A B C A B C General Notes: Lighting Layout Power Layout

The document outlines the electrical specifications and requirements for a proposed one-storey residential building, adhering to the Philippine Electrical Code and local ordinances. It details the necessary wire sizes, circuit specifications, mounting heights for switches and outlets, and mandates that all electrical work be supervised by a registered electrical engineer. Additionally, it includes a lighting layout and a schedule of loads for the electrical system.

Uploaded by

ging-ging salva
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
83 views1 page

A B C A B C General Notes: Lighting Layout Power Layout

The document outlines the electrical specifications and requirements for a proposed one-storey residential building, adhering to the Philippine Electrical Code and local ordinances. It details the necessary wire sizes, circuit specifications, mounting heights for switches and outlets, and mandates that all electrical work be supervised by a registered electrical engineer. Additionally, it includes a lighting layout and a schedule of loads for the electrical system.

Uploaded by

ging-ging salva
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

GENERAL NOTES

A B C A B C
5.75M 5.75M ALL ELECTRICAL WORKS SHALL BE DONE
IN ACCORDANCE WITH THE PROVISIONS OF
THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE AND EXISTING LOCAL
2.88M 2.88M 2.88M 2.88M
ORDINANCES AND REQUIREMENTS OF THE
LOCAL POWER THE CONTRACTOR
1.72M 1.72M COMPANY. SHALL VERIFY AND ORIENT THE
CONNECTION OF THE EXISTING FEEDER
LINES.THE TYPE OF POWER SUPPLY SERVICE
SUPPLY SHALL BE SINGLE PHASE- TWO WIRE
1 1 PB 220 VOLTS AND 60 HERTZ AC. UNLESS OTHER
WISE SPECIFIED THE MINIMUM SIZE OF WIRE
AND CONDUIT TO BE USED SHALL 3.5MM SQ.
TW AND 15MM DIAMETER RESPECTIVELY.
2
3.75M

3.75M

3.75M

3.75M
ALL LIGHTING CIRCUIT, HOMERUNS AND
CONVENIENCE OUTLETS SHALL BE WIRED WITH
1 NOT LESS THAN 3.5 MM SQ. IN SIZE. ALL 20
AMPERES CIRCUIT HOME RUNS TO PANEL BOARD
MORE THAN 30 METERS IN LENGTH SHALL BE
WIRE WITH 5.5 MM TW IN SIZE UNLESS
s1
2 2 OTHERWISE INDICATED. ALL ELECTRICAL
MATERIALS TO BE USED SHALL BE NEW AND OF
APIPEOVED TYPE FOR THE LOCATION AND
2.88M 2.88M 2.88M 2.88M PURPOSE. STANDARD TYPE OF ACCESSORIES,
SPLICING DEVICES, TERMINATION AND OTHER
APPURTUNANCES FOR THE ENTIRE
ELECTRICAL INSTALLATIONS SHALL BE USED.
5.75M 5.75M
MOUNTING HEIGHTS:
USE 2- NO.12 (3.5mm² )THW STRANDED
AT 1/2 " Ø RSC PIPE
a) WALL SWITCHES - - - - - - - - - - - - - - -1.20M
ABOVE FINISHED FLOOR LINE
E LIGHTING LAYOUT FROM MAIN
PANEL BOARD 30A 15 A
E POWER LAYOUT b) CONVENIENCE OUTLET - - - - - - - - - - 0.30M
ABOVE FINISHED FLOOR LINE
1 1 SCALE 1:100 M MAIN M
20 A -
1 L.O
2 1 SCALE 1:100 M c) AIRCONDITIONING UNIT OUTLET - - - AT
CONVENIENCE HEIGHT NEAR THE
C.O 2 3 SPARE
- EQUIPMENT
SPARE 4 d) PANEL BOARD - - - - - - - - - - - - - - - --1.82 M
FROM TOP OF PANEL TO THE FINISH
FLOOR LEVEL ALL ELECTRICAL WORKS
LIGHTING PANEL
SHALL BE DONE UNDER THE DIRECT
SPECIAL POWER OUTLETS
6 HOLES PANEL BOARD SUPERVISION OF A DULY REGISTERED

GROUND
E RISER DIAGRAM ELECTRICAL ENGINEER.

LIGHTING PANEL BOARD - LPB


3 1 SCALE 1:100 M

SCHEDULE OF LOAD
SWITCH NO OF CIRCUIT
MARK DESCRIPTION VOLTS WATTS AMPERE
S1 S2 S3 OUTLETS BREAKER SIZE OF CONDUCTOR AND CONDUITS

ELECTRICAL ENGINEER REG.NO: PROJECT TITLE OWNER SHEET CONTENT: DRAFTED BY: ADDEENDUM SHEET NO.
VALIDITY:
TIN NO.:: PROPOSED CONSTRUCTION OF (1) STOREY
ENGR. PTR NO.: RESIDENTIAL BUILDING RITA GACITA
MRS. AURORA LACABA TAN ·
·
ELECTRICAL LAYOUT
SCHEDULE OF LOADS
JOE ARTH E. SALVA E-1-1
DATE ISS.: REVISED: 05- 05