0% found this document useful (0 votes)
27 views36 pages

Ups-Apc en

The document provides operational guidelines and safety instructions for the Symmetra PX UPS systems, including models with power ratings of 48, 96, 160 kW at 400 V and 100 kW at 208 V. It covers installation, operation modes, maintenance procedures, and troubleshooting, emphasizing the importance of qualified personnel for handling electrical equipment. Additionally, it includes legal information regarding the use and reproduction of the guide's content.

Uploaded by

daskalovski
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views36 pages

Ups-Apc en

The document provides operational guidelines and safety instructions for the Symmetra PX UPS systems, including models with power ratings of 48, 96, 160 kW at 400 V and 100 kW at 208 V. It covers installation, operation modes, maintenance procedures, and troubleshooting, emphasizing the importance of qualified personnel for handling electrical equipment. Additionally, it includes legal information regarding the use and reproduction of the guide's content.

Uploaded by

daskalovski
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 36

Symmetra™ PX

48, 96, and 160 kW 400 V


100 kW 208 V
Operation

9/2023

www.schneider-electric.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
48, 96, and 160 kW 400 V 100 kW 208 V

Table of Contents
Important Safety Instructions — SAVE THESE
INSTRUCTIONS .........................................................................................5
Symbols in This Manual ..............................................................................5
Electromagnetic Compatibility .....................................................................6
FCC Statement ..........................................................................................6
Safety Precautions .....................................................................................6
Overview ......................................................................................................8
User Interface ............................................................................................8
Display Interface.........................................................................................8
Menu Tree............................................................................................9
Operation ................................................................................................... 11
Operation Modes...................................................................................... 11
Operation Procedures............................................................................... 11
Perform a Total Power Off....................................................................12
Start the System after Total Power Off ..................................................15
Turn the UPS Load Off ........................................................................17
Turn the UPS Load On ........................................................................18
Transfer the UPS into Maintenance Bypass Operation...........................18
Return to Normal Operation from Maintenance Bypass
Operation ...........................................................................................20
View the Status Screens......................................................................23
View the Log Screen ...........................................................................23
Configuration .............................................................................................24
System Settings .......................................................................................24
Set Up the Network .............................................................................24
Change the Display Interface Settings ..................................................24
Change the Date and Time ..................................................................24
Set Up Capacity Parameters for Classic Battery ....................................25
Configure Input Contacts .....................................................................25
Configure Output Relays .....................................................................25
Maintenance ..............................................................................................27
Life Cycle Monitoring (LCM) ......................................................................27
Parts Replacement ...................................................................................27
Determine if you need a Replacement Part ...........................................27
Return Parts to Schneider Electric........................................................28
Replacement Parts .............................................................................28
Troubleshooting ........................................................................................29
Status and Alarm Messages ......................................................................29
Modular Distribution Alarm List ..................................................................32
PDU Alarm List.........................................................................................33

990-3015L-001 3
Important Safety Instructions — SAVE THESE
INSTRUCTIONS 48, 96, and 160 kW 400 V 100 kW 208 V

Important Safety Instructions — SAVE THESE


INSTRUCTIONS
This manual contains important safety instructions for Symmetra PX 48 kW UPS,
Symmetra PX 100 kW UPS, SYCFXR9, SYCFXR48 Battery Cabinet, and
Symmetra PX PDPM100 that should be followed during installation and
maintenance of the UPS and batteries.
Read these instructions carefully and look at the equipment to become familiar
with it before trying to install, operate, service or maintain it. The following safety
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.

Symbols in This Manual

The addition of this symbol to a “Danger” or “Warning” safety message


indicates that an electrical hazard exists which will result in personal injury if the
instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages with this symbol to avoid possible injury
or death.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.

NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.

990-3015L-001 5
Important Safety Instructions — SAVE THESE
48, 96, and 160 kW 400 V 100 kW 208 V INSTRUCTIONS

Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
Per IEC 62040-1: "Uninterruptible power systems (UPS) -- Part 1: Safety
Requirements," this equipment, including battery access, must be inspected,
installed and maintained by a skilled person.
The skilled person is a person with relevant education and experience to enable
him or her to perceive risks and to avoid hazards which the equipment can create
(reference IEC 62040, section 3.102).

Electromagnetic Compatibility

NOTICE
RISK OF ELECTROMAGNETIC DISTURBANCE
This is a product category C2 UPS product. In a residential environment, this
product may cause radio inference, in which case the user may be required to
take additional measures.
Failure to follow these instructions can result in equipment damage.

FCC Statement
NOTE: This equipment has been tested and found to comply with the limits for
a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user
will be required to correct the interference at his own expense.
Any changes or modifications not expressly approved by the party responsible for
compliance could void the user’s authority to operate the equipment.

Safety Precautions

DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
All safety instructions in this document must be read, understood and followed.
Failure to follow these instructions will result in death or serious injury.

6 990-3015L-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS 48, 96, and 160 kW 400 V 100 kW 208 V

DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
After the UPS system has been electrically wired, do not start up the system.
Start-up must only be performed by Schneider Electric.
Failure to follow these instructions will result in death or serious injury.

