Iom1359 1
Iom1359 1
IOM 1359-1
                                                                        NOVEMBER 2024
TRAILBLAZER® AGZ-F
AIR-COOLED SCROLL CHILLERS
©2024 Daikin Applied, Minneapolis, MN. All rights reserved throughout the world.This document contains the most current product information as of this
printing. Daikin Applied Americas Inc. has the right to change the information, design, and construction of the product represented within the document
without prior notice. For the most up-to-date product information, please go to www.DaikinApplied.com.
™® MicroTech, SiteLine, RapidRestore, Trailblazer, and Daikin Applied are trademarks or registered trademarks of Daikin Applied Americas Inc. The
following are trademarks or registered trademarks of their respective companies: BACnet from American Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc.; Modbus from Schneider Electric; and Windows from Microsoft Corporation.
                             DANGER
                                                                             NOTE: Indicates important details or clarifying statements for
 LOCKOUT/TAGOUT all power sources prior to service,                                information presented.
 pressurizing, de-pressuring, or powering down the unit. Failure
 to follow this warning exactly can result in serious injury or death.
 Disconnect electrical power before servicing the equipment.
 More than one disconnect may be required to denergize the
 unit. Be sure to read and understand the installation, operation,
 and service instructions within this manual.
Nomenclature
                                                                                                          WARNING - flammable refrigerant
                                                                                                                     present
  No.                           Description
   1                           A = Air-Cooled
                                                                                                          WARNING - A2L low-burning veloc-
   2                             G = Global                                                                    ity refrigerant present
   3                       Z = Scroll Compressor
   4                          Number of Fans
   5                          Design Vintage
   6                         Compressor Code
Installation                                                                  Inspection
                                                                                                                 NOTICE
Operating Limits                                                              All units should be carefully inspected for damage when received. Report all
                                                                              loss or shipping damage using a claim form supplied by Daikin Applied.
Table 1: Operating/Standby Limits                                             VISIBLE LOSS OR DAMAGE: Any external evidence of loss or damage
                                                                              must be noted on the freight bill or carrier’s receipt, and signed by the carrier’s
  Operating/Standby Limits                           Temperature              agent. Failure to adequately describe such external evidence of loss or damage
  Maximum standby ambient temperature                130°F (54°C)             may result in the carrier’s refusal to honor a damage claim.
  Maximum operating ambient temperature              105°F (41°C)             CONCEALED LOSS OR DAMAGE: Concealed loss or damage
  Maximum operating ambient temperature with                                  means loss or damage which does not become apparent until the unit has
  optional high ambient package (see information     125°F (52°C)             been unpacked or unwrapped. The contents may be damaged in transit due
  under High Ambient Operation)                                               to rough handling even though the exterior may not show damages. When the
  Minimum operating ambient temperature (stan-                                damage is discovered, make a written request for inspection by the carrier’s
                                                     32°F (0°C)
  dard control)                                                               agent within five (5) days of the delivery date and file a claim with the
  Minimum operating ambient temperature (with                                 form provided by Daikin Applied. Refer to the Daikin Applied Freight Policy for
                                                     -4°F (-20°C)
  optional low-ambient control)                                               further information.
                                                     40°F to 65°F (4°C        Check all items carefully against the bill of lading. Inspect all
  Leaving chilled water temperature
                                                     to 18°C)                 units for damage upon arrival. Check the unit nameplate before
  Leaving chilled fluid temperatures (with glycol)                            unloading, making certain it matches with the power supply
  - Note that in cases of high ambient tempera-                               available. Daikin Applied is not responsible for physical damage
  ture, the lowest leaving water temperature         15°F to 65°F (-9°C
  settings may be outside of the chiller operating   to 18°C)                 after the unit leaves the factory.
  envelope; consult Daikin Tools to ensure chiller
  is capable of the required lift.
                                                                                                                CAUTION
                                                                               Forklifts may not be used to lift or move Trailblazer units as the
                                                                               method may result in unit damage.
Lifting Brackets
Lifting bracket designs vary from product to product. Rules of
engagement with the lifting brackets are the same regardless of
the bracket type. For Trailblazer units, a typical lifting bracket with
2ʺ (51 mm) diameter holes found on the sides of the unit base
are illustrated in Figure 1. See the as-designed certified drawings
for specific lifting points on this product model.
Engagement with each bracket is to be as close to vertical as
possible. The maximum allowable lift angle from the vertical is
30° as shown in Figure 2. If the lift angle shifts beyond 30 ° from
vertical on any of the lift points, the lift shall not proceed until
a corrective plan is formulated and rigging can be secured to
correct the angle of the lift.
                             WARNING
 The lifting angle must not go beyond 30 degrees from vertical or
 the unit can become unstable which may result in unit damage,                Lifting Equipment
 property damage, severe personal injury, or death.                           Lifting equipment is supplied by the user or their designate.
                                                                              This is typically selected around the unit certified information
Figure 1: Illustration of Lifting Bracket and Allowed Angle for               of the equipment to be lifted and the available lifting equipment
Lifting                                                                       planned to be at the site where the lift is to take place. It is the
                                                                              responsibility of the Lifting Director to follow a standard practice
                                                                              of lift planning and equipment selection, like that found in the
                                                                              ASME P30 series of standards. Lifting plan and equipment must
                                                                              ensure that the only contact with the unit is at the lifting brackets.
                                                                              Straps, chains or spreader bars that are likely to be used shall
                                                                              not come in contact with the unit.
                                                                                                           CAUTION
                                                                               Lifting mechanisms must not make contact with the unit beyond
                                                                               the lifting bracket. Extreme care must be used when rigging the
                                                                               unit to prevent damage to the control panels, unit handles, unit
                                                                               piping, and unit frame.
                                                                              Lifting Points
                                                                              Lifting points are predetermined by design. When lifting, all
                                                                              factory installed lifting brackets must be used. Figure 3 illustrates
                                                                              typical 8 point lifting configuration, with four lifting points on each
                                                                              side of the unit. The unit must remain level throughout the entire
                                                                              lifting event. Level is defined as one end being no more than
                                                                              0.25” per foot of unit length to the opposite end.
                                                                                                           WARNING
                                                                               Be aware that the center of gravity may not necessarily be in the
                                                                               geometric center of the unit. No additional items can be added to
                                                                               a lift with the unit as it may affect the center of gravity and cause
                                                                               unit damage, property damage, severe personal injury, or death.
                                                                               Refer to as-designed, certified drawings for weight, center of
                                                                               gravity location and details specific to unit configuration.
Figure 3: Lifting Points Locations                                         When the unit is being tied down for transit, the maximum
                                                                           allowable attachment angle from the vertical is 30 degrees in the
                                                                           opposite direction of lifting. Shimming of the unit under the lifting
                                                                           brackets or tie-down points must be used to ensure even contact
                                                                           along the length of the base rail.
                             NOTICE
 Outdoor installations are defined as open to the atmosphere
 with no permanent walls within the defined clearance distance
 and no roof is allowed above the unit.
For roof mounted applications, install the unit on a steel channel
or I-beam frame to support the unit above the roof. Spring
isolators for roof applications are recommended. For ground
level applications, install the unit on a substantial base that will
not settle. Use a one-piece concrete slab with footings extended
below the frost line. Be sure the foundation is level within 0.5”
(13 mm) over its length and width. The foundation must be
strong enough to support the unit weight. Drawings, dimensional
values, and other information may change depending on options
or configurations selected. Refer to the as-built submittal
drawings provided by a Daikin Applied sales representative for
configuration-specific details.
The addition of neoprene waffle pads (supplied by customer)                Table 2: Service Clearance
under the unit may allow water to drain from inside the frame,
which can act as a dam. Installation of optional spring or rubber-          Side   Minimum                          Notes
                                                                                   Clearance
in-shear isolators can also assist with drainage.
                                                                             A     8 ft (2.4 m)   Sides:
                                                                                                  It is highly recommended to provide a
Mounting                                                                                          minimum of 8 feet (2.4 meters) on one side
The inside of the base rail is open to allow access for                                           to allow for coil replacement. A minimum
                                                                                                  of 4 feet (1.2 meters) of side clearance is
securing mounting bolts, etc. Refer to the as-built submittal                                     required; however, the unit performance may
drawings provided by a Daikin Applied sales representative for                                    be derated.
configuration-specific details.                                              B     4 ft (1.2 m)   Control Panel Side:
All compressor bolts, rubber grommets, and fasteners should                                       Minimum of 4 feet (1.2 meters)
be left in place on the base plate as shown in Figure 5. None of             C     4 ft (1.2 m)   Sides:
these fasteners are considered to be ‘temporary shipping bolts.                    if all other   It is highly recommended to provide a
                                                                                   requirements   minimum of 8 feet (2.4 meters) on one side
                                                                                   are met        to allow for coil replacement. A minimum
Figure 5: Compressor Base Plate Mounting                                                          of 4 feet (1.2 meters) of side clearance is
                                                                                                  required; however, the unit performance may
                                                                                                  be derated.
                                                                             D     4 ft (1.2 m)   Opposite Control Panel End:
                                                                                                  Minimum of 4 feet (1.2 meters)
                              CAUTION
 Unit performance may be impacted if the operational clearance
 is not sufficient.
                                                                                                                 NOTICE
                                                                                  Distance between can only be reduced if the 8 ft (2.4 m)
                                                                                  clearance is on the outside of the two units for coil removal.
Case 5: Pit/Solid Wall Installation                                         Table 7: Pit/Solid Wall Installation - % Full Load Capacity
                                                                            Reduction
Pit installations can cause operating problems resulting from air
recirculation and restriction and require care that sufficient air                                             Height of Wall (ft)
clearance is provided, safety requirements are met and service                No. of     Distance
                                                                              Fans      from Wall    Up
access is provided. A solid wall surrounding a unit is substantially                                         10        12       13      14
                                                                                                    to 8
a pit and this data should be used. Derates are based on single                 4           4 ft    0.0%    1.4%     6.0%       NA     NA
chiller installation only.
                                                                                            5 ft    0.0%    0.8%     3.2%      6.0%    NA
Steel grating is sometimes used to cover a pit to prevent
                                                                                            6 ft    0.0%    0.0%     0.8%      1.6%    3.0%
accidental falls or trips into the pit. The grating material
and installation design must be strong enough to prevent                        6-8        < 5 ft    NA      NA       NA        NA     NA
such accidents, yet provide abundant open area to avoid                                     5 ft    0.5%    1.5%     6.0%       NA     NA
recirculation problems. Have any pit installation reviewed by the                           6 ft    0.0%    0.8%     3.2%      6.0%    NA
Daikin Applied sales representative prior to installation to ensure
                                                                                            8 ft    0.0%    0.0%     0.9%      1.6%    3.0%
it has sufficient air-flow characteristics and approved by the
installation design engineer to avoid risk of accident.                         10         < 6 ft    NA      NA       NA        NA     NA
                                                                                            6 ft    0.5%    1.5%     6.0%       NA     NA
Figure 11: Pit/Solid Wall Installation                                                      8 ft    0.0%    0.8%     3.3%      6.0%    NA
                                                                                           10 ft    0.0%    0.0%     0.8%      1.6%    3.0%
                                                                               12-14        6 ft     NA      NA       NA        NA     NA
                                                                                            6 ft    0.8%    1.8%     7.2%       NA     NA
                                                                                            8 ft    0.0%    1.0%     4.0%      7.2%    NA
                                                                                           10 ft    0.0%    0.0%     1.0%      1.9%    3.6%
                                                                              NA = Not Allowed
Application Consideration                                                    • Water pressure gauge connection taps and gauges at the
                                                                               inlet and outlet connections of the evaporator for measuring
                                                                               water pressure drop.
Chilled Water Piping                                                   It is recommended that the field-installed water piping to the
                                                                       chiller include:
All evaporators and condensers have OGS-type grooved water
                                                                             • Thermometers at the inlet and outlet connections of the
connections (adhering to Standard AWWA C606). The installing
                                                                               evaporator.
contractor must provide matching mechanical connections.
Be sure that water inlet and outlet connections match certified              • Vibration eliminators in both the supply and return water
drawings and nozzle markings.                                                  lines.
                                                                             • Insulated chilled water piping to reduce heat loss and
                             NOTICE                                            prevent condensation. For information on freeze protection,
 PVC piping should not be used.                                                see “Evaporator Freeze Protection” on page 15.
                                                                             • Isolation valves installed in the incoming and outgoing water
                            WARNING                                            piping to the evaporator.
 Polyolester Oil, commonly known as POE oil is a synthetic oil                                        NOTICE
 used in many refrigeration systems, and is present in this Daikin
                                                                           Failure to follow these measures may result in performance and
 Applied product. POE oil, if ever in contact with PVC/CPVC, will
                                                                           reliability issues.
 coat the inside wall of PVC/CPVC pipe causing environmental
 stress fractures. Although there is no PVC/CPVC piping in this
 product, please keep this in mind when selecting piping materials     Figure 12: Typical Piping, Brazed-Plate Evaporator
 for your application, as system failure and property damage
 could result. Refer to the pipe manufacturer’s recommendations
 to determine suitable applications of the pipe.
                            CAUTION
 To prevent damage to the evaporator and potential chiller failure,
 a supply strainer is required in the inlet water piping which
 connects to this evaporator. This strainer must be installed prior
 to operation of the chilled liquid pumps.
Field installed water piping to the chiller must include:
   • A cleanable strainer installed at the water inlet to the
     evaporator to remove debris and impurities before they
     reach the evaporator. Install cleanable strainer within 5
     feet (1500 mm) of pipe length from the evaporator inlet                                          NOTICE
     connection and downstream of any welded connections (no               Welded pipe connections are not allowed between the strainer
     welded connections between strainer and evaporator).                  and evaporator due to the chance of slag entering the evaporator.
   • Adequate piping support to eliminate weight and strain on             Evaporator may be oriented with connections on a different side
     the fittings and connections.                                         than shown.
   • A water flow switch must be installed in the horizontal
     piping of the supply (evaporator inlet) water line to avoid
     evaporator freeze-up under low or no flow conditions.
     The flow switch is supplied by the factory as an installed
     component or a field-installed kit shipped along with the
     unit. (See page 16 for more information.)
                             NOTICE
 Units with the optional pump package include the strainer and
 flow switch.
   • Piping for units with brazed-plate evaporators must have
     a drain and vent connection provided in the bottom of
     the lower connection pipe and to the top of the upper
     connection pipe respectively, see Figure 12. These
     evaporators do not have drain or vent connections due to
     their construction.
System Water Considerations                                             Operation of the heaters is automatic through the sensing
                                                                        thermostat that energizes the evaporator heaters for protection
All chilled water systems need adequate time to recognize a load        against freeze-up. Unless the evaporator is drained in the winter
change, respond to the change and stabilize to avoid undesirable        or contains an adequate concentration of glycol, the disconnect
short cycling of the compressors or loss of temperature control.        switch to the evaporator heater must not be open.
In air conditioning systems, the potential for short cycling usually
exists when the building load falls below the minimum chiller           Although the evaporator is equipped with freeze protection,
plant capacity or on close-coupled systems with very small              it does not protect water piping external to the unit or the
water volumes. Some of the things the designer should consider          evaporator itself if there is a power failure or heater burnout, or if
when looking at water volume are the minimum cooling load, the          the chiller is unable to control the chilled water pumps. Use one
minimum chiller plant capacity during the low load period and the       of the following recommendations for additional freeze protection:
desired cycle time for the compressors. Assuming that there are              1.	 If the unit will not be operated during the winter, drain the
no sudden load changes and that the chiller plant has reasonable                 evaporator and chilled water piping and flush with glycol.
turndown, a rule of thumb of “gallons of water volume equal to
                                                                             2.	 Add a glycol solution to the chilled water system. Burst
two to three times the chilled water gpm flow rate” is often used.
