G300 60-80 Operation
G300 60-80 Operation
60–80 kVA
Operation
07/2015
www.schneider-electric.com
Legal Information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the owner's
permission, given in writing. This guide and its content are protected, within the
meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
As standards, specifications, and designs change from time to time, please ask for
confirmation of the information given in this publication.
60–80 kVA
Table of Contents
Important Safety Information .....................................................................5
Safety Precautions .....................................................................................6
Overview ......................................................................................................7
Display Interface.........................................................................................7
LEDs ...................................................................................................7
Display Screen, Navigation Keys, and the ON/OFF Buttons .....................8
Default Screen......................................................................................8
Screen Saver .......................................................................................8
Overview of UPS without Internal Batteries...................................................9
One Line Diagram.................................................................................9
Overview of UPS with Internal Batteries .....................................................10
One Line diagram ...............................................................................10
Menu Tree ............................................................................................... 11
Operation ...................................................................................................12
Operation Modes......................................................................................12
Normal Operation ...............................................................................12
Battery Operation................................................................................12
Static Bypass Operation ......................................................................12
Maintenance Bypass Operation ...........................................................12
Frequency Converter Operation ...........................................................12
ECO Mode .........................................................................................12
Operation Procedures...............................................................................13
Start Up the UPS System with the Wizard Enabled ................................13
Initial Start-up of the UPS System with the Wizard Disabled ...................14
Turn into Normal Operation from Static Bypass Operation......................15
Turn into Static Bypass Operation from Normal Operation......................17
Turn into Frequency Converter Operation from Normal
Operation ...........................................................................................18
Turn into Normal Operation from Frequency Converter
Operation ...........................................................................................19
Turn into Maintenance Bypass Operation from Normal
Operation ...........................................................................................20
Turn into Normal Operation from Maintenance Bypass
Operation ...........................................................................................20
Perform a Total Power Off....................................................................21
Turn into Normal Operation from Total Power Off...................................21
Common Procedures ..........................................................................22
Configuration .............................................................................................26
Default Settings ........................................................................................26
Settings Not Requiring a Restart ................................................................26
General Information ............................................................................27
Set the LCD Contrast ..........................................................................27
Set the Wizard ....................................................................................27
Set the Date Format ............................................................................27
Set the Date and Time.........................................................................28
Set the Temperature............................................................................28
Set the Language ...............................................................................28
Set the Buzzer ....................................................................................29
990–5450–001 3
60–80 kVA
4 990–5450–001
Important Safety Information 60–80 kVA
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
990–5450–001 5
60–80 kVA Important Safety Information
Safety Precautions
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
All safety instructions in this document must be read, understood and followed.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
After the UPS system has been electrically wired, do not start up the system.
Startup must only be performed by Schneider Electric.
Failure to follow these instructions will result in death or serious injury.
6 990–5450–001
Overview 60–80 kVA
Overview
Display Interface
LEDs
NOTE: The mimic diagram (A-E) shows the electrical power flow and gives the
status of main functions.
A PFC
Green: Power factor correction (PFC) works on normal AC input.
Red: normal AC is out of tolerance, DC BUS has become inoperable, or
PFC has become inoperable.
OFF: The PFC is not working.
B INVERTER
Green: The inverter is operating.1
Red: The inverter or the static switch has become inoperable.
OFF: The inverter is OFF.1
C LOAD
Green: The inverter supports the load1 or the load is supported by the
bypass AC source.
Red: The inverter is not connected to the load1 and the load is not
supported by the bypass AC source or UOB is open.
OFF: The maintenance bypass breaker MBB is ON (closed).
D BATTERY
Green: The UPS is in battery operation.
Red: The battery or the charger has become inoperable, or the battery
circuit breaker is OFF.
OFF: The batteries are charging or ready to supply the load if the AC
power fails or the battery present configuration is absent.
E BYPASS
Green: The load is supported by the bypass AC source.
