TeSys U
TeSys U
TeSys U
All-in-one motor starters
Flexible
Motor
starters
Circuit breakers
Smart
Protection
Contactors
Thermal overload relays
Fuse switch-
disconnectors
Reliable Motor
controllers
Presentation TeSys U concept
102872_SE.eps
Motor circuit
breaker:
TeSys GV2 L Magnetic protection
> short-circuit protection
102860_SE.eps
Contactor:
TeSys D Control
> Start /Stop
Status monitoring
> signaling
> alarm monitoring
103287-SE.eps
Protection
relay:
TeSys LRD Thermal protection
> overload
DB414490.eps
A4/2
Presentation TeSys U concept
TeSys U
TeSys U starter-controller
> All basic or advanced protection
and control functions in one block
and more...
> Overload indication and alarm
> Status report, remote control via
communication bus
TeSys U
DB414490.eps
can be used in
80 %
of motor protection
and control
applications.
A4/3
Presentation Advantages
1 All in one
p Optimising space in enclosures.
otal coordination (No contact welding on short circuit).
pT
PB105087.eps
2 Simplicity of choice
p Controlled power.
p Protection functions ensured.
p Signaling functions, communication with PLC ensured.
3 Universal mounting
p On DIN rail or grid.
DB414490.eps
5 Electrically simple
Basic scheme of a TeSys U starter-controller
p Protection and power control
1/L1
3/L2
5/L3
DB414491R.eps
V1 4/T2
W1 6/T3
M
3a
A4/4
Presentation Common characteristics
Short-circuit protection
bb Isc:
vv 50 kA at y 400 V
vv 10 kA at 500 V
vv 4 kA at 690 V.
PB105087.eps
bb Up to 690 V AC.
Overload protection
bb From 0.15 to 32 A, 6 setting ranges (tripping 14.2 x I setting).
bb Test button.
bb Adjustment lock.
bb Coil choice: 24 V, 48…72 V, 110...240 V DC/AC.
3 power contacts
bb For non-reversing (reversing with reverser block).
bb Imax, for 12 A power base (direct - reversing):
vv 12 A at up to 500 V / 50 Hz
vv 9 A > 500 V, up to 690 V.
bb Imax, for 32 A power base (direct - reversing):
vv 32 A at up to 500 V / 50 Hz
TeSys U
vv 21 A > 500 V, up to 690 V.
1 NO contact
1 NC contact
bb 5 A / max. 690 V AC or 250 V CC.
Communication modules
bb Modbus,
bb Ethernet,
bb CANopen,
Motor up to bb DeviceNet,
p 7.5 kW / 1-phase 230 V / 50-60 Hz. bb Advantys stb,
p 15 kW / 3-phase 400-440 V / 50-60 Hz. bb Profibus DP,
bb Beckhoff,
p 15 kW / 3-phase 500 V / 50-60 Hz. bb AS-interface.
p 18.5 kW / 3-phase 690 V / 50-60 Hz.
p Non-reversing or reversing.
Dimensions
bb Base: b Base + reverser block:
DB416319.eps
DB416320.eps
154
224
126 45
126 45
A4/5
DB414493.eps
Presentation The modularity principle
E
A
A Cavity for control unit D Cavity for additional contact block or shutter
A4/6
Presentation Control units and modules
On/off control,
1 direction of rotation
Components overview
DB414494R.eps
1
24 5
4
E
3
A 2
11
10
B
C
9
6
8
TeSys U
19
D 7
13
22 12 16
23 15
20
14
17
21
18
Communication auxiliary
modules
11- LUFC00
Power base Auxiliary module Telefast parallel liaison Control terminal blocks
1- LUB 6- LUFN module, with RJ45 connector 19- LU9BN11
Non reversing power base - Auxiliary contacts module 12- ASILUFC5/ASILUFC51 Terminal block for imbedded
1 rotation direction AS-Interface c. m. auxiliary contacts
Load monitoring auxiliary 13- LULC031/LULC033 20- LU9BN11C
modules Modbus c. m Coil terminal block with its
Control units
7- LUFW10 14- LULC07 Profibus DP c. m connecting cable
2- LUCM Overload alarm module
15- LULC08 CANopen c. m. 21- LU9BN11L
Multifunctional control unit
8- LUFDH11 Coil terminal block with its
3- LUCB/LUCC/LUCD Overload alarm module with 16- LULC09 DeviceNET c. m. connecting cable
Advanced control units manual reset 17- LULC15 Advantys STB c. m.
