Reg-D, Pan-D
Reg-D, Pan-D
REGSysTM
(REG-D, PAN-D)
1 Wall-mounting housing
1 Panel-mounting housing
1 Plug-in module
Issue 05/2013
                                                                                                                    g
We take care of it.
Page 2                                                                                                        REGSysTM
Page 2
3.1 Regulator mode                                         Case             REG-D
                                                                                   TM
                                                                                          Conditions
                                                                            program
The actual value and a fixed or load-dependent
setpoint value are continually compared in the             free feed in     Δ cos ϕ       Any transformer, any
regulator, which then determines the correct                                              tap size
commands for the transformer's tap changer. The            Emergency        Δ cos ϕ       Any transformer, any
regulator's parameters can be fine-tuned to the            program in the                 tap size;
dynamic time behaviour of the grid voltage to obtain       event of an                    for the programs ΔI
high control performance for a low number of               ELAN failure                   sin ϕ and ΔI sin ϕ (S)
switching operations.
                                                          Table 1 Parallel operation of transformers
                  Master-        Identical
                  Follower       transformers,
                                 identical tap steps
REGSysTM                                                                                                  Page 3
                                                                                                          Page 3
We take care of it.
Page 4                                                                                               REGSysTM
Page 4
As shown in the graphic, both transformers A: and C:
are working on busbar '3', while transformer B: is       3.7 PAN-D Monitoring unit
feeding into busbar '4'.
                                                         The PAN-D monitoring unit is normally assigned to a
                                                               TM
                                                         REG-D and is connected via the E-LAN bus. When
3.6 Transformer monitoring module                        used in stand-alone mode, the PAN-D unit is used
    TMM                                                  without bus connection and is thus a fully
                                                         autonomous add-on monitoring unit.
The Transformer Monitoring module collects and
calculates information about the condition of the
transformer and tap changer.
The hot-spot temperature is calculated in accordance
with IEC 60354 and IEC 60076, and is used to
determine the transformer’s loss of life.
Up to 6 groups of fans and 2 oil pumps can be
controlled to regulate the temperature of the
transformer. The operating times of the fans and
pumps are stored for maintenance purposes.
Oil temperature is measured either directly as a PT100
input or via a mA transducer, and also be recorded
using the Recorder mode.
A total of three analogue input slots are available in
            TM
the REG-D , allowing the monitoring of several
temperatures, oil levels, gas levels, and so on.
Please refer to characteristic group 'E' in the Order
specifications for a list of the combination options.
                                                         The parameters for the PAN-D monitoring unit are set
                                                         either directly through the unit's interface or by using
                                                         the keyboard and display of the regulator.
REGSysTM                                                                                                Page 5
                                                                                                        Page 5
We take care of it.
Page 6                                                                                                   REGSysTM
Page 6
 Binary inputs (BI) *)                                  Binary outputs (BO) *)
 Common                                                 max. switching         ≤ 1 Hz
 Shape of the curve,      Rectangular, sinusoidal       frequency
 permissible
                                                        Potential isolation      Isolated from all internal
 Signal frequency         DC, 40 ... 70 Hz
                                                                                 device potentials
 Potential isolation      Optocoupler; all inputs
                                                        Contact load             AC: 250 V, 5 A (cosϕ = 1.0)
                          galvanically isolated from
                                                                                 AC: 250 V, 3 A (cosϕ = 0.4)
                          each other
                                                                                 Switching capacity max.
 Anti-bounce filter       Software filter, with
                                                                                 1250 VA
                          50Hz AC input filter
 Characteristic D1 - Inputs E1 ... E8                                            DC: 30 V, 5 A resistive
 Control signals Ust      AC/DC
                                                                                 DC: 30 V, 3.5 A L/R=7 ms
                          range 48 V ... 250 V
                                                                                 DC: 110 V, 0.5 A resistive
 H - Level                ≥ 48 V
                                                                                 DC: 220 V, 0.3 A resistive
 L - Level                < 10 V
                                                                                 Switching capacity
 Input resistance         108 kΩ
                                                                                 max. 150 W
 Characteristic D1 - Inputs E9 ... E16
 Control signals Ust      AC/DC                         Inrush current           250 V AC, 30 V DC
                          range 10 V ... 50 V                                    10 A for max. 4 s
                                                                                        5
 H - Level                ≥ 10 V                        Switching operations     ≥ 5·10 electrical
 L - Level                <5V
 Input resistance         6.8 kΩ                        Analog/Digital Conversion *)
 Characteristic D2 - Inputs E1 ... E16                  Type                   12 bit successive-
 Control signals Ust      AC/DC                                                approximation converter
                          range 48 V ... 250 V,         A/D bit resolution     +/- 11 bit
 H - Level                ≥ 48 V                        Sampling rate          24 samples per period, e.g.
 L - Level                < 10 V                                               1.2 kHz at a 50Hz signal *
 Input resistance         108 kΩ                       *The measurement inputs are equipped with an Anti-
 Characteristic D3 - Inputs E1 ... E16                 Aliasing filter.
