    Air
    deflector
                                                                                                                      Burner
Weishaupt WK-series burners have              heat exchanger in the flue can be used      Fuels
been designed especially for                  to reclaim a large amount of energy         • Fuel oil EL (< 6 mm2/s at 20 °C)
industrial use. The modular design            from these hot flue gases, increasing         in accordance with DIN 51 603-1
of the burners, coupled with their            efficiency by up to 10 %. Weishaupt         • Fuel oil S (< 60 mm2/s at 100 °C)
large capacity range, makes them              WK-series industrial burners can be                      (< 700 mm2/s at 50 °C)
ideally suited to a broad spectrum            operated with preheated combustion-           in accordance with DIN 51 603-3/-5
of special applications.                      air temperatures of up to 250 °C.           • Natural gas E/LL
                                                                                          • LPG B/P
Modular principle                             Nozzle-head shut-off device
Weishaupt WK-series industrial burners        At burner shutdown, or when changing        Permissible installation conditions
are of modular design. That means the         over to gas operation, a safety shut-off    • Ambient temperature during
fan, pump station, and preheater station      device located in the oil atomising           operation: -15 to +40 °C
are all selected independently of the         system shuts off the oil flow directly in   • Humidity: max. 80 % relative humidty,
burner. This concept offers a high            the nozzle orifice, preventing the            no condensation
degree of flexibility in matching to the      escape of any oil.                          • Standard burner protection: IP 54
most diverse applications.                                                                • Suitable for horizontal or vertical
                                              Modulating operation                          installation
Digital combustion management                 Within its operating range, the burner’s
Digital combustion management                 output is matched to the current heat       Standards conformity
ensures the simple and safe operation         demand.                                     • EN 267 and EN 676
of combustion plant. Emissions are                                                        • Pressure Equipment Directive,
minimised and economy is maximised.           Reduced capacity at start-up                  97/23/EC
                                              The burners start at gas operation at a     • Gas Appliance Directive,
Insulated burner housing                      reduced ignition load (WK (G) MS              2009/142/EC
The burner housing is fitted with internal    > 17.5 MW with an additional pilot bur-     • Machinery Directive, 2006/42/EC
insulation (optional extra on the ambient-    ner). This means that only a small quan-    • Electromagnetic Compatibility
air versions of the WK 40 and 50). This       tity of gas flows into the combustion         Directive, 2004/108/EC
significantly reduces the surface             chamber. After the ignition phase, the      • Low Voltage Directive, 2006/95/EC
temperature of the housing during             burner drives to partial load.              • The burners are marked with a
operation with preheated combustion                                                          - CE mark
air. The insulation also provides effective   Controlled shutdown from partial               - CE Product ID No.
noise reduction.                              load                                           - Type-test No.
                                              Controlled shutdown of the burner
Heat recovery using preheated                 always takes place from the partial-load
combustion air                                position, thus preventing impact on the
Many industrial processes create high         gas main.
flue-gas temperatures due to the high
temperature of the medium used. A
2
                                      Gas valve train and accessories
Oil-supply accessories
                                                                             3
Digital combustion management:
Precise, simple, and reliable
                                            Measures for saving energy and
                                                                                                          O2 trim saves fuel through a continual
                                            increasing safety and reliability
                                                                                                          and extremely efficient optimisation of
                                                                                                          the combustion air. Different O2 probes
                                            Electronic compound regulation with
                                                                                                          are available, providing suitable solutions
                                            the W-FM 100 and 200 combustion
                                                                                                          for almost all fuels in applications with
                                            managers facilitates the extremely
                                                                                                          flue-gas temperatures below 300 °C.
                                            precise, hysteresis-free setting of the
                                            burner. The burner can be adjusted for
                                                                                                          Combined CO/O2 control ensures an
                                            ideal combustion figures throughout its
                                                                                                          ultimate degree of safety. CO emissions
                                            entire capacity range. This reduces flue
                                                                                                          are continually monitored and, if the
                                            gas losses and saves fuel.
                                                                                                          defined limit is exceeded, the burner is
                                                                                                          operated with an increased amount of
                                            Variable speed drive reduces electrical
                                                                                                          excess air for a short period of time
                                            consumption and facilitates a soft start
                                                                                                          before the O2 trim returns the burner to
                                            of the combustion air fan. The use of
                                                                                                          its preset O2 setpoint. Should external
                                            VSD also reduces noise emissions by a
                                                                                                          influences prevent a non-critical
                                            considerable amount.
Setting via the control and display unit                                                                  condition from being reached, then the
                                                                                                          burner will undergo a controlled shut-
                                                                                                          down.
Digital combustion management
means optimal combustion figures,
                                                 Digital combustion management overview                             W-FM 100          W-FM 200
continuously reproducible setpoints,
and ease of use.                                 Continuous operation > 24 h                                            l                 l
                                                 Capacity control for temperature or pressure                        Optional             l
Weishaupt WK-series burners are                  O2 trim with QGO20/21 O2 probe                                                           l
equipped as standard with electronic             Combined CO/O2 control                                                                Optional
compound regulation and digital                  VSD                                                                                      l
combustion management. Modern                    Flue gas recirculation (temperature compensated)                                         l
combustion technologies demand a                 WK(G)MS 80 with gas ignition                                                             l
precise and continually reproducible             WKMS 80 with light-oil ignition                                        l                 l
dosing of fuel and combustion air.
                                                 SQM40/48/9... servomotors in electronic compound (max.)               x4                x6
                                                 W-FC 4.0 flame monitoring                                              l                 l
Simple operation
                                                 W-FC 5.0/6.0 flame monitoring                                                            l
Setting and control of the burner is
achieved using a control and display             Parallel burner firing
                                                                                                                     Optional             l
                                                 (in conjunction with KS... controller)
unit. This is linked to the combustion
                                                 Two gaseous fuels
manager via a bus system, enabling the                                                                                                    l
                                                 (also in combination with a liquid fuel)
user-friendly setting of the burner. The
                                                 Two liquid fuels
control and display unit has a clear text                                                                               lx2               lx2
                                                 with different calorific values
display with a choice of languages. An           Integral valve proving (with gaseous fuels)                            l                 l
English/Chinese dual-screen version is           Burner-mounted W-FM                                                    l                 l
available as an option should a Chinese-         for combustion-air temperatures up to 40 °C
character display be desired.                    W-FM supplied loose (for panel mounting)                            Optional          Optional
                                                 for combustion-air temperatures up to 40 °C
Flexible communication options                   Burner-mounted ABE                                                    l 1)              l 1)
The integrated interface enables all             for combustion-air temperatures up to 40 °C
necessary data and functions to be               ABE supplied loose (for panel mounting)                             Optional          Optional
                                                 for combustion-air temperatures up to 40 °C
relayed to a master control system via,
                                                 W-FM and ABE supplied loose (for panel mounting)                       l                 l
for example, eBUS, Modbus RTU,                   for combustion-air temperatures from 40 to 250 °C
Modbus TCP/IP, or Profibus-DP.                   Setpoint input (0)4-20 mA / 0-10 V                                  Optional             l
                                                 Configurable analogue output X63 (rating / drive position /                              l
                                                 flame signal / medium temperature or pressure)
                                                 eBUS / Modbus RTU                                                      l                 l
                                            1)
                                                 Not available with dual-screen Roman and Chinese-script version
4
                                                                                                                                                                                  (max. 10 m)
                                                                                                                                          • CO probe
                                                                                                                                                                    (max. 10 m)
                                                                                                                                          • O2 probe (QGO20)
                                                                                                                                          oder
                                                                                                                                          • O2 diffusion probe
                                                                                                                                            (QGO21 for
                                                                                                                                            heavy oil)
                Burner with inbuilt digital
                combustion manager
                                                                          0-10 V
                                                               T P        4-20 mA
Setpoint input
O2 module CO module
Gas feed
                                                                                                                                          Burner-mounted / panel-mounted
                     Oil feed                                                                                                             control and display unit
                                                                                Frequency convertor for
                                                                                variable speed drive
Air feed
                                           Regulating sleeve
                                           (air)
                                                                                                          CAN bus (max. 100 m)
                                                                                                                                          PC / touchscreen
                                                                                                                                          visualisation
                                                                                                                                 Modbus
                                                                                                                                          System networking
                                                                                                                                          via PLC / DDC
                                                                                                                                                                                                5
Limitless communications:
flexible, reliable and simple
                                                                            PC / touchscreen
                                                                            visualisation
CAN bus
Other burners
                               Programming
                               cable                        Various bus systems, e.g. Modbus TCP/IP, Profilbus-DP
Other burners
6
                              BMS              Worldwide
              SCADA                 Laptop /
              Supervisory Control   tablet
              and Data Aquisition
                                                 Email
                                                 SMS
Smartphone
                                                         • Monitoring and
                                                           alarms
• Adjust setpoints
                                                                                             7
Emissions reduced
by the multiflam® principle
Weishaupt’s multiflam® technology
was designed for gas and dual-fuel
burners. By using a patented 3LN
mixing head, NOx emissions on WK-
series burners can be reduced to
extremely low levels.