990-3015L-001 7
48, 96, and 160 kW 400 V 100 kW 208 V Overview

Overview
User Interface

A Load Powered LED When this LED is green, power to the load is on. When this LED is yellow, the load
is supplied through the batteries. When this LED is flashing yellow, the unit is in
bypass.

B Check Log LED When this LED is green, a new event has been added to the event log.

C Warning LED When this LED is yellow, there are one or more warning alarms in the system.

D Critical LED When this LED is red, there are one or more critical alarms in the system.

E LCD screen Displays alarms, status data, instructional help, and configuration items.

F Arrow keys Scrolls through and select menu items.

G Enter key Opens menu items and confirms changes to the system parameters.

H Help key Opens context-sensitive help.

I ESC key Returns to the previous screen displayed.

Display Interface
Overview Screens
The overview screen is the main entrance to the user functions of the display
interface. The arrow keys take you from one screen to another. When the system
is running, the display will scroll through screens showing information about the
system and any active alarms.
NOTE: The data values shown are for example only.

No Active Alarms

System Date/Time:
28-Mar-2010 10:37:01

Volts In Volts Out


L1: xxx L1: xxx
L2: xxx L2: xxx
L3: xxx L3: xxx

Out kVAAmps kW
L1:
xxx xx.xxx.x
L2:
xxx xx.xxx.x
L3:
xxx xx.xxx.x

Symmetra PX 160 kW
Runtime: xxhr xxmin
Capacity xxx.x%
UPS Load: xxx%

8 990-3015L-001
Overview 48, 96, and 160 kW 400 V 100 kW 208 V

System Bypass State:


UPS Operation
UPS State:
On Line

NOTE: Press the enter key to go from any overview screen to the main menu
screen.

Menu Tree
The menu tree provides a quick overview of the functions and views you may
access.

UPS Power Control


UPS UPS Status
UPS Tests & Diags

UPS Configuration

Total Loading

Power Dist Modular Loading

Volt-Meter
Subfeeds
Switchgear Status

Factory

Input Contacts

Environment Output Relays

Alarm Relay Map

Env Monitoring Card

Main Menu Screen Alarms All Active Alarms


Active by Severity

Active by Type

Log View New Log Items

View Entire Log

Clear Entire Log

Network Setup

Admin Local Interface


Date/Time
Device ID
Manufacturer Data
Factory Defaults

Firmware Upgrade

Life cycle Monitor

On any screen and any line, press ? for context


Help sensitive help. Try it now...

990-3015L-001 9
48, 96, and 160 kW 400 V 100 kW 208 V Overview

NOTE: The display provides access to more functions than described in this
manual. Those functions should not be accessed without the assistance of
Schneider Electric Customer Support in order to avoid unwanted load impacts.
If you by accident go beyond the functions described, press the ESC key to
return to previous screens.

10 990-3015L-001
Operation 48, 96, and 160 kW 400 V 100 kW 208 V

Operation
Operation Modes
The UPS has three operation modes: normal operation, battery operation and
static bypass operation. If the UPS system includes a PDU, a PDU with modular
batteries, or an external maintenance bypass enclosure, the mode maintenance
bypass operation also becomes available.

Normal Operation
During normal operation, the UPS converts the utility/mains supply to conditioned
power for the connected load.

Battery Operation
During battery operation, the UPS provides conditioned power to the connected
load from its batteries for a finite period. The UPS transfers to battery operation if
the utility/mains power supply becomes unavailable or is outside the predefined
limits.

Static Bypass Operation


Static bypass operation is a feature that keeps the load supplied directly from the
utility/mains supply during different scenarios on the UPS or downstream from the
UPS. In static bypass operation, the utility/mains is supplying power to the
connected load directly, bypassing all internal UPS functions.

Maintenance Bypass Operation (Optional)


The UPS can be connected to a PDU, a PDU with modular batteries, or an
external maintenance bypass enclosure that enables the user to bypass the UPS
completely for maintenance purposes that might even include replacement of the
entire UPS. In this situation, the connected load will then be fed directly from the
utility/mains supply, and there will be no conditioning of the supply or battery
backup of the load.

Operation Procedures
Breakers/Switches in the System
Q1 UPS input

Q2 UPS output

Q3 Maintenance bypass

Q5 Static bypass input (only in dual utility/mains systems)

990-3015L-001 11
48, 96, and 160 kW 400 V 100 kW 208 V Operation

NOTE: If the system does not contain a PDU or PDU with modular batteries,
the Q1, Q2, and Q3 switches and the Q5 breaker (if present) should be
located in an optional external maintenance bypass enclosure. See the
documentation included with the maintenance bypass enclosure for additional
information.

Perform a Total Power Off

NOTICE
RISK OF LOAD DROP
This procedure will disconnect the load.
Failure to follow these instructions can result in equipment damage.

NOTE: If shutdown via the display is disabled, then you cannot perform this
procedure and the message: Command not allowed, UPS configured to
never shutdown appears. If you want to enable shutdown via the display, this
is done by a Schneider Electric field service engineer.
1. Select UPS > UPS Power Control > Turn UPS Off and press the enter key.