Red: Bypass AC is out of tolerance, SSIB is OFF in normal mode, SSIB
is ON in frequency converter mode, or a transfer to bypass is
unavailable.
OFF: The load is not supported by the bypass AC source.
990–5450–001 7
60–80 kVA Overview
F LOAD PROTECTED
Green: The UPS is running in normal operation mode and the load is
protected.
OFF: The load is not protected by the UPS or a major alarm is present.
G ENVIRONMENT AND MINOR
ALARMS Orange: A minor alarm is present or redundancy is lost in parallel
system.
OFF: No minor alarm is present.
H LOAD UNPROTECTED
Red: The load is unprotected (and may be supplied by the bypass AC
source or another parallel UPS). A service call is required.
OFF: No major alarms are present.
Default Screen
The Default screen appears after UPS initialization and UPS configuration. The
Default screen is the main entrance to the user functions of the display interface.
Galaxy 300
The OK key and the navigation keys take you from the Default screen to the menu
and sub menu screens where it is possible to operate, configure, and monitor the
UPS. See Menu Tree, page 11.
Screen Saver
When the display has been inactive for 30 minutes, the screen saver turns ON and
the display changes every five seconds between the two screens below. The
backlight turns OFF after three minutes of inactivity.
Galaxy 300
8 990–5450–001
Overview 60–80 kVA
990–5450–001 9
60–80 kVA Overview
10 990–5450–001
Overview 60–80 kVA
Menu Tree
NOTE: The menu tree provides a quick overview of the functions and views you
may access. The UPS display screen will only display two lines at a time although
three lines occur below.
990–5450–001 11
60–80 kVA Operation
Operation
Operation Modes
Normal Operation
The UPS provides power to the connected load from mains power. The UPS
converts mains power to conditioned power for the connected load while
recharging the batteries.
This mode is accessed via the display.
Battery Operation
The UPS transfers to battery operation if the supply of mains power fails or is
outside the pre-defined limits. The UPS provides power to the connected load from
its internal external batteries for a finite period. In standby mode, the UPS can
make a cold start via the INVERTER ON button or via the display.
ECO Mode
ECO mode is used to obtain the maximum system power efficiency by supplying
the load with power via the static bypass switch while still being able to return to
inverter operation immediately if required. When ECO mode is enabled, the default
operation mode of the UPS is set to static bypass operation. In other words the
UPS will always prefer static bypass operation over normal operation and
automatically change to this mode whenever possible.
12 990–5450–001
Operation 60–80 kVA
Operation Procedures
Start Up the UPS System with the Wizard Enabled
NOTE: The default value of the wizard is ENABLE which is a prerequisite for
carrying out this procedure. See Set the Wizard, page 27.
NOTE: Upon initial startup, the UPS will automatically guide you via the wizard to
select different settings: language, current voltage, current frequency, and mode. If
a wizard prompt is ignored the default setting of the prompt will be enabled. You
must complete the wizard one time before you can disable it for subsequent
startup sessions of the UPS system.
NOTE: You must have your password ready as you will be asked to enter it during
this procedure. If you are in doubt about how to enter or set your password, see
Enter the Password, page 29 and Set the Password, page 29.
NOTE: When a settings value has been entered and confirmed by the prompt
Done!, the wizard automatically moves to the next display prompt after three
seconds.
1. Power on the UPS system by turning the input breaker (UIB) to the ON
(closed) position.
NOTE: If the prompt System init incorrect! Code: 1-x appears on the display
screen, see Troubleshooting, page 36.
System initialization..
2. When the Change language? (Y=OK, N=Esc) prompt appears on the display
screen, do one of the following:
– Press the OK key to view the list of languages, select one of the 18
languages by using the navigation keys and press the OK key again to
confirm. After three seconds the UPS confirms the new setting by the
prompt Done!.
– Press the ESC key to move on to Change voltage of 2XXV? (Y=OK, N=
Esc).
