Combustible Dust - Loss Prevention
Combustible Dust - Loss Prevention
October 2024
Page 1 of 70
COMBUSTIBLE DUSTS
Table of Contents
Page
©2024 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic,
mechanical, photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance
Company.
7-76 Combustible Dusts
Page 2 FM Property Loss Prevention Data Sheets
List of Figures
Fig. 2.2.2.3-1. Large collector showing partitions subdividing the unit ....................................................... 10
Fig. 2.4.2.1.1-1. Pulse jet collector; example of automatic sprinkler protection ......................................... 14
Fig. 2.4.2.7.6-1. Electrostatic precipitator with water spray protection for precipitator and ducts
(only one duct shown) ....................................................................................................... 17
Fig. 2.4.3.5.4-1. Large spray dryer unit – location of explosion vents ......................................................... 21
Fig. 2.4.3.7.5-1. Example of duct explosion venting at an elbow ............................................................... 23
Fig. 2.5.4.1-1. Rotary air lock ...................................................................................................................... 27
Fig. 3.1-1. Dust explosion pentagon ............................................................................................................. 33
Fig. 3.1.6.2-1. Particle Size ......................................................................................................................... 35
Fig. 3.4.1.1-1. Example of an enclosureless collector ................................................................................ 40
Fig. 3.4.1.2-1. Example of an enclosureless drum filter ............................................................................... 40
Fig. 3.4.4-1. Particle size .............................................................................................................................. 42
Fig. 3.4.5-1. Single stage electrostatic precipitator. (Unit is separated into two compartments
by vertical partition; each compartment has three fields; material collected on plates
drops down into hopper below.) ............................................................................................... 43
Fig. 3.4.5-2. Double-stage electrostatic precipitator with mechanical filtration ........................................... 44
Fig. 3.4.6-1. Typical grain elevator .............................................................................................................. 45
Fig. 3.4.8-1. Chain conveyor ....................................................................................................................... 46
Fig. 3.7-1. Powder bed processes ............................................................................................................... 50
Fig. 3.7-2. Material deposition processes .................................................................................................... 51
Fig. 3.7-3. 3D printing and liquid processes ................................................................................................ 51
Fig. 3.7-4. SLS design concept (Chemical Engineering Progress, May 2014) .......................................... 51
Fig. 3.7-5. Industrial-scale 3D systems: ProX300 and Concept M2 Laser printers
(Source: manufacturers’ brochures) ........................................................................................... 52
Fig. C.1.3-A. Schematic of rooftop explosion vents that project above the roof line ................................. 60
Fig. D.1-1. FM Approved flameless venting device (Photo courtesy of Rembe GmbH) ............................. 65
Fig. E.2.1-1. Rapid action float valve (Ventix ESI ®) .................................................................................. 68
Fig. E.2.2-1. Explosion diverter ..................................................................................................................... 68
Fig. E.2.2-2. Indoor installation of explosion diverter .................................................................................. 68
Fig. E.2.3-1. High-speed abort gate ............................................................................................................ 69
List of Tables
Table 2.4.3.4.1-1. Bucket Elevator Explosion Venting .................................................................................. 20
Table 2.6.2.1-1. Explosion Protection Device Inspection Frequencies ........................................................ 27
Table 2.10.7.2-1. Tangential Velocity and Danger for Ignition ..................................................................... 32
Table 3.1.6.2-1. Particle Size Comparison ................................................................................................... 35
Table 3.2.1-1. Typical Dust Bulk Density ..................................................................................................... 36
Table 3.4.2-1. Operating Temperature Limits for Commonly Used Filter Media as Woven or Felted Fabric . 41
1.0 SCOPE
This property loss prevention data sheet provides recommendations to reduce the frequency and severity
of fires and explosions involving combustible dust, dust mixture, or fibers fires and explosions. Following the
recommendations in this Standard does not eliminate the need to evaluate the processes/facilities with
standards/codes that go beyond property protection. Cases where the expected property damage from a
dust fire/explosion in a building do not justify corrective action from a property loss prevention standard point,
still represent a significant thermal event within the building.
Guidance for the following is included in this data sheet:
• General hazard mitigation for combustible dusts; including metal, wood plastic and agricultural dusts;
dust mixtures, and fiber.
• Fire and explosion protection for:
− Dust collection equipment, including dust collectors, cyclones, electrostatic precipitators
− Dust processing, storage and handling operations, including silos, bins and bucket elevators
• Explosion protection where combustible dusts, dust mixtures, or fibers create an equipment, room
or building explosion hazard
For the following subjects, refer to the applicable occupancy-specific data sheet for loss prevention
recommendations, which are not covered in this data sheet:
• Fire protection of spray dryers, flash dryers, ring dryers and rotary kilns and dryers. See to FM Data
Sheets 6-9, Industrial Ovens and Dryers and 7-111A, Fuel-Grade Ethanol
• Specific guidance related to woodworking and wood processing occupancies – See Data Sheet 7-10,
Wood Processing and Woodworking Facilities
• The review, design, testing and maintenance of explosion protection and isolation systems – See
Data Sheet 7-17, Explosion Protection Systems. Such guidance should be referenced in conjunction
with the guidance presented within this data sheet.
• Fire protection for processes within carbon black manufacturing plants that do not involve combustible
dust – See Data Sheet 7-111B, Carbon Black
• Wood chip storage - see Data Sheet 8-27, Storage of Wood Chips
The calculation methods associated with dust explosion hazard evaluations are primarily discussed/used in
metric (SI) units, and these units are used in this data sheet.
This data sheet references software called DustCalc. DustCalc is proprietary software used by FM engineers
in the calculation and verification of explosion vent sizing for buildings and equipment where a combustible
dust explosion hazard exists. Other vent sizing methodologies are available, but they are not used by FM.
1.1 Hazards
Combustible dust includes nearly all organic materials such as wood, paper, rubber, plastics, fiber, food and
tobacco along with other materials, such as metals, that exist in the form of particles less than 500 µm in
the largest dimension. Combustible dusts present both a fire and explosion hazard.
These materials can be ignited in the presence of air (oxygen). If a dust forms a low-density layer on surfaces
over a large area and is ignited, the resultant fire can spread rapidly, potentially faster than automatic
sprinklers can operate. This situation can result in a large and damaging event. For densely packed dusts,
a fire may not spread quickly but can become deep seated. If the dust layer is disturbed, the smoldering
area can become an open flame, igniting surrounding dust.
If a combustible dust is suspended in air and ignited, the resultant flame front can quickly spread through
the dust particles (a deflagration) and generate a significant temperature rise within a confined volume,
resulting in a fast pressure rise. If that pressure rise is not properly controlled, the confined volume will violently
fail, resulting in an explosion.
Dust explosion events in buildings/rooms often begin with ignition of a small amount of suspended dust.
The resulting pressure pulse may not initially damage the building/room structure but can result in the
suspension and ignition of additional dust. This process will propagate through all areas where dust is present.
If enough dust is available in a particular area, the developed pressure will cause the structure to fail. If not
enough dust is available to create pressures that cause the failure of the room/building, it will create a
spreading fireball across the roof level that produces large quantities of thermal radiation within the building/
room.
Dust explosions within equipment may also involve a very small amount of the contained dust. However,
due to the smaller enclosed volume, the produced pressure will often result in the failure of the equipment
and the release of unburned dust into the surrounding area. The flame front then ignites this suspended dust,
resulting in a secondary fireball outside the equipment which can produce damaging overpressure if confined
within a building. Beyond the fireball, parts of the failed equipment can also be ejected into the building.
Equipment inside a building that is vented into the building can produce significant flame jets.
The severity of a dust explosion depends on several factors such as dust composition, moisture content,
particle size, ignition energy, explosibility, along with the amount and location of the combustible dust involved.
Combustible particulate that is too large to be suspended in air or quickly propagate a flame front can be
reduced in size within dust handling equipment, thus increasing the dust explosion hazard. When identifying
where combustible dust might be present, looking at all areas within a process is important.
When located within rooms/buildings, the design and maintenance of dust processes is critical in preventing
dust liberation into the building, which can create a room/building fire and/or explosion hazard. Processes
that cannot be designed to prevent the release of dust into rooms/building should be isolated from other
important operations and designed to control a potential explosion with the provision of damage limiting
construction.
Wherever combustible dusts are present, housekeeping programs are not an acceptable alternative to
containing combustible dust within the process or isolating processes where dust release cannot be
prevented. However, housekeeping can be used as a supplementary method to fire and explosion protection
to control the level of dust within a facility.
1.2 Changes
October 2024. This document has been completely revised and consolidates several existing documents
into one. Significant changes include the following:
A. Changed title to Combustible Dusts (from Fire and Prevention and Mitigation of Combustible Dust
Explosion and Fire).
B. Incorporated guidance from FM Data Sheet 7-73, Dust Collectors and Collection Systems. Data sheet
7-73 has been made obsolete.
C. Incorporated guidance from FM Data Sheet 7-75, Grain Storage and Milling. Data Sheet 7-75 has been
made obsolete.
D. Added new guidance for the evaluation of combustible dust properties. This knowledge allows for better
hazard evaluation and development of risk mitigation strategies.
E. Updated the guidance for determining room/building and equipment explosion hazards.
F. Provided new guidance for the testing of non-combustible dusts and dust mixtures.
G. Updated the guidance for the evaluation and treatment of fugitive dust accumulations within buildings
and rooms.
H. Updated the guidance for enclosureless dust collectors to align with current FM Research guidance
on explosion potentials with these devices.
I. Provided new guidance for the hazards associated with horizontal drum filters (a subset of enclosureless
dust collectors).
J. Revised spray dryer fire protection guidance to reference FM Data Sheet 6-9, Industrial Ovens and
Dryers.
K. Relocated guidance for equipment isolation to Appendix E.
2.1 Introduction
Use FM Approved equipment, materials and services whenever they are applicable. For a list of products
and services that are FM Approved, see the Approval Guide, an online resource of FM Approvals.
2.1.1 General
2.1.1.1 Apply the guidance in this data sheet to all equipment, rooms and buildings that process, handle,
store and transport combustible dusts, dust mixtures or fibers, or anywhere they can be present.
2.1.1.2 Refer to FM Data Sheet 7-85, Combustible and Reactive Metals, for guidance on the protection of
combustible metal fires and hydrogen generating (water-reactive) metals.
2.1.1.3 Evaluate the potential for room/building or equipment explosion hazard in accordance with the
following:
A. A room/building explosion hazard exists when any of the following are true:
1. Combustible dust, dust mixture, or fibers is present outside of equipment and ducting located within
a room/building, despite process design and equipment upkeep.
2. Room/building containing combustible dust, dust mixture, or fibers handling/processing equipment
with a defined equipment explosion hazard that is not protected in accordance with this data sheet.
B. An equipment explosion hazard exists when any of the following are true:
1. Combustible dust, dust mixture, or fibers is handled/processed within a piece of equipment.
2. A piece of equipment generates combustible dust or dust mixtures as part of its operations (e.g.,
size reduction equipment such as hammer mills).
2.1.2.2 Conduct testing of combustible dusts, dust mixtures, or fibers to determine their properties before
designing explosion protection systems using recognized test standards/test methods including ISO, ASTM,
European Standards, etc.
2.1.2.2.1 Determine the following properties when testing combustible dusts, dust mixtures, or fibers:
A. Composition of any pure dusts or dust mixtures
B. The deflagration index (Kst)
C. Maximum pressure (Pmax)
D. Median particle size(s)
E. Moisture content
F. Materials subject to spontaneous heating
2.1.2.2.2 In some cases, combustible metal dust may require the use of larger scale explosion testing (e.g.,
use a 1 m3 sphere instead of the 20 L sphere) to develop an understanding of the material’s physical
properties due to the significant flame temperatures (e.g., greater than 5972°F [3300°C]) they develop.
2.1.2.2.3 Re-test combustible dusts, dust mixtures, or fibers when a change in composition, process, handling
or storage occurs.
C. The design and operation of the dust/dust mixture containing process follow the recommendations in
this document for process controls, grounding and bonding, ignition source controls, fire protection where
needed, non-combustible construction, and housekeeping programs.
2.1.4.2 Retest hard-to-ignite dusts or dust mixtures every five (5) years to ensure the dust of dust mixture
properties have not changed.
2.1.4.2.1 In cases where the process contains a known dust or dust mixture, i.e., dust mixture is tied to a
specific product, and the facility has a clear Management of Change (MOC) process, retesting of dust is not
required except as stated in 2.1.4.3.
2.1.4.3 Retest any dust or dust mixture after a change in formulation or composition to determine the
explosibility of the changed dust or dust mixture as part of the Management of Change process.
2.1.4.4 Where a change in composition or formulation of a hard-to-ignite dust or dust mixture renders the
material combustible or explosible, provide the required fire and explosion protection measures for a
combustible dust, per the guidance in this data sheet.
2.2.1 General
2.2.1.1 Construct buildings, piping, ductwork and equipment of noncombustible or FM Approved Class 1
materials. Examples of equipment include, but are not limited to:
• Dust collectors
• Cyclones
• The lining and packing materials used in wet dust collectors
• Bucket elevators
• Storage vessels containing combustible dust (e.g., silos and bins)
• Grain and malt dryers
2.2.1.1.1 If plastic ducts or ducts with plastic liners must be used, ensure they are FM Approved. If FM
Approved materials are not available, protect ductwork in accordance with FM Property Loss Prevention Data
Sheet 7-78, Industrial Exhaust Systems.
2.2.1.1.2 Where linings are added to the interior of a bucket elevator to address localized erosion issues,
use non-combustible materials. Where linings are required to be non-conductive or anti-static, these
properties should also be included when choosing the non-combustible linings.
2.2.1.2 Do not install combustible dust processes/operations in below-grade locations where adequate
explosion venting cannot be provided.
2.2.1.3 Locate dust control equipment and bucket elevators outside buildings. Dust control equipment includes
dust collectors, cyclones, electrostatic precipitators, etc.
2.2.1.4 Where dust processing and control equipment is present inside a building, and is protected by
explosion venting, locate the equipment along an outside wall to permit direct explosion venting outside the
building. Where vent ducts are used to direct explosion venting to the outside:
A. The ducts should be the shortest, straightest ducts practical.
B. The cross-sectional area of the duct should match the cross-sectional area of the explosion vent.
C. If a second vent panel is present where the duct exits to the exterior of the building, this panel should
be factored into venting calculations to ensure the explosion vents are adequately sized.
2.2.1.5 Design dust processes to prevent the release of dust into buildings by using sealed equipment and
dust collection systems at points of dust liberation.
2.2.1.6 In cases where dust liberation cannot be controlled, isolate the dust process from other areas within
the facility through the use of space separation and damage-limiting construction to prevent the propagation
of a dust fire or deflagration to other areas of the plant.
2.2.1.7 In rooms/buildings where some fugitive dust is likely despite process design, equipment upkeep and
use of dust collection systems, reduce the likelihood and amount of dust accumulation in areas that are not
easily accessible by any or all of the following, as appropriate:
A. Provide smooth interior walls with minimal ledges. Where smooth surfaces, ledges etc. should be used,
they should be of non-combustible construction.
B. Provide horizontal surfaces such as girders, beams, ledges, and equipment tops with a sloped cover
having a smooth finish, to shed dust settling out of the air.
C. Slope equipment covers at an angle of at least 60° from horizontal, unless a lesser slope is known
to be sufficient.
D. Enclose (box in) overhead structural steel that has horizontal ledges (such as I-beams or U-shaped
channels in the up or sideways position) with a noncombustible material to eliminate pockets for dust
accumulation.
E. Seal doors, windows, and any other wall penetrations (e.g., cables, ducts, etc.), where applicable, to
prevent dust migration into adjacent areas. Positive room pressurization can also be used to prevent dust
movement into adjacent areas instead of or in conjunction with seals.
F. Provide clearance beneath and around equipment as necessary to permit sweeping or vacuum cleaning.
2.2.1.8 Use DustCalc, Appendix D of this Standard and FM Data Sheet 1-44, Damage-Limiting Construction,
to design and install damage limiting construction in rooms/buildings with identified room explosion hazards.
2.2.2.4 Install a spark-arrester or settling chamber in the duct between process and collector, where spark
generation is common. A cyclone collector, scrubber or similar device that would deflect or extinguish heavier
embers or sparks from the gas stream is acceptable.
2.2.2.5 For dust collectors or collection systems handling noncombustible dusts, substitute a low
combustibility filter medium on a replacement basis for existing combustible bags/canisters.
2.2.4.2 Run conveyors connecting the workhouse to loading or unloading facilities and storage silos/tanks
above ground immediately after leaving subgrade structures. Avoid the use of tunnels or conveyor enclosure
galleries.
2.2.4.3 Locate elevating conveyors outside the workhouse, preferably as part of a separate structure. Inclined
conveyors are preferred over vertical bucket elevators.
2.2.4.4 Design and construct all facilities out of steel or reinforced concrete framing.
2.2.4.5 Provide damage-limiting construction for all enclosed areas, including but not limited to workhouses,
loading/unloading facilities, conveyor galleries and processing areas. Design the damage-limiting construction
using DustCalc and FM Property Loss Prevention Data Sheet 1-44, Damage-Limiting Construction.
2.2.4.6 Provide explosion venting along the length of elongated enclosures such as conveyor galleries.
2.2.4.7 Provide smooth, high-gloss finishes on interior wall and ceiling surfaces in the workhouse and in
bins above the maximum grain level to facilitate cleaning and to minimize horizontal surfaces where dust
can accumulate.
2.2.4.8 Construct storage silos as follows:
A. Use concrete or other non-combustible materials.
B. Provide damage-limiting construction designed per Data Sheet 1-44 and verified using DustCalc.
Arrange such construction so explosions vent outside and not into adjacent silos, bins or conveyors.
C. Construct the foundation in such a way that the retrieval conveyor beneath the bins is above grade
to permit the use of damage limiting construction.
This guidance relates to:
1. Open belt conveyors located below ground
2. Enclosed belt conveyors
In both situations, the location of these conveyor types provides an enclosure in which an explosion can
develop. Other conveyor types may present the same conditions, potentially allowing a dust explosion event.
A. Arrange breather vents for relieving dust-laden air to discharge directly to the outside. Do not vent one
bin into another or into a conveyor enclosure.
B. Avoid manifolding dust collection systems from different silo groups or tank groups.
2.3 Occupancy
2.3.1 Housekeeping
2.3.1.1 When fugitive dust is identified in a building, apply the following guidance:
A. Survey any equipment and/or ductwork where combustible dusts are generated, processed, handled,
collected or transported to identify any sources of dust release.
B. Modify, repair, or replace equipment and/or ductwork to eliminate, or at least reduce, dust escape.
C. Provide permanent dust collection pickup points for a dust collection system, a ventilated hood or
containment enclosure, where applicable, at the locations where dust is liberated.
D. Operate closed dust-handling systems under a slight negative pressure to reduce dust escape.
2.3.1.2 Where fugitive dust is released despite process design and equipment upkeep, apply the following
guidance:
A. Develop and implement a strict dust management program that clearly identifies where dust is being
released, where it is accumulating, and what the accumulation rate is. Audit the program on a regular basis.
B. Remove accumulations of dust where they are present. Prioritize the removal of accumulations in
below-grade areas or areas that are not visually accessible. These areas include but are not limited to
receiving tunnels near railcar and truck unloading stations, near openings for filling silos and bins, near
openings adjacent to bucket elevators, within electrical rooms and areas above floor level. Areas above
floor level include areas located above suspended ceilings, the tops of equipment and building structural
members.
C. Use vacuum removal wherever possible with a central, portable or truck-mounted vacuum system as
appropriate. Central vacuum dust collection systems are recommended for plants with inherently dusty
processes to facilitate plant clean-up and minimize dust clouds. In grain handling facilities, central vacuum
systems may operate from the elevator’s dust control system. Where used, these systems are to be
electrically rated for the dust hazards in the area.
D. Where vacuuming is impractical, sweeping or water wash-down are other acceptable options. Where
sweeping is used, soft push brooms are recommended; and pneumatic collector openings near floor level
may be used to pick up sweepings.
2.3.1.3. Where compressed air blow-down is the ONLY practical method for cleanup, use the following
precautions:
A. Shut down electrical equipment not suitable for Class II, Division 2 hazardous locations (or equivalent)
ratings and any operations.
B. Prohibit open flames and hot work, and ensure no hot surfaces exist.
C. Provide constant monitoring when blowing down, to ensure any dust suspended by the blowdown
operation does not create hazardous conditions (e.g., large dust clouds). The definition of hazardous will
depend on local conditions.
D. Limit the extent of blow-down to small areas at a time.
E. Conduct blow-down operations with as low a volume and pressure of air as possible.
F. Perform air blow-down frequently enough to prevent hazardous accumulations of dust. Required
frequencies and hazardous accumulations are dependent on location conditions.
2.4 Protection
2.4.1.3 In grain handling, storage and processing facilities, provide appropriate wet or dry standpipes at all
operating levels within elevator houses, conveyor structures, and cleaning and drying areas per FM Property
Loss Prevention Data Sheet 4-4N, Standpipe and Hose Systems. In unheated areas within these facilities
that are subject to freezing the following options are acceptable:
A. A small, approved deluge valve actuated by push buttons at each hose station. Emergency power should
be provided for any deluge valve circuitry. Ordinary hose valves may be used if pressure is not maintained
on piping.
B. A hose station supplied by a small dry pipe valve, separate from any dry pipe valves supplying sprinklers.
Low points should have drum drips and dual valves. Hose control valves should have an automatic air
device. Employees should be instructed in the operation of these devices and the need to allow air
discharge to occur until water reaches the hose.
2.4.1.4 Provide automatic sprinkler protection for buildings with additive manufacturing operations in
accordance with the following:
A. Design automatic sprinklers for all additive manufacturing areas (metal or plastic parts) in accordance
with FM Property Los Prevention Data Sheet 3-26, Fire Protection for Nonstorage Occupancies, for HC-2
occupancies.
B. Design automatic sprinklers for storage areas containing plastic feed stock in accordance with FM
Property Loss Prevention Data Sheet 8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities, in
accordance to how the materials are stored (i.e., cartoned or uncartoned).
C. Design automatic sprinklers for storage areas containing metal powders in metal containers based
on the surrounding occupancy. Sprinklers may be omitted in small noncombustible storage areas where
no combustibles are in the room except for the metal powders in metal containers.
Solenoid Valve
Compressed Air
Clean Gas
Outlet Air Nozzle
Venturi
Stay Grid
2.4.2.1.2 Provide rupture disks, hatches attached with springs or other reliable devices that actuate at 1.5
psig (10 kPa, 0.1 bar) or less where water from hose streams, sprinklers or water spray systems can
accumulate enough to result in structural damage to the collector. Locate these devices as close as possible
to the bottom of the hopper. Ensure the location of these devices does not interfere with venting.
2.4.2.1.3 Where a rotary valve is installed, interlock the rotary valve to stop on actuation of the collector
automatic water protection system.
2.4.2.1.4 In collectors handling non-combustible dusts, provide automatic water protection (see Section
2.4.2.1.1) EXCEPT for:
A. Collectors equipped with a fire resistive or flame-retardant filter media material
B. Small standalone collectors that, if damaged or destroyed, have only a minimal impact on business
interruption
C. Small standalone collectors that have a low frequency of fires. Where a high frequency of fires (more
than two or three in a year) or a high business interruption potential if the collector is destroyed or damaged
exists, protect the collector in accordance with the guidance in this standard for dust collection systems.
Collectors that have combustible filter media but handle non-combustible dusts still require sprinkler protection
due to the heat produced as the filter media burns.
2.4.2.1.5 Provide manual extinguishing equipment as follows when performing maintenance on a collector:
A. For small collectors: Portable extinguishers (preferably water-type units) are acceptable.
B. For larger, walk-in type collectors: Install 1-1/2 in. (40 mm) hose with a combination water spray/straight-
stream nozzle near the door outside the collector.
C. Provide access ports for all areas of the collector where necessary for effective manual firefighting.
To a Safe
Location
Separator
Tank
Drums for
Transfer
of Liquids Control
Recovered Panel
Fig. 2.4.2.7.6-1. Electrostatic precipitator with water spray protection for precipitator and ducts (only one duct shown)
2.4.2.7.7 Provide for drainage of the water originating from the protection systems. Slope ducts so that water
flow is toward the precipitator. Provide a separator tank for precipitators used to collect hydrocarbon mists,
so that discharge of the water spray system does not result in a release of hydrocarbon that could expose
plant buildings or property.
2.4.2.7.8 Provide interlocks to automatically de-energize the precipitator and shut down the fan on the exhaust
system upon actuation of the water spray systems.
2.4.2.7.9 Do not use electrostatic precipitators where dry combustible dust concentrations in air may exceed
the Minimum Explosible Concentration (MEC) due to the possibility of ignition by arcing in the precipitator.
2.4.3.1 General
2.4.3.1.1 Protect equipment with a dust explosion hazard using one or more of the following options, unless
specified otherwise in the equipment specific sections listed in Section 2.4.3:
A. Damage limiting construction. This includes explosion venting, combinations of explosion venting and
pressure resistance, and explosion containment
B. FM Approved flameless venting devices
C. Explosion isolation
D. Inerting
E. Explosion suppression
Examples of equipment to be protected include but are not limited to:
• Dust collectors
• Process vessels (mixers, blenders, etc.)
• Silos and bins
• Crushing equipment (Mills)
• Bucket elevators
• Dryers
2.4.3.1.2 When using damage-limiting construction to provide explosion protection for a piece of equipment,
design the damage limiting construction using DustCalc, Appendix D of this data sheet, and the following:
A. For equipment/vessel fitted with explosion vents located inside a room/building, direct the explosion
vents outside to a safe location. See also Section 2.2.1.4.
B. Do not use damage limiting construction to protect equipment/vessel with an explosion hazard created
by highly reactive combustible metal dusts.
C. Containment of an explosion within equipment/vessel (explosion-resistant design) is acceptable;
provided the design strength of the vessel can resist a pressure of at least 87 psig (6 barg), and the initial
pressure within the equipment/vessel is less than 1.5 psig (0.1 barg). Such a design should prevent
deformation of the equipment/vessel.
D. Providing explosion protection on equipment/vessels operating at pressures exceeding 1.5 psig
(0.1 barg) requires careful analysis. See Section C.3 for additional information.
2.4.3.1.3 When equipment/vessels located inside cannot be vented to the exterior of the building, use an
FM Approved flameless venting device in accordance with the following:
A. Select and install the device in accordance with Appendix D and the Approval Guide listing requirements.
B. Do not use flameless explosion venting devices with metal dusts.
C. Do not use flameless explosion venting devices with fibrous dusts or melting dusts unless specifically
FM Approved for such uses.
D. Do not use flameless explosion venting devices in areas where the liberation of fugitive dusts cannot
be prevented. The immediate area around the flameless explosion venting device should be kept free
of fugitive dusts. The size of the immediate area will be dependent upon the specific flameless vent used.
E. When using an FM Approved flameless venting device, make sure to account for the reduction in
nominal venting area (i.e., the effective vent area) caused by the installation of the venting device.
F. Do not cover (or install covers on) flameless explosion venting devices.
2.4.3.1.4 To prevent a deflagration from propagating between connected equipment/vessels or buildings,
use explosion isolation devices installed in accordance with the following:
A. Install the device(s) in accordance with Appendix E of this data sheet, Data Sheet 7-17 and the
manufacturer’s recommendations.
B. Where equipment, vessels or vessel groups are designed to contain the explosion pressure (explosion-
resistant design), explosion isolation should be provided on all connections to or from such equipment.
Rotary air-lock devices, high-speed abort gates, gate valves or chemical isolation systems are all isolation
systems that can be used. These should be installed per the guidance in this data sheet.
C. Long runs of ductwork, multiple bends within ductwork and changes in ductwork diameter are not
acceptable methods of explosion isolation/mitigation between connected equipment. Where needed,
explosion isolation should be provided per the guidance in this data sheet.
2.4.3.1.5 When a piece of equipment or vessel cannot be protected per 2.4.3.1.2 or 2.4.3.1.3 OR is critical
to a production process, use an FM Approved explosion suppression system in accordance with the following
and equipment specific guidance within this data sheet:
A. Design and install a FM Approved explosion suppression system in accordance with Appendix F, Data
Sheet 7-17, the FM Approval listing, and the manufacturer’s recommendations.
B. Where individual pieces of equipment/vessels had explosion suppression installed, provide explosion
isolation devices between these individual pieces of equipment/vessels.
C. Design the explosion suppression for the full volume of the equipment/vessel. Do not exclude the clean
plenum in a dust collector or the upper areas of a spray dryer.
D. Confirm that the final system pressure after the suppression system is discharged, including the
pressure rise created by the system discharge, is below the strength of the protected equipment/vessel.
E. Do not use explosion suppression for highly reactive metal dusts, unless test data developed using a
vessel of at least 1 m3 is available that shows the system design will work for this hazard.
F. Do not use explosion suppression systems in conjunction with explosion venting, unless the suppression
system is designed based on the assumption that venting is not provided.
G. Do not install explosion suppression systems where dusts with a Kst greater than 200 are used unless
proven effective by full-scale explosion tests. In general, these dusts cannot effectively be suppressed
due to their extremely fast rate of pressure rise.
H. Providing suppression on equipment/vessels operating at pressures exceeding 1.5 psig (0.1 barg)
requires careful analysis. See Section C.3 for additional information.
2.4.3.1.6 When a piece of equipment or process is protected with inert gas (inerting), use a gas inerting system
in accordance with the following:
A. Install gas inerting protection systems per the guidance in FM Property Loss Prevention Data Sheet
7-59, Inerting and Purging Vessels and Equipment.
B. When inerting equipment/vessels containing combustible metals, select an inerting gas that does not
react with the metal dust. See Data Sheet 7-59, and Data Sheet 7-85 for information on appropriate
inerting gases for various metals.
where:
Av,total is the total vent area required
Av,dirty,min is the minimum explosion venting area that should be on the dirty side of the dust collector
Vdirty is the volume of the dirty side of the dust collector
Vtotal is the total volume of the dust collector
2.4.3.2.4 Provide portable dust collection systems, such as vacuum cleaners, with appropriate protection
for the material being collected. This can include adequate venting, or explosion containment.
2.4.3.4.2 Route explosion venting for indoor elevators to the outside by short straight ducts, or provide FM
Approved flameless vents. Flameless vents should be installed per the guidance in this data sheet.
2.4.3.4.3 Install explosion venting in the head section (top) equivalent to the cross-sectional area of the casing
leg.
2.4.3.4.4 Install the first casing vent as close as practical to the boot (bottom) of the bucket elevator but not
to exceed the spacing shown in Table 2.4.3.4.1-1)
2.4.3.4.5 Size explosion vents equivalent to the cross-sectional area of the elevator leg enclosure. The vent
area can be installed as separate half-sized vents located on opposite sides of the enclosure.
2.4.3.4.6 Install explosion venting for the up and downside leg on double casing designs.
2.4.3.4.7 Explosion vents can be installed on the sides or face of the casing.
2.4.3.4.8 Set the explosion vent relief pressure (Pstat) to 0.1 barg (1.5 psig) or less, and construct vents of
lightweight material.
2.4.3.4.9 Where the elevator head or boot feeds into equipment or areas that have an explosion hazard,
provide explosion isolation (e.g., rotary air locks or chemical isolation) between the head or boot and adjacent
areas or equipment.
2.4.3.4.10 Where explosion suppression systems are used in bucket elevators, these systems should be
installed per Sections 2.4.3.1.5, 2.4.3.4.9 and Appendix F of this data sheet and the following guidance:
A. Where explosion suppression is used, it should be installed throughout all indoor elevator legs.
B. Within grain handling facilities where explosion venting has been installed (see Section 2.4.3.1.5),
explosion suppression blocking systems should be installed in bucket elevators in the boot, the infeed
and the discharge and head pulley areas to minimize the chance of an explosion propagating from one
area to another.
2.4.3.5.1 When evaluating explosion protection for spray dryers apply the following guidance:
A. The average dust concentration within the cylindrically shaped portion should be below the MEC of
the material being handled.
B. The average dust concentration within the cylindrically shaped portion should include (where present)
any recycle streams introduced at the top of the spray dryer.
2.4.3.5.2 Provide explosion protection for the spray dryer. Where explosion venting is used, FM’s DustCalc
software should be used to confirm the required explosion venting area accounts for a combustible cloud
existing within only a fraction of the total vessel volume.
2.4.3.5.2.1 Where other explosion protection systems are used (e.g., suppression and flameless venting),
follow the guidance for these protection systems as stated in this data sheet.
2.4.3.5.3 Evaluate connections from the spray dryer and downstream equipment following the guidance in
Section 2.4.3.1.4.
2.4.3.5.4 When explosion vents are installed on a spray dryer, distribute the explosion vents uniformly around
the circumference of the dryer. Vents should be placed in or near the conical section of the dryer first, as
this is the area with the greatest explosion hazard. See Figure 2.4.3.5.4-1.
Explosion vents
AS
100'
Sprinklers or
spray nozzles as
applicable
Exess-temp.- AS
limit switch Skirt
Exess-temp.-
Hot air limit switch
furnace
AS
Combustion Fixed temp.heat
chamber responsive device for
deluge valve
AS
Deluge valve
(if applicable)
Hydraulic Diameter = 4A
p
Where:
A = cross-sectional area of vent
p = perimeter of the cross-section
C. Provide a vent area at each location at least equal to the cross-sectional area of the duct.
D. Provide a full-size vent no more than two diameters away from the point of duct connection to a piece
of equipment.
E. Set the explosion vent relief pressures (Pstat) as low as possible with a maximum value of 0.1 barg
(1.5 psig).
F. Provide an explosion vent at all elbows and end flanges (see Figure 2.4.3.7.5-1).
G. When located inside, route the explosion products outside via a short duct (L/D less or equal to 1).
2.4.3.7.6 Ductwork used for dense phase pneumatic conveying of combustible dusts can be installed without
explosion isolation devices if the conveyed material is not metal dust or a hybrid mixture. Dense phase
conveying usually presents no hazard of explosion propagation.
2.4.3.8.3 Install part of the explosion venting on the dust collector, if possible, not to exceed the cross-sectional
area of the connecting pipe (although all of the explosion venting can be on the silo).
2.4.3.8.4 Where the dust collector/silo combination does not meet the criteria of a single unit, provide
explosion venting for each component based on their individual volume; and provide explosion venting for
the connecting duct itself.
2.4.3.8.5 Ensure the explosion venting area provided for a silo does not exceed its cross-sectional area
(Ax-sect).
2.4.3.8.6 If calculations show the explosion venting area required is more than the cross-sectional area, use
an explosion-suppression system or reinforce the silo so it can withstand the value of Pred corresponding
to Av = Ax-sect.
