Development of Water Distribution and Supply Facilities at Purbachal New Town
through Public Private Partnership
United Delcot Water Limited
FIELD DENSITY TEST BY SAND CONE METHOD
(AASHTO T-191)
Location : Pump House -14 Date of Test : 15.03.2025
Name of the of LayeSub base - 1st layer RFI Ref No: P2/P.H.-14/20250315
Bulk Density of the Calibration Sand, Ys: (g/cm 3) = 1.54 MDD_Ү max = 2.315 gm/cm3
OMC. = 6.2 %
Location of Test PH-14
Depth of Hole (mm) 150
FIELD DENSITY DETERMINATION
Test Number 1 2 3 4 5
Cone and Jar No. 1
Wt. of Wet Sample from Hole W1 g 3476
Wt. of Sand and Jar Before Pouring W2 g 6585
Wt. of Sand and Jar After Pouring W3 g 2965
Wt. of Sand in Cone and Hole, W4=(W2-W3) g 3392
Wt. of Sand in Cone g 1270
Wt. of Sand in Hole W5 g 3678
Volume of Hole V= W5/Ys cm3 3171
Wet Density Y wet=W1/V g/cm3 1.096
MOISTURE CONTENT DETERMINATION
Can No. 82
Weight of Wet Sample + Can W1 g 479
Weight of Dry Sample + Can W2 g 428.0
Weight of Water W3 = W1-W2 g 51.0
Weight of Can W4 g 76
Weight of Dry Sample W5 = W2-W4 g 352
Moisture Content W3/W5x100 % 14.6
Average Moisture Content % 14
DETERMINATION OF DEGREE OF COMPACTION
In -Situ Dry Density Yd = 100*Ywet/(100+m) g/cm3 0.951
Percent Compaction 100 Yd/Y' max. % 101.1
Minimum Specified Compaction % 98
Conclusion (Fail/Pass) - 95
Remarks: Prepared By
Name:Md.Delwar Hossain
Signature:
United Delcot Water Limiteds Independent Engineer's(IWM) RAJUK's
Representative Representative Representative
Signature: Signature: Signature:
Name: Md.Shahnewaz Name: Sohel Rana Name:
Position:Deputy Construction Manager Position: ARE Position:
DATE: DATE: DATE:
Development of Water Distribution and Supply Facilities at Purbachal New Town
through Public Private Partnership
United Delcot Water Limited
FIELD DENSITY TEST BY SAND CONE METHOD
(AASHTO T-191)
Location : Pump House -14 Date of Test : 17.03.2025
Name of the of LayeSub base - 2nd layer RFI Ref No: P2/P.H.-14/20250317
Bulk Density of the Calibration Sand, Ys: (g/cm 3) = 1.54 MDD_Ү max = 2.315 gm/cm3
OMC. = 6.2 %
Location of Test PH-14
Depth of Hole (mm) 150
FIELD DENSITY DETERMINATION
Test Number 1 2 3 4 5
Cone and Jar No. 2
Wt. of Wet Sample from Hole W1 g 3463
Wt. of Sand and Jar Before Pouring W2 g 6587
Wt. of Sand and Jar After Pouring W3 g 2965
Wt. of Sand in Cone and Hole, W4=(W2-W3) g 3392
Wt. of Sand in Cone g 1270
Wt. of Sand in Hole W5 g 3678
Volume of Hole V= W5/Ys cm3 3171
Wet Density Y wet=W1/V g/cm3 1.092
MOISTURE CONTENT DETERMINATION
Can No. 82
Weight of Wet Sample + Can W1 g 479
Weight of Dry Sample + Can W2 g 428.0
Weight of Water W3 = W1-W2 g 51.0
Weight of Can W4 g 76
Weight of Dry Sample W5 = W2-W4 g 352
Moisture Content W3/W5x100 % 14.6
Average Moisture Content % 14
DETERMINATION OF DEGREE OF COMPACTION
In -Situ Dry Density Yd = 100*Ywet/(100+m) g/cm3 0.947
Percent Compaction 100 Yd/Y' max. % 101.0
Minimum Specified Compaction % 98
Conclusion (Fail/Pass) - 95
Remarks: Prepared By
Name:Md.Delwar Hossain
Signature:
United Delcot Water Limiteds Representative Independent Engineer's(IWM) Representative RAJUK's Representative
Signature: Signature: Signature:
Name: Md.Shahnewaz Name: Sohel Rana Name:
Position:Deputy Construction Manager Position: ARE Position:
DATE: DATE: DATE:
Development of Water Distribution and Supply Facilities at Purbachal New Town
through Public Private Partnership
United Delcot Water Limited
FIELD DENSITY TEST BY SAND CONE METHOD
(AASHTO T-191)
Location : Pump House -03 Date of Test : 18.02.2025
