6000 CFM

The EcoloAir Unit is designed for efficient removal of grease and smoke in commercial kitchens, meeting ASHRAE standards and reducing fire hazards. It allows for flexible installation options, minimizing the need for extensive ductwork and fire-rated enclosures. The system includes multiple filtration stages and an odor control module, ensuring compliance with environmental standards and effective odor management.

Uploaded by

Ismail Mohammad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
55 views4 pages

6000 CFM

The EcoloAir Unit is designed for efficient removal of grease and smoke in commercial kitchens, meeting ASHRAE standards and reducing fire hazards. It allows for flexible installation options, minimizing the need for extensive ductwork and fire-rated enclosures. The system includes multiple filtration stages and an odor control module, ensuring compliance with environmental standards and effective odor management.

Uploaded by

Ismail Mohammad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

20/6000CFM/XXXX/0107/EN

6000 CFM
EcoloAir Unit

© Halton

• 99% of all grease and smoke is efficiently and Application


effectively removed to ASHRAE Standard 52-76
Ventilation is the critical factor to consider when investigating the
eliminating fire hazard.
feasibility of a new commercial kitchen site. New projects, new
• The cleaned exhaust air can be discharged to the
design to exisiting buildings, and non-traditional sites often require
outside at ground level, daving costly runs of heavy uncommon solutions for kitchen ventilation problems. EcoloAirTM
gauge welded exhaust ducts to the roof. may be your solution to code requirements, environmental
• No need for fire rated enclosures to the roofline standards, multi-story structures, high installation costs, limited
roof top space, historical/architectural sites or multi-restaurant
• Objectionable cooking odors are reduced to an
applications.
effective and acceptable level
• Complete system can be located in the ceiling
space, on the roof, or in a designated mechanical
room.
• Each EcoloAir Module can be assembled and
installed as one common unit or individually
installed in seperate areas.
• Commercial kitchens can not be located in areas
where there are no provisions for grease exhaust .

6000CFM - EcoloAir Unit 1


Consultant Specification

20/6000CFM/XXXX/0107/EN
The EcoloAir TM Ecology System shall be a Model _____ rated be a DWDI (double width, double inlet), Class 2,
__, as manufactured by Halton, supplied complete with backward inclined, with airfoil type blades and with non-
Filter Module, Odor Control Module, Fan Module, and overloading characteristics. The complete fan assembly
Control Panel. System mounting to be designed for; is statically and dynamically balanced. The shaft is ground
Interior/Exterior, Suspended/Floor/Roof. The system and polished steel. Bearings shall be pillow block type
shall deliver _________ CFM (_______m3/s) at _______ with lubrication nipples. Drives shall be V belt or grip notch
_in.wg. (________Pa) External Static Pressure (ESP). All with capacity 25% greater then motor horsepower. The fan
components to be UL/ULC Listed. and motor shall be mounted on a common base which is
spring vibration isolated from the fan housing. A fire stat
Filter Module shall be located at the fan inlet to stop the fan on high air
The unit casing shall be fully painted and be a double wall temperature. Hinged access doors shall be provided to allow
construction reinforced and braced for maximum rigidity. easy access to fan and motor. Units to be complete with a
Inner walls shall be 16-gauge liquid tight welded and _______HP (______kW) ________ Volt________ Phase________Hz
construction and outer walls shall be minimum 20-gauge motor, motor starter complete with electrical overloads and
steel. Filter sections to be insulated with 1.5” (38mm) electrical disconnect switch.
insulation to the requirements of UL/ULC. The unit shall
be complete with three stages of filtration. Control Panel
The control panel shall be constructed from heavy gauge
• The first stage shall be a 2” (51mm) deep pleated steel, be suitable for remote mounting and have front locking
filter, rated at 40% ASHRAE Std 52.1, UL 900 Class 2 screws. Controls shall be complete with PLC controls and
rating. digital status/condition display. Display will indicate system
• The second stage shall be a 15” (381 mm) deep bag operational status, condition of all three filter stages, lack
filter, rated at 90-95% ASHRAE 52.1 Std, UL 900 of air pressure, fire condition and odor reducing operation.
Class 2 rating. Controls and interconnecting field wiring to be standard
• The third stage shall be a 12” (305 mm) deep 120volt AC.
Microtein filter, rated at an efficiency of 95% on 0.3
µm particles (DOP), UL 900 Class 1 rating.