→ Turn UPS Off


Reboot UPS
UPS into Bypass
UPS to Sleep

2. Select No, Don’t Notify to shut down without delay and press the enter key.
NOTE: This action will cut all power to the load without shutting it down
first. If you want to shut down the servers first, then choose Yes, Notify
Servers. Note that this function is only available for servers with
PowerChute.
Notify PowerChute ?
Cancel
Yes, Notify Servers
→ No, Don't Notify

3. Confirm YES, Turn UPS Off and press the enter key.

Turn UPS off


Without Server
Notification?
> NO, ABORT
→> YES, Turn UPS Off

4. Wait for the UPS to turn off.


Turning UPS off,
please wait...

12 990-3015L-001
Operation 48, 96, and 160 kW 400 V 100 kW 208 V

5. Set the UPS SYSTEM ENABLE switch to the OFF position.

Front View of the UPS

6. Set the Q2 switch to the OFF position.


7. Set the Q1 switch to the OFF position.
8. Set the Q5 breaker to the OFF position (if applicable).
9. Verify that the maintenance bypass switch (Q3) is in the OFF position.

990-3015L-001 13
48, 96, and 160 kW 400 V 100 kW 208 V Operation

10. Set the DC DISCONNECT switch to the OFF position on all battery cabinets
and the PDU with modular batteries (if applicable) and on the UPS (only for
Symmetra PX 48 kW) .

Modular Battery Cabinets/PDU with Modular Batteries

Classic Battery Cabinet

11. Disconnect all battery units by removing them (all battery types) or pulling
them out to the disconnect line (modular batteries only).

NOTICE
RISKOF TILTING AND MODULAR BATTERY DAMAGE
To ensure that the UPS cabinet and the modular battery cabinet does not
tip, do not pull out the modular battery units beyond the red disconnect line.
If you intend to completely remove the modular battery units, remove them
from the UPS cabinet and modular battery cabinets one at a time. If you
don’t pull the modular battery units out to the red disconnect line, this could
cause deep discharge/damage to the modular batteries.
Failure to follow these instructions can result in equipment damage.

14 990-3015L-001
Operation 48, 96, and 160 kW 400 V 100 kW 208 V

12. Set the upstream utility/mains power to the OFF or LOCKED OUT position. If
the UPS has a dual utility/mains supply, set both supplies to the OFF or
LOCKED OUT position.

13. Measure bypass/output DC and utility/mains to ensure that the system is


completely powered off.

Start the System after Total Power Off


NOTE: If batteries/battery units have been removed or disconnected for the
total power off, reinsert and reconnect them before starting up the system.
1. Set the upstream utility/mains power to the ON or LOCKED IN position. If the
UPS has a dual utility/mains supply, set both supplies to the ON or LOCKED
IN position.

990-3015L-001 15
48, 96, and 160 kW 400 V 100 kW 208 V Operation

2. Set the DC DISCONNECT switch to the ON position on all modular battery


cabinets and the PDU with modular batteries (if applicable) and on the UPS
(only for Symmetra PX 48 kW).

Modular Battery Cabinets/PDU with Modular Batteries

Classic Battery Cabinet

3. Set the Q1 switch to the ON position.


4. Set the SYSTEM ENABLE switch on the UPS to the ON position.

Front View of UPS

NOTE: Wait approximately two minutes for the system to start.

16 990-3015L-001
Operation 48, 96, and 160 kW 400 V 100 kW 208 V

5. Set the Q5 breaker to the ON position (if applicable).


NOTE: The H2 LED next to the Q2 switch will turn on, indicating that the
Q2 switch can be operated.
6. Set the Q2 switch on the PDU, PDU with modular batteries, or the external
maintenance bypass to the ON position.
7. Select UPS > UPS Power Control > Turn UPS On and press the enter key.

→ Turn UPS On
UPS On Into Bypass

8. Confirm by selecting Yes, Turn UPS On and press the enter key.

Confirm:
Turn UPS On ?
>NO, ABORT
→ >Yes, Turn UPS On

9. Wait for the UPS to turn on.


Turning UPS on,
Please wait...

Turn the UPS Load Off


NOTE: If shutdown via the display is disabled, then you cannot perform this
procedure and the message: Command not allowed, UPS configured to
never shutdown appears. If you want to enable shutdown via the display, this
is done by a Schneider Electric field service engineer.
1. Select UPS > UPS Power Control > Turn UPS Off and press the enter key.

→ Turn UPS Off


Reboot UPS
UPS Into Bypass
UPS To Sleep

2. Select No, Don’t Notify and press the enter key.


NOTE: This action will cut all power to the load without shutting it off first.
If you want to shut down the servers first, then choose Yes, Notify
Servers. Note that this function is only available for servers with
PowerChute.
Notify PowerChute?
Cancel
Yes, Notify Servers
→ No, Don't Notify

3. Confirm YES, Turn UPS Off and press the enter key.

Turn UPS Off Without


Server Notification?
>NO, ABORT
→ YES, Turn UPS Off

4. Wait for the UPS to turn off.


Turning UPS off,
please wait...