                                                                                 protection should be approximately 10°F below minimum
A storage tank may have to be added to the system to reach the
                                                                                 design ambient temperature.
recommended system volume. Refer to AG 31-003 for method of
calculating “Minimum Chilled Water Volume”.                                  3.	 Insulate the exposed piping.
The water quality provided by the owner/occupant/operator/user               4.	 Add thermostatically controlled heat by wrapping the lines
to a chiller system should minimize corrosion, scale buildup,                    with heat tape.
erosion, and biological growth for optimum efficiency of HVAC           When glycol is added to the water system for freeze protection,
equipment without creating a hazard to operating personnel or           the refrigerant suction pressure will be lower, cooling
the environment. Strainers must be used to protect the chiller          performance less, and water side pressure drop greater.
systems from water-borne debris. Daikin Applied will not be
responsible for any water-borne debris damage or water side
damage to the chiller heat exchangers due to improperly treated
                                                                        Chilled Water Pump
water.                                                                  It is important that the chilled water pumps be wired to, and
                                                                        controlled by, the chiller’s microprocessor. When equipped with
Water systems should be cleaned and flushed prior to chiller
                                                                        the optional dual pump output, the chiller controller has the
installation. Water testing and treatment should be verified during
                                                                        ability to remotely send a signal to the pump relay to start pump
initial chiller installation/commissioning and maintained on a
                                                                        A or B, or automatically alternate the pump selection, as well
continuous basis by water treatment professionals (see Limited
                                                                        as enable standby operation. The controller will energize the
Product Warranty).
                                                                        pump whenever at least one circuit on the chiller is enabled to
                                                                        run, whether there is a call for cooling or not. This helps ensure
                            CAUTION
                                                                        proper unit start-up sequence. The pump will also be turned on
 The improper use of detergents, chemicals, and additives in the        when the water temperature goes below the Freeze Setpoint for
 chiller system water may adversely affect chiller performance          longer than a specified time to help prevent evaporator freeze-up.
 and potentially lead to repair costs not covered by warranty.          See the Field Wiring Diagram for connection points.
 Any decision to use these products is at the discretion of the
 owner/occupant/operator/user as such they assume full liability/                                      CAUTION
 responsibility for any damage that may occur due to their use.
                                                                            Adding glycol or draining the system and flushing with an
                                                                            adequate concentration of glycol are the recommended methods
Evaporator Freeze Protection                                                of freeze protection. If the chiller does not have the ability to
Evaporator freeze-up can be a concern in the application of                 control the pumps and the water system is not drained or does
air-cooled water chillers in areas experiencing below freezing              not have adequate glycol in temperatures below freezing,
temperatures. To protect against freeze-up, insulation and an               catastrophic evaporator failure may occur.
electric heater are furnished with the evaporator. All models           Failure to allow pump control by the chiller may cause the
have an external plate heater and thermostat. These heaters             following problems:
help protect the evaporator down to -20°F (-29°C) ambient air
temperature. The evaporator heater cable is factory wired to                 1.	 If the chiller attempts to start without the building
the 115 volt control circuit transformer in the control box. A 115V              automation enabling the pump, the chiller will lock out on
power source for the heater and controls may also be supplied                    the No Flow alarm and require manual reset.
from a separate power feed to maximize unit protection if desired.           2.	 If the chiller evaporator water temperature drops below the
Refer to the field wiring diagram for additional information on                  “Freeze setpoint” the chiller will attempt to start the water
supplying a separate 115V power feed.                                            pumps to avoid evaporator freeze. If the chiller does not
                                                                                 have the ability to start the pumps, the chiller will alarm due
                                                                                 to lack of water flow.
                                                                             3.	 If the chiller does not have the ability to control the pumps
                                                                                 and the water system is not to be drained in temperatures
      below freezing or contain glycol, the chiller may be subject          Glycol Solutions
      to catastrophic evaporator failure due to freezing. The
      freeze rating of the evaporator is based on the evaporator            The use of glycol may impact system performance depending on
      heater and pump operation. The external brazed plate                  its concentration and should be considered during initial system
      heater itself may not be able to properly protect the                 design. When glycol is added to the chilled water system for
      evaporator from freezing without circulation of water.                freeze protection, recognize that the refrigerant suction pressure
                                                                            will be lower, cooling performance less, and water side pressure
                                                                            drop will be higher. The reduction in performance depends upon
Flow Switch                                                                 the glycol concentration and temperature.
All chillers require a chilled water flow switch to check that there
                                                                            Test coolant with a clean, accurate glycol refractometer to
is adequate water flow through the evaporator and to shut the
                                                                            determine the freezing point.
unit down if necessary to avoid evaporator freeze-up under low
or no flow conditions. A factory-included thermal dispersion flow                                       CAUTION
switch will be installed on packaged models.
                                                                             The installed glycol level must align with the rated glycol
Installation should be per manufacturer’s instructions included              percentage indicated on the submitted chiller technical data
with the switch. Flow switches should be calibrated to shut off the          sheet. Failure to adhere to the rated glycol percentage may
unit when operated below the minimum listed flow rate for the                result in unit damage and loss of unit warranty.
unit. Flow switch installation and calibration is further discussed
on page 82.
                                                                                                        CAUTION
Figure 15: Flow Switch                                                       Do not use an automotive-grade antifreeze. Industrial grade
                                                                             glycols must be used. Automotive antifreeze contains inhibitors
                                                                             which will cause plating on the copper tubes within the chiller
                                                                             evaporator. The type and handling of glycol used must be
                                                                             consistent with local codes.
 Standard
 Microchan-    +++          -            -             -
 nel
 Epoxy Coat-
               +++          +++          +++           ++
 ed Coils
NOTE: 1. Non-corrosive environments may be estimated by
      the appearance of existing equipment in the immediate
      area where the chiller is to be placed.
         2. Marine environments should take into consideration
         proximity to the shore as well as prevailing wind
         direction.
         3. Industrial contaminants may be general or localized,
         based on the immediate source of contamination (i.e.
         diesel fumes due to proximity to a loading dock).
         4. Combined marine-industrial are influenced by
         proximity to shore, prevailing winds, general and local
         sources of contamination.
Pump Package
Figure 16: Pump Package Components
Variable Flow with Pump VFD Figure 17: Pump Control Curve
Isolator Information                                                                        In all cases, set the unit in place and level. If anti-skid pads are
                                                                                            used, do not use hold down bolts. If hold down bolts are used, do
                                                                                            not use anti-skid pads.
Figure 18: Spring Isolator
                                     ELASTOMERIC
                                                                                            When spring isolators are required, install springs running under
                                       SNUBBER                                              the main unit supports. Unit should be installed on blocks or
                                                                                            shims at the listed free height. Isolator springs should not be
                                                                                            loaded until the installation is complete, then adjust the springs to
       3
     [76.2]
                  .62 [15.8]
                                                                                            the vendor listed compression for the load point. When securing
                                                                                            the isolator, do not over-tighten the mounting bolts. Over-
                                                                                            tightening may result in cracking of the cast isolator housing and
                                        9.25 [235.0]                                        will have a negative impact on the isolation effect.
                                        10.5 [266.7]
                                                                                            Installation of spring isolators requires flexible piping connections
     .625
                                        7.75 [196.9]
                                                                                            and at least three feet of flexible electrical conduit to avoid
                                                        .5 [12.7] DIA.
     [15.9]                                            POSITIONING
                                                                         .25 TO .5 GAP
                                                                                            straining the piping and transmitting vibration and noise.
                                                             PIN
                                                                                            Neoprene waffle pads, supplied by customers, should be
                                                                           [6.4 to 12.7]
                                                        ADJ. BOLT                           mounted at the defined mounting point locations along the full rail
     6.25                                                                                   length.
    [127.0]
  FREE HT.                                                                                  Contact a Daikin Applied sales representative for isolator
                                                                                            information related to units with other fin materials.
  5\X [127.0]
  OPER. HT.
                                                                                            Pump Controller
                .56 [14.3]
                         .25 [6.4]
                   ELASTOMERIC PAD
                            NOTICE
 AGZ-F chiller VFD controllers support only BACnet MS/TP and
 Modbus communications. Daikin Applied does not support other
 protocol options that may be offered by the VFD manufacturer.
Configuring the VFD Controller for                                    Table 14: Modbus Network Parameters
Modbus Communication                                                      Parameter          Value (Range)/Definition                 Default Value
                                                                          8-02 Control
The VFD controller (frequency controller) is a native Modbus                                FC Port [1]/ On-board RS-485 port         FC Port [1]
                                                                          Source
device. In other words, it does not require any additional
                                                                                            Modbus RTU [2]/The protocol set-
communication card or other hardware for integration into a               8-30 Protocol
                                                                                            ting for the communication port
                                                                                                                                      FC [0]
building automation system (BAS) via the Modbus network. The                                1-247/The Modbus Address of
configuration process is described in the following section. It is                          VFD; this address must be unique
                                                                          8-31 Address                                                1
assumed that the user is familiar with Modbus technology and                                throughout the entire Modbus
terminology.                                                                                network.
                                                                                            2400 - 115200/This value should
Standard Modbus network rules apply. The network is a daisy-              8-32 Baud Rate    be set the same as all other devic-       9600 baud [2]
chain of unit controllers including the master (in this case, the                           es on the trunk.
BAS) and all slaves (VFD controller). The Modbus standard                                   Even parity, 1 stop bit [0]; Odd
recommends that the network be terminated on each end with                8-33 Parity/
                                                                                            Parity, 1 Stop Bit [1]; No Parity,
                                                                                                                                      Even parity, 1
the characteristic impedance of the network (about 120 ohms).                               1 Stop Bit [2]; No Parity, 2 Stop
                                                                          Stop Bits                                                   stop bit [0]
                                                                                            Bits [3]/Set to match the network
Follow the guidelines stated in the Modbus specifications.
                                                                                            settings
Steps for Modbus Configuration                                        NOTE: Remaining items in menus 8-* should likely remain at factory defaults. See
                                                                            VFD installation manual for further details.
Table 14 defines the network parameters of the Modbus
Communication Module that are available via the graphical             Figure 20: Modbus RTU Connection
interface. The Modbus network address and data transmission
rate (Baud Rate) are available via the local control panel. At
a minimum, you must set the network address and verify the
correct baud rate before establishing network communication
between the VFD controller and the BAS. Change remaining
parameters as required for your network.
  1.	 Set the Modbus network parameters as described in Table
      14. It is recommended that remaining items in menus 8-*
      remain at factory defaults. See VFD installation manual,
      available on www.DaikinApplied.com for further details.
  2.	 Cycle power to the VFD controller for changes to take
      effect.
  3.	 Verify connection from BAS to VFD - terminals 68 (+) and
      69 (-) on the main control board of the frequency converter.
  4.	 The VFD controller is now ready for network configuration
      from the BAS. Refer to the Modbus Operations Manual
      for the AGZ-F VFD Controller, which is available on www.
      DaikinApplied.com, for a complete points list and additional
      configuration information.
                                                                                                          WARNING
                                                                               Improper installation can cause refrigerant migration, flood back,
                                                                               oil loss, line corrosion, or mechanical failures.
                                                                                                          CAUTION
                                                                               Glycol is not allowed to be used in AGZ-F remote evaporator
                                                                               installations.
                                                                              For installations where the evaporator is installed either above or
                                                                              below the unit - the following recommendations apply:
Table 15: Remote Evaporator Piping Limitations                                   Table 18: Additional Oil Charge
                                              SE 002-004       SE 006-014
 Piping Restriction                                                                   Suction Line       Suction          Liquid Line        Liquid
                                              HE 002-006       HE 008-014
                                                                                       Diameter       Addition (oz/ft)     Diameter       Addition (oz/ft)
 Maximum measured actual piping
 distance between the unit and the            90 ft            150 ft                      7/8             0.002              7/8               0.060
 remote evaporator                                                                        1 1/8            0.003             1 1/8              0.103
 Maximum total equivalent feet of
 distance between the unit and                                                            1 3/8            0.005             1 3/8              0.156
                                              150 ft           300 ft
 evaporator including friction losses of                                                  1 5/8            0.007             1 5/8              0.221
 elbows and traps
                                                                                          2 1/8            0.012             2 1/8              0.385
 Horizontal sections of the suction lines must be downward                                3 1/8            0.026             3 1/8              0.848
 sloping toward the compressor with 1 inch slope per 10 foot of
 piping run to assist oil return.                                                Additional Piping Installation Guidelines
                                                                                 The brazed-plate evaporators have no charge and are not
Table 16: Fitting Losses Equivalent Feet of Pipe                                 sealed. A holding charge of an inert gas, such as nitrogen,
                                                                                 is provided for the outdoor condensing unit. Holding charges
                                                  90° Std.       90° Long        must be evacuated prior to the R-32 charging procedure. The
  Line Size       Angle           Globe
                                                  Radius          Radius
    In.OD         Valve           Valve                                          interconnecting refrigerant piping and the total system refrigerant
                                                   Elbow          Elbow
                                                                                 charge are field supplied and installed.
     7/8            9.0            22.0                2.0           1.4
    1 1/8          12.0            29.0                2.6           1.7                                        CAUTION
    1 3/8          15.0            38.0                3.3           2.3
                                                                                     Ensure all isolation valves are shut and not leaking before
    1 5/8          18.0            43.0                4.0           2.6
                                                                                     performing a leak test. Failure to do so may result in unit damage
    2 1/8          24.0            55.0                5.0           3.3
                                                                                     and loss of unit warranty.
    2 5/8          29.0            69.0                6.0           4.1
    3 1/8          35.0            84.0                7.5           5.0         After evacuating piping system to 500 microns or below, the
                                                                                 system cannot rise over 300 microns within an hour. Insulate the
SOURCE:             ASHRAE 2014 Handbook Refrigeration
                                                                                 suction line to reduce excessive superheat build-up. Insulate the
                                 NOTICE                                          liquid line to prevent loss of subcooling and consequent liquid
                                                                                 flashing.
 TEL values for the filter-drier and solenoid valve are already
 included and should not be added to the liquid line drop.                       The use of double risers for vertical gas risers is not allowed.
                                                                                 Size the single vertical riser per Table 19 and Table 20 on page
                                                                                 28. A small trap must be provided at the base of each major
Additional Refrigerant and Oil Charge                                            vertical gas riser to assist in the collection of oil. If vertical risers
Depending on the length of piping needed, additional refrigerant                 exceed more than 20 feet, install a second trap per guidelines
and oil charge will be needed. See Table 17 and Table 18 for                     above. Follow ASHRAE procedures and refrigerant piping
specific requirements.                                                           guidelines. Exceeding these recommendations will decrease
                                                                                 performance and could impact system reliability.
Table 17: Additional R-32 Line Charge                                            Use caution in sizing the liquid line in applications where the
                                                                                 evaporator is above the outdoor section. The weight of the liquid
  Suction Line        Suction              Liquid Line          Liquid           refrigerant in the vertical column will decrease the pressure at
   Diameter        Addition (oz/ft)         Diameter         Addition (oz/ft)
                                                                                 the top of the riser (approximately 0.5 psi per foot of vertical
      7/8                 0.09                 7/8                3.01           rise) allowing some of the refrigerant to flash to a gas. Adequate
      1 1/8               0.16                1 1/8               5.14           refrigerant subcooling is needed at the outdoor section to prevent
      1 3/8               0.24                1 3/8               7.82           refrigerant gas at the expansion valve.
