Powerflex 6000 Medium Voltage Variable Frequency Drive Commissioning Manual
Powerflex 6000 Medium Voltage Variable Frequency Drive Commissioning Manual
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
                              WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
                              which may lead to personal injury or death, property damage, or economic loss.
                              ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
                              damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
                              SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
                              voltage may be present.
                              BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
                              reach dangerous temperatures.
                              ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
                              potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
                              Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, Rockwell Automation, PowerFlex, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
                                                                                                                                         Table of Contents
Preface                                   Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
                                          Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
                                          What Is Not in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
                                          Required Supplemental Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
                                              Dimensional Drawings and Electrical Drawings. . . . . . . . . . . . . . . . . . . 7
                                              Shipping, Handling, and Installation Manual . . . . . . . . . . . . . . . . . . . . . 8
                                          General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
                                          Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
                                          Chapter 1
Introduction                              Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   11
                                          Documentation and Application Review . . . . . . . . . . . . . . . . . . . . . . . . . . .                                 12
                                             Review all Rockwell Automation Supplied Documentation . . . . . .                                                       12
                                             Pre-commissioning Customer Meeting . . . . . . . . . . . . . . . . . . . . . . . . .                                    13
                                             Review Drive Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                      13
                                          Chapter 2
Preparation and Inspection (For IEC)      Gather Required Tools and Test Equipment . . . . . . . . . . . . . . . . . . . . . . .                                     15
                                          Lockout and Tagout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              15
                                          Inspect Drive Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     16
                                          Functional Assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                17
                                          Interconnection Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 20
                                          Installation Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          21
                                              Mechanical Installation Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . .                            21
                                              Electrical Installation Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                        22
                                              Power Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            22
                                              Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             23
                                          Drive Megger Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               23
                                              Isolate the Power and Control Circuits. . . . . . . . . . . . . . . . . . . . . . . . .                                23
                                              Connect the Insulation Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                         27
                                          Final Steps before Equipment is Ready for Energization . . . . . . . . . . . . .                                           29
                                              Seal the Cabinet Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                29
                                          Chapter 3
Preparation and Inspection (For UL)       Gather Required Tools and Test Equipment . . . . . . . . . . . . . . . . . . . . . . .                                     31
                                          Lockout and Tagout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              31
                                          Inspect Drive Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     32
                                          Functional Assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                33
                                          Interconnection Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 36
                                          Installation Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          37
                                              Mechanical Installation Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . .                            37
                                              Electrical Installation Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                        38
                                              Power Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            38
                                              Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             39
                         Chapter 4
Commissioning            Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   47
                         Control System Check Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   48
                             Simulate Closed Input Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . .                              48
                             Energize Control Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 48
                         Control System Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              52
                             Verify Factory Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                      52
                             Set P Parameters to Enable Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . .                          55
                             Verify Settings for Low-Voltage Testing . . . . . . . . . . . . . . . . . . . . . . . .                              58
                             Verify Operation of Frequency Steps . . . . . . . . . . . . . . . . . . . . . . . . . . .                            63
                             Verify Operation to Set Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                          65
                             Simulate Warnings and Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                       67
                             Verify E-Stop Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    72
                             Verify Switching from Local Control to Remote Control . . . . . . . .                                                73
                             Verify Operation of Input/Output and Bypass Isolation Switches
                             (Manual Bypass). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           74
                             Verify Operation of Input/Output and Bypass Contactors
                             (Automatic Bypass) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             77
                             Verify Operation of DCS Input and Output Signals . . . . . . . . . . . . .                                           83
                             Restore P Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     84
                         Set Date and Time Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               86
                             Access T Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              86
                             Change Time/Date/Regional Settings. . . . . . . . . . . . . . . . . . . . . . . . . .                                87
                         Chapter 5
No-load Test             Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
                         No-load Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
                             Energize Drive Control Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
                             Configure P and T Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
                             Change Parameters T11...T13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
                             Close Isolation Switches in Bypass Cabinet . . . . . . . . . . . . . . . . . . . . 102
                             Close Input Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
                             Check Cooling Fan Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
                             Operate Motor by HMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
                         Load Test of Drive System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
                         Appendix A
Torque Requirements      Torque Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
                                                     Appendix B
Single Line Diagrams                                  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
                                                     Appendix C
Special Function Parameter Settings Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
                                                     System Setting Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     117
                                                         Number of Power Modules Per Phase . . . . . . . . . . . . . . . . . . . . . . . . .                                      117
                                                         Switch Control Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                       118
                                                         Rated/Maximum Output Frequency . . . . . . . . . . . . . . . . . . . . . . . . . .                                       118
                                                         Motor Parameter Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                         118
                                                         Hall Effect Current Sensor Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . .                                118
                                                         Analog Output Display Parameter Setting . . . . . . . . . . . . . . . . . . . . .                                        119
                                                         Restore Factory Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                      119
                                                     Speed Command Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                           120
                                                         Set Frequency Command Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                   120
                                                         Set Frequency Correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                         120
                                                         Frequency Command Deadband Upper Limit . . . . . . . . . . . . . . . . .                                                 120
                                                         Frequency Amplitude Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                            121
                                                         Frequency Skip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                121
                                                     Speed Reference Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                       122
                                                         V/F Curve Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   122
                                                         Set Maximum Modulation Index and Limit Output Voltage
                                                         Amplitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            122
                                                         Set Flux Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              122
                                                     Analog Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           123
                                                     Stop Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          123
                                                     Flying Start Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                123
                                                     Restart the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            124
Index
Notes:
Who Should Use This Manual      This manual is intended for Rockwell Automation Field Service Engineers with
                                Medium Voltage Drive factory training and field experience commissioning
                                medium voltage solid-state variable speed drive equipment.
                                                     WARNING: This document is for internal use only (for Rockwell CSM/field
                                                     support Engineers). DO NOT disclose this document to customers or any non-
                                                     Rockwell Automation employee. Disclosure of sensitive information in this
                                                     document may cause dire consequences to the drive.
What Is Not in This Manual      This manual is generic and does not include project-specific or drive-specific
                                information. Contact the Start-up Project Manager for required project-specific
                                or drive-specific information such as:
                                    • Dimensional Drawings and Electrical Drawings generated for the
                                       customer’s order.
                                    • Spare parts lists compiled for the customer’s order.
                                    • Drive-specific technical specifications.
                                    • Pre-commissioning Checklist
                                    • PLC program for standard, integral PLC
             If the drawings require changes to suit the installation and application of the
             system, fax or e-mail the marked up drawings to the Start-up Project Manager.
General Precautions                          ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts
                                             and assemblies. Static control precautions are required when installing, testing,
                                             servicing or repairing this assembly. Component damage may result if ESD
                                             control procedures are not followed. If you are not familiar with static control
                                             procedures, reference Allen-Bradley publication 8000-4.5.2, “Guarding Against
                                             Electrostatic Damage” or any other applicable ESD protection handbook.
Additional Resources      These documents contain additional information concerning related products
                          from Rockwell Automation.
                           Resource                                                    Description
                           Industrial Automation Wiring and Grounding Guidelines,      Provides general guidelines for installing a Rockwell
                           publication 1770-4.1                                        Automation industrial system.
                           Product Certifications website, http://www.ab.com           Provides declarations of conformity, certificates, and
                                                                                       other certification details.
Notes:
Introduction
              Prior to commissioning, the following work will have been performed by the
              customer or the customer’s electrical contractor:
              (2) Interconnection of power cables and low voltage control wiring bundles, between separately shipped cabinets, can be done by the
                  contractor or Rockwell Automation. The commissioning quote from Rockwell Automation reflects this and will contain two options:
                  a) the base quote, reflecting the power cable and control wiring interconnection work being done by the contractor
                  b) the optional quote adder, reflecting the additional time and cost for Rockwell Automation to perform the power cable and
                  control wiring interconnection work immediately prior to the commissioning process.
              This work will be reviewed during the pre-commissioning customer meeting and
              validated during the commissioning process; see Installaion Review on page 21 or
              page 37.
