Thank you for purchasing this series UPS.
This series UPS is an intelligent, single phase in single phase out, high frequency online
UPS designed by our R&D team who is with years of designing experiences on UPS.
With excellent electrical performance, perfect intelligent monitoring and network functions,
smart appearance, complying with EMC and safety standards, The UPS meets the
world’s advanced level.
Read this manual carefully before installation
This manual provides technical support to the operator of the equipment.
Table of Contents
1.   Important Safety Warning ..................................................................................................................... 2
     1-1        Transportation .............................................................................................................................. 2
     1-2        Preparation .................................................................................................................................... 2
     1-3        Installation ..................................................................................................................................... 2
     1-4        Operation ....................................................................................................................................... 3
     1-5        Maintenance, service and faults .............................................................................................. 3
     1-6        Symbols used in this guide ...................................................................................................... 3
2.   Installation and setup ............................................................................................................................. 4
     2-1        Unpack checking ......................................................................................................................... 4
     2-2        Real panel view ............................................................................................................................ 4
     2-3        LCD control panel........................................................................................................................ 6
     2-4        Setup the UPS .............................................................................................................................. 6
3.   Operations ................................................................................................................................................. 7
     3-1        Button operation .......................................................................................................................... 7
     3-2        LCD display ................................................................................................................................... 8
     3-3        UPS setting ................................................................................................................................. 11
     3-4        Operating Mode Description .................................................................................................. 13
     3-5        Operational Status and Mode(s) ............................................................................................ 14
     3-6        Alarm or Fault reference code ............................................................................................... 14
4.   Troubleshooting..................................................................................................................................... 15
5.   Storage and Maintenance.................................................................................................................... 15
6.   Options ..................................................................................................................................................... 16
7.   Specification ........................................................................................................................................... 18
                                                                                 1
1. Important Safety Warning
Important safety instructions – Save these instructions
    Please comply with all warnings and operating instructions in this manual strictly. Save
    this manual properly and read carefully the following instructions before installing the unit.
    Do not operate this unit before reading through all safety information and operating
    instructions carefully
        There exists dangerous voltage and high temperature inside the UPS. During the
    installation, operation and maintenance, please abide the local safety instructions and
    relative laws, otherwise it will result in personnel injury or equipment damage. Safety
    instructions in this manual act as a supplementary for the local safety instructions. Our
    company will not assume the liability that caused by disobeyingsafety instructions.
    1-1 Transportation
     Please transport the UPS system only in the original package to protect against
      shock and impact.
    1-2 Preparation
     Condensation may occur if the UPS system is moved directly from cold to warm
      environment. The UPS system must be absolutely dry before being installed. Please
      allow at least two hours for the UPS system to acclimate the environment.
     Do not install the UPS system near water or in moist environments.
     Do not install the UPS system where it would be exposed to direct sunlight or near
      heater.
     Do not block ventilation holes in the UPS housing.
    1-3 Installation
     Do not connect appliances or devices which would overload the UPS system (e.g.
      laser printers) to the UPS output sockets.
     Place cables in such a way that no one can step on or trip over them.
     Do not connect domestic appliances such as hair dryers to UPS output sockets.
     The UPS can be operated by any individuals with no previous experience.
     Connect the UPS system only to an earthed shockproof outlet which must be easily
      accessible and close to the UPS system.
     Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
      computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
     Please use only VDE-tested, CE-marked power cables to connect the loads to the
      UPS system.
     When installing the equipment, it should ensure that the sum of the leakage current of
      the UPS and the connected devices does not exceed 3.5mA.
                                                2
1-4 Operation
 Do not disconnect the mains cable on the UPS system or the building wiring outlet
  (shockproof socket outlet) during operations since this would cancel the protective
  earthing of the UPS system and of all connected loads.
 The UPS system features its own, internal current source (batteries). The UPS output
  sockets or output terminals block may be electrically live even if the UPS system is
  not connected to the building wiring outlet.
 In order to fully disconnect the UPS system, first press the OFF/Enter button to
  disconnect the mains.
 Prevent no fluids or other foreign objects from inside of the UPS system.
        CAUTION!
        Read this information to avoid equipment damage
                                         3
2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. Please keep the original package in a safe place for future use.
1KVA(H):
2KVA(S):
                                            4
2KVA(H)/3KVA(H)
2KVA(S)-6batt /3KVA(S):
          1.    AC input
          2.    Network /Fax/Modem Surge Protection(option)
          3.    Input circuit breaker
          4.    EPO(option)
          5.    USB communication port(option)
          6.    RS-232 communication port
          7.    SNMP intelligent slot (option)
          8.    Output receptacles
          9.    Battery Terminal
          10.   Output Terminal
                                           5
    2-3 LCD control panel
       To allow for unattended UPS shutdown/start-up and status monitoring, connect the
       communication cable one end to the USB/RS-232 port and the other to the
       communication port of your PC. With the monitoring software installed, you can
       schedule UPS shutdown/start-up and monitor UPS status through PC.
       The UPS is equipped with intelligent slot perfect for either SNMP or Relay card. When
       installing either SNMP or Relay card in the UPS, it will provide advanced
       communication and monitoring options.
       NOTE: USB port and RS-232 port can’t work at the same time.
                                               6
Step 4: Turn on the UPS
     Press the ON button on the front panel for two seconds to power on the UPS.
     Note: The battery charges fully during the first five hours of normal operation. Do not
     expect full battery run capability during this initial charge period.
Step 5: Install software
     For optimal computer system protection, install UPS monitoring software to fully
     configure UPS shutdown. You may insert provided CD into CD-ROM to install the
     monitoring software.
