installing Aluminum Building
Trailblazer units can be ordered with either standard multi-point Wire and Cable (ANSI). Wiring within the unit is sized in
power or optional single point power connections and with accordance with the NEC®. Refer to the unit nameplate and
various disconnect and circuit breaker options. Wiring within the unit selection report for the correct electrical ratings.
the unit is sized in accordance with the NEC®. 1. The control transformer is furnished and no separate
NOTICE 115V power is required. For both single and multi-point
power connections, the control transformer is in circuit
Wiring, fuse, and wire size must be in accordance with the
#1 with control power wired from there to circuit #2. In
National Electrical Code® (NEC). The voltage to these units
multi-point power, disconnecting power to circuit #1
must be within ±10% of nameplate voltage (415V units must
disconnects control power to the unit.
have voltage within -13% and +6% of nameplate voltage) and
the voltage unbalance between phases must not exceed 2%. 2. Wire sizing supplied to the control panel shall be in
Since a 2% voltage unbalance will cause a current unbalance accordance with field wiring diagram
of 6 to 10 times the voltage unbalance per the current version 3. Single-point power supply requires a single disconnect
of the NEMA MG-1 Standard, it is most important that the to supply electrical power to the unit. This power supply
unbalance between phases be kept at a minimum. must either be fused or use a circuit breaker.
4. All field wire lug range values given unit selection report
Table 17: Power Connection Availability
apply to 75°C rated wire per NEC.
Comp. 5. Must be electrically grounded according to national and
Power Disc. Panel High Short Circuit
Circuit
Connection Swt. Current Rating local electrical codes.
Breakers
Std. Single Point Std. Std. Opt. CAUTION
Opt. Multi-Point Opt. Opt. Opt. A static discharge while handling circuit boards can cause
damage to components. Use a static strap before performing
Required field wiring varies depending on unit configuration.
any service work. Never unplug cables, circuit board terminal
See wiring diagram information. Voltage limitations are:
blocks, or power plugs while power is applied to the panel.
1. Voltage must be within 10 percent of nameplate rating.
2. Voltage imbalance not to exceed 2%. Since a 2% Panel High Short Circuit Current Rating
voltage imbalance can cause a current imbalance of 6 The AGZ F control panels are designed with High Short Circuit
to 10 times the voltage imbalance per the NEMA MG-1 Capacity (HSCCR) ratings, these ratings can vary by size and
Standard, it is important that the imbalance between voltage. Please consult the unit data plate or submittal data for
phases be kept at a minimum. the value.
DANGER
Qualified, licensed electricians must perform wiring. Electrical
shock hazard exists that can cause severe injury or death.
DANGER
LOCKOUT/TAGOUT all power sources prior to starting,
pressurizing, de-pressuring, or powering down the Chiller.
Disconnect electrical power before servicing the equipment,
including condenser fan motors or compressors. More than
one disconnect may be required to de-energize the unit.
Failure to follow this warning exactly can result in serious
injury or death. Be sure to read and understand the installation,
operation, and service instructions within this manual.
Generator Sizing
WARNING
Generator must be sized by an electrical engineer familiar
with generator applications.
WARNING
Stop the chiller before transferring supply power from the
generator back to the utility power grid. Transferring power
while the chiller is running can cause severe chiller damage.
The necessary procedure for reconnecting power from the
generator back to the utility grid is as follows:
1. Set the generator to always run five minutes longer than
the unit start-to-start timer, which can be set from two to
sixty minutes, while keeping the chiller powered by the
generator until the fully synchronized Automatic Transfer
Switch properly hands over chiller power from the site.
2. Configure the transfer switch provided with the
generator to automatically shut down the chiller before
transfer is made. The automatic shut-off function can
be accomplished through a BAS interface or with the
“remote on/off” wiring connection shown in the field
wiring diagrams.
A start signal can be given anytime after the stop signal since
the start-to-start timer will be in effect.
Field Wiring
Figure 15: Field Wiring for Single Point
Table 29: Cool LWT 1 and Cool LWT2 Set Point Ranges Sensor Offsets
Suction Pressure -100 to 100 kPa
Evaporator Unit 0 kPa (0 PSI)
Range Sensor Offset (-14.5 to 14.5 PSI)
Glycol Vintage
Discharge Pressure -100 to 100 kPa
No F vintage 4.4 to 21.1°C (39.9 to 70°F) 0 kPa (0 PSI)
Sensor Offset (-14.5 to 14.5 PSI)
Yes F vintage -9.5 to 21.1°C (14.9 to 70°F) Suction Temperature -5.0 to 5.0 °C
0°C (0°F)
Sensor Offset (-9.0 to 9.0 °F)
Table 30: Evaporator Water Freeze Discharge
-5.0 to 5.0 °C
Temperature Sensor 0°C (0°F)
Evaporator Glycol Range (-9.0 to 9.0 °F)
Offset
No 2.2 to 5.6°C (36 to 42.1°F)
Yes -28.89 to 5.6°C (-20 to 42.1°F)
Unit Function
Table 31: Low Ambient Lockout
The calculations in this section are used in unit level control
Condenser Fan Configuration Range logic or in control logic across all circuits.
All Single Speed (AF) 0 to 15.6°C (32 to 60.1°F)
First Fan or All Fan Variable
Evaporator Delta T
Speed (DC, DD, DE, DF, DG, -23.3 to 15.6°C (-9.9 to 60.1°F) The evaporator water delta T is calculated as entering water
DH, DV, HA, HB)
temperature minus leaving water temperature.
Capacity Staging Deadbands Using the predicted capacity change for staging up, the
resulting change in leaving water temperature is predicted.
The staging deadbands the band in which unit capacity will
not be increased or decreased. They are based off a relation
of the evaporator temperature delta, the unit capacity, and
the capacity change of staging up or down a compressor. The Using the change in leaving water temperature, the stage up
largest compressor available for stage up or stage down is control band is calculated.
used in the following calculations for a conservative estimate.
The stage up and stage down deadbands are each determined
from a three-part calculation, then limited to stay within defined
boundaries of the range:
Stage Down Deadband
To calculate the stage down deadband, first the largest
compressor available for stage down is determined. With that
information, the percent change if this compressor were to
The stage up deadband is the measure of how far the leaving stage down is calculated.
water temperature be must above the target to trigger a stage
up in capacity.
The stage down deadband is the measure of how far the
Using the predicted capacity change for staging down, the
leaving water temperature be must below the target to trigger a
resulting change in leaving water temperature is predicted.
stage down in capacity.
The result of the first two equations will be a negative value,
reflecting a decrease in capacity.
Figure 18: Capacity Staging Deadbands
Start Up Temperature
No. Description
1 Leaving Water Temperature Unit Enable
2 Stage Up Control Band
Enabling and disabling the chiller is accomplished using set
3 Stage Down Control Band points and inputs to the chiller. The Unit Switch input and
4 LWT Target + Stage Down Control Band the Unit Enable HMI Set Point are both required to be On/
5 LWT Target Enable for the unit to be enabled when the control source is
6 LWT Target + Stage Up Control Band
set to ‘Local’. If the control source is set to ‘Remote’, the Unit
Switch and Remote Switch inputs are both required to be On/
Stage Up Deadband Enable for the unit to be enabled. If the control source is set to
‘Network’, the Unit Switch input and BAS Enable set point must
To calculate the stage up deadband, first the largest both be On/Enable for the unit to be enabled.
compressor available for stage up is determined. With that
information, the percent change if this compressor were to
stage up is calculated.
Unit is enabled according to the following table: Figure 19: Transitions between these states are shown in
the following diagram.
