DC48 Specs
DC48 Specs
4600 Campus Place • Mukilteo, WA 98275 • (425) 349-3500 • Fax (425) 349-3667
AC-DC
400-2400 Watts xppower.com
fleXPower Series
• Industrial/IT & Medical Approvals
• -20 ºC Operation
Specification
Input General
Input Voltage • 85-264 VAC (120-370 VDC). Full power at Efficiency • 83.5% typical at 115 VAC
90 VAC, derate by 10% at 85 VAC Isolation • 4000 VAC Input to Output
Input Frequency • 47-63 Hz, 400 Hz (unit meets all specs at 1500 VAC Input to Ground
400 Hz, except leakage current) 250 VDC Output to Ground
Input Current(1) • X4: 5.33 A at 115 VAC, 2.67 A at 230 VAC Switching Frequency • 60 kHz typ PFC, 200 kHz typ modules
X5: 6.67 A at 115 VAC, 3.33 A at 230 VAC Signals • See chassis & module signals pages
X7: 9.33 A at 115 VAC, 4.67 A at 230 VAC MTBF • 225 kHrs to MIL-HDBK-217F at +25 ºC
X9: 12.0 A at 115 VAC, 6.00 A at 230 VAC
X10: 13.3 A at 115 VAC, 6.67 A at 230 VAC Environmental
Inrush Current(1) • X4, X5, X7: <20 A, X9/X10: <40 A
Operating Temperature • -20 ºC to +70 ºC. For operation above
Power Factor • 0.99 typical at 115 VAC & 230 VAC +50 ºC, derate linearly to 50% load
full load at +70 ºC. Reverse air option derate from
Earth Leakage Current(1) • X models <1.5 mA at 264 VAC, 50 Hz +40 ºC to half load at +60 ºC
XM models <200 µA at 264 VAC, 50 Hz Cooling • Forced air cooling (via field-replaceable
Input Protection • Dual fusing, line & neutral internal fan)
Operating Humidity • 5-95% RH, non-condensing
Output Storage Temperature • -40 ºC to +85 ºC
Output Power • See tables. Chassis can deliver an extra Operating Altitude • 3000 m at full specification
200 W at high line (180-264 VAC) Shock • MIL STD-810 Method 516.4 Procedure 1,
Output Voltage • See table 30 g, half sine, 6 axis
Output Voltage Trim • ±10% Vibration • MIL STD-810 Method 514.4 Procedure 1,
Minimum Load • No min load required for 2 slot or 3 slot 1 g rms, 5-500 Hz, 3 axis
single output modules. 2 slot dual outputs
require 10% load on V1 to meet specified EMC & Safety
regulation on V2 output Emissions • X version: EN55022 (CISPR22) Class B
Start Up Delay • 2 s max conducted
Hold Up Time • 20 ms from 90 VAC input & full output load XM version: EN55011 (CISPR 11) Class A
Line Regulation • <0.1% conducted
Load Regulation • <1.0% Immunity • EN60601-1-2, EN61204-3
Ripple & Noise • 50 mV or 1% pk-pk at 20 MHz BW, Harmonic Currents • EN61000-3-2
whichever is greater Voltage Flicker • EN61000-3-3
Overvoltage Protection • 115-130% Vnom ESD Immunity • EN61000-4-2, level 4 Perf Criteria A
Overtemperature • 115 ºC measured internally, Radiated Immunity • EN61000-4-3, 10 V/m Perf Criteria A
Protection recycle mains to reset EFT/Burst • EN61000-4-4, level 3 Perf Criteria A
Overload Protection • 110-140% Surge • EN61000-4-5, level 3 Perf Criteria A
Short Circuit Protection • Continuous Conducted Immunity • EN61000-4-6, level 3 Perf Criteria A
Temperature • 0.03%/ºC Dips & Interruptions • EN61000-4-11, 30% 10 ms, 60% 100 ms,
Coefficient 100% 5000 ms, Perf Criteria A, B, B
Remote Sense • Compensates for up to 0.5 V drop Safety Approvals • EN60950-1, UL60950-1, CSA22.2 No.
Enable/Inhibit • See chassis signals page 60950-1-03, EN60601-1, UL60601-1,
Current Share • See module signals page SEMI F47
Note
Housekeeping Voltage • 5 V/1 A from each chassis
1. Current specifications double for DD chassis versions.
AC-DC
Configuration - Model Number Construction fleXPower
The fleXPower range allows for simple configuration of a custom modular power supply with up to fourteen outputs. The chassis con-
sists of either ten, twelve or fourteen slots, and modules are either two or three slots wide.