990-3015L-001 17
48, 96, and 160 kW 400 V 100 kW 208 V Operation

Turn the UPS Load On


1. Select UPS > UPS Power Control > Turn UPS On and press the enter key.

→ Turn UPS On
UPS On Into Bypass

2. Confirm by selecting Yes, Turn UPS On and press the enter key.

Confirm:
Turn UPS On?
>NO, ABORT
→ >YES, Turn UPS On

3. Wait for the UPS to turn the load on.


Turning UPS on,
please wait...

Transfer the UPS into Maintenance Bypass Operation


NOTE: If shutdown via the display is disabled, then you cannot perform this
procedure and the message: Command not allowed, UPS configured to
never shutdown appears. If you want to enable shutdown via the display, this
is done by a Schneider Electric field service engineer.
1. Select UPS > UPS Power Control > UPS into Bypass and press the enter
key.

Turn UPS Off


Reboot UPS
→ UPS into Bypass
UPS to Sleep

2. Select Yes, Into Bypass and press the enter key.

Confirm:
UPS into Bypass?
NO, ABORT
→ YES, Into Bypass

3. Wait for the transfer to complete.

Putting UPS into


Bypass, please
wait....

4. Confirm that the transfer to bypass is complete.


NOTE: The H3 LED next to the Q3 switch will turn on, indicating that the
Q3 switch can be operated.

UPS is now in
Bypass.
Press any key....

5. Set the Q3 switch to the ON position.


NOTE: The H2 LED beside the Q2 switch will turn on, indicating that the
Q2 switch can be operated.
6. Set the Q2 switch to the OFF position.

18 990-3015L-001
Operation 48, 96, and 160 kW 400 V 100 kW 208 V

7. Select UPS > UPS Power Control > Turn UPS Off and press the enter key.

→ Turn UPS Off


Reboot UPS
UPS into Bypass
UPS to Sleep

8. Select No, Don’t Notify and press the enter key.

Notify PowerChute ?
Cancel
Yes, Notify Servers
→ No, Don't Notify

9. Confirm by selecting YES, Turn UPS Off and press the enter key.

Turn UPS Off Without


Server Notification?
>NO, ABORT
→ >YES, Turn UPS Off

10. Wait for the UPS to turn off.


Turning UPS off,
please wait....

11. Set the UPS SYSTEM ENABLE switch to the OFF position.

Front View of UPS

12. Set the Q1 switch to the OFF position.


13. Set the Q5 breaker to the OFF position (if applicable).

990-3015L-001 19
48, 96, and 160 kW 400 V 100 kW 208 V Operation

14. Set the DC DISCONNECT switch to the OFF position on all modular battery
cabinets and the PDU with modular batteries (if applicable) and on the UPS
(only for Symmetra PX 48 kW).

Modular Battery Cabinets/PDU with Modular Batteries

Classic Battery Cabinet

Return to Normal Operation from Maintenance Bypass Operation


1. Set the DC DISCONNECT switch to the ON position on all modular battery
cabinets and the PDU with modular batteries (if applicable) and on the UPS
(only for Symmetra PX 48 kW).

20 990-3015L-001
Operation 48, 96, and 160 kW 400 V 100 kW 208 V

2. Set the Q1 switch to the ON position.

Modular Battery Cabinet/PDU with Modular Batteries

Classic Battery Cabinet

3. Set the SYSTEM ENABLE switch on the UPS to the ON position.


NOTE: Wait approximately two minutes for the system to start.

Front View of UPS

4. Set the Q5 breaker to the ON position (if applicable).

990-3015L-001 21
48, 96, and 160 kW 400 V 100 kW 208 V Operation

5. Select UPS > UPS Power Control > UPS On into Bypass and press the
enter key.

Turn UPS On
→ UPS On into Bypass

6. Select Continue Turn On and press the enter key.

Battery back-up not


available in bypass!
>Cancel
→ >Continue Turn On

7. Confirm by selecting Yes, On Into Bypass and press the enter key.

Confirm:
UPS on Into Bypass
>NO, ABORT
→ >Yes, On Into Bypass

8. Wait for the UPS to turn the load on.


Turning UPS on Into
Bypass.
Please wait...

9. The UPS is now ON.


NOTE: The H2 LED next to the Q2 switch will turn on, indicating that the
Q2 switch can be operated.

UPS’s output is now


in bypass
Press any key...

10. Set the Q2 switch on the PDU, PDU with modular batteries or the external
maintenance bypass enclosure to the ON position.
NOTE: The H3 LED next to the Q3 switch will turn on, indicating that the
Q3 switch can be operated.
11. Set the Q3 switch to the OFF position.
12. Use the display interface to transfer the UPS out of bypass:
13. Select UPS > UPS Power Control > UPS out of Bypass and press the enter
key.

Turn UPS Off


Reboot UPS
→ UPS out of Bypass
UPS to Sleep

14. Confirm by selecting Yes, Out of Bypass and press the enter key.

Confirm:
UPS out of Bypass?
>NO, ABORT
→ >YES, Out of Bypass

15. Wait for the UPS to transfer out of bypass.

Putting UPS out of


Bypass, please
wait....

22 990-3015L-001
Operation 48, 96, and 160 kW 400 V 100 kW 208 V

16. The UPS is now out of bypass and is in normal operation.

UPS is now out of


bypass
Press any key....