NOTE: If the output breaker (UOB) is ON (closed) at this point, you must
Close UIB to continue setting! followed by the OK key, and Open UOB to
continue setting! followed by the OK key.
NOTE: If the output breaker (UOB) is ON (closed), the menu freezes and is
unable to continue.
3. When the Change voltage of 2XXV? (Y=OK, N=Esc) prompt appears on the
display screen, do one of the following:
– Press the OK key to view the list of voltages, select 220 V, 230 V, or 240 V
by using the navigation keys and press the OK key again to confirm. After
three seconds the UPS confirms the new setting by the prompt Done!.
– Press the ESC key to move on to Change freq. of xxHz? (Y=OK, N=Esc).
4. When the Change freq. of XXHz? (Y=OK, N=Esc) prompt appears on the
display screen, do one of the following:
– Press the OK key to view the list of frequencies, select 50 Hz or 60 Hz by
using the navigation keys and press the OK key again to confirm. After three
seconds the UPS confirms the new setting by the prompt Done!.
– Press the ESC key to move on to Change normal/freq. converter/parallel
mode? (Y=OK, N=Esc).
NOTE: The UPS system does not support a combination of 240 V and 60 Hz. If
such a combination has been chosen, you will be asked to Change voltage of
2XXV (Y=OK, N=Esc) and a new voltage must be entered.
240V/60Hz output is
not supported!
990–5450–001 13
60–80 kVA Operation
5. When the Change xxxx mode? (Y=OK, N=Esc) prompt appears on the
display screen, do one of the following:
– Press the OK key to view the list of operation modes, select normal mode,
frequency converter mode, or parallel mode by using the navigation keys
and press the OK key again. After three seconds the UPS confirms the new
setting by the prompt Done!.
– Press the ESC key to move on to Save new settings?.
6. When the Save new settings? prompt appears on the display screen, press
the OK key for Saving Settings....... Wait for the UPS to confirm the new
settings by the prompt Setting success!
NOTE: If the Setting failed! is displayed, the UPS will ask you to Start with
previous setting values? Press the ESC key to select new settings or the OK
key to move to the next step without saving the new settings.
7. When the Disable wizard? (Y=OK, N=Esc) prompt appears on the display
screen, do one of the following:
– Press the OK key to disable the wizard where after the screen will return to
the Default screen three seconds after having confirmed with the prompt
Done!.
NOTE: Schneider Electric strongly recommends this choice to allow for the
use of the automatic start function for subsequent startups.
– Press the ESC key and the display screen returns to the Default screen
without disabling the wizard.
8. Turn the static switch input breaker (SSIB) to the ON (closed) position.
9. Turn the output breaker (UOB) to the ON (closed) position.
10.Do one of the following depending on your configuration:
– UPS with internal batteries: Turn the battery breaker (BB) to the ON
(closed) position.
– UPS without internal batteries: Turn the battery cabinet breaker (QFB) to the
ON (closed) position.
11. The UPS starts up in static bypass operation. Check the LEDs to see if the UPS
is in static bypass operation:
• PFC LED: during DC bus charging the LED flashes where after it stays
green
• LOAD LED: green (if the output breaker (UOB) is turned ON - otherwise the
LED is red)
• BYPASS LED: green
• LOAD UNPROTECTED LED: red
• Other LEDs: OFF
14 990–5450–001
Operation 60–80 kVA
5. The UPS starts up in static bypass operation. Check the LEDs to see if the UPS
is in static bypass operation:
• PFC LED: during DC bus charging the LED flashes where after it stays
green
• LOAD LED: green (if the output breaker (UOB) is turned ON - otherwise the
LED is red)
• BYPASS LED: green
• LOAD UNPROTECTED LED: red
• Other LEDs: OFF
990–5450–001 15
60–80 kVA Operation
16 990–5450–001
Operation 60–80 kVA
NOTE: In static bypass operation, the load is not protected by the UPS and the
output power is not conditioned.
