COMPACT FLAME CONTROLLER
CFC 2000
TECHNICAL DESCRIPTION
EDITION: TB CFC2000-REV.5 2012-03-07
Important: Please note, that all mounting and wiring as well as all changing or adjustment at
the flame monitoring and evaluation equipment should only be carried out by fully
trained and authorized personnel.
BFI Automation is pleased to support you if you do not have any experience with
the equipment. Our service personnel is carrying out world wide installations, su-
pervision and commissioning and is available upon request.
For the stage of planning you can ask our sales and project engineers for any
support you may need.
BFI Automation is providing any kind of training for your engineers.
BFI – Automation Dipl.-Ing. K.-H. Mindermann GmbH, Eggerscheidter Str. 57, D-40883 Ratingen
Phone. +49 (0) 2102 96 82 – 0, Fax +49 (0) 2102 9682 – 42
E-Mail: info@bfi-automation.de
1
Compact Flame Controller
CFC 2000
UV, UV1, IR, IR1, IR2
- Flame scanner with integrated flame amplifier and flame relay.
- TÜV approved, DIN-DVGW, SIL3 certified
- For intermitted, continuous operation
- Type UV, UV : For natural Gas-, Oil- and dual fuel operation
- Type IR (VIS-IR): For monitoring of oil flames on diffusion burners
- Type IR1 (IR): For monitoring of natural gas flame in duct burners
- Type IR2 (IR): For selective monitoring of gas- and oil burners
- Dual channel flame monitoring and evaluation system.
- Adjustable sensitivity for both channels separate by software.
- Analogue output 0(4) – 20mA Intensity
- Possible flame evaluation by software
- Status indication of flame relay and intensity indication by LED
- Class of protection IP 65.
- RS232 output
! WARNING: IMPROPER INSTALLATION OF THESE PRODUCTS
WARNING MAY BE HAZARDOUS TO LIFE AND PROPERTY
Function
that only the typical modulation of the flame ra-
diation of the primary combustion zone is valued
and so extraneous light signals by neighbour
burners can be distinguished from the own
flame.
Further functional groups include signal condi-
tioning and other for the so-called dynamic moni-
toring channel which checks the fail safe function
of the device continuously.
A component or component defect leads to an
immediate disconnection of the flame relay,
which one is available as a floating change-over
contact for use with the burner management sys-
tem.
The switching condition is announced addition-
ally by a yellow LED on the reverse side of the
device behind the Perspex pane.
For the optimal adjustment of the compact flame
For the flame radiation analysis, a well approved controller the flame strength can be read off di-
integral procedure in the respective spectrum is rectly on the device by means of a pulsating
carried out with the compact flame controller. green LED. For the visualization or remote indi-
cation, a current output is available at 0 or 4-20
After a pre-amplification, the unwanted CW light mA.
component is withdrawn from the output signal of
the wear-resistant detector. The subsequent The safety switched-off time which depends on
sensitiveness attitude allows an attenuation of the combustibles to be checked is set ex-works
the signal for adaptation to the combustion proc- to a second. Longer switched-off times are op-
ess. The post-connected band pass filter caused, tionally available upon request.
2
WARNING: The functioning of the compact flame controller depends
! both on the burner configuration and from the air flow as well as the
spectral pattern of the flames (wavelength). We will advise you gladly
WARNING
in this regard on request.
Selection of the current output 0 or 4 to 20mA
The switch over of the current output of the be carried out by the special software which is
compact flame controller CFC 1000 / 2000 will available from BFI Automation.
