Ups 80kva
Ups 80kva
www.schneider-electric.com
Legal Information
             The information provided in this document contains general descriptions, technical
             characteristics and/or recommendations related to products/solutions.
             This document is not intended as a substitute for a detailed study or operational and
             site-specific development or schematic plan. It is not to be used for determining
             suitability or reliability of the products/solutions for specific user applications. It is the
             duty of any such user to perform or have any professional expert of its choice
             (integrator, specifier or the like) perform the appropriate and comprehensive risk
             analysis, evaluation and testing of the products/solutions with respect to the relevant
             specific application or use thereof.
             The Schneider Electric brand and any trademarks of Schneider Electric SE and its
             subsidiaries referred to in this document are the property of Schneider Electric SE or
             its subsidiaries. All other brands may be trademarks of their respective owner.
             This document and its content are protected under applicable copyright laws and
             provided for informative use only. No part of this document may be reproduced or
             transmitted in any form or by any means (electronic, mechanical, photocopying,
             recording, or otherwise), for any purpose, without the prior written permission of
             Schneider Electric.
             Schneider Electric does not grant any right or license for commercial use of the
             document or its content, except for a non-exclusive and personal license to consult it
             on an "as is" basis.
             Schneider Electric reserves the right to make changes or updates with respect to or in
             the content of this document or the format thereof, at any time without notice.
             To the extent permitted by applicable law, no responsibility or liability is
             assumed by Schneider Electric and its subsidiaries for any errors or omissions
             in the informational content of this document, as well as any non-intended use
             or misuse of the content thereof.
             https://www.productinfo.schneider-electric.com/easyups3m/
                                                                                                        For Internal Batteries
Table of Contents
                Important Safety Instructions — SAVE THESE
                INSTRUCTIONS .........................................................................................7
                     Electromagnetic Compatibility .....................................................................8
                     Safety Precautions .....................................................................................8
                          Electrical Safety.................................................................................. 11
                          Battery Safety.....................................................................................12
                          Symbols Used in the Product ...............................................................14
                Specifications ............................................................................................16
                     Input Specifications ..................................................................................16
                     Bypass Specifications ...............................................................................16
                     Output Specifications ................................................................................16
                     Battery Specifications ...............................................................................17
                     Recommended Upstream Protection..........................................................17
                     Recommended Cables Sizes ....................................................................18
                     Recommended Bolts and Cable Lugs ........................................................18
                     Torque Specifications................................................................................19
                     UPS Weights and Dimensions ...................................................................19
                     Clearance ................................................................................................19
                     Environmental ..........................................................................................20
                        Heat Dissipation .................................................................................20
                     Compliance..............................................................................................20
                Overview ....................................................................................................21
                     Overview of Single UPS ............................................................................21
                     Overview of Parallel System ......................................................................22
                     Location of Breakers and Switches ............................................................23
                Connect the Power Cables ......................................................................24
                Communication Interfaces.......................................................................28
                     Route the Signal Cables............................................................................28
                     Input Contacts and Output Relays..............................................................30
                     Connect the Parallel Cables in a Parallel System ........................................33
                     Connect Synchronization Cables Between Two UPS Systems
                     (Option) ...................................................................................................34
                Backfeed Protection .................................................................................35
                Install Batteries in the UPS ......................................................................38
990-6204C-001                                                                                                                    5
Important Safety Instructions — SAVE THESE
INSTRUCTIONS                                                                                       For Internal Batteries
                                                                    DANGER
                                DANGER indicates a hazardous situation which, if not avoided, will result in
                                death or serious injury.
                                Failure to follow these instructions will result in death or serious injury.
                                                                   WARNING
                                WARNING indicates a hazardous situation which, if not avoided, could result
                                in death or serious injury.
                                Failure to follow these instructions can result in death, serious injury, or
                                equipment damage.
                                                                   CAUTION
                                CAUTION indicates a hazardous situation which, if not avoided, could result in
                                minor or moderate injury.
                                Failure to follow these instructions can result in injury or equipment
                                damage.