4- L
UCA 9- LUFDA01/LUFAD10 Additional contacts blocks
Standard control unit Overload alarm module with Shutters 22- LUA1
5- LUCL automatic reset/remote reset 18- L
U9C 1 Additional contacts
Magnetic protection 10- LUFV2 Shutter for module cavity
control unit Motor load indication module 24- LUA8
23- Shutter for contacts
additional block cavity side-mounting additional
contacts
A4/7
Presentation Control units and modules
On/off control,
2 directions of rotation, vertical mounting
1
6
2 3
A4/8
Presentation Control units and modules
On/off control,
2 directions of rotation, side-mounting
TeSys U
3
Reverser block
1- LU6M B0pp
Side-mounting reverser block
A4/9
References Components for
"standard control"
p Rotation control: 1 direction - 2 directions.
p Protection: overload + short circuits
+ main power fault.
p Monitoring: by dry contacts.
PB105100.eps
PB105101.eps
PB108212_20.eps
PB108208_20.eps
Auxiliary signaling Function Indicates the open/ closed status of the protection: by NO/NC contact
contacts block Protection standby/tripped: by SD contact
To be inserted below the auxiliary module cavity (B)
DB124030.eps
A4/10
The power bases are delivered with the following items
LUB12, LUB32
12 or 32 A power base with imbedded control terminal
block and 3 blanking shutters
LU2B12, LU2B32
12 A (LUB120) or 32 A (LUB320 (1) power base without
imbedded control terminal block
+ 1 assembling connector LU9MR1C
+ 1 reverser block - vertical mounting LU2MB0pp
+ 1 control terminal block LU9M1
(1) see description next page.
TeSys U
1 terminal S2 coil
2 terminals contact NF (24 ... 250 V DC/AC, 5 A max)
Note: both LUCA and LUCL units can be used in the advanced power bases
LUB120 and LUB320.
Modules and blocks are compatible with all standard and standard inverting power
DB414501.eps
bases
E Common electrical characteristics
bb Standard operating voltage: 24…250 V AC/DC.
bb Maximum current: 5 A.
A4/11
References Components for
p Rotation control: 1 direction - 2 directions.
p Protection: overload + short circuit
+ main power fault.
"advanced control"
p Signaling: by dry contacts.
p Digital display of electrical values.
p Overload alarms.
p Network/bus communication.
DB416347.eps
PB107387_19.eps
DB414503.eps
1
2
2 3
Advanced power base Reverser block - vertical mounting Reverser block - side mounting
Rating / Ue AC
12 A / 400 et 500 V LUB120 1 LU9MR1C 1 LU6MB0pp (1)
9 A / 690 V 2 LU2MB0pp (1)
2 LU9MR1
32 A / 400 V LUB320
3 LU9M1 3 LU9M1
23 A / 500 V
21 A / 690 V
DB414504.eps
of 3 phases motors 50/60 Hz
Protection type:
- overload
Lip_in - short-circuit
mounting on - Main power fault
Setting the power - alarm
400/440 V 500 V 600 V Multifunctional
range base - Rating
kW kW kW A A Class 10 Class 10 Class 20 Class 5...30
1P 3P 3P 3P 3P 1P 3P 1 - 3P
- 0.09 - - 0.15...0,6 12 and 32 LUCBX6pp LUCCX6pp LUCDX6pp LUCMX6BL
0.09 0.25 - - 0.35...1,4 12 and 32 LUCB1Xpp LUCC1Xpp LUCD1Xpp LUCM1XBL
0.55 1.5 2.2 3 1.25...5 12 and 32 LUCB05pp LUCC05pp LUCD05pp LUCM05BL
2.2 5.5 5.5 9 3...12 12 and 32 LUCB12pp LUCC12pp LUCD12pp LUCM12BL
4 7.5 9 15 4.5...18 32 LUCB18pp LUCC18pp LUCD18pp LUCM18BL
7.5 15 15 18.5 8...32 32 LUCB32pp LUCC32pp LUCD32pp LUCM32BL
Cial. ref. of the control unit: replace dots by the coil code.
