0% found this document useful (0 votes)
37 views58 pages

AB DO User Manual en 05

The Saitel DR AB_DO User Manual provides detailed instructions for the assembly, wiring, configuration, and maintenance of the AB_DO module, emphasizing safety and compliance with ISO 9001:2015 standards. It includes a change control section, technical specifications, and safety guidelines to ensure proper handling and installation by qualified personnel. The manual also outlines necessary precautions for working with electrical equipment and provides references to related documentation.

Uploaded by

harpatara71
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views58 pages

AB DO User Manual en 05

The Saitel DR AB_DO User Manual provides detailed instructions for the assembly, wiring, configuration, and maintenance of the AB_DO module, emphasizing safety and compliance with ISO 9001:2015 standards. It includes a change control section, technical specifications, and safety guidelines to ensure proper handling and installation by qualified personnel. The manual also outlines necessary precautions for working with electrical equipment and provides references to related documentation.

Uploaded by

harpatara71
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 58

Saitel DR

Part of EasyLogic

M554A0000y / AB_DO

User Manual
This manual provides information for the assembly, wiring, configuration and
maintenance of the AB_DO module.

SE-M554-USR

Publication Date (04/2024)


Read carefully the information contained in this manual before assembly, installation and use of the

www.se.com

Internal
19/04/2024 User Manual – AB_DO

Change Control
Rev Date Description
01 05/12/2019 Initial edition
02 22/05/2020 Configuring double digital output.
03 23/02/2021 Sections update
04 01/11/2023 Technical Specification table section updated with the reference to
railways certification (EN 51121-5)
05 19/04/2024 Introduced EasyLogic range branding

General Information
The Saitel platform and all its components have been developed in accordance to the requirements
for a quality management system, complying with the ISO 9001:2015 Norm.

Document nº: SE- USR-M554


Revision/Date: 05 / 19/04/2024
File: AB_DO – User Manual_EN_05.pdf
Retention period: Permanent throughout its validation period + 3 years after its
cancellation.

Reference Documents
User Manual Document Code

Easergy Builder User Manual FTE-S856-MSS


HUe user manual SE-M588-USR
HU_A user manual SE-M551-USR

HU_AF user manual SE-M503-USR


Saitel DR Platform user manual FTE-F800-MSS
webAPP user manual FTE-S856-WPP
webTool user manual FTE-S856-MSW

Software Version in this Manual


The information in this manual is valid for the software versions listed below. This information is
also valid for later versions, although some parameters may change slightly:

RTU Software Easergy Builder (Plugin)


Module
Module Version Plugin Version

Baseline HUe 11.06.27


Easergy Builder Tool 1.7.30
AB_DO software AB_DO.bin 01.07.10

R&D Digital Seville


Pag 2
User Manual – AB_DO 19/04/2024

Content
1 SAFETY & HEALTH ................................................................................................4

2 GENERAL DESCRIPTION OF AB_DO..................................................................15

3 PHYSICAL MOUNTING & INSTALLING ...............................................................21

4 CONFIGURATION & MAINTENANCE ...................................................................29

5 TECHNICAL SPECIFICATIONS TABLE ...............................................................49

R&D Digital Seville


Pag 3
19/04/2024 User Manual – AB_DO

1 Safety & Health

R&D Digital Seville


Pag 4
User Manual – AB_DO 19/04/2024

Content

1 SAFETY & HEALTH ................................................................................................4

1.1 INTRODUCTION .......................................................................................................6