Selection of the right modulation filter
For furnaces with very high power density, it combustible throughput for getting an optimal
can become necessary to activate another availability.
modulation filter besides. The adjustment of the modulation filter occurs
The compact flame controller should not be ad- via DIP switches which are arranged on the
justed to maximum signal level "Flame ON" but main board (red 4-part switches). A change of
as with the flame scanners also, to the highest adjustment to the DIP switches should only oc-
"Flame ON" / "Flame OFF" relation. Through cur if an adjustment of the compact flame con-
the numerous adjusting options of the compact troller is no more possible with the aid of soft-
flame controller the system itself could be eas- ware.
ily adjusted to all boiler geometries and any
Mounting
For guarantee of an optimal flame safeguard However the sight tube should always be kept
control, the correct and oscillation poor posi- as short as possible. A diameter of 2"is rec-
tioning of the sight tube to the flame is an es- ommended. The correct direction is repre-
sential assumption. For the selective burner sented in the subsequent drawing. The optical
control, the mounting has to occur in such a alignment system BFI 235 (part-no: P106) can
way that the primary combustion zone will be be supplied by BFI ex stock.
in all load ranges at the viewing angle of the
device. The prolongation of the viewpoint axis The compact flame controller CFC 1000 / 2000
must not cut the first half of other flames. is supplied completely with a quick release
Length and diameter of the viewpoint tube have flange. This flange assures possible assembly
a direct influence on the valuable flame radia- and dismantling of the device on site which
tion since the viewing angle of the compact
could be done as quickly as possible. The
flame controller CFC 2000 is defined. The
flange has a purge air connection which spe-
maximum length of the used sight tube should
cial construction prevents the lens of contami-
not exceed the maximum length 'L' on a given
diameter 'd' that no influence on the field of nation or damaging by dust polluted air.
view will occur. The optimal alignment system consists of heat
insulator, stop valve and ball flange.
d 1" 1,5" 2" This mechanical periphery can be supplied
L 0,5m 0,8m 1,1m upon request.
3
Flame root combustion area
Primary air
fuel
Changing in frequency and amplitude in
relationship to the distance of the flame root
Swivel
Viewing tube Sight pictures of the alignment device
Monting flange mount
Compact flame
controller
Swivel range
30°
░
30° max
Optical
alignment Heating
device insulator
correct wrong
30°
░
CAUTION: All alignments and or adjustments must always be applied
if new repair parts were installed, the flame scanner was moved or
! the flame picture was modified (e.g. through additional combustibles,
CAUTION new torches, changes to the torches / air registers), as well as all ini-
tial installations.
4
Installation
The pin assignment of the connector is shown in isolating transformer can be provided upon re-
the wiring diagram. quest. The burden of 250 ohms should always
not be exceeded.
The output signal 0(4)-20mA for flame intensity is
not separated by the supply voltage, so the sig- The device is immediately ready for operation af-
nal refers to the operating voltage measures. If ter switch-on of the supply voltage.
this should lead to problems, a corresponding
Wiring Diagram
Pin/Terminal Description colour code
BFI special cable KW6
1 Flame relay: Root white
2 Flame relay: Contact flame ON brown
3 Flame relay: Contact flame OFF pink
4 power supply: +24 V DC green
5 power supply: 0V (GND) yellow
6 current output 0(4)-20 mA grey
7 switch over canal 1 / canal 2 (+24V DC) blue
8 failure indication output +24V DC red
BFI-Spezialkabel KW 6
BFI special cable Kw6
Power supply +24 V DC
Spannungsversorgung +24V DC Green
grün 4 4
Flame relay “Flame
Flammenrelais On”EIN"
"Flamme Brown
braun 2 2
Flame relay “Root”
Flammenrelais "Zuleitung" weiss
White 1 1
Flame relay “Flame
Flammenrelais OFF”
"Flamme AUS" Pink
rosa 3 3
Power supply 0V (GND)
Spannungsversorgung 0V (GND) Yellow
gelb 5 5
Kompakt-
Current output0/4
Stromausgang 0(4) ... 20mA
- 20mA Grey
grau 6 6 flammen-
Blue wächter
Sensitivity switch over)
Empfindlichkeitsumschaltung rot 7 7
Compact
Failure output +24V DC
Fehlerausgang Red
blau 8 8 flame
controller
Outer braided
äußere shield
Abschirmung
CAUTION: In order to guarantee a proper operation the compact
flame controller must be tested several times at all conditions. The
burner has to be started and stopped several times (the flame relay
! must always interrupt reliably with no flame on). Carry out these tests
ACHTUNG while different neighbour burners are started and stopped as well as
on different boiler loads. This is a vital assumption for a proper and
reliable operation.
