W
CIRCUIT DRAWN WITH POWER SUPPLY OFF FOR TYPICAL REMOTE CONTROL
M 2 W (C)
2 DETAILS, SEE DOCUMENT
3
3 V
4
1 V (B)
3
PHASE
RWS133
SUPPLY
U
U (A)
3 1 TR AN S F OR ME R TAP P IN G OP TION S
6
5 T ap Nominal 50/60Hz
U V W E TYP E 1
FS1
W 220/230
X 380/400
C1 C2 Y 400,415/420
U W X Y Z
Z 440/460
F US E F S 1= 250mA A NTI-S UR G E
SK2 TYP E 2
0VAC 1 W 346/380
TRANSISTOR SWITCHING FOR
PS1 X 480/500
24VDC CONTACTORS (IQ10-35) 120VAC 4
RELAYS ONLY FITTED WHEN Y 240/240
0VDC
120VAC CONTACTOR IS FITTED 3 4 24VDC Z 550/575
FOR IQ40,70,90,91 & 95 24VDC 6 NOMINAL SUPPLY
F US E F S 1= 250mA A NTI-S UR G E
_ 5 (OUTPUT)
+
AVAILABLE WHEN TYP E 3
SK14 POWERED ONLY
X 660/660-690
0VDC 1
Y 690/-
24VDC 2 F US E F S 1= 150mA A NTI-S UR G E
SK13
26 WAY REFER TO SHEET 2 FOR NOTES
& OPTION PCB'S IF FITTED
SK3 SK13 SK14 DO NOT CONNECT TO
6 1 42 TERMINALS MARKED
MONITOR RELAY
5 3 43
= PLUG & SOCKET CONNECTION
TORQUE 4 2 44
3
2
SK7
SENSOR 1 1 6
SK8 BREAT AT CT/LS S1 8 7
POSITION 10 WAY 2 8
SENSOR BREAK AT OT/LS S2 7 9
SK9
3 10
BATTERY - 4
MAKE AT FULLY SHUT S3 6 11
4 12
+
1 MAKE AT FULLY OPEN S4 5 13
FS2 (IF FITTED) 100mA SK4
CLOSE 9 33
STOP/ MAINTAIN 10 34
50% SK6 OPEN 8 35
COMMON -VE 1 36
18 WAY
ESD 12 25
OPEN INTERLOCK 13 37
CLOSE INTERLOCK 14 38
COMMON -VE 5 31
SK1 SK2
SLOT A SLOT B
Iss Date Chkd Revision Details IQ SET + INDICATION RELAYS (2220-00) + PLUG &
1 300622 PJW First Issue www. .com SOCKET
ROTORK CONTROLS LTD ROTORK CONTROLS INC Drawn by: NJC Circuit Diagram Number Issue Sheet
BATH, BA1 3JQ ROCHESTER Date : 300622 No
ENGLAND NY 14624, USA
Base WD: 100S0012
Job No : - -
100S0012 1
1
of 2
Tel:01225-733200 Tel:585-247-2304 MI No : - - 92 94 B1 C1 B2 C2 J1 T1
IQ3
CIRCUIT DRAWN WITH POWER SUPPLY OFF
SLOT A
SK1
SLOT A SK3
EXTRA CHANGE OVER CONTACTS
2 14
FOR OTHER SETTINGS SEE PUB002-038
S5 3
BREAK AT FULLY SHUT 16
DEFAULT SETTINGS SHOWN
1 15
5 17
BREAK AT FULLY OPEN S6 6 19
4 18
8 20
MAKE WHEN STALLED S7 9 24
7 21
11 30
MAKE ON LOSS OF PHASE S8 12 47
10 46
NOTES 3.INDICATION:
1.FUSES: -For typical position, status and alarm indication see PUB002-041.
-PS1 is a self-resetting fuse. -“S” contacts are user configurable and are shown in their default
-Refer to publication PUB002-039 for approved fuses FS1 and FS2. setting.
-Actuator rated voltage specified on nameplate. Voltage tolerance +/-10%, -Voltage applied to indication contacts must not exceed 120V AC or
applies for rated torque performance; duty cycle is not guaranteed. DC
2.CONTROL: -Maximum individual Switching power must not exceed 60W inductive
-Supply provided on terminals 4 & 5 only available when power is applied to the load or 150W resistive load
actuator : -Total switched current for contacts S1 to S4 must not exceed 8A, with
-Max external load 5W at 24Vdc / 5VA at 120Vac maximum individual current of 5A.
-Connect motor control contactor coils in series with CT/LS S1(closed) and OT/LS
S2(open). 4.BATTERY:
-Voltage applied to CT/LS & OT/LS must not exceed 120V AC or DC. -Battery maintains local and remote “S” contact indication only.
-Maximum individual switching power must not exceed 60W inductive or 150W -Refer to installation manual for approved replacement battery types.
resistive.
Circuit Diagram Number Issue Sheet
No
2
See Sheet 1 for all Revision details/information 100S0012 1 of 2
IQ3