Control Unit BAS Unit
Source Unit Enable Remote Enable Enable/
Set Switch HMI Set Switch Set Disable
Point Point Point State
- Off - - - Disable
- Disable - - Disable
Local
On Enable - - Enable
- - Off - Disable
Remote
On - On - Enable
- - - Disable Disable
Network
On - - Enable Enable
Pumpdown – Packaged units with microchannel coils will • A Unit Fault is present
not do a pumpdown; however, the pumpdown state will exist
T5 – Start to Shut Down
for units with microchannel coils and remote evaporator. So
if the conditions for the Auto to Pumpdown transition occur, Any of the following are required:
the unit state will transition from Auto to Pumpdown and • A Unit Fault is present
then immediately to Off.
• Unit Enable = Off
T6 – Off to Alarm
All of the following are required:
• A Unit Fault is present
T7 – Alarm to Off If OAT drops below the low ambient lockout set point and
any circuits are running, then those circuits will be allowed
All of the following are required:
to remain running, and the unit will not enter the low ambient
• No Unit Faults are present lockout condition. Circuits that are not running will enter a
circuit level lockout condition when OAT drops below the
T8 – Shut Down to Off lockout set point. This condition will clear at the circuit level
All of the following are required: when OAT rises to the lockout set point plus 2.5°C (4.5°F).
• No Unit Faults are present If the OAT is below the low ambient lockout set point, the OAT
sensor fault is not active, and neither circuit is running, low
T9 – Off to Test ambient lockout is triggered. The unit will go directly into the
off state and will remain in the off state until the lockout has
All of the following are required:
cleared. This condition will clear when OAT rises to the lockout
• No Unit Faults are present set point plus 2.5°C (4.5°F).
• Unit Enable = Off
• Test Mode = True Disabled Option
When the chiller is configured to disable low ambient lockout,
T10 – Test to Shut Down the unit will not enter the low ambient lockout condition or shut
Any of the following are required: down any running circuits regardless of the OAT.
• A Unit Fault is present
BAS Annunciation
• Unit Enable = On
Low Ambient Lockout is not an alarm, but it can be
• Test Mode = False
annunciated to the BAS as if it is one. When the Low OAT
Lockout BAS Alert setpoint is set to On and the low ambient
Low Ambient Lockout lockout is active, the following alarm will trigger:
The operation of the chiller in response to OAT dropping below
the Low OAT Lockout set point is configurable if the chiller has Table 35: Low OAT Lockout
variable speed condenser fans. In that case, there are three
options: Alarm Low OAT Lockout
• Lockout and Stop – Chiller will shut down and lockout. Type Problem
• Lockout only – Chiller does not shut down running Displayed Text Message Module Module ID Payload
circuits, will lock out circuits that are off. Code Type
• Disabled – Chiller does not shut down or lock out. Alarm Parts 65 1 0 0
For chillers without condenser fan VFD’s, there is no Alarm Code 1090584576
configuration, and the chiller will always operate according to Trigger Trigger conditions are defined in the sections
the first option shown above. Descriptions of the operation for above
each option are in the following sections. Low ambient lockout Action Taken: No Action
logic resides on the PC. Reset Clearing conditions are defined in the section
above
Lockout and Stop Operation
When the chiller is configured for lockout and stop, it will
operate as described in this section.
If the OAT drops below the low ambient lockout set point
and the OAT sensor fault is not active, low ambient lockout
is triggered. The unit will perform a normal shutdown if any
circuits are running. Once all circuits shut off, the unit will
remain in the off state until the lockout has cleared. This
condition will clear when OAT rises to the lockout set point plus
2.5°C (4.5°F).
Unit Status Figure 20: Transitions between these states are shown in
the following diagram.
Unit Status is displayed to indicate the general operating
condition of the unit. The following table lists the text displayed
for each unit status and the conditions that enable each status.
If more than one status is enabled at the same time, the
highest numbered status overrides the others and is displayed.
Sound Reduction
On AGZ-F chillers, sound reduction is built into the fan code
which is input in the unit commissioning sequence. The
condenser control section contains information about rpm
T1 – Off to Start
ranges corresponding to the codes. Only the fan code the unit
was configured for should be used. All of the following are required:
• Circuit Enable = Enable
Test Mode • No Circuit Alarms active
Test mode is a variation of manual control that is not meant to • There is at least one compressor available to start
make cold water, but to test individual components. Test mode • Unit State = Auto
is useful in situations like opening the EXVs and solenoids
manually to allow for pump down. In test mode, compressors T2 – Start to Run
will “bump” when started, so they will turn themselves off after
a few seconds with no additional action. All of the following are required:
• The EXV preopen procedure has finished
• The first compressor to start is running
Circuit Functions
T3 - Run to Shut Down
Table 39: Circuit States Any of the following are required:
State Description • Unit Enable = Off
Off Circuit is off. EXV is at 0.2%, solenoids are closed • Circuit Enable = Disable
and no fans or compressors running. • A Circuit Fault is present
Start EXV is going through the preopen sequence. • There are no compressors running on the circuit
Run Circuit is running with at least one compressor.
Shut Down Circuit is going through shut down procedures. Can
T4 – Shut Down to Alarm
transition to Off or Alarm. All of the following are required:
Alarm Circuit fault is active. • A Circuit Fault is present
T6 – Off to Alarm
All of the following are required:
A Circuit Fault is present
HB High Static DC 300 rpm 900 rpm 3 hp Fan Output 1 UC NO2 K101 101 On On On On
Fan Motors Fan Output 3 UC NO5 K103 102 On On
DC DC Fan Motors 300 rpm 850 rpm 2 hp Fan Output 2 UC NO3 K102 103 On On
DD DC Fan Motors 300 rpm 800 rpm 2 hp
Fan Output 3 UC NO6 K103 104 On On
DE DC Fan Motors 300 rpm 750 rpm 2 hp
Circuit 2
DF DC Fan Motors 300 rpm 700 rpm 2 hp Stage
Description Output Contractor Fans
DG DC Fan Motors 300 rpm 650 rpm 2 hp 1 2 3 4
DH DC Fan Motors 300 rpm 600 rpm 2 hp Fan Output 1 UC NO7 K201 201 On On
Fan Output 2 UC NO8 K202 202 On
Fan Output 1 UC NO2 K101 101 On On On On Fan Output 1 UC NO2 K101 101 On On On On
Fan Output 3 UC NO6 K103 102 On On Fan Output 3 UE2 NO1 K103 102 On On On
Fan Output 2 UC NO3 K102 103 On On Fan Output 2 UC NO3 K102 103 On On On On
Fan Output 3 UC NO6 K103 104 On On Fan Output 3 UE2 NO1 K103 104 On On On
Fan Output 2 UC NO8 K202 203 On On Fan Output 1 UC NO7 K201 201 On On On On
Fan Output 3 UC NO11 K203 204 On On Fan Output 3 UC NO11 K203 202 On On
Fan Output 2 UC NO3 K102 103 On On On On Fan Output 1 UC NO2 K101 101 On On On On
Fan Output 3 UC NO6 K103 104 On On On Fan Output 3 UC NO6 K103 102 On On On
Fan Output 2 UC NO3 K102 105 On On On On Fan Output 2 UC NO3 K102 103 On On On On
Fan Output 3 UC NO6 K103 106 On On On Fan Output 3 UC NO6 K103 104 On On On
Fan Output 2 UC NO8 K202 203 On On Fan Output 1 UC NO7 K201 201 On On On On
Fan Output 3 UC NO11 K203 204 On On Fan Output 3 UC NO11 K203 202 On On On
Table 50: 12 Fans - AF - 6 Compressors F Vintage Model - First Fan ECM (DV)
Circuit 1
Stage Table 52: 2 Fans - DV
Description Output Contractor Fans
1 2 3 4 5 6
Circuit 1
Fan Output 1 UC NO2 K101 101 On On On On Description Output Contractor Fans Stage 1
Fan Output 3 UE2 NO1 K103 102 On On On Speed Signal 1 Modbus n/a 101 On
Circuit 2
Fan Output 2 UC NO3 K102 103 On On On On
Description Output Contractor Fans Stage 1
Fan Output 3 UE2 NO1 K103 104 On On On Speed Signal 1 Modbus n/a 201 On
Fan Output 2 UC NO3 K102 105 On On On On