Name of the of LayeSub base - 2nd layer RFI Ref No: P2/P.H.-03/20250218
Bulk Density of the Calibration Sand, Ys: (g/cm 3) = 1.54 MDD_Ү max = 2.315 gm/cm3
OMC. = 6.2 %
Location of Test PH-03 PH-03 PH-03 PH-03
Depth of Hole (cm) 10 10 10 10
FIELD DENSITY DETERMINATION
Test Number 1 2 3 4 5
Cone and Jar No. 3 1 3 1
Wt. of Wet Sample from Hole W1 g 6915 6999 6642 6819
Wt. of Sand and Jar Before Pouring W2 g 9380 9056 9295 8927
Wt. of Sand and Jar After Pouring W3 g 4071 3718 4192 3654
Wt. of Sand in Cone and Hole, W4=(W2-W3) g 1141 1201 1141 1201
Wt. of Sand in Cone g 1775
Wt. of Sand in Hole W5 g 4168 4132 3962 4072
Volume of Hole V= W5/Ys cm3 2706 2686 2572 2644
Wet Density Y wet=W1/V g/cm3 2.555 2.606 2.582 2.579
MOISTURE CONTENT DETERMINATION
Can No. 82 25 21 22
Weight of Wet Sample + Can W1 g 448 370 351 400.0
Weight of Dry Sample + Can W2 g 428.0 354 334 383.0
Weight of Water W3 = W1-W2 g 20.0 16 17 17
Weight of Can W4 g 72.2 58.7 63 60
Weight of Dry Sample W5 = W2-W4 g 355.8 295.3 271 323
Moisture Content W3/W5x100 % 5.6 5.4 6.3 5.3
Average Moisture Content % 15.3 15.2 15.1 15.3
DETERMINATION OF DEGREE OF COMPACTION
In -Situ Dry Density Yd = 100*Ywet/(100+m) g/cm3 2.216 2.472 2.450
Percent Compaction 100 Yd/Y' max. % 99.7 101.0 100.2 100.5
Minimum Specified Compaction % 98 98 98 98
Conclusion (Fail/Pass) - 95 95 95 95
Remarks: Prepared By:
Name:
Signature:
United Delcot Water Limiteds Representative Independent Engineer's(IWM) Representative RAJUK's Representative
Signature: Signature: Signature:
Name: Md.Shahnewaz Name: Sohel Rana Name:
Position:Deputy Construction Manager Position: ARE Position:
DATE: DATE: DATE:
Development of Water Distribution and Supply Facilities at Purbachal New Town
through Public Private Partnership
United Delcot Water Limited
FIELD DENSITY TEST BY SAND CONE METHOD
(AASHTO T-191)
Location : Pump House -03 Date of Test : 18.02.2025
Name of the of LayeSub base - 2nd layer RFI Ref No: P2/P.H.-03/20250218
Bulk Density of the Calibration Sand, Ys: (g/cm 3) = 1.54 MDD_Ү max = 2.315 gm/cm3
OMC. = 6.2 %
Location of Test PH-03 PH-03 PH-03 PH-03
Depth of Hole (cm) 10 10 10 10
FIELD DENSITY DETERMINATION
Test Number 1 2 3 4 5
Cone and Jar No. 3 1 3 1
Wt. of Wet Sample from Hole W1 g 6915 6999 6642 6819
Wt. of Sand and Jar Before Pouring W2 g 9380 9056 9295 8927
Wt. of Sand and Jar After Pouring W3 g 4071 3718 4192 3654
Wt. of Sand in Cone and Hole, W4=(W2-W3) g 1141 1201 1141 1201
Wt. of Sand in Cone g 1775
Wt. of Sand in Hole W5 g 4168 4132 3962 4072
Volume of Hole V= W5/Ys cm3 2706 2686 2572 2644
Wet Density Y wet=W1/V g/cm3 2.555 2.606 2.582 2.579
MOISTURE CONTENT DETERMINATION
Can No. 82 25 21 22
Weight of Wet Sample + Can W1 g 448 370 351 400.0
Weight of Dry Sample + Can W2 g 428.0 354 334 383.0
Weight of Water W3 = W1-W2 g 20.0 16 17 17
Weight of Can W4 g 72.2 58.7 63 60
Weight of Dry Sample W5 = W2-W4 g 355.8 295.3 271 323
Moisture Content W3/W5x100 % 5.6 5.4 6.3 5.3
Average Moisture Content % 15.3 15.2 15.1 15.3
DETERMINATION OF DEGREE OF COMPACTION
In -Situ Dry Density Yd = 100*Ywet/(100+m) g/cm3 2.216 2.472 2.450
Percent Compaction 100 Yd/Y' max. % 99.7 101.0 100.2 100.5
Minimum Specified Compaction % 98 98 98 98
Conclusion (Fail/Pass) - 95 95 95 95
Remarks: Prepared By:
Name:
Signature:
United Delcot Water Limiteds Representative Independent Engineer's(IWM) Representative RAJUK's Representative
Signature: Signature: Signature:
Name: Md.Shahnewaz Name: Sohel Rana Name:
Position:Deputy Construction Manager Position: ARE Position:
DATE: DATE: DATE: