Mbpn-A92czx R2 en PDF
Mbpn-A92czx R2 en PDF
10–80 kVA
Operation
10/2018
www.schneider-electric.com
Legal Information
             The Schneider Electric brand and any registered trademarks of Schneider Electric
             Industries SAS referred to in this guide are the sole property of Schneider Electric SA
             and its subsidiaries. They may not be used for any purpose without the owner's
             permission, given in writing. This guide and its content are protected, within the
             meaning of the French intellectual property code (Code de la propriété intellectuelle
             français, referred to hereafter as "the Code"), under the laws of copyright covering
             texts, drawings and models, as well as by trademark law. You agree not to reproduce,
             other than for your own personal, noncommercial use as defined in the Code, all or
             part of this guide on any medium whatsoever without Schneider Electric's permission,
             given in writing. You also agree not to establish any hypertext links to this guide or its
             content. Schneider Electric does not grant any right or license for the personal and
             noncommercial use of the guide or its content, except for a non-exclusive license to
             consult it on an "as is" basis, at your own risk. All other rights are reserved.
             Electrical equipment should be installed, operated, serviced, and maintained only by
             qualified personnel. No responsibility is assumed by Schneider Electric for any
             consequences arising out of the use of this material.
             As standards, specifications, and designs change from time to time, please ask for
             confirmation of the information given in this publication.
                                                                                                                    10–80 kVA
Table of Contents
                Important Safety Instructions — SAVE THESE
                INSTRUCTIONS ........................................................................................5
                     Electromagnetic Compatibility.....................................................................6
                     Safety Precautions ....................................................................................6
                          Electrical Safety ...................................................................................8
                          Battery Safety......................................................................................9
                Single System Overview ......................................................................... 11
                Parallel Redundant System Overview ..................................................13
                User Interface ...........................................................................................15
                     Display ...................................................................................................18
                     View UPS Measurements.........................................................................20
                     View System Configuration.......................................................................22
                Configuration ............................................................................................23
                     Set the Date and Time .............................................................................23
                     Set Up the Display ...................................................................................24
                         Reset the Display Language to English................................................24
                     Set Auto Start, Auto Boost, LCM Alerts, and ECO Mode.........................25
                     Set Battery Charge Mode .........................................................................26
                Operation ..................................................................................................27
                     Operation Modes .....................................................................................27
                     Operation Procedures..............................................................................29
                        Turn on the UPS ................................................................................29
                          Turn off the UPS ................................................................................29
                          Transfer from Normal Operation to ECO Mode .....................................29
                          Transfer from ECO Mode to Normal Operation .....................................30
                          Transfer from Normal Operation to Static Bypass Operation..................30
                          Transfer from Static Bypass Operation to Normal Operation..................30
                          Transfer from Normal Operation to Manual Bypass Operation ...............31
                          Transfer from Manual Bypass Operation to Normal Operation ...............32
                          Transfer from Normal Operation to Manual Bypass Operation –
                          Parallel UPS System ..........................................................................33
                          Transfer from Manual Bypass Operation to Normal Operation –
                          Parallel UPS System ..........................................................................34
                          Isolate One UPS in a Redundant UPS System .....................................36
                          Return an Isolated UPS to a Redundant UPS System...........................37
                          View the Event Log ............................................................................38
                          View the Alarms.................................................................................38
                          View Diagnosis ..................................................................................38
                          View Statistics ...................................................................................40
                Maintenance .............................................................................................41
                     Replace the Filters...................................................................................41
                     Perform LED and Display Test ..................................................................41
                     Perform Advanced Battery Monitoring (ABM) Test......................................42
                     Perform Discharge Test............................................................................43
                Troubleshooting .......................................................................................44
990–5731B–001                                                                                                                   3
Important Safety Instructions — SAVE THESE
INSTRUCTIONS                                                                                                  10–80 kVA
                                                                    DANGER
                                DANGER indicates a hazardous situation which, if not avoided, will result in
                                death or serious injury.
                                Failure to follow these instructions will result in death or serious injury.
                                                                   WARNING
                                WARNING indicates a hazardous situation which, if not avoided, could result
                                in death or serious injury.
                                Failure to follow these instructions can result in death, serious injury, or
                                equipment damage.
                                                                   CAUTION
                                CAUTION indicates a hazardous situation which, if not avoided, could result in
                                minor or moderate injury.
                                Failure to follow these instructions can result in injury or equipment
                                damage.
                                                                   NOTICE
                                NOTICE is used to address practices not related to physical injury. The safety
                                alert symbol shall not be used with this type of safety message.
                                Failure to follow these instructions can result in equipment damage.
Please Note
                               Electrical equipment should only be installed, operated, serviced, and maintained
                               by qualified personnel. No responsibility is assumed by Schneider Electric for any
                               consequences arising out of the use of this material.
                               A qualified person is one who has skills and knowledge related to the construction,
                               installation, and operation of electrical equipment and has received safety training
                               to recognize and avoid the hazards involved.
990–5731B–001                                                                                                            5
                                                          Important Safety Instructions — SAVE THESE
10–80 kVA                                                                               INSTRUCTIONS
Electromagnetic Compatibility
                                                  NOTICE
                 RISK OF ELECTROMAGNETIC DISTURBANCE
                 This is a product Category C3 according to IEC 62040-2. This is a product for
                 commercial and industrial applications in the second environment - installation
                 restrictions or additional measures may be needed to prevent disturbances. The
                 second environment includes all commercial, light industry, and industrial
                 locations other than residential, commercial, and light industrial premises
                 directly connected without intermediate transformer to a public low-voltage
                 mains supply. The installation and cabling must follow the electromagnetic
                 compatibility rules, e.g.:
                 •   the segregation of cables,
                 •   the use of shielded or special cables when relevant,
                 •   the use of grounded metallic cable tray and supports.
                 Failure to follow these instructions can result in equipment damage.
Safety Precautions
                                                   DANGER
                 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                 All safety instructions in this document must be read, understood and followed.
                 Failure to follow these instructions will result in death or serious injury.
                                                   DANGER
                 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                 Read all instructions in the Installation Manual before installing or working on
                 this UPS system.
                 Failure to follow these instructions will result in death or serious injury.
                                                   DANGER
                 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                 Do not install the UPS system until all construction work has been completed
                 and the installation room has been cleaned.
                 Failure to follow these instructions will result in death or serious injury.
                                                   DANGER
                 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                 •   The product must be installed according to the specifications and
                     requirements as defined by Schneider Electric. It concerns in particular the
                     external and internal protections (upstream breakers, battery breakers,
                     cabling, etc.) and environmental requirements. No responsibility is assumed
                     by Schneider Electric if these requirements are not respected.
                 •   After the UPS system has been electrically wired, do not start up the system.
                     Start-up must only be performed by Schneider Electric.
                 Failure to follow these instructions will result in death or serious injury.
6                                                                                     990–5731B–001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS                                                                                                10–80 kVA
                                                                   DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                The UPS system must be installed according to local and national regulations.