Speed Signal 1 Modbus n/a 101 On On On On Speed Signal 1 Modbus n/a 101 On On On On On On
Fan Output 3 UC NO3 K102 102 On On Fan Output 4 UE2 NO1 K103 102 On On
Fan Output 2 UC NO2 K101 103 On On Fan Output 2 NO2 K101 103 On On On
Fan Output 3 UC NO3 K102 104 On On Fan Output 4 UE2 NO1 K103 104 On On
Fan Output 2 UC NO7 K201 203 On On Speed Signal 1 Modbus n/a 201 On On On On
Fan Output 3 UC NO8 K202 204 On On Fan Output 3 UC NO8 K202 202 On On
Fan Output 2 NO2 K101 103 On On On Speed Signal 1 Modbus n/a 101 On On On On On On
Fan Output 4 NO6 K103 104 On On On Fan Output 3 UC NO6 K103 102 On On
Fan Output 3 NO3 K102 105 On On On On Fan Output 2 UC NO3 K101 103 On On On
Fan Output 3 NO3 K102 106 On On On Fan Output 3 UC NO6 K103 104 On On
Fan Output 2 NO7 K201 203 On On Speed Signal 1 Modbus n/a 201 On On On On On On
Fan Output 3 NO8 K202 204 On On Fan Output 3 UC NO11 K203 202 On On On On
Where Optimum Tccircuit x is in Fahrenheit, outdoor air The Stage Up Error Step is added to a Stage Up Accumulator
temperature is in Fahrenheit, and nominal capacity is in once every 5 seconds, only if the Saturated Condenser
nominal horsepower calculated: Refrigerant Temperature is not falling. When Stage Up Error
Accumulator is greater than the Stage Up Limit the fan stage
is increased by one stage if the stage up timer has expired. If
the chiller is in a low ambient condition the low ambient staging
conditions must be satisfied (see low ambient starts and
Simultaneously, using the compressor envelope of the most staging section.
conservative compressor in the product line, a minimum bound
for the condenser target is calculated: Outdoor Air < 20 20-50 50-80 80-110 >110
Temperature (°F)
Stage Up 5.0 5.0 5.0 5.0 5.0
Deadband (°F)
The 20°F is added as a buffer to make sure that even if the Stage Down 30.0 23.0 29.8 19.8 15.0
Tc overshoots below the target, the compressor is not in Deadband (°F)
danger of leaving the envelope. The condenser target takes The only exception to the above table is if there are no fans
the maximum value of the two, the optimum Tc and the lower running on a circuit (circuit just started).
bound Tc. This makes it so the target Tc is never outside of the
compressor envelope. Outdoor Air All
Temperature (°F)
The calculated condenser target is capped at a high bound of
Stage Up 1.0
133°F. A 133°F saturated condenser temperature correlates
Deadband (°F)
to a discharge pressure of about 509.4 PSI (gauge). If the
discharge pressure is higher than 515 PSI (gauge), the circuit Stage Down 1.0
Deadband (°F)
will not have room to start another compressor. When looking
to stage up a compressor, capacity control monitors discharge
pressure and will not stage up that circuit is the pressure is High Ambient Starts
higher than 515 PSI. This cap makes it so the condenser fans When a circuit is called to start, if the saturated condenser
will ramp to 100% output to keep the discharge pressure below temperature is greater than 90°F before the preopen
515 PSI to allow more compressors to start. sequence, a high ambient start is initiated.
AF and DV
In an AF or DV high ambient start, the goal is to have the first
one or two fans on the circuit running at maximum capacity
before the compressor is turned on. In the high ambient start
logic, the stage up accumulation term is overridden and set to
the limit value, triggering an immediate stage up. By triggering
a regular stage up by maxing out the stage up accumulator,
the logic evaluates if a “skipping first stage” case should be
utilized (see section below). In most cases this results in the
condenser skipping the first stage. Another feature of the
high ambient start is that the PID output to the ECM fans (if
applicable) is overridden and set to the maximum value. By
setting the fan output to the maximum before the compressor
starts, the fans have time to ramp up in time to curb the
discharge pressure rise. If the outdoor air temperature is
greater that 105°F, all fans are staged up immediately.
Figure 25: Pressure Control Target Figure 27: Close uop of Blended Region
5 Mechanical High Fault Circuit Controller Trigger Conditions required to trigger the alarm.
Pressure Switch Shutdown HMI or Action Actions that should be taken when the alarm triggers.
BAS Taken
6 Motor Protection Fault Circuit n/a Reset Conditions required for clearing. Method for clearing
Fault Shutdown defined in the auto clear section below.
7 Low OAT Restart Fault Circuit Controller
Fault Shutdown HMI or Module Type Information
BAS
# Module Associated Module IDs Associated Payloads
8 No Pressure Fault Circuit n/a Type
Change After Start Shutdown
1 Unit “0”: Unit “0”: “None”
9 Evaporator Fault Circuit Controller
3 Fans “11”: Fan 1 on Circuit 1, “0”: “Modbus Communication Error”,
Pressure Sensor Shutdown HMI or “12”: Fan 2 on Circuit 1, “1”: “Short Circuit Fault”,
Fault BAS “13”: Fan 3 on Circuit 1, “2”: “Motor Stalled Fault”,
“14”: Fan 4 on Circuit 1, “3”: “Module NTC Fault”,
10 Condenser Fault Circuit Controller “15”: Fan 5 on Circuit 1, “4”: “Module Over Temp Fault”,
Pressure Sensor Shutdown HMI or “16”: Fan 6 on Circuit 1, “5”: “Bus Over Voltage Fault”,
Fault BAS “17”: Fan 7 on Circuit 1, “6”: “Bus Low Voltage Fault”,
“18”: Fan 8 on Circuit 1, “7”: “Output Phase Lost Fault”,
11 Suction Fault Circuit Controller “21”: Fan 1 on Circuit 2, “8”: “Input Phase Lost Fault”,
“22”: Fan 2 on Circuit 2, “9”: “Overload Fault”,
Temperature Shutdown HMI or “23”: Fan 3 on Circuit 2, “10”: “Comm Fail Fault”,
Sensor Fault BAS “24”: Fan 4 on Circuit 2, “11”: “Bus Unbalance Fault”,
“25”: Fan 5 on Circuit 2, “12”: “AC Low Fault”,
12 Discharge Fault Circuit n/a “26”: Fan 6 on Circuit 2 “13”: “AC High Fault”,
Temperature Shutdown “14”: “External Fault”,
“15”: “EEPROM Fault”,
Sensor Fault “16”: “Inner Comm Fault”,
“17”: “Ambient Over Temp Shutdown Fault”,
13 High Discharge Fault Circuit n/a “18”: “Ambient NTC Fault”,
Temperature Shutdown “19”: “Ext NTC Error Fault”,
“20”: “Current Sample Fault”,
14 EEXV Module Fault Circuit Controller “21”: “EEPROM Warning”,
Comm Failure Shutdown HMI or “22”: “Over Temp Fast Down Warning”,
BAS “23”: “Over Temp Slow Down Warning”,
“24”: “Over Temp Limit Warning”,
15 DC Fan Fault Problem Ignore Controller “25”: “Analog Input Warning”,
“26”: “Overload Warning”,
Affected Fan HMI or “27”: “Comm Fail Warning”,
BAS “28”: “Over Temp Fast Down Warning”,
“29”: “Ambient Over Temp Warning”,
“30”: “Fan Fail Warning”,
“31”: “Ext NTC Error Warning”
# Module Associated Module IDs Associated Payloads Evaporator Water Freeze Protect
Type
7 BAS Ex- “0”: Expansion Module – “0”: “None” Alarm Evaporator Water Freez Protect
pansion Main Box (UE02)
Module Type Fault
8 Circuit “1”: Circuit 1, “0”: “None”, Displayed Evaporator Water Freeze Protect
“2”: Circuit 2 “1”: “Ground Fault Monitor”, Text
“2”: “Phase Voltage Monitor”
Alarm Message Module Module Payload
Parts Code Type ID
PVM/GFP Fault
151 1 0 0
Alarm PVM/GFP Fault
Alarm 2533425152
Type Fault Code
Displayed PVM/GFP Fault Trigger [Evaporator LWT drops below evaporator freeze
Text protect set point and LWT sensor fault is not active]
for a time longer than the evaporator recirculation
Alarm Message Module Module Payload time set point
Parts Code Type ID
Action Shutdown all circuits and lock out unit from running
228 1 0 1 Taken
Alarm 3825270785 Reset Alarm trigger no longer exists – Cannot be auto
Code cleared
Trigger Alarm is trigged if all of the following are true for at
least one second: Evaporator LWT Sensor Fault
-Power Configuration = Single Point
Alarm Evaporator LWT Sensor Fault
-PVM/GFP Input #1 is off
Type Warning
Action Shutdown all circuits and lock out unit from running
Taken Displayed Evaporator LWT Sensor Fault
Text
Reset Reset when input is on for at least 5 seconds or if
Power Configuration = Multi Point. Alarm Message Module Module Payload
Parts Code Type ID
Evaporator Flow Loss 162 5 0 0
Alarm 2718236672
Alarm Evaporator Flow Loss
Code
Type Fault
Trigger Trigger any time sensor status is other than “10”
Displayed Evaporator Flow Loss and UC01 communication with UE01 module is OK,
Text for at least one second.
Alarm Message Module Module Payload Action Shutdown all circuits and lock out unit from running
Parts Code Type ID Taken
150 1 0 0 Reset Sensor status returns to “10”
Alarm 2516647936
Code Evaporator EWT Sensor Fault
Trigger 1: Evaporator Pump State = Run AND Evaporator Alarm Evaporator EWT Sensor Fault
Flow input is off for time > Flow Proof Set Point AND
at least one compressor running Type Warning
2: Evaporator Pump State = Start for time greater Displayed Evaporator Water Freeze Protect
than Recirc Timeout Set Point and all pumps have Text
been tried and Evaporator Flow input is off
Alarm Message Module Module Payload
Action Shutdown all circuits and lock out unit from running Parts Code Type ID
Taken
2 5 0 0
Reset Alarm trigger no longer exists
Alarm 33882112
Code
Trigger Trigger any time sensor status is other than “10”
and UC01 communication with UE01 module is OK,
for at least one second.
Action Ignore sensor value in applicable calculations
Taken
Reset Sensor status returns to “10”
Displayed Evaporator Pressure Sensor Fault Trigger Trigger any time sensor status is other than “10”
Text and UC01 communication with UE01 module is OK,
for at least one second.
Alarm Message Module Module Payload
Parts Code Type ID Action Shutdown circuit and lock circuit out from running
Taken
155 5 1,2 0
Reset Sensor status returns to “10”
Alarm Circuit 1: 2600797184
Code
Circuit 2: 2600798208 Suction Temperature Sensor Fault
Trigger Trigger any time sensor status is other than “10”
Alarm Suction Temperature Sensor Fault
and UC01 communication with UE01 module is OK,
for at least one second Type
Action Shutdown circuit and lock circuit out from running Displayed Suction Temperature Sensor Fault
Taken Text
Reset Sensor status returns to “10” Alarm Message Module Module Payload
Parts Code Type ID
Displayed DC Fan Fault Action Taken Action that should be taken when the event
Text triggers and while active
Alarm Message Module Module Payload Reset Conditions for the event to reset
Parts Code Type ID
33 3 See
Module
See
Module Circuit Events
Type Type
Table Table
The events in this section exist for both circuit one and circuit
Above Above two.
Alarm Generated on a case-by-case basis
Code Low Evaporator Pressure - Hold
Trigger Triggered when a DC fan reports an alarm Alarm Low Evaporator Pressure - Hold
Action Ignore affected fan in condenser staging logic Displayed Cn Low Evap Pr Hold
Taken Text
Reset DC fan reports alarm is cleared Trigger This event is triggered if all of the following are true:
• circuit state = Run
Auto Clearing Alarms • evaporator pressure <= Low Evaporator
Alarm auto-clearing only occurs if there are no alarms present Pressure - Hold set point
that cannot be auto cleared. Alarms that cannot be auto • circuit is not currently in a low OAT start
cleared are noted in the alarm descriptions above.
• it has been at least 30 seconds since a
The auto clearing process is equivalent to if the user manually compressor has started on the circuit.
cleared the alarms from the HMI or sent the clear alarms
Action Inhibit starting of additional compressors on the
command via the BAS system. Taken circuit
A successful auto-clear means all alarms have been cleared. Reset While still running, the event will be reset if
evaporator pressure > Low Evaporator Pressure
The first successful auto-clear starts an hour-long timer, while Hold SP + 90 KPA(13 PSI). The event is also reset if
the timer is active, no more than 3 successful auto-clears can the circuit is no longer in the run state.
occur. After the third successful auto-clear, there will be no
more attempts until the timer expires.
Touchscreen Controller Entering an invalid password has the same effect as not
entering a password.
Once a valid password has been entered, the controller
Home Screen allows further changes and access without requiring the user
to enter a password until either the password timer expires
or a different password is entered. The default value for this
Figure 28: Home Screen
password timer is 10 minutes.
Navigation Menu
Figure 30: Navigation Menu
Login Screen From the Navigation Menu you can select the following
options:
Figure 29: Login Screen • Unit
• Circuit 1
• Circuit 2
• Trends
• Configuration
• Maintenance
To close the Navigation Menu, tap the “X” in the upper right
corner of the display screen.
Unit/Setpoints Configuration
The Unit Home screen displays important information about the
unit, including the active setpoint, entering water temperature, Figure 33: Configuration Screen
startup temperature, and more.
• Setpoints
• Compressors
• Condenser Fans
half the control band plus the startup delta-T before the
MicroTech controller will stage on cooling.)
Shutdown
• Set the Evap Delta T based on a percent of unit nominal Temporary Shutdown
flow and the Start Delta T as a starting point. Delta-
T=Tons x 24 / gpm 1. Use the LED Enable button on the Main control box door
to disable the unit.
• Check the controller setpoints to be sure that factory
defaults are appropriate. 2. Turn off chilled water pump. Chilled water pump to
operate while compressors are pumping down.
Table 66: Unit Enable Button Light Legend 3. To start the chiller after a temporary shutdown, follow the
Light Activity Unit Status Description
startup instructions.
Figure 35: Thermal Dispersion Flow Switch and Adapter If the flow sensor is to be mounted away from the unit, the
sensor should be mounted on the wall of the inlet pipe of
evaporator, or in a run of straight pipe that allows 5 to 10 pipe
diameters prior to the sensor and 3 to 5 pipe diameters of
straight pipe after the sensor. Flow switch is placed in inlet pipe
to reflect flow entering the evaporator.