Step 6: External battery connection
     If your UPS is not including batteries. Please connect external batteries as below
     chart.
3. Operations
   3-1 Button operation
         Button                                  Function
                          Turn on the UPS: Press and hold ON button for at least
                           2 seconds to turn on the UPS.
                          Down key: Press this button to display next selection in
       ON Button           UPS setting mode.
                          Exit setting mode:Press this button to confirm seletion
                           and exit setting mode when LCD display the last
                           selection in UPS setting mode.
                          Turn off the UPS: Press and hold this button at least 2
                           seconds to turn off the UPS in battery mode. UPS will
                           be in standby mode under power normal or transfer to
                           Bypass mode if the Bypass enable setting by pressing
                           this button.
                          Switch to bypass mode: When the main power is
       OFF Button
                           normal, press and hold this button for 2 seconds. Then
                           UPS will enter to bypass mode. This action will be
                           ineffective when the input voltage is out of acceptable
                           range.
                          Up key: Press this button to display previous selection
                           in UPS setting mode.
                                            7
                      Switch LCD message: Press this button to change the
                       LCD message for input voltage, input frequency, battery
                       voltage, output voltage and output frequency etc.
                      Mute the alarm: When the UPS is on battery mode,
   FUNC/Mute           press and hold this button for at least 2 seconds to
     Button            disable or enable the alarm system. But it’s not applied
                       to the situations when warnings or errors occur.
                      Switch to UPS self-test mode: Press and hold this
                       button for 2 seconds to enter UPS self-testing while in
                       AC mode.
  OFF + FUNC          Setting mode: Press and hold this button for 5 seconds
    Button             to enter UPS setting mode.
01 Input voltage
02 Battery voltage
                                        8
03       Output voltage
04 Load
           Temperature
     (EnvironmentTemperatu
05
               re)
                              9
             CODE
07   (Operational status and
             mode)
      Alarm Code(Warming
             Message)
08     All alarm codes are
     present when abnormal
       behavior(s) occur(s)
            Cc MODE
09
Cv MODE
                                10
    3-3 UPS setting
     The setting fuction is controled by 3 buttons (Func,Off/up ▲, On/down▼): Func +Off/up
▲---goes into the setting page, Func --- value adjustment; Off ▲ & On ▼---for choosing
different pages.
     After the UPS turn ON, press buttons Func & ▲ for 5seconds and then goes into the
setting interface page.
    Note: Figure at left corner is the page number of the setting pages.
Frequency setting
                                             11
     Battery capacity setting
                                      12
           Mute setting
           Press Func button to change
           thesetting(ON or OFF).
           Press UP button ▲ to select the
           previous setting.
    08
           Press DOWN ▼ button to save and
           exit the setup.
Online mode         When the input voltage is within        Inverter led light
                    acceptable range, UPS will provide
                    pure and stable AC power to output.
                    The UPS will also charge the battery
                    at online mode.
ECO mode            Energy saving mode:                     Bypass led light
                    When the input voltage is within
                    voltage regulation range, UPS will
                    bypass voltage to output for energy
                    saving.
Battery mode        When the input voltage is beyond the    Battery led light
                    acceptable range or power failure and
                    alarm is sounding every 4 second,
                    UPS will backup power from battery.
Standby mode        UPS is powered off and no output        All LEDs turn off
                    supply power, but still can charge
                    batteries.
Bypass mode         When input voltage is within          Bypass led light
                    acceptable range but UPS is overload,
                    UPS will enter bypass mode or
                    bypass mode can be set by front
                    panel.
                                         13
  3-5 Operational Status and Mode(s)
                         item              Content Displayed
                          2                  Standby Mode
                          3                    No Output
                          4                  Bypass Mode
                          5                   Utility Mode
                          6                  Battery Mode
                          7             Battery Self-diagnostics
                          8              Inverter is starting up
                          9                   ECO Mode
                         10                   EPO Mode
                         11            Maintenance Bypass Mode
                         12                   Fault Mode
Alarm code is shown as “34”      Battery voltage is too low or     Contact your dealer.
and battery led blinking         the charger is fault.
Alarm code is shown as           A UPS internal fault has          Contact your dealer.
“01,02, 15,16,17,18”             occurred.
                                                                   Charge the batteries for at
                                 Batteries are not fully           least 5 hours and then check
Battery backup time is           charged                           capacity. If the problem still
shorter than nominal value                                         persists, consult your dealer.
                                                                   Contact your dealer to
                                 Batteries defect
                                                                   replace the battery.
6. Options
SNMP card: internal SNMP
            ◆Loosen the 2 torquescrews (on each side of thecard).
            ◆Carefully insert the SNMP card and lock the screws
      The slot called SNMP supports the MEGAtec protocol.We advise that Net AgentII-3
port is also a tool to remotely monitorand manage any UPS system
Relaycard
    Mini dry contact card is used foproviding the interface for UPS peripheral monitoring.
The contact signals canreflect UPS running status.The card is connected to peripheral
monitoring devices via terminal board to facilitate the effective monitoring of the
real-timestatus of UPS and timely feedback the statusto monitor when abnormal situation
occurs(suchas UPS failure, mains interruption,UPS bypassand ect.). It is installed in the
intelligent slotof the UPS.
The relay card includes 6 output ports and one input port.Please refer to thefollowing table
for detail.
                                             16
Pins definition of connecting terminal on the board
               Line Mode
               (synchroni                                          47-53Hz or 57-63Hz
Frequency      zed range)