2.4.3.8.7 Do not use air cannons to break bridges in silos handling combustible materials, if particles smaller
than approximately 500 microns exist within the material.
2.4.3.8.8 Do not use weak seam roofs or weak roof-to-shell seams as explosion vents on vessels containing
combustible dusts.
2.4.3.8.9 Where turnhead distributors are used, fit the turnhead distributors with a rotating annular sleeve
to seal any spouts when not in use.
2.4.3.8.10 When bins are being filled, pressurize turnhead distributors to minimize dust buildup within the
equipment.
Turnhead distributors are hollow conical casings commonly found in bulk storage occupancies (e.g., grain
handling and grain storage). The simplest of these has a single inlet feed at the top and multiple outlets at
the bottom. The inlet feed can be rotated (turned) within the conical structure to distribute products to a specific
area (such as a particular storage silo or bin).
2.5.1 General
The following methods of dust control reduce the frequency of dust fires and explosions. Providing one or
more of these methods does not preclude or remove the need for fire and explosion protection. In all cases,
a thorough evaluation of the fire and explosion hazards must be undertaken.
2.5.1.1 When possible, preclean the combustible material to reduce the amount of fines (particles less than
75 microns in size) within it and/or the process equipment.
2.5.1.2 Choose dust handling and conveying processes that limit the production of fines.
2.5.1.3 If a liquid suppressant mist (water or other compatible liquid) system is used to reduce airborne dust
liberation from solids being moved on a conveyor, do the following:
A. Use a non-ignitable liquid suppressant. If a non-ignitable suppressant is not available, use an ignitable
liquid with a minimum closed cup flash point greater than or equal to 414°F (212°C).
B. Apply the liquid suppressant as close to the solid material surface as possible.
C. Use the lowest pressure possible for spraying the liquid suppressant to prevent the creation of a liquid
mist in the air around the application zone.
D. Interlock the solids conveying system and the liquid suppressant system to shut down if:
1. The conveyor stops moving
2. The liquid suppressant system shuts down
3. A fire or explosion is detected
E. Apply the liquid suppressant at a point in the process that involves substantial turbulence (e.g., at a
discharge spout), to ensure the suppressant is thoroughly mixed with the material stream.
F. Do not apply oil or other liquid suppressants to equipment, where it could lead to slipping of the rubber
belts and potential friction heating.
2.5.1.4 Do the following when charging vessels/equipment having both combustible powders and ignitable
liquids when the ignitable liquid is handled at or above its closed cup flash point:
A. Avoid simultaneous charging of the powders and the liquids into the equipment.
B. Arrange liquid charging operations in accordance with FM Property Loss Prevention Data Sheet 7-32,
Ignitable Liquid Operations. Use a dip tube to fill the vessel/equipment from the bottom.
C. Arrange dust charging operations to minimize the dispersion of dust outside the equipment opening
by using screw conveyors or closed shoots connected to solids charging tanks.
D. If dust can escape from the equipment opening, arrange permanent dust pickup points adjacent to
the opening.
E. Ensure all equipment, including the vessel and the transfer pipes/ducts, are properly grounded and
bonded.
F. If the dust has a minimum ignition energy (MIE) equal to or less than 10 mJ, provide a grounding
management system that confirms all conductive elements are properly grounded before allowing the
introduction of the low MIE dust.
B. For steady dust-generation rates without significant peaks, keep the dust concentration to no more
than 90% of the MEC.
2.5.2.6 For non-alkali metal dusts, use wet dust collectors.
2.6.2.2 When conducting inspections of explosion vents, ensure the condition or mobility of the vents is not
impaired. Possible impairments include the following:
A. Corrosion
B. Improper painting of movable parts or rupture membranes
C. Icing
D. Snow accumulation on or in front of vents
E. Obstruction by pipes, wires or other utilities
F. Permanent or temporary equipment located next to the venting device
2.6.3 Remove accumulated dust on rotating equipment bearings and components at least quarterly.
2.6.4 Lubricate bearings and rotating equipment (fans, blowers, size-reduction equipment) in accordance
with manufacturer’s guidelines. At a minimum, this lubrication should be completed quarterly.
2.6.5 Where suppressant spray systems are present (e.g., oil/water spray systems for bulk grain handling),
develop a maintenance and inspection program to ensure the dust suppressant spray system is functioning
properly whenever grain is being handled.
2.6.6 Maintain and inspect all interlocks in accordance with the guidance in FM Property Loss Prevention
Data Sheet 7-45, Safety Controls, Alarms and Interlocks (SCAI).
2.6.7 Maintain electrically rated equipment classified for use in combustible dust areas per the guidance in
FM Property Loss Prevention Data Sheet 5-1, Electrical Equipment in Hazardous (Classified) Locations.
2.7 Training
2.7.1 Create a training program for all employees (including operators, emergency response team
management, contractors and security personnel) who work in or have access to areas containing or
processing combustible dusts. Design and supervise the training program to address the complexity of
process operations and the hazard level present at a given facility. At a minimum, include the following in the
program:
A. The hazards of the materials in use
B. Common ignition sources for combustible dusts
C. The proper operation and shutdown of the equipment under normal and emergency conditions. Post
critical procedures as needed.
D. Proper material handling procedures (i.e., grounding and bonding, electrical ratings, manual handling,
etc.)
E. Combustible dust duct system operations and shutdown, including all local and remote shutdowns of
the transport media
F. Proper combustible dust transfer procedures
G. Explosion protection equipment related to combustible dusts within the facility and their locations. Items
to be addressed include (as appropriate):
• Explosion vents
• Flameless venting devices
• Back-blast dampers
• Abort gates
• Valves (e.g., guillotine and float valves)
• Suppression systems
• Explosion containment
• Inerting systems
2.9.2 Sparing
Sparing can be a mitigation strategy to reduce the downtime caused by a dust collection system breakdown
depending on the type, compatibility, availability, fitness for the intended service, and viability of the sparing.
Routine dust collection equipment spares are spares that are considered to be consumables. These spares
are expected to be put into service under normal operating conditions over the course of the life of the dust
collection systems but not reduce equipment downtime in the event of a breakdown. This can include sparing
recommended by the original equipment manufacturer.
2.9.2.1 For general sparing guidance, see Data Sheet 9-0.
2.10.1 General
2.10.1.1 Develop and use a hot work program to manage all hot work operations. (See FM Property Loss
Prevention Data Sheet 10-3, Hot Work Management).
2.10.1.2 Prohibit smoking and open flames.
2.10.1.3 Do not use space heaters that have any exposed surfaces where the temperature is above 340°F
(171°C).
2.10.1.4 Provide magnetic separators at the following locations:
A. Upstream of all size-reduction equipment (e.g., grinders, pulverizers, milling or grinding equipment,
or other equipment involving mechanical impact with the process material)
B. At car and truck dump hoppers and associated conveyors prior to entering the plant/process
C. At other incoming transition points where materials first enter a plant/process from areas outside of
the plant/process
2.10.1.5 Provide separators other than magnetic (e.g., air separators, grates, coarse screens) if nonferrous
metal or other objects (e.g., rocks) could enter the product stream and cause an ignition hazard.
2.10.1.6 Within buildings where loading/unloading of railcars or trucks takes place, do not operate railroad
locomotives or other vehicles that could ignite a dust cloud while the dust cloud is present.
2.10.1.7 Vehicles such as lift trucks or front-end loaders operating in any facility where combustible dusts
are present should be rated per the guidance in FM Property Loss Prevention Data Sheet 7-39, Lift Trucks.
A. Operate any equipment that presents an explosion hazard under an inert environment.
B. Operate at a pressure of less than 0.1 bara (1.5 psia).
C. Eliminate the ignitable mixture by operating at no more than 50% of the MEC.
D. Reduce charge generation or accumulation with process changes, such as reducing the flow rate of
the transferred material.
E. Provide static eliminators or neutralizers. Ensure they are firmly fixed, well grounded, properly adjusted
and kept clean of foreign accumulations.
2.10.6.4 Do not store excessively wet materials subject to spontaneous heating within bins, silos or other
storage vessels for long periods.
2.10.6.5 Where storage of materials subject to spontaneous heating is required, use any/all of the following:
A. Install heat detectors in silos and bins used for long-term storage.
B. Maintain air flow within the vessels to remove heat generated.
C. Turn over the materials storage at frequent intervals to prevent heat generation.
D. Do not store excessively wet materials in silos or bins.
E. Use a first-in/first-out process for stored materials.
Where:
v = length (same units as r) per second
r = length of the rotating part from shaft center to outer tip
2.10.7.3 Where low-velocity, high-power equipment is used, protect against uncontrolled heating using one
or more of the following:
A. Shear pins
B. Overload detection and alarm
C. Proper maintenance and cleaning
D. Screens and Separators
Excessive heating in such equipment can be due to excessive residence times of material, accumulations
at bearings and foreign objects.
2.10.8.4 Do not locate or expose bearings within the bucket elevator casing. Locate bearings outside of
machinery enclosures, where overheated bearings will be less exposed to dust clouds and more accessible
for inspection and service.
2.10.8.5 Use antifriction bearings on all elevator legs.
2.10.8.6 Maintain all bearings per manufacturer’s recommendations and keep them free of dust, product
and excessive lubrication.
2.10.8.6.1 Within grain occupancies, bearings for conveyor bucket elevator terminal pulleys should be press-
or shrink-fitted with tapered adapter sleeves.
2.10.8.6.2 Within grain occupancies, do not use slip-fit bearings secured with set screws.
2.10.8.7 Do not apply oil or other liquid suppressants in bucket elevators, as this could lead to slipping of
the rubber belts and potential friction heating.
2.10.8.8 Limit the use of combustible linings (e.g., plastic, rubber, wood) to impact points, wear surfaces
and connected hoppers.
2.10.8.9 Install drive belts (e.g., v-belts, timing belts and flat belts) that are electrically conductive at 1
megaohm or less, as well as being fire and oil resistant.
2.10.8.10 Design the drive train with a 1.5 service factor to stall the drive without slipping.
2.10.8.11 Install belts in elevator legs that have a surface resistivity of less than 100 megaohm per square
foot (3 x 108 Ohms per square foot) and are fire and oil resistant. (Oil resistance is not needed in flour mills.)
2.10.8.12 For elevator legs whose belt speeds exceed 500 ft/min (2.6 m/sec) provide bearing-temperature
monitoring or vibration detection.
3.1.1 Fuel
Fuel must be in dust form. To characterize a dust sample, the “mass median particle size” is typically used
to quantify the range of particle sizes that exist. If a fraction of finer material within the sample could become
segregated, then the system consists of two distinct particle streams each with its own median particle size.
Any stream with a median particle size smaller than 500 microns should be considered explosible until proven
otherwise by testing, although a particle size as low as 420 microns has been used in the past as the upper
limit of explosibility. Note that a sample with a median particle size above 500 microns could still present an
explosion hazard if it is suspended in a dust cloud.
3.1.3 Oxidizer
In a dust cloud, the oxidizer (usually air) is intimately mixed with the fuel. This condition allows for rapid
combustion of a large amount of material and the rapid release of a large amount of energy.
3.1.4 Suspension
Combustible dust needs to be suspended in air before an explosion can occur, because the rate of combustion
of a material is proportional to the exposed surface area. In a pile or layer, the exposed surface area is limited.
In a cloud, the exposed surface area is significantly greater. This phenomenon of faster combustion with
greater surface area availability partly explains why energy is so rapidly released in a dust explosion.
3.1.5 Confinement
A small cloud of dust ignited in a large open area is not truly a dust explosion. This situation may be referred
to as a flash fire, fireball or deflagration. If the combustion gases are totally or partially contained in a closed
volume, and the volume expansion produced by combustion does not immediately dissipate to an unconfined
environment; the pressure produced can lead to an explosion. Even if the vessel is vented, combustion of a
dust cloud within the vessel is still considered an explosion.
also be available in a safety data sheet for the material and/or the individual components. Knowing the
composition of a material (or mixture) helps to determine any potential fire and/or explosion hazard.