                                                               Process Flowcharts
Documentation and Application Review
         Review
        Rockwell
                              Pre-commissioning            Review Drive
      Automation
                              Customer Meeting              Application
        Supplied
     Documentation
    Gather
 Required Tools           Lockout              Inspect Drive          Functional         Interconnection        Installation                Final Review
                                                                                                                               Meggering
   and Test              and Tagout            Components             Assessment             Review               Review                   and Preparation
  Equipment
Commissioning
                                No-load Test
        Control                                            Load Test of
                                  of Drive
     System Check                                          Drive System
                                  System
       (LV Only)                                               (MV)
                                   (MV)
                                                               Before commissioning the drive, ensure you have the following resources:
                                                                  • Project-specific Electrical Drawings and Dimensional Drawings
                                                                  • PowerFlex 6000 Medium Voltage Variable Frequency Drive Shipping,
                                                                     Handling, and Installation Manual 6000-IN006_-EN-P): provides
                                                                     procedural information for physically unloading, moving, and installing
                                                                     equipment
                                                                  • PowerFlex 6000 Medium Voltage Variable Frequency Drive
                                                                     Commissioning Manual (6000-IN007_-EN-P): required procedures and
                                                                     checklists for Rockwell Automation Field Service Engineers.
                                                                  • PowerFlex 6000 Medium Voltage Variable Frequency Drive User Manual
                                                                     (6000-UM002_-EN-P): instructions for daily recurring drive usage, HMI
                                                                     interface, and maintenance tasks
        • PLC Program: The PLC I/O processes control signals within the drive
          and I/O signals to and from the customer’s control system and input
          circuit breaker. The PLC program is standardized. However, it may be
          customized to address specific customer requirements by Rockwell
          Automation during the Application Engineering phase of order execution.
                                                 ATTENTION: Make sure the medium voltage input circuit breaker feeding the
                                                 drive is locked out and tagged out. Make sure the LV circuit breaker feeding
                                                 control power to the drive is locked out and tagged out. Make sure the drive is
                                                 de-energized before conducting the drive inspection process.
                              Once all documentation has been reviewed, an on-site inspection of the drive is
                              required. Identify the physical locations of the connections to the drive using Tag
                              Identification names or numbers from the one-line diagram and Rockwell
                              Automation Electrical Drawings.
                              All customer power and control wiring required for the drive line-up installation
                              has been identified on the Rockwell Automation Electrical Drawings by a dashed
                              line.
                              Installation of all external power cabling and control wiring interfacing with the
                              drive is completed by the customer or their electrical contractor. Verify that this
                              wiring is installed correctly and meets electrical voltage and current capacity
                              requirements. Trace the power cables point-to-point from the input circuit
                              breaker to the drive, and from the drive to the motor using the Electrical
                              Drawings as a reference for proper drive power cable termination locations. Any
                              discrepancy between the physical installation and the Electrical Drawings of the
                              following items should be reviewed prior to commissioning the drive:
                                  • Medium voltage power cabling in from the input circuit breaker to drive
                                  • Medium voltage power cabling out from drive to motor
                                  • Low Voltage control power cables from LV MCC or circuit breaker to
                                     drive
                                  • Ground connection from system ground to drive
                                  • Control signal wires and communication cables from remote DCS/PLC
                                     or other remote device to drive
                                  • Electrical safety interlock/control wiring from the drive to the input
                                     circuit breaker
                               Electrical Equipment
                                    •   High voltage gloves – 17 kV insulation rating (minimum)
                                    •   Anti-static strap
                                    •   Live-line tool (Hot stick)
                                    •   5 kV Insulation Tester
                               Test Equipment
                                    • 600V (1000V rating) digital multimeter with assorted clip leads
Lockout and Tagout                                SHOCK HAZARD: Servicing energized industrial control equipment can be
                                                  dangerous. Severe injury or death can result from electrical shock, burn, or
                                                  unintended actuation of control equipment. Hazardous voltages may exist in
                                                  the cabinet even with the input circuit breaker in the off position. Required
                                                  practice is to disconnect and lock out control equipment from power sources,
                                                  and confirm discharge of stored energy in capacitors. If it is necessary to work in
                                                  the vicinity of energized equipment, the safety related work practices outlined
                                                  in Electrical Safety requirements for Employee Work places must be followed.
                                                  Before attempting any work, verify the system has been locked out and tested
                                                  to have no potential.
                                                      Lockout and tagout the input circuit breaker before opening the doors to the
                                                      drive system cabinets. After the cabinet doors are opened, immediately test the
                                                      incoming and outgoing power cables and any components connected to medium
                                                      voltage with a live-line tool (hot stick) while wearing high voltage gloves. Pay
                                                      special attention to any capacitors connected to medium voltage that can retain a
                                                      charge for a period of time. Only after the equipment has been verified as isolated
                                                      and de-energized can subsequent work be performed. Even though the input to
                                                      the drive may be open, it is still possible for hazardous voltage to be present.
                                                      Refer to local safety guidelines for detailed procedures on how to safely isolate
                                                      the equipment from hazards.
                                                      Safety Test
                                                      Complete every point included in this section prior to continuing with the drive
                                                      commissioning, to ensure that the commissioning continues in an environment
                                                      safe to all those involved in servicing the drive. Ensure that commissioning of this
                                                      drive is performed in accordance with local safety standards.
Inspect Drive Components                              After performing the lockout and tagout procedure (see page 15), open all of the
                                                      cabinet doors. Inspect each component for signs of shipping damage (see Table 3
                                                      on page 18). An initial inspection would have been done by the customer when
                                                      the equipment was received. However, this would have been done from the front
                                                      only and was just looking for obvious signs of damage (see publication 6000-
                                                      IN006_-EN-P). Record the part number and description of any damaged
                                                      components and immediately contact the Start-up Project Manager to order
                                                      replacement components, if required.
                                                      Most components will be easily visible on the doors or from the front of the
                                                      cabinets after the doors are opened. Some components are best viewed from the
                                                      rear of the cabinet.
                                                      For rear inspection, remove top and bottom rear access plates from the drive and
                                                      bypass cabinet (if supplied). See publication 6000-IN006_-EN-P.
                                                        IMPORTANT            The Inspect Drive Components Checklist (see page 18) mentions the principal
                                                                             base components supplied in the drive and bypass units. It is not
                                                                             comprehensive, as customer-required options may be supplied and three
                                                                             different bypass configurations are available.
                                                                             Perform the shipping damage inspection for all components mounted in the
                                                                             drive cabinets and specific bypass unit cabinet (if supplied).
Functional Assessment      After the components are visually inspected to identify any shipping damage, a
                           thorough functional assessment should be performed (see Table 4 on page 19).
                           The main purpose of this assessment is to ensure that all movable parts and
                           assemblies operate properly, connect properly, and components are wired
                           properly and securely.
                           The Functional Assessment procedure can be combined with the “Inspect Drive
                           Components” checklist on page 18.
                                                                                      Bypass Cabinet (if supplied)                                 Isolation Transformer Cabinet                     Power Module Cabinet                                 Low Voltage Control Cabinet
                                                                                      Door:                                                        Door:                                             Fixed Mounted Power Module Configuration:            Door:
                                                                                      Pilot Lights                                               Transformer Temperature monitor                 Power Module retaining tabs                        Pilot lights
                                                                                      Voltage Indicator Relay                                    LV Cabinet components                           Check for debris                                   Push buttons
                                                                                      Cabinet:                                                        – Fan control circuit breakers                 Output Bus Supports                                Selector switches
                                                                                      Insulators                                                 Cabinet:                                          Fuse Mounting Supports                             HMI
                                                                                      Switch assemblies                                          Transformer Plastic Baffle                      Drawout Power Module Configuration:                  Interface board (on the back of the LV door)
                                                                                      Vacuum contactors                                          Outgoing Motor Power Cable standoffs on         Support frame                                      Panel:
                                                                                      Mechanical linkages                                        Cabinet Sidesheet(1)                              Power Modules                                      DIN rail mounted components
                                                                                                                                                   Outgoing Motor Power Cable Terminal                                                                  UPS
                                                                                                                                                                                                                                                                                                           Preparation and Inspection (For IEC)
19
                                                                                                                                                                                                                                                                                               Chapter 2
Chapter 2    Preparation and Inspection (For IEC)
Interconnection Review                                    The interconnection checklist summarizes the required items to review to
                                                          validate the reconnection of power, ground, and control cables between cabinets
                                                          within the drive system, that were disconnected for shipment. Power and control
                                                          cables that pass from one cabinet to another are bundled in the appropriate
                                                          cabinet. These cables are connected for system test at the factory but
                                                          disconnected and coiled up for shipment. If this interconnection work was done
                                                          by the contractor, use this checklist to review and ensure the work was done
                                                          correctly. If the interconnection work was not done by the contractor, the scope
                                                          of work required to be performed is described in 6000-IN006_-EN-P.