NOTE: Turning into static bypass can be done either via the INVERTER OFF
button or via the display.
990–5450–001 17
60–80 kVA Operation
NOTICE
HAZARD OF EQUIPMENT DAMAGE OR LOAD DROP
In frequency converter operation the UPS cannot run in static bypass or
maintenance bypass operation. Before turning the UPS into this operation mode,
you must contact a Schneider Electric-certified service partner to make sure that
the static switch input breaker (SSIB) and the maintenance bypass breaker
(MBB) are in the OFF (opened) position (Schneider Electric strongly
recommends to lock these with a padlock available from Schneider Electric), and
that the cables are disconnected according to the instructions in the installation
manual.
Failure to follow these instructions can result in equipment damage.
NOTE: You must have your password ready as you will be asked to enter it during
this procedure. If you are in doubt about how to enter or set your password, see
Enter the Password, page 29 and Set the Password, page 29.
18 990–5450–001
Operation 60–80 kVA
9. Wait for the converters to restart and the PFC to finish charging.
NOTE: Make sure that the static switch input breaker (SSIB) and the
maintenance bypass breaker (MBB) are in the OFF (opened) position.
Otherwise, the transfer is forbidden.
10.When the PFC LED changes to green, push the INVERTER ON button.
11. Turn the output breaker (UOB) to the ON (closed) position.
12.Check the LEDs to see if the UPS is in frequency converter mode:
• PFC LED: green
• INVERTER LED: green
• LOAD LED: green
• BYPASS LED: OFF
• LOAD PROTECTED LED: green
• Other LEDs: OFF
NOTICE
LOAD DROP
When UOB is opened while the UPS is in frequency converter operation, the
load will not be transferred, but will be dropped.
Failure to follow these instructions can result in equipment damage.
NOTE: You must have your password ready as you will be asked to enter it during
this procedure. If you are in doubt about how to enter or set your password, see
Enter the Password, page 29 and Set the Password, page 29.
990–5450–001 19
60–80 kVA Operation
1. Turn the output breaker (UOB) and the static switch input breaker (SSIB) to the
ON (closed) position. Now the load is supported by the UPS.
2. Turn the maintenance bypass breaker (MBB) to the OFF (opened) position.
3. Check the LEDs to see if the UPS is in bypass operation:
• BYPASS LED: green
• LOAD LED: green
4. Do one of the following depending on your configuration:
a. UPS with internal batteries: Turn the battery breaker (BB) to the ON
(closed) position.
b. UPS without internal batteries: Then turn the battery cabinet breaker (QFB)
to the ON (closed) position.
5. Turn the input breaker (UIB) to the ON (closed) position.
NOTE: Now, the inverter is OFF and the DC bus will start charging. Wait for the
DC bus to finish charging before you continue. If the UPS AUTOMATIC START
function has been enabled under PERSONALIZATION, the inverter will start up
automatically. If not, the inverter is OFF and must be turned ON via the
INVERTER ON button or the display. See Turn into Normal Operation from
Static Bypass Operation, page 15.
20 990–5450–001
Operation 60–80 kVA
6. Make sure that the INVERTER is ON. Check the LEDs to see if the UPS is in
normal operation:
• PFC LED: green
• INVERTER LED: green
• LOAD LED: green
• LOAD PROTECTED LED: green
• Other LEDs: OFF
NOTE: The load is now protected by the UPS.
1. Check that the load which is supported by the UPS units is turned OFF.
2. Turn into static bypass operation via the display or via the INVERTER OFF
button. See Turn into Static Bypass Operation from Normal Operation, page 17.
3. Turn the output breaker (UOB) and the static switch input breaker (SSIB) into
OFF (opened) position on both UPS units.
4. Turn the input breaker (UIB) into OFF (opened) position.
5. Do one of the following depending on your configuration:
– UPS with internal batteries: Turn the battery breaker (BB) into OFF
(opened) position.