                                Install the UPS according to:
                                •   IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
                                    4–42 - protection against thermal effect, and 60364–4–43 - protection
                                    against overcurrent), or
                                •   NEC NFPA 70, or
                                •   Canadian Electrical Code (C22.1, Part 1)
                                depending on which one of the standards apply in your local area.
                                Failure to follow these instructions will result in death or serious injury.
                                                                   DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                •   Install the UPS system in a temperature controlled indoor environment free
                                    of conductive contaminants and humidity.
                                •   Install the UPS system on a non-flammable, level and solid surface (e.g.
                                    concrete) that can support the weight of the system.
                                Failure to follow these instructions will result in death or serious injury.
                                                                   DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                The UPS is not designed for and must therefore not be installed in the following
                                unusual operating environments:
                                •   Damaging fumes
                                •   Explosive mixtures of dust or gases, corrosive gases, or conductive or
                                    radiant heat from other sources
                                •   Moisture, abrasive dust, steam or in an excessively damp environment
                                •   Fungus, insects, vermin
                                •   Salt-laden air or contaminated cooling refrigerant
                                •   Pollution degree higher than 2 according to IEC 60664-1
                                •   Exposure to abnormal vibrations, shocks, and tilting
                                •   Exposure to direct sunlight, heat sources, or strong electromagnetic fields
                                Failure to follow these instructions will result in death or serious injury.
                                                                   DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                Do not drill or cut holes for cables or conduits with the gland plates installed and
                                do not drill or cut holes in close proximity to the UPS.
                                Failure to follow these instructions will result in death or serious injury.
                                                                  WARNING
                                HAZARD OF ARC FLASH
                                Do not make mechanical changes to the product (including removal of cabinet
                                parts or drilling/cutting of holes) that are not described in the Installation Manual.
                                Failure to follow these instructions can result in death, serious injury, or
                                equipment damage.
990–5731B–001                                                                                                            7
                                                              Important Safety Instructions — SAVE THESE
10–80 kVA                                                                                   INSTRUCTIONS
                                                      NOTICE
                     RISK OF OVERHEATING
                     Respect the space requirements around the UPS system and do not cover the
                     product’s ventilation openings when the UPS system is in operation.
                     Failure to follow these instructions can result in equipment damage.
                                                      NOTICE
                     RISK OF EQUIPMENT DAMAGE
                     Do not connect the UPS output to regenerative load systems including
                     photovoltaic systems and speed drives.
                     Failure to follow these instructions can result in equipment damage.
Electrical Safety
                                                       DANGER
                     HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
                     •   Electrical equipment must be installed, operated, serviced, and maintained
                         only by qualified personnel.
                     •   The UPS system must be installed in a room with restricted access (qualified
                         personnel only).
                     •   Apply appropriate personal protective equipment (PPE) and follow safe
                         electrical work practices.
                     •   Turn off all power supplying the UPS system before working on or inside the
                         equipment.
                     •   Before working on the UPS system, check for hazardous voltage between all
                         terminals including the protective earth.
                     •   The UPS contains an internal energy source. Hazardous voltage can be
                         present even when disconnected from the utility/mains supply. Before
                         installing or servicing the UPS system, ensure that the units are OFF and
                         that utility/mains and batteries are disconnected. Wait five minutes before
                         opening the UPS to allow the capacitors to discharge.
                     •   A disconnection device (e.g. disconnection circuit breaker or switch) must be
                         installed to enable isolation of the system from upstream power sources in
                         accordance with local regulations. This disconnection device must be easily
                         accessible and visible.
                     •   The UPS must be properly earthed/grounded and due to a high leakage
                         current, the earthing/grounding conductor must be connected first.
                     Failure to follow these instructions will result in death or serious injury.
                                                       DANGER
                     HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                     In systems where backfeed protection is not part of the standard design, an
                     automatic isolation device (backfeed protection option or other device meeting
                     the requirements of IEC/EN 62040–1 or UL1778 5th Edition – depending on
                     which of the two standards apply to your local area) must be installed to prevent
                     hazardous voltage or energy at the input terminals of the isolation device. The
                     device must open within 15 seconds after the upstream power supply fails and
                     must be rated according to the specifications.
                     Failure to follow these instructions will result in death or serious injury.
                    When the UPS input is connected through external isolators that, when opened,
                    isolate the neutral or when the automatic backfeed isolation is provided external to
8                                                                                        990–5731B–001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS                                                                                               10–80 kVA
                                                                   DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS and
                                check for hazardous voltage between all terminals including the protective
                                earth.
                                Failure to follow these instructions will result in death or serious injury.
Battery Safety
                                                                   DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                •   Battery circuit breakers must be installed according to the specifications and
                                    requirements as defined by Schneider Electric.
                                •   Servicing of batteries must only be performed or supervised by qualified
                                    personnel knowledgeable of batteries and the required precautions. Keep
                                    unqualified personnel away from batteries.
                                •   Disconnect charging source prior to connecting or disconnecting battery
                                    terminals.
                                •   Do not dispose of batteries in a fire as they can explode.
                                •   Do not open, alter, or mutilate batteries. Released electrolyte is harmful to
                                    the skin and eyes. It may be toxic.
                                Failure to follow these instructions will result in death or serious injury.
                                                                   DANGER
                                HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                Batteries can present a risk of electric shock and high short-circuit current. The
                                following precautions must be observed when working on batteries
                                •   Remove watches, rings, or other metal objects.
                                •   Use tools with insulated handles.
                                •   Wear protective glasses, gloves and boots.
                                •   Do not lay tools or metal parts on top of batteries.
                                •   Disconnect the charging source prior to connecting or disconnecting battery
                                    terminals.
                                •   Determine if the battery is inadvertently grounded. If inadvertently grounded,
                                    remove source from ground. Contact with any part of a grounded battery can
                                    result in electric shock. The likelihood of such shock can be reduced if such
                                    grounds are removed during installation and maintenance (applicable to
                                    equipment and remote battery supplies not having a grounded supply
                                    circuit).
                                Failure to follow these instructions will result in death or serious injury.
990–5731B–001                                                                                                        9
                                                     Important Safety Instructions — SAVE THESE
10–80 kVA                                                                          INSTRUCTIONS
                                              DANGER
            HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
            When replacing batteries, always replace with the same type and number of
            batteries or battery packs.
            Failure to follow these instructions will result in death or serious injury.
                                              NOTICE
            RISK OF EQUIPMENT DAMAGE
            •   Wait until the system is ready to be powered up before installing batteries in
                the system. The time duration from battery installation until the UPS system
                is powered up must not exceed 72 hours or 3 days.
            •   Batteries must not be stored more than six months due to the requirement of
                recharging. If the UPS system remains de-energized for a long period,
                Schneider Electric recommends that you energize the UPS system for a
                period of 24 hours at least once every month. This charges the batteries,
                thus avoiding irreversible damage.
            Failure to follow these instructions can result in equipment damage.