Coil voltage (V) 24c 24a 48...72 c and 48a 110...220 c and 110...240a
Coil code BL B ES FU
> Selection of the modules and signaling blocks: see page A4/14
A4/12
LUB120, LUB320 - 12 or 32 A advanced power base equipped with:
One NO latching contact + one NC contact
Operation voltage 24 ... 250V AC/DC - I max 5 A
+ 2 blanking shutters
The cavity C is empty, ready for insertion of a terminal block:
for local control LU9BN11
for centralized control LU9BN11C, LU9BN11L
or insertion of an assembling connector LU9MR1C, for reverser block - vertical mounting
Inverser block: its maximum controlled power might be limited by the power base capacity
Power base interlocking control:
vertical mounting: by the assembling connector LU9MR1C
side mounting: by a LU9MR1 terminal block (to be linked to a LU9B N11 terminal block
TeSys U
in the advanced power base).
Reverse control:
Local control, to be wired on a LU9M1 terminal block
centralized control, by a LU9MRC or LU9MRL terminal block; its connector must be plugged in a
communication module, in the advanced power base.
A4/13
References Components for
p Rotation control: 1 direction - 2 directions.
p Protection: overload + short circuits
+ main power fault.
"advanced control"
p Signaling: by dry contacts.
p Digital display of electrical values.
p Overload alarms.
(continued)
p Network/bus communication.
4a- Selection of the auxiliary module and terminal block for Modicon Telefast system
Telefast system Terminal block / control cable
Module 1 direction of rotation 2 directions of rotation
DB414505.eps
DB414506.eps
DB414507.eps
DB414527.eps
DB414525.eps
DB414524.eps
Function Indicates the off/ready status of TeSys U: Indicates the off/ready status of the protection
by NO/NC contact
Protection on/tripped: by SD contact
To be inserted below the auxiliary module cavity (B)
Output OF and SD contacts: OF contact: NC type 2 OF contacts: NO type
NO type SD contact: NO type
Cial. reference LUA1C20 LUA1C11 LUA8E20
A4/14
bb The signaling modules with dry contacts are directly wired on indicators and electrical warning devices.
bb Contacts rating: 5 A / 24...250 V AC/DC.
bb The LUF V2 module is connected to a datalogger or any other indication device providing a 4-20 mA analog
input.
TeSys U
bb Outputs: OF / SD contacts from protection device, OF contact from the poles (to a 24 V PLC input)
bb RJ45 connector for Telefast PLC pre-wiring system:
vv Modicon TM3 (map I/O controllers for RJ45 M221, M241, M25)
vv Modicon STB modules (I/O for automation island)
vv Modicon Telefast (interfaces RJ45/HE10).
bb Must be connected to a LU9 G02 or LU9 G03 Telefast distribution box
bb Compatible exclusively with LUCppp control unit with coil code B
bb The terminal blocks + control cables provide the connection to the coil of the power base and the signal contacts.
bb Communication modules:
vv indicates the position of the control pad and the state of the poles,
vv collects the FWD, REV commands from an automation process.
bb The states and the control orders are coded according to the selected communication protocol.
bb Screw clamp terminals to the bus cable.
bb The terminal blocks + control cables provide the connection to the coil of the power base and the signal contacts.
bb Additional blocks:
vv used for wiring indicator lights or controllers.
bb Advantage:
vv the locations for these blocks are always available, regardless of the configuration of the power base.
bb Contact rating: 5 A / 24...250 V AC/DC.