– UPS without internal batteries: Turn the battery cabinet breaker (QFB) into
the OFF (opened) position.
990–5450–001 21
60–80 kVA Operation
Common Procedures
Galaxy 300
3:3 ser. no.
Current date
Current time
FIRMWARE VERSION
xx.xx.xx.xx
4. Press the ESC key to return to another screen or the Default screen.
Measurement Description
VOLTAGE MEASUREMENTS Shows the output, input, and bypass
voltage (V) on each phase.
CURRENT MEASUREMENTS Shows the output, input, and bypass
ampere (A) on each phase.
POWER MEASUREMENTS Shows the apparent output power
(kVA) and actual output power (kW)
on each phase.
FREQUENCY MEASUREMENTS Shows the input, bypass, and output
frequency in Hertz (Hz).
LOAD MEASUREMENTS Shows the percentage (%) of the
unitary load (and system load if
parallel mode is configured) in
relation to total UPS capacity, its
crest and power factor.
BATTERY MEASUREMENTS Shows the battery voltage, current,
charge level, and temperature,
backup time and remaining battery
lifetime.
22 990–5450–001
Operation 60–80 kVA
2009/12/31 23:59:59 A
PFC fuse blown
2009/12/31 23:59:59 D
PFC fuse blown
Activate Controls
NOTE: When the command values INVERTER OFF or FORCE LOAD
TRANSFER TO BYPASS are activated, the Risk of load drop, continue or not?
prompt appears. Press the OK key to continue (or the ESC key to return to
previous screens).
990–5450–001 23
60–80 kVA Operation
5. Press the ESC key to return to another command or the Default screen.
Command Description
RESET ALARM Resets all alarms.
INVERTER ON Makes a secure transfer from static bypass operation
to normal operation. The command will be refused if
the bypass and inverter conditions are not
synchronized.
INVERTER OFF Makes a secure transfer from normal operation to
static bypass operation. The command will be refused
if the bypass and inverter conditions are not
synchronized.
FORCE LOAD TRANSFER TO INV Forces the UPS to transfer from static bypass
operation to normal operation whereby the bypass
condition is ignored. A short interruption can occur.
FORCE LOAD TRANSFER TO BYPASS Forces the UPS to transfer from normal operation to
static bypass operation whereby the bypass condition
is ignored. A short interruption can occur.
LED TEST Tests the LEDs and the buzzer.
ENABLE LCM WARNING Enables all Life Cycle Monitoring (LCM) warnings,
such as start-up, warranty expiring soon, and technical
check needed warnings.
DISABLE LCM WARNING Disables all LCM warnings, such as start-up, warranty
expiring soon, and technical check needed warnings.
ACKNOWLEDGE LCM ALARMS Temporarily acknowledges LCM warning when
present. The repetitions quantity and interval between
alarms can both be adjusted by a Schneider Electric-
certified service partner.
BATTERY TEST Launches a battery test if the load is supported by the
inverter and if the batteries are available and fully
charged without alarms.
ACKNOWLEDGE DUST FILTER ALARM Acknowledge dust filter pre-alarm when present.
Acknowledge dust filter alarm and reset dust filter
timer when present. The number of alarm repetitions
and interval between alarms can both be adjusted by a
Schneider Electric-certified service partner.
RESET DUST FILTER TIMER Resets the dust filter elapsed time.
ENABLE SINGLE UPS OUTPUT Enables single UPS output when the other parallel-
installed UPS is powered down.
View Alarms
NOTE: The UPS supports all active alarms. An alarm description is limited to one
line. If an alarm is resolved, the UPS automatically removes the alarm from the list.
24 990–5450–001
Operation 60–80 kVA
Example
ALARM (2/6)
Load short circuit
990–5450–001 25
60–80 kVA Configuration
Configuration
Default Settings
NOTE: The configuration procedures in this chapter describe how to change UPS
settings after initial startup.
NOTE: Every new setting has to be confirmed by pressing the OK key as
described in the procedures. If this step is omitted, the display will return to its
previous setting.