CHASSIS OUTPUT MODULES 1-5 (1-6: 900 W chassis/ 1-7: 1000 W chassis) OPTIONS
MOD. 1 MOD. 2 MOD. 3 MOD. 4 MOD. 5 MOD. 6 MOD. 7
X X X - - P P S S + +
Chassis Designations, Power & sizes Single Output - Module Voltage/Current Rating Parallel Option Codes
Code Power Slots Voltage Current Slots Code Code Description
X4 400 W Industrial 10 3.3 V 40.0 A 2 2C 00 No parallel required
X5 500 W Industrial 10 3.3 V 60.0 A 3 3C 12 Modules 1 & 2
X7 700 W Industrial 10 5.0 V 40.0 A 2 2D 13 Modules 1 to 3
X9 900 W Industrial 12 5.0 V 60.0 A 3 3D 14 Modules 1 to 4
X10 1000 W Industrial 14 12.0 V 17.0 A 2 2J 23 Modules 2 & 3
XM4 400 W Medical 10 12.0 V 25.0 A 3 3J 24 Modules 2 to 4
XM5 500 W Medical 10 15.0 V 14.0 A 2 2L 25 Modules 2 to 5
XM7 700 W Medical 10 15.0 V 20.0 A 3 3L 34 Modules 3 & 4
XM9 900 W Medical 12 24.0 V 10.5 A 2 2P 35 Modules 3 to 5
XM10 1000 W Medical 14 24.0 V 17.0 A 3 3P 40 Modules 1 & 2, 3 & 4
28.0 V 9.0 A 2 2Q
Power increases by 200 W at high line
(180-264 VAC). 28.0 V 14.0 A 3 3Q Series Option Codes
36.0 V 7.0 A 2 2U Code Description
36.0 V 11.0 A 3 3U 00 No series required
48.0 V 5.2 A 2 2W 12 Modules 1 & 2
Step 1
48.0 V 8.5 A 3 3W 13 Modules 1 to 3
To configure your fleXPower unit,
60.0 V 4.2 A 2 2Y 23 Modules 2 & 3
select the required output power
60.0 V 7.0 A 3 3Y 24 Modules 2 to 4
and application type. fleXPower
40 Modules 1 & 2, 3 & 4
chassis are available in five industrial
Dual Output - Module Voltage/Current Rating
and five medical power formats,
Output 1 Output 2 Other Option Codes
detailed above. Slots Code
Voltage Current Voltage Current Code Description
5.0 V 10.0 A 5.0 V 10.0 A 2 5A 01 Reverse Air
Step 2 5.0 V 10.0 A 3.3 V 10.0 A 2 5B 02 Global Enable - Logic 1
fleXPower can accommodate up to 12.0 V 10.0 A 12.0 V 8.0 A 2 5D 03 Option 01 & 02
seven modules, resulting in an 15.0 V 8.0 A 15.0 V 6.0 A 2 5E 04 Global DC OK - Logic 1
extensive range of output combina- 15.0 V 8.0 A 12.0 V 8.0 A 2 5F 05 Option 01 & 04
tions. However, as all modules are 12.0 V 10.0 A 5.0 V 10.0 A 2 5G 06 Option 02 & 04
designed to fit across either two or 12.0 V 10.0 A 3.3 V 10.0 A 2 5H 07 Option 01, 02 & 04
three slots in the chassis, configura- 12.0 V 10.0 A 2.0 V 10.0 A 2 5J 08 Global AC OK - Logic 1
tion is very simple. Select the appro- 15.0 V 10.0 A 5.0 V 10.0 A 2 5K 09 Option 01 & 08
priate modules for your output 15.0 V 10.0 A 3.3 V 10.0 A 2 5L 10 Option 02 & 08
requirements, ensuring that all mod- 15.0 V 10.0 A 2.0 V 10.0 A 2 5M 11 Option 01, 02 & 08
ules will fit in the chassis. Insert 24.0 V 6.0 A 5.0 V 10.0 A 2 5N 12 Option 04 & 08
three-slot modules first, then the 24.0 V 6.0 A 3.3 V 10.0 A 2 5P 13 Option 01, 04 & 08
lowest voltage for same module 24.0 V 6.0 A 2.0 V 10.0 A 2 5Q 14 Option 02, 04 & 08
width. Follow with 2 slot single out- 24.0 V 6.0 A 12.0 V 6.0 A 2 5T
put, lowest voltage to highest volt- 15 Option 01, 02, 04 & 08
age, then 2 slot multi output,
ordered alphabetically a-z.