                                                          .
                                                              IMPORTANT            Check torque on all power and ground cable connections per specifications
                                                                                   listed in Torque Requirements on page 109.
Installation Review      Prior to commencing the commissioning of the drive, verify the equipment was
                         properly installed. Identifying errors in the drive installation prior to
                         commencing the commissioning as opposed to mid-way through the
                         commissioning process will greatly reduce the amount of time required to
                         commission the drive. Verify the drive and all associated equipment have the
                         system power grounding cable installed. Refer to 6000-IN006_-EN-P to review
                         the contractor’s drive installation responsibilities and understand the scope of the
                         work you will be reviewing.
                                                      Power Cabling
                                                      Trace the power cabling from termination point to termination point while
                                                      examining the cable and its routing for mechanical damage, sharp bend radiuses
                                                      and sources of induced noise and heat. The power cabling must be is sufficiently
                                                      braced to contain the cabling in the event of a ground fault. Color coding is used
                                                      to indicate the phase orientation of the drive.
                                                      Table 6 - Color Coding
                                                       Color               Incoming Line Side                         Outgoing Motor Side
                                                       Black               L11 (A Phase) Line Cable Terminal          U Phase:
                                                                                                                      • Power Module Bus
                                                                                                                      • VSB Input Cable
                                                                                                                      • Motor Cable Termination
                                                                                                                      • Motor Cable Connection to Power Module Bus
                                                       Brown               L12 (B Phase) Line Cable Terminal          V Phase:
                                                                                                                      • Power Module Bus
                                                                                                                      • VSB Input Cable
                                                                                                                      • Motor Cable Termination
                                                                                                                      • Motor Cable Connection to Power Module Bus
                                                       Grey                L13 (C Phase) Line Cable Terminal          W Phase:
                                                                                                                      • Power Module Bus
                                                                                                                      • VSB Input Cable
                                                                                                                      • Motor Cable Termination
                                                                                                                      • Motor Cable Connection to Power Module Bus
                        Incoming Line and Outgoing Motor cables must be routed separately to prevent
                        cable insulation damage.
                        All customer power cables must be Hi-Potted or Meggered and read a sufficient
                        insulation value. Review Hi-Pot or megger test report from the customer.
                        Control Wiring
                        Identify all customer-required control wiring detailed on the Electrical Drawings
                        and locate it within the terminal blocks. Verify the cable insulation is not
                        tightened in a terminal connection. All connections must have proper continuity.
                        Inspect the control cable routing to ensure that DC control wiring and AC
                        control wiring are separated from each other. Routing them together in the same
                        bundle or cabling product may result in unwanted noise being induced in the
                        drive control. In the overhead cable tray provided at the front of the drive, the AC
                        control, DC control and fiber optic cables must be separate. These cables may
                        also be from the bottom.
                        Perform a tug test on all control cables to ensure that they are securely fastened,
                        and check each plug and connector to ensure it is properly seated in its socket.
                            1. Isolate and lock out the drive system from any high voltage source.
                                 Disconnect any incoming power sources, medium voltage sources should
                                 be isolated and locked out and all control power sources should be turned
                                 off at their respective circuit breaker(s).
                                 Verify with a potential indicator that power sources have been
                                 disconnected, and that the control power in the drive is de-energized.
                                                          2. Disconnect four 380V AC cables (a, b, c, and o cables) from the bottom of
                                                             the Isolation Transformer.
                                                          3. Disconnect the Voltage Sensing Board Output Cable. Keep the plug at
                                                             least 100 mm away from the Voltage Sensing Board.
                                       7. Remove two star connection cables (the cabling that goes through the
                                          HECS) and connect them to the output connections of any two power
                                          modules within a phase.
                                                                                                                             HECS
                                                                                                                   (located at the top of the
                                                                                                                      power unit cabinet)
Control Cable
     10. Remove the Analog Interface board and disconnect all of the terminals
         from the Control Unit.
       1. Connect the red wire from the insulation meter to the U Phase and the
          black wire to the grounding bus.
Insulation Meter
Final Steps before                             1. Review interior of all cabinets for foreign material that might have been
                                                  left behind during the installation process. Ensure no tools, hardware, or
Equipment is Ready for                            wiring debris remain in the drive system cabinets. Clear any metal shavings
Energization                                      that may result from any drilling activities.
                                               2. If any internal barriers were removed during the commissioning process,
                                                  ensure they are reinstalled.
                                           Once the back plates have been reattached, the seams along the plates must be
                                           sealed with silicone. Where the silicone is applied is dependent on the cabinet
                                           configuration (Fixed-mounted or Drawout Power Module).
IMPORTANT Use the approved silicone that is shipped with the drive.
Notes:
                               Electrical Equipment
                                    •   High voltage gloves – 17 kV insulation rating (minimum)
                                    •   Anti-static strap
                                    •   Live-line tool (Hot stick)
                                    •   5 kV Insulation Tester
                               Test Equipment
                                    • 600V (1000V rating) digital multimeter with assorted clip leads
Lockout and Tagout                                SHOCK HAZARD: Servicing energized industrial control equipment can be
                                                  dangerous. Severe injury or death can result from electrical shock, burn, or
                                                  unintended actuation of control equipment. Hazardous voltages may exist in
                                                  the cabinet even with the input circuit breaker in the off position. Required
                                                  practice is to disconnect and lock out control equipment from power sources,
                                                  and confirm discharge of stored energy in capacitors. If it is necessary to work in
                                                  the vicinity of energized equipment, the safety related work practices outlined
                                                  in Electrical Safety requirements for Employee Work places must be followed.
                                                  Before attempting any work, verify the system has been locked out and tested
                                                  to have no potential.
                                                     Lockout and tagout the input circuit breaker before opening the doors to the
                                                     drive system cabinets. After the cabinet doors are opened, immediately test the
                                                     incoming and outgoing power cables and any components connected to medium
                                                     voltage with a live-line tool (hot stick) while wearing high voltage gloves. Pay
                                                     special attention to any capacitors connected to medium voltage that can retain a
                                                     charge for a period of time. Only after the equipment has been verified as isolated
                                                     and de-energized can subsequent work be performed. Even though the input to
                                                     the drive may be open, it is still possible for hazardous voltage to be present.
                                                     Refer to local safety guidelines for detailed procedures on how to safely isolate
                                                     the equipment from hazards.
                                                     Safety Test
                                                     Complete every point included in this section prior to continuing with the drive
                                                     commissioning, to ensure that the commissioning continues in an environment
                                                     safe to all those involved in servicing the drive. Ensure that commissioning of this
                                                     drive is performed in accordance with local safety standards.
Inspect Drive Components                             After performing the lockout and tagout procedure (see page 31), open all of the
                                                     cabinet doors. Inspect each component for signs of shipping damage (see Table 8
                                                     on page 34). An initial inspection would have been done by the customer when
                                                     the equipment was received. However, this would have been done from the front
                                                     only and was just looking for obvious signs of damage (see publication 6000-
                                                     IN006_-EN-P). Record the part number and description of any damaged
                                                     components and immediately contact the Start-up Project Manager to order
                                                     replacement components, if required.
                                                     Most components will be easily visible on the doors or from the front of the
                                                     cabinets after the doors are opened. Some components are best viewed from the
                                                     rear of the cabinet.
                                                     For rear inspection, remove top and bottom rear access plates from the drive and
                                                     bypass cabinet (if supplied). See publication 6000-IN006_-EN-P.
                                                       IMPORTANT            The Inspect Drive Components Checklist (see page 34) mentions the principal
                                                                            base components supplied in the drive and bypass units. It is not
                                                                            comprehensive, as customer-required options may be supplied and three
                                                                            different bypass configurations are available.
                                                                            Perform the shipping damage inspection for all components mounted in the
                                                                            drive cabinets and specific bypass unit cabinet (if supplied).
Functional Assessment      After the components are visually inspected to identify any shipping damage, a
                           thorough functional assessment should be performed (see Table 9 on page 35).
                           The main purpose of this assessment is to ensure that all movable parts and
                           assemblies operate properly, connect properly, and components are wired
                           properly and securely.