10                                                                               990–5731B–001
Single System Overview                                                                           10–80 kVA
990–5731B–001                                                                                           11
10–80 kVA                                                            Single System Overview
12                                                                          990–5731B–001
Parallel Redundant System Overview                                                                      10–80 kVA
990–5731B–001                                                                                                  13
10–80 kVA                                                           Parallel Redundant System Overview
14                                                                                    990–5731B–001
User Interface                                                                                                                                           10–80 kVA
User Interface
                             User Interface on the UPS Cabinet
                                     Normal operation
                                                                                    N or ma l Op er at io n                               ESC
                                 C Battery operation                             A      F lo at C ha rg e
                                     Bypass operation
                                                                                 L oa d 0 58 % C ap . 0 93 %                             B ?
                                                                                 4 05 U in 4 00 U ou t 5 0 H z
                                     Common Alarm
                                                                     D                                                 D
                                                                            ON                                   OFF
                                    Mains
                                                                                                                                                Output
                                    Input
                                                              Q001       T101              T101
                                                                                                       SBS               Q601
                                                                                                       Q401
Float
                                                    Initial
                                                                          Q201
                                                                                                  E                      Q528
                                    Bypass
                                      Input
                                                              Q501
Overtemperature
                              A. Display
                              B. Display navigation keys
                              C. UPS status LEDs that show the current operation mode of the UPS
                              D. ON and OFF buttons
                              E. Mimic diagram that shows the power flow of the UPS
                              F. Alarm LEDs.
Use the HELP key to access help information about a menu point.
990–5731B–001                                                                                                                                                  15
10–80 kVA                                                                                                          User Interface
Mimic Diagram
                                                   A B        C               D               E        F
                             Mains
                                                                                                                     Output
                             Input
                                                       Q001   T101            T101
                                                                          I            SBS
                                                                                       Q401
                                                                                                  L   Q601
                                                                                                             M
                                             G
                                             Float
Initial
                                                                                              K
                                                               Q201                                   Q528
                                                               H                                      N
                                                   J
                             Bypass
                               Input
                                                       Q501
16                                                                                                                990–5731B–001
User Interface                                                                                     10–80 kVA
Menu Tree
 Overview Menu
 Main Menu                System Status
                          Settings             System
                                               Date and time
                                               Display setup
                          Diagnosis
                          Configuration
990–5731B–001                                                                                             17
10–80 kVA                                                                                  User Interface
Display
                      In normal operation with no alarms present, the display will show the overview
                      screen with the system operation mode, operation information, and
                      measurements.
                         NOTE: If the advanced battery monitoring (ABM) function is not available, the
                         overview screen will not show calculated runtime or capacity.
Standby
                       Normal Operation
                       Float Charge
                       Load 058% Cap. 093%
                       xxxUin xxxUout xxHz
                      The second line shows the battery charge mode: Float Charge, Boost Charge,
                      Initial Charge, or Cyclic Charge.
                       Battery Operation
                       Runtime: 02h 42min
                       Load 058% Cap. 093%
                       xxxUin xxxUout xxHz
                      The calculated remaining runtime for the load percentage and the battery charge
                      is shown on the second line if advanced battery monitoring (ABM) is set up. If an
                      ABM test or a discharge test is running this is indicated in the second line. See
                      Perform Advanced Battery Monitoring (ABM) Test, page 42 and Perform
                      Discharge Test, page 43.
                       Temporary Static
                       Bypass Operation
                       Load 058% Cap. 093%
                       xxxUin xxxUout xxHz
                       Requested Static
                       Bypass Operation
                       Load 058% Cap. 093%
                       xxxUin xxxUout xxHz
18                                                                                       990–5731B–001
User Interface                                                                               10–80 kVA
                       Manual Bypass
                       Normal Operation
                       Load 058% Cap. 093%
                       405Uin xxxUout xxHz
                      The second line indicates the state of the isolated system: Standby, Normal
                      Operation, Battery Operation, Static Bypass Operation. Input voltage, output
                      voltage, and output frequency are not shown in manual bypass operation.
990–5731B–001                                                                                       19
10–80 kVA                                                                            User Interface
               Out kW         kVA       PF ↑
               1 017.3       019.4     096C
               2 020.3       020.3     1.00
               3 016.7       018.7     0.81I↓
               •   Battery voltage
               •   Battery current (positive = charging, negative = discharging)
               •   Actual battery charge in % of installed capacity
               •   Calculated runtime for the actual load and battery charge
20                                                                                 990–5731B–001
User Interface                                                         10–80 kVA
                  Temperature            ↑
                  Sensor 1:         028°C
                  Sensor 2:         024°C
                  Sensor 3:         036°C↓
990–5731B–001                                                                21
10–80 kVA                                                                       User Interface
                 •   System type
                 •   SKU
                 •   System configuration: Single or Redundant
                 •   System number
                 Alarm Thresholds: ↑
                   Load:     075 kVA
                   Runtime: 00h 20min
                   Bat. Temp.: 075 °C
22                                                                            990–5731B–001
Configuration                                                                           10–80 kVA
Configuration
Set the Date and Time
                  1. From the Main Menu, select Settings > Date and time using the UP/DOWN
                     keys and the ENTER key. You can press the ESC key at any time to cancel
                     the modification of the parameter values.
                  3. Press the UP/DOWN keys to modify the parameter values and press the
                     ENTER key to confirm modification and move to the next parameter value.
                  4. When you have modified all the parameter values, the cursor will point to SET
                     – press the ENTER key to confirm and save the modified date and time
                     values.
990–5731B–001                                                                                  23
10–80 kVA                                                                                Configuration
                           Display Setup:
                           Language: English
                           Contrast: 1
                           Beeper Volume: 3
                       2. Press the UP/DOWN keys to select a parameter to modify and press the
                          ENTER key.
                           Display Setup:
                           ►Language: English
                           Contrast: 1
                           Beeper Volume: 3
                       3. Press the UP/DOWN keys to modify the parameter values and press the
                          ENTER key to save the modification and move to the next parameter value.
                           Display Setup:
                           ↕Language: English
                           Contrast: 2
                           Beeper Volume: 1
                       4. When you have modified all the parameter values, press the ESC key return
                          to a higher menu level.
                       1. From the overview menu, press the ESC key ten times (within 10 seconds).
                          The display language will now reset to English.
24                                                                                    990–5731B–001
Configuration                                                                      10–80 kVA
Set Auto Start, Auto Boost, LCM Alerts, and ECO Mode
                 1. From the Main Menu, select Settings > System using the UP/DOWN keys
                    and the ENTER key. You can press the ESC key at any time to cancel the
                    modification of the parameter values.
                     System:
                     ►Auto Start : On
                      Auto Boost : Off
                      LCM Alerts: On↓
                     System:↑
                     ►ECO Mode : On
                 2. Select Auto Start, Auto Boost, LCM Alerts, or ECO Mode using the UP/
                    DOWN keys and the ENTER key.
                 3. Select On or Off using the UP/DOWN keys and the ENTER key to save the
                    setting.