Step 3
Add any required options. These are grouped into three types; parallel options, series options and other options. The standard signal set
for each chassis includes Global Inhibit, Global DC OK and Global AC OK, each having logic 0 operation. Optionally a logic 1 operating
version of each is available along with reverse air flow.
Example X7-3C3L2C-0023
X7 - 700 W industrial chassis, 10 module slots available.
3C - 3.3 V @ 60.0 A. Three slot width module.
3L - 15.0 V @ 20.0 A. Three slot width module.
2C - 3.3 V @ 40.0 A. Two slot width module.
00 - No parallel option.
23 - Modules 2 and 3 in series to give 18.3 V @ 20.0 A.
AC-DC
Signals fleXPower
POWER SUPPLY
5 V Standby
Pin 7
3300R
5 V Standby
Return Pin 8
Chassis J2 Logic Connector
POWER SUPPLY
5 V Standby
Pin 7
3300R
Global DC OK
Global DC OK is an open collector signal providing DC OK Collector
warning that the output voltage has fallen below Pin 4
90% of nominal. The signal is fully isolated and the Standard Logic 0
collector and emitter must be connected externally. Transistor On (<0.8 V): DC OK
Transistor Off (>4.5 V): DC NOT OK
DC OK Emitter
Maximum sink current 2 mA, maximum voltage 20 V. Pin 3
Optional Logic 1
Transistor Off (>4.5 V): DC OK
Transistor On (<0.8 V): DC NOT OK
On Dual output module, DC OK monitors V1
output only 5 V Standby
Return Pin 8
Chassis J2 Logic Connector
800R
POWER SUPPLY
5 V Standby
Pin 7
5 V Standby
Return Pin 8
Module DC OK 1K Ohm
Collector Pin 8
Module Inhibit
Pin 6
Current Share
Connecting pins 2 and 4 of like voltage modules (4 maximum) within the
Module 1 Module 2 Module 4
same chassis or separate chassis will force the current to share between
the outputs. Different slot width modules can share.
Single Output
0.425
0.691 (10.8)
(17.55)
Notes Notes
1. All dimensions in inches (mm). 1. All dimensions in inches (mm).
2. Weight: 0.48 lb (218 g) approx. 2. Weight: 0.74 lb (335 g) approx.
3. Mating plug: JST p/n PHDR-10VS. 3. Mating plug: JST p/n PHDR-10VS.
4. Contact: 26-22 AWG JST p/n SPHD-001T-P0.5. 4. Contact: 26-22 AWG JST p/n SPHD-001T-P0.5.
Dual Output
2 Slot Modules
Mechanical
Chassis Details Details
Mechanical fleXPower
800 (1200) (4) Watt X4DD & XM4DD Chassis
1000 (1400) (4) Watt X5DD & XM5DD Chassis
Weight: 5.5 lb (2500 g) approx.
1400 (1800) (4) Watt X7DD & XM7DD Chassis
10.00 (254.0)
5V STANDBY AND LOGIC CONNECTORS 1.50
8.20 (208.3)
0.10 (2.5) (38.1)
TYP 4X M4 X 0.7 THD EACH P/S IS SHOWN WITH 2-SLOT-WIDTH
0.15 (3.8) MAX SCREW PENETRATION MODULE FOR REFERENCE
.75
2 10
2 10
1 9
1 9
(19.1)
J2
J2
3.50 5.20
(88.9) AIRFLOW (132.1)
N
N
J1
J1
L
1.50 (38.1)
8.20 (208.3)
0.75
(19.1)
2 10
2 10
1 9
1 9
J2
J2
6.20
4.50
(157.5)
(114.3) AIRFLOW
N
N
J1
J1
L
1.50
AC INPUT TERMINAL BLOCKS 8.20 (208.3)
(38.1)
(PARALLEL CONNECTED)
6-32 HARDWARE, 0.375 (9.52) 1.25
CENTERS (31.7) Weight: 6.6 lb (3000 g) approx.
2.50
(63.5)
5.00
(127.0)