The three photos below (Figure 3.1.6.2-1) show table salt, granular (table) sugar, and wheat flour, highly
magnified. The salt is mostly in the 250-to-500-micron range, and the median is 375 microns. The sugar is
also mostly in the 250-to-500-micron range, and the median is 400 microns. Finally, the flour is almost
entirely under 125 microns with a median particle size of about 60 microns.
3.1.8 DustCalc
DustCalc is FM’s proprietary software for verification of explosion vent area and prediction of explosion effects
based on the specifics of a given situation. This data sheet does not include any explosion vent sizing
equations, nor does it have any dust-testing results to characterize previously tested materials.
DustCalc software is available in all FM offices worldwide but is limited to FM personnel who have been
trained in the details of its basis and use. Clients are encouraged to work with those FM personnel trained
in DustCalc.
The variables that have an impact on explosion effects are as follows:
• Vessel/room volume (V)
• Dust explosibility constant (Kst) and maximum unvented pressure (Pmax)
• Explosion-vent area (Av)
• Explosion-vent relief pressure (Pstat)
• Explosion-vent panel mass and orientation
• Explosion-vent duct length (Ld) and area (Ad), if present
• Fraction of vessel volume containing an explosible mixture
• Pre-explosion equipment pressure (Po)
3.2 Occupancy
3.2.1 Housekeeping
Combustible dust accumulations outside of equipment—known as fugitive dust—present the potential for
an explosion. As stated in Section 2.0 of this data sheet, eliminating the source of the fugitive dust release
should be the priority, with the subsequent removal of any fugitive dust accumulations where these situations
exist. Damage Limiting Construction (DLC) and space separation are options for areas that are subject to
uncontrolled releases that cannot be resolved.
As a rule of thumb, in areas that are subject to uncontrolled releases that cannot be resolved (see Section
2.3.1), 1/16 in. (1.6 mm) of dust is a cause for cleanup. This amount is about the thickness of a US quarter
(25¢ coin) and assumes wood dust with an approximate bulk density of about 36 lb/ft3 [580 kg/m3].
Where dusts of different bulk density are used, the thickness of the equivalent mass of 1/16 in. (1.6 mm)
wood dust would be inversely proportional to their bulk densities. For example, for a dust with a bulk density
of about 60 lb/ft3 (950 kg/m3), a layer of about 1/25 in. (1 mm) thick would be equivalent.
Equivalent thickness = 1.6 mm x (580 kg/m3 / 950 kg/m3) = 0.97mm (rounded up approximately 1 mm in
thickness.).
For reference, typical bulk density data is given in Table 3.2.1-1.
3.3 Protection
3.3.1 Detection
High-speed, infrared detectors are most suitable for detection of burning or smoldering dust particles in a
duct transporting dusts at high velocities. Abort gates or extinguishing systems actuated by these detectors
can prevent an ignition source from reaching a bag collector or quickly control and extinguish a fire in a
collector before the bags are damaged (see FM Property Loss Prevention Data Sheet 5-48, Automatic Fire
Detection).
Sensors to activate these systems are usually located in the duct as close to the process as possible, unless
a fan is located in the duct between the process and the dust collector. Where this situation occurs, sensors
should be located between the fan and the dust collector. In manifolded ducts, the sensors are located on
the main exhaust duct close to the point of the last duct connection.
• Maintenance of canisters is easier, and filter changes are faster than with bags.
• Canister filters offer high efficiency and low pressure drop. This makes them best suited for dry dusts
and applications handling high quantities of particles less than one micron in size.
• Canister filters have a shorter service life than filter bags and deteriorate faster.
• Canisters are not suited to high temperatures, but some specialized filter media for high temperature
applications exist. Filter bags operate well in collectors where elevated temperatures (heat), moisture,
heavy dust loading and/or fibrous dusts are seen.
Dust is collected on the filter media (bags or canister media) in a layer. This layer of dust is then removed
(cleaned) from the media, collected and removed from the collector itself. Filter cleaning methods can include:
1. Shaker cleaning – This is generally seen in filter bag units rather than canisters. A vibratory action shakes
the dust off the bags.
2. Reverse air flow – Incoming air is stopped to allow the cleaning process to occur. Cleaning is
accomplished via high pressure air flowing in the reverse direction across the media. If the incoming
air cannot be stopped, two compartments within the collector with diverter valves are required.
3. Pulse jet cleaning involves using compressed air that blows the dust off the filter media surface. Incoming
air need not be interrupted. This cleaning method is the most common for canister units and is the
most aggressive cleaning method. Air pulses are in the range of 0.1-0.15 seconds with a frequency
between pulses in the range of 1-30 seconds.
Pulse-jet or reverse-jet collectors can process air with higher dust/air concentrations than can shaker-type
units. They are often used when small air volumes are processed or as part of a continuous process.
Bag filter units and canister filter units present the same fire hazard. As such, they should be fitted with
automatic sprinkler protection per the guidance in this data sheet.
Use of dust collectors is generally the most economical way to meet local air pollution codes. Air from
collectors may be recirculated to the plant as an energy conservation measure.
In dust-collection equipment, detection and/or monitoring systems commonly known as bag-break monitors
may be present. Such devices provide advance warning of a filter media failure by monitoring the level of
combustible particulates within the equipment. This warning assist with maintenance activities and reduce
atmospheric emissions of dust from this equipment.
These filters can be enclosed, or they can be enclosureless. If enclosed, they have the same hazards as a
regular dust collector and should be protected as such.
Enclosureless air (drum) filters cannot be fitted with venting due to their construction. The hazard with these
units is the same as for enclosureless collectors, and they should be treated and protected as such.
Interlocking these units to shut down in the event of an interruption to the power and/or loss of suction is
something that should be considered also.
These devices should not be confused with rotary drum filters seen in some occupancies to remove dust
or with rotary drum vacuum filters seen in wet milling operations.
Table 3.4.2-1. Operating Temperature Limits for Commonly Used Filter Media as Woven or Felted Fabric.
Filter Medium Operating Temperature Limit
Cotton 180°F (82°C)
Wool (seldom used) 190°F (88°C)
Polypropylene 200°F (93°C)
Nylon 200°F (93°C)
Polyester 275°F (135°C)
Acrylic (Woven) 275°F (135°C)
Acrylic (Felt) 250°F (120°C)
Nomex 400°F (204°C)
Teflon Polytetrafluoroethylene 425°F (220°C)
Fiberglass 500°F (260°C)
Clean gas
Relief vent
Dust bin
Cyclone collectors are used widely for collection of coarse dusts generated in operations such as
woodworking and metal grinding. They may also be used as rough filters to reduce dust loading on bag type
dust collectors or electrostatic precipitators.
The cleaned air is exhausted to the atmosphere or to a more efficient collector, such as a dust collector,
for further treatment.
High efficiency cyclones consist of a number of small diameter cyclones, usually under 10 in. (250 mm) in
diameter, arranged in parallel with a common hopper and common inlet and outlet plenums. Separation forces
increase with radial velocity of the particle. Radial velocity in turn increases with decreasing diameter of
cyclone tube. High efficiency cyclones may make further air treatment unnecessary.
Transformer-
rectifiers
To
atmosphere
From
process
Charging electrodes
for first field
Fig. 3.4.5-1. Single stage electrostatic precipitator. (Unit is separated into two compartments by vertical partition; each
compartment has three fields; material collected on plates drops down into hopper below.)
Voltage is supplied to the charging electrodes, increasing from a preset level to a point where the gas between
the electrode and the collecting surface ionizes and an electrical discharge (corona discharge) occurs. The
voltage is then automatically reduced to a preset level, and the cycle is repeated. Collection efficiency is
highest immediately before the corona discharge.
Mechanical rappers or water wash are used to transfer particulate to the hopper below. Collected particulate
is removed from the hopper through rotary valves or by screw conveyor.
Large single stage precipitators may have two parallel compartments. Each compartment has from three to
five collection fields arranged in series with their own power supply. Rectifier transformers on large units
are usually mounted on top of the precipitator. Overall collection efficiencies on modern precipitators may
range up to 99.9%.
In double-stage precipitators (Figure 3.4.5-2), charging electrodes are located upstream of the collecting
surfaces, with the electrodes arranged parallel to the flow of gas.
Double-stage precipitators may be encountered in metalworking operations and air purification systems for
clean rooms. Larger double stage precipitators are frequently used to meet Environmental Protection Agency
(EPA) requirements in plastics working, rubber curing, printing, textile-finishing and asphalt-saturating
processes.
If solid particulate or a combination of solid particulate and oil mist is collected, a prefilter is generally located
upstream of the precipitator. The prefilter may be fiberglass or a series of baffles.
Small double stage precipitators [up to 10,000 cfm (280 m3/min)] are usually located at ceiling level near
the equipment they serve or on mobile carts inside the work area. Cleaned air is usually returned to the work
area. Units larger than 10,000 cfm (280 m3/min) are usually located on the roof or on the ground adjacent
Power supply
Mechanical
Mechanical afterfilter
prefilter
Charging electrodes
Ionizer section Collecting plates
Collecting cell
to the building. These units often serve more than one piece of equipment. Ducts usually pass from the
equipment directly through the roof. The ducts are manifolded and enter the precipitator. Cleaned air is usually
exhausted to the atmosphere.
Elevator
head
Spouts
Elevator Scales
legs
Bins
Conveyor
Cleaning,
screening,
etc.
Truck Cleaning,
or car etc.
unloading Cleaning or
bagging
Conveyor Conveyor
Elevator
boot
Weigh scales are present to allow the grain(s) to be weighed at various points within the facility. Grain
sampling is performed as the grain passes from the shipping bins to belt conveyors for transfer to ships,
barges, rail cars, etc.
Within flour or feed milling operations, various mills, separators and blenders, bagging, bulk storage or bulk
loading areas are common. Other processes such as mash tubs or cookers may also be present.
Ignition source control and housekeeping are the traditional methods used to reduce the potential for an
explosion within these facilities. Hence explosion venting, if present, is usually inadequate.
Explosive dust and air mixtures can develop within the legs of a bucket elevator, especially in the down leg
where residual dust from the upside-down buckets can filter through the entire leg. Common ignition sources
include overheated bearings in the head, knee or boot of the conveyor, cutting and welding, tramp metal, or
falling buckets. An explosion originating in an elevator leg, especially one located inside a concrete shaft
in the workhouse, can rapidly develop extreme pressure and transmit it throughout the entire elevator.
Chain conveyors (Figure 3.4.8-1) can also be used. They consist of paddles or flights in a heavy steel, usually
dust-tight, enclosure, installed vertically, horizontally or in an incline position. The flights and material within
form a solid mass as they move upward. Dust accumulations with the legs are usually less than that seen
in bucket elevators.
Conventional belt conveyors installed on an incline may also be seen in lieu of vertical elevators. Such an
installation requires considerable space but eliminates the need for any elevator legs.
For short conveyor runs, screw conveyors are common. These conveyors can provide a choked feed,
especially if flights are omitted. One hazard with screw conveyors is that material particles can be caught
between the auger and the enclosure and be partially ground, creating dust. Hence, ensuring that the duct
around the screw conveyor be completely dust tight is important.
Pneumatic conveying may be used for light materials including dusts. Pneumatic conveying is generally used
to transport materials between processes as well as for dust collection. Interconnected pneumatic ducts may
provide a means of carrying burning material throughout a facility. Design of the ducts should prevent dust
from escaping into the external environment as it is transported.
Additional dust is generated each time the grain is transferred, but it is usually returned to the grain stream.