NOTICE
Flow switch MUST be calibrated before chiller operation. Failure to
properly calibrate the switch may result in severe chiller damage and/or
void warranty.
Mounting
It is important that the flow switch be mounted so that the
Figure 36 highlights the position of the electrical connector and
probe is sufficiently inserted into the fluid stream. Figure 38
indentation ‘mark’ on flow switch.
illustrates the recommended orientation of the sensor. It may
not be mounted directly on top or directly on the bottom of a
Figure 36: Flow Switch Details horizontal pipe.
NOTICE
DO NOT alter or relocate factory installed flow switch. If issues exist,
contact Chiller Technical Response at TechResponse@DaikinApplied.com.
No. Descriptions
1 Electrical Connector
2 Indentation
2.5 2.46 9.79 14.7 24.5 36.7 49.0 73.4 97.9 122.4 146.9 2.42
3 3.07 15.1 22.7 37.8 56.7 75.6 113.4 151.2 189.0 226.8 3.78
3.5 3.55 20.2 30.3 50.6 75.8 101.1 151.7 202.2 252.8 303.3 5.06
4 4.03 26.0 39.1 65.1 97.7 130.2 195.3 260.4 325.5 390.5 6.51
5 5.05 40.9 61.4 102.3 153.5 204.6 306.9 409.2 511.5 613.7 10.2
6 6.07 59.1 88.6 147.7 221.6 295.5 443.2 590.9 738.7 886.3 14.8
8 7.98 102.3 153.5 255.8 383.7 511.6 767.5 1023.3 1279.1 1534.7 25.6
10 10.02 161.3 241.9 403.2 604.8 806.5 1209.7 1612.9 2016.2 2419.1 39.0
12 11.94 229.0 343.4 572.4 858.6 1144.7 1717.1 2289.5 2861.9 3433.8 57.2
14 13.13 276.8 415.2 692.0 1037.9 1383.9 2075.9 2767.8 3459.8 4151.3 69.2
16 15.00 361.5 542.2 903.6 1355.5 1807.3 2710.9 3614.6 4518.2 5421.2 90.4
18 16.88 457.5 686.3 1143.8 1715.7 2287.6 3431.4 4575.2 5719.0 6862.1 114.4
20 18.81 572.4 853.0 1421.6 2132.4 2843.2 4264.8 5686.4 7108.0 8528.6 142.2
Flow Switch Adapter Step 1: Adjust flow through the evaporator to the minimum
If needed, the adapter is threaded into the pipe wall using desired operating gpm. Maintain this flow throughout the setup
pipe sealant appropriate for the application. The flow sensor procedure.
is mounted onto the adapter using silicone grease. Carefully Step 2: Once steady state minimum desired operating flow is
apply lubricant to the inside threads and o-ring so temperature obtained, perform the ‘Teach’ function on the flow switch. The
probe does not become coated with lubricant or pipe thread ‘Teach’ function is initiated by holding down the minus ‘-’ button
sealant. Torque the adapter/sensor connection to 18.5 ft/lbs. on the face of the flow switch for 15 seconds. During this 15
second period, LEDs ‘0’ and ‘9’ will be lit green. Once the
Wiring ‘Teach’ function is completed, the outer LEDs will flash green
Refer to wiring diagram in the unit control panel. as shown in Figure 39.
Step 3: After the ‘Teach’ function is completed and the outer Figure 41: Upper Range of Minimum Flow
LEDs flashed, the flow switch will indicate a new set point
based upon the current flow which should still be at the steady
state minimum desired operating flow. Figure 40 shows a
typical display for this condition. All LEDs to the left of the
SP LED are lit green. The SP LED is lit RED (or may toggle
amber) which indicates that the flow switch is OPEN. Typically,
an increase in fluid flow is between 15% to 30% above the
‘Teach’ function flow is required for the SP LED to turn AMBER
and the flow switch to CLOSE indicating acceptable flow.
Flow above display range: The SP LED will be lit amber, all
LEDs to the left and right of the SP LED with be green with the
rightmost LED flashing green. For example, if the SP was set
to 200 cm/s, the flashing LED labeled ‘9’ would indicate that
the flow was above 230 cm/s. This may be a normal display
depending on range by which flow varies through chiller.
DANGER Lubrication
LOCKOUT/TAGOUT all power sources prior to starting, No routine lubrication is required on AGZ units. The fan motor
pressurizing, de-pressuring, or powering down the Chiller. bearings are permanently lubricated and no further lubrication
Disconnect electrical power before servicing the equipment. is required. Excessive fan motor bearing noise is an indication
Failure to follow this warning exactly can result in serious of a potential bearing failure.
injury or death.
POE type oil is used for compressor lubrication. Further details
DANGER and warnings are listed on page 67.
The panel is always energized even if the system switch is off. WARNING
If it is necessary to de-energize the complete panel, including
POE oil must be handled carefully using proper protective
crankcase heaters, pull the main unit disconnect. More than
equipment (gloves, eye protection, etc.). The oil must not come
one disconnect may be required to de-energize the unit.
in contact with certain polymers (e.g. PVC), as it may absorb
Failure to do so may result in serious injury or death.
moisture from this material. Daikin Applied recommends
against the use of PVC and CPVC piping for chilled water
WARNING systems. Also, do not use oil or refrigerant additives in the
Electrical Shock Hazard. Before servicing or inspecting system.
the equipment, disconnect power to the unit. The internal
capacitor remains charged after power is turned off. Wait at
least the amount of time specified on the drive before touching
any components. Failure to do can result in property damage,
personal injury, or death.
WARNING
Warranty may be affected if wiring is not in accordance
with specifications. A blown fuse or tripped protector may
indicate a short, ground fault, or overload. Before replacing
fuse or restarting compressor, the trouble must be found and
corrected. It is important to have a qualified control panel
electrician service this panel. Unqualified tampering with the
controls can cause serious damage to equipment and void
the warranty.
CAUTION
Periodically check electrical terminals for tightness and tighten
as required. Always use a back-up wrench when tightening
electrical terminals.
Expansion Valve The pressure regulating valve is factory set to begin opening
at 110 psig with R-32 and can be changed by adjusting the
The expansion valve’s function is to keep the evaporator pressure setting. To raise the pressure setting, remove the cap
supplied with the proper amount of refrigerant to satisfy the and turn the adjustment screw clockwise. To lower the setting,
load conditions. Before adjusting superheat, check that unit turn the screw counterclockwise. Do not force the adjustment
charge is correct and liquid line sight glass is full with no beyond the range it is designed for as this will damage the
bubbles and that the circuit is operating under stable, full load adjustment assembly. The regulating valve opening point
conditions. can be determined by slowly reducing the system load while
Electronic Expansion Valve - For suction superheat targets, observing the suction pressure. When the bypass valve starts
see “Circuit Level Set Points” on page 26. to open, the refrigerant line on the evaporator side of the valve
will begin to feel warm to the touch.
Filter-Driers A solenoid valve is located ahead of the bypass valve and is
Replace the filter-drier any time excessive pressure drop is controlled by the MicroTech controller. It is active when only the
read across the filter-drier and/or when bubbles occur in the first stage of cooling on a circuit is active.
sight glass with normal subcooling. The filter-drier should also
be changed if the moisture indicating liquid line sight glass
WARNING
indicates excess moisture in the system. When performing valve checkout procedure, the hot gas
line may become hot enough in a short period of time to
Any residual particles from the condenser tubing, compressor
cause personal injury. Be sure to read and understand the
and miscellaneous components are swept by the refrigerant
installation, operation, and service instructions within this
into the liquid line and are caught by the filter-drier.
manual.