 Control signals Ust      AC/DC
                          range 10 V ... 50 V           Device real time clock *)
 H - Level                ≥ 10 V                        Accuracy                 +/- 20 ppm
 L - Level                <5V
 Input resistance         6.8 kΩ                        Limit value monitoring *)
 Characteristic D4 - Inputs E1 ... E16                  Limit values            programmable
 Control signals Ust      AC/DC                         Response times          programmable
                          range 80 V ... 250 V
                                                        Alarm indicators        LED programmable
 H - Level                ≥ 80 V
 L - Level                < 40 V
 Input resistance         108 kΩ
 Characteristic D5 - Inputs E1 ... E16
 Control signals Ust      AC/DC
                          range 190 V ... 250 V
 H - Level                ≥ 176 V
 L - Level                < 88 V
 Input resistance         108 kΩ
REGSysTM                                                                                               Page 7
                                                                                                       Page 7
We take care of it.
Page 8                                                                                                        REGSysTM
Page 8
 Test voltages *)                 Description                  Test voltage / kV               counter circuit*
 Binary inputs                          BI                             2.3                     BI
 Binary inputs                          BI                             2.3                     BO
 Binary outputs                        BO                              2.3                     BO
*Counter circuits are always at the rack potential.
All test voltages are AC voltages in kV, which may be applied for 1 minute.
The COM interfaces are tested against each other with 0.5 kV.
 Function (Housing)               -10 °C ... +50 °C                  Other data and          SDRAM, battery-backed
                                                                     recorder data           (plug-in lithium battery),
 Function (plug-in module)        -10 °C ... +60 °C                                          Backup to flash memory possible
 Transport and storage            -25 °C ... +65 °C                  Characteristic S1
 Dry cold                         IEC 60068-2-1,
                                  - 10°C / 16 h
 Dry heat                         IEC 60068-2-2,
                                                                    5. Mechanical design
                                  + 55°C / 16 h                      Plug-in module *)
 Humid heat                       IEC 60068-2-78                     Front panel                     Plastic, RAL 7035 grey
 constant                         + 40°C / 93% / 2 days                                              on aluminium brackets
 Humid heat                       IEC 60068-2-30
                                                                     Height                          3 U (132.5 mm)
 cyclical                         12+12 h, 6 cycles
                                  +55°C / 93%                        Width                           28 HP (142.2 mm)
 Drop and topple                  IEC 60068-2-31                     Printed circuit board           160 mm x 100 mm
                                  100 mm drop height,
                                                                     Weight                          ≤ 1.5 kg
                                  unpackaged
 Vibration                        IEC 60255-21-1,                    Protection type
                                  Class 1                                – Plug-in module    IP 00
 Shock                            IEC 60255-21-2,                        – Female multipoint IP 00
                                  Class 1                                 connector
 Earthquake resistance            IEC 60255-21-3,                    Mounting                        in conformity with DIN
                                  Class 1                                                            41494 Part 5
                                                                     Plug-in connector               DIN 41612
                  TM
 Display (REG-D        only)
 LC - Display             128 x 128 graphic display
 Back-lighting            LED, automatic switch off after
                          15 minutes
REGSysTM                                                                                                                  Page 9
                                                                                                                          Page 9
We take care of it.
Position of the REG-D™ socket connectors Position of the PAN-D socket connectors
Position of the REG-D™ blade connectors Position of the PAN-D blade connectors
Page 10                                                                                               REGSysTM
Page 10
5.2 Pin assignment of the REG-DTM                                        socket connector 2; (binary inputs) Characteristics D2...D5
                                                                         Raise                         E1          +           b2          -             z2
Socket connector 1; (binary outputs)
                                                                         Lower                         E2          +           b4          -             z4
Raise (2 contact pairs)    R1      Pole    b2          NCC        z2
1 NCC + 1 NOC                      Pole    b4          NOC        z4     Inhibit                       E3          +           b6          -             z6
Lower (2 contact pairs)    R2      Pole    b8          NCC         Z8    Fast switching                E4          +           b8          -             z8
1 NCC + 1 NOC                      Pole    b10         NOC        z10    Manual/Auto                   E5          +           b10         -         z10
Freely programmable        R3      Pole    b14         NOC        z14    Manual                        E6          +           b12         -         z12
Freely programmable        R4      Pole    b16         NOC        z16    Freely programmable           E7          +           b14         -         z14
Freely programmable        R5      Pole    b20         NOC        Z20    Freely programmable           E8          +           b16         -         z16
                                   Pole    b22       Automatic    Z22    BCD 1                         E9          +           b18         -         z18
Manual/Auto
(converter)                     Man        b24                           BCD 2                        E10          +           b20         -         z20
REGSysTM                                                                                                                                       Page 11
                                                                                                                                               Page 11
We take care of it.