View the Status Screens


1. Select UPS > UPS Status and press the enter key.

UPS Power Control


→ UPS Status
UPS Tests & Diags
UPS Configuration

2. Use the arrow keys to navigate through the status screens.

Symmetra PX 160 kW
Status: On Line
No UPS Alarms

View the Log Screen


1. Select Log and press the enter key.
2. Select View New Log Items to see new log items when the Check Log LED
is green and press the enter key. To see historical events select the View
Entire Log and press the enter key.

→ View New Log Items


View Entire Log
Clear Entire Log

3. Use the arrow keys to navigate through the log screens.

Log Item ≥ 1 of 2
03/14/07 10:37:02
<Description>

990-3015L-001 23
48, 96, and 160 kW 400 V 100 kW 208 V Configuration

Configuration
System Settings
Set Up the Network
1. Select Admin > Network Setup > Mode and press the enter key.

Stat:
→ Mode:
IP:
SM:

2. Select Fixed IP Addr to give a specific IP address to the UPS system or


select one of the other two methods to obtain an IP address. In this example
Fixed IP Addr mode is selected.
→ Fixed IP Addr
DHCP Only
BOOTP Only

3. Select IP (Internet Protocol), SM (Subnet Mask), and GW (GateWay) and


change the settings using the arrow keys. Press the enter key to confirm the
changes.

→ IP:
→ SM:
→ GW:

Change the Display Interface Settings


1. Select Admin > Local Interface > Display Behaviour and press the enter
key.

Local Password
→ Display Behaviour
Alarm Beeper

2. Select Contrast, Key Click, Beeper Volume, or Check Log Light and
change the settings using the arrow keys. Press the enter key to save the
changes.

→ Contrast ≥ 4
Key Click ≥ On
Beeper Volume > High
Check Log Light

Change the Date and Time


1. Select Admin > Date/Time and press the enter key.

Network Setup
Local Interface
→ Date/Time
Device ID

24 990-3015L-001
Configuration 48, 96, and 160 kW 400 V 100 kW 208 V

2. Select Date or Time and change the settings by using the arrow keys. Press
the enter key to save the changes.

Mode: Manual
Format: mm/dd/yyyy
Date: xx/xx/xxxx
Time: xx:xx:xx

Set Up Capacity Parameters for Classic Battery


NOTE: It is necessary to set up the capacity parameters for UPSs with classic
batteries. This is not necessary for UPSs with modular batteries.
1. Select UPS > UPS Configuration > Other and press the enter key.

UPS Configuration
Shutdown Output
Alarms Bypass
Default → Other

2. Select BatFrmAmpHour and input the battery capacity C10Ah and press the
enter key to confirm.

Self Test: xx days


UPS ID: XXXXX
→ BatFrmAmpHour: C10AH
Charger Rate: xxx

Configure Input Contacts


1. Select Environment > Input Contacts and press the enter key.

→ Input Contacts
Output Relays
Alarm Relay Map

2. Select desired input contact, 1 through 4, select Configuration, and press


the enter key.

Input Contact:xof4
<contact name>
Status: Normal
→ Configuration

3. Change the settings for Name/Location, Alarms, Severity, and Normal


state.

Name/Location x
Alarms: Enabled
Severity: Critical
Normal: Open

Configure Output Relays


1. Select Environment > Output Relays and press the enter key.

Input Contacts
→ Output Relays
Alarm Relay Map

990-3015L-001 25
48, 96, and 160 kW 400 V 100 kW 208 V Configuration

2. Select desired output relay, 1 through 4, select Configuration, and press the
enter key.

Output Relay:xof4
<relay name>
Status: Closed
→ Configuration

3. Change the settings for Name and Normal position for the selected output
relay.

Relay x Name
<output relay>
Normal: Closed

26 990-3015L-001
Maintenance 48, 96, and 160 kW 400 V 100 kW 208 V

Maintenance
Life Cycle Monitoring (LCM)
The Life Cycle Monitoring (LCM) function provides UPS preventive maintenance
advice. It is currently only supported on Symmetra PX 100 kW UPSs.
The display shows the following three messages:

Display Message Description – corrective action

Contact Schneider Electric for Secure Start-Up Start-up check is recommended. Please call the Schneider Electric
support center.

Warranty Expiring Soon The end of the contractual legal warranty. Please call the Schneider
Electric support center.

Technical Check Recommended Regular maintenance requirements and the end of service life
consumable components. Please call the Schneider Electric
support center.

In addition to these messages, the Warning LED lights up and the buzzer sounds.
These messages can be disabled by choosing Admin > Life Cycle Monitor >
Settings > Yes. This will cause the Warning LED to go out, the buzzer to stop
and remove any Life Cycle Monitoring messages.

Parts Replacement

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices for all part replacement procedures.
Failure to follow these instructions will result in death or serious injury.