      1 5/8               0.34                1 5/8               11.07          Care should be taken while designing piping system to avoid the
                                                                                 draining of condensed refrigerant to the lower component when
      2 1/8               0.59                2 1/8               19.26
                                                                                 normal shut-down procedures do not occur (such as a power
      2 5/8               0.90                2 5/8               29.70          failure).
      3 1/8               1.29                3 1/8               42.40
Remote evaporator units include a Refrigerant Specialties Kit             The liquid line filter drier must be installed at the remote
which supplies the following field-installed components:                  evaporator, upstream of the liquid solenoid valve and expansion
                                                                          valve.
   • Expansion Valves
   • Liquid Line Solenoid Valve and DIN Connector                            • Install a ball valve before and after the filter drier
   • Liquid Line Filter Drier with Filter Drier Core and Clamp               • Only charging valve installed for remote evap. is on suction
                                                                               line
   • Liquid Line Sight Glasses
                                                                             • Use schrader fitting on ball valves before and after filter
   • Liquid Line Ball Valves
                                                                               drier to maeasure pressure drop
   • Charging Valve
   • Suction Line Temperature Sensor Tube                                 Hot Gas Bypass Applications
   • Schrader and Schrader Core for Suction Line Transducers              Provide condenser fan VFDs for applications when operation
   • Suction Pressure Transducer                                          below 32°F ambient is expected and hot gas bypass is desired.
   • Check Valve for Hot Gas Bypass Line (specific installation           This is necessary to maintain adequate condensing pressures
     requirements)                                                        and liquid refrigerant at the expansion valve when condenser
                                                                          capacities are at their minimum.
Field Installed Component Locations                                       Referencing the refrigerant piping schematics, the solenoid valve
The following components must be installed adjacent to the                and hot gas bypass valve need to be as close to the condensing
remote evaporator.                                                        unit as possible.
The expansion valves must be installed within 12 inches of the            If at the same elevation or if evaporator is below the condensing
evaporator inlet connection and the outlet piping of the expansion        unit, the hot gas bypass piping must be downward sloping toward
valve must go directly into the evaporator with no bends in               the evaporator with a 1inch drop per 10 ft of piping run in the
between.                                                                  direction of flow.
The liquid line solenoid valves must be installed within 3 ft of          If the evaporator is above the condensing unit, add a check
the evaporator. The liquid line solenoid valve cable must be              valve in the hot gas bypass piping at the evaporator to prevent
connected to the solenoid valve using a junction box to extend            refrigerant condensing in the line, which results in loss of
the wiring to the length required to reach the solenoid.                  subcooling.
Table 19: Remote Evaporator Recommended Line Sizes - Standard Efficiency Models
                                   Liquid Size
                                                                                              Suction Line Size Recommendation
                                 Recommendation
Unit Model   Fans   Compressor                        Up to 50        Up to 75        Up to 100       Up to 125       Up to 150       Up to 200       Up to 250     Up to 300
                                    All Equiv ft
                                                      Equiv. ft       Equiv. ft       Equiv. ft       Equiv. ft       Equiv. ft       Equiv. ft       Equiv. ft     Equiv. ft
                                  Cir. 1    Cir. 2   Cir. 1 Cir. 2 Cir. 1 Cir. 2 Cir. 1 Cir. 2 Cir. 1 Cir. 2 Cir. 1 Cir. 2 Cir. 1 Cir. 2 Cir. 1 Cir. 2 Cir. 1 Cir. 2
AGZ002F 2 DDNNDDNN 7/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8
AGZ002F 2 GGNNFFNN 7/8 7/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8
AGZ002F 2 GGNNGGNN 7/8 7/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8
AGZ004F 4 JJNNHHNN 7/8 7/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8 1 3/8
AGZ004F 4 JJNNJJNN 7/8 7/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8
AGZ004F 4 LLNNJJNN 1 1/8 7/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8
AGZ004F 4 LLNNLLNN 1 1/8 1 1/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8
AGZ004F 4 LPNNLLNN 1 1/8 1 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
AGZ004F 4 LPNNLPNN 1 1/8 1 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
AGZ006F 6 SPNNLLNN 1 1/8 1 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
AGZ006F 6 SSNNLLNN 1 1/8 1 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
AGZ006F 6 SUNNLLNN 1 3/8 1 1/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ006F 6 SVNNLPNN 1 3/8 1 1/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ006F 6 UUNNLPNN 1 3/8 1 1/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ008F 8 SUNNSUNN 1 3/8 1 3/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ008F 8 UUNNSUNN 1 3/8 1 3/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ008F 8 UUNNUUNN 1 3/8 1 3/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ010F 10 VVNNUUNN 1 5/8 1 3/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ010F 10 SVSNSSSN 1 5/8 1 3/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 3 1/8 2 5/8
AGZ010F 10 SVVNSSSN 1 5/8 1 3/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8
AGZ012F 12 SVVNSSVN 1 5/8 1 5/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8
AGZ012F 12 SVVNSVVN 1 5/8 1 5/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8
AGZ014F 14 VVVNUUUN 1 5/8 1 5/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8
Table 20: Remote Evaporator Recommended Line Sizes - High Efficiency Models
                                   Liquid Size
                                                                                              Suction Line Size Recommendation
                                 Recommendation
Unit Model   Fans   Compressor                        Up to 50        Up to 75         Up to 100      Up to 125       Up to 150        Up to 200       Up to 250     Up to 300
                                    All Equiv ft
                                                      Equiv. ft       Equiv. ft        Equiv. ft      Equiv. ft       Equiv. ft        Equiv. ft       Equiv. ft     Equiv. ft
                                  Cir. 1    Cir. 2   Cir. 1 Cir. 2 Cir. 1 Cir. 2 Cir. 1 Cir. 2 Cir. 1 Cir. 2 Cir. 1 Cir. 2 Cir. 1 Cir. 2 Cir. 1 Cir. 2 Cir. 1 Cir. 2
AGZ004F 4 DDNNDDNN 7/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8
AGZ004F 4 GGNNFFNN 7/8 7/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8
AGZ004F 4 GGNNGGNN 7/8 7/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8
AGZ006F 6 JJNNHHNN 7/8 7/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8
AGZ006F 6 JJNNJJNN 7/8 7/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8
AGZ006F 6 LLNNJJNN 1 1/8 7/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 1 5/8 2 1/8 1 5/8 2 1/8 1 5/8
AGZ006F 6 LPNNJJNN 1 1/8 7/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
AGZ006F 6 PPNNJJNN 1 1/8 7/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
AGZ006F 6 PPNNLLNN 1 1/8 1 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
AGZ008F 8 LPNNLPNN 1 1/8 1 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
AGZ008F 8 PPNNLPNN 1 1/8 1 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
AGZ008F 8 PSNNPSNN 1 1/8 1 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
AGZ008F 8 SSNNSSNN 1 1/8 1 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8
AGZ010F 10 SUNNSSNN 1 3/8 1 1/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ010F 10 UUNNSSNN 1 3/8 1 1/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ010F 10 UUNNSUNN 1 3/8 1 3/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ012F 12 UUNNUUNN 1 3/8 1 3/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ012F 12 VVNNUUNN 1 5/8 1 3/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ012F 12 VVNNVVNN 1 5/8 1 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8
AGZ014F 14 SSVNSSSN 1 5/8 1 3/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 2 5/8 3 1/8 2 5/8
AGZ014F 14 UUUNSSSN 1 5/8 1 3/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8
AGZ014F 14 SVVNSSVN 1 5/8 1 5/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8 3 1/8
  No.    Description
   1     Individual wire interconnects (for 120V) - field provided 14 AWG (red x2 ea., white x1 ea., green x1 ea.)
   2     18 AWG 2-conductor shield cable (field provided unit evaporator sensor box connect cable - TB03 - TB12 for terminals: EEWT & ELWT
   3     18 AWG 3-conductor shielded communications cable for Modbus cable routed to chiller unit controller UC01:FBUS2
                                                                      NOTICE
 All wires in Figure 23 are specified by Daikin Applied and field provided.
 Evaporator   Evaporator Model             Minimum Flow Rate                        Nominal Flow Rate                  Maximum Flow Rate
    Part
                                   GPM       DP ft    l/s    DP kPa         GPM       DP ft   l/s    DP kPa    GPM       DP ft   l/s    DP kPa
  Number
 332955701     ACK240DQ-58AH       36.0       1.3     2.3       4.0         72.0      7.2     4.5       21.6   144.0     32.7    9.1       97.9
 332955702     ACK240DQ-66AH       42.0       1.6     2.6       4.7         84.0      7.8     5.3       23.4   168.0     34.4    10.6   102.8
 332955703     ACK240DQ-78AH       54.0       2.2     3.4       6.6         108.0     9.7     6.8       29.0   216.0     40.7    13.6   121.6
 332955704     ACK240DQ-86AH       60.0       2.4     3.8       7.2         120.0     10.0    7.6       30.0   240.0     41.1    15.1   122.9
 332955705     ACK240DQ-98AH       66.0       2.5     4.2       7.4         132.0     9.6     8.3       28.8   264.0     38.0    16.7   113.6
 332955706    ACK240DQ-106AH       72.0       2.7     4.5       8.0         144.0     10.0    9.1       29.8   288.0     38.5    18.2   114.9
 332955707    ACK240DQ-114AH       66.0       2.1     4.2       6.4         132.0     7.5     8.3       22.5   264.0     28.1    16.7      84.0
 332955708    ACK240DQ-122AH       78.0       2.7     4.9       8.1         156.0     9.3     9.8       27.7   312.0     33.9    19.7   101.4
 332955710    ACK240DQ-138AH       84.0       2.8     5.3       8.4         168.0     8.9     10.6      26.5   336.0     30.7    21.2      91.9
 332955711    ACK240DQ-142AH       90.0       3.1     5.7       9.2         180.0     9.6     11.4      28.7   360.0     33.1    22.7      98.9
 332955712    ACK240DQ-154AH       96.0       3.2     6.1       9.6         192.0     9.6     12.1      28.8   360.0     28.5    22.7      85.1
 332955713    ACK240DQ-170AH       108.0      3.6     6.8      10.9         216.0     10.3    13.6      30.8   360.0     24.0    22.7      71.6
 332955714    ACK240DQ-194AH       120.0      4.0     7.6      11.8         240.0     10.5    15.1      31.3   360.0     19.5    22.7      58.3
 332955715    ACK240DQ-210AH       138.0      4.6     8.7      13.8         276.0     11.8    17.4      35.4   360.0     17.5    22.7      52.3
NOTE: Exceeding max flow rates can cause erosion damage to the evaporator.
      Each channel count has its own maximum flow rate and the frame itself has an maximum flow rate of 360 GPM.
 Evaporator   Evaporator Model             Minimum Flow Rate                        Nominal Flow Rate                  Maximum Flow Rate
    Part
                                   GPM       DP ft    l/s    DP kPa         GPM       DP ft   l/s    DP kPa    GPM       DP ft   l/s    DP kPa
  Number
 332956501     ACK502-DQ-162       150.0      2.9     9.5       8.7         300.0     11.2    18.9      33.4   501.0     30.7    31.6      91.7
 332956503     ACK502-DQ-190       168.0      3.3     10.6      9.8         336.0     11.1    21.2      33.0   528.0     25.4    33.3      76.0
 332956504     ACK502-DQ-206       192.0      4.0     12.1     11.8         384.0     12.6    24.2      37.8   528.0     22.3    33.3      66.6
 332956505     ACK502-DQ-234       204.0      4.2     12.9     12.5         408.0     12.1    25.7      36.2   528.0     18.5    33.3      55.3
 332956506     ACK502-DQ-254       216.0      4.5     13.6     13.4         432.0     12.2    27.3      36.6   528.0     16.7    33.3      50.0
NOTE: Exceeding max flow rates can cause erosion damage to the evaporator.
      Each channel count has its own maximum flow rate and the frame itself has an maximum flow rate of 360 GPM.
 Evaporator    Evaporator Model             Minimum Flow Rate                       Nominal Flow Rate                  Maximum Flow Rate
    Part
                                    GPM       DP ft    l/s   DP kPa         GPM       DP ft    l/s   DP kPa    GPM       DP ft   l/s    DP kPa
  Number
 332956402    ACH1000DQ-166AH       240.0      3.8    15.1      11.3        480.0     13.4    30.3      40.2   801.6     35.6    50.6   106.3
 332956452
 332956403    ACH1000DQ-178AH       264.0      4.0    16.7      12.0        528.0     14.2    33.3      42.4   881.0     37.3    55.6      111.4
 332956453
 332956404    ACH1000DQ-182AH       276.0      4.2    17.4      12.6        552.0     14.8    34.8      44.2   881.0     35.7    55.6   106.8
 332956454
NOTE: Exceeding max flow rates can cause erosion damage to the evaporator.
      Each channel count has its own maximum flow rate and the frame itself has an maximum flow rate of 360 GPM.
Electrical Data                                                        Power wiring connections to the chiller may be done with either
                                                                       copper or aluminum wiring, provided the wire size and count fit in
                                                                       the chiller lugs provided. All wiring must be done in accordance
                                                                       with applicable local and national codes, including NECA/AA
Electrical Connection                                                  10402012, Standard for Installing Aluminum Building Wire and
Trailblazer units can be ordered with either standard single-point     Cable (ANSI). Wiring within the unit is sized in accordance with
power or optional multi-point power connections and with various       the NEC®. Refer to the unit nameplate and the unit selection
disconnect and circuit breaker options. Wiring within the unit is      report for the correct electrical ratings.
sized in accordance with the NEC®.                                          1.	 The control transformer is furnished and no separate 115V
                               NOTICE                                           power is required. For both single and multi-point power
                                                                                connections, the control transformer is in circuit #1 with
Wiring, fuse, and wire size must be in accordance with the
                                                                                control power wired from there to circuit #2. In multi-point
National Electrical Code® (NEC). The voltage to these units must
                                                                                power, disconnecting power to circuit #1 disconnects
be within ±10% of nameplate voltage (415V units must have
                                                                                control power to the unit.
voltage within -13% and +6% of nameplate voltage) and the
voltage unbalance between phases must not exceed 2%. Since                  2.	 Wire sizing supplied to the control panel shall be in
a 2% voltage unbalance will cause a current unbalance of 6 to 10                accordance with field wiring diagram.
times the voltage unbalance per the current version of the NEMA             3.	 Single-point power supply requires a single disconnect to
MG-1 Standard, it is most important that the unbalance between                  supply electrical power to the unit. This power supply must
phases be kept at a minimum.                                                    either be fused or use a circuit breaker.
                                                                            4.	 All field wire lug range values given unit selection report
Table 29: Power Connection Availability
                                                                                apply to 75°C rated wire per NEC.
                                 Comp.                                      5.	 Must be electrically grounded according to national and
                       Disc.             Panel High Short Circuit
 Power Connection                Circuit
                       Swt.                  Current Rating                     local electrical codes.
                                Breakers
  Std. Single Point     Std.      Std.               Std.                                             CAUTION
   Opt. Multi-Point     Opt.      Opt.               Opt.                  A static discharge while handling circuit boards can cause
                                                                           damage to components. Use a static strap before performing
Required field wiring varies depending on unit configuration. See          any service work. Never unplug cables, circuit board terminal
wiring diagram information. Voltage limitations are:                       blocks, or power plugs while power is applied to the panel.