160 160
150 150
140 140
                                              130                                         130
                                                                                                  LRV (Switzerland)
                                              120                                         120
                                                                    TA Luft (Germany)
                                              110               1. BImschV (Germany)      110
                                                                        10 to 20 MW
                                              100                                         100
                                                                                                                        NOx
                                               90                                         90
                                                        LRV (Switzerland)
                                               80                                         80
70 70
                                               60                                         60
                                                                                 NOx
50 50
40 40
30 30
                                               20                                          20
                                                                CO
CO
10 10
Gas Oil
8
Flame monitoring
for demanding safety requirements
                                                         burners firing from different directions
                                                         into a single combustion chamber, and
                                                         for process plant with various flame                                             W-FC 4.0
                                                         sources. The W-FC assembly monitors
                                                         each flame separately via a load-
                                                         dependent switching threshold for each
                                                         fuel. This guarantees a distinct
                                                         differentiation from extraneous sources.
                                                         The CFC3... flame sensor functions in
                                                         parallel with the QRA73 flame sensor on
                                                         the W-FM 200 combustion manager. This
                                                         convenient, load-dependent setting of            For classical parallel firing into a combustion
                                                         the on and off thresholds rests upon the         chamber, with a maximum turndown of 4:1
                                                         electronic VLoad module, which can be
                                                         configured using software.                                                       W-FC 5.0
                                                                                                               M
                                                                                                               M
                                                                                                          FU
                                                                                                               M
                                                                                                               M
                                                                                                                            M      M
                                                                                                                                                            9
Ignition variants for every fuel and rating
 Variant A                                          Variant B                                                   Variant C
 Standard ignition for liquid fuels                 Standard ignition for gaseous fuels                         Ignition option for liquid fuels on
 on WKL/WKMS40-70 and WKL80.                        on WKG(L/MS)40-70 and WKG(L)80.3)                           WKMS40-70.
 Liquid fuels are ignited directly by the           The pilot line feeds a controlled amount                    The pilot line feeds a controlled amount
 high-voltage ignition electrodes.                  of gas to the ignition electrodes for                       of LPG to the ignition electrodes for
                                                    ignition. The main gas line is released                     ignition. This pilot flame ignites the
                                                    and ignited after a short delay.                            main liquid fuel upon release.
Oil nozzle Ignition pilot Oil nozzle Ignition pilot Oil nozzle
Ignition variant A Ignition variant B with ignition pilot Ignition variant C with ignition pilot
  A                                                  B                                                          C
                                                                         V1            V2
                                                                                                                 LPG
                                                    Main gas line
Gas valve train with ignition variant B Gas valve train with ignition variant C
                                                                                                                 G
                                                                       Light-oil ignition burner
                                                                                                                                    P
10
Variants D to F
Optimal ignition for high-viscosity                       Flame monitoring is via a separate
liquid fuels on WK(G)MS80, using a                        ionisation probe, which necessitates the
high-quality ignition burner                              use of a W-FM 200 combustion
This variant facilitates reliable ignition                manager.
at a considerably reduced rating.                                                                                                      Ignition electrode
                                                          This reliable solution was developed
An ignition electrode is used to ignite                   especially for heavy and special fuel
                                                                                                                                                                         Ionisation electrode
the pilot burner’s gas mixture. The                       oils with widely varying characteristics.
pilot burner is then used to ignite the                   It is also suitable for extreme ignitions,                                   Front view:
main flame upon fuel release.                             such as cold-starting plant that utilises                                    Ignition electrode
                                                          pre-heated combustion air.
A typical LPG bottle (11/33 kg) is
adequate for ensuring reliable ignition.
For example, an 11 kg LPG bottle is
sufficient for well over 300 ignitions.                                                                                                Ignition variants D to F with ignition burner
D                 P P
                         W-MF
                                                            E                      P P
                                                                                             W-MF
                                                                                                                                            F                       W-MF
                                                                                             V1     V2                                                              V1   V2
                                                          Main gas line                                                                 Main gas line
Gas valve train with ignition variant D Gas valve train with ignition variant E Gas valve train with ignition variant F
                WK…40–70                                                                                                                    WK…80
          WKL             WKG 3) / WKGL            WKL                    WKMS                        WKMS                       WKG                        WKGMS           WKGMS
          WKMS              WKGMS                                                                    < 17,5 MW                   WKGL                                      < 17,5 MW
A l l l 2)
B l l l 2)
C l (WKMS)
D l 1) l 1)
E l 1) l 1)
F                                                                                                                                  l   1)
                                                                                                                                                             l 1)
G l l
Accessories for variants C to E                         1                                                   Complete set (Part No. 271 805 2601 2) comprising:
                                                                          2                              1 Pressure regulator for 11/33 kg LPG bottle
                                                                                         3
                                                                                                         2 Hose-rupture protection
                                                                                                         3 3 m hose
l Standard l Optional      1)
                                W-FM 200 combustion manager required          2)
                                                                                   1SF version excluded          3)
                                                                                                                      WKG 40-70 ZM(H)-LN burners ignite from main gas line - no pilot
                                                                                                                                                                                            11
The right mixing assembly for every application
                                                                                                      Burner                                                                                           NOx Class 1)
                                                                                                                  Load-dependent air
                                                                                                       type                                                                              EN 676                EN 267
                                                                                                                                                                                         Natural gas
     standard-length combustion head (i.e. the flame tube and mixing
                                                                                                                                                                             Heavy oil
     assembly) can be inserted and withdrawn through the service
                                                                                                                                                                 Light oil
     opening in the burner housing. To further assist removal, the
LPG
                                                                                                                                                                                                         LPG
     mixing assemblies on WK80 burners are guided by rail.