1.1.1 INFORMATION OF SECURITY .............................................................................6
1.1.2 PRESENTATION ...............................................................................................6
1.2 INTRODUCTION TO SAFETY .....................................................................................7
1.3 SYMBOLS AND LABELS ON THE EQUIPMENT.............................................................8
1.4 INSTALLATION, SETUP AND OPERATION...................................................................8
1.5 EARTHING ............................................................................................................10
1.5.1 ELECTRICAL SAFETY .....................................................................................10
1.5.2 FUNCTIONAL EARTH (EMC) ...........................................................................11
1.6 HANDLING ELECTRONIC COMPONENTS..................................................................12
1.7 TECHNICAL SPECIFICATIONS FOR SAFETY .............................................................12
1.7.1 PROTECTIVE ELEMENTS ................................................................................12
1.7.2 ENVIRONMENTAL CONDITIONS .......................................................................12
1.7.3 STORAGE CONDITIONS ..................................................................................13
1.8 TECHNICAL LABEL ...............................................................................................13
1.9 PACKING AND UNPACKING ....................................................................................14
1.10 DECOMMISSIONING AND DISPOSAL........................................................................14

R&D Digital Seville


Pag 5
19/04/2024 User Manual – AB_DO

1.1 Introduction

1.1.1 Information of Security


Important information
Read these instructions carefully and look at the equipment to become familiar with the device
before trying to install, operate, service or maintain it. In this manual you can find different types of
messages associated with situations that have different level of risk for people and / or for the
equipment.

This symbol indicates "DANGER" or "WARNING". This symbol informs of an


electrical risk that will cause personal injuries if the instructions are not followed.

This symbol is associated to a safety alert. It is used to warn of possible personal


injury hazards. The user must follow all instructions or messages associated to this
symbol to avoid possible injuries.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious
injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or
serious injury.

NOTICE
NOTICE is used to address practices not related to physical injury. The safety alert symbol shall
not be used with this signal word.

To Keep in Mind
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
A qualified person is who fulfill with requirements in paragraph 1.2

1.1.2 Presentation
This manual provides information for a safe handling, commissioning and testing. This Safety
chapter also includes descriptions of the labels on the equipment.
Documentation for equipment ordered from Schneider Electric is dispatched separately from
manufactured goods and may not be received at the same time. Therefore, this guide is provided in
order to do that printed information which may be present on the equipment is fully understood by
the recipient.
The technical data in this safety guide is typical only, see the technical data section of the user
manual for specific details of a particular equipment.

R&D Digital Seville


Pag 6
User Manual – AB_DO 19/04/2024

Before carrying out any work on the equipment the user should be familiar with the
contents of this Safety chapter and the ratings on the equipment’s rating label.
THE SAFETY SECTION MUST BE READ BEFORE STARTING ANY WORK ON
THE EQUIPMENT.

1.2 Introduction to Safety

The information in this section is intended to get that equipment is properly installed and handled in
order to maintain it in safety conditions. It is assumed that everyone who will be associated with the
equipment will be familiar with the contents of that Safety section.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of the
equipment. Failure to observe warning notices, an incorrect or improper use may endanger
personnel and equipment and also cause personal injury or physical damage.

WARNING
Before working with the terminal of connection, the device must be turned off and disconnected
of the feeding.

Proper and safe operation of the equipment depends on appropriate shipping and handling, proper
storage, installation and commissioning, and on careful operation, maintenance and servicing. For
this reason only qualified personnel may work on or operate the equipment.
Qualified personnel are individuals who:
• Have read and understood the information on the device and its user manual.
• Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected.
• Are able to safely perform switching operations in accordance with accepted safety engineering
practices and are authorized to energize and de-energize equipment and to isolate, ground,
and label it.
• Are trained in the care and use of safety apparatus in accordance with safety engineering
practices.
• Are trained in emergency procedures (first aid).
It is necessary to consider that the documentation of the device collects the instructions for its
installation, set up and operation. However, the manuals could not cover all the possible
circumstances neither include specific information on all the details.
In case of questions or specific problems, contact with his office of sales Schneider Electric or with
the center of attention to the customer and request the necessary information.

R&D Digital Seville


Pag 7
19/04/2024 User Manual – AB_DO

1.3 Symbols and Labels on the Equipment

Before the equipment is installed or commissioned, the user must understand the following
symbols, which may be used on the equipment or referred to in the user documentation:
Table 1 – Symbols

Symbol Associated Text Description

IEC symbol associated to a DANGER or


Possibility of electric WARNING message indicating that there is an
chock electrical risk. Failure to follow these instructions
could cause damage to people or death.