                     System:
                     ↕Auto Start: On
                      Auto Boost: Off
                      LCM Alerts: On↓
                     System:↑
                     ↕ECO Mode : On
990–5731B–001                                                                                25
10–80 kVA                                                                            Configuration
                     Charge mode:
                           Float
                     Ubat: 440.3V      438 V
                     Ibat:+004.2A      007.2A
                     Charge mode:
                           Cyclic
                     Ubat: 440.3V      438 V
                     Ibat:+004.2A      007.2A↓
                    Cyclic charge mode has a second page that shows the configured period and
                    charge time.
                 2. Press the ENTER key to start modifying the parameter values.
                 3. Press the UP/DOWN keys to modify the parameter values and press the
                    ENTER key to confirm modification.
                     Charge mode:
                     ↕      Float
                     Ubat: 440.3V      438 V
                     Ibat:+004.2A      007.2A
26                                                                                 990–5731B–001
Operation                                                                                       10–80 kVA
Operation
Operation Modes
                      The manual bypass switch (Q601) offers the possibility of setting the system volt-
                      free when performing work inside the system, e.g. service and maintenance.
                      There is no interruption to the load when the switch is switched over. Two
                      positions are available:
                       •   AUTO: In this position, the load is supplied by the UPS.
                       •   BYPASS: In this position the load is supplied directly from the bypass mains.
Normal Operation
                      In normal operation, the manual bypass switch must be in the position AUTO.
                      During normal operation, the UPS supports the load with conditioned power.
                      While the UPS is in normal operation, the status LED Normal operation is green.
Battery Operation
                      In battery operation, the manual bypass switch must be in the position AUTO.
                      If the input source becomes unavailable or outside the specified limits, the UPS
                      transfers to battery operation and supports the load with conditioned power from
                      the DC source.
                      If the input source is recovered, the system is automatically transferred back to
                      normal operation.
                      While the UPS system is in battery operation, the status LED Battery operation is
                      yellow.
                      If the battery discharge limit is approached an alarm is activated. If the batteries
                      are depleted, the system transfers to bypass operation if the bypass source is
                      available and within tolerance. If the input source or the bypass source are still
                      unavailable, the UPS system will turn off and stop supplying the load, but if Auto
                      Start is configured for the UPS system, then the UPS will automatically restart and
                      return to normal operation again as soon as the input source is recovered.
990–5731B–001                                                                                             27
10–80 kVA                                                                                      Operation
                     The UPS will transfer to normal or battery operation if the bypass source becomes
                     unavailable.
                     While the UPS system is in requested static bypass, the status LED Bypass
                     operation is yellow.
ECO Mode
                     In ECO mode, the manual bypass switch must be in the position AUTO. The UPS
                     can be transferred to ECO mode following a command from the display or when
                     enabled the system will automatically switch to ECO mode after system has been
                     running for one minute in normal operation and the bypass voltage quality is
                     above the acceptable limits. ECO mode will transfer the system to static bypass
                     operation. In this operation mode the total system efficiency is increased. During
                     static bypass operation, the load is supplied from the bypass source. To avoid
                     interruptions during the transfer, the voltage, frequency and phase relation of the
                     UPS system must be synchronized to the bypass source. The UPS will transfer to
                     normal or battery operation if the bypass source becomes unavailable or if the
                     bypass voltage quality drops below the acceptable limits. While the UPS system is
                     in requested static bypass, the status LED Bypass operation is yellow.
Charger Only
                     When the UPS is in charger mode, the UPS does not supply the connected load
                     with power.
Standby
                     When the UPS is in standby mode, the UPS is OFF and does not supply the
                     connected load with power, and the batteries are not charged.
OFF
                     When the UPS is in OFF mode, the UPS does not supply the connected load with
                     power, and the batteries are not charged.
28                                                                                       990–5731B–001
Operation                                                                                       10–80 kVA
Operation Procedures
Turn on the UPS
                       1. Press the ON and the OFF buttons simultaneously on the display. The UPS
                          will shut down with no voltage on the output.
                                                          DANGER
                           HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                           After this operation, power will still be present on the power connection
                           terminals. Ensure that the protection covers are installed.
                           Failure to follow these instructions will result in death or serious
                           injury.
                       1. From the Main Menu, select System Control > Bypass Control using the
                          UP/DOWN keys and the ENTER key.
                           Confirm action:
                           UPS into ECO Mode
                            NO, Abort
                           ►YES, UPS into ECO Mode
                       2. Select YES, UPS into ECO Mode to transfer to ECO Mode. The following
                          message will appear on the display:
                       3. After the transfer to ECO Mode is complete, press the ESC key.
                             NOTE: For parallel UPS units, it is only necessary to perform the transfer
                             into ECO Mode on one UPS – the other parallel UPSs will automatically
                             transfer to ECO Mode.
990–5731B–001                                                                                          29
10–80 kVA                                                                                        Operation
                        1. From the Main Menu, select System Control > Bypass Control using the
                           UP/DOWN keys and the ENTER key.
                        2. Select YES, UPS out of ECO Mode to transfer to normal operation.
                            Confirm action:
                            UPS out of ECO Mode
                             NO, Abort
                            ►YES, UPS out of ECO Mode
                               NOTE: For parallel UPS units, it is only necessary to perform the transfer
                               into normal operation on one UPS – the other parallel UPSs will
                               automatically transfer to normal operation.
                        1. From the Main Menu, select System Control > Bypass Control using the
                           UP/DOWN keys and the ENTER key.
                            Confirm action:
                            UPS into Bypass
                             NO, Abort
                            ►YES, UPS into Bypass
                        1. From the Main Menu, select System Control > Bypass Control using the
                           UP/DOWN keys and the ENTER key.
                        2. Select YES, UPS out of Byp to transfer to normal operation.
                            Confirm action:
                            UPS out of Bypass
                             NO, Abort
                            ►YES, UPS out of Byp
                               NOTE: For parallel UPS units, it is only necessary to perform the transfer
                               into normal operation on one UPS – the other parallel UPSs will
                               automatically transfer to normal operation.
30                                                                                         990–5731B–001
Operation                                                                                      10–80 kVA
                       1. From the Main Menu, select System Control > Bypass Control using the
                          UP/DOWN keys and the ENTER key.
                       2.
                            – With ECO Mode enabled: Select YES, UPS into ECO Mode to transfer
                              to bypass operation.
                               Confirm action:
                               UPS into ECO Mode
                                NO, Abort
                               ►YES, UPS into ECO Mode
                            – With ECO Mode disabled: Select YES, UPS into Bypass to transfer to
                              bypass operation.
                               Confirm action:
                               UPS into Bypass
                                NO, Abort
                               ►YES, UPS into Bypass
                       3. If the UPS is able to turn on the static bypass switch, the following message
                          appears You may switch to manual bypass now!. Perform the manual
                          switch-over now to go to manual bypass operation.