Determine if you need a Replacement Part


To determine if you need a replacement part, contact Schneider Electric and
follow the procedure below so that the representative can assist you promptly:
1. In the event of an alarm condition, scroll through the alarm lists, record the
information, and provide it to the representative.
2. Write down the serial number of the unit so that you will have it easily
accessible when you contact Schneider Electric.
3. If possible, call Schneider Electric from a telephone that is within reach of the
display so that you can gather and report additional information to the
representative.
4. Be prepared to provide a detailed description of the problem. A representative
will help you solve the problem over the telephone, if possible, or will assign a
return material authorization (RMA) number to you. If a module is returned to
Schneider Electric, this RMA number must be clearly printed on the outside of
the package.
5. If the unit is within the warranty period and has been started up by Schneider
Electric, repairs or replacements will be performed free of charge. If it is not
within the warranty period, there will be a charge.

990-3015L-001 27
48, 96, and 160 kW 400 V 100 kW 208 V Maintenance

6. If the unit is covered by a Schneider Electric service contract, have the


contract available to provide information to the representative.

Return Parts to Schneider Electric


To return an inoperable part to Schneider Electric, contact Schneider Electric
customer support to obtain an RMA number.
Pack the part in the original shipping materials, and return it by insured, prepaid
carrier. The customer support representative will provide the destination address.
If you no longer have the original shipping materials, ask the representative about
obtaining a new set.
• Pack the part properly to avoid damage in transit. Never use styrofoam beads
or other loose packaging materials when shipping a part. The part may settle
in transit and become damaged.
• Enclose a letter in the package with your name, RMA number, address, a
copy of the sales receipt, description of the problem, a phone number, and a
confirmation for payment (if necessary).
NOTE: Damages sustained in transit are not covered under warranty.

Replacement Parts

DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
All safety instructions in this document must be read, understood and followed.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
Only trained personal familiar with the construction and operation of the
equipment, as well as the electrical and mechanical hazards involved, may
install and remove system components.
Failure to follow these instructions will result in death or serious injury.

NOTE: A maximum of two smart slots can be used.

Part Part number


16 kW power module for 48, 96 and 160 kW 400 V SYPM10K16H

10 kW power module for 100 kW 208V, high efficiency SYPM10KF2

Modular battery string (four battery units) SYBT9-B4

Modular battery unit SYBTU2-PLP

SmartSlot relay I/O module (option) AP9613

Modbus/Jbus interface card (option) AP9622

Network management card (option) Go to www.apc.com for a list of network management cards

Power distribution module Go to www.apc.com for a complete list of breakers

28 990-3015L-001
Troubleshooting 48, 96, and 160 kW 400 V 100 kW 208 V

Troubleshooting

DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
Only trained personal familiar with the construction and operation of the
equipment, as well as the electrical and mechanical hazards involved, may
install and remove system components.
Failure to follow these instructions will result in death or serious injury.

Status and Alarm Messages


This section lists the status and alarm messages that the UPS might display. The
messages are listed in alphabetical order, and a suggested corrective action is
listed with each alarm message to help you troubleshoot problems.
NOTE: Contact Schneider Electric Customer Support if you see alarm or
status messages that are not listed here.
NOTE: If a problem is reported, ensure that the system component in question
is correctly installed.

Display Messages
Display Message Meaning Corrective Action

Battery Alarm A battery module has become inoperable Replace battery. See or contact Schneider
and requires replacement. Electric Customer Support for replacement
of a classic battery.

Battery Charger Alarm The battery charger is not functioning Contact Schneider Electric Customer
properly. Support.

Battery High Temperature Alarm The temperature of one or more battery Ensure that the ambient temperature meets
units has exceeded system specifications. the specifications of the system. If the
ambient temperature is below 40 °C (104 °
F), then initiate a self-test to detect any
damaged battery units. Replace any
damaged battery units.

Battery High Voltage Alarm The battery voltage is too high and the Contact Schneider Electric Customer
charger has been deactivated. Support.

Battery Monitor Card Alarm The battery monitor card has become Contact Schneider Electric Customer
inoperable. Support.

Battery Monitor Card Removed The battery monitor card has been Contact Schneider Electric Customer
removed. Support.

Contact Schneider Electric For Secure The UPS has been running 5 days. Start-up Contact Schneider Electric Customer
Start-Up check by a Schneider Electric Field Service Support.
Engineer (FSE) is recommended.

Discharged Battery The UPS is online and the battery charge is No corrective action necessary. Note: If the
low. input voltage becomes unavailable, runtime
will be limited.
Extended Run Frame Alarm One of the battery cabinets has become Contact Schneider Electric Customer
inoperable. Support.

External DC Disconnect Switch Open The external DC DISCONNECT switch Close the external DC DISCONNECT
tripped. Battery power is not available or the switch. If the problem continues, call
runtime is lower than expected. Schneider ElectricCustomer Support.

External Switch Gear Communication The external switch gear communication Contact Schneider Electric Customer
Card Alarm card has become inoperable. Support.

External Switch Gear Communication The system no longer detects an external Option 1: Ensure the external switch gear
Card Removed switch gear communication card. communication card is installed properly.

990-3015L-001 29
48, 96, and 160 kW 400 V 100 kW 208 V Troubleshooting

Display Message Meaning Corrective Action

Option 2: Contact Schneider Electric


Customer Support.

Graceful Shutdown Initiated A graceful shutdown or reboot has been No corrective action necessary.
initiated from the display interface or other
accessory.