Symbol associated with a risk alert. The user


Caution, read the
must read the manual before handling the
manual.
equipment.

ANSY symbol associated to a DANGER or


Possibility of electric WARNING message indicating that there is an
chock electrical risk. Failure to follow these instructions
could cause damage to people or death.

Protective earth Associated symbol to the protective ground


connection connection. See paragraph in this manual.

Associated symbol to the functional ground


Functional earth
connection. See paragraph 1.5.2 Error!
connection
Reference source not found.in this manual.

This symbol indicates that the equipment has


CE Mark been developed in compliance with all
applicable European Directives.

Electronic device. This symbol indicates that, at the end of its life,
Special instructions this module must be discarded according to the
must be follow for WEEE Directive (Waste Electrical and Electronic
discard it. Equipment).

The equipment has been designed and


Compliant with
manufactured according to RoHS Directive
RoHS.
(Restriction of Hazardous Substances).

Direct Voltage Symbol of direct voltage (VDC).

Alternate Voltage Symbol of alternate voltage (VAC).

1.4 Installation, Setup and Operation

There are several acquisition blocks in Saitel DR that use dangerous tensions (> 50 V). The user is
responsible to check that the characteristics of each device are adapted and convenient for his
installation. The user should read the instructions of installation before proceeding to the use or
maintenance of the devices. Not following these instructions can be dangerous for the people and
the devices.
Not following these instructions can be dangerous for the people and the devices.

R&D Digital Seville


Pag 8
User Manual – AB_DO 19/04/2024

DANGER
Devices that handle dangerous tensions are marked with a sticker on the front label (size: 12,5
mm). This label must be visible all the time while the module is installed on the DIN rail

The following products handle dangerous tensions:

• HU120: High-performance CPU with acquisition (P/N M590xx000x).

• HU_AF: Advanced head unit with acquisition (P/N M503xx3x0x and P/N M503xx4x0x). For
other part numbers, depending on the voltage handled by the equipment connected to the
digital outputs (voltage > 50 V), this module must be marked with an electric risk label. It will
not be marked on factory.

• AB_DI: Digital inputs module (P/N: M55520000x, M55530000x and M55540000x).

• AB_DIDO: Input and output digital module (P/N M5722x000x, M5723x000x and M5724x000x).
For other part numbers, depending on the voltage handled by the equipment connected to the
digital outputs (voltage > 50 V), this module must be marked with a electric risk label. It will not
be marked on factory.

• AB_AC: Direct measurements module (P/N M562x0000x).

• AB_DO: This module does not handle high voltages, it will not be marked at the factory. This
module must be marked to inform about the risk when some equipment that manage voltage
higher than 50 V are connected to digital outputs.
It is recommended to install the RTU inside a cabinet with a key. This cabinet only should be
opened by a qualified person.

WARNING
If this type of cabinet isn't available, a barrier must be installed in order to avoid an accidental
contact with these dangerous elements. This barrier only should can be removed using a
special tool.

If the barrier has to be removed in order to access to equipment, personnel responsible for the
task must be sure that the barrier is installed again when the task is finished.

While the RTU is accessible for a user, all people must follow all instructions to prevent
electrical risk or discharges.

Not following these instructions can give like result that the device do not work properly
or even can damage to the people or devices.

An electrical risk symbol with enough size must be included on the cabinet’s door or
on the barrier.

The following image shows an example:


Figure 1 - Barrier of protection for elements with dangerous voltages.

R&D Digital Seville


Pag 9
19/04/2024 User Manual – AB_DO

NOTICE
Terminals will not be accessible to the user directly once it has made the installation of the
device. The cabinet will have to remain closed with key or the screen of installed protection.

The cabinet or installation must have a general switch placed just in the cable entry of the
installation (see paragraph 1.7.1 )
For the cleaning of the device it is only necessary using a dry cloth by the surface when it detects
excessive presence of dust or any element deposited on the surface.
WARNING
Don’t use liquid products of cleanliness due to the presence of active parts.