                           The Functional Assessment procedure can be combined with the “Inspect Drive
                           Components” checklist on page 34.
                                                                                      Bypass Cabinet (if supplied)                                 Isolation Transformer Cabinet                     Power Module Cabinet                                 Low Voltage Control Cabinet
                                                                                      Door:                                                        Door:                                             Fixed Mounted Power Module Configuration:            Door:
                                                                                      Pilot Lights                                               Transformer Temperature monitor                 Power Module retaining tabs                        Pilot lights
                                                                                      Voltage Indicator Relay                                    LV Cabinet components                           Check for debris                                   Push buttons
                                                                                      Cabinet:                                                        – Fan control circuit breakers                 Output Bus Supports                                Selector switches
                                                                                      Insulators                                                 Cabinet:                                          Fuse Mounting Supports                             HMI
                                                                                      Switch assemblies                                          Transformer Plastic Baffle                      Voltage Sensing Board                              Interface board (on the back of the LV door)
                                                                                      Vacuum contactors                                          Outgoing Motor Power Cable standoffs on         Drawout Power Module Configuration:                  Panel:
                                                                                      Mechanical linkages                                        Cabinet Sidesheet(1)                              Support frame                                      DIN rail mounted components
                                                                                                                                                   Outgoing Motor Power Cable Terminal             Power Modules                                      UPS
                                                                                                                                                                                                                                                                                                           Preparation and Inspection (For UL)
                                                                 Front
                                                                                                                                                   Insulators on transformer (1)                                                                          Fiber optic cables
                                                                                                                                                   Incoming Line Power Cable Terminal Insulators                                                        PLC
                                                                                                                                                   on transformer                                                                                         Control Unit
                                                                                                                                                   Motor Cable Braces
                                                                                                                                                   Fixed Mounted Power Module Configuration:
                                                                                                                                                   Transformer Secondary Windings (2 sets)
                                                                                                                                                      – Inspect nomex wrap
                                                                                                                                                      – Verify windings from core are undamaged
                                                                                                                                                      – Check for debris in top of core
                                                                                                                                                   Fixed Mounted Power Module Configuration:         Fixed Mounted Power Module:                          UPS connections
                                                                                                                                                   Transformer Secondary Windings (1)              Heat sink
                                                                 Rear                                                                                 – Inspect nomex wrap                              – Verify orientation relative to barrier plates
                                                                                                                                                      – Verify windings from core are undamaged
                                                                                                                                                      – Check for debris in top of core
                                                                (1) Motor Cable terminations could be on the transformer structure or cabinet sidesheet, depending on the power rating.
35
                                                                                                                                                                                                                                                                                             Chapter 3
Chapter 3    Preparation and Inspection (For UL)
Interconnection Review                                    The interconnection checklist summarizes the required items to review to
                                                          validate the reconnection of power, ground, and control cables between cabinets
                                                          within the drive system, that were disconnected for shipment. Power and control
                                                          cables that pass from one cabinet to another are bundled in the appropriate
                                                          cabinet. These cables are connected for system test at the factory but
                                                          disconnected and coiled up for shipment. If this interconnection work was done
                                                          by the contractor, use this checklist to review and ensure the work was done
                                                          correctly. If the interconnection work was not done by the contractor, the scope
                                                          of work required to be performed is described in 6000-IN006_-EN-P.
                                                          .
                                                              IMPORTANT            Check torque on all power and ground cable connections per specifications
                                                                                   listed in Torque Requirements on page 109.
Installation Review      Prior to commencing the commissioning of the drive, verify the equipment was
                         properly installed. Identifying errors in the drive installation prior to
                         commencing the commissioning as opposed to mid-way through the
                         commissioning process will greatly reduce the amount of time required to
                         commission the drive. Verify the drive and all associated equipment have the
                         system power grounding cable installed. Refer to 6000-IN006_-EN-P to review
                         the contractor’s drive installation responsibilities and understand the scope of the
                         work you will be reviewing.
                                                     Power Cabling
                                                     Trace the power cabling from termination point to termination point while
                                                     examining the cable and its routing for mechanical damage, sharp bend radiuses
                                                     and sources of induced noise and heat. The power cabling must be is sufficiently
                                                     braced to contain the cabling in the event of a ground fault. Color coding is used
                                                     to indicate the phase orientation of the drive.
                                                     Table 11 - Color Coding (UL)
                                                      Color               Incoming Line Side                         Outgoing Motor Side
                                                      Black               L1 (A Phase) Line Cable Terminal           U Phase:
                                                                                                                     • Power Module Bus
                                                                                                                     • VSB Input Cable
                                                                                                                     • Motor Cable Termination
                                                                                                                     • Motor Cable Connection to Power Module Bus
                                                      Red                 L2 (B Phase) Line Cable Terminal           V Phase:
                                                                                                                     • Power Module Bus
                                                                                                                     • VSB Input Cable
                                                                                                                     • Motor Cable Termination
                                                                                                                     • Motor Cable Connection to Power Module Bus
                                                      Blue                L3 (C Phase) Line Cable Terminal           W Phase:
                                                                                                                     • Power Module Bus
                                                                                                                     • VSB Input Cable
                                                                                                                     • Motor Cable Termination
                                                                                                                     • Motor Cable Connection to Power Module Bus
                        Incoming Line and Outgoing Motor cables must be routed separately to prevent
                        cable insulation damage.
                        All customer power cables must be Hi-Potted or Meggered and read a sufficient
                        insulation value. Review Hi-Pot or megger test report from the customer.
                        Control Wiring
                        Identify all customer-required control wiring detailed on the Electrical Drawings
                        and locate it within the terminal blocks. Verify the cable insulation is not
                        tightened in a terminal connection. All connections must have proper continuity.
                        Inspect the control cable routing to ensure that DC control wiring and AC
                        control wiring are separated from each other. Routing them together in the same
                        bundle or cabling product may result in unwanted noise being induced in the
                        drive control. In the overhead cable tray provided at the front of the drive, the AC
                        control, DC control and fiber optic cables must be separate. These cables may
                        also be from the bottom.
                        Perform a tug test on all control cables to ensure that they are securely fastened,
                        and check each plug and connector to ensure it is properly seated in its socket.
                            1. Isolate and lock out the drive system from any high voltage source.
                                 Disconnect any incoming power sources, medium voltage sources should
                                 be isolated and locked out and all control power sources should be turned
                                 off at their respective circuit breaker(s).
                                 Verify with a potential indicator that power sources have been
                                 disconnected, and that the control power in the drive is de-energized.
                                                         2. Disconnect four 380V AC cables (a, b, c, and o cables) from the bottom of
                                                            the Isolation Transformer.
                                                         3. Disconnect the Voltage Sensing Board Output Cable. Keep the plug at
                                                            least 100 mm away from the Voltage Sensing Board.
                                                         7. Remove two star connection cables (the cabling that goes through the
                                                            HECS) and connect them to the output connections of any two power
                                                            modules within a phase.
Control Cable
                                                                                                                                   HECS
                                                                                                                         (located on the right side
                                                                                                                         of the power unit cabinet
                                  10. Remove the Analog Interface board and disconnect all of the terminals
                                      from the Control Unit.
                                                         1. Connect the red wire from the insulation meter to the U Phase and the
                                                            black wire to the grounding bus.
Insulation Meter
Final Steps before                                            1. Review interior of all cabinets for foreign material that might have been
                                                                 left behind during the installation process. Ensure no tools, hardware, or
Equipment is Ready for                                           wiring debris remain in the drive system cabinets. Clear any metal shavings
Energization                                                     that may result from any drilling activities.
                                                              2. If any internal barriers were removed during the commissioning process,
                                                                 ensure they are reinstalled.
                                                          Once the back plates have been reattached, the seams along the plates must be
                                                          sealed with silicone. Where the silicone is applied is dependent on the cabinet
                                                          configuration (Fixed-mounted or Drawout Power Module).
IMPORTANT Use the approved silicone that is shipped with the drive.
Commissioning
Introduction
                                         ATTENTION: The Control System Check requires LV Control power only. The
                                         Input Circuit Breaker must remain locked out and tagged out for this procedure.
                  A number of activities are required before the Control System Check can be
                  performed.