     ZM(H)
     Mixing assembly for gas, oil,
                                                                                                     WK 40-50                               ○             ○     ○           ○             –             –         –
     and dual-fuel burners.                                                                          WK 70/1                                ●             ○     ●           ○             1             –         1
     For plant with no particular                                                                    WK 80/3                                  –           –     ●           ○             –             –         1
     NOX requirements.
     ZM(H)-NR
     Gas-side NOX reduction                                                                          WK 50                                  ○             ○     ○           ○             –             –         –
     compared to ZM version.                                                                         WK 70/1                                ●             ●     ●           ○             2             3         2
                                                                                                     WK 70/3                                ●             ●     ●           ○             3             3         1
                                                                                                     WK 80/3                                ●             ●     ●           ○             3             3         1
     ZM(H)-1LN
     Low-NOX mixing assembly for
     gas and dual-fuel burners.                                                                      WK 50                –                  ○             ○     ○            –            –             –         –
                                                                                                     WK 70                –                  ●             ●     ●            –            3             3         2
     For plant with gas and oil-side
     NOX requirements.
     ZM(H)-LN
     Low-NOX mixing assembly for
     gas burners.                                                                                    WK 40                –                  ○             ○      –           –            –             –         –
                                                                                                     WK 70                –                  ●             ○      –           –            3             –         –
     Further reduction in NOX
     emissions compared to 1LN-
     version burners.
     (ZMH)-3LN
     Low-NOX mixing assembly for
     gas, oil, and dual-fuel burners.
                                                                                                     WK 40-50                               ○             ○     ○            –            –             –         –
     For plant with extremely low                                                                    WK 70                                  ●             ●     ●            –            3             3         3
     NOX limits. Lowest NOX                                                                          WK 80                                  ●             –     ●            –            3             3         3
     emissions in comparison with
     all other versions.
     1)
          Combustion-air temperatures < 40 °C
     2)
          Minimum requirements for the combustion-chamber geometry must be agreed with Weishaupt’s headquarters
     3)
          Mixing assembly
12
                                                                                                          Burner                                                                                              NOx Class 1)
                                                                                                                      Load-dependent air
                                                                                                           type                                                                                 EN 676                 EN 267
Length Diameter
Natural gas
Natural gas
                                                                                                                                                                                                                LPG
 ZM(H)-1SF
 Mixing assembly for gas, oil,
 and dual-fuel burners.
                                                                                                        WK 40-
                                                                                                                                                ○             ○       ○            ○             –             –            –
                                                                                                        80/3
 Mixing assembly for extremely
 short combustion chambers in
 water-tube boilers.
 ZM(H) - VSF
 Mixing assembly for gas
 burners, type WKG80/4 to
 80/6.
EN emission classes
 Fuel                                Natural Gas (EN 676)                               LPG (EN 676)                                                                 Light Oil (EN 267)
Emission Class 1 2 3 1 2 3 1 2 3
 NOx emissions in
                            ≤ 170           ≤ 120            ≤ 80           ≤ 230            ≤ 180           ≤ 140                               ≤ 250                             ≤ 185                              ≤ 120
 mg/kWh
Maximum turndown
 Burner                Version                                               Natural Gas/LPG                        Light Oil                                                                         HFO
Basic conditions:
Without excess air limitations. Combustion values not guaranteed throught the entire turndown range. All operational points must lie within the burner’s capacity chart.
Higher turndowns may be achievable in certain cases (subject to agreement with Weishaupt’s headquarters).
                                                                                                                                                                                                                                             13
Overview of capacities
Gas burners
 Version ZM
 WKG natural-gas and LPG burners
 Burner type Version        Fuel              Rating kW          0             5.000           10.000            15.000            20.000            25.000            30.000
                                                                      2.500            7.500            12.500            17.500            22.500            27.500
                            ZMH        / ZM
 WK 40/1-A ZM(H)            Nat. gas     300 – 1800 / 2200                                                                                    min. full load (kW) ZM/ZMH
                            LPG          300 – 1800 / 2200                                                                                       1000 / 1000
 Version NR
 WKG natural-gas and LPG burners
 Burner type Version        Fuel              Rating kW          0             5.000           10.000            15.000            20.000            25.000            30.000
                                                                      2.500            7.500            12.500            17.500            22.500            27.500
                            ZMH        / ZM
 WK 50/1-B ZM(H)-NR Nat. gas             600 – 3200 / 4000                                                                                    min. full load (kW) ZM/ZMH
                    LPG                  600 – 3200 / 4000                                                                                       2000 / 2000
 Version 1LN
 WKG natural-gas and LPG burners
 Burner type Version        Fuel              Rating kW          0             5.000           10.000            15.000            20.000            25.000            30.000
                                                                      2.500            7.500            12.500            17.500            22.500            27.500
                            ZMH        / ZM
 WK 50/1-B ZM(H)-1LN Nat. gas            600 – 3000 / 3600                                                                                    min. full load (kW) ZM/ZMH
                     LPG                 600 – 3000 / 3600                                                                                       2000 / 2000
 Burner-selection criterion:
 The minimum full-load rating within a burner’s capacity range corresponds to the maximum rating of the next smallest size of the same version burner.
14
Version LN
WKG natural-gas burners
Burner type Version   Fuel              Rating kW        0              5.000             10.000            15.000                 20.000             25.000            30.000
                                                                2.500            7.500             12.500                17.500              22.500            27.500
                      ZMH        / ZM
WK 40/2-A ZM(H)-LN Nat. gas 500 – 2500 / 3000 min. full load (kW) ZM 1800 / ZMH 1800
WK 70/1-B (ZMH)-3LN Nat. gas      1000 – 9400 / 10000                                                                                          min. full load (kW) ZM/ZMH
                    LPG           1550 – 9400 / 10000                                                                                             5000 / 5000
Version ZM 1SF
WKG natural-gas and LPG burners
Burner type Version   Fuel              Rating kW        0              5.000             10.000            15.000                 20.000             25.000            30.000
                                                                2.500            7.500             12.500                17.500              22.500            27.500
                      ZMH        / ZM
WK 50/2-A ZM(H)-1SF Nat. gas 800 – 4800 / 6000 min. full load (kW) ZM 4000 / ZMH 3200
Version ZM VSF
WKG natural-gas and LPG burners
Burner type Version   Fuel              Rating kW   0                5.000           10.000            15.000             20.000             25.000            30.000
                                                             2.500           7.500            12.500            17.500              22.500            27.500            32.500
                      ZMH        / ZM
WK 80/4    ZM(H)-VSF Nat. gas     2200 – 17600 / 22000                                                                                         min. full load (kW) ZM/ZMH
                     LPG          3200 – 17600 / 22000                                                                                           12000 / 9600
   Version ZM:        Combustion-air temperatures up to 40 °C                        See the planning and installation handbook for fan selection and arrangement,
   Version ZMH:       Combustion-air temperatures up to 100 °C                       gas valve trains, special equipment, technical data, and dimensions.