Because of the variety of uses of the product, the managers of the application and use of this
device of control will have to take the measures to ensure the fulfillment of all the requests of
security and provision of each application. The requests do reference to the applicable laws,
regulations, codes and standard.

1.5 Earthing

WARNING
Before energizer the device, it has to be placed to earth properly such as it indicates in sections
1.5.1 and 1.5.2.

When installing the device, ground is the first thing that should be connected and the last one
that should be disconnected.

Saitel can need put to earth for two distinct needs:


• For purposes of electrical safety (Protective Earth, PE).
• Improve the behavior in EMC and derive perturbations to earth (functional Earth).

1.5.1 Electrical Safety


Only qualified personnel, with knowledge about hazards associate with electrical equipment is
allowed to install Saitel DR. In general, the installation will be following IEC 61010-1
recommendations in order to be compliant with this norm.

The DIN rail must be installed on a metallic surface. This metallic surface must have
available an M4 screw marked with this symbol. The ground of the cabinet or
installation must be connected to this screw, according to the norm IEC 61010-1.

Saitel DR modules have a metallic enclosure offering protection for isolation faults. Earthing is
done by the metal rail fixing clip.

R&D Digital Seville


Pag 10
User Manual – AB_DO 19/04/2024

WARNING
All devices with high voltage must be disconnected before dismount a module from the DIN rail.

A dedicated connection with green/yellow wire should be used to assure electric continuity to the
installation protective earth. Section of these wires must be enough in order to support 25 A
(ground bonding test).

Figure 2 - Yellow and Green cable for earthing.

The design and installation of the cabinet is responsible for compliance with all the existing
international and national electrical codes concerning protective grounding of any device.
WARNING
According to Electrical Safety:

• The screw for ground must be exclusive for this use.


• The power voltage must be supplied by a power supply that offers double or reinforced
insulation against high voltages (higher than 50 V).

1.5.2 Functional Earth (EMC)


In this case the main rule is that the connection has to do with wires of the lower possible length to
the screen or connection of put to earth nearer. In this case the section of the driver is not notable,
is more, it advises that the use of flat wires or flexible conductive bands for a good behavior EMC.
NOTICE
The DIN rail must have terminals of earthing (of yellow and green colour) necessary to connect
the terminals of PE (if it is present).

Figure 3 - Terminal for functional earth (EMC).

All Saitel DR modules with power or polarization input connectors have an exclusive terminal for
earthing EMC. These modules are HUe, HU_B, HU_A, HU_AF, XU, AB_DO, AB_DIDO and
AB_SER with external polarization.
R&D Digital Seville
Pag 11
19/04/2024 User Manual – AB_DO

Figure 4 - Example of earthing for EMC.

1.6 Handling Electronic Components

Saitel is susceptible to receive electrostatic discharges during the handling. It is necessary to take
the usual measures to minimize this risk, since serious damage to the equipment can be caused,
which may not be detected immediately but which may affect the reliability of the product.
WARNING
The enclosure ONLY should be removed when is strictly necessary, because this action has a
risk for the equipment:

• Before removing the enclosure, the operator must be equipotential with the equipment.

• Avoid touching the electronic. The board must be always manipulated for the edges.

• If the equipment has to be passed between two persons, both must be equipotential.

• Put the module always on an antistatic surface or on a surface equipotential with you.

• During the storage and transport, the module will remain in the packaging.

Not following these instructions can give like result that the device do not work properly
or even can damage to the people or devices.

1.7 Technical Specifications for Safety

1.7.1 Protective Elements


The cabinet's engineering and installation must include a general automatic switch next to the
cables' input in the cabinet; once the door is opened, high voltages must be interrupted inside. This
switch must be located at a place which is not accessible by a third person while the operator is
using the boards in the cabinet.
Moreover, the installation will incorporate a circuit breaker of 5A next to the cabinet protecting it
from possible overcurrent in the power supply.
Both switches will be labeled with the symbol O as "Off" and I as “On”.
WARNING
The connection / disconnection switch must be installed in a fixed element (for example the wall
of the cabinet) and it mustn’t break any earthing wire.

