Safety Relay H-462
General Connections
• 4 or 6 contacts • Soldering pins for PCB, pre-soldered with Sn100
• Forced guided contact set Drive
• According to EN 50205, application type A • Direct current or AC-current
• Ambient temperature – 25 … + 80 °C • Current controlled or bistable upon request
• Soldering heat resistance 260 °C/5s Approvals
• RoHS compliance • cULus • TÜV
• Signal relay according to UIC 736e
Standards
• EN 50205 • IEC 61810-1 • UL 508
Technical Data Dimensions L x W x H (in mm) Size 1: 57,8 x 20,5 x 48,6
Size 2: 67,4 x 20,5 x 48,6
mechanical
Shock resistance NO-contact/NC-contact 10/10 g, 16 ms Half sinus
Vibration resistance NO-contact/NC-contact 10/10 g, 10 – 55 Hz
Operating time NC-contact, contact opens typical 17 ms
Operating time NO-contact, contact closes typical 23 ms
Releasing time NO-contact, contact opens typical 5 ms
Releasing time NC-contact, contact closes typical 7 ms
Mechanical service life (without load) >10 7 cycles
Weight Size 1: 90 g
Size 2: 115 g
Technical Data Max. switching capacity AC 2.000 VA, DC *W
Max. switching voltage AC 230/240 V, DC *V
electrical Max. switching current 10 A
Constant current Ith2 10 A for deliveries from 2008 on:
Constant current Ith2 at the same time over 2 contacts 10,0 A 10.0 A
Constant current Ith2 at the same time over 3 contacts 8,4 A 10.0 A
Constant current Ith2 at the same time over 4 contacts 7,3 A 10.0 A
Switching capacity AC-15 230/240 V Ie = 4 A
DC-13 24 V Ie = 2 A
Electrical service life (with nominal load) >10 5 cycles
Short-circuit capacity 1.000 A/AC 230 V 10 A gL/gG-fuse
* see DC-switching capacity
Insulation Over voltage category (Ü) III B-I = Basic insulation
Degree of pollution (V) 2 V-I = Reinforced (double) insulation
Insulating material group II
Insulation Nominal voltage network system Air-/ Test voltage
between AC 120/240 V AC 230/400 V creeping distance 50Hz/60 s
Contact – Contact V-l B-l > 3 mm AC 2.500 V
Contactset – Drive V-l B-I > 3 mm AC 2.500 V
Dimensions H-462 Size 1 (4 contacts) H-462 Size 2 (6 contacts)
16 Relay catalogue
Safety Relay H-462
Type key Housing Connections Special version Version
0 dustproof (RT II) 3 Soldering pins 4 Standard 00 Standard
for PCB and 3 2 screw caps M3 01 Special version
sockets 5 Code drill at yoke right side
6 Code drill at yoke left side
H O Z - 0 3 4 6 2 / 1 4 - 0 0 1 3 1 6 - 3 1 0 / 0 8 1 . 0 0
Drive NO-contact
0 DC neutral, monostable* Size Coils Contactset-number
3 AC with Diode circuit 1 4 contacts See coil table See contactset table
NC-contact
5 neutral, bistable 2 6 contacts
CO-contact
* Preferred version
Number of contacts AgCdO AgCdO AgCdO AgSnO2 AgSnO2 Contact
Contactset table N O / N C / C O - contacts + 0,2 µm Au + 5 µm Au + 10 µm Au + 0,2 µm Au + 5 µm A material
220 080 082 061 088 092 Contactset
310 079 081 059 087 091 number
330 077 084 057 058 101
420 078 083 055 086 089
All values at ambient temperature Tu = 20 °C
Coil-No. Resistance Resistance- U1/V U2/V U3/V Urück/V Printing
DC-Coil table
R/Ω tolerance± Unom/V
Number of contacts 1228 33 5% 3,4 11,6 11 0,8 6
310 1323 110 6% 6,2 21,2 19 1,4 12
220 1316 480 8% 13,9 43,9 42 3,0 24
1312 1.700 7% 27,3 82,9 83 5,9 48
1311 2.700 7% 34,4 104,4 104 7,4 60
1306 10.000 9% 69,8 199,7 205 14,7 110
1303 40.000 12% 139,8 395,0 394 28,2 220
All values at ambient temperature Tu = 20 °C
Coil-No. Resistance Resistance- U1/V U2/V U3/V Urück/V Printing
R/Ω tolerance ± Unom/V