Note: the indication the direction of rotation is available on the reverser block unit:
- On a LU9M R1C assembling connector
- On a LU9M R1 terminal block.
A4/15
References Typical wiring diagrams
21 22
95 NC 96 17 NO 18
A1
33 34 43 44
NO NO
95 NC 96 17 NO 18
A1
A2 13 NO 14 21 NC 22
ON indication
"Motor RUN" indicator wiring "Motor starter READY" indicator wiring
DB414428.eps
DB414429.eps
READY
a
43 44
3333 3434 4343 4444 LUA8 E20
LUF N20
NO NO
33 34 43 44 33 34 43 44
95 NC 96 17 NO 18 NO NO NO NO
RUN
95 NC 96 17 NO 18 95 NC 96 17 NO 18
a A1 a
A1 A1
A2 13 NO 14 21 NC 22 A2 13 NO 14 21 NC 22
a A2 13 NO 14 21 NC 22
ALARM indication
Protection device status indicator wiring
DB414427.eps
95
33 34 43 44
NO NO
95NC
95 96
NC 96 17 NO 18
LUA1 C20
A1
33 34 43 44
A2 13 NO 14 21 NC 22
Protection OK NO NO
a 95 NC 96 17 NO 18
ALARM A1
A2 13 NO 14 21 NC 22
A4/16
References Typical wiring diagrams
and contacts status
DB414431R.eps
82 81 84
1 2
33 34
A2A2 A1A1 A3A3 B1B1 B3B3
3333 3434 4343 4444
LUFN20
NO
NO NO
NO
OFF REV FW 33 34 43 44
95 NC 96 17 NO 18 33 34 43 44
a NO NO
NO NO
95 NC 96 17 NO 18
95 NC 96 17 NO 18
82 81 84
A1
A1
1 2
TeSys U
82 81 84
RUN FW
82 81 84
1 2 a
RUN REV 1 2
a
A2 A1 A3 B1 B3
A2 A1 A3 B1 B3
Ready to operate 0
Start 1
A4/17
References Parallel-type cabling systems
Principle
Point-to-point wiring
PB105089.eps
DB416375.eps
bb The control inputs and signaling outputs of the starter are grouped in a
single socket, usually RJ45.
They are individually connected to PLC outputs and inputs.
bb The wires run in parallel in a multicore cable equipped with a multipin
connectors, RJ45 in the case of Telefast type system.
bb 3 parallel wiring systems are available:
vv Modicon TM3, based on a RJ45 I/O module for M221, M241, M25 PLC
vv Modicon STB, based on I/O modules for automation island
vv Modicon Telefast: RJ45 / HE10 interfaces.
bb Simple way of proximity wiring. Quick cabling.
It is suitable for machine control panels when a large number of TeSys U
starter-controller are installed.
A4/18
References Parallel-type cabling systems
Modicon TM3
DB415968_Tesys U.eps
TeSys U
2
A4/19
References Parallel-type cabling systems
Modicon Advantys STB
A4/20
References Parallel-type cabling systems
Modicon Telefast
TeSys U
1
4 5 7
A4/21
References Parallel-type cabling systems
Components TeSys U
DF510918.eps
Designation Reference
1 Parallel connection module, RJ45 output 2 coil control inputs, 3 signal outputs LUFC00
2 Pre wired connector, one direction of rotation, for coil connection and one LU9BN11C
contact for emergency stop
Designation Reference
Splitter box LU9G02
Connection to TeSys U:
4 RJ45 connectors: for 1 to 4 TeSys U, 1 or 2 directions
4 RJ45 connectors: for 1 to 4 TeSys U, 1 direction
Connection to PLC:
1 x HE10 connector - 20 chanels, for pole status, alarms
1 x HE10 connector - 20 chanels, for control.
24 V DC auxiliary power supply required
Splitter box LU9G03
Connection to TeSys U:
8 RJ45 connectors: for 1 to 8 TeSys U, 1 or 2 directions
Connection to PLC:
LU9 G02 LU9 G03 1 x HE10 connector - 20 chanels, for pole status, alarms
1 x HE10 connector - 20 chanels, for control.