1.7.2 Environmental Conditions


The protection degree of the device is IP20.

WARNING
R&D Digital Seville
Pag 12
User Manual – AB_DO 19/04/2024

This equipment has been designed ONLY for indoor use.

If it is necessary for his use in some external surroundings, it has to mount in a cabinet or specific
accommodation that contributes a degree of protection IP54, protected against the dust and water.
The electronic cards of the modules will be able to be tropicalized or no according to the option of
setting chosen. The tropicalized used is the AVR80, of the company ABchimie. It can consult all the
technical information of this type of finishing in http://www.abchimie.com/.
Other data to take into account about the environmental are:

• Altitude until 2000 m.

• Operation temperature range: Between -40 ºC and 70 ºC. (IEC 60068-2-1 and IEC 60068-2-2).

WARNING
According to the standard 60950-1, all electrical safety tests have been done in an
environmental temperature range of -40 ºC to 60 ºC. For higher temperature (> 60 ºC), the
module must be handled with care, since the metal surface could reach a dangerous
temperature for the user.

• Maximum relative humidity of 95%. (IEC 60068-2-30)

• Degree of pollution II. (IEC 60255-5)

• Overvoltage transitory until levels of Category III. (IEC 60255-5)

1.7.3 Storage Conditions


The continuous exhibition to some high levels of humidity during the storage can cause damages
to the electronic components and reduce the useful life of the device.
We recommend that, in the enclosure of storage, the relative humidity do not exceed 50%.
Before the installation of an electrical equipment, it is recommended to leave the necessary time for
the acclimatization of the environmental temperature.

1.8 Technical Label


Each Saitel product includes a technical label with the following information:
Figure 5 - Technical label.

NOTICE

R&D Digital Seville


Pag 13
19/04/2024 User Manual – AB_DO

On the “Technical data” zone, you can see relevant information about the input and output
voltage in the module. Any voltage greater than 50 V must be consider as a high voltage.

1.9 Packing and Unpacking


All Saitel modules are packaged separately in their own carton box and shipped inside outer
packaging. Use special care when unpacking the device. Don’t use force.
The design revision and manufacturing options can be determined using the P/N included in the
packaging label on packaging.
After unpacking the device, inspect it visually to be sure it is in proper mechanical condition.
If the product needs to be shipped, the original packaging must be used, including foams and the
carton box. If the original packaging is no longer available, make sure that the packaging used is
according to ISO 2248 specifications for a drop height 1 m.

1.10 Decommissioning and Disposal


When the product is marked with this symbol, it means that, at the end of its life
cycle, you mustn't dispose the product together with habitual residues. To avoid
possible damage to the environment or to the human health that represents the
uncontrolled elimination of residues, please, separate the battery (if there is one) of
the other elements, and each one must be recycled according to the local regulation.

R&D Digital Seville


Pag 14
User Manual – AB_DO 19/04/2024

2 General Description

R&D Digital Seville


Pag 15
19/04/2024 User Manual – AB_DO

Content

2 GENERAL DESCRIPTION OF AB_DO..................................................................15

2.1 SAITEL DR PLATFORM .........................................................................................17


2.2 AB_DO FEATURES ..............................................................................................17
2.3 INTERFACES.........................................................................................................19
2.4 HARDWARE ARCHITECTURE.................................. ERROR! BOOKMARK NOT DEFINED.

R&D Digital Seville


Pag 16
User Manual – AB_DO 19/04/2024

2.1 Saitel DR Platform

Saitel DR – part of the EasyLogic range - is a hardware platform by Schneider Electric specifically
designed for real-time control and energy automation applications. Saitel DR is a high-technology
embedded platform which serves Schneider Electric’s business areas.
On this hardware platform, the Baseline Software Platform is installed. This software is used in
Saitel families (Saitel DP and Saitel DR) and other Schneider Electric products.
Other features identifying Saitel DR are:

• A DIN rail is used for the mechanical installation.