Larger quantities of dust must be handled in regional and export elevahead3tors as opposed to country
elevators or other grain handling facilities such as those at solvent extraction plants, distilleries, etc. In
addition, certain grains (i.e., corn, milo) produce more dust than others (i.e., wheat).
controlled by maintaining sufficient airflow, typically on the order of 3,500 – 4,000 ft/min (18-20 m/sec). Dust
that has accumulated can be re-entrained by the pressure wave from an explosion and create localized
combustible concentrations that can move and become ignited by the trailing flame front. After considerable
propagation, this turbulent jet flame becomes a very strong ignition source (see Appendix A) that can destroy
even properly protected equipment.
A small amount of deposited dust can propagate an explosion. For a circular duct of diameter ”D” with a
dust layer of thickness “h” settled on 1/4 of its inner circumference (i.e., at the bottom), the concentration of
dust dispersed homogeneously throughout the cross section of the duct would be C = ρbulk h/D.
As an example, a dust with a bulk density of 31 lb/ft3 (500 kg/m3), a thickness of only 1/125 in. (0.2 mm)
and a duct of 8 in. (0.2 m) diameter, could generate a dust concentration of 500 g/m3. This concentration is
well above the MEC of virtually any dust; and therefore, can propagate an explosion.
The settled dust is most likely not homogenously dispersed throughout the duct, but research by the US
Bureau of Mines has shown that explosions can propagate through ducts even at dust concentrations as low
as half the MEC. Propagation only requires a continuous path of mixture that is above the MEC. This condition
can be satisfied even when not enough dust exists to fill the entire volume of the duct with a mixture above
the MEC. Even very small amounts of dust can be sufficient to create a propagating explosion. Thus, the air
velocity through the duct should be sufficient to prevent any settling of the transferred dust.
Explosion venting in duct work is not provided to save the duct (which is usually of low value and easily
replaced) but to reduce the violence of a potential explosion propagating down its length. Venting would not
stop the explosion propagation but would reduce the intensity of the ignition source to exposed, connected
equipment. Designing the duct to fail at low pressure rather than installing explosion vents could be an
acceptable alternative approach where no equipment exposure exists.
Explosion isolation systems may be needed for connecting ducts where the consequence of an unprotected
event in equipment or flash-back to a building is unacceptable. For example, a large panel sander might
have six dust pickup points, three on the top and three on the bottom, all joining into a common duct. Each
pickup pipe would not need an isolation device. Explosion isolation would best be provided on the main duct
after it leaves the building to prevent an explosion in the dust collector from propagating back towards the
sander.
3.4.10 Silos
Silos can also present a dust explosion hazard, even when they are used with granular material having a
very small portion of fines. As the coarse material continually transfers into the silo, it will fall to the bottom,
but the finest, most explosible material will remain in suspension. If transfer operations continue long enough,
the airborne combustible dust concentration will exceed the MEC and create an explosion hazard.
When a dust collector is mounted directly onto a silo (i.e., with a short connecting pipe of sufficiently large
diameter), any explosion originating within the dust collector will create a silo explosion as if the explosion had
originated there. So, the dust collector can be considered part of the silo. Explosion venting provided on
the silo and dust collector assembly and sized based on the sum of both volumes is adequate, regardless
of whether an explosion originates in the silo or the attached dust collector.
When the dust collector is separated from the silo via a small or elongated pipe, the silo and dust collector
no longer act as a single volume during an explosion. If an explosion originates in a dust collector that has
no explosion venting of its own, the jet flame will propagate down the connecting pipe, igniting any combustible
dust cloud within the silo. This situation would cause a much more violent explosion than if the silo explosion
was ignited by a conventional (weaker) ignition source.
Air cannons used to break up bridging material can disperse fines in the bulk material into the silo headspace.
Even if the percentage of fines is very small (e.g., 1-2%), repeated air blasts will concentrate the fines at
the top of the bed. Repeated air-cannon operation creates more fines at the top of the bed and a higher
concentration of dust in the head space at every air cannon firing. Only an ignition source is needed for a
potentially severe dust explosion.
Additionally, certain combustible materials such as coal, grain and wood are susceptible to spontaneous
heating; and introducing air over an extended period of time can increase the probability of such spontaneous
heating. Air introduced to glowing combustion could fan it into flames or ignite a dust explosion.
Alternative solutions to air cannons include using vibratory wands inserted temporarily or permanently into
the bottom portion of the silo or using acoustic horns and lances.
3.5 Protection
Precipitators serving cement kilns, black liquor recovery boilers and pulverized coal-fired boilers have a high
frequency of loss, despite handling non-combustible materials.
The most common forms of protection for electrostatic precipitators are automatic sprinkler or water spray.
Carbon dioxide and steam suppression are also used as supplementary protection to sprinkler/water spray
systems. Fixed temperature detection is the usual form of actuation for these systems, either in the ductwork
or the precipitator.
Powder
AM Category bed
processes
Powder bed fusion is generally the most common method used with metal powders. It involves using digital
design data to construct a component by depositing a layer of material 20 to 100 microns thick (0.0008 to
0.004 in. [0.02 to 0.1 mm]), fusing the component pattern into the layer and repeating the sequence until the
“build,” (the part being created) is complete. With metal powders, the fusing is done with a laser or electron
beam; while polymers/plastics may be fused with a laser or a binding liquid sprayed onto the powder layer.
Figure 3.7-4 is a schematic representing the selective laser sintering (SLS) fusion bed technology that
produces the actual product. The powder layer is distributed by a spreader bar located just above the surface
of the build platform or the prior layer.
Material deposition processes use powders or extrusion methods to build the design layer-by-layer. One
technique uses selective dispersion of a powder through an aerosol jet, followed by fusing with heat or an
electron beam (material jetting). These processes use small individual “shots” of material and typically do not
create clouds of dust in the equipment.
Material
AM Category deposition
processes
3D Printing Liquid
AM Category
Sterolitho
Process Type graphy (SL)
Thermosets
Elastomer
Graphite
Lenses
Scanning mirror
Laser beam
Leveling roller
Sintered part
Powder
feed supply Powder bed
Fig. 3.7-4. SLS design concept (Chemical Engineering Progress, May 2014)
For liquid plastic resins used in a pool, the shaping mechanism fuses the polymer into the form needed
(stereolithography) with light beams (laser, UV). One method uses high flash point liquid resins (over 212°F,
100°C) and moderate flash point cleaning fluids (185°F, 85°C).
The build material can be fine powdered metal, plastic, ceramic or glass. Commonly used metal alloy powders
include cobalt-chromium, aluminum-titanium, magnesium, stainless steel (iron and chromium plus other,
lesser metal additives) and Inconel (nickel and chromium with iron and other metals as lesser additives).
Material explosibility (Kst) varies with the particular metal or alloy. Dust should generally be considered
combustible until proven otherwise by testing.
Figure 3.7-5 shows examples of typical industrial printers. The ProX 300 and the Concept M2 have a build
envelope (chamber for the printing part) of about 10 x 10 x 12 in. (250 x 250 x 300 mm). The industrial-scale
printer can cost US$0.5 million or more per machine.
Fig. 3.7-5. Industrial-scale 3D systems: ProX300 and Concept M2 Laser printers (Source: manufacturers’ brochures)
jets in a glove box enclosure. Where air blowdown is used it could create a small, local, dust flash fire hazard;
or an associated dust collection system could present a dust explosion hazard.
4.0 REFERENCES
4.1 FM
Data Sheet 1-28, Wind Design
Data Sheet 1-44, Damage-Limiting Construction
Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers
Data Sheet 4-4N, Standpipe and Hose Systems
Data Sheet 5-1, Electrical Equipment in Hazardous Locations
Data Sheet 5-8, Static Electricity
Data Sheet 5-48, Automatic Fire Detection
Data Sheet 6-9, Industrial Ovens and Dryers
Data Sheet 7-10, Wood Processing and Woodworking Facilities
Data Sheet 7-14, Fire Protection for Chemical Plants
Data Sheet 7-17, Explosion Protection Systems
4.2 Other
Air Movement and Control Association (AMCA). Classifications for Spark Resistant Construction. AMCA
99040186, latest edition.
American Society for Testing and Materials (ASTM). Standard Test Method for Limiting Oxygen (Oxidant)
Concentration of Combustible Dust Clouds. E2931.
American Society for Testing and Materials (ASTM). Standard Test Method for Minimum Explosible
Concentration of Combustible Dusts. Standard E1515, latest edition.
American Society for Testing and Materials (ASTM). Standard Test Method for Minimum Ignition Energy of
a Dust Cloud in Air. ASTM E2019, latest edition.
American Society for Testing and Materials (ASTM). Standard Test Method for Pressure and Rate of Pressure
Rise of Combustible Dusts. Standard E1226, latest edition.
Green, D. W., and R. H. Perry. Perry’s Chemical Engineers’ Handbook, Eighth Edition (Chemical Engineers
Handbook). New York: McGraw-Hill, 2007.
National Fire Protection Association (NFPA). Standard on Explosion Protection by Deflagration Venting. NFPA
68, latest edition.
National Fire Protection Association (NFPA). Standard on Explosion Prevention Systems. NFPA 69, latest
edition.
National Fire Protection Association (NFPA). Standard on the Fundamentals of Combustible Dust. NFPA
652, latest edition.
National Fire Protection Association (NFPA). Standard for the Prevention of Fire and Dust Explosions from
the Manufacturing, Processing, and Handling of Combustible Particulate Solids. NFPA 654, latest edition.
National Fire Protection Association (NFPA). Standard for Combustible Metals. NFPA 484, latest edition.
National Fire Protection Association (NFPA). Standard for the Prevention of Fires and Dust Explosions in
Agricultural and Food Processing Facilities. NFPA 61, latest edition.
Siwek, R. “A Review of Explosion Isolating Techniques.” Europex International Seminar, March 1996.
Verein Deutscher Ingenieure (VDI). VDI Guideline 2263 Part 8.1, “Dust Fires and Dust Explosions; Hazards,
Assessment, Protective Measures; Fire and Explosion Protection on Elevators.” 2011.
Verein Deutscher Ingenieure (VDI). VDI Guideline 3673, Part 1, “Pressure Venting of Dust Explosions.” Latest
edition.
Bag collectors: Air material separators (dust collectors) that separate dust from a gas stream by passing
the stream through a felted or woven-fabric filter medium.
Bakery: A place where baked goods are made (baked) and/or sold. Baked goods can include, but are not
limited to, breads, cakes, cookies, biscuits (sweet or savory), doughnuts, bagels, pastries and pies. Typically,
these goods are produced using flour. However, such products can also be gluten-free.
Bara: bar, absolute (unit of pressure).
Barg: bar, gauge (unit of pressure)
Bins: Short squat metal storage vessels. See also “Silos”.
Bonding: Electrical connection between two electrically-conductive objects that minimizes any difference
in electrical potential between them.
Canister collectors: Air material separators (dust collectors) that use a filter media contained in a cartridge
(such as a steel cage). The media is pleated to increase the surface area for dust capture.
Damage-limiting construction (DLC): Construction designed to minimize the damage from a deflagration
(explosion) in equipment or building. This can be pressure resistive, pressure relieving, or some combination
of the two. Most commonly this would be vent panels on enclosures (buildings or equipment) releasing at a
pressure below the strength of the enclosure.
Design strength: Pressure to which a vessel can be exposed without any risk of damage (because a safety
factor has been applied to the yield strength).
Discharge, brush: An electrostatic discharge between an insulating (non-conductive) surface that has
accumulated a charge and a conductive surface.
Distributor, turnhead: See definition for “Turnhead distributor”.
Double dump valve: An arrangement of two gate or butterfly valves in series. Only one is open at a time.