                                                                   NOTICE
                                NOTICE is used to address practices not related to physical injury. The safety
                                alert symbol shall not be used with this type of safety message.
                                Failure to follow these instructions can result in equipment damage.
Please Note
                               Electrical equipment should only be installed, operated, serviced, and maintained
                               by qualified personnel. No responsibility is assumed by Schneider Electric for any
                               consequences arising out of the use of this material.
                               A qualified person is one who has skills and knowledge related to the construction,
                               installation, and operation of electrical equipment and has received safety training
                               to recognize and avoid the hazards involved.
990-6204C-001                                                                                                            7
                                                                   Important Safety Instructions — SAVE THESE
For Internal Batteries                                                                           INSTRUCTIONS
Electromagnetic Compatibility
                                                           NOTICE
                          RISK OF ELECTROMAGNETIC DISTURBANCE
                          This is a product Category C3 according to IEC 62040-2. This is a product for
                          commercial and industrial applications in the second environment - installation
                          restrictions or additional measures may be needed to prevent disturbances. The
                          second environment includes all commercial, light industry, and industrial
                          locations other than residential, commercial, and light industrial premises
                          directly connected without intermediate transformer to a public low-voltage
                          mains supply. The installation and cabling must follow the electromagnetic
                          compatibility rules, e.g.:
                          •   the segregation of cables,
                          •   the use of shielded or special cables when relevant,
                          •   the use of grounded metallic cable tray and supports.
                          Failure to follow these instructions can result in equipment damage.
Safety Precautions
                                                            DANGER
                          HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                          All safety instructions in this document must be read, understood and followed.
                          Failure to follow these instructions will result in death or serious injury.
                                                            DANGER
                          HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                          Read all instructions in the Installation Manual before installing or working on
                          this UPS system.
                          Failure to follow these instructions will result in death or serious injury.
                                                            DANGER
                          HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                          Do not install the UPS system until all construction work has been completed
                          and the installation room has been cleaned.
                          Failure to follow these instructions will result in death or serious injury.
8                                                                                              990-6204C-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS                                                                                    For Internal Batteries
                                                                  DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                •   The product must be installed according to the specifications and
                                    requirements as defined by Schneider Electric. It concerns in particular the
                                    external and internal protections (upstream breakers, battery breakers,
                                    cabling, etc.) and environmental requirements. No responsibility is assumed
                                    by Schneider Electric if these requirements are not respected.
                                •   After the UPS system has been electrically wired, do not start up the system.
                                    Start-up must only be performed by Schneider Electric.
                                Failure to follow these instructions will result in death or serious injury.
                                                                  DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                The UPS system must be installed according to local and national regulations.
                                Install the UPS according to:
                                •   IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
                                    4–42 - protection against thermal effect, and 60364–4–43 - protection
                                    against overcurrent), or
                                •   NEC NFPA 70, or
                                •   Canadian Electrical Code (C22.1, Part 1)
                                depending on which one of the standards apply in your local area.
                                Failure to follow these instructions will result in death or serious injury.
                                                                  DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                •   Install the UPS system in a temperature controlled indoor environment free
                                    of conductive contaminants and humidity.
                                •   Install the UPS system on a non-flammable, level and solid surface (e.g.
                                    concrete) that can support the weight of the system.
                                Failure to follow these instructions will result in death or serious injury.
                                                                  DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                The UPS is not designed for and must therefore not be installed in the following
                                unusual operating environments:
                                •   Damaging fumes
                                •   Explosive mixtures of dust or gases, corrosive gases, or conductive or
                                    radiant heat from other sources
                                •   Moisture, abrasive dust, steam or in an excessively damp environment
                                •   Fungus, insects, vermin
                                •   Salt-laden air or contaminated cooling refrigerant
                                •   Pollution degree higher than 2 according to IEC 60664-1
                                •   Exposure to abnormal vibrations, shocks, and tilting
                                •   Exposure to direct sunlight, heat sources, or strong electromagnetic fields
                                Failure to follow these instructions will result in death or serious injury.