• The communication between the control units integrated in a distributed system is mainly
established by Ethernet.

• The terminal blocks for field-connection are completely built into acquisition blocks.
Figure 6 – Saitel DR

Saitel DR’s design has been optimized to meet the most demanding requirements of multiple
sectors:

• Safety and reliability requirements for power, gas and water supply, as well as sewage
treatment plants, etc.

• Compliance with electric safety, electromagnetic compatibility, and environmental standards.

• Centralized monitoring and control of geographically-distributed systems which support


hierarchical data acquisition and sharing networks.

• Local monitoring and control with data sharing capabilities of plant-distributed equipment.

• Quick troubleshooting, including the possibility of using programmable automation execution.

WARNING
Please note Saitel DR does not support hot-swapping, that is, module replacements during
operation.

2.2 AB_DO Functions

The main features of this module are:


Figure 7 – AB_DO Module

R&D Digital Seville


Pag 17
19/04/2024 User Manual – AB_DO

• Switching power input for digital outputs.

• 8 digital outputs using 2 removable terminal blocks. Each terminal allows connecting 4 signals
with common outputs.
• Each digital output can be configured as: Single / Double
• The module is synchronized via a message received from the HU.
• 12 LED indicators are available on the front side.
The diagram below illustrates the functional blocks integrated in the AB_DO module:
Figure 8 – Functional block diagram

Controller Block
This block manages the AB’s digital outputs, depending on the operation mode. The AB_DO can
operate in one of the two available modes: Select Before Operate (SBO) or Direct Operate (DO).
This operation mode is set before the module switches to the acquisition state. The active mode is
indicated by means of the LED SBO on the front panel.

• SBO Mode (Select Before Operate)


The SBO mode is related to the field outputs or commands triggering procedure. It has the
following restrictions:
o Only one command can be activated at a time.
o The triggering time for outputs is restricted, so latching signals are not supported.

R&D Digital Seville


Pag 18
User Manual – AB_DO 19/04/2024

• DO Mode (Direct Operate)


The DO mode also provides a great level of security even though it is not as restrictive as the
SBO mode:
o This mode can activate several outputs at a time.
o The triggering time can be permanent (latching).

NOTICE
Both modes have a security mechanism that prevents unwanted commands to be transmitted to
field devices if there is hardware/firmware failure.

Digital Outputs
The AB_DO has two terminal blocks labeled as B1 and B3 which allow the connection of 8 digital
outputs (4 per terminal block). The main features of these outputs are:

• The outputs can be SBO (Select Before Operate) or DO (Direct Operate).

• The outputs can be single or double.

• Each output can be pulsing or latching.

• They are permanently monitored.

• Each output is independent.

• External switching power input (Pol).

• Number of operations (resistive load) > 30*106.

• Number of operations (L/R=80ms, 24V/1.25A) > 2*105.

• Automatic switching power input test.

• Galvanic isolation.

• Input protection against electromagnetic disturbances.

2.3 Hardware Architecture

The following P/N describes all available ordering options for this module:
Figure 9 – AB_DO P/N description

Ordering options:

• (A2) Digital outputs switching mechanism is driven by a 24 VDC power input.

• (A3) Digital outputs switching mechanism is driven by a 48 VDC power input.


The following figure illustrates the AB_DO hardware blocks diagram:

R&D Digital Seville


Pag 19
19/04/2024 User Manual – AB_DO

Figure 10 – AB_DO - Hardware block diagram

Switching Power
The AB_DO digital outputs need an external switching power input source; therefore a 24/ 48 VDC
±20% input is provided.

NOTICE
The 48 V version is available for revision B8 and later.

Indicators
There are 12 LED indicators on the module’s front panel which provide information about the
module and the output signals.
Section 3.3 provides detailed information about the information of each LED.
Digital Outputs (B1 and B3)
The signals from DO 1 to DO 4 are connected to B1 and the signals from DO 5 to DO 8 are
connected to B3.
Digital outputs require an external switching power input source, which is wired to the B2 terminal
block on the top left area of the module.