This valve is often used where material discharged from one vessel is gravity fed to another vessel (i.e.,
not pneumatically conveyed) such as a dust collector discharging into a hopper below it or a material blender
or grinder discharging into a pneumatic conveying system.
Dust: Small solid particles capable of being suspended in air by pouring, blowing, grinding, etc. For the
purposes of this data sheet, it refers only to combustible dusts.
Dust, combustible: Any organic material (agricultural, plastic, chemical, coal, etc), unoxidized metal
particles, or other oxidizable materials (e.g., zinc stearate) should be considered combustible.Tests involving
the application of a spark, match flame, Bunsen or Meker burner flame to small layers or piles of material
may help in identifying such materials, but can result in false negatives.
Dust, explosible: Established by ASTM E1226, Standard Test Method for the Explosibility of Dust Clouds,
or international equivalent (e.g., EN 14034-1, Determination of Explosion Characteristics of Dust Clouds -
Part 1: Determination EN of the Maximum Explosion Pressure Pmax of Dust Clouds, and EN 14034-2,
Determination of Explosion Characteristics of Dust Clouds - Part 2: Determination of the Maximum Rate of
Explosion Pressure Rise [dP/dt]max) of Dust Clouds). A dust that does not ignite and burn in layer or pile
testing could be determined to be explosible in an E1226-type test.
In the past, particles larger than 500 microns were specified as unlikely to present a dust explosion hazard.
Mixtures consisting of a range of sizes could present a dust explosion hazard even where a large portion
of the dust exceeds the 500 micron limit. Where there is a doubt, testing is the most appropriate way to
determine the explosibility of such a mixture.
Dust, fines: See definition for “Fines”.
Dust, fugitive: See definition for “Fugitive dust”.
Dust, hard-to-ignite: A dust that has been confirmed by FM test protocol to require a strong ignition source
to cause a combustible dust cloud to ignite.
Dust, inert: A dust that will not ignite or combust in the presence of oxygen when exposed to an ignition
source.
Dust, reactive: A dust that will ignite and/or combust in the presence of oxygen when exposed to an ignition
source.
Electrostatic precipitators: Equipment that collects dusts and hydrocarbon mists from gas streams by using
an electrostatic charge. They may be used to condition air to meet air pollution codes or recover a product
or by-product.
Enclosureless Dust Collector: A device designed and used to remove dust from the transport air where
the filter media is not enclosed or in a container.
Explosion isolation: System or single device that prevents the propagation of explosion effects from one
volume to an adjacent volume.
Explosion mitigation: Methods used to reduce damage from the explosion after the explosion has started.
Explosion prevention: Methods used to prevent an explosion by controlling either the air, fuel, ignition
source, or a combination of these.
Explosion-resistant design: Any vessel with a design pressure of 6 barg (87 psig) or more that would not
be deformed by a dust explosion that occurs at an initial (pre-explosion) pressure of less than 0.1 barg (1.5
psig).
Fines: Particles less than 75 microns in size.
FM Approved: Products and services that have satisfied the criteria for FM Approval. Refer to the Approval
Guide, an online resource of FM Approvals, for a complete listing of products and services that are FM
Approved.
Fugitive dust: Dust that has escaped from process equipment, ductwork or dust collection systems.
Gallery, conveyor: A structure (usually composed of steel trusses) that surround and house a conveyor
belt.
Grain elevator: A facility used to store grain. An alternate use for a grain elevator, specific to the grain industry,
is a tower containing a vertical bucket elevator or other pneumatic conveyor which transfers grain from a
lower level to a storage silo.
Grounding: Electrical connection between a conductive object and the ground that minimizes the difference
in the electrical potential between the object and ground.
Hard-to-ignite (HTI) dust: This is a sub-category of combustible dusts that have been tested using the
appropriate FM testing protocol. Hard-to-ignite dusts require a larger ignition source compared to other
combustible dusts. Hard-to-ignite dusts are still combustible dusts that can explode, with all the potential
consequences. This definition of hard-to-ignite is not related to definitions found in other codes and standards.
Ignitable Liquid: Any liquid or liquid mixture that is capable of fueling a fire, including flammable liquids,
combustible liquids, inflammable liquids, or any other reference to a liquid that will burn. An ignitable liquid
must have a fire point.
Inert: See definition for Dust, inert.
Kst: The dust explosibility constant, defined as the maximum rate of pressure rise of a dust explosion in a
1 cubic meter vessel. The units are bar meter per second (bar m/s). The test method used to obtain this
constant is standardized worldwide. This value (Kst) is used in all modern dust explosion vent sizing to
characterize the reactivity (i.e., explosibility) of a particular dust. Only metric units are used for this constant.
MEC: Minimum explosible concentration, the lowest concentration of dust that can support a self-propagating
explosion. (The terms LEL [lower explosible limit] or LFL [lower flammable limit] mean the same, but are
not often used in the context of dust explosions.)
Media type collector: A device (enclosure) that separates dry, solid material from air by passing the air
through a dry filtering medium. Examples are enclosures with bag-type filters, cartridge-type filters (normally
a pleated filter arranged in a cylindrical shape, similar to automobile air filters), rotary drum filters, and panel
filters. (See Data Sheet 1-45, Air Conditioning and Ventilating Systems, and Data Sheet 7-73, Dust
Collectors and Collection Systems, for information on filter types.)
MIE (minimum ignition energy): The minimum amount of thermal energy released at a point in a
combustible mixture to cause indefinite flame propagation under specified test conditions. The lowest value
of MIE, known as LMIE, is found at a certain optimum mixture. It is this value that is usually reported as
the MIE.
Overpressure: This is the pressure above normal atmospheric pressure that is caused by a shock wave
from an explosion.
Packing material: Filler material inside a wet collector used to increase the surface area of contact between
the gaseous stream carrying the dust and the liquid stream within the collector unit. Such material can be
metal, ceramic or even plastic.
Phlegmatization: The process of mixing inert dusts with combustible dusts to reduce or eliminate the
explosion hazard.
Pblast, : The localized pressure as a result of the fireball and pressure from a vented explosion.
max
Pmax: The maximum pressure developed in the 20-liter sphere when testing dust for explosibility
characteristics by ASTM E1226 method. It is factor used to help size explosion vents.
Pred: Highest explosion pressure in a vessel protected with explosion vents; usual units are barg or psig.
Pstat: Explosion vent relief pressure; usual units are barg or psig.
Psia: Pounds per square inch, absolute (unit of pressure).
Psig: Pounds per square inch, gauge (unit of pressure).
Reactive: See definition for “Dust, reactive”.
Scrubber: A scrubber is a device used to remove particulates and/or gases from an industrial exhaust stream.
Shock-resistant design: Any vessel having 3 barg (43 psig) design pressure or more when designed in
accordance with ASME Boiler and Pressure Vessel Code, Section VIII, or yield strength of 6 barg (87 psig)
or more according to other codes. With this design, the vessel may deform but not rupture in the event of
a dust explosion that occurs at an initial (pre-explosion) pressure of less than 0.1 barg (1.5 psig).
Silos: Large, tall structures of concrete used for storage of grains. See also “Bins”.
Strong ignition source: A strong ignition can provide more than approximately 100 Joules of energy.
A. Examples of a strong ignition source include open flame, welding arc, gas or dust explosion, and electric
arc/short.
B. Conversely, examples that would not be considered a strong ignition source include frictional sparks,
mechanical impact sparks, static sparks, cigarettes, hot surfaces, overheated electrical components.
Strong vessel: A vessel that can withstand explosion pressures in excess of 0.2 barg (3 psig) without being
damaged or destroyed. This includes most process vessels constructed or used in Europe.
Textile tenter frame: Found in the textile industries, this is a machine that allows the uniform distribution
of heat to a fabric, while preventing the fabric from shrinking as a result of the applied heat.
Tobacco manufacturing: Facilities where tobacco products are made, mixed, manufactured, fabricated,
assembled, processed, labelled, repacked, relabeled or imported. Such products include cigarettes, cigars,
snuff, chewing tobacco and pipe tobacco. Electronic cigarettes, “vapes” and other electronic nicotine delivery
devices are classified under tobacco manufacturing.
Tube sheet: The mounting plate for cartridge-type filters or bag-type filter tubes and cages.
Turnhead distributor: Also known as “Swivel switches” these are devices used to distribute products from
a single inlet to multiple outlets (typically storage silos or bins). This distribution can either be done via gravity
or pneumatically. They are most commonly found in grain handling and grain storage occupancies.
Ultimate strength: Pressure at which an enclosure will be torn open (i.e., ruptured).
Weak vessel or enclosure: A structure that cannot withstand explosion pressures in excess of 0.2 barg
(3 psig) without being damaged or destroyed. This includes most rooms, buildings, and many North American
process vessels.
Wet scrubbers: Wet scrubbers use a liquid medium as the principal method of separating particulates from
an air stream.
Yield strength: Pressure at which an enclosure will be deformed without rupturing.
October 2014. Interim revision. The defnition of an explosible dust was modified to align with industry practice
by removing the specific particle size limit.
January 2014. Minor editorial changes were made.
April 2013. Minor editorial changes were made.
January 2012. Terminology related to ignitable liquids has been revised to provide increased clarity and
consistency with regard to FM’s loss prevention recommendations for ignitable liquid hazards.
March 2009. Minor editorial changes were made for this revision.
January 2009. Correction to the equation in Section 2.4.2.2.1 was made.
May 2008. Reformatted the document for clarity and ease of use, especially the recommendations.
Added more construction and location guidance on preferred locations for dust hazard occupancies.
Emphasized explosion-hazard elimination and mitigation features.
Added chokes as an isolation method.
Refined the criteria on fans and blowers located in fugitive dust – air streams where they can become an
ignition source in an atmosphere that may exceed the MEC.
Simplified the criteria for protection of vessels of unknown strength.
Resolved inconsistencies with other data sheets, especially Data Sheet 7-73, Dust Collectors.
Simplified the Support for Recommendations section.
May 2006. Minor editorial changes were done for this revision.
New section 3.2.3.9.1, Typical Vent Panel Mass (inertia) was added.
May 2005. Added recommendations to implement a management of change program.
January 2005. Minor editorial changes
May 2004. Minor editorial changes
May 2003. Minor editorial changes
January 2001. The document was reorganized to provide a consistent format.
August 1995. Major revisions implementing Kst based vent sizing technology and abandoning the prior
method of vent area to protected volume method.
This data sheet includes many new recommendations which were not in the 1976 edition but many locations
will require less protection than the previous version required. The following exceptions have been made
to the general explosion protection requirements:
• Explosion venting is not needed for cyclones handling dusts with a Kst less than 80 (weakly explosible)
and having an open gas outlet on top whose diameter equals or exceeds 45% of the cyclone diameter.
• Systems operating at a pressure below 0.1 bara (1.5 psia) require no protection.
• Spray dryers require a reduced amount of explosion venting compared to other equipment with the same
volume. Note: the explosion venting area for spray dryers and for other equipment is now calculated using
the FM Research DustCalc software.
A. If the walls cannot provide the needed explosion relief area, conduct an engineering study to confirm
if the roof can be used to provide the portion of the explosion venting area needed.
B. Where explosion venting/pressure relief should be provided on the roof:
1. Position the explosion vents at a minimum 60° angle, either on a roof pitched at that angle or as a
projection above the roof line (see Figure C.1.3-A).
2. For vents projected above the roof line, the effective vent relief area to be used in vent sizing
calculations is the smallest cross-sectional area through which the combustion gases would flow.
C. In areas subject to snow and ice, prevent the buildup of snow and ice on the explosion vent as follows:
1. Provide heat tracing along the perimeter and across the surface area of the explosion vent.
2. The heat tracing can be left on permanently, or a system can be used that automatically turns on
heat tracing whenever the outside temperature drops to 32°F (0°C) or lower.