Socket connector 5; (binary inputs) Characteristic X25          Socket connector 5; (binary outputs) Characteristic X01
Freely programmable      E17      +         b2     -       z2   Relay 13                    Pole       b14    NOC            z14
Freely programmable      E18      +         b4     -       z4   Freely programmable         NCC        b16
                                                                Relay 14                    Pole       b18    NOC            z18
Freely programmable      E19      +         b6     -       z6
                                                                Freely programmable         NCC        b20
Freely programmable      E20      +         b8     -       z8
                                                                Relay 15                    Pole       b22    NOC            z22
Freely programmable      E21      +         b10    -      z10   Freely programmable         NCC        b24
Freely programmable      E22      +         b12    -      z12   Relay 16                    Pole       b26    NOC            z26
Freely programmable      E23      +         b14    -      z14   Freely programmable         NCC        b28
Freely programmable      E24      +         b16    -      z16   Relay 17                    Pole       b30    NOC            z30
                                                                Freely programmable         NCC        b32
Freely programmable      E25      +         b24    -      b32
Freely programmable      E26      +         b26    -
Freely programmable      E27      +         b28    -            Socket connector 5; (SCADA interface) Characteristic XW1
Freely programmable      E28      +         b30    -             COM1/RxD          d2    COM1/GND      b2     COM1/TxD        z2
Socket connector 5; (binary inputs) Characteristics X15, 24,     VCC/+5 V DC      d12   VCC/+5 V DC    b12   VCC/+5 V DC     z12
28, 29                                                           GND/5 V DC       d14   GND/5 V DC     b14    GND/5 V DC     z14
Freely programmable      E17      +         b2     -       z2
                                                                 Fibre optic/               free              Fibre optic/
                                                                                  d16                  b16                   z16
Freely programmable      E18      +         b4     -       z4         Rx                   GND*                    Tx
Page 12                                                                                                              REGSysTM
Page 12
Socket connector 6; (analogue inputs and outputs;                      Socket connector 2; (binary inputs) Characteristic D1
interfaces)                                                            TC. in operation          E1       +       b2       -       z2
                  d2      Analogue         b2     Analogue      z2
     free                 channel 1               channel 2            Freely programmable       E2       +       b4       -       z4
                              +                       +                Freely programmable       E3       +       b6       -       z6
                  d4      Analogue         b4     Analogue      z4     Freely programmable       E4       +       b8       -       z8
  DCF GND                 channel 1               channel 2
                              -                       -                Freely programmable       E5       +      b10       -      z10
                  d6      E-LAN left       b6     E-LAN right   z6     Freely programmable       E6       +      b12       -      z12
  DCF EA+
                             EA +                    EA +
                                                                       Freely programmable       E7       +      b14       -      z14
                  d8      E-LAN left       b8     E-LAN right   z8
   DCF EA-                                                             Freely programmable       E8       +      b16       -      z16
                             EA -                    EA -
  E-LAN left      d10     E-LAN left       b10    E-LAN right   z10    Freely programmable       E9       +      b24       -      b32
     GND                     E+                       E+
                                                                       Freely programmable      E10       +      b26       -
 E-LAN right      d12     E-LAN left       b12    E-LAN right   z12
    GND                       E-                      E-               Freely programmable      E11       +      b28       -
free d30 COM3 Tx + b30 COM3 Rx + z30 Freely programmable E9 + b18 - z18
COM3 GND d32 COM3 TX- b32 COM3 Rx - z32 Freely programmable E10 + b20 - z20
                                 Pole       b22
Status
                              Failure       b24     Operation    z22
REGSysTM                                                                                                                       Page 13
                                                                                                                               Page 13
We take care of it.
 Socket connector 3; (measuring voltage, auxiliary voltage)           Socket connector 6; (analogue inputs and outputs;
 DC output (max. 5 W)      +5V     d2, b2, z2    GND     d4, b4, z4   interfaces)
                                                                                     d2    Analogue     b2     Analogue     z2
 Measuring voltage 1       U1a         20       U1b**        22                            channel 1           channel 2
                                                                          free
 Measuring voltage 2      U2a**        26        U2b         24                                +                  +
 Regulator                 Pole        b6       NOC          z6        E-LAN left    d10   E-LAN left   b10   E-LAN right   z10
 failure                                                                  GND                 E+                  E+
                           NCC         b8
 <U1                       Pole        b10      NOC          z10       E-LAN right   d12   E-LAN left   b12   E-LAN right   z12
 >U2                       Pole        b14      NOC          z14                     d14   Analogue     b14    Analogue     z14
                                                                          free             channel 3           channel 4
                           NCC         b16
                                                                                               +                  +
 «U3                       Pole        b18      NOC          z18
                                                                                     d16   Analogue     b16    Analogue     z16
                           NCC         b20                              COM1-S
                                                                                           channel 3           channel 4
                                                                          TxD
 »U4                       Pole        b22      NOC          z22                               -                   -
                           NCC         b24                              COM1-S       d18     free       b18      free       z18
 Fast circuit switching    Pole        b26      NOC          z26          RTS
                           NCC         b28                              COM1-S       d20   COM2 TxD     b20   COM2 RTS      z20
 Freely programmable       Pole        b30      NOC          z30          GND
                           NCC         b32                              COM1-S       d22   COM2 RxD     b22   COM2 CTS      z22
                                                                          RxD
Page 14                                                                                                                REGSysTM
Page 14
6. Block diagrams
REGSysTM                                 Page 15
                                         Page 15
We take care of it.