A condenser liquid line service valve is provided for isolating
A field installed HGBP kit can be added to units already
the charge in the condenser, but also serves as the point from
installed. If a 120-V version of the kit is ordered, the solenoid
which the liquid line can be pumped out. With the line free of
valve comes with a DIN connector and has to be wired. The
refrigerant, the filter-drier core(s) can be easily replaced.
wiring should be two 14 AWG wires, one red and one white to
AGZ-F units come equipped with replaceable core filter driers. be run in conduit. Field to wire:
The core assembly of the replaceable core drier consists of a
• Circuit 1 Red to NO2 on UE01 and white to SPL1 (splice
filter core held tightly in the shell in a manner that allows full
connector)
flow without bypass.
• Circuit 2 Red to NO4 on UE01 and white to SPL1 (splice
connector)
Hot Gas Bypass (Optional)
NOTE: PIPING SHOWN FOR ONE SYSTEM OF UNIT. UNITS AGZ140-180E PACKAGE CHILLER
HAVE TWO INDEPENDENT SYSTEMS.
DIN connection size is 1/2 in. NPTF for conduit fitting. Required
MICROCHANNEL ALUMINUM COIL
334549802 0D
wire, conduit fittings, and conduit to be supplied by the field.
CONDENSER
ASSEMBLY
cycling. HGBP is required to be on both refrigerant circuits Figure 45: HGBP Portion of Refrigerant Schematic
SUCTION
TRANSDUCER
(WL1, WL2)
NOTE: The hot gas bypass valve should not generate a CONDENSER RAIL TUBING
100% false load. For glycol applications, HGBP may OIL SIGHT OIL
HEATER
ENTERING WATER
TEMPERATURE
LIQUID SENSOR WYE STRAINER REQUIRED
TUBING (FACTORY OR FIELD
INSTALLED)
HOT GAS SOLENOID HGBP
ACCESS BYPASS TUBING VALVE VALVE
FITTING
(OPTIONAL) WATER
SCHRADER IN
VALVE
LEAVING WATER
LIQUID TEMP. SENSOR
SHUT-OFF
VALVE
WATER
OUT
FILTER SCHRADER SOLENOID SCHRADER SIGHT ELECTRICAL FLOW SENSOR PLATE TYPE
DRIER VALVE VALVE VALVE GLASS EXPANSION VALVE (OPTIONAL) EVAPORATOR
(REPLACEABLE CORE)
Quarterly
Monthly
Operation
(Note 1)
(Note 2)
Weekly
Annual
absorb moisture if exposed to air and may form acids that can
be harmful to the chiller. Avoid prolonged exposure of POE oil
General to the atmosphere to prevent this problem.
Complete unit log and review (Note 3) X It is important that only the manufacturer’s recommended oils
Visually inspect unit for loose or be used. Acceptable POE oil types are:
X
damaged components
Inspect thermal insulation for integrity X • Danfoss POE lubricant 1855L
Clean and paint as required X
Electrical
WARNING
Check terminals for tightness, X POE oil must be handled carefully using proper protective
tighten as necessary
equipment (gloves, eye protection, etc.) The oil must not come
Clean control panel interior X
in contact with certain polymers (e.g. PVC), as it may absorb
Visually inspect components for
signs of overheating X moisture from this material. Daikin Applied recommends
Verify compressor heater operation X against the use of PVC and CPVC piping for chilled water
Test and calibrate equipment systems. Also, do not use oil or refrigerant additives in the
X
protection and operating controls system.
Verify solenoid plug(s) tightness and X
gasket integrity
Refrigeration
WARNING
Leak test X Polyolester Oil, commonly known as POE oil is a synthetic
Check sight glasses for clear flow X oil used in many refrigeration systems, and is present in this
Check filter-drier pressure drop X Daikin Applied product. POE oil, if ever in contact with PVC/
Perform compressor vibration test X CPVC, will coat the inside wall of PVC/CPVC pipe causing
Acid test oil sample X environmental stress fractures. Although there is no PVC/
Condenser (air-cooled) CPVC piping in this product, please keep this in mind when
Rinse condenser coils (Note 5) X selecting piping materials for your application, as system
Clean epoxy coated condenser coils X
failure and property damage could result. Refer to the pipe
(Note 5)
manufacturer’s recommendations to determine suitable
Check fan blades for tightness on
shaft (Note 6) X applications of the pipe.
Check fans for loose rivets and X
cracks Procedure Notes
Check coil fins for damage X
• Use only new sealed metal containers of oil to insure
Notes: quality.
1. Monthly operations include all weekly operations. • Buy smaller containers to prevent waste and
2. Annual (or spring start-up) operations includes all weekly contamination.
and monthly operations. • Use only filter driers designed for POE and check
pressure drops frequently.
3. Log readings can be taken daily for a higher level of unit
observation. • Test for acid and color at least annually. Change filter
driers if acid or high moisture (> 200 ppm) is indicated (<
4. Never Megohm motors while they are in a vacuum to 100 ppm typical).
avoid damage to the motor.
• Evacuate to 500 microns and hold test to insure systems
5. Coil rinsing and cleaning can be required more frequently are dry.
in areas with a high level of airborne particles.
6. When cleaning condenser coils, be sure fan motors are Control and Alarm Settings
electrically locked out. The software that controls the operation of the unit is factory-
set for operation with R-32.
Refrigerant Charging If subcooling is low, add charge to clear the sight glass. Once
the subcooler is filled, extra charge will not lower the liquid
temperature and does not help system capacity or efficiency.
CAUTION
If subcooling is normal (15 to 20° F at full load) and flashing is
When moving refrigerant to/from the chiller using an auxiliary
visible in the sight glass, check the pressure drop across the
tank, a grounding strap must be used. An electrical charge
filter-drier.
builds when halo-carbon refrigerant travels in a rubber
hose. A grounding strap must be used between the auxiliary Overcharging of refrigerant will raise the compressor discharge
refrigerant tank and the end sheet of the chiller (earth ground), pressure due to filling of the condenser tubes with excess
which will safely take the charge to the ground. Damage to refrigerant.
sensitive electronic components could occur if this procedure
is not followed. Service
If a unit is low on refrigerant, you must first determine the Special tools will be required due to higher refrigerant
cause before attempting to recharge the unit. Locate and repair pressures with R-32. Oil-less/hp recovery units, hp recovery
any refrigerant leaks. Soap works well to show bubbles at cylinders (DOT approved w/525# relief), gauge manifold 30”-
medium size leaks but electronic leak detectors are needed to 250 psi low/0-800 psi high, hoses w/800 psi working & 4,000
locate small leaks. psi burst.
Charging or check valves should always be used on charging All filter driers and replacement components must be rated for
hoses to limit refrigerant loss and prevent frostbite. Ball valve POE oils and for the refrigerant pressure
type recommended. Charge to 80-85% of normal charge
Brazed connections only. No StayBrite or solder connections
before starting the compressors.
(solder should never be used with any refrigerant). K or L type
refrigeration tubing only. Use nitrogen purge. Higher R-32
Charging procedure pressures and smaller molecule size make workmanship more
The units are factory-charged with R-32. Use the following critical.
procedure if recharging in the field is necessary. Cooling the recovery cylinder will speed recovery and lessen
The charge can be added at any load condition between stress on recovery equipment.
25 to 100 percent load per circuit, but at least two fans per
refrigerant circuit should be operating if possible.
Evaporator waterflow MUST be established while charging the
unit.
• Start the system and observe operation.
• Trim the charge to the recommended liquid line sub-
cooling (approximately 15-20°F typical at full load).
• Use standard charging procedures (liquid only) to top off
the charge.
• Check the sight glass to be sure there is no refrigerant
flashing.