990-6204C-001                                                                                                       9
                                                                   Important Safety Instructions — SAVE THESE
For Internal Batteries                                                                           INSTRUCTIONS
                                                            DANGER
                         HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                         Do not drill or cut holes for cables or conduits with the gland plates installed and
                         do not drill or cut holes in close proximity to the UPS.
                         Failure to follow these instructions will result in death or serious injury.
                                                           WARNING
                         HAZARD OF ARC FLASH
                         Do not make mechanical changes to the product (including removal of cabinet
                         parts or drilling/cutting of holes) that are not described in the Installation Manual.
                         Failure to follow these instructions can result in death, serious injury, or
                         equipment damage.
                                                           NOTICE
                         RISK OF OVERHEATING
                         Respect the space requirements around the UPS system and do not cover the
                         product’s ventilation openings when the UPS system is in operation.
                         Failure to follow these instructions can result in equipment damage.
                                                           NOTICE
                         RISK OF EQUIPMENT DAMAGE
                         The UPS must use an external regenerative braking kit to dissipate energy
                         when connected to regenerative loads including photovoltaic systems and
                         speed drives.
                         Failure to follow these instructions can result in equipment damage.
10                                                                                              990-6204C-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS                                                                                   For Internal Batteries
Electrical Safety
                                                                  DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                •   Electrical equipment must be installed, operated, serviced, and maintained
                                    only by qualified personnel.
                                •   Apply appropriate personal protective equipment (PPE) and follow safe
                                    electrical work practices.
                                •   Turn off all power supplying the UPS system before working on or inside the
                                    equipment.
                                •   Before working on the UPS system, check for hazardous voltage between all
                                    terminals including the protective earth.
                                •   The UPS contains an internal energy source. Hazardous voltage can be
                                    present even when disconnected from the mains supply. Before installing or
                                    servicing the UPS system, ensure that the units are OFF and that mains and
                                    batteries are disconnected. Wait five minutes before opening the UPS to
                                    allow the capacitors to discharge.
                                •   A disconnection device (e.g. disconnection circuit breaker or switch) must be
                                    installed to enable isolation of the system from upstream power sources in
                                    accordance with local regulations. The disconnection device must be easily
                                    accessible and visible.
                                •   The UPS must be properly earthed/grounded and due to a high leakage
                                    current, the earthing/grounding conductor must be connected first.
                                Failure to follow these instructions will result in death or serious injury.
                                                                  DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                In systems where backfeed protection is not part of the standard design, an
                                automatic isolation device (backfeed protection option or other device meeting
                                the requirements of IEC/EN 62040–1 or UL1778 5th Edition – depending on
                                which of the two standards apply to your local area) must be installed to prevent
                                hazardous voltage or energy at the input terminals of the isolation device. The
                                device must open within 15 seconds after the upstream power supply fails and
                                must be rated according to the specifications.
                                Failure to follow these instructions will result in death or serious injury.
                               When the UPS input is connected through external isolators that, when opened,
                               isolate the neutral or when the automatic backfeed isolation is provided external to
                               the equipment or is connected to an IT power distribution system, a label must be
                               fitted at the UPS input terminals, and on all primary power isolators installed
                               remote from the UPS area and on external access points between such isolators
                               and the UPS, by the user, displaying the following text (or equivalent in a language
                               which is acceptable in the country in which the UPS system is installed):
                                                                  DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS and
                                check for hazardous voltage between all terminals including the protective
                                earth.
                                Failure to follow these instructions will result in death or serious injury.
990-6204C-001                                                                                                     11
                                                                   Important Safety Instructions — SAVE THESE
For Internal Batteries                                                                           INSTRUCTIONS
                                                            CAUTION
                         RISK OF ELECTRICAL DISTURBANCE
                         This product can cause a DC current in the PE conductor. Where a residual
                         current-operated protective device (RCD) is used for protection against
                         electrical shock, only an RCD of Type B is allowed on the supply side of this
                         product.
