The Compact Flame Controller CFC 2000 is a TÜV approved, dual channel flame monitoring system designed for various fuel types, featuring adjustable sensitivity and a range of outputs. It requires installation and adjustments to be performed by trained personnel, with support available from BFI Automation. The device includes safety features, such as immediate disconnection of the flame relay upon component failure, and is suitable for use in hazardous areas classified as Zone 1 and Zone 2.

Uploaded by

chuvanphuc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
211 views9 pages

TB cfc2000 en

The Compact Flame Controller CFC 2000 is a TÜV approved, dual channel flame monitoring system designed for various fuel types, featuring adjustable sensitivity and a range of outputs. It requires installation and adjustments to be performed by trained personnel, with support available from BFI Automation. The device includes safety features, such as immediate disconnection of the flame relay upon component failure, and is suitable for use in hazardous areas classified as Zone 1 and Zone 2.

Uploaded by

chuvanphuc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

COMPACT FLAME CONTROLLER

CFC 2000

TECHNICAL DESCRIPTION

EDITION: TB CFC2000-REV.5 2012-03-07

Important: Please note, that all mounting and wiring as well as all changing or adjustment at
the flame monitoring and evaluation equipment should only be carried out by fully
trained and authorized personnel.
BFI Automation is pleased to support you if you do not have any experience with
the equipment. Our service personnel is carrying out world wide installations, su-
pervision and commissioning and is available upon request.
For the stage of planning you can ask our sales and project engineers for any
support you may need.
BFI Automation is providing any kind of training for your engineers.

BFI – Automation Dipl.-Ing. K.-H. Mindermann GmbH, Eggerscheidter Str. 57, D-40883 Ratingen
Phone. +49 (0) 2102 96 82 – 0, Fax +49 (0) 2102 9682 – 42
E-Mail: info@bfi-automation.de

1
Compact Flame Controller
CFC 2000
UV, UV1, IR, IR1, IR2
- Flame scanner with integrated flame amplifier and flame relay.
- TÜV approved, DIN-DVGW, SIL3 certified
- For intermitted, continuous operation
- Type UV, UV : For natural Gas-, Oil- and dual fuel operation
- Type IR (VIS-IR): For monitoring of oil flames on diffusion burners
- Type IR1 (IR): For monitoring of natural gas flame in duct burners
- Type IR2 (IR): For selective monitoring of gas- and oil burners

- Dual channel flame monitoring and evaluation system.


- Adjustable sensitivity for both channels separate by software.
- Analogue output 0(4) – 20mA Intensity
- Possible flame evaluation by software
- Status indication of flame relay and intensity indication by LED
- Class of protection IP 65.
- RS232 output

! WARNING: IMPROPER INSTALLATION OF THESE PRODUCTS


WARNING MAY BE HAZARDOUS TO LIFE AND PROPERTY

Function
that only the typical modulation of the flame ra-
diation of the primary combustion zone is valued
and so extraneous light signals by neighbour
burners can be distinguished from the own
flame.
Further functional groups include signal condi-
tioning and other for the so-called dynamic moni-
toring channel which checks the fail safe function
of the device continuously.

A component or component defect leads to an


immediate disconnection of the flame relay,
which one is available as a floating change-over
contact for use with the burner management sys-
tem.
The switching condition is announced addition-
ally by a yellow LED on the reverse side of the
device behind the Perspex pane.
For the optimal adjustment of the compact flame
For the flame radiation analysis, a well approved controller the flame strength can be read off di-
integral procedure in the respective spectrum is rectly on the device by means of a pulsating
carried out with the compact flame controller. green LED. For the visualization or remote indi-
cation, a current output is available at 0 or 4-20
After a pre-amplification, the unwanted CW light mA.
component is withdrawn from the output signal of
the wear-resistant detector. The subsequent The safety switched-off time which depends on
sensitiveness attitude allows an attenuation of the combustibles to be checked is set ex-works
the signal for adaptation to the combustion proc- to a second. Longer switched-off times are op-
ess. The post-connected band pass filter caused, tionally available upon request.
2
WARNING: The functioning of the compact flame controller depends
! both on the burner configuration and from the air flow as well as the
spectral pattern of the flames (wavelength). We will advise you gladly
WARNING
in this regard on request.

Selection of the current output 0 or 4 to 20mA


The switch over of the current output of the be carried out by the special software which is
compact flame controller CFC 1000 / 2000 will available from BFI Automation.