   Version ZMH:       Combustion-air temperatures up to 250 °C
                                                                                                                                                                            15
Overview of capacities
Oil burners
 Version ZM
 WKL and WKMS light and heavy-oil burners
 Burner type Version       Fuel               Rating kW          0           5.000           10.000            15.000            20.000            25.000            30.000
                                                                     2.500           7.500            12.500            17.500            22.500            27.500
                           ZMH         / ZM
 WK 40/1-A ZM(H)           Light oil     450 – 1800 / 2200                                                                                  min. full load (kW) ZM/ZMH
                           Heavy oil     550 – 1800 / 2200                                                                                     1200 / 1200
WK 70/1-B* 3LN Light oil 1550 –10000 min. full load (kW) ZM 5000
 * 3LN-version WK 70 and WK 80 burners are not available as single-fuel oil burners. However, the WKGL dual-fuel burners are available in a special
   “oil only” execution without gas-side components. Refer to the price list for the appropriate price reduction.
 Version 1SF
 WKL and WKMS light and heavy-oil burners
 Burner type Version       Fuel               Rating kW          0           5.000           10.000            15.000            20.000            25.000            30.000
                                                                     2.500           7.500            12.500            17.500            22.500            27.500
                           ZMH         / ZM
 WK 50/2-A ZM(H)-1SF Light oil          1125 – 4800 / 6000                                                                                   min. full load (kW) ZM/ZMH
                     Heavy oil          1700 – 4800 / 6000                                                                                     4000 / 3200
16
Overview of capacities
Dual-fuel burners
Version ZM
WKGL and WKGMS dual-fuel burners
Burner type Version        Fuel               Rating kW            0           5.000           10.000            15.000            20.000            25.000            30.000
                                                                       2.500           7.500            12.500            17.500            22.500            27.500
                           ZMH         / ZM
WK 40/1-A ZM(H)            Nat. gas      300 –   1800   /   2200                                                                              min. full load (kW) ZM/ZMH
                           LPG           300 –   1800   /   2200                                                                                1000 / 1000
                           Light oil     450 –   1800   /   2200                                                                              min. full load (kW) ZM/ZMH
                           Heavy oil     550 –   1800   /   2200                                                                                1200 / 1200
Burner-selection criterion:
The minimum full-load rating within a burner’s capacity range corresponds to the maximum rating of the next smallest size of the same version burner.
   Version ZM:             Combustion air temperatures up to 40 °C                       See the planning and installation handbook for fan selection and arrangement,
   Version ZMH:            Combustion air temperatures up to 250 °C                      gas valve trains, special equipment, technical data, and dimensions.
                                                                                                                                                                           17
Overview of capacities
Dual-fuel burners
 Version NR
 WKGL and WKGMS dual-fuel burners
 Burner type Version        Fuel             Rating kW              0           5.000           10.000            15.000            20.000            25.000            30.000
                                                                        2.500           7.500            12.500            17.500            22.500            27.500
                            ZMH       / ZM
 Version 1LN
 WKGL dual-fuel burners
 Burner type Version        Fuel             Rating kW              0           5.000           10.000            15.000            20.000            25.000            30.000
                                                                        2.500           7.500            12.500            17.500            22.500            27.500
                            ZMH       / ZM
 Burner-selection criterion:
 The minimum full-load rating within a burner’s capacity range corresponds to the maximum rating of the next smallest size of the same version burner.
18
Version 3LN multiflam®
WKGL dual-fuel burners
Burner type Version   Fuel          Rating kW            0           5.000           10.000            15.000            20.000            25.000            30.000
                                                             2.500           7.500            12.500            17.500            22.500            27.500
                      ZM
Version 1SF
WKGL and WKGMS dual-fuel burners
Burner type Version   Fuel               Rating kW       0           5.000           10.000            15.000            20.000            25.000            30.000
                                                             2.500           7.500            12.500            17.500            22.500            27.500
                      ZMH         / ZM
   Version ZM:        Combustion air temperatures up to 40 °C                  See the planning and installation handbook for fan selection and arrangement,
   Version ZMH:       Combustion air temperatures up to 250 °C                 gas valve trains, special equipment, technical data, and dimensions.
                                                                                                                                                                 19
Burner selection based on steam boiler rating
      Steam rate                         t/h                                                                                          15
      Steam pressure                     bar                 10                                              16                                                                      25
      Firing rate                        MW          10.4          10.0      10.5          10.0      11.5          11.0       12.4          12.0     10.5         10.1       11.4         10.9       12.3         11.9
      Oil flow rate (LHV=11.86 kWh/kg)   kg/h         876          840        881           845       967           931       1046          1009      884         848        958          922        1040         1004
      Gas flow rate (LHV =10.35 kWh/m³) m³/h         1004          963        1010         968        1108         1067        1198         1157     1013         972        1098         1057       1192         1151
      Min. gas supply pressure *        mbar         200           200        200          200        200           200        200          200      200          200         200         200        200          200
      Gas flow rate (LHV = 8.83 kWh/m³) m³/h          1177         1128       1184         1135      1299          1250        1404         1356     1188         1139       1287         1238       1397         1349
      Min. gas supply pressure *        mbar          200          200        200          200        200           200         200          200     200          200        200           200       200           200
      Burner:
Oil burner WK(L/MS) 70/3 ZM 70/3 ZM 70/3 ZM 70/3 ZM 70/3 ZM 70/3 ZM 80/3 ZM 70/3 ZM 70/3 ZM 70/3 ZM 70/3 ZM 70/3 ZM 80/3 ZM 70/3 ZM
      Gas burner                         WKG..     70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 80/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 80/3 ZM-NR 70/3 ZM-NR
                                                                                                                     80/4 ZM-VSF                                                       80/4 ZM-VSF
      Dual-fuel burner                   WKGL.. 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 80/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 80/3 ZM-NR 70/3 ZM-NR
                                         WKGMS.. 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 80/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 70/3 ZM-NR 80/3 ZM-NR 70/3 ZM-NR
Air volume m³/h 14000 13500 14000 13500 15500 15000 17000 16000 14000 13500 15500 15000 17000 16000
      Firing rate                        MW          13.9          13.3      13.9          13.4      15.3          14.7       16.5          16.0     14.0         13.4       15.2         14.6       16.5         15.9
      Oil flow rate (LHV=11.86 kWh/kg)   kg/h         1169         1120       1175         1127      1289          1241        1394         1346     1179         1131       1278         1229       1387         1339