Page 16                                                REGSysTM
Page 16
Block diagram PAN-D Characteristic D1
REGSysTM                                Page 17
                                        Page 17
We take care of it.
Page 18                                                 REGSysTM
Page 18
7. Housing technology
REGSys™ has a very flexible housing technology. A few
                                                                      7.2 Panel/wall mounting housing
of the housing configurations are described below.                    Material                                   Plastic
Most of the housings and 19” racks come with
                                                                      Protection type                            Front panel IP 65
customer-specific wiring. The terminal configuration
can be taken from the system-specific wiring                          Weight                                     ≤ 4 kg
diagrams. Please contact A. Eberle support if you do                  Dimensions                                 see drawings
not have the diagrams.                                                Housing width                              30 or 49 HP
REGSysTM                                                                                                                      Page 19
                                                                                                                              Page 19
We take care of it.
Schalttafelausschnitt:
 Conductor cross section of the terminals                          Conductor cross section of the terminals
 connector, pitch,                        cross section / mm2      connector, pitch,                        cross section / mm2
 application example                  stranded            solid    application example                  stranded            solid
 10 poles, 7.62 mm,                                                10 poles, 7.62 mm,
                                           4                4                                                4                4
 measurements , aux. voltage                                       measurements , aux. voltage
 16 poles, 5 mm, BIs, relays               2,5            2,5      16 poles, 5 mm, BIs, relays               2,5            2,5
 4/5 poles, 3.81 mm,                                               4/5 poles, 3.81 mm,
                                           1,5            1,5                                                1,5            1,5
 additional functions, COMs                                        additional functions, COMs
Panel mounting housing 30 HP - Characteristic B03                 Panel mounting housing 49 HP - Characteristic B06/B91
Dimensions in mm                                                  Dimensions in mm
Page 20                                                                                                                 REGSysTM
Page 20
                      Mounting holes                                                    Mounting holes
 Conductor cross section of the terminals                         Conductor cross section of the terminals
 connector, pitch,                        cross section / mm2     connector, pitch,                        cross section / mm2
 application example                  stranded            solid   application example                  stranded            solid
 10 poles, 7.62 mm,                                               10 poles, 7.62 mm,
                                           4                4                                               4                4
 measurements , aux. voltage                                      measurements , aux. voltage
 16 poles, 5 mm, BIs, relays               2,5            2,5     16 poles, 5 mm, BIs, relays               2,5            2,5
 4/5 poles, 3.81 mm,                                              4/5 poles, 3.81 mm,
                                           1,5            1,5                                               1,5            1,5
 additional functions, COMs                                       additional functions, COMs
Wall mounting housing 30 HP short terminal box                    Wall mounting housing 30 HP long terminal box
Characteristic B03, Dimensions in mm                              Characteristic B03, Dimensions in mm
REGSysTM                                                                                                                 Page 21
                                                                                                                         Page 21
We take care of it.
Conductor cross section of the terminals                          Conductor cross section of the terminals
connector, pitch,                        cross section / mm2      connector, pitch,                        cross section / mm2
application example                  stranded            solid    application example                  stranded            solid
10 poles, 7.62 mm,                                                10 poles, 7.62 mm,
                                          4                4                                                4                4
measurements , aux. voltage                                       measurements , aux. voltage
16 poles, 5 mm, BIs, relays               2,5            2,5      16 poles, 5 mm, BIs, relays               2,5            2,5
4/5 poles, 3.81 mm,                                               4/5 poles, 3.81 mm,
                                          1,5            1,5                                                1,5            1,5
additional functions, COMs                                        additional functions, COMs
Wall mounting housing 49 HP short terminal box                   Wall mounting housing 49 HP long terminal box
Characteristic B07/B91, Dimensions in mm                         Characteristic B91, Dimensions in mm
Page 22                                                                                                                REGSysTM
Page 22
                                                             , and are available
19” card rack 84 HP Rear view with screw terminals - Characteristic B92
19” card rack 84 HP with Phoenix pluggable screw terminals Rear view - Characteristic B92
REGSysTM                                                                                                                         Page 23
                                                                                                                                 Page 23
We take care of it.
                                                                                               Description             No.
7.4 Backplane terminal configuration
                                                                                                                        43
                                                                                              Relay 3 (NOC)
    for REG-D (characteristic B95)                                                                                      42
                                                                                                                        45
                                                                                              Relay 4 (NOC)
            The below terminal configuration always applies to                                                          44
            one device only (REG-D or PAN-D). If the MR is
            equipped with several devices, the terminal                                                                 47
                                                                                              Relay 5 (NOC)
configuration will be identical for each device, but the terminal                                                       46
configuration numbers (-X1, -X2) will be different for each device.                        Common Relay 6…9             28
                                                                                             Relay 6 (NOC)              27
                                                                                             Relay 7 (NOC)              25
                                Description                   No.                            Relay 8 (NOC)              26
                                     PE                        PE                            Relay 9 (NOC)              24
                                                                                          Manual/Auto common            31
UH
                                    L(+)                      161
                                    N(-)                      162                            Manual (NCC)               29
                                    U1a                       163                             Auto (NOC)                30
Voltage
                                 BI 6 (+)                     16                                                       SUB
                                                                                                 COM1-S
                                                                                                                        -D
                                 BI 7 (+)                     15
                                 BI 8 (+)                     14
                               GND BI 3…8 (-)                 18                               COM2 TXD                 97
                                                                      COM2****
Binary inputs
Page 24                                                                                                            REGSysTM
Page 24
                                                                                             Description                No.                                    Description                    No.