                       4. When the UPS has transferred to manual bypass operation this message will
                          appear on the display:
990–5731B–001                                                                                             31
10–80 kVA                                                                                     Operation
                                Confirm action:
                                UPS into ECO Mode
                                 NO, Abort
                                ►YES, UPS into ECO Mode
                            – With ECO Mode disabled: Select YES, UPS into Bypass to transfer to
                              bypass operation.
                                Confirm action:
                                UPS into Bypass
                                 NO, Abort
                                ►YES, UPS into Bypass
                       4. If the UPS is able to turn on the static bypass switch, the following message
                          appears You may switch to auto now!. Perform the manual switch-over now
                          to go to static bypass operation.
                       5. From the Main Menu, select System Control > Bypass Control using the
                          UP/DOWN keys and the ENTER key.
                       6.
                            – With ECO Mode enabled: Select YES, UPS out of ECO Mode to transfer
                              to normal operation.
                                Confirm action:
                                UPS out of ECO Mode
                                 NO, Abort
                                ►YES, UPS out of ECO Mode
                            – With ECO Mode disabled: Select YES, UPS out of Bypass to transfer to
                              normal operation.
                                Confirm action:
                                UPS out of Bypass
                                 NO, Abort
                                ►YES, UPS out of Bypass
32                                                                                      990–5731B–001
Operation                                                                                       10–80 kVA
Transfer from Normal Operation to Manual Bypass Operation – Parallel UPS System
                       1. On UPS1: From the Main Menu, select System Control > Bypass Control
                          using the UP/DOWN keys and the ENTER key.
                       2.
                            – With ECO Mode enabled: Select YES, UPS into ECO Mode to transfer
                              to bypass operation. All UPS units in the parallel system will now transfer
                              to static bypass operation.
                                Confirm action:
                                UPS into ECO Mode
                                 NO, Abort
                                ►YES, UPS into ECO Mode
                            – With ECO Mode disabled: Select YES, UPS into Bypass to transfer to
                              bypass operation. All UPS units in the parallel system will now transfer to
                              static bypass operation.
                                Confirm action:
                                UPS into Bypass
                                 NO, Abort
                                ►YES, UPS into Bypass
                       3. If the UPS is able to turn on the static bypass switch, the following message
                          appears You may switch to manual bypass now!.
                       4. Turn switch Q601 on UPS1 from position AUTO to position BYPASS.
                       5. Turn switch Q601 on UPS2 from position AUTO to position BYPASS.
                       6. To isolate the UPS, turn switch Q528 of UPS1 and UPS 2 to the OFF position.
                       7. The overview screen now shows:
                                Manual Bypass
                               Normal Operation
                             Load xxx% Cap. 093%
                             405Uin xxxUot xxHz
990–5731B–001                                                                                             33
10–80 kVA                                                                                        Operation
Transfer from Manual Bypass Operation to Normal Operation – Parallel UPS System
                                Confirm action:
                                UPS into ECO Mode
                                 NO, Abort
                                ►YES, UPS into ECO Mode
                            – With ECO Mode disabled: Select YES, UPS into Bypass to transfer to
                              bypass operation. All UPS units in the parallel system will now transfer to
                              static bypass operation.
                                Confirm action:
                                UPS into Bypass
                                 NO, Abort
                                ►YES, UPS into Bypass
                       4. If the UPS is able to turn on the static bypass switch, the following message
                          appears You may switch to auto now!.
                       5. Turn switch Q601 on UPS1 from position BYPASS to position AUTO.
                       6. Turn switch Q601 on UPS2 from position BYPASS to position AUTO.
                       7. The overview screen now shows:
                                Requested Static
                               Bypass Operation
                             Load xxx% Cap. 093%
                             405Uin xxxUot xxHz
                       8. On one UPS: From the Main Menu, select System Control > Bypass
                          Control using the UP/DOWN keys and the ENTER key.
34                                                                                         990–5731B–001
Operation                                                                                10–80 kVA
                 9.
                      – With ECO Mode enabled: Select YES, UPS out of ECO Mode to transfer
                        to normal operation. All UPS units in the parallel system will now transfer
                        to normal operation.
                          Confirm action:
                          UPS out of ECO Mode
                           NO, Abort
                          ►YES, UPS out of ECO Mode
                      – With ECO Mode disabled: Select YES, UPS out of Bypass to transfer to
                        normal operation. All UPS units in the parallel system will now transfer to
                        normal operation.
                          Confirm action:
                          UPS out of Bypass
                           NO, Abort
                          ►YES, UPS out of Bypass
                          Normal Operation
                         Float Charge
                       Load xxx% Cap. 093%
                       405Uin xxxUot xxHz
990–5731B–001                                                                                    35
10–80 kVA                                                                                       Operation
                      1. Press the ON and the OFF buttons simultaneously on the display. The UPS
                         will shut down with no voltage on the output.
                                                         DANGER
                          HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                          After this operation, power will still be present on the power connection
                          terminals. Ensure that the protection covers are installed.
                          Failure to follow these instructions will result in death or serious
                          injury.
2. Open coupling switch Q694 for UPS2 or Q692 for UPS1 (if present).
                                                         DANGER
                          HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                          In a redundant system without coupling switches there will be voltage
                          backfeed from the other UPS when only UPS is switched off for
                          maintenance.
                          Failure to follow these instructions will result in death or serious
                          injury.
                                                         DANGER
                          HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                          Hazardous voltage is still present on the connecting terminals as input
                          source, bypass source, and batteries are still connected.
                          Failure to follow these instructions will result in death or serious
                          injury.
36                                                                                       990–5731B–001
Operation                                                                                                          10–80 kVA
                                                                                   DANGER
                                             HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                             After this operation, power will still be present on the power connection
                                             terminals. Ensure that the protection covers are installed.
                                             Failure to follow these instructions will result in death or serious
                                             injury.
                                       8. Close coupling switch Q694 for UPS2 or Q692 for UPS1 (if present).
                                       9. Press the ON button on the display.
                                          The load is supplied by both UPS units in redundant operation with load
                                          sharing.
1. The system can have one internal battery switch Q201, or one battery switch Q211, or both.
990–5731B–001                                                                                                                37
10–80 kVA                                                                                  Operation
                      1. From the Main Menu, select Event Log > View Log using the UP/DOWN
                         keys and the ENTER key. Wait a few seconds while the event log is being
                         prepared.
                      2. Use the UP/DOWN keys to browse through the log entries. All system events
                         and alarms are stored in this event log.
                      1. From the Main Menu, select Event Log > Clear Log > YES, Clear Log using
                         the UP/DOWN keys and the ENTER key.
                      1. From the Main Menu, select Event Log > View Alarms using the UP/DOWN
                         keys and the ENTER key. Wait a few seconds while the alarm list is being
                         prepared.
                      2. Use the UP/DOWN keys to browse through the alarms present on the UPS
                         system.
Example
                          Present Alarms:     ↓
                          Bypass RMS not ok 123
                          Output RMS not ok 034
                          Inverter async. 456
View Diagnosis
                      1. From the Main Menu, select System Status > Diagnosis using the UP/
                         DOWN keys and the ENTER key.