With outdoor temperatures above 60°F (15.6°C), all condenser
fans should be operating and the liquid line temperature
should be within 15°F to 20°F (8.3°C to 11.1°C) of the outdoor
air temperature. At 25-50% load, the liquid line temperature
should be within 5°F (2.8°C) of outdoor air temperature with all
fans on. At 75-100% load the liquid line temperature should be
within 10°F (5.6°C) of outdoor air temperature with all fans on.
If the unit is at steady full load operation and bubbles are
visible in the sight glass, then check liquid subcooling. The
AGZ units have a condenser coil design with approximately
15% of the coil tubes located in a subcooler section of the coil
to achieve liquid cooling to within 15 to 20°F (8.3 to11.1°C)
of the outdoor air temperature when all condenser fans are
operating. Subcooling should be checked at full load with 70°F
(21.1°C) ambient temperature or higher, stable conditions, and
all fans running. Liquid line subcooling at the liquid shut-off
valve should be between 15 and 20°F at full load.
Information and Training vii. Discharge capacitors in a way that won’t cause any
spark. The standard procedure to short circuit the
The training should include the substance of capacitor terminals usually creates sparks.
the following viii. Reassemble sealed enclosures accurately. If seals are
worn, replace them.
• Information about the explosion potential of flammable
refrigerants to show that flammables may be dangerous ix. Check safety equipment before putting into service.
when handled without care. — Repair
H. Do not overfill cylinders (no more than 80 % volume • The recovered refrigerant shall be returned to the
liquid charge. refrigerant supplier in the correct recovery cylinder,
and the relevant waste transfer note arranged. Do not
I. Do not exceed the maximum working pressure of the
mix refrigerants in recovery units and especially not in
cylinder, even temporarily.
cylinders.
J. When the cylinders have been filled correctly and the • If compressors or compressor oils are to be removed,
process completed, make sure that the cylinders and ensure that they have been evacuated to an acceptable
the equipment are removed from site promptly and all level to make certain that FLAMMABLE REFRIGERANT
isolation valves on the equipment are closed off. does not remain within the lubricant. The evacuation
K. When the cylinders have been filled correctly and the process shall be carried out prior to returning the
process completed, make sure that the cylinders and compressor to the suppliers. Only electric heating to the
the equipment are removed from site promptly and all compressor body shall be employed to accelerate this
isolation valves on the equipment are closed off. process. When oil is drained from a system, it shall be
carried out safely.
Equipment shall be labelled stating that it has been de-
commissioned and emptied of refrigerant. This label should be
dated and signed.
For appliances containing FLAMMABLE REFRIGERANTS,
ensure that there are labels on the equipment stating the
equipment contains FLAMMABLE REFRIGERANT.
Labeling
Equipment shall be labelled stating that it has been de-
commissioned and emptied of refrigerant. The label shall be
dated and signed. For appliances containing FLAMMABLE
REFRIGERANTS, ensure that there are labels on the
equipment stating the equipment contains FLAMMABLE
REFRIGERANT.
Recovery
• When removing refrigerant from a system, either for
servicing or decommissioning, it is recommended good
practice that all refrigerants are removed safely.
• When transferring refrigerant into cylinders, ensure
that only appropriate refrigerant recovery cylinders are
employed. Ensure that the correct number of cylinders for
holding the total system charge is available. All cylinders
to be used are designated for the recovered refrigerant
and labelled for that refrigerant (i. e. special cylinders for
the recovery of refrigerant). Cylinders shall be complete
with pressure-relief valve and associated shut-off valves
in good working order. Empty recovery cylinders are
evacuated and, if possible, cooled before recovery
occurs.
• The recovery equipment shall be in good working order
with a set of instructions concerning the equipmenthat
is at hand and shall be suitable for the recovery of all
appropriate refrigerants including, when applicable,
FLAMMABLE REFRIGERANTS. In addition, a set of
calibrated weighing scales shall be availableand in good
working order. Hoses shall be complete with leak-free
disconnect couplings and in good condition. Before using
the recovery machine, check that it is in satisfactory
working order, has been properly maintained and that any
associated electrical components are sealed to prevent
ignition in the event of a refrigerant release. Consult
manufacturer if in doubt.
Troubleshooting
PROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS
1. Main or compressor disconnect switch open 1. Close switch.
2. Fuse blown; circuit breakers open 2. Check electrical circuits and motor windings for shorts or grounds.
Investigate for possible overloading. Check for loose or corroded
connections. Replace fuse or reset breakers after fault cause is corrected
3. Thermal overloads tripped 3. Overloads are auto-reset. Check voltages, cycle times and mechanical
operations. Allow time for auto-reset
Compressor Thermal 3. Short cycling 3. Stabilize load or correct control settings for application
Protection Switch Open 4. Voltage range or imbalance 4. Check and correct
5. High superheat 5. Adjust to correct superheat
6. Compressor mechanical failure 6. Replace compressor
Appendix
Pre-Start Checklist
Pre-Start Checklist – Scroll Compressor Chillers
Must be completed, signed, and provided to Daikin Applied sales office at least 2 weeks prior to requested start date.
Job Name
Installation Location
Customer Order Number
Model Number(s)
G.O. Number(s)
Chilled Water Piping and Condenser Water Piping for Water-cooled Chiller Yes No N/A Initials
Piping Complete
Water strainer(s) installed in piping per IOM requirements
Chilled Water System – flushed, filled, and vented; Water treatment in place
Condenser Water System (incl. cooling tower) - flushed, filled, vented; Water treatment
in place (applicable for water-cooled systems)
Pumps installed and operational (rotation checked, strainers cleaned)
Water system operated and tested; flow meets unit design requirements
Flow switch(es) - installed, wired, and ready for calibration during startup
Air vent installed on evaporator chilled water inlet piping
Glycol at design % (if applicable)
Electrical Yes No N/A Initials
Building controls operational (3-way valves, face/bypass dampers, bypass valves, etc.)
*Power leads connected to power block or optional disconnect
Power leads have been checked for proper phasing and voltage
All interlock wiring complete and compliant with Daikin Applied specifications
Power applied at least 24 hours before startup
Crankcase heaters must operate for 24+ hours before startup to maximize separation
Chiller components (EXV Sensors Transducers) installed and wired properly
*Wiring complies with National Electrical Code and local codes (See Notes)
Remote EXV wired with shielded cable
Miscellaneous Yes No N/A Initials
Unit control switches all off
Remote Evaporator / Condenser Piping factory reviewed
All refrigerant components/piping leak tested, evacuated and charged
Thermometers, wells, gauges, control, etc., installed
Minimum system load of 80% capacity available for testing/adjusting controls
SiteLineTM cloud-connected controls included and needs to be commissioned
Document Attached: Technical Breakdown from Selection Software
Document Attached: Final Order Acknowledgement
Document Attached: Remote piping approval
Notes: The most common problems delaying start-up and affecting unit reliability are:
1. Field installed compressor motor power supply leads too small. Questions: Contact the local Daikin Aplied sales representative*. State size, number
and type of conductors and conduits installed:
a. From Power supply to chiller
* Refer to NFPA 70-2017, Article 440.35
2. Remote Evaporator piping incomplete or incorrect. Provide approved piping diagrams.
3. Items on this list incorrectly acknowledged resulting in delayed start and possible extra expenses incurred by return trips.