                                                                              X 15, 24,     X25         X01    XW1                             BI 31 (+)   BI 28 (+)     Rel 17               34
                                                                               28, 29                                                                                    COM
                                                                              BI 17 (+)   BI 17 (+)   Rel 10            80                     BI 31 (-)   BI 32 (+)     Rel 17                32
                                                                                                      COM                                                                 NOC
                                                                              BI 17 (-)   BI 17 (-)   Rel 10   COM1     81                     BI 32 (+)   BI 25..28     Rel 17                53
                                                                                                       NOC      TxD                                            (-)        NCC
                                                                              BI 18 (+)   BI 18 (+)   Rel 10   COM1     82                     BI 32 (-)   BI 29..32                           33
                                                                                                       NCC      GND                                            (-)
                                                                              BI 18 (-)   BI 18 (-)            COM1     77                                                         COM1        79
                                                                                                                RTS                                                                 RxD
                                                                              BI 19 (+)   BI 19 (+)   Rel 11            83                                                         COM1        78
                                                                                                      COM                                                                           CTS
                                                                              BI 19 (-)   BI 19 (-)   Rel 11            84                                                         RS485       62
                                                                                                       NOC                                                                         N (B)*
                                                                              BI 20 (+)   BI 20 (+)   Rel 11            85    * assignment characteristic XZ22/23: 41 RS485 N(B); 62 RS485 P(A)
                                                                                                       NCC                    ** customer-specific wiring for characteristics M2, M3 and M9
                                                                                                                              *** based on characteristic U, the status contact is either NOC or NCC
                                                                              BI 20 (-)   BI 20 (-)                     76
                                                                                                                              **** COM2 can only be used without SCADA interface installed
Additional BIs, relays, SCADA interface (X01, X15, X24, X25, X28, X29, XW1)
                                                                                                                                                               L(+)                          161
                                                                                                      COM
                                                                                                                                                               N(-)                          162
                                                                              BI 23 (-)   BI 23 (-)   Rel 13            60
                                                                                                       NOC                                                   U1a (L1)                        163
                                                                                                                               Voltage
                                                                              BI 27 (-)               Rel 15            39
                                                                                                                                                  BI 9 (+)                                    12
                                                                                                       NOC
                                                                                                                                                 BI 10 (+)           Characteristic D1        11
                                                                              BI 28 (+)   BI 25 (+)   Rel 15            38
                                                                                                       NCC                                       BI 11 (+)                                    10
                                                                              BI 28 (-)   BI 29 (+)                     55                       BI 12 (+)               BI 9 (+)              9
                                                                                                                                                BI 9…12 (-)             BI 13 (+)             13
                                                                              BI 29 (+)   BI 26 (+)   Rel 16            37                       BI 13 (+)              BI 10 (+)              2
                                                                                                      COM
                                                                                                                                                 BI 13 (-)              BI 14 (+)              1
                                                                              BI 29 (-)   BI 30 (+)   Rel 16            36
                                                                                                                                                 BI 14 (+)              BI 11 (+)              4
                                                                                                       NOC
                                                                              BI 30 (+)   BI 27 (+)   Rel 16            35                       BI 14 (-)              BI 15 (+)              3
                                                                                                       NCC                                       BI 15 (+)              BI 12 (+)              6
                                                                              BI 30 (-)   BI 31 (+)                     54                       BI 15 (-)              BI 16 (+)              5
                                                                                                                                                 BI 16 (+)           GND BI 9…12 (-)           8
                                                                                                                                                 BI 16 (-)           GND BI 13…16 (-)          7
REGSysTM                                                                                                                                                                                 Page 25
                                                                                                                                                                                         Page 25
We take care of it.