                      2. Use the UP/DOWN keys to browse through the diagnosis screens. Here you
                         can see information about the digital inputs, internal measurements, and
                         internal status.
Breaker status:
                          Q502 Q528↑
                          OFF OFF
                          Q601 Q611
                          OFF  OFF
38                                                                                   990–5731B–001
Operation                                                                            10–80 kVA
                 Inputs status:              ↑
                 ECB-EPO     :0
                 ECB-IN1     :1
                 ECB-IN2     :1↓
                 •   Rectifier input voltage per phase measured after the rectifier transformer
                 •   Bypass voltage per phase measured after the bypass transformer
                 •   Inverter output voltage per phase measured before the output
                     transformer
                 U   dc-bus:      + 389.5V↑
                                  - 370.8V↓
                 Temperatures            ↑
                 T001: 123 °C
                 T401: 105 °C
                 T501: 042 °C↓
990–5731B–001                                                                                39
10–80 kVA                                                                               Operation
View Statistics
                   1. From the Main Menu, select Event Log > View Statistic using the UP/
                      DOWN keys and the ENTER key.
                   2. Use the UP/DOWN keys to browse through the statistics available on the
                      UPS.
                   023 Transfers->Bat.
                   006 Transfers->Byp.
                   004836hr Inv. Time
                   024h 13min on Bat↓
• The highest and lowest measured input voltages on mains and battery
Clear Statistics
                   1. From the Main Menu, select Event Log > Clear Statistic > YES, Clear
                      Statistic using the UP/DOWN keys and the ENTER key.
40                                                                                990–5731B–001
Maintenance                                                                               10–80 kVA
Maintenance
Replace the Filters
                      1. Pull the top of the air grid free of the cabinet.
                  All status, mimic diagram, and alarm LEDs will be activated. All segments on the
                  display will be switched on. When the test is complete all LEDs will go back to
                  normal function and the display returns to the overview menu.
990–5731B–001                                                                                      41
10–80 kVA                                                                               Maintenance
                 1. From the Main Menu, select System Control > Functional Test > ABM Test
                    > Start ABM test using the UP/DOWN keys and the ENTER key.
                     ABM test:
                     ►Start ABM test
                      Reset ABM data
                     Confirm action:
                     Start ABM test
                      NO, Abort
                     ►YES, Start test
During the ABM test, the overview menu shows the following:
                     Battery Operation
                     ABM test
                     Load 058% Cap. 093%
                     405Uin 400Uout 50Hz
42                                                                                   990–5731B–001
Maintenance                                                                               10–80 kVA
                 1. From the Main Menu, select System Control > Functional Test >
                    Discharge Test using the UP/DOWN keys and the ENTER key.
                     Functional test:
                     ►Discharge test
                      ABM test
                     Confirm action:
                     Start discharge test
                      NO, Abort
                     ►YES, Start test
During the discharge test, the overview menu shows the following:
                     Battery Operation
                     Discharge test
                     Load xxx% Cap. xxx%
                     xxxUin xxxUout xxHz
                        NOTE: After the test the system returns to the former operation mode.
                        The data of the last discharge test are shown in the menu View Statistic.
990–5731B–001                                                                                     43
10–80 kVA                                                                                                          Troubleshooting
Troubleshooting
Alarm Messages
                                   The following table lists all pop-up messages that can appear on the display:
 186        Bat. temp. warning      Battery temperature     The battery temperature is above the             Check the air inlet
                                    has exceeded upper      configured warning level.
                                    limit                                                                    Check the ambient
                                                                                                             temperature
 266        -                       High output voltage     The UPS output voltage (RMS) is above the        -
                                                            configured voltage level.
269 Overload UPS overloaded The UPS output is overloaded (>105%). Reduce the load
 304        High Battery voltage    Battery voltage too     The battery voltage is above the configured      -
                                    high                    high battery voltage warning level. This
                                                            warning is suppressed in battery operation.
 306        Battery discharged      Inverter shutdown due   The battery voltage is below the configured      Charge the battery
                                    to low Battery          low battery voltage shutdown level.
 826        -                       Battery earth fault     The UPS measures a battery earth fault.          Check the battery
                                                                                                             wiring
 312        Battery weak            Battery weak            The advanced battery monitoring test has         Charge the battery
                                                            detected a weak battery.
                                                                                                             Maintain the battery
 313        Battery inoperable      Battery inoperable      The advanced battery monitoring test has         Maintain the battery
                                                            detected an inoperable battery.
331 Q201/Q202: open Battery disconnected The battery switch Q201 / Q202 is open. -
 351        ABUS term incorrect     ABUS termination        The ABUS wiring is disconnected or the           -
                                    incorrect               ABUS termination is incorrect.
 371        No parallel master      No Master present in    No master is present in the redundant            -
                                    the parallel system     system.
 375        Redundancy alarm        Loss of Parallel        At least one UPS is isolated or turned off. In   -
                                    Redundancy              this case the redundancy operation is not
                                                            assured.
 397        PBUS1 com inoperable    Parallel bus            The internal or external PBUS1 wiring            -
                                    communication on        (parallel bus) is disconnected or the PBUS1
                                    cable 1 inoperable      termination is incorrect.
 398        PBUS2 com inoperable    Parallel bus            The internal or external PBUS2 wiring            -
                                    communication on        (parallel bus) is disconnected or the PBUS2
                                    cable 2 inoperable      termination is incorrect.
 440        EPO active              EPO activated           The digital input "emergency power off           -
                                                            (EPO)" is activated (contact open) or the
                                                            EPO wiring is disconnected.
 447        Int inoperable state    Internal inoperable     An internal inoperable state was detected.       -
                                    state detected
 803        -                       Static Bypass Switch    The communication to the SBS is not              -
                                    inoperable              working or DC is detected during requested
                                                            static bypass operation.
 814        -                       Overtemperature in PM   The UPS measures a temperature above the         Check the air inlet and
                                    or Trafos               threshold level in one of the power modules      the air filters
                                                            or in one of the power transformers.
                                                                                                             Check the ambient
                                                                                                             temperature
44                                                                                                                 990–5731B–001
Troubleshooting                                                                                                             10–80 kVA
 HMI_1    -                        ABUS communication         Communication via ABUS does not work.            Check the ABUS
                                   inoperable                                                                  wiring
 HMI_2    -                        ABUS supply missing        The SELV4 supply of the HMI is missing.          Check the ABUS
                                                                                                               wiring
 HMI_3    -                        No more space for          The HMI Flash memory does not offer              Unplug and reconnect
                                   configurations in HMI      enough free space to save the configuration      HMI supply
                                   FLASH memory               change.
 HMI_4    -                        HMI SRAM is                The external SRAM on the HMI was detected        -
                                   inoperable                 to be inoperable.
 HMI_5    -                        HMI code memory            The HMI firmware detected an invalid code        -
                                   checksum invalid           memory CRC.