  1.	 Voltage must be within 10 percent of nameplate rating.
  2.	 Voltage imbalance not to exceed 2%. Since a 2% voltage           Panel High Short Circuit Current Rating
      imbalance can cause a current imbalance of 6 to 10 times         The AGZ F control panels are designed with High Short Circuit
      the voltage imbalance per the NEMA MG-1 Standard, it is          Capacity (HSCCR) ratings, these ratings can vary by size and
      important that the imbalance between phases be kept at a         voltage. Please consult the unit data plate or submittal data for
      minimum.                                                         the value.
                               DANGER
 Qualified, licensed electricians must perform wiring. Electrical
 shock hazard exists that can cause severe injury or death.
                               DANGER
 LOCKOUT/TAGOUT all power sources prior to starting,
 pressurizing, de-pressuring, or powering down the Chiller.
 Disconnect electrical power before servicing the equipment,
 including condenser fan motors or compressors. More than one
 disconnect may be required to de-energize the unit. Failure to
 follow this warning exactly can result in serious injury or death.
 Be sure to read and understand the installation, operation, and
 service instructions within this manual.
Generator Sizing
                           WARNING
 Generator must be sized by an electrical engineer familiar with
 generator applications.
                           WARNING
 Stop the chiller before transferring supply power from the
 generator back to the utility power grid. Transferring power while
 the chiller is running can cause severe chiller damage.
To properly reconnect power from the generator back to the utility
grid, configure the transfer switch provided with the generator to
automatically shut down the chiller before transfer is made. The
automatic shut-off function can be accomplished through a BAS
interface or with the “remote on/off” wiring connection shown in
the field wiring diagrams.
A start signal can be given any time after the unit has stopped
since the unit will use the normal start up sequence to restart.
Field Wiring
Figure 28: Field Wiring for Single Point
Table 31: Digital Inputs                                                      N08      Fan Contactor            Fan(s) Off             Fan(s) On
                                                                                       (K202)
 #       Description                 Signal Off        Signal On              N09      Compressor #2            Compressor Off         Compressor On
 ID1     Unit Switch                 Unit Disable      Unit Enable                     (CMK2)
 ID2     Motor Protect Relay         Fault             No Fault               N010     Compressor #4            Compressor Off         Compressor On
         Circuit 1 (MP01)                                                              (CMK4)
 ID3     Motor Protect Relay         Fault             No Fault               N011     See Table 33 and Table 34 Below
         Circuit 2 (MP02)                                                     N012     Evaporator Water         Pump Off               Pump On
 ID4     High Press Switch Circuit   Fault             No Fault                        Pump 1
         1 (HPR1)                                                             N013     Evaporator Water         Pump Off               Pump On
 ID5     High Press Switch Circuit   Fault             No Fault                        Pump 2
         2 (HPR2)                                                           NOTE: Digital outputs N06 and N011 are dependent on how
 ID6     Transformer High Tem-       Fault             No Fault                   the unit is configured. There are two options as outlined
         perature Switch (TX1R)                                                   in Table 33 and Table 34 below.
         (OPT for TX01)
 ID7     Evaporator Flow Switch      No Flow           Flow                 Table 33: Digital Outputs (Less than 6 Compressors)
 ID8     Phase Voltage Monitor       Fault             No Fault
         Circuit 1 (PVM1)                                                     #         Description                       Output Off       Output On
 ID9     Phase Voltage Monitor       Fault             No Fault               N06       Fan Contactor (K103)              Fans Off         Fans On
         Circuit 2 (PVM1)
                                                                              N011      Fan Contactor (K203)              Fans Off         Fans On
 ID10    Ground Fault Circuit 1      Fault             No Fault
         (GFM1) (OPT)
                                                                            Table 34: Digital Outputs (6 Compressors)
 ID11    Ground Fault Circuit 2      Fault             No Fault
         (GFM2) (OPT)
                                                                              #         Description          Output Off            Output On
 ID12    External Alarm/Event        External Fault    No External
                                                       Fault                  N06       Compressor #5        Compressor Off        Compressor On
                                                                                        (CMK5)
 ID13    Double Set Point/Mode       Use alternate mode or LWT
         Switch                      set point. See sections on Unit          N011      Compressor #6        Compressor Off        Compressor On
                                     Mode Selection and LWT Target.                     (CMK6)
 ID14    Remote Switch               Remote Dis-       Remote
                                     able              Enable               Table 35: Expansion Valve Outputs
Table 38: Digital Outputs                                                   Table 42: Stepper Motor Driver Configuration - Packaged
                                                                            Unit Models)
         Description                Output Off           Output On
         Liquid Line Solenoid                                                           Parameter                   Value                         Unit
 N01                                Solenoid Off         Solenoid On
         Circuit 1 (LLS1)                                                               Total Steps                   600                         steps
         Hot Gas Bypass Circuit                                                      Movement Speed                   160                    steps/sec
 N02                                Solenoid Off         Solenoid On
         1 (SV1)
                                                                                       Move Current                   800                         mA
         Liquid Line Solenoid
 N03                                Solenoid Off         Solenoid On                    Hold Current                  160                         mA
         Circuit 2 (LLS2)
         Hot Gas Bypass Circuit                                                         Duty Cycle                     50                          %
 N04                                Solenoid Off         Solenoid On
         2 (SV2)                                                                      Full Close Steps                600                         steps
         Four Way Valve Circuit 1   Solenoid Off         Solenoid On                 Extra Open Enable              False                          n/a
 N05
         (FWV1)                     (Cool)               (Heat)
                                                                                     Extra Close Enable               True                         n/a
         Four Way Valve Circuit 2   Solenoid Off         Solenoid On
 N06
         (FWV2)                     (Cool)               (Heat)
                                                                            Table 43: Stepper Motor Driver Configuration (Remote
Expansion Module (Main Box)                                                 Evaporator Models)
N01 Fan Contactor (K103) Fan(s) Off Fan(s) On Overdrive Block Time 1440 min
N02 Fan Contactor (K104) Fan(s) Off Fan(s) On Valve Neutral Zone 0 %
Configuration Validation
A configuration will be marked as invalid if the operator enters an           The stage up deadband is the measure of how far the leaving
invalid compressor code. An invalid compressor code is a code                 water temperature be must above the target to trigger a stage up
not listed in the tables above.                                               in capacity.
                                                                              The stage down deadband is the measure of how far the leaving
Calculations                                                                  water temperature be must below the target to trigger a stage
The calculations in this section are used in unit level control logic         down in capacity.
or in control logic across all circuits.
                                                                              Figure 31: Capacity Staging Deadbands
Evaporator Delta T
The evaporator water delta T is calculated as entering water
temperature minus leaving water temperature.
LWT Slope
LWT slope is calculated such that the slope represents the
estimated change in LWT over a time frame of one minute.
Pulldown Rate
The slope value calculated above will be a negative value as the
water temperature is dropping. A pulldown rate is calculated by
inverting the slope value and limiting to a minimum value of 0°F/
min.
                                                                                No.        Description
                                                                                  -          Off          -              -             -      Disable
                                                                                              -        Disable           -             -      Disable
                                                                                Local
Using the predicted capacity change for staging up, the resulting                            On         Enable           -             -      Enable
change in leaving water temperature is predicted.
                                                                                              -           -             Off            -      Disable
                                                                               Remote
                                                                                             On           -             On             -      Enable
                                                                                              -           -              -        Disable     Disable
Using the change in leaving water temperature, the stage up                    Network
                                                                                             On           -              -        Enable      Enable
control band is calculated.
Unit Enable
Enabling and disabling the chiller is accomplished using set
points and inputs to the chiller. The Unit Switch input and the Unit
Enable HMI Set Point are both required to be On/Enable for the
unit to be enabled when the control source is set to ‘Local’. If the
control source is set to ‘Remote’, the Unit Switch and Remote
Switch inputs are both required to be On/Enable for the unit to be
enabled. If the control source is set to ‘Network’, the Unit Switch
input and BAS Enable set point must both be On/Enable for the
unit to be enabled.
Figure 32: Transitions between these states are shown in the           T4 – Shut Down to Alarm
following diagram.                                                     All of the following are required:
                                                                          • A Unit Fault is present
                                                                       T6 – Off to Alarm
                                                                       All of the following are required:
                                                                          • A Unit Fault is present
                                                                       T7 – Alarm to Off
                                                                       All of the following are required:
                                                                          • No Unit Faults are present
The operation of the chiller in response to OAT dropping below               Alarm                  Low OAT Lockout
the Low OAT Lockout set point is configurable if the chiller has             Type                   Problem
variable speed condenser fans. In that case, there are three
                                                                             Displayed Text       Message        Module     Module ID       Payload
options:                                                                                           Code           Type
   • Lockout and Stop – Chiller will shut down and lockout.                  Alarm Parts                65          1            0             0
   • Lockout only – Chiller does not shut down running circuits,             Alarm Code             1090584576
     will lock out circuits that are off.
                                                                             Trigger                Trigger conditions are defined in the sections
   • Disabled – Chiller does not shut down or lock out.                                             above
For chillers without condenser fan VFDs, there is no                         Action Taken:          No Action
configuration, and the chiller will always operate according to the          Reset                  Clearing conditions are defined in the section
first option shown above. Descriptions of the operation for each                                    above
option are in the following sections. Low ambient lockout logic
resides on the PC.
                                                                         Unit Status
Lockout and Stop Operation                                               Unit Status is displayed to indicate the general operating
                                                                         condition of the unit. The following table lists the text displayed
When the chiller is configured for lockout and stop, it will operate
                                                                         for each unit status and the conditions that enable each status.
as described in this section.
                                                                         If more than one status is enabled at the same time, the highest
If the OAT drops below the low ambient lockout set point and the         numbered status overrides the others and is displayed.
OAT sensor fault is not active, low ambient lockout is triggered.
The unit will perform a normal shutdown if any circuits are              Table 55: Unit Status
running. Once all circuits shut off, the unit will remain in the off
state until the lockout has cleared. This condition will clear when          #      Status                      Conditions
OAT rises to the lockout set point plus 2.5°C (4.5°F).                       0      None                        There is an initialization error
                                                                             1      Auto                        Unit State = Auto
Lockout Only Operation                                                       2      Off:Low OAT Lockout
                                                                                                                Unit State = Off and low ambient
                                                                                                                lockout is active
When the chiller is configured for lockout only, it will operate as
                                                                                                                Unit State = Auto and all circuits or
described in this section.                                                   3      Auto:All Disabled
                                                                                                                compressors are disabled
If OAT drops below the low ambient lockout set point and any                 4      Alarm                       Unit State = Off and Unit Alarm active
circuits are running, then those circuits will be allowed to remain          5      Off:HMI Disable
                                                                                                                Unit State = Off, Control Source =
running, and the unit will not enter the low ambient lockout                                                    Local, and Local Enable = Disable
condition. Circuits that are not running will enter a circuit level                                             Unit State = Off, Control Source =
                                                                             6      Off:Remote Switch
lockout condition when OAT drops below the lockout set point.                                                   Remote, and Remote Switch is open
This condition will clear at the circuit level when OAT rises to the                                            Unit State = Off, Control Source =
                                                                             7      Off:BAS Disable
                                                                                                                Network, and BAS Enable = false
lockout set point plus 2.5°C (4.5°F).
                                                                                                                Unit State = Off and Unit Switch =
                                                                             8      Off:Unit Switch
If the OAT is below the low ambient lockout set point, the OAT                                                  Disable
sensor fault is not active, and neither circuit is running, low              9      Off:Test Mode               Unit State = Off and Unit Mode = Test
ambient lockout is triggered. The unit will go directly into the off                                            Unit State = Off and Unit Mode = Ice
                                                                             10     Off:Ice Mode Timer
state and will remain in the off state until the lockout has cleared.                                           and Ice Mode Timer = Active
This condition will clear when OAT rises to the lockout set point            11     Auto:Wait For load
                                                                                                                Unit State = Auto, no circuits running,
plus 2.5°C (4.5°F).                                                                                             and LWT is less than startup temp
                                                                                                                Unit State = Auto and Evaporator
                                                                             12     Auto:Evap Recirculate
Disabled Option                                                                                                 State = Start
                                                                                                                Unit State = Auto, Evaporator State =
When the chiller is configured to disable low ambient lockout, the           13     Auto:Wait For Flow
                                                                                                                Start, and Flow Switch is open
unit will not enter the low ambient lockout condition or shut down           14     Shutdown                    Unit State = Shutdown
any running circuits regardless of the OAT.                                                                     Unit State = Auto, max pulldown rate
                                                                             15     Auto:Max PDR
                                                                                                                has been met or exceeded
BAS Annunciation                                                                                                Unit State = Auto, unit capacity limit
                                                                             16     Auto:Unit Cap Limit
                                                                                                                has been met or exceeded
Low Ambient Lockout is not an alarm, but it can be annunciated
                                                                                                                Unit State = Auto and transformer high
to the BAS as if it is one. When the Low OAT Lockout BAS Alert               17     Auto:Trns Hold
                                                                                                                temperature hold is active
setpoint is set to On and the low ambient lockout is active, the
                                                                                                                Unit State = Auto and high ambient
following alarm will trigger:                                                18     Auto:High Amb Limit
                                                                                                                capacity limit is active
                                                                                                                Unit State = Auto and normal Rapid
                                                                             19     Auto:Rapid Restore
                                                                                                                Restore is active
                                                                              Pump Selection
                                                                              The pump output used will be determined by the Pump Control
                                                                              Mode set point. This setting allows the following configurations:
                                                                             Circuit Status
                                                                             The displayed circuit status should be determined by the
                                                                             conditions in the following table. If more than one status is
                                                                             enabled at the same time the highest numbered status overrides
                                                                             the others and is displayed.
                                                                              #       Status             Conditions
                                                                              0       None               There is an initialization error.
                                                                              1       Off:Ready          Circuit is ready to start when needed.
T1 – Off to Start
                                                                              2       Off:Cycle          Circuit is off and cannot start due to
All of the following are required:
                                                                                      Timers             active cycle timer on all compressors.
   • Circuit Enable = Enable                                                  3       Off:All Comp       Circuit is off and cannot start due to all
   • No Circuit Alarms active                                                         Disable            compressors being disabled.
   • There is at least one compressor available to start                      4       Off:Keypad         Circuit is off and cannot start due to
   • Unit State = Auto                                                                Disable            circuit enable set point.
                                                                              5       Off:Circuit        Circuit is off and circuit switch is off.
T2 – Start to Run
                                                                                      Switch
All of the following are required:
                                                                              6       Off:Alarm          Circuit is off and cannot start due to
   • The EXV preopen procedure has finished                                                              active circuit alarm.
   • The first compressor to start is running                                 7       Off:Test Mode      Circuit is in test mode.
T1 – Off to Start
All of the following are required:
   • Circuit State = Start
T2 – Start to Run
Any of the following are required:
   • Circuit State = Run
   • Outdoor Air Temperature > 80°F
• Circuit State is not Start DV DC Fan Motors 300 rpm 850 rpm 2 hp
Condenser Stages
Condenser staging on each refrigerant circuit will use up to 4
digital outputs for control of condenser fans. When equipped with
variable speed (ECM) condenser fans, the speed signal(s) sent
to the fans(s) via Modbus starts and stops the fan or fans. The
variable speed (ECM) fans do not use digital outputs.