                                                                     E-LAN R
                                                               64                                 E+                             107
                 Relay 1 (triggered by circuit breaker) NOC
                                                               63                                 E-                             106
                                                               70                                GND                             110
                 Relay 2 (Emergency OFF tap changer) NOC
                                                               69
                                                                     COM1-S
                                                               68                                                                SUB-
                 Relay 2 (Emergency OFF tap changer) NOC                                        COM1-S
                                                               67                                                                 D
                                                               43
                     Relay 3 (increase interlock) NOC
                                                               42                             COM2 TXD                            97
                                                                                              COM2 RXD                            98
                                                                     COM2**
                                                               45
                     Relay 4 (decrease interlock) NOC
                                                               44                             COM2 GND                            99
                                                               47                              COM2 RTS                           96
                    Relay 5 (freely programmable) NOC
                                                               46                              COM2 CTS                           95
                               Status common                   31                              COM3 Tx+                           89
                      Status NCC (closes upon failure)         29                              COM3 Tx-                           88
                                                                     COM3
                     Status NOC (opens upon failure)           30                              COM3 Rx+                           86
                  Relay 7 (tap changer failure) Common         80                              COM3 Rx-                           87
                     Relay 7 (tap changer failure) NOC         81                             COM3 GND                            90
                     Relay 7 (tap changer failure) NCC         82                        Analogue Channel 1 (+)                  105
                    Relay 8 (regulator failure) Common         83                        Analogue Channel 1 (-)                  104
Binary outputs
                                      E+                      114
                                      E-                      113
                                     GND                      117
Page 26                                                                                                                 REGSysTM
Page 26
                                                         COM2 is mainly used to connect the regulator to the
8. Interfaces and software                               SCADA system. If a SACDA interface is not installed,
Several regulators need to be interconnected in a        COM2 in the terminal compartment can be used to
network when transformers are connected in parallel.     connect a modem, a COM server, a PC or a DCF77
                                                         receiver.
The ΔI*sinϕ, ΔI*sinϕ (S) and Master-Follower parallel
programs can only be implemented through the
system bus (E-LAN). This bus enables each of the         Connection elements
members in a group of parallel regulators to
                                                         COM1                     Sub-D 9-pole male (optionally
communicate with each other easily, without using                                 as mini USB) at the front of
any additional components.                                                        the device
The regulators do not have to be connected in order
                                                         COM1-S                   Male multipoint connector
to run a parallel program that functions in accordance                            (printed circuit board VI)
                                                         (switched off when
to the Δcosϕ method. It may not be possible to           COM1 is used)            depends on the housing
connect the participants due to the long distances
between them, for example.                               COM2                     Male multipoint connector
                                                                                  (printed circuit board VI)
If an interconnection needs to be established over                                depends on the housing
long distances, the E-LAN can be redirected through a
fibre optic cable or an Ethernet connection.             Connection options       PC, modem, PLC, SCADA
                                                                                  connection module, DCF77
8.1 Serial interfaces                                                             signal
           TM
The REG-D and the PAN-D have two RS232 serial            Number of data           Data bits: 8
interfaces with three connections (COM1, COM1-S,         bits/protocol            Parity: even, none
COM2). COM1 is the parameterisation interface, while
COM1-S is an alternative connection option for COM1.     Transmission rate        1200, 2400, 4800, 9600,
                                                         bit/s                    19200, 38400, 57600, 115200
COM1 has priority, meaning that when COM1 has a
connection, COM1-S is switched off. Devices              HANDSHAKE                RTS / CTS, XON / XOFF, delay,
connected to COM1-S do not have to be physically                                  none
disconnected. This enables COM1-S to function as an
alternative remote parameterisation interface that is
only active when parameters are not being set locally.
COM1 can also be configured as a USB port (optional).
REGSysTM                                                                                               Page 27
                                                                                                       Page 27
We take care of it.
Time synchronisation input is not supported until          WinREG runs on the following operating systems:
firmware version 2.22.
                                                           0 Windows XP, Vista, Windows 7
                                                           0 Windows Server from 2003 onwards
Page 28                                                                                               REGSysTM
Page 28
REG-D parameters (selection)                                          PAN-D parameters (selection)
 Parameter                         Setting range                       Parameter                       Setting range
 permissible voltage                                                   Undervoltage <U1                -25 … 10 %
                                   ± 0.1 ... 10 %
 deviation                                                             Overvoltage >U2                 0 ... 25 %
 Time factor                       0.1 ... 30                          Undervoltage «U3                -35 … 10 %
 Setpoint value 1..2               60.0 ... 140.0 V                    Overvoltage »U4                 0 ... 35 %
                                   60.0 ... 140.0 V or                 Inhibit high                    65 V ... 150 V
 Setpoint value 3..4               -140 … 140 % for P/Q                Switching delay for <U1,
                                   regulation                          >U2, «U3, »U4, Inhibit          1 ... 999 s
                                   ΔU · t = const                      high (independent setting for
                                   REG 5A/E                            each limit)
 Time behaviour
                                   LINEAR                              TC in operation -
                                   CONST                                                               3 ... 40 s
                                                                       maximum time
 Trend memory                      0 ... 60 s
                                   Apparent current
 current influence                 Active current
                                                                      8.3 REGSimTM simulation software
 (load-dependent setpoint)         Reactive current                   REGSim™ was designed to simulate the parallel
                                   LDC                                connection of several transformers in any network
 Apparent, active, reactive                                           and load configuration, and to show the results on a
 current                                                              PC.
                                                                                                TM
 Increase (I) (pos.)               0 ... 400 V/In                     To ensure that the REG-D produces the same results
                                   0 ... 400 V/In                     during the simulation as in a live environment, the
 Increase (I) (neg.)                                                  transformers, the network and the load are accurately
                                   -40 ... 40 V
 Limit (I) (max.)                                                     recreated mathematically.