                   Procedure                                                                                 Page
                   Simulate Closed Input Circuit Breaker                                                     48
                   Energize Control Circuit                                                                  48
                   Procedure                                                                                  Page
                   Verify Factory Default Settings                                                            52
                   Set P Parameters to Enable Testing                                                         55
                   Verify Settings for Low-Voltage Testing                                                    58
                   Verify Operation of Frequency Steps                                                        63
                   Verify Operation to Set Frequency                                                          65
                   Simulate Warnings and Faults                                                               65
                   Verify E-Stop Functionality                                                                72
                   Verify Switching from Local Control to Remote Control                                      73
                   Verify Operation of Input/Output and Bypass Isolation Switches (Manual Bypass)(1)          74
                                                                                               (1)
                   Verify Operation of Input/Output and Bypass Contactors (Automatic Bypass)                  77
                   Verify Operation of DCS Input and Output Signals                                           83
                   Restore P Parameter Settings                                                               84
                  (1) Only required if a bypass configuration is supplied.
                                  IMPORTANT            The “normal” operating mode is for the input circuit breaker to be closed.
                                                       Install a temporary jumper (X1-117, X1-119) in the LV Control Cabinet to
                                                       simulate operating the system in “normal” mode (input circuit breaker closed)
                                                       to allow the Control System Check process to proceed.
                                                       Refer to Electrical Drawings.
                                Control power voltage used in the control circuit is nominally 220V and referred
                                to in the example. The control circuit can directly accommodate other widely
                                used voltages of 230V and 240V also. If 110V or 120V is the control power
                                voltage supplied by the customer, a control power transformer is supplied in the
                                LV control cabinet to step up the customer supplied control power to 220V
                                (Figure 24). This must be specified at time of order.
                                Test points indicated in the instructions are at the circuit breaker terminals, not at
                                the terminal blocks.
                                Circuit breaker device designation labels (Q1 (CB1), Q2 (CB2), etc.) are affixed
                                to the device mounting surfaces.
                                                                                                            Control Power
                                                                                                            Transformer
                                                                                                            UPS
                                                          FRONT
1 3 5
                                                                          Q1 Q2 Q3 Q5 Q6
                                                                         (CB1) (CB2) (CB3) (CB5) (CB6)
2 4 6
Q4 Q7
     Start UPS      Before pressing the ON button, withdraw the Type I UPS             Verify that UPS operates normally and that the        UPS feeds control power to the circuits supplied
     (Press ON      power plug from the power receptacle (XS2). Verify that the        UPS output is AC220V. The output of the UPS is        by the Q2 and Q3 circuit breakers.
     button)        input voltage of the XS2 receptacle is AC220V. Verify that the     connected to the input of Q2 and Q3. The UPS
                    PE connection of the XS2 receptacle is properly grounded.          output voltage can be checked at the input of Q2
                    Plug the UPS into the receptacle. Press and hold the ON            or Q3 (1 is L, 3 is N).
                    button for 3 seconds to turn on the UPS (all status lights on
                    the UPS will be green).
     Close          Verify that the input voltage at the Q2 circuit breaker is         Verify that the input voltage of power supplies is    Q2 connects control power directly to AC/DC
     Breaker Q2     AC220V (1 is L, 3 is N). Ignore if done in “Start UPS” step.       AC220V (L-N). Refer to Figure 27. Verify that the     power supplies (G1, G2, and G3), PLC, HMI, and
                    Verify output is not shorted (2 and 4).                            PLC, HMI, and Control Unit power up.                  Control Unit
     Close          Verify that the input voltage at the Q3 circuit breaker is         Verify that the output voltage is AC220V (2 is L, 4   Q3 connects control power to PLC I/O and control
     Breaker Q3     AC220V (1 is L, 3 is N). Ignore if done in “Start UPS” step.       is N). Verify CLOSED state (5 and 6). Verify that     relays.
                    Verify output is not shorted (2 and 4). Verify OPEN state (5       the PLC I/O status lights and control relay red
                    and 6).                                                            indicating lights illuminate.
     Close          Control power is fed from the isolation transformer tertiary       Verify closed status (1 and 2).                       Q4 connects control power from isolation
     Breaker Q4     winding for the Q4 circuit breaker, therefore not present for                                                            transformer tertiary winding to bottom-
                    this test. A two pole breaker is supplied for lower power                                                                mounted auxiliary fans (6).
                    drives (220V powered auxiliary fans). A three pole breaker is
                    supplied for higher power drives (380V power auxiliary
                    fans). Verify open status (1 and 2) and output not shorted (2
                    and 4).
     Close          Control power is fed from the isolation transformer tertiary       Verify closed status (1 and 2).                       Q5 connects back-up control power from
     Breaker Q5     winding for the Q5 circuit breaker, therefore not present for                                                            isolation transformer tertiary winding to switch
                    this test. Verify open status (1 and 2) and output not shorted                                                           to the control circuit (UPS) if the main (customer-
                    (2 and 4).                                                                                                               supplied) control power is lost.
     Close          Verify that the input voltage at the Q6 circuit breaker is       Verify that the output voltage is AC220V (2 is L, 4     Q6 connects control power to door mounted pilot
     Breaker Q6     AC220V (1 is L, 3 is N). Verify output is not shorted (2 and 4). is N). Verify that the LV Door pilot lights             lights and spare relays for DCS.
                                                                                     illuminate.
     Close          Verify that the input voltage at the Q7 circuit breaker is       Verify that the output voltage is AC220V (2 is L, 4     Q7 connects control power to isolation
     Breaker Q7     AC220V (1 is L, 3 is N). Verify output is not shorted (2 and 4). is N). Verify that the Isolation Transformer            transformer temperature monitor
                                                                                     temperature monitor powers up.
     Start UPS   Before pressing the ON button, withdraw the Type I UPS                Verify that UPS operates normally and that the        UPS feeds control power to the circuits supplied
     (Press ON   power plug from the power receptacle (XS2). Verify that the           UPS output is AC220V. The output of the UPS is        by the CB2 and CB3 circuit breakers.
     button)     input voltage of the XS2 receptacle is AC220V. Verify that the        connected to the input of CB2 and CB3. The UPS
                 PE connection of the XS2 receptacle is properly grounded.             output voltage can be checked at the input of
                 Plug the UPS into the receptacle. Press and hold the ON               CB2 or Q3 (1 is L, 3 is N).
                 button for 3 seconds to turn on the UPS (all status lights on
                 the UPS will be green).
     Close       Verify that the input voltage at the CB2 circuit breaker is           Verify that the input voltage of power supplies is    CB2 connects control power directly to AC/DC
     Breaker CB2 AC220V (1 is L, 3 is N). Ignore if done in “Start UPS” step.          AC220V (L-N). Refer to Figure 27. Verify that the     power supplies (G1, G2, and G3), PLC, HMI, and
                 Verify output is not shorted (2 and 4).                               PLC, HMI, and Control Unit power up.                  Control Unit
  Close       Verify that the input voltage at the CB6 circuit breaker is      Verify that the output voltage is AC220V (2 is L, 4    CB6 connects control power to door mounted
  Breaker CB6 AC220V (1 is L, 3 is N). Verify output is not shorted (2 and 4). is N). Verify that the LV Door pilot lights            pilot lights and spare relays for DCS.
                                                                               illuminate.
  Close       Verify that the input voltage at the CB7 circuit breaker is      Verify that the output voltage is AC220V (2 is L, 4    CB7 connects control power to isolation
  Breaker CB7 AC220V (1 is L, 3 is N). Verify output is not shorted (2 and 4). is N). Verify that the Isolation Transformer           transformer temperature monitor
                                                                               temperature monitor powers up.
NL NL
The default Language setting and bypass mode are set before shipment.
                                 IMPORTANT            You can change the language but cannot change the bypass mode, as this is set
                                                      at the factory to match the shipped drive configuration.
                                   2. In the Languages dialog box, select the language you want and press
                                                         .
                                                                                            Manual Bypass
                                                                                            Two Cabinets
                                                                                            Automatic Bypass
                                                                                            Two Cabinets
   There are two specific “P” parameters that must be changed to allow the Control
   System Check to proceed.
   This section is password protected and the setup login process must be
   completed before making any changes.
                                   4. Press                    to login.
                                        The Current User will now display Setup, indicating appropriate access has
                                        been granted.