24 V DC auxiliary power supply required.
0.3 m LU9R03
1m LU9R10
3m LU9R30
5m TSXCDP503
Section: AWG 28 / 0.080 mm² (flat cable)
1m ABFH20H100
2m ABFH20H200
3m ABFH20H300
A4/22
References Bus-type cabling systems
Principle
Many motors are scattered on the site, the process control requires individual control
to ensure safety and proper operation.
TeSys U is a suitable communicating actuator. The integration of a bus communication
module in the starter-controller saves space in the control board and simplifies wiring,
compared to solutions based on conventional components (circuit breaker + contactor).
TeSys U
bb The bus wiring interconnects TeSys U starters
DB416376.eps
A4/23
References Bus-type cabling systems
View
4 XZ CG0142
Details page
A4/26
CANopen
Etoile
1 LUL C08
2 LU9B N11C
5
3 LU9M RC
1 1
1
2 2 3 4 TSX CAN Cppp
Bus
1 1
1
2 2 3
4 4 4
Details page
A4/27
A4/24
Network Architecture Component
references
Modbus
Etoile Bus
1 UL C031 or
L
LUL C033
2 LU9B N11C
5 3 LU9M RC
1 1 1 1
2 2 3 2 2 1
4 VW3 A8 306Rppp
5 LU9 GC3
6 VW3 A8 306TF
4
6 6
TeSys U
Details page
A4/28
Advantys STB
Starter-controllers
1 LUL C15
communicate
using ADVANTYS
STB protocol to fit
2 LU9B N11C
into a remote I/O
architecture. 6
3 LU9M RC
1
1
2 3
4 LU9 RDDppp
5 LU9 RCD
5 4
Details page 6 STB XBE1100
A4/29
Profibus-DP (Decentralized Peripherals)
is used for connecting 5 1 LUL C07
actuators and sensors
to a central controller
for applications in 6
2 LU9B N11C
industrial production.
The standard bus
3 LU9M RC
1
provides a number of 1
2 3
diagnostic means 4 U9 RPB010
L
LU9 RPB100
c 24 V LU9 RPB400
4
5 LU9 AD7
2 LU9B N11C
3 LU9M RC
1
1
2 3
c 24 V
Details page
A4/31
A4/25
References Bus-type cabling systems
TeSys U components
for AS-Interface bus
The LULC09 communication module, combined with the power base and control unit
1 2
is used to control TeSys U starters-controllers via DeviceNet bus.
The LULC09 communication module is slave type.
PB105093.eps
Module Specifications
I/O terminal block
bb Powered by external 24 V DC (power supply not included):
vv 2 x configurable inputs for binary sensors
vv 1 x 24 V DC output - 0.5 A local auxiliary command.
Connectors
3 4 5 bb For TeSys U 24 V DC coil (common, direction 1, direction 2).
bb For AS-Interface bus.
1 Green LED: AS-Interface voltage present
Signaling
2 Red LED: AS-Interface or module fault
3 Outputs for starter commands
bb Module Status - Error - 24 V, by LED.
4 Black connector for connection to c 24 V
auxiliary power supply
5 Yellow connector for connection to the AS-Interface system
Tesys components
DB414635.eps
Description References
DB414636.eps
A4/26
References Bus-type cabling systems
TeSys U components
for CANopen bus
The LUL C08 communication module, combined with the power base and control
1 2 3
unit is used to control TeSys U starters-controllers via CANopen bus.
The LULC09 communication module is slave type.
PB105094.eps
Module Specifications
I/O terminal block
bb Powered by external 24 V DC (power supply not included):
vv 2 x configurable inputs for binary sensors
vv 1 x 24 V DC output - 0.5 A local auxiliary command.
4
Connectors
bb For TeSys U 24 V DC coil (common, direction 1, direction 2).
bb For CANopen bus.
5
Signaling
9 8 7 6 bb Module Status - Error - 24 V, by LED.