                         Failure to follow these instructions can result in injury or equipment
                         damage.
Battery Safety
                                                              DANGER
                         HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                         •   Battery circuit breakers must be installed according to the specifications and
                             requirements as defined by Schneider Electric.
                         •   Servicing of batteries must only be performed or supervised by qualified
                             personnel knowledgeable of batteries and the required precautions. Keep
                             unqualified personnel away from batteries.
                         •   Disconnect charging source prior to connecting or disconnecting battery
                             terminals.
                         •   Do not dispose of batteries in a fire as they can explode.
                         •   Do not open, alter, or mutilate batteries. Released electrolyte is harmful to
                             the skin and eyes. It may be toxic.
                         Failure to follow these instructions will result in death or serious injury.
                                                              DANGER
                         HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                         Batteries can present a risk of electric shock and high short-circuit current. The
                         following precautions must be observed when working on batteries
                         •   Remove watches, rings, or other metal objects.
                         •   Use tools with insulated handles.
                         •   Wear protective glasses, gloves and boots.
                         •   Do not lay tools or metal parts on top of batteries.
                         •   Disconnect the charging source prior to connecting or disconnecting battery
                             terminals.
                         •   Determine if the battery is inadvertently grounded. If inadvertently grounded,
                             remove source from ground. Contact with any part of a grounded battery can
                             result in electric shock. The likelihood of such shock can be reduced if such
                             grounds are removed during installation and maintenance (applicable to
                             equipment and remote battery supplies not having a grounded supply
                             circuit).
                         Failure to follow these instructions will result in death or serious injury.
                                                              DANGER
                         HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                         When replacing batteries, always replace with the same type and number of
                         batteries or battery packs.
                         Failure to follow these instructions will result in death or serious injury.
12                                                                                             990-6204C-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS                                                                                   For Internal Batteries
                                                                 CAUTION
                                RISK OF EQUIPMENT DAMAGE
                                •   Mount the batteries in the UPS system, but do not connect the batteries until
                                    the UPS system is ready to be powered up. The time duration from battery
                                    connection until the UPS system is powered up must not exceed 72 hours or
                                    3 days.
                                •   Batteries must not be stored more than six months due to the requirement of
                                    recharging. If the UPS system remains de-energized for a long period, we
                                    recommend that you energize the UPS system for a period of 24 hours at
                                    least once every month. This charges the batteries, thus avoiding
                                    irreversible damage.
                                Failure to follow these instructions can result in injury or equipment
                                damage.
990-6204C-001                                                                                                     13
                                                                                    Important Safety Instructions — SAVE THESE
For Internal Batteries                                                                                            INSTRUCTIONS
                         This is the positive polarity symbol. It is used to identify the positive terminal(s) of equipment which is used
                         with, or generates direct current.
                         This is the negative polarity symbol. It is used to identify the negative terminal(s) of equipment which is
                         used with, or generates direct current.
                         This is the static bypass switch symbol. It is used to indicate switches that are designed
                         to bypass the UPS normal operation, in cases of high inrush or fault conditions.
                         This is the AC/DC converter (rectifier) symbol. It is used to identify an AC/DC converter (rectifier) and, in
                         case of plug-in devices, to identify the relevant receptacles.
                         This is the DC/AC converter (inverter) symbol. It is used to identify an DC/AC converter (inverter) and, in
                         case of plug-in devices, to identify the relevant receptacles.
This is the fuse symbol. It is used to identify fuse boxes or their locations.
                         This is the input symbol. It is used to identify an input terminal when it is necessary to distinguish between
                         inputs and outputs.
                         This is the output symbol. It is used to identify an output terminal when it is necessary to distinguish
                         between inputs and outputs.
                         This is the switch disconnector symbol. It is used to identify the disconnecting device in the form of switch
                         that protects the equipment from short circuit or heavy load current. It opens the circuits once the current
                         flow crosses its maximum limit.
                         This is the circuit breaker symbol. It is used to identify the disconnecting device in the form of circuit
                         breaker that protects the equipment from short circuit or heavy load current. It opens the circuits once the
                         current flow crosses its maximum limit.