Number of contacts 1228 33 5% 3,7 11,6 11 0,8 6
420 1323 110 6% 6,9 21,2 19 1,4 12
1316 480 8% 15,5 43,9 42 3,0 24
1312 1.700 7% 30,3 82,9 83 5,9 48
1311 2.700 7% 38,2 104,4 104 7,4 60
1306 10.000 9% 77,8 199,7 205 14,7 110
1303 40.000 12% 155,7 395,0 394 28,2 220
U 1: Minimum operating voltage with consideration of coil self heating
U 2: Thermal restricted maximum coil voltage
U 3: Maximum admissible coil voltage to realize a contact gap of > 0.5 mm also at a contact fault
U rück: Releasing voltage
Further coils are possible and available
Relay catalogue 17
Safety Relay H-462
All values at ambient temperature Tu = 20 °C
Coil-No. Resistance Resistance- U1/V U2/V U3/V Urück/V Printing
DC-Coil table
R/Ω tolerance± Unom/V
Number of contacts 1228 33 5% 4,1 11,6 11 0,8 6
330 1323 110 6% 7,6 21,2 19 1,4 12
1316 480 8% 17,1 43,9 42 3,0 24
1312 1.700 7% 33,5 82,9 83 5,9 48
1268 2.650 7% 39,5 103,5 98 7,0 60
1306 10.000 9% 86,0 199,7 205 14,7 110
1303 40.000 12% 172,2 395,0 394 28,2 220
U 1: Minimum operating voltage with consideration of coil self heating
U 2: Thermal restricted maximum coil voltage
U 3: Maximum admissible coil voltage to realize a contact gap of > 0.5 mm also at a contact fault
U rück: Releasing voltage
Further coils are possible and available
All values at ambient temperature Tu = 20 °C
Coil-No. Resistance Resistance- Umin/V Umax/V Printing
AC-Coil table
R/Ω tolerance ± Unom/V
Number of contacts 1128 30 10% 9,6 13,2 12
220 1323 110 10% 19,2 26,4 24
310 1316 480 10% 38,4 52,8 48
330 1514 750 10% 48,0 66,0 60
420 1311 7.200 15% 88,0 121,0 110/115
1306 10.000 15% 176,0 242,0 220/230
Further coils are possible and available
Printing U1/V U2/V U3/V Urück/V
Running types Article-No. Type key
Unom
462-1026 HOZ-03462/14-001316-220/080.00 DC 24 V 13,9 43,9 42 3,0
462-1027 HOZ-03462/14-001316-310/079.00 DC 24 V 13,9 43,9 42 3,0
462-1045 HOZ-03462/24-001316-330/077.00 DC 24 V 17,1 43,9 42 3,0
462-1140 HOZ-03462/14-001323-310/079.00 DC 12 V 6,2 21,2 19 1,4
462-1210 HOZ-03462/24-001316-420/078.00 DC 24 V 15,5 43,9 42 3,0
462-1312 HOZ-03462/24-001316-330/084.00 DC 24 V 17,1 43,9 42 3,0
462-1320 HOZ-03462/14-001316-310/081.00 DC 24 V 13,9 43,9 42 3,0
462-1326 HOZ-03462/14-001323-220/082.00 DC 12 V 6,2 21,2 19 1,4
462-1328 HOZ-03462/14-001312-220/082.00 DC 48 V 27,3 82,9 83 5,9
462-1333 HOZ-03462/24-001323-420/083.00 DC 12 V 6,9 21,2 19 1,4
462-1334 HOZ-03462/24-001316-420/083.00 DC 24 V 15,5 43,9 42 3,0
462-1342 HOZ-03462/24-001312-330/084.00 DC 48 V 33,5 82,9 83 5,9
18 Relay catalogue
Safety Relay H-462
Connection grid 2 NO / 2 NC (220) 3 NO / 1 NC (310)
Few on soldering side
Size 1
Inactive area
3 NO / 3 NC (330) 4 NO / 2 NC (420)
Size 2
Inactive area
Diagram
Contactgap:
current (A)
Arc duration
current (A)
. ,1
0 Switching voltage 0 switching cycles
DC-switching capacity Electrical service life
Relay catalogue 19
Safety Relays H-462
Accessories Socket Removal tool
H-462/1
(4 contacts)
Article-No.: 462-8005
Sockets for PCB mounting Sockets for conventional wiring
Article-No.: 462-8003 Article-No.: 462-8001
Socket Removal tool
H-462/2
(6 contacts)
Article-No.: 462-8005
20 Relay catalogue
Safety Relay H-462
Accessories Sockets for PCB mounting Sockets for conventional wiring
H-462/2
(6 contacts)
Article-No.: 462-8004 Article-No.: 462-8002
Base plate for dust protection
and insulation strength: 2,5 kV
Article-No.: 462-8009
Relay catalogue 21