IMPORTANT If the login information was incorrect, you will be prompted to login again.
Set P Parameters
                               Once the appropriate access has been granted, you can now select and change
                               parameters.
                               For the simulation tests, you only need to change two parameters: P007 and
                               P224.
           TIP            When the “P” Parameter number is pressed (e.g. P007), the description
                          appears in the information box at the bottom of the screen.
   .
                                 IMPORTANT            Before performing high-voltage testing, the “Power Loss” setting must be
                                                      restored to the unshielded state.
       4. Press                    to login.
            The Current User will now display RD, indicating appropriate access has
            been granted.
IMPORTANT If the login information was incorrect, you will be prompted to login again.
Set P Parameters
   Once the appropriate access has been granted, you can now select and change
   parameters.
                               For UL Standard
                                    7. Press                         to change the button to                            .
                               .
                                   IMPORTANT          After the end of the simulation tests, the “Power Loss” setting must be restored
                                                      to the unshielded state.
   There are two parts to this procedure, increasing the frequency in set increments
   and increasing the frequency to a specific rated frequency.
           TIP            During the Control System Check procedure, an “Abnormal Output Voltage
                          Warning” will appear, as the procedure is done without MV and the Control
                          System is expecting an output voltage. Ignore this warning for this procedure.
1. From the Main Interface Screen, press the Set Frequency: input field.
2. In the Set Freq: dialog box, enter a value of “10” and press .
Press to confirm.
           TIP            The Set Frequency and Actual Frequency occasionally will not show the exact
                          integral value selected, due to internal data conversion in the HMI program.
                                 IMPORTANT            When the drive is ≥0.5 Hz, the “Connect” light will be illuminated. When the
                                                      speed of the drive surpasses 0.5 Hz, the “Connect” and “Running” lights will be
                                                      red. The “Warning” light will illuminate when the Actual Frequency increases
                                                      above 10.00 Hz. This is an internal function for testing purposes only.
                                       TIP            T Parameter T09 determines the value of the frequency step change. The
                                                      default is 1. Refer to Access T Parameters on page 86.
1. Press the Set Frequency: input field and enter “50” in the Set Freq: dialog
3. Once the actual frequency has reached the set frequency, press
   This section describes how to simulate warnings and faults, and how to clear or
   reset the alarm. Warning codes begin with a W prefix, and fault codes begin with
   a F prefix.
   The Set Frequency: field will already have 50 Hz shown from the previous
   exercise in the Set Freq: dialog box.
       1. Start the drive, then open the door of the Control cabinet.
       2. In the control cabinet, remove the wire from terminal block 419. This
          triggers the transformer overtemperature warning alarm.
                                   4. Replace the wire for terminal block 419 and tighten properly to remove the
                                      warning.
                                   1. Start the drive, then open the door of the Control cabinet.
                                   2. In the Control cabinet, remove the wire from terminal block 418. This
                                      triggers the transformer overtemperature trip alarm.
                                   4. Replace the wire for terminal block 418 and tighten properly to remove the
                                      trip message.
            Wait until the Ready status indicator is red before starting another
            simulation.
           TIP            The circuit breakers for the main cooling fans for the entire drive are located
                          here.
       3. Turn the first motor control circuit breaker (Q10 for IEC and CB10 for
          UL), controlling the Isolation Transformer Cabinet Main Cooling Fans
          (one per fan), to the OFF position.
                                       TIP         From left to right on the DIN rail in the LV cabinet, the main cooling fan circuit breakers are located
                                                   first for the Isolation Transformer cabinet then the Power Module cabinet.
                                                   Almost all drive configurations will have a maximum of three main cooling fans for the Isolation
                                                   Transformer Cabinet. Therefore, the main cooling fan circuit breaker designations of Q10, Q11, and
                                                   Q12 are reserved for the Isolation Transformer Main Cooling Fans. Power Module Cabinet Main
                                                   Cooling Fan circuit breaker designations begin at Q13.
                                                   Refer to the appendix in 6000-IN006_-EN-P to determine the number of main cooling fans in each
                                                   cabinet location, or look at the fans on the top plate of the drive.
                                   3. Turn the applicable motor control circuit breaker (Q13 for IEC and CB13
                                      for UL), controlling the Power Module Main Cooling Fans (one per fan),
                                      to the OFF position.
4. Twist to pull out the E-stop button on the front of the LV Control cabinet.
       2. Open the Bypass cabinet door, and close QS2 and QS3.
            Verify the Input and Output contactors are closed on the HMI.
     IMPORTANT            Turn the 3-position on the selector switch on the front of the LV Cabinet to the
                          Drive position.
Bypass Contactors
                                   IMPORTANT          Turn the 3-position on the selector switch on the front of the LV Cabinet to the
                                                      Bypass position.
   Table 16 - 4-20 mA
    Output Current              925-926                     Motor Current              0-Rated Current
    Output Frequency            927-928                     Actual Frequency           0-Rated Frequency
                               When the two terminals specified are shorted, verify the result shown in the third
                               column occurs.
                               Table 17 - DCS to Drive
                                Signal Name                          Terminal Number              Function
                                Fault Reset                          412-401                      Reset System
                                DCS Start                            449-401                      Start Drive
                                DCS Stop                             450-401                      Stop Drive
                                E-stop                               1101-1101                    E-stop Drive
                                Frequency Set                        931-402                      Set Drive Frequency
3. Press to login.
WARNING: Do NOT press Reset. This will reset all factory-set parameters.
5. Press the P007 parameter field to enter the number of power cells per
Set Date and Time Zone         To access the Date and Time Zone settings, you must exit the PowerFlex 6000
                               HMI to Windows CE.
Access T Parameters
4. Press to login.
7. Press the T10 parameter input field. Enter “555” and press .
IMPORTANT Enter the Time Zone settings before changing the date and time.
Notes:
No-load Test
Introduction                             ATTENTION: Medium Voltage is required for parts of this test. Close and lock all
                                         medium voltage doors on the PowerFlex 6000 and Bypass Cabinet (if supplied)
                                         prior to removing Lockout and Tagout provisions and closing the input circuit
                                         breaker. All safety related work practices outlined in Electrical Safety
                                         requirements for Employee Work places must be followed when removing the
                                         input circuit breaker from the locked out, tagged out state.
No-load Test      The No-load Test consists of the following procedures and must be performed in
                  the sequence shown.
                   Sequence        Procedure                                                                         Page
                             1     Energize Drive Control Circuit                                                    90
                   LV
                   Only      2     Configure P and T Parameters                                                      90
                             3     Close Isolation Switches in Bypass Cabinet(1)                                     102
                             4     Close Input Circuit Breaker                                                       103
                   MV        5     Check Cooling Fan Operation                                                       103
                             6     Operate Motor by HMI                                                              104
                  (1) This procedure is performed only if an optional bypass configuration is supplied.
                                         WARNING: These procedures must be performed in the order they are listed
                                         here. Failure to do so may result in personal injury or death, property damage,
                                         or economic loss.
                              The “Energize Control Circuit” process is already described on page 48. For the
                              “Energize Drive Control Circuit” procedure, repeat the process in the same
                              sequence, without the requirements of taking voltage measurements.
                              This table outlines the specific parameters that must be checked and/or
                              modified. Parameters that must be modified are outlined in the Instruction
                              column. All other parameters listed must be verified. For special functions or
                              actions which are not listed here, but are commonly performed while
                              commissioning a drive, see Special Function Parameter Settings on page 117.
                              Table 18 - Setup and R&D P Parameters
                               Parameter Description                                         Min.     Max.      Default Modify
                               Number                                                                                   Root
                               P004          Command Source                                  0        2         0        OFF
                                             0 = Communication Port
                                             1 = Digital Input
                                             2 = EtherNet/IP
                               P005          Restore Factory Settings                        0        50        0        OFF
                                             30 = Restore Setup Level
                                             40 = Restore User Level
                                             50 = Restore R&D Level
                               P007          Number of Power Cells Per Phase                 0        9         9        ON
                               P008          Motor Rotation Direction Under Local Control    0        1         1        OFF
                                             0 = Reverse
                                             1 = Forward
                               P009          Motor Rotation Direction Command Selection:     0        1         0        OFF
                                             0 = Local Control
                                             1 = DCS
                               P010          Power Cell Fault Mask                           0        32767     32767    ON
                               P017          Number Of Motor Pole Pairs                      0        100       2        OFF
                               P019          Encoder Resolution                              0        4096      1024     OFF
                      ATTENTION: If you enter a value that is greater than the allowed range for the
                      parameter, the input field will turn red.