                         This is the circuit breaker/switch symbol. It is used to identify the disconnecting device in the form of circuit
                         breaker or switch that protects the equipment from short circuit or heavy load current. It opens the circuits
                         once the current flow crosses its maximum limit.
14                                                                                                                       990-6204C-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS                                                                                                         For Internal Batteries
This is the neutral symbol. It is used to identify the neutral conductors or their locations.
This is the phase conductor symbol. It is used to identify the phase conductors or their locations.
990-6204C-001                                                                                                                           15
For Internal Batteries                                                                    Specifications
Specifications
Input Specifications
                                                            60 kVA                  80 kVA
 Voltage (V)                                                380      400   415      380     400   415
Maximum input current (A) 109 104 100 154 146 141
 Protection                                                 Fuse
 Ramp-in                                                    7 seconds
Bypass Specifications
                                                            60 kVA                  80 kVA
 Voltage (V)                                                380      400   415      380     400   415
Minimum bypass voltage (V) 266 280 291 266 280 291
Maximum bypass voltage (V) 475 480 477 475 480 477
Frequency (Hz) 50 or 60
 Frequency range (%)                                        ±1, ±2, ±4, ±5, ±10. Default is ±10 (user
                                                            selectable).
Output Specifications
                                                            60 kVA                  80 kVA
 Voltage (V)                                                380      400   415      380     400   415
16                                                                                    990-6204C-001
Specifications                                                                                                       For Internal Batteries
                                                                                                60 kVA                  80 kVA
 Voltage (V)                                                                                    380     400    415      380     400    415
Battery Specifications
                                                                                                60 kVA                  80 kVA
 Charging power in % of output power                                                            1–16%                   1–24%
Battery current at full load and nominal battery voltage (A) 133 176
Battery current at full load and minimum battery voltage (A) 166 222
                                60 kVA                                           80 kVA
                                Input                      Bypass                Input                         Bypass
 Breaker type                   NSX160F 36kA AC            NSX100F 36kA AC       NSX160F 36kA AC               NSX160F 36kA AC
                                3P3D 125A TMD              3P3D 100A TMD         3P3D 160A TMD                 3P3D 160A TMD
                                C16F3TM125                 C10F3TM100            C16F3TM160                    C16F3TM160
 In setting                     125                        100                   160                           160
990-6204C-001                                                                                                                            17
For Internal Batteries                                                                                   Specifications
                                                                  DANGER
                              HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                              All wiring must comply with all applicable national and/or electrical codes. The
                              maximum allowable cable size is 50 mm².
                              Failure to follow these instructions will result in death or serious injury.
                          Cable sizes in this manual are based on table B.52.5 of IEC 60364-5-52 with the
                          following assertions:
                              •   90 °C conductors
                              •   An ambient temperature of 30 °C
                              •   Use of copper conductors
                              •   Installation method C
                          PE size is based on table 54.2 of IEC 60364-5-54.
                          If the ambient temperature is greater than 30 °C, larger conductors are to be used
                          in accordance with the correction factors of the IEC.
                                  NOTE: Neutral conductor is sized to handle 1.73 times phase current in case
                                  of high harmonic content from non-linear loads. If non or less harmonic
                                  currents are expected, neutral conductor can be sized accordingly but not less
                                  than the phase conductor.
60 kVA
                         Cable size per phase (mm2)       Neutral cable size (mm2)       PE cable size (mm2)
Input 35 2x25 16
Bypass 25 16
Output 25 2x25 16
Battery 50 50 25
80 kVA
                         Cable size per phase (mm2)       Neutral cable size (mm2)       PE cable size (mm2)
Input 50 2x50 25
Bypass 50 25
Output 50 2x50 25
 16                                  M8                                        KST TLK16-8
 25                                  M8                                        KST TLK25-8
18                                                                                                     990-6204C-001
Specifications                                                                                For Internal Batteries
 35                                M8                                      KST TLK35-8
 50                                M8                                      KST TLK50-8
                                NOTE: If the recommended lug type is not available, use a local M8 lug type
                                as a substitute.