 18       Temporary Bypass     -                           Temporary Static          The system is in          Check the event log
                                                           bypass                    temporary static          for the reason, why the
                                                                                     bypass operation due      system has switched
                                                                                     to a problem in the       to static bypass
                                                                                     system.                   operation
990–5731B–001                                                                                                                         45
10–80 kVA                                                                                                          Troubleshooting
 102        PFC inoperable        PFC OK                PFC inoperable           The rectifier part of the   -
                                                                                 power module is not
                                                                                 working.
 110        Charger inoperable    Charger OK            Charger inoperable       The charger part of the     -
                                                                                 power module is not
                                                                                 working.
 132        Inverter inoperable   Inverter OK           Inverter inoperable      The inverter part of the    -
                                                                                 power module is not
                                                                                 working.
 146        Inverter async.       Inverter sync.        Inverter                 The UPS is unable to        Check the bypass
                                                        asynchronous             synchronize to the          source quality
                                                                                 bypass source.              (voltage, frequency)
 161        Static Bypass ON      Static Bypass OFF     SBS ON                   The system is in static     -
                                                                                 bypass operation. The
                                                                                 bypass supplies the
                                                                                 load (temporary or
                                                                                 requested static
                                                                                 bypass operation).
 162        SBS inoperable        SBS OK                SBS inoperable           The static bypass           Check if the static
                                                                                 switch is not               bypass switch
                                                                                 energized, the              controller board is
                                                                                 communication wiring        energized
                                                                                 from the UPS
                                                                                 controller to the static    Check the
                                                                                 bypass switch               communication wiring
                                                                                 controller is               between main
                                                                                 disconnected or the         controller and the
                                                                                 static bypass switch        static bypass switch
                                                                                 controller is               controller
                                                                                 inoperable.
                                                                                                             Check the function of
                                                                                                             the static bypass
                                                                                                             switch controller board
 163        SBS Indep fired       SBS OK                SBS Independent          The SBS is no longer        Check the
                                                        fired                    controlled by the UPS       communication wiring
                                                                                 controller and is
                                                                                 locked in the fire state.   Check the function of
                                                                                                             the UPS controller
                                                                                                             This state can only be
                                                                                                             left when the SBS
                                                                                                             controller board is
                                                                                                             reset. This should be
                                                                                                             done by switching the
                                                                                                             manual bypass switch
                                                                                                             to 'Bypass'
46                                                                                                                 990–5731B–001
Troubleshooting                                                                                                   10–80 kVA
 187      Bat. temp. shutdown   Battery temp. OK      Battery temperature   The battery              Check the air inlet
                                                      shutdown              temperature is above
                                                                            the configured           Check the ambient
                                                                            shutdown level. The      temperature
                                                                            battery charger
                                                                            switches off.            Check the health of
                                                                                                     the battery
990–5731B–001                                                                                                                 47
10–80 kVA                                                                                                       Troubleshooting
 201        SBS fan inoperable     SBS fan OK            SBS fan inoperable     One of the static         Check the static
                                                                                bypass switch fans is     bypass switch fans
                                                                                inoperable.
 202        Trafo fan inoperable   Trafo fans OK         Trafo fan inoperable   One of the transformer    Check the transformer
                                                                                fans is inoperable        fans
                                                                                (rectifier transformer,
                                                                                output transformer or
                                                                                bypass transformer).
 220        Mains RMS not OK       Mains RMS OK          Mains RMS not OK       The rectifier mains       Check the quality of
                                                                                voltage is out of the     the mains input
                                                                                configured tolerance.     (voltage and
                                                                                                          frequency)
 221        Mains Inp RMS not      Mains Input RMS OK    Mains input RMS not    The rectifier mains       Check the quality of
            OK                                           OK                     voltage on primary        the mains input
                                                                                side of the input         (voltage and
                                                                                transformer is out of     frequency)
                                                                                the configured
                                                                                tolerance.
 222        Mains FAST not OK      Mains FAST OK         Mains FAST not OK      The rectifier mains       -
                                                                                voltage is out of
                                                                                tolerance.
 223        Mains freq. not OK     Mains frequency OK    Mains frequency not    The rectifier mains       -
                                                         OK                     frequency is out of the
                                                                                configured tolerance.
 224        Mains phase missing    Mains phases OK       Mains phase missing    A rectifier mains input   Check the contacts of
                                                                                phase is missing.         the input switch
 228        Mains synch.           Mains synch. OK       Mains synch missing    The mains PFC             Check the quality of
            missing                                                             rectifier is unable to    the mains input
                                                                                synchronize to the        (voltage and
                                                                                rectifier mains input.    frequency)
 229        Mains neutral lost     Mains neutral OK      Mains neutral          The rectifier mains       Check the mains
                                                         missing                neutral is missing.       neutral wiring
48                                                                                                              990–5731B–001
Troubleshooting                                                                                                     10–80 kVA
 241      Byp. Inp. RMS not      Bypass Input RMS      Bypass input RMS       The bypass mains           -
          OK                     OK                    not OK                 voltage on the primary
                                                                              side of the bypass
                                                                              transformer is out of
                                                                              the configured
                                                                              tolerance.
 242      Bypass FAST not OK     Bypass FAST OK        Bypass FAST not OK     The bypass voltage is      -
                                                                              out of the configured
                                                                              tolerance. The UPS is
                                                                              unable to transfer to
                                                                              static bypass
                                                                              operation.
 243      Bypass freq. not OK    Bypass frequency      Bypass frequency       The bypass frequency       -
                                 OK                    not OK                 is out of the configured
                                                                              tolerance. The UPS is
                                                                              unable to transfer to
                                                                              static bypass
                                                                              operation.
 244      Bypass phase           Bypass phases OK      Bypass phase           One phase of the           -
          missing                                      missing                bypass mains is
                                                                              missing.
 245      Byp. In. phase miss.   Byp. Inp. phases OK   Bypass input phase     One phase of the           -
                                                       missing                bypass voltage on the
                                                                              primary side of the
                                                                              transformer is missing.
 260      Inv. Out. RMS not OK   Inv. Out. RMS OK      Inverter output RMS    The UPS output             -
                                                       not OK                 voltage is out of the
                                                                              configured tolerance.
 261      Output RMS not OK      Output RMS OK         Output RMS not OK      The output voltage on      -
                                                                              the secondary side of
                                                                              the output transformer
                                                                              is out of the configured
                                                                              tolerance.
 262      Output FAST not OK     Output FAST OK        Output FAST not OK     The UPS output             -
                                                                              voltage is out of the
                                                                              configured tolerance.
 263      Output freq. not OK    Output frequency OK   Output frequency not   The UPS output             -
                                                       OK                     frequency is out of the
                                                                              configured tolerance.
 264      Output phase           Output phases OK      Output phase           One phase of the           -
          missing                                      missing                output voltage on the
                                                                              secondary side of the
                                                                              transformer is missing.
 267      High load warning      Load OK               High Load warning      The load is above the      Reduce the load
                                                                              configured load alarm
                                                                              level.
