75W Single Output Switching Power Supply SCP-75 series
■
‧
‧
‧
‧
‧
‧
‧
‧
■ ‧
https://www.meanwell.com/serviceGTIN.aspx ‧
SPECIFICATION UL62368-1 TPTC004 IEC62368-1
MODEL SCP-75-12 SCP-75-24
DC VOLTAGE 13.8V 27.6V
RATED CURRENT 5.4A 2.7A
CURRENT RANGE 0 ~ 5.4A 0 ~ 2.7A
PEAK 5S Note.6 6.5A 3.2A
RATED POWER 74.5W 74.5W
RIPPLE & NOISE (max.) Note.2 120mVp-p 200mVp-p
OUTPUT
VOLTAGE ADJ. RANGE +15,-5% +15,-5%
VOLTAGE TOLERANCE Note.3 ±2.0% ±1.0%
LINE REGULATION Note.4 ±1.0% ±1.0%
LOAD REGULATION Note.5 ±2.0% ±1.0%
SETUP, RISE TIME 600ms, 30ms/230VAC 1200ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.) 50ms/230VAC 16ms/115VAC at full load
VOLTAGE RANGE 85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE 47 ~ 63Hz
EFFICIENCY (Typ.) 80% 84%
INPUT
AC CURRENT (Typ.) 1.5A/115VAC 0.9A/230VAC
INRUSH CURRENT (Typ.) COLD START 45A
LEAKAGE CURRENT <2mA / 240VAC
TEMP. COMPENSATION By NTC (not provide with the power supply)
FUNCTION
OUTPUT VOLTAGE SENSOR L=output voltage +0.2 ~ 0.7V(AC OK); L=0V(AC Fail)
6.5 ~ 8.7A rated output power 3.2 ~ 4.3A rated output power
OVERLOAD
Protection type : Hiccup mode, recovers automatically after fault condition is removed
PROTECTION
16.6 ~ 19.3V 33.1 ~ 38.6V
OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
WORKING TEMP. -20 ~ +60℃ (Refer to output load derating curve)
WORKING HUMIDITY 20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.05% /℃ (0 ~ 45℃)
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
SAFETY STANDARDS UL62368-1, CB(IEC62368-1), EAC TP TC 004 approved, Design refer to BS EN/EN62368-1
SAFETY & WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2.0KVAC O/P-FG:0.5KVAC
EMC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
(Note 6) Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,3, EAC TP TC 020
EMC EMISSION
Compliance to BS EN/EN61000-4-2, 3, 4, 5, 6, 8,11, BS EN/ENV50204, BS EN/EN55035, BS EN/EN61000-6-1, light industry level,
EMC IMMUNITY
EAC TP TC 020
MTBF 2775.7K hrs min. Telcordia SR-332 (Bellcore) ; 461.3K hrs min. MIL-HDBK-217F (25℃)
OTHERS DIMENSION 159*97*38mm (L*W*H)
PACKING 0.5Kg; 30pcs/16Kg/1CUFT
℃
NOTE μFμF
(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
℃℃
※:https://www.meanwell.com/serviceDisclaimer.aspx
File Name:SCP-75-SPEC 2024-02-23
75W Single Output Switching Power Supply SCP-75 series
Mechanical Specification Case No. 901 Unit:mm
152.5
7
1
3.5
FS1
F4A/250V
TB1 2
400 3 FS2
65
F10A/250V
RED(B+) B+
L
BLACK(B-) B- (-V)
84.5
97
-V (B-)
+V =4
ORANGE(+V) 3L
BLACK(-V) TB2
1 2-M
YELLOW(L) 2
SVR1
CN2
LED
Terminal Pin No. Assignment (TB1)
Pin No. Assignment .5
ψ3
1 AC/L 4.5
2 AC/N 78
24
3 FG
159
Terminal Pin No. Assignment (TB2) 6.5 150
Pin No. Assignment
1 DC OUTPUT +V
9
9
2 DC OUTPUT -V
18.5
3-
ψ
M3
3.5
3.5
38
CN2 : JST B2B-XH or equivalent
18
L=
28.5
6
Mating Housing Terminal
JST XHP JST SXH-001T-P0.6
or equivalent or equivalent
22 117
Block Diagram
fosc : 60KHz
L
B+
RECTIFIERS POWER RECTIFIERS +V
EMI
I/P & SWITCHING &
FILTER -V
FILTER FILTER
B-
DETECTION
FG
CIRCUIT
O.L.P. CONTROL
O.V.P.
Derating Curve Output Derating VS Input Voltage
Ta=25℃
100
100
90
80
80
60 70
LOAD (%)
LOAD (%)
60
40
50
20
40
-20 0 10 20 30 40 50 60 70 (HORIZONTAL) 85 95 100 115 120 140 160 180 200 220 240 264
AMBIENT TEMPERATURE (℃) INPUT VOLTAGE (VAC) 60Hz
File Name:SCP-75-SPEC 2024-02-23
75W Single Output Switching Power Supply SCP-75 series
Function Description
1.B+,B-
Connect the battery : B+ connected to battery positive.
B- connected to battery negative.
2.L
Output voltage detection, detect output voltage or battery voltage ( if battery is used).
Voltage of L Pin
AC OK Output voltage +0.2~0.7V(depends on Vf of diode)
AC Fail 0V
3.+V,-V
Output voltage. Can't connect the battery.
4.CN2
Temperature sensor can be connected to the unit to allow temperature compensation of the charging voltage.
If the sensor is not used, the charger still works normally.
Reference example: (Under rated DC output voltage)
Connect 100KΩ Thermistor(THINKING) on NTC. The output voltage will change along
with the temperature change. If the output voltage is adjusted other than the rated value by internal potential meter,
please consult Meanwell for suitable value of Thermistor.
Ta :0℃ Ta :25℃ Ta :50℃
SCP-75-12 14.4±0.2V 13.8±0.1V 13.2±0.2V
SCP-75-24 29.3±0.4V 27.6±0.2V 26.4±0.4V
29.3
27.6 (24V)
26.4
14.4
13.8 (12V)
13.2
(℃)
0 25 50
Temperature Sensor
File Name:SCP-75-SPEC 2024-02-23