Torque Specifications
 Bolt Size                                                 Torque
M8 17.5 Nm
Clearance
                                NOTE: Clearance dimensions are published for airflow and service access
                                only. Consult with the local safety codes and standards for additional
                                requirements in your local area.
990-6204C-001                                                                                                    19
For Internal Batteries                                                                                                      Specifications
Environmental
                                               Operating                                      Storage
 Elevation                                     Power derating factor:                         < 15000 m above sea level (or in an
 According to IEC 62040–3                      0-1500 m: 1.000                                environment with equivalent air pressure)
                                               1500-2000 m: 0.975
 Audible noise                                 <65 dBA at full load and an ambient
                                               temperature of 30 °C3
Heat Dissipation
                               60 kVA                                                80 kVA
                               W                        BTU/hr                       W                           BTU/hr
 Normal operation              3084                     10523                        4296                        14659
Compliance
 Safety                  IEC 62040-1:2017, Edition 2.0, Uninterruptible power systems (UPS) – Part 1: Safety requirements
                         IEC 62040-1: 2008-6, 1st edition, Uninterruptible Power Systems (UPS) – Part 1: General and safety requirements
                         for UPS
 EMC/EMI/RFI             IEC 62040-2:2016, Edition 3.0, Uninterruptible power systems (UPS) – Part 2: Electromagnetic compatibility
                         (EMC) requirements.
                         IEC 62040-2:2005-10, 2nd edition, Uninterruptible Power Systems (UPS) – Part 2: Electromagnetic compatibility
                         (EMC) requirements
 Performance             IEC 62040-3: 2011-03, 2nd edition Uninterruptible Power Systems (UPS) - Part 3: Method of specifying the
                         performance and test requirements
Transportation ISTA 2B
Pollution degree 2
 Overvoltage             III
 category
20                                                                                                                        990-6204C-001
Overview                                           For Internal Batteries
Overview
Overview of Single UPS
                UIB      Unit input breaker
BB Battery breaker
990-6204C-001                                                         21
For Internal Batteries                                                                                       Overview
BB Battery breaker
22                                                                                                    990-6204C-001
Overview                                                                                     For Internal Batteries
                                                              NOTICE
                              RISK OF EQUIPMENT DAMAGE
                              To ensure correct load sharing in bypass operation in a parallel system, the
                              following recommendations apply:
                              •   The bypass cables must be the same length for all UPSs.
                              •   The output cables must be the same length for all UPSs.
                              •   The input cables must be the same length for all UPSs in a single mains
                                  system.
                              •   Cable formation recommendations must be followed.
                              •   The reactance of busbar layout in the bypass/input and output switchgear
                                  must be the same for all UPSs.
                              If the above recommendations are not followed the result can be uneven load
                              sharing in bypass and overload of individual UPSs.
                              Failure to follow these instructions can result in equipment damage.
 Front View of the 60 kVA 400 V UPS for Internal        Front View of the 80 kVA 400 V UPS for Internal
 Batteries                                              Batteries
990-6204C-001                                                                                                   23
For Internal Batteries                                                            Connect the Power Cables
24                                                                                         990-6204C-001
Connect the Power Cables                                                               For Internal Batteries
990-6204C-001                                                                                             25
For Internal Batteries                                                             Connect the Power Cables
26                                                                                           990-6204C-001
Connect the Power Cables                                                                   For Internal Batteries
10. Fasten the cables to the cable relief in the bottom of the UPS.
990-6204C-001                                                                                                 27
For Internal Batteries                                                              Communication Interfaces
Communication Interfaces
                         A. Parallel ports
                         B. CAN_R: CAN termination resistor
                         C. Dry contacts
                         D. USB port
                         E. EPO
                         F. Slot for optional cold start button
                         G. Network management card (NMC)
                         H. Load bus synchronization port
                         I. RS485
28                                                                                           990-6204C-001
Communication Interfaces                                                                    For Internal Batteries
2. Remove the rear gland plate and the rear brush plate from the UPS.
990-6204C-001                                                                                                   29
For Internal Batteries                                                             Communication Interfaces
5. Fasten the signal cables with cable ties on the rear of the UPS.
                                                         NOTICE
                         RISK OF EQUIPMENT DAMAGE
                         The battery breaker contact drive J6–1 and J6–2 can provide a maximum of +24
                         VDC 400 mA to the undervoltage release coil or shunt trip release coil. If this
                         value is exceeded it can damage the UPS.