The tables in the following sections show the output states for
each stage of condenser control with all the supported unit
configurations.
Condenser Target for AF Configurations                                      The 20°F is added as a buffer to make sure that even if the Tc
                                                                            overshoots below the target, the compressor is not in danger of
(Fantrol)                                                                   leaving the envelope. The condenser target takes the maximum
The condenser target for AF configurations is selected based on             value of the two, the optimum Tc and the lower bound Tc. This
circuit capacity using the condenser target set points. Since the           makes it so the target Tc is never outside of the compressor
AF configuration has a lower resolution for targeting a setpoint,           envelope.
more conservative targets are used. There are set points that               The calculated condenser target is capped at a high bound of
establish the condenser target for part load and 100% capacity.             133°F. A 133°F saturated condenser temperature correlates to a
              Load                             Range                        discharge pressure of about 509.4 PSI (gauge). If the discharge
                                                                            pressure is higher than 515 PSI (gauge), the circuit will not have
            Part Load                          90.0°F
                                                                            room to start another compressor. When looking to stage up a
            Full Load                          100.0°F                      compressor, capacity control monitors discharge pressure and
A minimum condenser target will also be enforced. This minimum              will not stage up that circuit is the pressure is higher than 515
will be calculated based on the saturated evaporator temperature            PSI. This cap makes it so the condenser fans will ramp to 100%
and is designed to keep the compressors within their envelopes.             output to keep the discharge pressure below 515 PSI to allow
                                                                            more compressors to start.
The 20°F is added as a buffer to make sure that even if the Tc
overshoots below the target, the compressor is not in danger of
leaving the envelope. The condenser target takes the maximum
value of the two, the target and the lower bound Tc. This makes it
so the target Tc is never outside of the compressor envelope.
Staging Up                                                                    H[X]
                                                                              In an H[X] high ambient start, the goal is to turn all available
Regular State Up Logic                                                        ECM fans on. This allows the fans to skip staging up individually
The first fan will not start until the circuit is in the run state and the    and go directly to their most efficient stage for high ambient. If
stage up error has accumulated past the limit. The only exception             the outdoor air temperature is greater than 105°F, the fan speed
to this is a high ambient start (special stage up case #1).                   setpoint is set to the maximum speed. Otherwise, the fan speed
                                                                              is set to the minimum speed. In the latter case, once at minimum
When the saturated condenser temperature is above the target
                                                                              speed the fans can ramp up together to the max speed if needed
plus the active deadband, stage up error is accumulated.
                                                                              to hit the condenser target.
The Stage Up Error Step is added to a Stage Up Accumulator                    Low Ambient Starts and Staging
once every 5 seconds, only if the Saturated Condenser                         On units with ECM fans (DV and H[X]), if the ambient
Refrigerant Temperature is not falling. When Stage Up Error                   temperature is less than 50°F when the first fan is staged on,
Accumulator is greater than the Stage Up Limit the fan stage                  the speed command is held at the minimum for 5 seconds
is increased by one stage if the stage up timer has expired. If               after staging the first fan on. This mitigates windup in the PID
the chiller is in a low ambient condition the low ambient staging             integrator term as the fan ramps up to its minimum speed. Since
conditions must be satisfied (see low ambient starts and staging              there is a delay in condenser temperature change between when
section).                                                                     the fan is activated and when it has ramped up to speed, the PID
                                                                              loop sees this as a need to increase output, the condenser output
  Outdoor Air            < 20      20-50     50-80     80-110     >110        could overshoot the target and cause an unnecessary drop in
  Temperature (°F)
                                                                              suction pressure.
  Stage Up Dead-          5.0       5.0       5.0       5.0        5.0
  band (°F)                                                                   Another low ambient consideration on units with AF and DV
  Stage Down             30.0      23.0       29.8      19.8      15.0
                                                                              configurations is when a sequential compressor starts and the
  Deadband (°F)                                                               saturated condenser temperature increases, the regular stage up
                                                                              logic may call an additional on/off fan to stage up. This additional
The only exception to the above table is if there are no fans                 fan is often too much condenser output at low temperatures and
running on a circuit (circuit just started).                                  causes a compressor to stage down on low suction pressure
  Outdoor Air Temperature (°F)                          All
                                                                              unloading. Units with the AF and DV configurations at ambient
                                                                              temperatures under 30F with at least one fan already running
  Stage Up Deadband (°F)                               1.0                    must wait to stage up until the output term of the PID loop is
  Stage Down Deadband (°F)                             1.0                    greater than 90%. This allows extra time before staging up
                                                                              an additional fan to bring the condenser temperature back
High Ambient Starts                                                           to the target area at the current stage. Even if the condenser
When a circuit is called to start, if the saturated condenser                 configuration is AF, the PID loop still runs in the background, so
temperature is greater than 90°F before the preopen sequence, a               this logic still holds true.
high ambient start is initiated.
                                                                              Skipping First Stage
AF and DV                                                                         • Case 1: If the circuit has 4 or more fans and OAT is at
In an AF or DV high ambient start, the goal is to have the first                    least 21.11°C (70°F) when the first condenser stage would
one or two fans on the circuit running at maximum capacity                          normally be started.
before the compressor is turned on. In the high ambient start                     • Case 2: If the circuit has an H[X] configuration and OAT is
logic, the stage up accumulation term is overridden and set to                      at least 10° (50°F) when the first condenser stage would
the limit value, triggering an immediate stage up. By triggering                    normally be started.
a regular stage up by maxing out the stage up accumulator, the                    • Case 3: If the circuit has a DV configuration and OAT is at
logic evaluates if a “skipping first stage” case should be utilized                 least 65°F when the first condenser stage would normally
(see section below). In most cases this results in the condenser                    be started.
skipping the first stage. Another feature of the high ambient start               • Case 4: If the circuit has an AF configuration and OAT is at
is that the PID output to the ECM fans (if applicable) is overridden                least 100°F when the first condenser stage would normally
and set to the maximum value. By setting the fan output to the                      be started.
maximum before the compressor starts, the fans have time to
ramp up in time to curb the discharge pressure rise. If the outdoor
air temperature is greater that 105°F, all fans are staged up
immediately.
When a stage down occurs or the saturated temperature rises                MOP Control           EXV is controlling to evaporator MOP target in
                                                                                                 high pressure situation
back above the target minus the Stage Down dead band, the
Stage Down Error Accumulator is reset to zero.                             SSH Control           EXV is controlling to suction superheat target
                                                                                                 in a normal situation
The stage down timer is 60 seconds divided by the number of
fans on the circuit. The stage down deadband and limit do not
                                                                         Figure 38: EXV Control Transitions
vary with conditions:
T8 – Pressure Control to MOP Control                                If the calculation returns a value outside of the EXV preopen
                                                                    range, the closest value inside of the range will be taken. This
All of the following are required:
                                                                    ensures the preopen position is always inside of the range.
   • Evaporator Pressure > Evaporator Pressure Hold Setpoint
   • Evaporator Pressure > (Evaporator Maximum Operating            Control Error Calculations
     Pressure Setpoint – 10.0 PSI)
                                                                    Regardless of the EXV control state, control error calculations are
T9 – SSH Control to Closed                                          made for Pressure Control, SSH Control, and MOP Control. The
                                                                    error equation is as follows:
All of the following are required:
   • Circuit State is not Start
   • Circuit State is not Run
  16      High Discharge       Fault       Circuit        Controller                                     “22”: Fan 2 on Circuit 2,      “7”: “Output Phase Lost
                                                                                                                                        Fault”,
           Temperature                    Shutdown       HMI or BAS                                      “23”: Fan 3 on Circuit 2,
                                                                                                                                        “8”: “Input Phase Lost Fault”,
  17      EEXV Module          Fault       Circuit        Controller                                     “24”: Fan 4 on Circuit 2,
          Comm Failure                    Shutdown       HMI or BAS                                                                     “9”: “Overload Fault”,
                                                                                                         “25”: Fan 5 on Circuit 2,
                                                                                                                                        “10”: “Comm Fail Fault”,
  18      DC Fan Fault       Problem        Ignore        Controller                                     “26”: Fan 6 on Circuit 2
                                         Affected Fan    HMI or BAS                                                                     “11”: “Bus Unbalance Fault”,
                                                                                                                                        “12”: “AC Low Fault”,
                                                                                                                                        “13”: “AC High Fault”,
                                                                                                                                        “14”: “External Fault”,
                                                                                                                                        “15”: “EEPROM Fault”,
                                                                                                                                        “16”: “Inner Comm Fault”,
                                                                              4         cpCOe            “1”: Expansion                 “0”: “None”
                                                                                        Expansion        Module – Sensor Box
                                                                                        Module           (UE01)
                                                                              5         Sensor           “0”: Unit,                     “0”: “None”
                                                                                                         “1”: Circuit 1,
                                                                                                         “2”: Circuit 2
Action Taken Shutdown all circuits and lock out unit from running Action Taken Ignore sensor value in applicable calculations
Reset Alarm trigger no longer exists Reset Sensor status returns to “10”
  Alarm          PVM/FFP Fault                                                    Reset       Alarm trigger no longer exists – Cannot be auto
                                                                                              cleared
  Type           Fault
  Displayed      PVM/FFP Fault                                                   Low Evaporator Pressure
  Text
  Alarm          Message       Module        Module        Payload                Alarm       Low Evaporator Pressure
  Parts          Code          Type          ID                                   Type        Fault
                 228           8             1,2           1,2                    Displayed   Low Evaporator Pressure
  Alarm          Circuit 1 GFM: 3825730561                                        Text
  Code                                                                            Alarm       Message          Module         Module        Payload
                 Circuit 2 GFM: 3825731585
                                                                                  Parts       Code             Type           ID
                 Circuit 1 PVM: 3825730562
                                                                                              153              8              1,2           0
                 Circuit 2 PVM: 3825731586
                                                                                  Alarm       Circuit 1: 2567439360
  Trigger        [Power Configuration = Multi Point and PVM/GFP                   Code
                 input is off] for longer than one second                                     Circuit 2: 2567440384
  Action         Shutdown circuit and lock circuit out from running               Trigger     This alarm should trigger when Freeze time is exceed-
  Taken                                                                                       ed, Low Ambient Start is not active, and Circuit State
                                                                                              = Run. It should also trigger if [Evaporator Pressure
  Reset          PVM/GFP input is on for at least 5 seconds or if Power                       < Low Evaporator Pressure Fault setpoint and Circuit
                 Configuration = Single Point                                                 State = Run] for longer than one second.
                                                                                              Freezestat logic allows the circuit to run for varying
Mechanical High Pressure Switch                                                               times at low pressures. The lower the pressure, the
                                                                                              shorter the time the compressor can run. This time is
  Alarm          Mechanical High Pressure Switch                                              calculated as follows:
  Type           Fault                                                                        Freeze error = Low Evaporator Pressure Unload –
                                                                                              Evaporator Pressure
  Displayed      Mechanical High Pressure Switch
  Text                                                                                        Freeze time =
  Alarm          Message       Module        Module        Payload                            •       For units equipped with shell and tube type
  Parts          Code          Type          ID                                                       evaporator: 80 – (freeze error/6.895), limited to a
                                                                                                      range of 40 to 80 seconds
                 166           8             1,2           0
                                                                                              •       For units with plate frame type evaporator: 60 –
  Alarm          Circuit 1: 2785543168                                                                (freeze error/6.895), limited to a range of 20 to 60
  Code                                                                                                seconds
                 Circuit 2: 2785544192
  Trigger        Mechanical High Pressure switch input is off for longer                      When the evaporator pressure goes below the Low
                 than one second                                                              Evaporator Pressure Unload set point, a timer starts.
                                                                                              If this timer exceeds the freeze time, then a freezestat
  Action         Shutdown circuit and lock circuit out from running                           trip occurs. If the evaporator pressure rises to the
  Taken                                                                                       unload set point or higher, and the freeze time has not
  Reset          Alarm trigger no longer exists– Cannot be auto cleared                       been exceeded, the timer will reset.
                                                                                              The alarm cannot trigger if the evaporator pressure
Mechanical Low Pressure Switch                                                                sensor fault is active.
                                                                                  Action      Shutdown circuit and lock circuit out from running
  Alarm          Mechanical Low Pressure Switch                                   Taken
  Type           Fault                                                            Reset       Evaporator Pressure > Low Evaporator Pressure Fault
  Displayed      Mechanical Low Pressure Switch                                               setpoint
  Text
  Alarm          Message       Module        Module        Payload
  Parts          Code          Type          ID
                 186           8             1,2           0
  Alarm          Circuit 1: 3121087488
  Code
                 Circuit 2: 3121088512
  Trigger        Mechanical Low Pressure switch input is off for longer
                 than 40 seconds and the circuit state is run. This alarm
                 requires Evaporator configuration = Remote Evap to
                 trigger
  Reset          Sensor status returns to “10”                                   Displayed   Suction Temperature Sensor Fault
                                                                                 Text
                                                                                 Alarm       Message       Module        Module        Payload
                                                                                 Parts       Code          Type          ID
                                                                                             183           5             1,2           0
                                                                                 Alarm       Circuit 1: 3070559232
                                                                                 Code
                                                                                             Circuit 2: 3070560256
                                                                                 Trigger     Trigger any time sensor status is other than “10” and
                                                                                             UC01 communication with UE01 module is OK, for at
                                                                                             least one second
                                                                                 Action      Shutdown circuit and lock circuit out from running
                                                                                 Taken
                                                                                 Reset       Sensor status returns to “10”
A successful auto-clear means all alarms have been cleared.                 Reset          While still running, the event will be reset if evaporator
                                                                                           pressure > Low Evaporator Pressure Hold SP + 90
The first successful auto-clear starts an hour-long timer, while                           KPA(13 PSI). The event is also reset if the circuit is no
the timer is active, no more than 3 successful auto-clears can                             longer in the run state.
occur. After the third successful auto-clear, there will be no more
attempts until the timer expires.
Touchscreen Controller                                                 Entering an invalid password has the same effect as not entering
                                                                       a password.
                                                                       Once a valid password has been entered, the controller allows
Home Screen                                                            further changes and access without requiring the user to enter
                                                                       a password until either the password timer expires or a different
                                                                       password is entered. The default value for this password timer is
Figure 42: Home Screen
                                                                       10 minutes.
                                                                       Navigation Menu
                                                                       Figure 44: Navigation Menu
Login Screen                                                           From the Navigation Menu you can select the following options:
                                                                           • Unit
Figure 43: Login Screen                                                    • Circuit 1
                                                                           • Circuit 2
                                                                           • Trends
                                                                           • Configuration
                                                                           • Maintenance
                                                                       To close the Navigation Menu, tap the “X” in the upper right
                                                                       corner of the display screen.
Unit/Setpoints                                                          Configuration
The Unit Home screen displays important information about the
unit, including the active setpoint, entering water temperature,        Figure 47: Configuration Screen
startup temperature, and more.
   • Setpoints
   • Compressors
   • Condenser Fans
  6.	 Check all exposed brazed joints for evidence of leaks.                   5.	 Check for 120 Vac at the control transformer and at TB-2
      Joints may have been damaged during shipping or when                         terminal #1 and the neutral block (NB).
      the unit was installed.                                                  6.	 Check between TB-2 terminal #7 and NB for 120 Vac
  7.	 Check that all refrigerant valves are either opened or                       supply for transformer #2.
      closed as required for proper operation of the chiller.                  7.	 Check between TB-2 terminal #2 and NB for 120 Vac
  8.	 A thorough leak test must be done using an electronic leak                   control voltage. This supplies the compressor crank case
      detector. Check all valve stem packing for leaks. Replace                    heaters.
      all refrigerant valve caps and tighten.                                  8.	 Check between TB-3 terminal #17 and #27 for 24 Vac
  9.	 Check all refrigerant lines to insure that they will not vibrate             control voltage.
      against each other or against other chiller components and
      are properly supported.