Selection of the right modulation filter


For furnaces with very high power density, it combustible throughput for getting an optimal
can become necessary to activate another availability.
modulation filter besides. The adjustment of the modulation filter occurs
The compact flame controller should not be ad- via DIP switches which are arranged on the
justed to maximum signal level "Flame ON" but main board (red 4-part switches). A change of
as with the flame scanners also, to the highest adjustment to the DIP switches should only oc-
"Flame ON" / "Flame OFF" relation. Through cur if an adjustment of the compact flame con-
the numerous adjusting options of the compact troller is no more possible with the aid of soft-
flame controller the system itself could be eas- ware.
ily adjusted to all boiler geometries and any

Mounting

For guarantee of an optimal flame safeguard However the sight tube should always be kept
control, the correct and oscillation poor posi- as short as possible. A diameter of 2"is rec-
tioning of the sight tube to the flame is an es- ommended. The correct direction is repre-
sential assumption. For the selective burner sented in the subsequent drawing. The optical
control, the mounting has to occur in such a alignment system BFI 235 (part-no: P106) can
way that the primary combustion zone will be be supplied by BFI ex stock.
in all load ranges at the viewing angle of the
device. The prolongation of the viewpoint axis The compact flame controller CFC 1000 / 2000
must not cut the first half of other flames. is supplied completely with a quick release
Length and diameter of the viewpoint tube have flange. This flange assures possible assembly
a direct influence on the valuable flame radia- and dismantling of the device on site which
tion since the viewing angle of the compact
could be done as quickly as possible. The
flame controller CFC 2000 is defined. The
flange has a purge air connection which spe-
maximum length of the used sight tube should
cial construction prevents the lens of contami-
not exceed the maximum length 'L' on a given
diameter 'd' that no influence on the field of nation or damaging by dust polluted air.
view will occur. The optimal alignment system consists of heat
insulator, stop valve and ball flange.
d 1" 1,5" 2" This mechanical periphery can be supplied
L 0,5m 0,8m 1,1m upon request.

3
Flame root combustion area

Primary air

fuel

Changing in frequency and amplitude in


relationship to the distance of the flame root

Swivel
Viewing tube Sight pictures of the alignment device
Monting flange mount
Compact flame
controller

Swivel range
30°

30° max

Optical
alignment Heating
device insulator

correct wrong
30°

CAUTION: All alignments and or adjustments must always be applied


if new repair parts were installed, the flame scanner was moved or
! the flame picture was modified (e.g. through additional combustibles,
CAUTION new torches, changes to the torches / air registers), as well as all ini-
tial installations.

4
Installation
The pin assignment of the connector is shown in isolating transformer can be provided upon re-
the wiring diagram. quest. The burden of 250 ohms should always
not be exceeded.
The output signal 0(4)-20mA for flame intensity is
not separated by the supply voltage, so the sig- The device is immediately ready for operation af-
nal refers to the operating voltage measures. If ter switch-on of the supply voltage.
this should lead to problems, a corresponding

Wiring Diagram

Pin/Terminal Description colour code


BFI special cable KW6

1 Flame relay: Root white


2 Flame relay: Contact flame ON brown
3 Flame relay: Contact flame OFF pink
4 power supply: +24 V DC green
5 power supply: 0V (GND) yellow
6 current output 0(4)-20 mA grey
7 switch over canal 1 / canal 2 (+24V DC) blue
8 failure indication output +24V DC red

BFI-Spezialkabel KW 6
BFI special cable Kw6

Power supply +24 V DC


Spannungsversorgung +24V DC Green
grün 4 4

Flame relay “Flame


Flammenrelais On”EIN"
"Flamme Brown
braun 2 2

Flame relay “Root”


Flammenrelais "Zuleitung" weiss
White 1 1

Flame relay “Flame


Flammenrelais OFF”
"Flamme AUS" Pink
rosa 3 3

Power supply 0V (GND)


Spannungsversorgung 0V (GND) Yellow
gelb 5 5

Kompakt-
Current output0/4
Stromausgang 0(4) ... 20mA
- 20mA Grey
grau 6 6 flammen-
Blue wächter
Sensitivity switch over)
Empfindlichkeitsumschaltung rot 7 7
Compact
Failure output +24V DC
Fehlerausgang Red
blau 8 8 flame
controller

Outer braided
äußere shield
Abschirmung

CAUTION: In order to guarantee a proper operation the compact


flame controller must be tested several times at all conditions. The
burner has to be started and stopped several times (the flame relay
! must always interrupt reliably with no flame on). Carry out these tests
ACHTUNG while different neighbour burners are started and stopped as well as
on different boiler loads. This is a vital assumption for a proper and
reliable operation.