      Gas flow rate (LHV =10.35 kWh/m³) m³/h         1339          1284       1347         1291       1477         1422        1598         1542     1351         1295       1464         1409       1590         1534
      Min. gas supply pressure *        mbar          200           200       200          200        200           200         200          200     200           200        200          200        200          200
      Gas flow rate (LHV = 8.83 kWh/m³) m³/h         1570          1505       1578         1513       1732         1667        1873         1808     1583         1518       1716         1651       1863         1798
      Min. gas supply pressure *        mbar         200            200       200          200        250           200        250           250      200         200        250          200         250         250
Burner:
Oil burner WK(L/MS) 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM
      Gas burner                         WKG..     80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR
                                                   80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF
      Dual-fuel burner                   WKGL.. 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR
                                         WKGMS.. 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR
Air volume m³/h 19000 18000 19000 18000 21000 20000 22000 22000 19000 18000 21000 20000 22000 22000
      Firing rate                        MW          17.3          16.6       17.4         16.7      19.1          18.4       20.7          20.0     17.5         16.8       18.9         18.2       20.6         19.8
      Oil flow rate (LHV=11.86 kWh/kg)   kg/h        1461          1400       1469         1408       1612         1551        1743         1682     1474         1413       1597         1537       1734         1674
      Gas flow rate (LHV =10.35 kWh/m³) m³/h         1674          1605       1683         1614       1847         1778        1997         1928     1689         1619       1830         1761       1987         1918
      Min. gas supply pressure *        mbar         250            250        250         250        250          250         250           250      250         250         250         250        250          250
      Gas flow rate (LHV = 8.83 kWh/m³) m³/h         1962          1881       1973         1892       2165         2084        2341         2259     1979         1898       2145         2064       2329         2248
      Min. gas supply pressure *        mbar         300           300        300          300        300          300         500          300      300           300       300          300        500          300
Burner:
Oil burner WK(L/MS) 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM
      Gas burner                         WKG..     80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR
                                                   80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF
      Dual-fuel burner                   WKGL.. 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR
                                         WKGMS.. 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR
Air volume m³/h 24000 23000 24000 23000 26000 25000 28000 27000 24000 23000 26000 25000 28000 27000
*) Total resistance < 30 mbar (boiler, flue-gas heat exchanger, and flue gas system) o. a. = on application Saturated steam Superheated steam
20
                                                                                                                                   Guidelines at 98 % boiler efficiency
                                                 Installation altitude < 500 m, combustion-air temperature < 40 °C
      Firing rate                        MW           20.8          19.9      20.9          20.0      22.9           22.1         24.8          23.9      21.0          20.1     22.7           21.9     24.7          23.8
      Oil flow rate (LHV=11.86 kWh/kg)   kg/h         1753          1680       1763         1690      1934           1861          2091         2019       1768         1696     1917           1844     2081          2008
      Gas flow rate (LHV =10.35 kWh/m³) m³/h          2009          1925      2020          1937       2216          2133         2396          2313       2026         1943     2196           2113     2385          2301
      Min. gas supply pressure *        mbar          300           300       300           300        300           300           300          300        300          300      300            300      300           300
      Gas flow rate (LHV = 8.83 kWh/m³) m³/h          2354          2257      2368          2270      2598           2500         2809          2711       2375         2278     2574           2477     2795          2697
      Min. gas supply pressure *        mbar          500           300        500          500        500           500           500          500        500          500      500            500      500           500
      Burner:
Oil burner WK(L/MS) 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM – – – – 80/3 ZM 80/3 ZM – 80/3 ZM – –
      Gas burner                         WKG..      80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/3 ZM-NR 80/3 ZM-NR 80/5 ZM-VSF 80/3 ZM-NR 80/5 ZM-VSF 80/5 ZM-VSF
                                                    80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF 80/4 ZM-VSF                                             80/4 ZM-VSF 80/4 ZM-VSF           80/4 ZM-VSF
      Dual-fuel burner                   WKGL..  80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR             –             –            –             –      80/3 ZM-NR 80/3 ZM-NR     –       80/3 ZM-NR      –             –
                                         WKGMS.. 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR 80/3 ZM-NR                                                             80/3 ZM-NR 80/3 ZM-NR             80/3 ZM-NR
Air volume m³/h 28000 27000 28000 27000 31000 30000 33000 32000 28000 27000 31000 30000 33000 32000
      Firing rate                        MW           24.3          23.2      24.4          23.4      26.8           25.8         28.9          27.9      24.5          23.5     26.5           25.5     28.8          27.8
      Oil flow rate (LHV=11.86 kWh/kg)   kg/h         2045          1960      2056          1972      2256           2172         2440          2355       2063         1978     2236           2152     2428          2343
      Gas flow rate (LHV =10.35 kWh/m³) m³/h          2343          2246      2356          2259      2586           2489          2796         2699       2364         2267     2562           2465     2782          2685
      Min. gas supply pressure *        mbar          300           300       300           300        500            300          500           500       300          300       500            300     500            500
      Gas flow rate (LHV = 8.83 kWh/m³) m³/h          2747          2633       2762         2648      3031           2917          3277         3163       2771         2657     3004           2890     3261          3147
      Min. gas supply pressure *        mbar          500           500        500           500      500            500           500          500        500          500       500            500     500           500
Burner:
      Gas burner                         WKG..      80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/6 ZM-VSF 80/6 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/6 ZM-VSF 80/6 ZM-VSF
                                                                                                    80/6 ZM-VSF                                                             80/6 ZM-VSF
Air volume m³/h 33000 31000 33000 32000 36000 35000 39000 38000 33000 32000 36000 34000 39000 37000
      Firing rate                        MW           27.7          26.6      27.9          26.7      30.6           29.4         33.1          31.9      28.0          26.8     30.3           29.2     32.9          31.8
      Oil flow rate (LHV=11.86 kWh/kg)   kg/h         2337          2240      2350          2253      2579           2482           –           2692       2358         2261     2556           2459       –           2678
      Gas flow rate (LHV =10.35 kWh/m³) m³/h          2678          2567      2693          2582      2955           2844           –           3084       2702         2591     2929           2818       –           3068
      Min. gas supply pressure *        mbar          500           500        500           500       500            500           –            500       500          500       500           500        –            500
      Gas flow rate (LHV = 8.83 kWh/m³) m³/h          3139          3009       3157         3027       o. a.          o. a.         –            o. a.     3167         3037      o. a.         o. a.      –            o. a.
      Min. gas supply pressure *        mbar          500            500       500           500       o. a.          o. a.         –            o. a.     500           500      o. a.         o. a.      –            o. a.