3. The wiring for the heat trace cabling incorporates enough slack to allow the explosion vent to deploy
as intended.
4. An acceptable alternative to heat tracing is explosion venting panels without insulation. These panels
allow building heat to melt away snow or ice. Expect condensation under the explosion vent, and
take measures to ensure condensation does not cause problems.
Explosion Vent
Roof
Fig. C.1.3-A. Schematic of rooftop explosion vents that project above the roof line
C.1.4 Where explosion venting devices swing out of the way rather than rupture, use gravity or mechanical
devices to ensure they cannot reclose.
C.1.5 To prevent uncontrolled release of explosion vent panels where they could become projectile hazards,
take the following steps:
A. Provide tethering cables to limit the vent movement.
B. Attach tethering cables to no more than two corners, making sure the tethered corners are adjacent.
C. To prevent the tethered panels from swinging back into the vent opening after the explosion, make
connections at the side or bottom of the panel rather than the top. If tethers are used, set the minimum
tether length per the guidance in Section 3.1.9.
D. Where the tether length is less than that specified above, consider the explosion vent a hinged panel
when calculating the vent area and vented explosion pressure (Pred). This will account for the hindrance
to the venting process created by the short tethers.
E. Tethers located at all four corners can be considered tolerable if the cable length exceeds the minimum
length specified in item D. Any less, and the vent area is restricted to the annular space determined by
the cable length and the dimensions of the panel.
C.1.6 Construct explosion vents of material as light in weight (mass per unit area) as possible to minimize
the vent area required.
C.1.7 Avoid any windows and/or other penetrations (doors, cable runs etc.) in pressure-resistant walls. Where
necessary, these penetrations should be designed to withstand the same pressure as the wall and should
be sealed dust-tight using non-combustible materials.
C.1.8 Design ductwork that penetrates pressure resistant walls to prevent buckling at the juncture with the
wall.
C.2.1 General
C.2.1.1 Locate equipment with identified explosion hazards outside of buildings.
C.2.1.2 Where equipment with identified explosion hazards is inside, locate equipment along an outside wall
to permit venting to an outside location.
C.2.1.3 Do not use damage-limiting construction to control an explosion involving combustible metal dusts.
C.2.1.4 Install vent ducts that redirect the flame, combustion products and pressure produced by a
deflagration in a piece of equipment to a safe area in accordance with the following:
A. Route the vent to a safe outdoor area.
B. Do not locate objects in the path of explosion vents.
C. Use straight sections of duct only.
D. Limit the length-to-diameter ratio (L/D) of the duct to 1. For non-circular ducts, the equivalent diameter
(Deff) can be calculated as follows:
√
4Ad
Deff =
π
E. Ensure the vent duct is at least as strong as the Pred design of the vessel.
F. Permit no closures on the discharge end of the duct that obstruct the free venting of the discharged
combustion products or pressure.
G. When the above conditions cannot be met, quantify the effect on the vent area using FM DustCalc
software.
C.2.1.5 Where explosion vents can reclose, and no other openings could draw in air, provide vacuum
breakers. Reclosure can potentially create vacuum conditions that can cause the vessel to implode.
C.2.1.5.1 When using tethers to prevent an explosion vent from becoming a projectile, set the minimum tether
length to prevent reclosing of the vent using the following equation:
l ≥ (a x b)
2 x (a+b)
Where:
l = Length of tethering cables
a, b = Side dimensions of explosion vent
C.2.1.6 Where venting devices are heavier than light-weight membranes, calculate the effect on the vent
area using FM DustCalc software.
C.2.1.7 Explosion vents that are rupture membranes (e.g., prefabricated rupture disks, aluminum foil, etc.)
have virtually no inertia and require no adjustment to the required explosion vent area.
C.2.1.8 Where a wire mesh screen or other obstruction should be provided between an explosion vent and
the free atmosphere, adjust the effective area of the explosion vent for the reduction in venting efficiency
as follows:
A. If the screen or obstruction is less than 15% of the explosion vent area, no adjustment is required.
B. A screen or obstruction that is between 15% and 40% of the explosion vent area will reduce the actual
vent area. Calculate the effective explosion venting area using:
Hydraulic Diameter = 4A
p
Where:
A = Cross-sectional area of vent
p = Perimeter of the cross-section
C.2.1.12 Do not provide explosion venting if the dust or its combustion products
A. Are poisonous
B. Are radioactive
C. Are corrosive to nearby equipment or structures
D. Should not be released from an otherwise closed system for any other reason
Alternatives to venting should be used instead.
C.2.1.13 Where a vessel requiring explosion venting contains significant obstructions to the free flow of gases,
the installation of one large vent may be impeded by these obstructions. Use of multiple smaller explosion
vents distributed at different places around the vessel can mitigate these obstruction effects. Where this is
done, the total venting area provided by the multiple smaller vents should meet or exceed the vent area
as specified by DustCalc. (See Section C-3.6 for support information.)
B. If the gases heading toward the explosion vent pass over any significant obstructions, turbulence will
increase substantially within the vessel. Because the rate of pressure rise of an explosion increases with
turbulence, the obstacles can worsen the explosion.
C. Vents distributed throughout an entire enclosure will help ensure the gases vented during the explosion
take the shortest path out of the enclosure.
Fig. D.1-1. FM Approved flameless venting device (Photo courtesy of Rembe GmbH)
efficiency factor is reported as “Efficiency (Ef).” Their methodology for calculating the efficiency is different
from that used in FM Approvals’ testing.
E. Maximum protected volume (MPV): The maximum protected volume (MPV) is limited by the dust loading
on the device, mst,max, and the dust loading per nominal vent area (lb/in.2 [g/cm2]). This loading is directly
related to the nominal dust concentration used in Approval testing (lb/ft3 [g/m3]).
For actual applications, the design loading is based on the Cst of the dust used in the vent sizing design.
The Cst is the concentration, determined by testing where Kst and Pmax occur. In practice, the MPV may need
to be adjusted if the Cst is different from the dust loading used for testing. The adjustment factor is:
Vmax2 = Vmax1 x (Cst1/Cst2 )
Where:
Vmax1 = MPV listed
Vmax2 = Volume corrected for Cst
Cst1 = Concentration used in the Approvals testing.
Cst2 = Concentration of the design dust determined by testing
In choosing the proper flameless explosion venting device (FEVD), calculate the required vent area for the
application, and then use the “Effective Vent Area” in the Approval Guide listing to select the device that
would provide at least the required vent area. Doing so may require one or more devices. Some manufacturers
limit the number of flameless venting devices that may be installed on the equipment to be protected. Where
this limitation cannot be avoided, other protection measures may need to be used.
The selected flameless venting device(s) should not exceed the MPV. Where multiple devices are used to
provide the required venting, the MPV of each device should be added to determine the total MPV. For
example, if two devices each having an MPV of 110 ft3 (3.1 m3) are used, the vessel volume to be protected
would be limited to 220 ft3 (6.2 m3).
As the explosion is vented through the flameless venting device, any burned or unburned dust is retained,
combustion gases are cooled and no flame exits the quench pipe. In addition, the nearfield blast (pressure)
effects outside the vent are greatly reduced. Thus, an explosion can be safely vented indoors through the
device without the fear of igniting nearby combustibles or creating damaging pressure in the room. However,
the exit gases are hot (approximately 212°F [100°]).
The listing of all FM Approved devices includes their vent efficiency, which is the factor by which the effective
vent area of the device is reduced. This is different than the pressure effect calculation above.
As flameless explosion protection devices are a form of explosion venting, they can be used anywhere a
traditional explosion vent can be used, subject to the specific limitations of the flameless explosion venting
device.
E.1 General
Explosion propagation between connected equipment can allow an explosion to progress through an
interconnected system. Additionally, it can create “pressure piling” (see Section E.3 for additional information).
The result is a large explosion pressure that can rupture connected equipment, increasing property damage
and/or business interruption.
Two types of isolation devices are commonly used.
1. Mechanical isolation: This includes rotary air locks, rapid action valves, flame front/explosion diverters,
high speed abort gates, double-dump valves and back-blast dampers.
2. Chemical isolation/chemical blocking systems. These systems create a chemical curtain that interferes
with the explosion flame front.
For equipment designed to contain an explosion, any mechanical isolation devices on both the upstream
and downstream sides of the equipment should be the same strength as the equipment they are protecting.
This will prevent the device from failing and becoming a potential weak point.
On equipment fitted with explosion venting, the mechanical isolation equipment should be designed to resist
the reduced design pressure (Pred).
When using chemical isolation systems (chemical blocking systems), consider the following factors:
A. The duct volume the system is designed to protect (may include the largest duct volume from any
documented tests)
B. Actual volume to be protected by the blocking system
C. Duct strength and Pred
D. Worst case explosion Pred
E. SRD (standard-rate discharge) device layout
F. Fuel type (the material within the duct that requires protection)
G. Detection type and detection time of the blocking (isolation) system
H. Delivery rate of the suppressant
I. Delivery time of the suppressant into the volume to be protected
J. Type and quantity of suppressant used
K. System drawings of the proposed/installed system
L. The recognized code or standard (or national equivalent) to which the system is designed
M. If the vessels are not certified to a recognized code, provide documentation, signed by a PE (or national
equivalent), indicating the design methods, design criteria and any safety factors used.
Fig. E.2.2-1. Explosion diverter Fig. E.2.2-2. Indoor installation of explosion diverter
E.2.6 Chokes
Chokes allow the accumulation of material through which an explosion cannot propagate.
When using chokes as a method to control explosion propagation, the following guidance applies:
A. Rotary air locks are acceptable to act as chokes if they meet all the criteria in Section 2.5.4.
B. Rotary air locks that do not meet all the criteria in Section 2.5.4 can serve as chokes if the height of
powder above the air lock is equivalent to the diameter of the discharge opening and this powder height
is always present.
E.3.1 General
When an explosion occurs within a vessel protected by pressure containment, the pressure and the generated
flame propagate along any open connected ductwork into adjacent enclosures. If the adjacent enclosure
(e.g., vessel) also has a pressure-resisting design, “pressure piling” can occur. Pressure piling increases the
pressure within the second vessel before the explosion flame front arrives, as the pressure disturbance
travels faster than the flame front. Thus, when a dust explosion is ignited within the second vessel, the initial
pressure will be well above the normal (ambient) pressure. This increase can render the pressure-resistance
design of the second enclosure ineffective.
For a given fuel-to-air ratio, the final, unvented pressure of an explosion is directly proportional to the initial
pressure. For example, if the first explosion pre-pressurizes the second vessel to 44 psi (3 bar) absolute,
then the final pressure of the explosion in the second vessel would increase by a factor of three. For a dust
with a Pmax value of 131 psi (9 bara), the final unvented pressure in this example would be 392 psi (27 bara),
well above the strength of even the sturdiest vessel designed for dust explosion pressure containment. Thus,
where explosion containment is used as a protection method, providing explosion isolation is important to
prevent pre-pressurizing a vessel from another explosion.
When an explosion occurs within one vessel protected by explosion containment that is connected to a second
vessel protected with explosion venting, the turbulence created by the pressure front and the strong ignition
source from the flame front results in a more rapid explosion in the second vessel. This connection is often
unaccounted for in the vent design, causing the failure of the second vessel.
These effects occur to a lesser extent if the connected vessels are both protected with explosion venting.
Thus, where explosion venting is used as a protection method, providing explosion isolation is important to
separate the vented vessel from any connected vessels protected by explosion containment.
When using active devices for explosion isolation, adequate separation between the point of detection (i.e.,
the installed sensor) and the isolation device is important to allow the active device time to react.
If installed too close together, the protection offered by the isolation device can be ineffective; as it will not
open in time to divert the flame front. Consult with the manufacturer of the isolation device to provide the
appropriate separation for that device and its associated sensor.