DANGER
Please, check paragraph 1.4 if it’s necessary to mark the module with an electrical risk label
depending on voltage level of the devices to be connected to digital outputs.

R&D Digital Seville


Pag 20
User Manual – AB_DO 19/04/2024

3 Physical Mounting & Installing

R&D Digital Seville


Pag 21
19/04/2024 User Manual – AB_DO

Content

1 SAFETY & HEALTH ................................................................................................4

1.1 INTRODUCTION .......................................................................................................6


1.1.1 INFORMATION OF SECURITY .............................................................................6
1.1.2 PRESENTATION ...............................................................................................6
1.2 INTRODUCTION TO SAFETY .....................................................................................7
1.3 SYMBOLS AND LABELS ON THE EQUIPMENT.............................................................8
1.4 INSTALLATION, SETUP AND OPERATION...................................................................8
1.5 EARTHING ............................................................................................................10
1.5.1 ELECTRICAL SAFETY .....................................................................................10
1.5.2 FUNCTIONAL EARTH (EMC) ...........................................................................11
1.6 HANDLING ELECTRONIC COMPONENTS..................................................................12
1.7 TECHNICAL SPECIFICATIONS FOR SAFETY .............................................................12
1.7.1 PROTECTIVE ELEMENTS ................................................................................12
1.7.2 ENVIRONMENTAL CONDITIONS .......................................................................12
1.7.3 STORAGE CONDITIONS ..................................................................................13
1.8 TECHNICAL LABEL ...............................................................................................13
1.9 PACKING AND UNPACKING ....................................................................................14
1.10 DECOMMISSIONING AND DISPOSAL........................................................................14

2 GENERAL DESCRIPTION .....................................................................................15

2.1 SAITEL DR PLATFORM .........................................................................................17


2.2 AB_DO FUNCTIONS .............................................................................................17
2.3 HARDWARE ARCHITECTURE..................................................................................19

3 PHYSICAL MOUNTING & INSTALLING ...............................................................21

3.1 INSTALLATION ......................................................................................................24


3.1.1 HANDLING ....................................................................................................24
3.1.2 LOCATION IN THE ITB ....................................................................................24
3.1.3 POWER SUPPLY REQUIREMENTS ...................................................................24
3.1.4 MOUNTING PROCEDURE ................................................................................24
3.2 WIRING AB_DO ...................................................................................................25
3.2.1 WIRING RECOMMENDATIONS .........................................................................26
3.2.2 DIGITAL OUTPUT CONNECTION ......................................................................26
3.2.3 SWITCHING POWER .......................................................................................27
3.3 LED INDICATORS .................................................................................................28

4 CONFIGURATION & MAINTENANCE ...................................................................29

4.1 ITB CONFIGURATION ............................................................................................31


4.2 AD_DO CONFIGURATION .....................................................................................33
4.2.1 INFORMATION OF LOCAL ACQUISITION ............................................................34
4.2.2 AB_DO SIGNALS ..........................................................................................35
4.2.3 LOCAL ACQUISITION COORDINATES................................................................36
4.2.4 INFORMATION IN TABLES STATUS AND COMMAND ...........................................37
4.3 MAINTENANCE OF MODULE VIA WEB ....................................................................38

R&D Digital Seville


Pag 22
User Manual – AB_DO 19/04/2024

4.3.1 WEBAPP VS WEBTOOL ...................................................................................38


4.4 USING WEBAPP ....................................................................................................39
4.4.1 HOME TAB ....................................................................................................40
4.5 USING WEBTOOL ..................................................................................................44
4.5.1 INFORMATION ...............................................................................................45
4.5.2 MONITORING ................................................................................................46
4.6 FIRMWARE UPDATE ..............................................................................................47

5 TECHNICAL SPECIFICATIONS TABLE ...............................................................49

R&D Digital Seville


Pag 23
19/04/2024 User Manual – AB_DO

3.1 Installation
3.1.1 Handling
DANGER
Depending on the devices connected, the AB_DO could have hazard of electric shock,
electric arc or burns. For any of these cases, follow these instructions:

• Only qualified operator should install this equipment. Such work should be performed only
after reading this entire set of instructions and checking the technical characteristics of the
device.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it. Consider all
sources of power, including the possibility of back feeding.
• Always use a properly rated voltage sensing device to confirm that all power is off.
• Start by connecting the device to the protective ground and to the functional ground.
• Screw tight all terminals, even those not in use.
Failure to follow these instructions will result in death or serious injury.