In Bypass: Hardware Not Fully The system has transferred into bypass Contact Schneider Electric Customer
Functional because an event has occurred. Support.

In Bypass: Overload The system has transferred into bypass Option 1: Decrease the load.
because the load has exceeded the power Option 2: Add a power module to the
capacity of the system. system.

In Bypass: User-Initiated The system has been transferred into Check for any abnormalities with the
bypass due to user action. system.

Transfer the system to normal operation.

Internal Communication Bus Alarm One of the buses used for communication Contact Schneider Electric Customer
between the UPS modules has become Support.
inoperable.

Input Voltage or Frequency Cannot The frequency or voltage is out of Correct the input voltage to provide
Support Bypass acceptable range for bypass. This message acceptable voltage or frequency.
occurs when the UPS is online, and
indicates that bypass mode may not be
available if required.

Inverter Not Synchronized To AC Input System cannot synchronize to AC line and Option 1: Decrease the sensitivity to input
bypass mode may not be available. frequency.

Option 2: Correct the input voltage to


provide acceptable voltage/frequency.

Load (kVA) Alarm The load has exceeded the user specified Option 1: Use the display interface to raise
load alarm threshold. the alarm threshold.

Option 2: Reduce the load.

Local Management-To-UPS Internal communications in the system is no Contact Schneider Electric Customer
Communication Lost longer available. Support.

Loss Of Battery Capacity (Lower Than The battery capacity is estimated to be Replace battery. See or contact Schneider
50%) below 50% of the expected. Electric Customer Support for replacement
of a classic battery.

Loss Of Battery Capacity (Lower Than The battery capacity is estimated to be Replace battery. See or contact Schneider
75%) below 75% of the expected. Electric Customer Support for replacement
of a classic battery.

Low Battery The UPS is in battery operation and the Runtime is limited. Shut down the system
battery charge is low. and the load equipment or restore the input
voltage.

Main Intelligence Module Alarm The main intelligence module has become Contact Schneider Electric Customer
inoperable and requires replacement. Support.

No Batteries Detected No battery power is available. Option 1: Ensure the batteries are installed
properly.

Option 2: Check to see whether the DC


Breaker has been tripped.

Option 3: Contact Schneider Electric


Customer Support.

No Power Modules Detected No power modules are available. Option 1: Ensure that the power modules
are properly installed, the two fastening
screws are tight, and the enable switch is
engaged.

Option 2: Check for other communication


alarm messages in the log.

Overload On UPS The load has exceeded the system power Option 1: Decrease the load.
capacity.
Option 2: Add a power module to the
system.

Power Module Alarm A power module has become inoperable Replace power module. See
and requires replacement. .

30 990-3015L-001
Troubleshooting 48, 96, and 160 kW 400 V 100 kW 208 V

Display Message Meaning Corrective Action

Power Outage The input voltage is not acceptable for Contact Schneider Electric Customer
normal operation. Support.

Redundancy Alarm Actual power module redundancy has fallen Option 1: If possible, install additional
below user-specified redundancy alarm power modules. See
threshold. At least one power module has .
become inoperable, or the load has
increased. Option 2: Replace inoperable modules. See
.

Option 3: Reduce the load.

Option 4: Change alarm limit.

Redundancy Lost The UPS no longer detects redundant Option 1: If possible, install additional
power modules. One or more power power modules. See
modules have become inoperable, or the .
load has increased.
Option 2: Replace inoperable modules. See
.

Option 3: Reduce the load.

Option 4: Change alarm limit.

Redundant Intelligence Module Alarm The redundant intelligence module has Contact Schneider Electric Customer
become inoperable and requires Support.
replacement.

Redundant Intelligence Module in The main intelligence module has become Contact Schneider Electric Customer
Control inoperable, and the redundant intelligence Support.
module is functioning as the primary
intelligence module.

Replacement Battery Needed One or more battery packs have been Replace battery unit(s). See
detected to be inoperable (caused by
symmetry event, fuse blown, over- or contact Schneider Electric Customer
temperature event, or wrong battery type). Support for replacement of a classic battery.
The UPS display will point out the position
of the batteries you have to replace.

Runtime Alarm The predicted runtime is lower than the Option 1: Install additional battery modules.
user-specified minimum runtime alarm
threshold. At least one battery module has Option 2: Replace the inoperable battery
become inoperable or the load has modules.
increased.
See

or contact Schneider Electric Customer


Support for replacement of a classic battery.

Option 3: Reduce the load.

Option 4: Change alarm limit.

Site Wiring Incorrect There is a problem with the phase rotation Contact the certified electrician that installed
or a phase is missing in the input voltage to the system.
the UPS, or the neutral is missing.

Static Bypass Switch Module Not Fully The static bypass switch module has Contact Schneider Electric Customer
Functional become inoperable and requires Support.
replacement.

Static Bypass Switch Module Removed The system no longer detects a static Option 1: Ensure that the static bypass
bypass switch module. switch module is installed properly.

Option 2: Call Schneider Electric Customer


Support for replacement of the static bypass
switch module.
System in Maintenance Bypass The system is in maintenance bypass: the No corrective action necessary.
Q2 breaker is open and the Q3 breaker is
closed.
System Power Supply Card Alarm The system power supply card has become Ensure that the power supply card is
inoperable and requires replacement. installed properly. See
.
System Start-Up Configuration Incorrect The system configuration download did not Check for other alarms and contact
succeed. Unable to determine the system Schneider Electric Customer Support.
voltage or frame size.