TeSys U
6 Discrete input
7 Discrete input
8 Discrete output
9 Outputs for starter commands
Tesys components
DB414637.eps
A4/27
References Bus-type cabling systems
TeSys U components
for Modbus bus
LUL C031 LUL C033 The LULC031 and LULC032 communication modules, combined with the power
base and control unit is used to control TeSys U starters-controllers via Modbus.
1 1
Module Specifications
PB105096.eps
PB105095.eps
Tesys components
Description Item Bin. input References
DB414639.eps
Modbus hub
1 Description Length References
(m)
Modbus communication distributor - LU9GC3
2 Cables fitted with 2 x RJ45 connectors 0.3 VW3A8306R03
1 VW3A8306R10
3 VW3A8306R30
Tees derivations 0.3 VW3A8306TF03
1 VW3A8306TF10
DB414640.eps
Description References
RS 485 line terminator VW3A8306R
A4/28
References Bus-type cabling systems
TeSys U components
for Advantys STB bus
fallback positions.
Module Specifications
I/O terminal block
9 bb Powered by external 24 V DC (power supply not included):
vv 2 x configurable inputs for binary sensors (on LULC033 only)
4 vv 1 x 24 V DC output - 0.5 A local auxiliary command.
Connectors
bb For TeSys U 24 V DC coil (common, direction 1, direction 2).
bb For Advantys STB bus.
8 6 5
7 Signaling
bb Com - Error - 24 V, by LED.
1 Two-colour LED indicating module status
2 Fault signalling LED
3 LED indicating that c 24 V supply is ON
4 Bus connectors
TeSys U
5 c 24 V supply connection
6 Discrete input
7 Discrete input
8 Discrete output
9 Outputs for starter commands
Tesys components
Description Item References
Advantys STB communication module 1 LULC15
Pre-wired connector: coil - LUB powerbase 2 LU9BN11L
Pre-wired connector: coil - LUB2B powerbase 3 LU9MRL
DB414641.eps
Cables
Description Length References
(m)
Cables fitted with connectors, one straight and one 0.3 LU9RCD03
elbowed 1 LU9RCD10
3 LU9RCD30
5 LU9RCD50
Cables fitted with two straight connectors 0.3 LU9RDD03
1 1 LU9RDD10
2 3 LU9RDD30
A4/29
References Bus-type cabling systems
TeSys U components
for Profidus DP bus
When used in conjunction with the power base and control unit, communication
1 2 3
module LULC07 allows TeSys U starter-controllers to be controlled via Profibus DP
(Deported Periphery) bus.
Communication module LULC07 is of the slave type.
PB105098.eps
Module Specifications
I/O terminal block
bb Powered by external 24 V DC (power supply not included):
9 vv 2 x configurable inputs for binary sensors
4 vv 1 x 24 V DC output - 0.5 A local auxiliary command.
Connectors
bb For TeSys U 24 V DC coil (common, direction 1, direction 2).
bb For Profibus DP bus.
8 6 5
7 Signaling
bb Com - Error - 24 V, by LED.
1 Two-colour LED indicating module status
2 Fault signalling LED
3 LED indicating c 24 V supply ON for outputs
OA1, OA3 and LO1
4 SUB-D connector for bus link
5 c 24 V supply connection
6 Discrete input
7 Discrete input
8 Discrete output
9 Outputs for starter-controller commands
(non-reversing and reversing)
Tesys components
Description Item References
DB414643.eps
A4/30
References Bus-type cabling systems
TeSys U components
for DeviceNet bus
When used in conjunction with the power base and control unit, communication
module LULC09 allows TeSys U starter-controllers to be controlled via DeviceNet bus.
1 2 3 Communication module LUL C09 is of the slave type.
Module Specifications
PB105099.eps
TeSys U
4 DeviceNet connector for bus link
5 c 24 V supply connection
6 Discrete input
7 Discrete input
8 Discrete output
9 Outputs for starter-controller commands
(non-reversing and reversing)
Tesys components
Description Item References
DeviceNet communication module 1 LULC09
DB414645.eps
A4/31
References Communication gateways LUFP
Presentation
108816_SE_R.eps
Communication gateways LUF P allow connection between the Modbus serial link
and Fipio, Profibus DP or DeviceNet field buses.