Burner:
      Gas burner                         WKG..      80/6ZM-VSF 80/5ZM-VSF 80/6ZM-VSF 80/5ZM-VSF 80/6ZM-VSF 80/6ZM-VSF               –       80/6ZM-VSF 80/6ZM-VSF 80/5ZM-VSF 80/6ZM-VSF 80/6ZM-VSF         –       80/6ZM-VSF
                                                               80/6ZM-VSF            80/6ZM-VSF                                                                   80/6ZM-VSF
Air volume m³/h 37000 36000 38000 36000 41000 40000 – 43000 38000 36000 41000 39000 – 43000
*)
     Total resistance < 30 mbar (boiler, flue-gas heat exchanger, and flue gas system)                                        o. a. = on application                     Saturated steam                Superheated steam
                                                                                                                                                                                                                                21
Burner selection based on steam boiler rating
      Steam rate                         t/h                                                                                     15
      Steam pressure                     bar                10                                          16                                                                     25
      Firing rate                        MW        11.3          10.8     11.4         10.9     12.5          12.0       13.5          13.0    11.4          10.9     12.4          11.9     13.4          13.0
      Oil flow rate (LHV=11.86 kWh/kg)   kg/h      954            915     960           920     1053          1013        1139         1099    963           923      1044          1004      1133         1093
      Gas flow rate (LHV =10.35 kWh/m³) m³/h       1094          1048     1100         1054     1207          1161        1305         1259    1103          1058     1196          1151     1298          1253
      Min. gas supply pressure *        mbar        200           200     200           200     200           200          200          200    200            200     200           200       200           200
      Gas flow rate (LHV = 8.83 kWh/m³) m³/h       1282          1229     1289         1236     1414          1361        1529         1476    1293          1240     1402          1349     1522          1469
      Min. gas supply pressure *        mbar       200            200      200          200     200           200          200         200      200           200      200           200      200           200
Burner:
Oil burner WK(L/MS) 70/3 ZM 70/3 ZM 70/3 ZM 70/3 ZM 80/3 ZM 70/3 ZM 80/3 ZM 80/3 ZM 70/3 ZM 70/3 ZM 80/3 ZM 70/3 ZM 80/3 ZM 80/3 ZM
Gas burner WKG.. 70/3 NR 70/3 NR 70/3 NR 70/3 NR 80/3 NR 70/3 NR 80/3 NR 80/3 NR 70/3 NR 70/3 NR 80/3 NR 70/3 NR 80/3 NR 80/3 NR
      Dual-fuel burner                   WKGL..  70/3 NR     70/3 NR     70/3 NR 70/3 NR       80/3 NR       70/3 NR 80/3 NR 80/3 NR 70/3 NR 70/3 NR                 80/3 NR    70/3 NR 80/3 NR        80/3 NR
                                         WKGMS.. 70/3 NR     70/3 NR     70/3 NR 70/3 NR       80/3 NR       70/3 NR 80/3 NR 80/3 NR 70/3 NR 70/3 NR                 80/3 NR    70/3 NR 80/3 NR        80/3 NR
Air volume m³/h 15500 14500 15500 15000 17000 16000 18000 18000 15500 15000 17000 16000 18000 18000
      Firing rate                        MW        15.1          14.5     15.2         14,6     16.7          16.0       18.0          17.4    15.2          14.6     16.5          15.9     17.9          17.3
      Oil flow rate (LHV=11.86 kWh/kg)   kg/h      1272          1220     1280         1227     1404          1351        1518         1465    1284          1231     1391          1339      1511         1458
      Gas flow rate (LHV =10.35 kWh/m³) m³/h       1458          1398     1466         1406     1609          1548        1740         1679    1471          1411     1594          1534      1731         1671
      Min. gas supply pressure *        mbar       200            200      200          200      200           200        250          200     200           200       200           200      250          200
      Gas flow rate (LHV = 8.83 kWh/m³) m³/h       1709          1638     1719         1648     1886          1815       2039          1968    1724          1653     1869          1798     2029          1958
      Min. gas supply pressure *        mbar       250            250     250           250      250          250         300           300    250            250      250          250      300           300
Burner:
Oil burner WK(L/MS) 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM
      Gas burner                         WKG..   80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR
                                                 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF
      Dual-fuel burner                   WKGL..  80/3 NR 80/3 NR         80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR                                       80/3 NR
                                         WKGMS.. 80/3 NR 80/3 NR         80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR                                       80/3 NR
      Combustion air fan:
Air volume m³/h 21000 20000 21000 20000 23000 22000 24000 24000 21000 20000 22000 22000 24000 23000
      Firing rate                        MW        18.9          18.1     19.0         18.2     20.8          20.0       22.5          21.7    19.0          18.2     20.6          19.8     22.4          21.6
      Oil flow rate (LHV=11.86 kWh/kg)   kg/h      1591          1525     1599         1534     1755          1689       1898          1832    1605          1539     1739          1673     1888          1822
      Gas flow rate (LHV =10.35 kWh/m³) m³/h       1823          1747     1833         1757     2011          1936        2174         2099    1839          1763     1993          1918     2164          2088
      Min. gas supply pressure *        mbar       250           250      250          250      300            300        300           300     250          250       300          250      300            300
      Gas flow rate (LHV = 8.83 kWh/m³) m³/h       2136          2048     2148         2060     2357          2269       2549          2460    2155          2067     2336          2248     2536          2448
      Min. gas supply pressure *        mbar       300            300     1000          300     1000          1000       1000          1000    1000          300      1000          1000     1000          1000
Burner:
Oil burner WK(L/MS) 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM - 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM 80/3 ZM - 80/3 ZM
      Gas burner                         WKG..   80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/5 VSF 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/5 VSF 80/3 NR
                                                 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF    80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF 80/4 VSF     80/4 VSF
      Dual-fuel burner                   WKGL..  80/3 NR 80/3 NR         80/3 NR 80/3 NR 80/3 NR 80/3 NR                   -       80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR                     -       80/3 NR
                                         WKGMS.. 80/3 NR 80/3 NR         80/3 NR 80/3 NR 80/3 NR 80/3 NR                   -       80/3 NR 80/3 NR 80/3 NR 80/3 NR 80/3 NR                     -       80/3 NR
Air volume m³/h 26000 25000 26000 25000 28000 27000 30000 29000 26000 25000 28000 27000 30000 29000
*) Total resistance < 30 mbar (boiler, flue-gas heat exchanger, and flue gas system) o. a. = on application Saturated steam Superheated steam
22
                                                                                                                                  Guidelines at 92 % boiler efficiency
                                                 Installation altitude < 500 m, combustion-air temperature < 40 °C
      Firing rate                        MW           22.1           21.2     22.3           21.4     24.4         23.5         26.4           25.5       22.3           21.4     24.2          23.3      26.3           25.4
      Oil flow rate (LHV=11.86 kWh/kg)   kg/h         1867           1790      1878          1800     2060         1983          2228          2150       1884           1806     2042          1964       2217          2139
      Gas flow rate (LHV =10.35 kWh/m³) m³/h          2140           2051      2152          2063     2361         2272          2553          2464       2158           2070     2340          2251      2540           2451
      Min. gas supply pressure *        mbar          300            300       300           300      300          300           500           300        300            300      300           300        500           300
      Gas flow rate (LHV = 8.83 kWh/m³) m³/h          2508           2404     2522           2418     2767         2663         2992           2888       2530           2426     2742          2639      2977           2873
      Min. gas supply pressure *        mbar           500            500      500           500      500           500          500            500        500            500     500            500      500            500
Burner:
      Gas burner                         WKG..      80/5 ZM-VSF 80/3 ZM-NR 80/5 ZM-VSF 80/3 ZM-NR 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/3 ZM-NR 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF
                                                                80/4 ZM-VSF            80/4 ZM-VSF                        80/6 ZM-VSF                        80/4 ZM-VSF                         80/6 ZM-VSF
Air volume m³/h 30000 29000 30000 29000 33000 32000 36000 34000 30000 29000 33000 31000 35000 34000
      Firing rate                        MW           25.8           24.8     26.0           24.9     28.5         27.4         30.8           29.8       26.1           25.0     28.3          27.2      30.7           29.6
      Oil flow rate (LHV=11.86 kWh/kg)   kg/h          2178          2088      2191          2100     2404         2313         2599           2509       2198           2107     2382          2292      2586           2496
      Gas flow rate (LHV =10.35 kWh/m³) m³/h          2496           2393      2510          2407     2754         2651          2978          2875        2518          2415     2730          2626      2963           2860
      Min. gas supply pressure *        mbar           300           300       300           300      500          500           500           500         500           300      500           500        500            500
      Gas flow rate (LHV = 8.83 kWh/m³) m³/h          2926           2805     2942           2821     3228         3107          o. a.          o. a.     2952           2831     3199          3078       o. a.          o. a.