 10.	 Check all connections and all refrigerant threaded
      connectors.
 11.	 Look for any signs of refrigerant leaks around the
      condenser coils and for damage during shipping or
      installation.
 12.	 Connect refrigerant service gauges to each refrigerant
      circuit before starting unit.
  The pump control is factory set for this mode and no field
  changes or programming is required.
                                                                      Removing Temporary Strainer
                                                                      The temporary strainer must be removed following system clean
                            NOTICE                                    up as follows:
 Sensorless operation is only allowed for single chiller systems.     After all debris has been removed from the system, or a
 Systems with parallel chiller operation must use one of the other    maximum of 24 running hours, stop the pump and close the
 control methods.                                                     pump isolation valves. Drain the Suction Guide by removing the
                                                                      drain plug or opening the blowdown valve, if installed. Remove
Setup #2 External Sensor                                              the insulation disc held on with Velcro (the disc has a “CAUTION
  Normally a differential pressure sensor.                            Remove Startup Strainer After 24 Hours” sticker). Remove the
                                                                      suction guide cover and remove the strainer assembly from the
Setup #3 BAS                                                          valve body.
  “BAS Integration of Pumps” on page 22.                              The temporary fine-mesh start-up strainer is tack-welded to the
                                                                      permanent stainless steel strainer. This temporary strainer should
Hand On                                                               now be removed from the permanent strainer. The fine-mesh
                                                                      strainer is designed to remove small particulate from new piping
  Manual operation - not programmed.                                  systems and could easily clog with debris if left in place. This will
  Change from the sensorless default setup #1 to setup #2 or #3       be detrimental to the operation of the pump.
  on the graphic keypad display as follows:                           Replace the permanent strainer into the fitting body once the
  1.	 Press the OFF key. The keypad display will remain               temporary strainer is removed.
      powered.                                                        Inspect the cover O-ring and replace if necessary. Replace the
  2.	 Press the MAIN MENU key. Should show parameter “0- **           cover into the body. Ensuring that the strainer is properly seated,
      Operations/Display”.                                            tighten the cover bolts diagonally, evenly and firmly.
  3.	 Press OK.                                                       The seal may drip at initial start up as it breaks in. If the drip
                                                                      continues for more than a few hours, service may be required.
  4.	 Press ▼ key to 0-1 “Set UP Operations”.
  5.	 Press “OK”. Display goes to 0-10 “Active Setup”
  6.	 Press “OK”. Display will show boxed #1, #2, or #3
  7.	 Press ▼ or ▲ key to select either mode #2 or #3. #1 is
      factory default.
  8.	 Press OK. The upper right-hand corner of the display
      should show 2(2) or 3(3) depending on the choice.
  9.	 Press AUTO for normal operation.
 10.	 Press STATUS to return to the normal operating screen.
Figure 49: Thermal Dispersion Flow Switch and Adapter                      It is required that the flow switch be mounted such that the
                                                                           electrical connection and indentation ‘mark’ are pointed in the
                                                                           direction of flow as shown in Figure 51.
                                                                           If the flow sensor is to be mounted away from the unit, the sensor
                                                                           should be mounted on the wall of the inlet pipe of evaporator, or
                                                                           in a run of straight pipe that allows 5 to 10 pipe diameters prior
                                                                           to the sensor and 3 to 5 pipe diameters of straight pipe after the
                                                                           sensor. Flow switch is placed in inlet pipe to reflect flow entering
                                                                           the evaporator.
                            NOTICE
 Flow switch MUST be calibrated before chiller operation. Failure
 to properly calibrate the switch may result in severe chiller
 damage and/or void warranty.
                                  NOTICE
 DO NOT alter or relocate factory installed flow switch. If issues exist, contact
 Chiller Technical Response at TechResponse@DaikinApplied.com.
2.5 2.46 9.79 14.7 24.5 36.7 49.0 73.4 97.9 122.4 146.9 2.42
3 3.07 15.1 22.7 37.8 56.7 75.6 113.4 151.2 189.0 226.8 3.78
3.5 3.55 20.2 30.3 50.6 75.8 101.1 151.7 202.2 252.8 303.3 5.06
4 4.03 26.0 39.1 65.1 97.7 130.2 195.3 260.4 325.5 390.5 6.51
5 5.05 40.9 61.4 102.3 153.5 204.6 306.9 409.2 511.5 613.7 10.2
6 6.07 59.1 88.6 147.7 221.6 295.5 443.2 590.9 738.7 886.3 14.8
8 7.98 102.3 153.5 255.8 383.7 511.6 767.5 1023.3 1279.1 1534.7 25.6
10 10.02 161.3 241.9 403.2 604.8 806.5 1209.7 1612.9 2016.2 2419.1 39.0
12 11.94 229.0 343.4 572.4 858.6 1144.7 1717.1 2289.5 2861.9 3433.8 57.2
14 13.13 276.8 415.2 692.0 1037.9 1383.9 2075.9 2767.8 3459.8 4151.3 69.2
16 15.00 361.5 542.2 903.6 1355.5 1807.3 2710.9 3614.6 4518.2 5421.2 90.4
18 16.88 457.5 686.3 1143.8 1715.7 2287.6 3431.4 4575.2 5719.0 6862.1 114.4
20 18.81 572.4 853.0 1421.6 2132.4 2843.2 4264.8 5686.4 7108.0 8528.6 142.2
Flow Switch Adapter                                                            Step 1: Adjust flow through the evaporator to the minimum
If needed, the adapter is threaded into the pipe wall using                    desired operating gpm. Maintain this flow throughout the setup
pipe sealant appropriate for the application. The flow sensor is               procedure.
mounted onto the adapter using silicone grease. Carefully apply                Step 2: Once steady state minimum desired operating flow is
lubricant to the inside threads and o-ring so temperature probe                obtained, perform the ‘Teach’ function on the flow switch. The
does not become coated with lubricant or pipe thread sealant.                  ‘Teach’ function is initiated by holding down the minus ‘-’ button
Torque the adapter/sensor connection to 18.5 ft/lbs.                           on the face of the flow switch for 15 seconds. During this 15
                                                                               second period, LEDs ‘0’ and ‘9’ will be lit green. Once the ‘Teach’
Wiring                                                                         function is completed, the outer LEDs will flash green as shown
Refer to wiring diagram in the unit control panel.                             in Figure 53.
Step 3: After the ‘Teach’ function is completed and the outer             Figure 55: Upper Range of Minimum Flow
LEDs flashed, the flow switch will indicate a new set point based
upon the current flow which should still be at the steady state
minimum desired operating flow. Figure 54 shows a typical
display for this condition. All LEDs to the left of the SP LED are
lit green. The SP LED is lit RED (or may toggle amber) which
indicates that the flow switch is OPEN. Typically, an increase in
fluid flow is between 15% to 30% above the ‘Teach’ function flow
is required for the SP LED to turn AMBER and the flow switch to
CLOSE indicating acceptable flow.
Flow above display range: The SP LED will be lit amber, all
LEDs to the left and right of the SP LED with be green with the
rightmost LED flashing green. For example, if the SP was set to
200 cm/s, the flashing LED labeled ‘9’ would indicate that the flow
was above 230 cm/s. This may be a normal display depending on
range by which flow varies through chiller.
Electrical Terminals                                                      Power must be supplied to the heaters 24 hours before starting
                                                                          the compressors.
Prior to attempting any service on the control center, study the
wiring diagram furnished with the unit so that you understand the
operation of the unit.                                                    Lubrication
                             DANGER                                       No routine lubrication is required on AGZ units. The fan motor
                                                                          bearings are permanently lubricated and no further lubrication is
 LOCKOUT/TAGOUT all power sources prior to starting,
                                                                          required. Excessive fan motor bearing noise is an indication of a
 pressurizing, de-pressuring, or powering down the Chiller.
                                                                          potential bearing failure.
 Disconnect electrical power before servicing the equipment.
 Failure to follow this warning exactly can result in serious injury      POE type oil is used for compressor lubrication. Further details
 or death.                                                                and warnings are listed on page 93.
                             DANGER                                                                     WARNING
 The panel is always energized even if the system switch is off.              POE oil must be handled carefully using proper protective
 If it is necessary to de-energize the complete panel, including              equipment (gloves, eye protection, etc.). The oil must not come
 crankcase heaters, pull the main unit disconnect. More than one              in contact with certain polymers (e.g. PVC), as it may absorb
 disconnect may be required to de-energize the unit. Failure to               moisture from this material. Daikin Applied recommends against
 do so may result in serious injury or death.                                 the use of PVC and CPVC piping for chilled water systems. Also,
                                                                              do not use oil or refrigerant additives in the system.
                            WARNING
 Electrical Shock Hazard. Before servicing or inspecting the
 equipment, disconnect power to the unit. The internal capacitor
                                                                          All-Aluminum Condenser Coils
 remains charged after power is turned off. Wait at least the             The condenser coils are an all-aluminum design including the
 amount of time specified on the drive before touching any                connections, microchannel, fins (an oven brazing process brazes
 components. Failure to do can result in property damage,                 the fins to the microchannel flat tube), and headers (see Figure
 personal injury, or death.                                               58), which eliminates the possibility of corrosion normally found
                                                                          between dissimilar metals of standard coils.
                            WARNING
                                                                          During the condensing process, refrigerant in the coil passes
 Warranty may be affected if wiring is not in accordance with             through the microchannel flat tubes, resulting in higher efficiency
 specifications. A blown fuse or tripped protector may indicate           heat transfer from the refrigerant to the airstream. In the unlikely
 a short, ground fault, or overload. Before replacing fuse or             occurrence of a coil leak, contact Daikin Applied to receive a
 restarting compressor, the trouble must be found and corrected.          replacement coil module.
 It is important to have a qualified control panel electrician service
 this panel. Unqualified tampering with the controls can cause
 serious damage to equipment and void the warranty.
Figure 58: Microchannel Coil Cross Section                                  Periodic Clean Water Rinse
                                                                            A monthly clean water rinse is recommended for all coils
                                                                            according to Table 73. Coils should be rinsed with water at a
                                                                            lower pressure such as from a hose. Pressure washers are not
                                                                            recommended as the higher pressure may damage the fins.
                                                                            Regular water rinsing of epoxy coated coils that are applied in
                                                                            coastal or industrial environments will help to remove chlorides,
                                                                            dirt and debris. An elevated water temperature (not to exceed
                                                                            130ºF) will reduce surface tension, increasing the ability to
                                                                            remove chlorides and dirt.
Remove Surface Loaded Fibers                                                For routine quarterly cleaning, first clean the coil with a coil
                                                                            cleaner (see Table 74). After cleaning the coils with a cleaning
Surface loaded fibers or dirt should be removed prior to water              agent, use the chloride remover to remove soluble salts and
rinse to prevent further restriction of airflow. If unable to back          revitalize the unit.
wash the side of the coil opposite that of the coils entering air
side, then surface loaded fibers or dirt should be removed with             Recommended Coil Cleaning Agents
a vacuum cleaner. If a vacuum cleaner is not available, a soft
non-metallic bristle brush may be used. In either case, the tool            The following cleaning agents, used in accordance with the
should be applied in the direction of the fins. Coil surfaces can be        manufacturer’s directions on the container for proper mixing and
easily damaged (fin edges bent over) if the tool is applied across          cleaning, has been approved for use on epoxy coated coils to
the fins.                                                                   remove mold, mildew, dust, soot, greasy residue, lint and other
                                                                            particulates:
                             NOTICE
 Use of a water stream, such as a hose, against a surface loaded            Table 89: Epoxy Coated Coil Recommended Cleaning Agents
 coil will drive the fibers and dirt into the coil. This will make            Chemical Type               Cleaning Agent
 cleaning efforts more difficult. Surface loaded fibers must be               Coil Cleaner                Enviro-Coil Concentrate
 completely removed prior to using low velocity clean water rinse.
                                                                              Coil Cleaner                GulfCoat™
                                                                              Chloride Remover            CHLOR*RID®
                                                                                                           DANGER
Hot Gas Bypass (Optional)                                                       LOCKOUT/TAGOUT all power sources prior to starting,
                                                                                pressurizing, de-pressuring, or powering down the Chiller.
The hot gas bypass (HGBP) option allows the system to operate                   Disconnect electrical power before servicing the equipment.
at lower loads without excessive on/off compressor cycling.                     Failure to follow this warning exactly can result in serious injury
HGBP is required to be on both refrigerant circuits because of                  or death.
the lead / lag feature of the controller. HGBP allows passage of
discharge gas into the evaporator inlet (between the electronic
                                                                                                            NOTICE
expansion valve and the evaporator) which generates a false
load to supplement the actual chilled water or air handler load.                The transformer filter should be inspected and cleaned regularly.
                                                                                Failure to do so can result in loss of performance.
                              NOTICE
 The hot gas bypass valve should not generate a 100% false                     Figure 59: Transformer Filter Cleaning
 load. For glycol applications, HGBP may not have full range of
 setting or turn down.
The pressure regulating valve is factory set to begin opening
at 120 psig with R-32 and can be changed by adjusting the
pressure setting. To raise the pressure setting, remove the cap
and turn the adjustment screw clockwise. To lower the setting,
turn the screw counterclockwise. Do not force the adjustment
beyond the range it is designed for as this will damage the
adjustment assembly. The regulating valve opening point can be
determined by slowly reducing the system load while observing
the suction pressure. When the bypass valve starts to open, the
refrigerant line on the evaporator side of the valve will begin to
feel warm to the touch.
A solenoid valve is located ahead of the bypass valve and is
controlled by the MicroTech controller. It is active when only the
first stage of cooling on a circuit is active.
                             CAUTION
 High velocity water or compressed air may damage the filter and
 must only be used at a pressure lower than 100 psig.
  4.	 Reinstall transformer filter and transformer cover before
      starting up unit.
                                                                Quarterly
                                                     Monthly
                                                     (Note 1)
                                                                            (Note 2)
                                            Weekly
                                                                            Annual
 Operation                                                                              absorb moisture if exposed to air and may form acids that can be
                                                                                        harmful to the chiller. Avoid prolonged exposure of POE oil to the
                                                                                        atmosphere to prevent this problem.
 General
                                                                                        It is important that only the manufacturer’s recommended oils be
 Complete unit log and review (Note 3)      X
                                                                                        used. Acceptable POE oil types are:
 Visually inspect unit for loose or
                                                      X
 damaged components                                                                           • Danfoss POE lubricant 1855L
 Inspect thermal insulation for integrity                                    X
 Clean and paint as required                                                 X
                                                                                                                      WARNING
 Electrical                                                                                 POE oil must be handled carefully using proper protective
 Check terminals for tightness,                                                             equipment (gloves, eye protection, etc.) The oil must not come
                                                                             X              in contact with certain polymers (e.g. PVC), as it may absorb
 tighten as necessary
 Clean control panel interior                                                X              moisture from this material. Daikin Applied recommends against
 Visually inspect components for                                                            the use of PVC and CPVC piping for chilled water systems. Also,
                                                      X
 signs of overheating                                                                       do not use oil or refrigerant additives in the system.