Example of architecture
Configuration
of gateway TeSys U starter-controllers
by PC
DF511517.eps
LUF P
Fipio (1)
Profibus DP Modbus
DeviceNet
1
Communication gateway LUFP
Description Reference
Fipio / Modbus gateway LUFP1
Profidus DP / Modbus gateway LUFP7
DeviceNet / Modbus gateway LUFP9
Description
Front panel of the product
1 LED indicating :
2 - communication status of the Modbus serial links,
- gateway status,
- communication status of the Fipio, Profibus DP or DeviceNet bus.
2 Connectors for connection to Fipio, Profibus DP or DeviceNet buses.
561512.eps
Underside of product
3 RJ45 connector for connection of the Modbus serial link
4 RJ45 connector for link to a PC
5 c 24 V power supply
3
4 Software set-up
For the Fipio bus, software set-up of the gateway is performed using either PL7
Micro/Junior/Pro software or ABC Configurator software.
5 For the Profibus DP and DeviceNet buses, software set-up is performed using
ABC Configurator.
This software is included in the TeSys U user’s manual.
(1) Connection kit for PowerSuite software workshop.
A4/32
References Current limiter blocks
and accessories
PB113846.eps
To be connected in series and upstream of a TeSys U starter-controller . It increases its
ability to withstand the short circuit current from 50 kA to 100 or 130 kA under 400 V.
Principle: under the action of a short-circuit, the opening of two contacts of each
phase of the limiter creates a resistive arc. The current then decreases to a value
tolerable by a TeSys U power base.
LUA LF1
Limiter blocks and accessories
Description Breaking capacity Iq (kA) Mounting Unit reference
y 440 V 690 V
Limiter-disconnector 130 70 Direct on power base LUALB1 (1)
DB414653.eps
(1 x LUAFL1
cartridge supplied)
Limiter 100 35 Separate LA9LB920 (2)
limiter cartridge 130 70 Limiter-disconnector LUALF1
for LUALB1
(1) Must be connected to one power base only.
(2) Can be connected to multiple power bases in parallel, max total current 63 A.
LUA LB1 LUA LB920
TeSys U
Phase barrier
DB414654.eps
LUA LB920
Clip-in labels
Can be clipped on any TeSys U power base, on LU6M B0pp inverser block,
and Linergy HK busbar system.
Marking accessory
Description Sold by lot of Reference per unit
Clip-in label 8 x 18 mm 100 LAD90
The red sticker is dedicated to TeSys U LUCA, LUCB, LUCC, LUCD and LUCL
control units.
Description Reference per unit
LU9ET1S Retrofit safety-chain identification sticker LU9ET1S
A4/33
References Handles and components for
rotary control
Mounting kit
1 TeSys U Power base bracket; its horseshoe shaped sides hold the rotary
mechanism facing the original handle.
2 Mechanism, shaft and handle; the shaft enters the handle attached to the door
during closing.
Long shaft
LUA PN21 mounting kit
bb to be cut to the required length. Equipped with a connection endpiece.
Shaft support plate for deep enclosure
bb Provides horizontal guiding of the shaft, when the door is open.
DB414538.eps
Handle
GVA PA1 long shaft bb Delivered as a single unit, to be fitted on a side of the enclosure.
Note: references below are suitable for TeSys U power bases after 2004.
"Safety" stickers
bb Marking: Electrical hazard, etc.
GVA PK12 shaft support plate for deep
enclosure Description Tripping Reference
indication
Mounting kit Black handle, with error status, IP54 p LU9APN21
Red handle, with error status, IP54 p LU9APN22
Red handle, without error status, IP65 - LU9APN24
DB414520.eps
A4/34
References Handles and components
for MCC control drawers
TeSys U
Mounting kit and handle for MCC drawer
Together, this provides manual control of a TeSys U starter-controller from the front
DB123404.eps
1 2 3
MCC drawer
RESET
0
A4/35