Parameter T11
Parameter T12
Parameter T13
2. Enter desired speed values in the Enter Four Steps dialog box.
3. Press to accept.
                      ATTENTION: Medium Voltage is required for this test. Close and lock all
                      medium voltage doors on the PowerFlex 6000 and Bypass Cabinet (if supplied)
                      prior to closing the input circuit breaker. All safety related work practices
                      outlined in Electrical Safety requirements for Employee Work places must be
                      followed when removing the input circuit breaker from the locked out, tagged
                      out state.
       1. Open the Low Voltage panel door on the Isolation Transformer Cabinet
          door.
       2. Close all of the Drive Main Cooling Fan circuit breakers (Q10, ...) in the
          Isolation Transformer Cabinet LV Panel.
       3. Verify that all cooling fans are operating.
       4. Turn off the first Main Cooling Fan Circuit Breaker (Q10) and record the
          direction of the fan.
            Viewed from the rear, the blades will rotate left to right (counter-clockwise
            when viewed from the top). If the fan is rotating in the wrong direction,
            turn off the specific Main Cooling Fan breaker. Verify the output voltage is
            0. Switch two wires on the output of the circuit breaker.
       5. Turn the circuit breaker back on, and repeat for the remaining Main
          Cooling Fan circuit breakers.
       6. Verify that there are no faults or warnings on the HMI screen.
                                IMPORTANT            Before completing this procedure, verify there are no warnings or failure
                                                     messages on the HMI. The “Ready” status indicator must be red.
1. From the Main Interface Screen, press the Set Frequency: input field.
2. In the Set Freq: dialog box, enter a value of “5” and press .
Press to confirm.
                                      TIP            The Set Frequency and Actual Frequency occasionally will not show the exact
                                                     integral value selected, due to internal data conversion in the HMI program.
     IMPORTANT            When the drive is ≤0.5 Hz, the “Connect” light will be illuminated. When the
                          speed of the drive surpasses 0.5 Hz, the “Connect” and “Running” lights will be
                          red.
            a. Press                     .
            b. Open the Input Circuit Breaker.
            c. Perform the Lockout and Tagout procedures.
            d. Verify that medium voltage is not present in the drive and in the
               motor’s cable connection box by using a hot stick.
            e. Swap any two cables in the motor’s cable connection box.
            f. Repeat Close Input Circuit Breaker on page 103.
            If the motor rotating direction is correct, continue to step 5.
       5. From the Main Interface Screen, press the Set Frequency: input field.
6. In the Set Freq: dialog box, enter a value of “10” and press .
Press to confirm.
                               Drive Voltage                     10 Hz          20 Hz        30 Hz      40 Hz      50 Hz
                               3 kV                              310            770          1370       2110       3000
                               3.3 kV                            340            850          1500       2320       3300
                               4.16 kV                           430            1060         1900       2930       4160
                               6 kV                              620            1540         2740       4220       6000
                               6.6 kV                            690            1690         3010       4650       6600
                               10 kV (Not applicable for UL)     1040           2560         4560       7040       10,000
9. Press the Set Frequency: input field. In the Set Freq: dialog box, enter a
14. Press .
Load Test of Drive System This process is essentially a repeat of the No Load test procedure.
                               The Input Circuit Breaker should be off and locked out and tagged out to
                               prevent any possibility of energization of the motor circuit while the application
                               is reconfigured to apply load.
Notes:
Torque Requirements
Torque Requirements      Proper tightening torque must be used for installation and wiring.
                         Table 20 - Torque Requirements
                                                                                      Torque
                                      Thread Size
                                                                              N•m               lb•ft
                                          M4                                   1.4              1.0
                                          M5                                   2.8              2.1
                                          M6                                   4.6              3.4
                                          M8                                   11               8.1
                                         M10                                   22               16.2
                                         M12                                   39               28.8
                                         M14                                   62               45.7
                                         M16                                   95               70.1
                                         M20                                   184             135.7
Notes:
PowerFlex 6000
                M                                               Circuit
                                                                Breaker
KM2
KM3
                   M                                                                                  Circuit    Vacuum
                                                                                                      Breaker   Contactor
KM2
KM3
QS2
M
                                                              Circuit               Vacuum            Isolation
                                                              Breaker              Contactor           Switch
Bypass Unit
QS2
QS3
Figure 34 - PowerFlex 6000 Automatic Bypass for Two Cabinets (with Isolation Switches)
Notes:
Overview                      Table 18 on page 90 and Table 19 on page 98 outlines specific parameters that
                              must be checked and/or modified when commissioning a drive. Listed below are
                              specific parameters, a brief description and their function to execute optional
                              special functions which, while not essential to commissioning a drive and will not
                              be done every time, are frequently performed.
System Setting Functions      The system setting includes the amount of power modules in one phase, the
                              command source, the drive rated parameter setting, the motor parameter setting,
                              the sensor parameter setting, the restoring of factory default parameter setting,
                              analog output parameter setting.
IMPORTANT This number MUST match the actual amount of power cells in one phase.
                              P7 is equal to the amount of power modules in one phase; for example, if the
                              amount of power cells in one phase is 6, P007=6. Power Module fault and
                              warning information is based on P007. If P007=0, this is ignored and the user
                              can run the drive using low voltage.
Use this parameter to check low voltage components and the control box.
Description: P004 selects the control source to start, stop, or reset the drive.
                                                      There are two Control Sources, the HMI and the hard-wired I/O interface
                                                      (DCS). They cannot be enabled at the same time.
                                                      Instruction: P460 is drive’s rated output frequency, which should be the same as
                                                      the motor’s rated frequency (0…75 Hz). P466 is the drive’s Maximum Output
                                                      Frequency; P460 cannot exceed P466.
                                                      Description: set basic motor parameters, such as rated current and the number of
                                                      pole pairs.
                                                      Instruction: P199 is motor rated current, which is used to determine faults. P017
                                                      sets the number of motor pole pairs.
Instruction: Set the HECS rated current (A) used for the drive current sampling.
Relevant parameters:
   Description: sets the display parameters for the following analog output signals:
   Set Frequency, Actual Frequency, Motor Voltage and Motor Current.
   Instruction: each signal has four display parameters: memory address, filter
   parameter, HMI display integer part and HMI display decimal part.
       EXAMPLE            To output the “given frequency” when the memory address is 221, the filter
                          time is 100 ms, the maximum integer part is 60, the maximum decimal part is
                          0, set P351=100, P352=60, P353=0, P371=221.
                          The value of P371, P372, P373, P374 are default values and do not generally
                          need to be changed. Field Support Engineers can change them according to the
                          specific configuration.
   Instruction: this function includes the three different access levels: User Level,
   Setup Level, and R&D Level. The amount of parameters restored is dependent
   on the access level. Press Reset to restore parameters.
   The following table shows the parameters which can be restored in the different
   access levels.
    Setup (P005 = 30)   P004, P007, P008, P009, P024, P030, P031, P032, P033, P040, P087, P088, P089, P090, P091,
                        P092, P093, P113, P114, P115, P198, P199, P205, P206, P210, P212, P213, P215, P216, P222,
                        P223, P224, P238, P252, P253, P259, P260, P262, P263, P264, P278, P281, P282, P283, P285,
                        P335, P339, P352, P355, P358, P361, P385, P386, P387, P388, P389, P390, P391, P392, P399,
                        P401, P416, P417, P438, P441, P442, P451, P452, P453, P455, P456, P457, P459, P460, P463,
                        P466, P467
    User (P005 = 40)    P004, P198, P199, P262, P352, P355, P358, P361, P399, P401
    R&D (P005 = 50)     All P parameters
IMPORTANT It can only be enabled when the setting frequency source is set to analog.
                                                      Description: this function limits the low frequency starting range, reduce the low
                                                      frequency output error for analog input mode. This parameter avoids the drive’s
                                                      output fluctuation when the frequency is around 0 Hz.
                                                      Instruction: if the original set frequency is lower than P414, the set frequency will
                                                      be changed to P414.