                                   -40 ... 40 V
 Limit (I) (min.)                                                     The authenticity of the simulation is guaranteed
                                                                                       TM                   TM
 LDC                      R : 0 ... ± 30 Ω                            because REGSim uses the REG-D relay’s original
 (Line drop compensation) X : 0 ... ± 30 Ω                            algorithm.
                                                                      All of the settings match those of the real regulator
 Undervoltage <U                   -25 % ... +10 %                    and the simulation is run in real time.
 Overvoltage >U                    0 ... 25 %                                 TM
                                                                      REGSim enables parameters to be tested and set
 Overcurrent >I                    0 ... 210 % (1A / 5A)              before using them in a live environment.
 Undercurrent >I                   0 ... 100 % (1A / 5A)
 Inhibit High                      65 V ... 150 V
 Fast switching forward            0 ... -35 %
 Fast switching backward           0 ... 35 %
 Inhibit low                       -75 % ... 0 %
 Switching delay for <U,
 >U, <I, Inhibit high,
                                   1 ... 999 s
 Fast switching,
                                   (Fast step-up 2...999 s)
 Inhibit low can be set
 separately
 Parallel programs                 dI*sin(phi)
                                   dI*sin(phi)[S]
                                   dcos (phi)
                                   Master-Follower
                                   MSI
                                   MSI2
 TC in operation -
                                   3 ... 40 s
 maximum time*
*when a PAN-D is available, the TC in operation signal is monitored
 by the PAN-D.
REGSysTM                                                                                                                Page 29
                                                                                                                        Page 29
We take care of it
9. Order specifications
0 Only one code of the same capital letter is possible
0 When the capital letter is followed by number 9, further details are necessary
0 The code can be omitted when the capital letter is followed by zero or one option is marked as standard
 CHARACTERISTIC                                                                                         CODE
                                                                                                         TM
                                                                                                 REG-D          PAN-D
       TM                                                                                                TM
 REG-D Relay for Voltage Control & Transformer Monitoring                                        REG-D
 Plug-in module 28 HP, 3 U
 basic configuration with dual ELAN interface, COM1, COM2,
 16 binary inputs, 10 relay outputs and status relays and WinREG parameterisation and
 programming software incl. connection cable
 PAN-D Monitoring unit                                                                                          PAN-D
 Plug-in module 28 HP, 3 U
 basic configuration with dual ELAN interface, COM1, COM2,
 16 binary inputs, 14 relay outputs and status relays
 Design
 0 19" plug-in module                                                                             B01            B01
 0 Wall mounting housing (30 HP) - without wiring                                                 B02            B02
 0 Wall mounting housing (30 HP) - with wiring (terminals are compatible with REG 5A)             B03             -
 0 Wall mounting housing (30 HP) - with wiring (terminals are compatible with Pantavolt 2)         -             B03
 0 Panel mounting housing (30 HP) - with wiring                                                   B05            B05
 0 Panel mounting housing (49 HP) - with wiring                                                   B06            B06
 0 Wall mounting housing (49 HP) - with wiring                                                    B07            B07
 0 Wall mounting or Panel mounting housing (30/49 HP) on request                                  B91            B91
 0 19“ card racks on request                                                                      B92            B92
 0 19“ backplane card racks on request                                                            B95            B95
 Power supply
 0 from the measuring circuit AC 80 V ... 110 V ... 185 V                                         H0             H0
 0 external AC 85 V ... 110 V ... 264 V / DC 88 V ... 220 V ... 280 V                             H1             H1
 0 external AC 85 V ... 110 V ... 264 V / DC 88 V ... 220 V ... 280 V, 20 Watt                    H11             -
    Note: H11 for REG-PE with fibre optic connection without separate REG-NTZ
Page 30                                                                                                       REGSysTM
Page 30
CHARACTERISTIC                                                                                        CODE
                                                                                                      TM
                                                                                               REG-D       PAN-D
Recorder function for quantities U, I, P, Q, S, PF, tap position incl. REGView visualisation
software
0 without                                                                                        S0           S0
0 with max. 3 channels                                                                           S1           S1
0 with max. 256 channels and 108 MB internal memory                                              S2            -
Parallel operation
0 without firmware for parallel operation                                                        K0           -
0 with firmware for parallel operation                                                           K1           -
Transformer monitoring in conformity with IEC 60354 and IEC 60076
0 without transformer monitoring                                                                TM0           -
0 with transformer monitoring                                                                   TM1           -
Analogue inputs and outputs
0 without                                                                                        E00          E00
0 with 2 inputs                                    Note:                                         E91          E91
                                                   Please specify scaling if known:
0 with 4 inputs                                    Example:
                                                                                                 E92          E92
0 with 6 inputs                                    Channel 1: -100 ... 0 ... + 100 MW            E93          E93
0 with 2 outputs                                               -20 ... 0 . . . + 20 MW           E94          E94
0 with 4 outputs                                   Channel 2:    0 ... 80 ... 100 V              E95          E95
                                                                 4 ... 16 . .. 20 mA
0 with 6 outputs                                   Channel 3:    1 ... 19 taps
                                                                                                 E96          E96
0 with 2 inputs and 2 outputs                                    0 ... 20 mA                     E97          E97
0 with 2 inputs and 4 outputs                                                                    E98          E98
0 with 4 inputs and 2 outputs                                                                    E99          E99
0 PT100 direct input (three-wire circuit)                                                       E901         E901
0 any combination on request, 2 analogue inputs and outputs each, PT100 direct input,           E900         E900
   resistance measurement input (tap position potentiometer)
Note: A total of three modules can be used.