Contractor Representative Daikin Applied Sales Representative
Signed: Signed:
Name: Name:
Company: Company:
Date: Date:
Phone/Email: Phone/Email:
JOB INFORMATION
UNIT INFORMATION
Is the unit free of visible shipping damage, corrosion, or paint problems? Yes No N/A
Is unit level and isolators installed? Yes No N/A
Does the unit meet all location, installation and service clearances per IOM Bulletin? Yes No N/A
Are all fan fastener nuts on the fans tights? Yes No N/A
Does electrical service correspond to unit nameplate? Yes No N/A
Nameplate: Volts: Hertz: Phase:
Has electrical service been checked for proper phasing at each circuit power terminal block? Yes No N/A
Has unit been properly grounded and all field wiring confirmed to unit electrical specifications? Yes No N/A
Has a fused disconnect and fuses or breaker been sized per product manual and installed per Yes No N/A
local code?
Number of Conduits: Number of Wires: Wire Size:
Are all electrical power connections tight? Yes No N/A
Has power been applied for 24 hours prior to start-up? Yes No N/A
Does all field wiring conform to unit electrical specifications? Yes No N/A
Are all service and liquid line valves per the IOMM in correct position? Yes No N/A
Water Strainer installed? Brazed Plate Evaporator 0.063” (1.6mm) or smaller perforations Yes No N/A
Has a flow switch been installed per the IOM manual? Yes No N/A
Has the chilled water circuit been cleaned, flushed, and water treatment confirmed? Yes No N/A
Does the chiller water piping conform to the IOM manual? Yes No N/A
Are fans properly aligned and turn freely? Yes No N/A
Is wind impingement against the air-cooled condenser a consideration? Yes No N/A
Are the condenser coils coated? Yes No N/A
Description of unit location with respect to building structures. Include measured distances.
DESIGN CONTROLS
CHILLER
Water Pressure Drop: psig (kPa) Ft. (kPa) gpm (lps)
Water Temperatures: Entering: °F (°C) Leaving: °F (°C)
CONDENSER
Design Ambient Temperatures: Entering: °F (°C) Leaving: °F (°C)
Minimum Ambient Temperatures: Entering: °F (°C) Leaving: °F (°C)
START-UP
Does unit start and perform per sequence of operation as stated in the IOM Manual? Yes No
Do condenser fans rotate in the proper directions? Yes No
MICROTECH STATUS CHECK
Each Reading Must be Verified with Field Provided Instruments of Known Accuracy
Water Temperatures MicroTech Verification
Leaving Evaporator: °F (°C) °F (°C)
Entering Evaporator: °F (°C) °F (°C)
Circuit #1 Refrigerant Pressures
Evaporator: psig (kPa) psig (kPa)
Liquid Lines Pressure: psig (kPa)
Condenser Pressure: psig (kPa) psig (kPa)
Circuit #2 Refrigerant Pressures
Evaporator: psig (kPa) psig (kPa)
Liquid Lines Pressure: psig (kPa)
Condenser Pressure: psig (kPa) psig (kPa)
Circuit #1 Refrigerant Temperatures
Saturated Evaporator Temperature: °F (°C) °F (°C)
Suction Line Temperature: °F (°C) °F (°C)
Suction Superheat: °F (°C) °F (°C)
Saturated Condenser Temperature: °F (°C) °F (°C)
Liquid Line Temperature: °F (°C)
Subcooling: °F (°C)
Discharge Temperature: °F (°C)
Circuit #2 Refrigerant Temperatures:
Saturated Evaporator Temperature: °F (°C) °F (°C)
Suction Line Temperature: °F (°C) °F (°C)
Suction Superheat: °F (°C) °F (°C)
Saturated Condenser Temperature: °F (°C) °F (°C)
Liquid Line Temperature: °F (°C)
Subcooling: °F (°C)
Discharge Temperature: °F (°C)
Ambient Air Temperature: °F (°C) °F (°C)
www.DaikinApplied.com 3 SF-20001 AGZ/AMZ Warranty Registration Startup Form
NON-MICROTECH READINGS
Water Pressure Drop: (ft) (psig) (gpm)*
NOTE: Actual DP ft ÷ Design DP ft = √ x Design GPM = Actual GPM
Does the system contain glycol? Yes No
Percentage by weight: or by volume: Glycol Type:
If the chilled water system include glycol, have the freeze protection, low pressure devices and settings
been adjusted for the actual job requirements? Detail these settings on page 8 - Remarks section Yes No
NOTE: See operation manual for low temperature on ice bank applications.
MICROTECH SETPOINTS
ALARM SETPOINTS MUST BE VERIFIED WITH INSTRUMENTS OF KNOWN ACCURACY
Repairs Made:
Items not installed per IOM Manual and/or recommended corrective actions:
Project Name:
Building Address:
Contractor Name:
Site Contact Name: Site Contact Number:
Your Company: Your Name:
Pump Model: Pump Tag Number:
Pump Serial: Sales Order Number:
NOTE: For independent sensorless operation, go to Section 1. For independent external sensor operation, go to Section 2. For external
controller, go to Section 3.
WARRANTY
Daikin Applied Americas Inc. dba Daikin Applied (“Company”) warrants to contractor, purchaser and any owner of the product
(collectively “Owner”) that, subject to the exclusions set forth below Company, at its option, will repair or replace defective parts in
the event any product manufactured by Company, including products sold under the brand name Daikin and used in the United States
or Canada, proves defective in material or workmanship within twelve (12) months from initial startup or eighteen (18) months from
the date shipped by Company, whichever occurs first. Authorized replacement parts are warranted for the remainder of the original
warranty. All shipments of such parts will be made FOB factory, freight prepaid and allowed. Company reserves the right to select
carrier and method of shipment. In addition, Company provides labor to repair or replace warranty parts during Company normal
working hours on products with rotary screw compressors or centrifugal compressors. Warranty labor is not provided for any other
products.
Company must receive the Registration and Startup Forms for products containing motor compressors and/or furnaces within ten (10)
days of original product startup, or the ship date and the startup date will be deemed the same for determining the commencement
of the warranty period and this warranty shall expire twelve (12) months from that date. For additional consideration, Company will
provide an extended warranty(ies) on certain products or components thereof. The terms of the extended warranty(ies) are shown on
a separate extended warranty statement.
No person (including any agent, sales representative, dealer or distributor) has the authority to expand the Company’s obligation
beyond the terms of this express warranty or to state that the performance of the product is other than that published by Company.
EXCLUSIONS
1. If free warranty labor is available as set forth above, such free labor does not include diagnostic visits, inspections, travel time and
related expenses, or unusual access time or costs required by product location.
2. Refrigerants, fluids, oils and expendable items such as filters are not covered by this warranty.
3. This warranty shall not apply to products or parts : (a) that have been opened, disassembled, repaired, or altered, in each case by
anyone other than Company or its authorized service representative; (b) that have been subjected to misuse, abuse, negligence,
accidents, damage, or abnormal use or service; (c) that have not been properly maintained; (d) that have been operated or
installed, or have had startup performed, in each case in a manner contrary to Company's printed instructions; (e) that have been
exposed, directly or indirectly, to a corrosive atmosphere or material such as, but not limited to, chlorine, fluorine, fertilizers,
waste water, urine, rust, salt, sulfur, ozone, or other chemicals, contaminants, minerals, or corrosive agents; (f) that were
manufactured or furnished by others and/or are not an integral part of a product manufactured by Company; or (g) for which
Company has not been paid in full.
4. This warranty shall not apply to products with rotary screw compressors or centrifugal compressors if such products have not
been started, or if such startup has not been performed, by a Daikin Applied or Company authorized service representative.
ASSISTANCE
To obtain assistance or information regarding this warranty, please contact your local sales representative or a Daikin Applied office.
Now that you have made an investment in modern, efficient Daikin Applied equipment, its care should
be a high priority. For training information on all Daikin Applied HVAC products, please visit us at www.
DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including
Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. To find
your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-
date product information, please go to www.DaikinApplied.com.