                            Description: this function limits the amplitude of the Set Frequency. The Set
                            Frequency must not exceed the maximum output frequency of the drive.
                            Instruction: this function can limit the Set Frequency between P413 and P415,
                            P415>P413>0.
                            Frequency Skip
                            Relevant parameter: P089, P090, P091, P092, P093
                            Instruction: this function is enabled by P089. There are two bands, one is
                            between P090 and P091, the other is between P092 and P093. The Set
                            Frequency can skip out from these two bands if it is within them. The Set
                            Frequency will be changed automatically into the upper limit of the bands while
                            the speed increases, or changed into the lower limit of the band while the speed
                            decreases (Figure 35). The recommended width of these intervals is 1 Hz.
                             fB2
Drive Recognize Frequency
fB1
fA2
fA1
                                                      Instruction: P451 is low speed voltage compensation (%), P452 is low speed
                                                      voltage compensation frequency threshold. If the output frequency is lower than
                                                      P452, the output voltage will be improved per P451 (Low Speed Voltage
                                                      Compensation).
                                                      Description: this function sets the maximum modulation index and limit the
                                                      output voltage amplitude, so the drive can run above rated frequency.
                                                      Instruction: change the output voltage without changing the output frequency by
                                                      adjusting P455. Adjust this value according to the field conditions to ensure the
                                                      output voltage/frequency is consistent with standard V/F curve.
                                                      P456 is the output voltage amplitude limit; the amplitude of output voltage
                                                      cannot exceed this value.
                                                      Instruction: P454 is the time to build the rotating magnetic field. This value will
                                                      not generally be changed.
                               Voltage Level (kV)            VSB Output Line-to-Line Voltage (RMS V)                               P205, P206
                               3                             3.62                                                                  195.20
                               3.3                           3.98                                                                  177.46
                               4.16                          3.77                                                                  187.64
                               6                             3.63                                                                  195.09
                               6.6                           3.98                                                                  177.35
                               10 (Not applicable for UL)    4.02                                                                  175.54
Description: the drive has two ways to stop the drive, ramp down or coast stop.
                           If P024=1, the output will stop immediately, so the motor will stop by inertance.
                           If P024=0, the output will stop the from the set frequency to 0 Hz. When the
                           frequency=P252*rated frequency (P252 is a percentage value), the system will be
                           locked.
                           To restart the drive if coast stop was selected, wait until it stops before restarting.
                           The time needed is:
                                                                      FrequencyBeforeStop
                                                               P253 × ----------------------------------------------------------
                                                                        MaximumFrequency
Flying Start Function      Relevant parameter: P113, P114, P115, P416, P417, P438, P457, P459,
                           P463, K5
                           Instruction: the flying start feature identifies the motor speed based on the
                           output current.
                                                        IMPORTANT            P416 enables Flying Start Selection. If the Flying Start is not successful, change
                                                                             the other parameters listed accordingly. Otherwise, these parameters do not
                                                                             normally need to be changed.
                                                      If the drive cannot search the speed in the field, increase P417 to decrease the
                                                      search step and improve the accuracy; or increase P113 and decrease P115 to
                                                      improve the accuracy. If there was any noise during the restore stage, increase
                                                      P457 or P459. P463 does not need to be changed.
Description: these parameters use the auto-restart feature after a system fault.
                                                      Instruction: if P461 is enabled (P461=1), the drive will restart at once when
                                                      system fault occurs.
                                                      If there is something wrong with a Power Module, it will wait for P465 before
                                                      restarting. If a fault happens twice during the Fault Reset Timeout (P462), the
                                                      drive will trip.
                                                        IMPORTANT            If restart feature was enabled, the second mode of flying start feature must be
                                                                             enabled.
               A                                                            E
   Analog Input 123                                             Electrical Installation Inspection 22, 38
               C                                                            F
   Cabinet Plates                                               Flying Start Function 123
        Pre-Commissioning Sealing 29, 46                        Functional Assessment 17, 33
   Commissioning 47                                                  Checklist 19, 35
        Control System Check 52
               Procedure List 47
               Setup 48                                                     I
        Process Flowcharts 12                                   Installation Review 21, 37
        Set Date 86
        Set Regional Settings 87                                     Electrical Inspection 22, 38
        Set Time Zone 86                                             Mechanical Inspection 21, 37
   Commissioning Requirements                                   Interconnection Review 20, 36
        Computer Requirements 15, 31                                 Checklist 20, 36
        Electrical Equipment 15, 31
        Hand Tools 15, 31
        Software 15, 31                                                     L
        Test Equipment 15, 31                                   Lockout 15, 31
   Control System Check 52                                           Safety Test 16, 32
        P Parameters
               Restore Settings 84
               Set to Enable Testing 55                                     M
        Procedure List 47                                       Mechanical Installation Inspection 21, 37
        Setup 48
               Energize Control Circuit 48
               Simulate Closed Input Circuit Breaker 48
        Simulate Warnings and Faults 67                                     N
        Verify                                                  No-Load Test
               E-Stop Functionality 72                              Check Cooling Fan Operation 103
               Factory Default Settings 52                          Close Input Circuit Breaker 103
               Operation to Set Frequency 65                        Close Isolation Switches in Bypass Cabinet 102
               Switching, Local to Remote Control 73                Configure P and T Parameters 90
        Verify Operation of                                         Energize Drive Control Circuit 90
               Bypass Contactors 77                                 Operate Motor by HMI 104
               Bypass Isolation Switches 74
               DCS Input 83
               Frequency Steps 63                                           O
               Input/Output 74, 77
               Output Signals 83                                Overviews
   Control Wiring 23, 39                                             Commissioning 47
                                                                     Documentation and Application Review 12
                                                                     Load Test 107
               D                                                     No-load Test 89
                                                                     Special Function Parameter Settings 117
   Diagrams
        6012M Automatic Bypass Version 1 112
        6012M Automatic Bypass Version 2 113                                P
        6012M Manual Bypass 114, 115                            Power Cabling 22, 38
        PowerFlex 6000 without Bypass 111
   Documentation and Application Review                              Color Coding 22, 38
                                                                Pre-Commissioning
        Process Flowcharts 12
   Documentation, Rockwell Automation 12                             Cabinet Plates 29, 46
                                                                     Computer Requirements 15, 31
   Drive Application                                                 Drive Megger Check 23, 39
        Review 13                                                    Electrical Equipment 15, 31
   Drive Components                                                  Final Steps 29, 46
        Inspection 16, 32                                            Functional Assessment 17, 33
             Checklist 18, 34                                               Checklist 19, 35
   Drive Megger Check 23, 39                                         Installation Review 21, 37
                                                                            Electrical Inspection 22, 38
                       R
           Restart the Drive 124
                       S
           Safety Test (Lockout) 16, 32
           Special Function Parameter Settings 117
                Analog Input 123
                Flying Start Function 123
                Restart the Drive 124
                Speed Command Function
                      Frequency Amplitude Limit 121
                      Frequency Command Deadband Upper
                             Limit 120
                      Frequency Skip 121
                      Set Frequency Command Source 120
                      Set Frequency Correction 120
                Speed Command Functions 120
                Speed Reference Functions 122
                      Limit Output Voltage Amplitude 122
                      Set Flux Time 122
                      Set Maximum Modulation Index 122
                      V/F Curve Setting 122
                Stop Mode 123
                System Setting Functions 117
                      Analog Output Display Parameter Set-
                             ting 119
                      Hall Effect Current Sensor Setting 118
                      Motor Parameter Setting 118
                      Number of Power Modules Per Phase
                             117
                      Rated/Maximum Output Frequency 118
                      Restore Factory Setting 119
                      Switch Control Sources 118
           Speed Command Functions 120
           Speed Reference Functions 122
           Stop Mode 123
                       T
           Tagout 15, 31
           Torque Requirements 109
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more
information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/services/online-phone.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada                              1.440.646.3434
Outside United States or Canada                      Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
                                                     Rockwell Automation representative.
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States                                        Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
                                                     distributor to complete the return process.
Outside United States                                Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Medium Voltage Products, 135 Dundas Street, Cambridge, ON, N1R 5X1 Canada, Tel: (1) 519.740.4100, Fax: (1) 519.623.8930
Online: www.ab.com/mvb
Allen-Bradley, Rockwell Software, Rockwell Automation, PowerFlex, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.