A UL/ULC Listed fire damper actuated by fusible link Modifications & Options
(165°F UL / 286°F ULC) shall be located at the outlet. This
module to be complete with three pressure switches GENERAL
to monitor the condition of each of the three stages of • Weather Proof Insulation Package
filtration, and a fourth pressure switch to detect a lack of • Rear Access Doors
air pressure. • 24v Control Wiring

Hinged access doors shall be provided to allow easy FILTER MODULE


access to the filters. • Fire Suppression System
• Extra Set of Filters
Odor Control Module
• Inlet Plenum
The EcoloAir TM Odor Control Module shall consist of a
• Missing Filter Pressure Switch
housing and a self contained odor reducing system. The
• Air Proving Switch
housing shall be fully painted and be constructed of 16
• Magnehelic Gauge (Visual Monitors)
gauge (minimum) steel with all joints suitably reinforced
and braced for rigidity. The “Ecolo Scentry TM” liquid spray
ODOR CONTROL MODULE
odor reducing system shall produce an atomized spray that
• Cold Climate Insulation
permeates the filtered exhaust air to attack and neutralize
• Extra Container of Odor Solution
airborne odors. The system housing shall be constructed
• Low Level Odor Control Indicator Light
of heavy steel with locking hinged access door and two
security bolts. The system shall be complete with an
FAN MODULE
adjustable spray nozzle, 5-gallon liquid reservoir. Timers
• Acoustic Insulation Package
mounted in the EcoloAir TM control panel to switch on, off
• Outlet Cowl
and cycle control to provide for infinite adjustment.
• Non Standard Voltage
Fan Module • Single Phase Motor
The fan housing shall be fully painted and be constructed • Internal Seismic Isolators
from 16 gauge (minimum) steel with all joints suitably • Top Discharge
reinforced and braced for rigidity. The fan shall be AMCA • Piggy Back Mount
• Variable Frequency Drive (VFD)

6000CFM - EcoloAir Unit 2


Dimension: Inches

20/6000CFM/XXXX/0107/EN
mm

FILTER MODULE EF6


585lbs/265kg
TYPICAL HANGER BRACKET
FILTER
#1
(LEFT SIDE)
FILTER
SPECIFY

50.625”
#2

( 1286)
AIR FLOW ACCESS SIDE
FILTER (RIGHT SIDE SHOWN)
(RIGHT SIDE) #3
FIRE DAMPER

( 762)
30”
Service
Clearance
PLAN VIEW
FILTER PRESSURE
48” 7.5” SWITCH BOX 48”
(1219) (191) (1219)

( 1067)
42”
( 914)

36”
( 914)
36”

53.725” 45” 55.25”


(1365) (1143) (1403)

INLET END VIEW ACCESS SIDE ELEVATION OUTLET END VIEW

ODOR CONTROL MODULE OC6


400lbs/180kg
TYPICAL HANGER BRACKET

(LEFT SIDE)
50.625”

SPECIFY
( 1286)

AIR FLOW ACCESS SIDE


(RIGHT SIDE SHOWN)
(RIGHT SIDE)
( 762)
30”

Service
Clearance
ODOR CONTROL
CABINET
48” 11” PLAN VIEW 48”
(1219) (279) (1219)
( 1067)

( 914)
36”
( 914)

42”
36”

53.725” 18” 55.25”


(1365) (457) (1403)

INLET END VIEW ACCESS SIDE ELEVATION OUTLET END VIEW

6000CFM - EcoloAir Unit 3


Dimension: Inches

20/6000CFM/XXXX/0107/EN
mm

FAN MODULE OC6


1400lbs/635kg
TYPICAL HANGER BRACKET

(LEFT SIDE)
SPECIFY

52.375”
( 1330)
AIR FLOW ACCESS SIDE
(RIGHT SIDE SHOWN)
(RIGHT SIDE)

( 762)
Service

30”
Clearance

PLAN VIEW

49.375” 10” DISCONNECT 18.5”


(1254) (254) STARTER (470)

15.875”
(403)
36”
( 914)

( 1067)
42”

56.375” 55” 7” 58.375”


(1432) (1397) (178) (1483)

INLET END VIEW ACCESS SIDE ELEVATION OUTLET END VIEW

EXTERNAL STATIC PRESSURE TO ECOLOAIRTM SYSTEM

1.0” 1.5” 2.0” 2.5” 3.0” 3.5” 4.0” 4.5”


MODEL
BHP BHP BHP BHP BHP BHP BHP BHP
NUMBER RPM RPM RPM RPM RPM RPM RPM RPM
HP KW HP KW HP KW HP KW HP KW HP KW HP KW HP KW

4400 1789 2.77 2.07 1902 3.22 2.40 2009 3.67 2.74 2111 4.13 3.08 2207 4.60 3.43 2299 5.08 3.79 2388 5.57 4.16 2473 6.07 4.53

B6 5200 1978 3.86 2.88 2081 4.37 3.26 2179 4.89 3.65 2273 5.42 4.04 2363 5.95 4.44 2450 6.49 4.84 2534 7.04 5.25 2614 7.6 5.67

6000 2170 5.18 3.86 2263 5.76 4.30 2352 6.35 4.74 2439 6.94 5.18 2524 7.54 5.62 2605 8.14 6.07 2684 8.76 6.53 2761 9.37 6.99

Continuous product improvement is a Halton policy, therefore specifications and designs are subject to change without notice.

6000CFM - EcoloAir Unit 4