5
Standard Housing
235 108
BFI Automa tion
technology for your future
Typ e CFC 2000
Ser.-No.:
G1
24V dc
Germany
190
G1/2
Spülluft
Suitable for use in hazardous areas Zone 2
II 3 G
Ex nA II T4
OE-Converter housing
SKL
Fibre optic cable
G1
155
152
120
122
106
CFC 2000
88
O/E-Converter
Suitable for use in hazardous areas Zone 2
II 3 G
Ex nA II T4
6
Explosion Proof Housing
Ø120
G1
63 223
0032
Type 07-6152-9024
II 2 G Ex d IIC T6
II 2 D IP 66 T 80°C
For us in hazardous areas classified as Zone 1
PTB 03 ATEX 1051
EXPLOSION PROOF HOUSING FOR OE-CONVERTER
For one OE-Converter
232
Ø13
232
195.5
262
304
166.5
142
14
II 2 G Ex d IIC T6
II 2 D Ex tD A21 T80°C
For us in hazardous areas classified as Zone 1
KEMA 08 ATEX 0123
7
Accessories
Power supply 230/115V AC
Ball flange 1” with 2” flange plate
Heating insulator 1“
3-way-ball-valve 1“
5bar pressure barrier 1“
Optical adjustment device
Accessories for OE-Converter
Probe SKL for IR or UV
Fibre optic cable
Y-fibre optic cable
Fibre optic lance
Technical Data Sheet
Spectral Sensitivity
UV 270 to 420 nm
UV1 190 to 500 nm
IR 300 to 1050 nm
IR1 1050 to 2700 nm
IR2 300 to 2700 nm
Viewing angle 2,7°
Power supply 24 V DC
Current consumption approx. 100 mA, for triple Ex-OE-Converter approx. 300 mA
Construction protection class III SELV
Ambient temperature range -20°C...+60°C
Current output 0(4)...20 mA (Ra < 250 Ohm)
Current window possible adjustment by software
Failure output 24 V DC, short circuit protected
Application programming interface IRDA/RS232 (IRDA/USB in preparation)
Sensitivity switch over Selection of the sensitivity switch over 24 V DC
Flame relay 1 change over contact, floating
VDE 0110, class A
max. 48 V switching voltage
max. 1 A switching current
max. 30 W switching power
Switching thresholds programmable by software
Safety switch off time factory adjusted to 1s
Sight tube connection 1" inside screw ISO 228
Purge air connection 1/2" inside screw ISO 228
Value of purge air 10 Nm3/h
8
Electrical connection
Standard Harting connector HAN8 90 degrees
Explosion proof housing 3m special cable
OE-Converter housing Harting connector HAN8 90 degrees
Ex-OE-Converter housing M20-screw joint and terminal clamps inside
Dimension
Standard with flange 235 x 108 mm (Length x Diameter)
Flame proof housing 223 x 120 mm (Length x Diameter)*
OE-Converter housing 120 x 122 x80 mm (Length x Width x Height)*
Triple Ex-OE-Converter 276 x 276 x 166.5 mm (Length x Width x Height)*
*without connectors and mounting bracket
Class of protection Standard housing and OE-Converter housing IP 65, similar to
NEMA 4/Class 1 Div 2
ATEX Zone 2
II 3 G
Ex nA II T4
Ex- housing IP 66, similar to NEMA 4/Class 1 Div 1
ATEX Zone 1
PTB 03 ATEX 1051
0032
Type 07-6152-9024
II 2 G Ex d IIC T6
II 2 D IP 66 T 80°C
Ex-OE-Converter housing
ATEX Zone 1
KEMA 08 ATEX 0123
II 2 G Ex d IIC T6
II 2 D Ex tD A21 T80°C
Weight
Standard 1.5 kg
Flame proof housing 4.0 kg
OE-Converter housing 1.5 kg
Ex-OE-Converter housing 7.0 kg
Triple Ex-OE-Converter 13.0 kg
Full electronically self-check function for the guarantee of the faultless function of the device after VDE
0116, EN 230, EN 298, it correspond the guidelines TRD 411 to 414. DIN DVGW approved and CE
conform.