This is particularly important when the transformer monitoring module is used!
REGSysTM                                                                                                   Page 31
                                                                                                           Page 31
We take care of it
CHARACTERISTIC                                                                                                  CODE
                                                                                                                TM
                                                                                                         REG-D       PAN-D
SCADA connection: internal or external
0 without (continue with characteristics group 'Y')                                                       XW0          XW0
0 with internal protocol interface (continue with characteristic group 'XL'), only with characteristic    XW1          XW1
   X00
0 with external protocol interface: REG-P/-PE/-PED/-PM (continue with characteristic group 'Y')           XW9          XW9
Integrated protocol interface card
0 to connect one REG-D™ to SCADA                                                                          XL1           -
0 to connect several systems to SCADA                                                                     XL9           -
Note: XL9 can only be combined with XZ15...XZ19, XZ91
Connection type
0 Copper conductors
   – RS232                                                                                                XV10          -
   – RS485 2-wire operation only                                                                          XV11          -
Note: XV13 ... XV19 can only be selected with B02…B95.
In all other cases, select a suitable fibre optic cable module!
0 Fibre optic cable with FSMA connection technology
  – Fibreglass (Wave length 800...900 nm, range 2000 m)                                                   XV13          -
  – All-plastic (Wave length 620...680 nm, range 50 m)                                                    XV15          -
0 Fibre optic cable with ST connection technology
  – Fibreglass (Wave length 800...900 nm, range 2000 m)                                                   XV17          -
  – All-plastic (Wave length 620...680 nm, range 50 m)                                                    XV19          -
Protocol
0 IEC60870-5-103 for ABB                                                                                  XZ10          -
0 IEC60870-5-103 for Areva                                                                                XZ11          -
0 IEC60870-5-103 for SAT                                                                                  XZ12          -
0 IEC60870-5-103 for Siemens (LSA/SAS)                                                                    XZ13          -
0 IEC60870-5-103 for Sprecher Automation                                                                  XZ14          -
0 IEC60870-5-103 for others                                                                               XZ90          -
0 IEC60870-5-101 for ABB                                                                                  XZ15          -
0 IEC60870-5-101 for IDS                                                                                  XZ17          -
0 IEC60870-5-101 for SAT                                                                                  XZ18          -
0 IEC60870-5-101 for Siemens (LSA/SAS)                                                                    XZ19          -
0 IEC60870-5-101 for others                                                                               XZ91          -
0 DNP 3.00                                                                                                XZ20          -
0 LONMark (ask for availability)                                                                          XZ21          -
0 SPABUS                                                                                                  XZ22          -
0 MODBUS RTU                                                                                              XZ23          -
Local/Remote control via keyboard (local/remote key)
0 without                                                                                                  Y0           -
0 with                                                                                                     Y1           -
Status contact
0 closes in case of malfunction                                                                            U0           -
0 opens in case of malfunction                                                                             U1           -
Page 32                                                                                                          REGSysTM
Page 32
CHARACTERISTIC                                                                                    CODE
                                                                                                  TM
                                                                                           REG-D       PAN-D
Operating instructions
0 German                                                                                    G1             G1
0 English                                                                                   G2             G2
0 French                                                                                    G3             G3
0 Spanish                                                                                   G4             G4
0 Italian                                                                                   G5             G5
0 Russian                                                                                   G6              -
0 Portuguese                                                                                G7              -
0 Czech                                                                                     G8              -
0 other on request                                                                          G10             -
Display language
0 same as the operating manual                                                               A0            -
0 German                                                                                     A1            -
0 English                                                                                    A2            -
0 French                                                                                     A3            -
0 Spanish                                                                                    A4            -
0 Italian                                                                                    A5            -
0 Russian                                                                                    A6            -
0 Portuguese                                                                                 A7            -
0 Czech                                                                                      A8            -
0 Dutch                                                                                      A9
REGSysTM                                                                                               Page 33
                                                                                                       Page 33
We take care of it
Page 34                                                                                           REGSysTM
Page 34
Add-ons for REG-D/PAN-D                                                                                  ID-No.
Transformer Monitoring Module - TMM (REG-D only)                                                          TMM
0 Consists of:
   – Firmware update (> 2.x)
   – User guide and parameterisation module WinTM for WinREG
   – Analogue module with two inputs for the temperature transducer                                       A1
   – Input for PT100 in a three-wire circuit in conformity with DIN 43760                                 A2
0 Auxiliary voltage
  – AC 85…264 V, DC 88 … 280 V                                                                            H1
  – DC 18 … 72 V                                                                                          H2
REGSysTM                                                                                                     Page 35