                         Failure to follow these instructions can result in equipment damage.
30                                                                                             990-6204C-001
Communication Interfaces                                                                      For Internal Batteries
 Terminal     Function
 BAT_T–1      Input contact for battery temperature
              sensor
 BAT_T–2      Signal ground
 J5–1         AUX contact for battery breaker
 J5–2         Signal ground
NC configuration
990-6204C-001                                                                                                     31
For Internal Batteries                                                                      Communication Interfaces
     •   Disable
     •   INV ON
     •   INV OFF
     •   Battery alarm
     •   Genset enable
     •   Custom alarm 3
     •   Custom alarm 4
     •   Disable ECO
     •   Disable
     •   Common alarm
     •   Normal operation
     •   Battery operation
     •   Static bypass operation
     •   Output overload
     •   Fan inoperable
     •   Battery alarm
     •   Battery disconnected
     •   Battery voltage low
     •   Input out of tolerance
     •   Bypass out of tolerance
     •   EPO activated
     •   Maintenance mode
     •   Parallel lost
32                                                                                                    990-6204C-001
Communication Interfaces                                                                 For Internal Batteries
                           2. Verify the setting of the CAN_R (for location of CAN_R see Communication
                              Interfaces, page 28).
                              – For parallel systems with ≤ 4 parallel UPSs, CAN_R of all UPSs must be in
                                ON position.
                              – For parallel systems with ≥ 5 parallel UPSs, CAN_R of all UPSs must be in
                                OFF position.
990-6204C-001                                                                                               33
For Internal Batteries                                                           Communication Interfaces
34                                                                                         990-6204C-001
Backfeed Protection                                                                    For Internal Batteries
Backfeed Protection
                                                         DANGER
                       HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                       In systems where backfeed protection is not part of the standard design, an
                       automatic isolation device (backfeed protection option or other device meeting
                       the requirements of IEC/EN 62040–1) must be installed to prevent hazardous
                       voltage or energy at the input terminals of the isolation device. The device must
                       open within 15 seconds after the upstream power supply fails and must be rated
                       according to the specifications.
                       Failure to follow these instructions will result in death or serious injury.
                      When the UPS input is connected through external isolators that, when opened,
                      isolate the neutral or when the automatic backfeed isolation is provided external to
                      the equipment or is connected to an IT power distribution system, a label must be
                      fitted at the UPS input terminals, and on all primary power isolators installed
                      remote from the UPS area and on external access points between such isolators
                      and the UPS, by the user, displaying the following text (or equivalent in a language
                      which is acceptable in the country in which the UPS system is installed):
                                                         DANGER
                       HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                       Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS and
                       check for hazardous voltage between all terminals including the protective
                       earth.
                       Failure to follow these instructions will result in death or serious injury.
990-6204C-001                                                                                             35
For Internal Batteries                           Backfeed Protection
36                                                   990-6204C-001
Backfeed Protection                            For Internal Batteries
990-6204C-001                                                     37
For Internal Batteries                                                              Install Batteries in the UPS
                         2. Install battery modules one string at a time and from the bottom and up. One
                            row is one battery string.
38                                                                                             990-6204C-001
Install Batteries in the UPS                                                                 For Internal Batteries
3. Fasten the battery modules with a screw in front of the battery module
                               4. Remove the shrink tubes from the power terminals and connect the power
                                  terminals to the batteries.
                               5. Reinstall the plate in front of the battery shelves.
990-6204C-001                                                                                                   39