      Min. gas supply pressure *        mbar          500             500      500           500       500         500           o. a.          o. a.      500           500      500           500        o. a.          o. a.
Burner:
      Gas burner                         WKG..      80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/6 ZM-VSF 80/6 ZM-VSF 80/6 ZM-VSF 80/6 ZM-VSF 80/5 ZM-VSF 80/5 ZM-VSF 80/6 ZM-VSF 80/6 ZM-VSF 80/6 ZM-VSF 80/6 ZM-VSF
                                                                                                                                                    80/6 ZM-VSF
Air volume m³/h 35000 33000 35000 34000 38000 37000 41000 40000 35000 34000 38000 37000 41000 40000
      Firing rate                        MW           29.5           28.3     29.7           28.5     32.6         31.4         35.2           34.0       29.8           28.6     32.3          31.1      35.1           33.8
      Oil flow rate (LHV=11.86 kWh/kg)   kg/h         2490           2386     2503           2400        –         2644           –              –         2512          2408       –           2619        –              –
      Gas flow rate (LHV =10.35 kWh/m³) m³/h          2853           2735     2869           2751        –         3030           –              –        2878           2760       –           3001        –              –
      Min. gas supply pressure *        mbar          500            500       500           500         –          500           –              –        500            500        –           500         –              –
Burner:
Gas burner WKG.. 80/6 ZM-VSF 80/6 ZM-VSF 80/6 ZM-VSF 80/6 ZM-VSF – 80/6 ZM-VSF – – 80/6 ZM-VSF 80/6 ZM-VSF – 80/6 ZM-VSF – –
Air volume m³/h 40000 38000 40000 38000 – 42000 – – 40000 38000 – 42000 – –
*)
     Total resistance < 30 mbar (boiler, flue-gas heat exchanger, and flue gas system)                                      o. a. = on application                       Saturated steam                 Superheated steam
                                                                                                                                                                                                                                  23
Correctly sized gas valve trains
save money and trouble
 Low-pressure gas supply
 Rating                                                             FRS regulator PE <300 mbar                                         SKP25 regulator PE <360 mbar
                                                                    Gas shut-off valve assembly                                        Gas shut-off valve assembly
                                                                    DMV - Dungs            VGD - Siemens                               VGD - Siemens
             • The overall resistance (combustion chamber and flue gas resistance) in mbar must be added to the minimum gas pressure determined from the above chart.
 ATTENTION
  NOTE
24
High-pressure gas supply
 Rating                                                           High-pressure regulator PE 500 - 4000 mbar 1)
                                                                  Gas shut-off valve assembly
                                                                  DMV - Dungs                                            VGD - Siemens
OF = Burner rating, PE = Pressure before ball valve, PA = Regulated gas pressure, o. a. = on application
PE / PA see page 28/29, 1) See accessories list for special 0.5-4/5/10 bar regulators and spring selections >240 mbar
• See planning handbook for LPG selection values up to 22 MW.
                                                                                                                                                             25
Fuel systems
Oil burners
 WKL40, integral pump                                        WKMS40, integral pump and preheater
13 3 6 8 2 13 3 4 10 6 8
P P
                                                115V
                                                                                                               115V
                                                                                230V
                            115V                                                           115V
                                    P       M                                                      P       M
M 9 7 12 11 M 9 7 12 5 11
1 1
3 6 8 2 3 4 10 6 8
P P
                                                 115V
                                                                                                                115V
                                                                                 230V
                             115V                                                          115V
                                    P        M                                                     P       M
     M                                                         M
                              9     7       12          11                                     9   7       12 5        11
1a 14 1a 14
26
WKL multiflam®                                                                   Light-oil ignition burner, WKMS 80
14 3 6 8 8 11b 6 8 8 11b
P P
115V 115V
                            115V 115V
                                           P         M
                                                                                  M
     M
                                                                                       1             13              26
1a 14 9 9 7 12 11a
15 16 17 18 19 24 20 23 25
                                                                                 1     Oil pump
     LPG LPG LPG
                                                                                 1a    External pump station with pressure maintenance
                                               26                                2     Oil preheater
                                                                                 3     Strainer
Oil-firing burner with gas ignition                                               4     Temperature sensor in supply
                                                                                 5     Temperature sensor in return
                                                                                 6     Low-pressure switch
                                                                                 7     High-pressure switch
                                                                                 8     Solenoid valve in supply (fitted in the direction of flow)
LPG ignition burner, WKMS 80                                                     9     Solenoid valve in return (fitted against the direction of flow)
                                                                                 10    Bypass solenoid valve (normally open)
                                                                                 11    Solenoid valve assembly
15                     16       17 18 19            20 21            22   25     11a   Nozzle head with secondary nozzles
                                                                                 11b   Nozzle head with primary nozzle
                                                      P P                        12    Oil regulator
                                                                                 13    Pressure regulating valve
                                                                                 14    Filter
                                                                                 15    LPG bottle (supplied by others)
                                                                                 16    LPG pressure regulator (accessory)
                                                                                 17    Hose rupture protection (accessory)
     LPG                                                                         18    Ball valve
                                                                                 19    Pressure gauge with push-button valve
                                               26
                                                                                 20    Low-gas-pressure switch
Oil-firing burner with gas ignition                                               21    High-gas-pressure switch
                                                                                 22    W-MF multi-function assembly
                                                                                 23    DMV gas solenoid valve assembly
                                                                                 24    FRS gas pressure regulator
                                                                                 25    Burner
                                                                                 26    Sub-assembly fitted to burner at works
                                                                                                                                                         27
Fuel systems
Gas and dual-fuel burners
                                                                                                                                                                               Gas side, WKG(L) 40 – 80, WKGMS 40 – 70
                                                                                        A                                B                        C                            Versions ZM / NR / 1LN / 3LN / 1SF / VSF
                                                        Gas shut-off assembly type
                                                                                                                                                                                             9b                                     9b            10        11
                                                                                                                                               High-pressure regulator
                                                                                                                                               High-pressure supply with
                           Nominal valve train size
FRS governor
                                                                                                                                                                           A        PE                                   PA
                                                                                                                   assembly
                                                                                                                                                                                                                    P              PP         P
 40 50 70 80
                                                                                                                                                 PE                                      1    2                 3a 4a              4b 5       6 7              8
                                                                                      PE                               PE
                                                                                                                                               > 300-
                                                                                     ≤ 300                            ≤ 360
                                                                                                                                                4000
                                                                                     mbar                             mbar
                                                                                                                                               mbar 1)
                                                                                                                       PA                        PA
                                                                                      PA
                                                                                                                      ≤ 250                    ≤ 210 /
                                                                                     ≤ 200
                                                                                                                      mbar                    240 mbar
                                                                                                                                                                               Gas side, WKG(L) 80
                                                                                     mbar                                    2)                         1)                     Versions NR / 3LN / 1SF / VSF
                                                                                                                                                                                             9b                                     9b            10        11
                         1 1/2“
                                                       W-MF
                                                        512
                                                                                           l                                                         l
                                                       DMV                                 l                                                         l
                           2“
                                                      525/12
                                                                                                                                                                           B        PE                                                                    PA
                         DN 65
                                                       DMV
                                                      5065/12
                                                                                           l                                                         l                                                                              P         P        PP
1 2 5 6 7 3a 4d 5 8
                         DN 80
                                                       DMV
                                                      5080/12
                                                                                           l                                                         l
                                                                                                                                                                               2)
                                                                                                                                                                                    Spring for PA > 250 mbar on application
9a 9a 10 11
                         DN 125
                                                       VGD
                                                      40.125
                                                                                           l                               l                         l
                         DN 150
                                                       VGD                                 l                               l                         l
                                                                                                                                                                           C        PE                                        PA
                                                      40.150
 l   Standard
                                                                                                                                                                                         1    2               3b        4c          5         6    7           8
 l   Optional SKP25 regulator for burner type WK 80, including
     stabilisation section (suitable for horizontal burner installations only)
                                                                                                                                                                               1)   See accessories list for special 0.5-4/5/10 bar regulators and spring selections > 240 mbar
28
Gas side, WKG 40 – 70                                                                                  Gas side, WKGMS 80 3) Versions ZM / NR / 1SF
Version LN
                                                                                                             15              12        13 1    9a        4e 5                   14   11
9a 9b 11 P P
                                                                                                                                                    16                      14
                                                                                                                  LPG
 PE                                   PA
                                                                                                                      9b
                                                                                                        PE                                     PA                 V1       V2
                                P                 PP                  P
       1          2        3a 4a                  4b 5                6    7             8
                                                                                                                                                            PP         P
1 2 3a 4b 5 6 7 8
                                                                                                        Compensator
                                                                                                        To enable a tension free mounting of the valve train, the fitting of a compensator is
 PE                                                   PA              V1       V2                       recommended.