5
Standard Housing
235 108

BFI Automa tion


technology for your future

Typ e CFC 2000


Ser.-No.:

G1
24V dc
Germany

190
G1/2

Spülluft

Suitable for use in hazardous areas Zone 2

II 3 G
Ex nA II T4

OE-Converter housing

SKL

Fibre optic cable


G1

155

152
120
122

106

CFC 2000

88

O/E-Converter

Suitable for use in hazardous areas Zone 2

II 3 G
Ex nA II T4

6
Explosion Proof Housing

Ø120
G1
63 223

0032
Type 07-6152-9024
II 2 G Ex d IIC T6
II 2 D IP 66 T 80°C

For us in hazardous areas classified as Zone 1


PTB 03 ATEX 1051

EXPLOSION PROOF HOUSING FOR OE-CONVERTER

For one OE-Converter

232
Ø13
232

195.5

262

304
166.5
142
14

II 2 G Ex d IIC T6
II 2 D Ex tD A21 T80°C

For us in hazardous areas classified as Zone 1


KEMA 08 ATEX 0123

7
Accessories
Power supply 230/115V AC
Ball flange 1” with 2” flange plate
Heating insulator 1“
3-way-ball-valve 1“
5bar pressure barrier 1“
Optical adjustment device

Accessories for OE-Converter


Probe SKL for IR or UV
Fibre optic cable
Y-fibre optic cable
Fibre optic lance

Technical Data Sheet


Spectral Sensitivity
UV 270 to 420 nm
UV1 190 to 500 nm
IR 300 to 1050 nm
IR1 1050 to 2700 nm
IR2 300 to 2700 nm

Viewing angle 2,7°

Power supply 24 V DC
Current consumption approx. 100 mA, for triple Ex-OE-Converter approx. 300 mA
Construction protection class III SELV
Ambient temperature range -20°C...+60°C

Current output 0(4)...20 mA (Ra < 250 Ohm)


Current window possible adjustment by software
Failure output 24 V DC, short circuit protected
Application programming interface IRDA/RS232 (IRDA/USB in preparation)
Sensitivity switch over Selection of the sensitivity switch over 24 V DC

Flame relay 1 change over contact, floating


VDE 0110, class A
max. 48 V switching voltage
max. 1 A switching current
max. 30 W switching power

Switching thresholds programmable by software

Safety switch off time factory adjusted to 1s

Sight tube connection 1" inside screw ISO 228


Purge air connection 1/2" inside screw ISO 228
Value of purge air 10 Nm3/h

8
Electrical connection
Standard Harting connector HAN8 90 degrees
Explosion proof housing 3m special cable
OE-Converter housing Harting connector HAN8 90 degrees
Ex-OE-Converter housing M20-screw joint and terminal clamps inside

Dimension
Standard with flange 235 x 108 mm (Length x Diameter)
Flame proof housing 223 x 120 mm (Length x Diameter)*
OE-Converter housing 120 x 122 x80 mm (Length x Width x Height)*
Triple Ex-OE-Converter 276 x 276 x 166.5 mm (Length x Width x Height)*
*without connectors and mounting bracket

Class of protection Standard housing and OE-Converter housing IP 65, similar to


NEMA 4/Class 1 Div 2
ATEX Zone 2
II 3 G
Ex nA II T4

Ex- housing IP 66, similar to NEMA 4/Class 1 Div 1


ATEX Zone 1
PTB 03 ATEX 1051

0032
Type 07-6152-9024
II 2 G Ex d IIC T6
II 2 D IP 66 T 80°C

Ex-OE-Converter housing
ATEX Zone 1
KEMA 08 ATEX 0123

II 2 G Ex d IIC T6
II 2 D Ex tD A21 T80°C

Weight
Standard 1.5 kg
Flame proof housing 4.0 kg
OE-Converter housing 1.5 kg
Ex-OE-Converter housing 7.0 kg
Triple Ex-OE-Converter 13.0 kg

Full electronically self-check function for the guarantee of the faultless function of the device after VDE
0116, EN 230, EN 298, it correspond the guidelines TRD 411 to 414. DIN DVGW approved and CE
conform.
Right of technical changes reserved!

© BFI Automation 2012