 268      Current limitation     No limitation         Current limitation     The inverter current       Reduce the load
                                                                              limiter is active.
 269      Overload               No overload           Output overloaded      The UPS output is          Reduce the load
                                                                              overloaded (>105%).
 301      High Bat.V.            Battery voltage OK    High Battery           The battery voltage is     -
          shutdown                                     shutdown               above the configured
                                                                              high battery voltage
                                                                              shutdown level. The
                                                                              charger is shut down.
 304      High Battery voltage   Battery voltage OK    High Battery warning   The battery voltage is     -
                                                                              above the configured
                                                                              high battery voltage
                                                                              warning level. This
                                                                              warning is suppressed
                                                                              in battery operation.
990–5731B–001                                                                                                                49
10–80 kVA                                                                                                     Troubleshooting
 306        Battery discharged     Battery OK            Low Battery           The battery voltage is   Charge the battery
                                                         shutdown              below the configured
                                                                               low battery voltage
                                                                               shutdown level.
 307        Bat. earth fault pos   No bat. earth fault   Battery earth fault   The UPS measures a       Check the battery
                                                         positive              positive battery earth   wiring
                                                                               fault.
 308        Bat. earth fault neg   No bat. earth fault   Battery earth fault   The UPS measures a       Check the battery
                                                         negative              negative battery earth   wiring
                                                                               fault.
 309        ABM test Start         -                     ABM test started      The advanced battery     -
                                                                               monitoring test has
                                                                               been started.
 310        ABM test End           -                     ABM test done         The advanced battery     -
                                                                               monitoring test has
                                                                               been completed.
 311        ABM test Stop          -                     ABM test aborted      The advanced battery     -
                                                                               monitoring test has
                                                                               been aborted.
 312        Battery weak           Battery OK            Battery weak          The advanced battery     Charge the battery
                                                                               monitoring test has
                                                                               detected a weak          Maintain the battery
                                                                               battery.
 313        Battery inoperable     Battery OK            Battery inoperable    The advanced battery     Maintain the battery
                                                                               monitoring test has
                                                                               detected an inoperable
                                                                               battery.
 314        Low runtime warning    Runtime OK            Low runtime warning   The battery runtime is   -
                                                                               less than 2 minutes
                                                                               above the configured
                                                                               warning level.
 315        Low runtime alarm      Runtime OK            Low runtime alarm     The battery runtime is   -
                                                                               below the configured
                                                                               battery runtime level.
 331        Q201/Q202: open        Q201/Q202: closed     Q201/Q202 open        The battery switch       -
                                                                               Q201 / Q202 is open.
 332        Q501: open             Q501: closed          Q501 open             The bypass mains         -
                                                                               input switch Q501 is
                                                                               open.
 334        Q611: open             Q611: closed          Q611 open             The load output switch   -
                                                                               Q611 is open.
 338        K401: open             K401: closed          K401 open             The bypass backfeed      -
                                                                               contactor K401 is
                                                                               open.
 339        Q528: open             Q528: closed          Q528 open             The SBS input switch
                                                                               Q528 is open.
 351        ABUS term incorrect    ABUS term OK          ABUS termination      The ABUS wiring is       -
                                                         incorrect             disconnected or the
                                                                               ABUS termination is
                                                                               incorrect.
50                                                                                                           990–5731B–001
Troubleshooting                                                                                                    10–80 kVA
 374      Parallel load alarm    Parallel load OK       Parallel load alarm   The actual load is too     -
                                                                              high to guarantee the
                                                                              redundant operation. If
                                                                              one UPS switches
                                                                              OFF, the remaining
                                                                              systems would be
                                                                              overloaded.
 375      Redundancy alarm       Redundancy OK          Redundancy alarm      At least one UPS is        -
                                                                              isolated or turned off.
                                                                              In this case the
                                                                              redundancy operation
                                                                              is not assured.
 397      PBUS1 com              PBUS1 OK               PBUS1                 The internal or            -
          inoperable                                    communication         external PBUS1 wiring
                                                        inoperable            (parallel bus) is
                                                                              disconnected or the
                                                                              PBUS1 termination is
                                                                              incorrect.
 398      PBUS2 com              PBUS2 OK               PBUS2                 The internal or            -
          inoperable                                    communication         external PBUS2 wiring
                                                        inoperable            (parallel bus) is
                                                                              disconnected or the
                                                                              PBUS2 termination is
                                                                              incorrect.
 399      PBUS1 term             PBUS1 term OK          PBUS 1 termination    The internal or            -
          incorrect                                     incorect              external PBUS1 wiring
                                                                              (parallel bus) is
                                                                              disconnected or the
                                                                              PBUS1 termination is
                                                                              incorrect.
 400      PBUS2 term             PBUS2 term OK          PBUS 2 termination    The internal or            -
          incorrect                                     incorect              external PBUS2 wiring
                                                                              (parallel bus) is
                                                                              disconnected or the
                                                                              PBUS2 termination is
                                                                              incorrect.
 440      EPO active             EPO cleared            Emergency Power       The digital input          -
                                                        Off (EPO)             "emergency power off
                                                                              (EPO)" is activated
                                                                              (contact open) or the
                                                                              EPO wiring is
                                                                              disconnected.
 447      Int inoperable state   Int operation OK       Internal inoperable   An internal inoperable     -
                                                        state                 state was detected.
 448      Locked in Bypass       Bypass unlocked        SBS locked            The system has been        -
                                                                              locked in static bypass
                                                                              operation after 8
                                                                              unsuccessful tries to
                                                                              switch back to normal
                                                                              or battery operation.
990–5731B–001                                                                                                                51
10–80 kVA                                                                                                     Troubleshooting
 814        -                    -                     Overtemperature        The UPS measures a        Check the air inlet and
                                                                              temperature above the     the air filters
                                                                              threshold level in one
                                                                              of the power modules      Check the ambient
                                                                              or in one of the power    temperature
                                                                              transformers.
                                                                                                        Check the output load
 826        -                    -                     Battery earth fault    The UPS measures a        Check the battery
                                                                              battery earth fault.      wiring
52                                                                                                            990–5731B–001
Troubleshooting                                                                                                                10–80 kVA
 146       Inverter asynchronous                 The UPS is unable to synchronize to the       Check the bypass source quality
                                                 bypass source.                                (voltage, frequency)
 305       Battery discharged                    The battery voltage is below the              Charge the battery
                                                 configured low battery voltage warning
                                                 level.
 331       Q201/Q202 open                        The battery switch Q201 / Q202 is open.       -
 814       Overtemperature                       The UPS measures a temperature                Check the air inlet and the air filters
                                                 above the threshold level in one of the
                                                 power modules or in one of the power          Check the ambient temperature
                                                 transformers.
                                                                                               Check the output load
990–5731B–001                                                                                                                            53
10–80 kVA                                                                                          Troubleshooting
54                                                                                                 990–5731B–001
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.schneider-electric.com