990-3015L-001 31
48, 96, and 160 kW 400 V 100 kW 208 V Troubleshooting

Display Message Meaning Corrective Action

Technical Check Recommended Regular maintenance requirements and the Contact Schneider Electric Customer
end of service life consumable components. Support.

Warranty Expiring Soon The end of the contractual legal warranty. Contact Schneider Electric Customer
Support.

Modular Distribution Alarm List


The display interface will identify the number of the power distribution modules
that has caused an alarm or warning.

Display Message Meaning Corrective Action

High Module Current Alarm The threshold of the high module current Evaluate the threshold setting. If necessary,
has been exceeded. adjust it for your situation.

High Subfeed Current Alarm The threshold of the high subfeed current Evaluate the threshold setting. If necessary,
has been exceeded. adjust it for your situation.

Low Module Current Alarm The threshold of the low module current has Evaluate the threshold setting. If necessary,
been exceeded. adjust it for your situation.

Low Subfeed Current Alarm The threshold of the low subfeed current Evaluate the threshold setting. If necessary,
has been exceeded. adjust it for your situation.

Max Module Current Alarm The threshold of the maximum module Evaluate the threshold setting. If necessary,
current has been exceeded. adjust it for your situation.

Max Subfeed Current Alarm The threshold of the maximum subfeed Evaluate the threshold setting. If necessary,
current has been exceeded. adjust it for your situation.

Min Module Current Alarm The threshold of the minimum module Evaluate the threshold setting. If necessary,
current has been exceeded. adjust it for your situation.

Min Subfeed Current Alarm The threshold of the minimum subfeed Evaluate the threshold setting. If necessary,
current has been exceeded. adjust it for your situation.

Communication Lost With Metering Communication has been lost with the Check the communication cables to ensure
Board Alarm power distribution module. that they are properly connected. Contact
Schneider Electric Customer Support (see
the back cover).

Module Breaker Open Alarm A modular circuit breaker is open. Check the modular circuit breakers to see if
one has been over-loaded. Replace if
necessary.

Subfeed Breaker Open Alarm A subfeed circuit breaker is open. Check the subfeed circuit breakers to see if
one has been over-loaded.

32 990-3015L-001
Troubleshooting 48, 96, and 160 kW 400 V 100 kW 208 V

PDU Alarm List


Display Message Meaning Corrective Action

System In Maintenance Bypass The system is in maintenance bypass: the No corrective action necessary.
Q2 switch is open and the Q3 switch is
closed.
Min Output Voltage Alarm Phase-to-neutral output voltage for phase Evaluate the threshold setting. If necessary,
<L-N> has dropped below the configured adjust it for your situation.
limit.
Max Output Voltage Alarm Phase-to-neutral output voltage for phase Evaluate the threshold setting. If necessary,
<L-N> exceeded the configured limit. adjust it for your situation.

Max Total Output Current Alarm Current of output phase <n> exceeded the Evaluate the threshold setting. If necessary,
configured limit. adjust it for your situation.

Min Total Output Current Alarm Current of output phase <n> dropped below Evaluate the threshold setting. If necessary,
the configured limit. adjust it for your situation.

Output Frequency Alarm Frequency of the output current is above or Evaluate the threshold setting. If necessary,
below the range that is configured as adjust it for your situation.
acceptable.

Critical Input Contact Fault A user-configured contact connected to the Determine why the alarm has occurred. This
system is reporting an alarm condition. is a user-specific alarm setting.

System Mode Alarm1 The Q1 switch is open, and the UPS is Close the Q1 switch to reconnect the UPS
disconnected from the input voltage. to utility/mains power.

System Mode Alarm1 The Q2 & Q3 switches are open, and the For safety reasons, ensure that the switches
system is not supporting the connected were not closed for maintenance purposes.
equipment. If the switches are open, close Q2 for UPS
operation, and Q3 for maintenance bypass.

System Mode Alarm1 The alarm will be active in the event Q3 is Option 1: Resume normal UPS operation.
on at the same time as Q1 and Q5.
Option 2: Go to maintenance bypass.

Option 3: Contact Schneider Electric


Customer Support.

Transformer Overheating The temperature of the transformer has Option 1: Resume normal UPS operation.
exceeded 180 °C.
Option 2: Go to maintenance bypass.

Option 3: Contact Schneider Electric


Customer Support.

Cooling Fan Outage Alarm One fan is not working or not spinning fast Option 1: Make sure all four fans are
enough, or one pole of the 3-pole circuit running.
breaker has tripped.
Option 2: Check breaker positions.

Option 3: Contact Schneider Electric


Customer Support.

1. See the event log for further clarification.

990-3015L-001 33
Printed in:
Schneider Electric

Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00

*990-3015L-001*

As standards, specifications, and design change from time to time,


please ask for confirmation of the information given in this publication.

© 2013 – 2023 Schneider Electric. All rights reserved.


990-3015L-001

You might also like