 Verify compressor heater operation                   X
 Test and calibrate equipment
                                                                             X                                        WARNING
 protection and operating controls
                                                                                            Polyolester Oil, commonly known as POE oil is a synthetic oil
  Verify solenoid plug(s) tightness and
  gasket integrity
                                                                             X              used in many refrigeration systems, and is present in this Daikin
                                                                                            Applied product. POE oil, if ever in contact with PVC/CPVC, will
 Refrigeration
                                                                                            coat the inside wall of PVC/CPVC pipe causing environmental
 Leak test                                            X
                                                                                            stress fractures. Although there is no PVC/CPVC piping in this
 Check sight glasses for clear flow         X
                                                                                            product, please keep this in mind when selecting piping materials
 Check filter-drier pressure drop                     X                                     for your application, as system failure and property damage
 Perform compressor vibration test                                           X              could result. Refer to the pipe manufacturer’s recommendations
 Acid test oil sample                                                        X              to determine suitable applications of the pipe.
 Condenser (air-cooled)
 Rinse condenser coils (Note 5)                       X                                 Procedure Notes
 Clean epoxy coated condenser coils
                                                                X                             • Use only new sealed metal containers of oil to insure
 (Note 5)
 Check fan blades for tightness on                                                              quality.
                                                                             X
 shaft (Note 6)                                                                               • Buy smaller containers to prevent waste and contamination.
 Check fans for loose rivets and cracks                                      X                • Use only filter driers designed for POE and check pressure
 Check coil fins for damage                                     X                               drops frequently.
 Inspect and clean transformer filter
                                                                X                             • Test for acid and color at least annually. Change filter driers
 (non-460V units only)
                                                                                                if acid or high moisture (> 200 ppm) is indicated (< 100 ppm
Notes:                                                                                          typical).
  1.	 Monthly operations include all weekly operations.                                       • Evacuate to 500 microns and hold test to insure systems
  2.	 Annual (or spring start-up) operations includes all weekly                                are dry.
      and monthly operations.
                                                                                        Control and Alarm Settings
  3.	 Log readings can be taken daily for a higher level of unit
      observation.                                                                      The software that controls the operation of the unit is factory-set
                                                                                        for operation with R-32.
  4.	 Never Megohm motors while they are in a vacuum to avoid
      damage to the motor.
  5.	 Coil rinsing and cleaning can be required more frequently
      in areas with a high level of airborne particles.
  6.	 When cleaning condenser coils, be sure fan motors are
      electrically locked out.
Refrigerant Charging                                                        If subcooling is low, add charge to clear the sight glass. Once
                                                                            the subcooler is filled, extra charge will not lower the liquid
                                                                            temperature and does not help system capacity or efficiency.
                            CAUTION
                                                                            If subcooling is normal (15 to 20° F at full load) and flashing is
 When moving refrigerant to/from the chiller using an auxiliary
                                                                            visible in the sight glass, check the pressure drop across the
 tank, a grounding strap must be used. An electrical charge
                                                                            filter-drier.
 builds when halo-carbon refrigerant travels in a rubber hose. A
 grounding strap must be used between the auxiliary refrigerant             Overcharging of refrigerant will raise the compressor discharge
 tank and the end sheet of the chiller (earth ground), which will           pressure due to filling of the condenser tubes with excess
 safely take the charge to the ground. Damage to sensitive                  refrigerant.
 electronic components could occur if this procedure is not
 followed.                                                                  Service
If a unit is low on refrigerant, you must first determine the cause         Special tools will be required due to higher refrigerant pressures
before attempting to recharge the unit. Locate and repair any               with R-32. Oil-less/hp recovery units, hp recovery cylinders (DOT
refrigerant leaks. Soap works well to show bubbles at medium                approved w/525# relief), gauge manifold 30”-250 psi low/0-800
size leaks but electronic leak detectors are needed to locate               psi high, hoses w/800 psi working & 4,000 psi burst.
small leaks.
                                                                            All filter driers and replacement components must be rated for
Charging or check valves should always be used on charging                  POE oils and for the refrigerant pressure
hoses to limit refrigerant loss and prevent frostbite. Ball valve
                                                                            Brazed connections only. No StayBrite or solder connections
type recommended. Charge to 80-85% of normal charge before
                                                                            (solder should never be used with any refrigerant). K or L type
starting the compressors.
                                                                            refrigeration tubing only. Use nitrogen purge. Higher R-32
                                                                            pressures and smaller molecule size make workmanship more
Charging procedure                                                          critical.
The units are factory-charged with R-32. Use the following                  Cooling the recovery cylinder will speed recovery and lessen
procedure if recharging in the field is necessary.                          stress on recovery equipment.
The charge can be added at any load condition between 25 to
100 percent load per circuit, but at least two fans per refrigerant
circuit should be operating if possible.
Evaporator waterflow MUST be established while charging the
unit.
   • Start the system and observe operation.
   • Trim the charge to the recommended liquid line sub-cooling
     (approximately 15-20°F typical at full load).
   • Use standard charging procedures (liquid only) to top off the
     charge.
   • Check the sight glass to be sure there is no refrigerant
     flashing.
With outdoor temperatures above 60°F (15.6°C), all condenser
fans should be operating and the liquid line temperature should
be within 15°F to 20°F (8.3°C to 11.1°C) of the outdoor air
temperature. At 25-50% load, the liquid line temperature should
be within 5°F (2.8°C) of outdoor air temperature with all fans on.
At 75-100% load the liquid line temperature should be within
10°F (5.6°C) of outdoor air temperature with all fans on.
If the unit is at steady full load operation and bubbles are visible
in the sight glass, then check liquid subcooling. The AGZ units
have a condenser coil design with approximately 15% of the coil
tubes located in a subcooler section of the coil to achieve liquid
cooling to within 15 to 20°F (8.3 to11.1°C) of the outdoor air
temperature when all condenser fans are operating. Subcooling
should be checked at full load with 70°F (21.1°C) ambient
temperature or higher, stable conditions, and all fans running.
Liquid line subcooling at the liquid shut-off valve should be
between 15 and 20°F at full load.
The following checks shall be applied to installations using                   • Intrinsically safe components are the only types that can
FLAMMABLE REFRIGERANTS:                                                          be worked on while live in the presence of a flammable
                                                                                 atmosphere. The test apparatus shall be at the correct
   • if an indirect refrigerating circuit is being used, the
                                                                                 rating.
     secondary circuit shall be checked for the presence of
     refrigerant;                                                              • Replace components only with parts specified by the
                                                                                 manufacturer. Other parts may result in the ignition of
   • marking to the equipment continues to be visible and
                                                                                 refrigerant in the atmosphere from a leak.
     legible. Markings that are illegible shall be corrected;
   • refrigerating pipe or components are installed in a position                                       NOTICE
     where they are unlikely to be exposed to any substance                  The use of silicon sealant can inhibit the effectiveness of some
     which may corrode refrigerant containing components,                    types of leak detection equipment. Intrinsically safe components
     unless the components are constructed of materials which                do not have to be isolated prior to working on them.
     are inherently resistant to being corroded or are suitably
     protected against being so corroded.                                   Cabling
Checks to electrical devices                                                   • Check that cabling will not be subject to wear, corrosion,
                                                                                 excessive pressure, vibration, sharp edges or any other
Repair and maintenance to electrical components shall include
                                                                                 adverse environmental effects. The check shall also take
initial safety checks and component inspection procedures. If
                                                                                 into account the effects of aging or continual vibration from
a fault exists that could compromise safety, then no electrical
                                                                                 sources such as compressors or fans.
supply shall be connected to the circuit until it is satisfactorily
dealt with. If the fault cannot be corrected immediately but it
is necessary to continue operation, an adequate temporary
                                                                            Leak Detection
solution shall be used. This shall be reported to the owner of the          Under no circumstances shall potential sources of ignition
equipment so all parties are advised.                                       be used in the searching for or detection of refrigerant leaks.
                                                                            NEVER use the following when attempting to detect flammable
Initial safety checks shall include:
                                                                            refrigerant leaks:
   • that capacitors are discharged: this shall be done in a safe
                                                                               • A halide torch (or any other detector using a naked flame)
     manner to avoid possibility of sparking;
                                                                               • Substances containing chlorine
   • that no live electrical components and wiring are exposed
     while charging, recovering or purging the system;                      Detection of flammable refrigerants
   • that there is continuity of earth bonding.
                                                                            The following leak detection methods are deemed acceptable for
Repairs to sealed components                                                all refrigerant systems:
   • During repairs to sealed components, all electrical supplies              • Electronic leak detectors may be used to detect refrigerant
     shall be disconnected from the equipment being worked                       leaks. For FLAMMABLE REFRIGERANTS, the sensitivity of
     upon prior to any removal of sealed covers, etc. If it is                   electronic leak detectors may not be adequate, or may need
     absolutely necessary to have an electrical supply to                        re-calibration. (Detection equipment shall be calibrated
     equipment during servicing, then a permanently operating                    in a refrigerant-free area.) Ensure that the detector is
     form of leak detection shall be located at the most critical                not a potential source of ignition and is suitable for the
     point to warn of a potentially hazardous situation.                         refrigerant used. Leak detection equipment shall be set
                                                                                 at a percentage of the LFL of the refrigerant and shall be
   • Particular attention shall be paid to the following to ensure
                                                                                 calibrated to the refrigerant employed, and the appropriate
     that by working on electrical components, the casing is not
                                                                                 percentage of gas (25 % maximum) is confirmed.
     altered in such a way that the level of protection is affected.
     This shall include damage to cables, excessive number of                  • Leak detection fluids are also suitable for use with most
     connections, terminals not made to original specification,                  refrigerants but the use of detergents containing chlorine
     damage to seals, incorrect fitting of glands, etc.                          shall be avoided as the chlorine may react with the
                                                                                 refrigerant and corrode the copper pipe-work.Examples of
   • Ensure that the apparatus is mounted securely.
                                                                                 leak detection fluids are:
   • Ensure that seals or sealing materials have not degraded
                                                                                 — bubble method; or
     to the point that they no longer serve the purpose of
     preventing the ingress of flammable atmospheres.                            — fluorescent method agents
     Replacement parts shall be in accordance with the                         • If a leak is suspected, all open flames shall be removed/
     manufacturer’s specifications.                                              extinguished.
                                                                               • If a leakage of refrigerant is found which requires brazing,
Repair to intrinsically safe components                                          all of the refrigerant shall be recovered from the system,
   • Do not apply any permanent inductive or capacitance loads                   or isolated (by means of shut off valves) in a part of the
     to the circuit without ensuring that this will not exceed the               system remote from the leak. Removal of refrigerant shall
     permissible voltage and current permitted for the equipment                 be according to instructions in “Pressure Testing and
     in use.                                                                     Refrigerant Evacuation”.
Pressure Testing and Refrigerant                                            — Protect from heat and direct sunlight
Evacuation                                                                • Maximum storage temperature: 40°C (104°F)
   • Make sure that air or any matter other than R-32 refrigerant     Fire and Explosion Protection Information
     does not get into the refrigeration cycle.
                                                                      Open and handle refrigerant receptacle with care. Keep ignition
   • If refrigerant gas leaks occur, ventilate the area as soon as    sources away. Do not smoke. Protect against electrostatic
     possible.                                                        charges. Waste air is to be released into the atmosphere only via
   • R-32 should always be recovered and never released               suitable separators.
     directly into the environment.
   • Only use tools meant for use on R-32 refrigerant (such as a      Commissioning
     gauge manifold, charging hose, or vacuum pump adapter).              • Ensure that the floor area is sufficient for the refrigerant
                                                                            charge.
Removal and evacuation
                                                                          • Connect the pipes and carry out a leak test before charging
When breaking into the refrigerant circuit to make repairs, or              with refrigerant.
for any other purpose, conventional procedures shall be used.
                                                                          • Check safety equipment before putting into service.
However, for flammable refrigerants it is important that best
practice be followed, since flammability is a consideration.          Charging procedures
   • The following procedure shall be adhered to:                     In addition to conventional charging procedures and specific unit
      i.	 safely remove refrigerant following local and national      charging guidelines on page 94, the following requirements
          regulations - see “Recovery” section;                       shall be followed.
     ii.	 purge the circuit with inert gas;                               • Ensure that contamination of different refrigerants does not
     iii.	 evacuate;                                                        occur when using charging equipment.
                                                                          • Hoses or lines shall be as short as possible to minimize the
     iv. purge with inert gas;
                                                                            amount of refrigerant contained in them.
     v. open the circuit by cutting (if flammable refrigerant).           • Cylinders shall be kept in an appropriate position according
   • The refrigerant charge shall be recovered into the correct             to the instructions.
     recovery cylinders according to local and national codes.            • Ensure that the refrigerating system is earthed prior to
     For equipment containing flammable refrigerants, the                   charging the system with refrigerant.
     system shall be purged with oxygen-free nitrogen to render
                                                                          • Label the system when charging is complete (if not already).
     the equipment safe for flammable refrigerants. This process
     might need to be repeated several times.                             • Extreme care shall be taken not to overfill the refrigerating
                                                                            system.
   • Compressed air or oxygen shall not be used for purging
     refrigerant systems.                                                 • Prior to recharging the system, it shall be pressure-
                                                                            tested with the appropriate purging gas. The system shall
   • For equipment containing flammable refrigerants,
                                                                            be leak-tested on completion of charging but prior to
     refrigerants purging shall be achieved by breaking the
                                                                            commissioning. A follow up leak test shall be carried out
     vacuum in the system with oxygen-free nitrogen and
                                                                            prior to leaving the site.
     continuing to fill until the working pressure is achieved,
     then venting to atmosphere, and finally pulling down to a
     vacuum.
                                                                      Decommissioning
   • When the final oxygen-free nitrogen charge is used, the              • If the safety is affected when the equipment is put out of
     system shall be vented down to atmospheric pressure to                 service, the refrigerant charge shall be removed before
     enable work to take place.                                             decommissioning.
   • Ensure that the outlet for the vacuum pump is not close              • Ensure sufficient ventilation at the equipment location.
     to any potential ignition sources and that ventilation is            • Be aware that malfunction of the equipment may be caused
     available.                                                             by refrigerant loss and a refrigerant leak is possible.
                                                                          • Discharge capacitors in a way that won’t cause any spark.
Handling and Storage                                                      • Remove the refrigerant according to details in “Recovery”
                                                                            section. If recovery is not required by national regulations,
Conditions for Safe Storage                                                 drain the refrigerant to the outside. Take care that the
   • Requirements to be met by storerooms and receptacles:                  drained refrigerant will not cause any danger. In doubt,
     — Store only in unopened original receptacles                          one person should guard the outlet. Take special care that
                                                                            drained refrigerant will not float back into the building.
     — Store in a cool and dry location
                                                                          • Ensure all isolation valves on the equipment are closed off.
   • Further information about storage conditions:
     — Keep container tightly sealed
     — Store in cool, dry conditions in well sealed receptacle
Prior to the task being carried out, an oil and refrigerant sample
shall be taken in case analysis is required prior to re-use of
recovered refrigerant.
It is essential that electrical power is available before the task is
commenced.