                                                                                                                                                                                               29
Key dimensions at a glance
     Ambient combustion air (ZM...)
                                                             l3
                                                                                                h3
                                                 G 3/4“
                                                                  DN                    h1 h2
                     60            ZM-..
                                                                  l2
                                                   l1
     Optional
                                                                                                                                     l6
     compensator                                                                                                          l4              l5
                                             l9 l10
                                     l7
                                     l8
h3
               l11
                                           l12
     120                  ZMH-..
                                                                                         Ø90
                     l13                                                     l14
     Type       DN          l1       l2     l3          l4             l5          l6      l7        l8    l9       l10        l11    l12      l13   l14   h1    h2    h3
     WK.. 40    65          388      116    116         313            340         140     226       336   264      368        452    1046     231   255   444   384   400
     WK.. 50    80          528      158    158         373            404         165     270       403   370      495        452    1212     258   311   518   464   540
     WK.. 70    100         730      188    313         454            466         205     418       548   500      630        650    1689     300   360   628   589   700
     WK.. 80    150         1023     368    522         486            524         283     556       670   556      670        697    2124     393   410   708   741   850
Weishaupt reserve the right to make changes in light of future developments. Additional burner dimensions and oil-side connection details are available on request.
30
Heat-exchanger mounting
                                                                                    Typ             Ausf.                  d1    d2      d3    l15 1)
             l15                                                                    WK.. 40/1       ZM(H)                  250   280     290   260
                                60°-90°                                             WK.. 40/2       ZM(H)                  261   280     290   260
                                                                                    WK.. 40/2       ZM(H)-LN               296   280     290   424
       The space between the combustion head and the refractory                     WK.. 70/1       ZM(H)-NR               400   518     530   347
       should be filled with a resiliant, non-solid insulating material,            WK.. 70/2       ZM(H)-NR               480   518     530   362
       such as Cerafelt.
                                                                                    WK.. 70/3       ZM(H)-NR               480   518     530   462
                                                                                    WKG 70/1        ZM(H)-LN               406   518     530   457
Maintenance-friendly combustion head:                                               WKG(L) 70/1     ZM(H)-1LN              406   518     530   439
On all burner versions, the standard-length combustion head can be inserted
                                                                                    WKG(L) 70/2     ZM(H)-LN/ZM(H)-1LN     480   518     530   477
and withdrawn through the service opening in the burner housing.
                                                                                    WKG(L) 70/1     ZM(H)-3LN              444   518     530   475
                                                                                    WKG(L) 70/3     ZM(H)-3LN              480   518     530   475
                                                                                    WK.. 70/1       ZM(H)-1SF              400   518     530   347
                                                                                    WK.. 70/2       ZM(H)-1SF              480   518     530   362
                                                                                    WKL(MS) 70/1    ZM(H)                  400   518     530   417
                                                                                    WKL(MS) 70/2    ZM(H)                  480   518     530   422
                                                                                                                                               °
                                                                                                            30
                                                                                                                                               30
                                                                              245
                                  180
3 0°
                                                                                                                                                    3 0°
                                                 270
       200
3 0°
3 0°
WK 40 WK 50 WK 70 WK 80
                                                                                                                                                           31
Overview of options, installation
positions, and weights
Vertically firing Weishaupt burners have been
especially designed for use on vertical plant,
such as steam boilers, thermal fluid heaters,
                                                        Vertical execution
                                                                                                                          l18
and process applications.
                                                                                                         h6
                                                                                                              h4
                                                                                                                                 l16
                                                                                                                          l19
                                                           Optional
l18
133
h5
h6
                                                                                                                          l17
                                                           Optional                                                 l20
                                                           Extended option (with accessory components)
32
Vertical-execution dimensions
            Burner flange to butterfly       Gas valve assembly
            valve outlet DN                DN                           l16 1)        l17           l18         l19 1)     l20       h4          h5         h6
WK.. 40     65                             1 1/2"                       492           686           641         841 2)     1035 2)   116         502        382
                                           2"                           492           686           641         881 2)     1075 2)   116         502        382
                                           65                           492           686           641         784        978       116         502        382
                                           80                           492           686           641         991 2)     1185 2)   124         510        382
                                           100                          -             686           641         -          1237 2)   -           521        382
                                           125                          -             686           641         -          1317 2)   -           533        382
WK.. 50     80                             2"                           469           801           697         858 2)     1190 2)   158         594        424
                                           65                           469           801           697         948 2)     1280 2)   165         601        424
                                           80                           469           801           697         781        1113      158         594        424
                                           100                          469           801           697         1030 2)    1362 2)   169         605        424
                                           125                          469           801           697         1105 2)    1437 2)   181         617        424
WK.. 70     100                            65                           589           1001          760         1080 2)    1492 2)   207         723        579
                                           80                           589           1001          760         1110 2)    1522 2)   199         715        579
                                           100                          589           1001          760          941       1353      188         704        579
                                           125                          589           1001          760         1227 2)    1639 2)   201         717        579
                                           150                          589           1001          760         1320 2)    1732 2)   215         731        579
WK.. 80     150                            100                          522           976           815         1123 2)    1577 2)   395         1121       788
                                           125                          522           976           815         1176 2)    1630 2)   382         1108       788
                                           150                          522           976           815         1004       1458      368         1094       788
1) Including horizontal intermediate flange (not shown) 2) Including concentric reducer (not shown)
3) Burner-mounted oil pump 4) Burner-mounted oil preheater 5) Separate oil pump 6) Separate oil preheater
                                                                                                                                                                  33
Combustion test chamber at the
Schwendi Research & Development Institute
34
35
                                                                                           Max Weishaupt GmbH
                                                                                           88475 Schwendi
                                                                                           Tel +49 7353 830
                                                                                           Fax +49 7353 83358
                                                                                           www.weishaupt.de