2. These settings require a restart. See Settings Requiring a Restart, page 31.
26 990–5450–001
Configuration 60–80 kVA
General Information
NOTE: It is possible to change several settings under the SETTINGS menu
without having to escape and reenter the menu. Before you escape the SETTINGS
menu, the UPS will save all new settings by the prompt Done!.
NOTE: When your new settings have been confirmed by the prompt Done!, press
the ESC key until you return to the Default screen.
- 2
4. Press the OK key to confirm the new display contrast value. After three
seconds the UPS confirms the new setting by the prompt Done!.
5. Press the ESC key until you return to the Default screen.
990–5450–001 27
60–80 kVA Configuration
2010-01-01
00:00:00
4. Use the navigation keys to select a value of the active digit and press the OK
key.
5. Use the navigation keys to select a value of the next active digit followed and
press the OK key and repeat this procedure until a value of the last digit has
been chosen.
2010-01-01
00:00:00
6. Press the OK key to confirm the last value. After three seconds the UPS
confirms the new setting by the prompt Done!.
7. Press the ESC key until you return to the Default screen.
4. Press the OK key to confirm the new display language. After three seconds the
UPS confirms the new setting by the prompt Done!.
5. Press the ESC key until you return to the Default screen.
28 990–5450–001
Configuration 60–80 kVA
000
4. The second digit is now active. Use the navigation keys to select the second
digit from 0 to 4 and press the OK key.
000
5. The third digit is now active. Use the navigation keys to select the third digit
from 0 to 4 and press the OK key to confirm the password.
000
6. When the password has been set, the prompt Done! is displayed for three
seconds before the new password is displayed. Press the ESC key to return to
the previous menu at any time.
990–5450–001 29
60–80 kVA Configuration
NOTE: If you choose a wrong digit, press the ESC key at any time during this
procedure to return to the previous menu and reenter your password.
1. When the first digit is active, use the navigation keys to select the first digit from
0 to 4 and press the OK key.
2. The second digit is now active. Use the navigation keys to select the second
digit from 0 to 4 and press the OK key.
3. The third digit is now active. Use the navigation keys to select the third digit
from 0 to 4 and press the OK key to confirm the password.
NOTE: If the password is correct, you are allowed to continue your desired
procedure. If the password is incorrect, the prompt Wrong password! is
displayed for three seconds before the display returns to the previous menu
and then you can try again.
30 990–5450–001
Configuration 60–80 kVA
General Information
NOTICE
• Only trained personnel following the required training course may undertake
modifications to UPS system parameters.
• All personalization settings described below require a UPS restart and must
not be performed if the UPS is up running and supports the load. Before
starting the personalization sequence, the output breaker UOB must
therefore be turned to the OFF (opened) position.
• After the personalization sequence, the UPS will automatically turn into
normal operation (after DC bus charging) if UPS Automatic start has been
enabled under SETTINGS >PERSONALIZATION. Otherwise, see the
manual procedure under Turn into Normal Operation from Static Bypass
Operation, page 15.
Failure to follow these instructions can result in equipment damage.
NOTE: You must have your password ready as you will be asked to enter it during
this procedure. If you are in doubt about how to enter or set your password, see
Enter the Password, page 29 and Set the Password, page 29.
NOTE: When a setting value has been selected, the prompt Selected! will be
displayed for three seconds where after the display will return to the option
selected. Press the ESC key to return to the item menu and press the navigation
keys to scroll to new setting items to make new settings.
NOTE: As mentioned above, it is possible to change several settings under the
PERSONALIZATION menu without having to leave and reenter the menu via the
ESC key. Before you go back to the PERSONALIZATION menu, the UPS will save
all new settings by the prompts:
• Save new settings? (press the OK key to confirm or the ESC key to return to
the previous screen(s)).
• Saving settings......
• Setting success!