  1.	 Become familiar with the equipment and its operation.
Troubleshooting
  PROBLEM            POSSIBLE CAUSES                                POSSIBLE CORRECTIVE STEPS
                     1. Main or compressor disconnect switch open   1. Close switch.
                     2. Fuse blown; circuit breakers open           2. Check electrical circuits and motor windings for shorts or grounds.
                                                                    Investigate for possible overloading. Check for loose or corroded connec-
                                                                    tions. Replace fuse or reset breakers after fault cause is corrected
                     3. Thermal overloads tripped                   3. Overloads are auto-reset. Check voltages, cycle times and mechanical
                                                                    operations. Allow time for auto-reset
  Compressor Will    4. Defective contactor or coil                 4. Replace
  Not Run
                     5. System shutdown by equipment protection     5. Determine type and cause of shutdown and correct it before restarting
                     devices                                        equipment
                     6. No cooling required                         6. None. Wait until unit calls for cooling
                     7. Liquid line solenoid will not open          7. Repair or replace solenoid. Check wiring
                     8. Motor electrical trouble                    8. Check motor for opens, shorts, or burnout
                     9. Loose wiring                                9. Check all wire junctions. Tighten all terminal screws
                     1. Low lift, inverted start                    1. Control issues or condenser fan VFDs needed
                     2. Compressor running in reverse               2. Check unit and compressor for correct phasing
  Compressor
                     3. Improper piping or support on suction or    3. Relocate, add, or remove hangers
  Noisy Or Vibrat-
                     discharge
  ing
                     4. Worn compressor isolator bushing            4. Replace
                     5. Compressor mechanical failure               5. Replace
                     1. Noncondensables in system                   1. Extract noncondensables with approved procedures or replace charge
                     2. Circuit overcharged with refrigerant        2. Remove excess, check liquid subcooling
                     3. Optional discharge shutoff valve not open   3. Open valve
  High Discharge
                     4. Condenser fan control wiring not correct    4. Correct wiring
  Pressure
                     5. Fan not running                             5. Check electrical circuit and fan motor
                     6. Dirty condenser coil                        6. Clean coil
                     7. Air recirculation                           7. Correct
                     1. Rapid load swings                           1. Stabilize load
                     2. Lack of refrigerant                         2. Check for leaks, repair, add charge. Check liquid sight glass
                     3. Fouled liquid line filter drier             3. Check pressure drop across filter drier. Replace
                     4. Expansion valve malfunctioning              4. Repair or replace and adjust for proper superheat
  Low Suction
                     5. Condensing temperature too low              5. Check means for regulating condenser temperature
  Pressure
                     6. Compressors not staging properly            6. See corrective steps - Compressor Staging Intervals Too Low
                     7. Insufficient water flow                     7. Correct flow
                     8. Excess or wrong oil used                    8. Recover or change oil
                     9. Evaporator dirty                            9. Back flush or clean chemically
                     1. Defective capacity control                  1. Replace
  Compressor Will
                     2. Faulty sensor or wiring                     2. Replace
   Not Stage Up
                     3. Stages not set for application              3. Adjust controller setting for application
                     1. Control band not set properly               1. Adjust controller settings for application
                     2. Faulty water temperature sensor             2. Replace
Appendix
Pre-Start   Checklist
  Pre-Start Checklist – Scroll Compressor Chillers
    Must be completed, signed, and provided to Daikin Applied sales office at least 2 weeks prior to requested start date.
                        Job Name
             Installation Location
         Customer Order Number
                Model Number(s)
                  G.O. Number(s)
     Chilled Water Piping and Condenser Water Piping for Water-cooled Chiller                                         Yes       No      N/A        Initials
     Piping Complete
     Water strainer(s) installed in piping per IOM requirements
     Chilled Water System – flushed, filled, and vented; Water treatment in place
     Condenser Water System (incl. cooling tower) - flushed, filled, vented; Water treatment
     in place (applicable for water-cooled systems)
     Pumps installed and operational (rotation checked, strainers cleaned)
     Water system operated and tested; flow meets unit design requirements
     Flow switch(es) - installed, wired, and ready for calibration during startup
     Air vent installed on evaporator chilled water inlet piping
     Glycol at design % (if applicable)
     Electrical                                                                                                       Yes       No      N/A        Initials
     Building controls operational (3-way valves, face/bypass dampers, bypass valves, etc.)
     *Power leads connected to power block or optional disconnect
     Power leads have been checked for proper phasing and voltage
     All interlock wiring complete and compliant with Daikin Applied specifications
     Power applied at least 24 hours before startup
     Crankcase heaters must operate for 24+ hours before startup to maximize separation
     Chiller components (EXV Sensors Transducers) installed and wired properly
     *Wiring complies with National Electrical Code and local codes (See Notes)
     Remote EXV wired with shielded cable
     Miscellaneous                                                                                                    Yes       No      N/A        Initials
     Unit control switches all off
     Remote Evaporator / Condenser Piping factory reviewed
     All refrigerant components/piping leak tested, evacuated and charged
     Thermometers, wells, gauges, control, etc., installed
     Minimum system load of 80% capacity available for testing/adjusting controls
     SiteLineTM cloud-connected controls included and needs to be commissioned
     Document Attached: Technical Breakdown from Selection Software
     Document Attached: Final Order Acknowledgement
     Document Attached: Remote piping approval
     Notes: The most common problems delaying start-up and affecting unit reliability are:
     1.    Field installed compressor motor power supply leads too small. Questions: Contact the local Daikin Aplied sales representative*. State size, number
           and type of conductors and conduits installed:
           a.    From Power supply to chiller
     * Refer to NFPA 70-2017, Article 440.35
     2. Remote Evaporator piping incomplete or incorrect. Provide approved piping diagrams.
     3. Items on this list incorrectly acknowledged resulting in delayed start and possible extra expenses incurred by return trips.
     Contractor Representative                                                       Daikin Applied Sales Representative
     Signed:                                                                         Signed:
     Name:                                                                           Name:
     Company:                                                                        Company:
     Date:                                                                           Date:
     Phone/Email:                                                                    Phone/Email:
IOM 1359-1
     ©2023 Daikin Applied                                         Form SF-18002        101                                                    19WWW.DAIKINAPPLIED.COM
                                                                                                                                                 June 2023
Appendix
JOB INFORMATION
UNIT INFORMATION
     Is the unit free of visible shipping damage, corrosion, or paint problems?                                 Yes      No      N/A
     Is unit level and isolators installed?                                                                     Yes      No      N/A
     Does the unit meet all location, installation and service clearances per IOM Bulletin?                     Yes      No      N/A
     Are all fan fastener nuts on the fans tights?                                                              Yes      No      N/A
     Does electrical service correspond to unit nameplate?                                                      Yes      No      N/A
       Nameplate: Volts:                   Hertz:                             Phase:
     Has electrical service been checked for proper phasing at each circuit power terminal block?               Yes      No      N/A
     Has unit been properly grounded and all field wiring confirmed to unit electrical specifications?          Yes      No      N/A
     Has a fused disconnect and fuses or breaker been sized per product manual and installed per local code?    Yes      No      N/A
Description of unit location with respect to building structures. Include measured distances.
     Reviewed and confirmed piping is per the approved SF-99006 form submitted to the factory?                  Yes      No      N/A
     Has all field piping been leak tested? (R-410a at 150 psig [1034 kPA], R-32 at 300 psig [2068 kPa])        Yes      No      N/A
     Has system been properly evacuated and charged?                                                            Yes      No      N/A
     Refrigerant:                         Circuit 1:                  lbs.       Circuit 2:              lbs.
     Is a liquid line filter-drier installed in each circuit?                                                   Yes      No      N/A
     Is a liquid line solenoid installed correctly in each circuit?                                             Yes      No      N/A
     Is the suction temperature sensor properly installed?                                                      Yes      No      N/A
     SF-20001 AGZ Warranty Registration Startup Form (11/2024)               2                                   www.DaikinApplied.com
DESIGN CONTROLS
     CHILLER
     Water Pressure Drop:                              psig (kPa)                                Ft. (kPa)                           gpm (lps)
     Water Temperatures: Entering:                                  °F (°C)           Leaving:                    °F (°C)
     CONDENSER
     Design Ambient Temperatures: Entering:                                       °F (°C)        Leaving:                       °F (°C)
     Minimum Ambient Temperatures: Entering:                                      °F (°C)        Leaving:                       °F (°C)
START-UP
     Does unit start and perform per sequence of operation as stated in the IOM Manual?                                           Yes            No
     Do condenser fans rotate in the proper directions?                                                                           Yes            No
                                                              HMI STATUS CHECK
                                   Each Reading Must be Verified with Field Provided Instruments of Known Accuracy
     Water Temperatures                                     HMI                                    Verification
        Leaving Evaporator:                                                   °F (°C)                              °F (°C)
        Entering Evaporator:                                                  °F (°C)                              °F (°C)
     Circuit #1 Refrigerant Pressures
        Evaporator:                                                           psig (kPa)                           psig (kPa)
        Liquid Lines Pressure:                                                                                     psig (kPa)
        Condenser Pressure:                                                   psig (kPa)                           psig (kPa)
     Circuit #2 Refrigerant Pressures
        Evaporator:                                                           psig (kPa)                           psig (kPa)
       Liquid Lines Pressure:                                                                                      psig (kPa)
       Condenser Pressure:                                                    psig (kPa)                           psig (kPa)
     Circuit #1 Refrigerant Temperatures
        Saturated Evaporator Temperature:                                     °F (°C)                              °F (°C)
        Suction Line Temperature:                                             °F (°C)                              °F (°C)
        Suction Superheat:                                                    °F (°C)                              °F (°C)
        Saturated Condenser Temperature:                                      °F (°C)                              °F (°C)
        Liquid Line Temperature:                                                                                   °F (°C)
        Subcooling:                                                                                                °F (°C)
        Discharge Temperature:                                                                                     °F (°C)
     Circuit #2 Refrigerant Temperatures:
        Saturated Evaporator Temperature:                                     °F (°C)                              °F (°C)
       Suction Line Temperature:                                              °F (°C)                              °F (°C)
        Suction Superheat:                                                    °F (°C)                              °F (°C)
        Saturated Condenser Temperature:                                      °F (°C)                              °F (°C)
        Liquid Line Temperature:                                                                                   °F (°C)
        Subcooling:                                                                                                °F (°C)
        Discharge Temperature:                                                                                     °F (°C)
     Ambient Air Temperature:                                                 °F (°C)                              °F (°C)
     SF-20001 AGZ Warranty Registration Startup Form (11/2024)                    3                                                www.DaikinApplied.com
                                                           NON-MICROTECH READINGS
   Water Pressure Drop:                         (ft)           (psig)                            (gpm)*
   NOTE: Actual DP ft ÷ Design DP ft = √ x Design GPM = Actual GPM
   Does the system contain glycol?                                                                                                Yes           No
   Percentage by weight:                                       or by volume:                                  Glycol Type:
   If the chilled water system include glycol, have the freeze protection, low pressure devices and settings
   been adjusted for the actual job requirements? Detail these settings on page 8 - Remarks section                               Yes           No
NOTE: See operation manual for low temperature on ice bank applications.
                                                    MICROTECH SETPOINTS
                          ALARM SETPOINTS MUST BE VERIFIED WITH INSTRUMENTS OF KNOWN ACCURACY
IOMSF-20001
     1359-1 AGZ Warranty Registration Startup Form (11/2024)                     4 105                                                 WWW.DAIKINAPPLIED.COM
                                                                                                                                      www.DaikinApplied.com
Appendix
Repairs Made:
Items not installed per IOM Manual and/or recommended corrective actions:
 Project Name:
 Building Address:
 Contractor Name:
 Site Contact Name:                                                         Site Contact Number:
 Your Company:                                                              Your Name:
 Pump Model:                                                                Pump Tag Number:
 Pump Serial:                                                               Sales Order Number:
 NOTE: For independent sensorless operation, go to Section 1. For independent external sensor operation, go to Section 2. For external controller, go
 to Section 3.
 SF-20001
DAIKIN    AGZ Warranty Registration Startup Form (11/2024)
       APPLIED                                                            6 107                                            www.DaikinApplied.com
                                                                                                               TRAILBLAZER AIR-COOLED  SCROLL CHILLER
Appendix
              WARRANTY
             Daikin Applied Americas Inc. dba Daikin Applied (“Company”) warrants to contractor, purchaser and any owner of the product
             (collectively “Owner”) that, subject to the exclusions set forth below Company, at its option, will repair or replace defective parts in
             the event any product manufactured by Company, including products sold under the brand name Daikin and used in the United States
             or Canada, proves defective in material or workmanship within twelve (12) months from initial startup or eighteen (18) months from
             the date shipped by Company, whichever occurs first. Authorized replacement parts are warranted for the remainder of the original
             warranty. All shipments of such parts will be made FOB factory, freight prepaid and allowed. Company reserves the right to select
             carrier and method of shipment. In addition, Company provides labor to repair or replace warranty parts during Company normal
             working hours on products with rotary screw compressors or centrifugal compressors. Warranty labor is not provided for any other
             products.
             Company must receive the Registration and Startup Forms for products containing motor compressors and/or furnaces within ten (10)
             days of original product startup, or the ship date and the startup date will be deemed the same for determining the commencement
             of the warranty period and this warranty shall expire twelve (12) months from that date. For additional consideration, Company will
             provide an extended warranty(ies) on certain products or components thereof. The terms of the extended warranty(ies) are shown on
             a separate extended warranty statement.
             No person (including any agent, sales representative, dealer or distributor) has the authority to expand the Company’s obligation
             beyond the terms of this express warranty or to state that the performance of the product is other than that published by Company.
             EXCLUSIONS
             1. If free warranty labor is available as set forth above, such free labor does not include diagnostic visits, inspections, travel time and
                 related expenses, or unusual access time or costs required by product location.
             2. Refrigerants, fluids, oils and expendable items such as filters are not covered by this warranty.
             3. This warranty shall not apply to products or parts : (a) that have been opened, disassembled, repaired, or altered, in each case by
                 anyone other than Company or its authorized service representative; (b) that have been subjected to misuse, abuse, negligence,
                 accidents, damage, or abnormal use or service; (c) that have not been properly maintained; (d) that have been operated or
                 installed, or have had startup performed, in each case in a manner contrary to Company's printed instructions; (e) that have been
                 exposed, directly or indirectly, to a corrosive atmosphere or material such as, but not limited to, chlorine, fluorine, fertilizers,
                 waste water, urine, rust, salt, sulfur, ozone, or other chemicals, contaminants, minerals, or corrosive agents; (f) that were
                 manufactured or furnished by others and/or are not an integral part of a product manufactured by Company; or (g) for which
                 Company has not been paid in full.
             4. This warranty shall not apply to products with rotary screw compressors or centrifugal compressors if such products have not
                 been started, or if such startup has not been performed, by a Daikin Applied or Company authorized service representative.
             ASSISTANCE
             To obtain assistance or information regarding this warranty, please contact your local sales representative or a Daikin Applied office.
A I R H A N D L E R S | W AT E R - C O O L E D C H I L L E R S | A I R - C O O L E D C H I L L E R S
U N I T H E AT ER S | FA N CO I L S | A I R P U R I F I ER S | WAT ER S O U R C E H E AT P U M P S
VA R I A B L E A I R V O L U M E U N I T S | U N I T V E N T I L AT O R S
        1 3 6 0 0 I N D U S T R I A L PA R K B LV D .                  |   MINNEAPOLIS, MN 55441
                             1-800-432-1342                        |   763-553-5330
                               LEARN MORE AT
                             DAIKINAPPLIED.COM
                                           PART NUMBER: IOM1359-1
                                 © 2024 DAIKIN APPLIED | (800) 432.1342 | WWW.DAIKINAPPLIED.COM