NOTE: If the Setting failed! prompt appears, wait three seconds before the
display returns to the PERSONALIZATION menu, and then try again.
990–5450–001 31
60–80 kVA Configuration
32 990–5450–001
Maintenance 60–80 kVA
Maintenance
Parts Replacement
Determine if you need a Replacement Part
To determine if you need a replacement part, contact Schneider Electric and follow
the procedure below so that the representative can assist you promptly:
1. In the event of an alarm condition, scroll through the alarm lists, record the
information, and provide it to the representative.
2. Write down the serial number of the unit so that you will have it easily
accessible when you contact Schneider Electric.
3. If possible, call Schneider Electric from a telephone that is within reach of the
display so that you can gather and report additional information to the
representative.
4. Be prepared to provide a detailed description of the problem. A representative
will help you solve the problem over the telephone, if possible, or will assign a
return material authorization (RMA) number to you. If a module is returned to
Schneider Electric, this RMA number must be clearly printed on the outside of
the package.
5. If the unit is within the warranty period and has been started up by Schneider
Electric, repairs or replacements will be performed free of charge. If it is not
within the warranty period, there will be a charge.
6. If the unit is covered by a Schneider Electric service contract, have the contract
available to provide information to the representative.
AP9635CH
NOTE: Please refer to the replacement procedures in the manual shipped with the
card. Please also refer to the UPS installation manual shipped with the UPS on
how to connect the communication cables.
990–5450–001 33
60–80 kVA Maintenance
Storage
1. Open the UPS cabinet door. The four dust filters are installed in the door frame
and held in place with six sheet metal bars.
2. Press on the top end of the sheet metal bars and push them downwards to
release them from the clip brackets.
3. Then remove the bottom end of the sheet metal bars from the clip brackets.
34 990–5450–001
Maintenance 60–80 kVA
4. Pull the dust filters gently out from the clip brackets.
5. Insert the new dust filters in the clip brackets.
6. Insert the bottom end of the sheet metal bars in the clip bracket and the reinsert
the top end of the sheet metal bar to keep the dust filters in place.
990–5450–001 35
60–80 kVA Troubleshooting
Troubleshooting
Status and Alarm Messages
This section lists status and alarm messages from the display and the LEDs. The
display messages are listed in alphabetical order, and a suggested corrective
action is listed with each display alarm message to help you troubleshoot
problems.
Buzzer
NOTE: The buzzer turns on as soon as an alarm condition is detected. It can be
turned off by pressing the ESC key from the Default screen. If a new alarm
condition is detected, the buzzer turns on again. The buzzer turns OFF
automatically when the last alarm has been cleared. The buzzer can be enabled or
disabled under the Settings menu. See Set the Buzzer, page 29.
Alarm Pop–Ups
NOTE: An alarm automatically pops up on the display screen when an unexpected
event or alarm condition occurs, unless the screen displays:
• an alarm in the alarm list
• a prompt as part of a command, password or settings process
• a viewing or settings prompt under the PERSONALIZATION menu
An alarm is also prohibited from popping up for 30 seconds after one of the four
navigation keys has been pressed in order to avoid disturbance when a menu is
being viewed.
NOTE:
The screen displays the alarm in the following format:
ALARM
Alarm description
Example
ALARM
Load short circuit
NOTE: The display screen will show one alarm at a time. When several alarms
occur at the same time, the latest alarm appears at the top of the list and can be
deleted by pressing the ESC key. If all alarms are deleted, the display returns to
the screen displayed before the alarm(s) occurred. Deleted alarms can still be
viewed. See View Alarms, page 24.
36 990–5450–001
Troubleshooting 60–80 kVA
Displayed Messages
990–5450–001 37
60–80 kVA Troubleshooting
38 990–5450–001
Troubleshooting 60–80 kVA
990–5450–001 39
60–80 kVA Troubleshooting
40 990–5450–001
Troubleshooting 60–80 kVA
990–5450–001 41
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.schneider-electric.com