To avoid electrostatic damage, the following precautions must be strictly followed:


• Do not touch the bus connector pins.
• If unused, keep the modules in the antistatic bag.

WARNING

Electrostatic discharges may damage semi-conducive devices within the module.

3.1.2 Location in the ITB


There are not special considerations for locating this module in the ITB.

3.1.3 Power Supply Requirements


The main power is supplied by the HU through the bus. An additional power input source is
required to drive the switching mechanism of the digital outputs, and the voltage depends on the
ordering option.
The maximum power requirement for each AB_DO module is:
• Main power supply (through the bus): Basic consumption1
• Switching mechanism power supply: 8 * Switching power input voltage2 * Maximum
consumption per relay1

3.1.4 Mounting Procedure


WARNING
It is important to assure that handling is always done while the ITB elements are unpowered.

1Basic consumption and Maximum consumption per relay values are indicated in the technical specifications table
at the end of this manual.

2 Switching power input voltage value depends on the manufacturing option of each module.
R&D Digital Seville
Pag 24
User Manual – AB_DO 19/04/2024

All Saitel DR modules, have a DIN-rail bracket at the rear side that allows mounting on a DIN rail:
Figure 11 - Mount bracket on DIN rail

The mounting procedure is described below:


• Switch off the power supply.
• Attach the module’s rear bracket on the upper DIN rail.
• Press the lower front panel gently until a click confirms that the bracket is fit on the rail.
• Verifying the module is anchored firmly to the rail, although lateral movement is possible.

Figure 12 Saitel DR module on a DIN rail

The module is dismounted from the DIN rail as follows:


• Switch off the power supply.
• If necessary, disconnect the bridge(s) connecting the module to the system bus.
• Holding the module by the front panel, push the upper metal tab downward. The user can
also pull the tab down using for example a screwdriver as shown in
Figure 13 Remove Module

• Pressing the tab, remove the module from the lower DIN rail.
• Once detached, the module can be removed easily.

3.2 Wiring AB_DO

This module has three terminal blocks labeled as B1, B2 and B3. B2 and B3 allow the 8 digital
outputs to be connected through screw terminals. B1 allow connect the external switching power
input source.
R&D Digital Seville
Pag 25
19/04/2024 User Manual – AB_DO

3.2.1 Wiring Recommendations


The following table shows several wiring recommendations for signals and switching power input
source:

Type of wire

1.5 – 2.5 mm²


Switching power 7 mm 0.5 Nm Copper
15 - 13 AWG
1.5 – 2.5 mm²
Digital outputs 7 mm 0.5 Nm Copper
15 - 13 AWG

3.2.2 Digital Output Connection


Both B1 and B3 have 4 terminals for signals. The field outputs are voltage-free NO (Normally open)
contacts.

Figure 14 – AB_DO – B1 and B3 terminal blocks wiring.

The 4 signals wiring in each terminal block is described below:


Figure 15 – Digital outputs wiring.

R&D Digital Seville


Pag 26
User Manual – AB_DO 19/04/2024

3.2.3 Switching power


The figure below shows how to connect the external switching power input source to the B2
terminal block:
Figure 16 – Switching power input wiring.

The following schematic shows the connection to field for B2 terminal block:
Figure 17 – AB_DO - B1 and B2 terminal blocks wiring.

The following figure shows how you can wire digital outputs in an AB_DO with digital inputs in an
AB_DI module.
Figure 18 – Example of wiring digital inputs and digital outputs.

R&D Digital Seville


Pag 27
19/04/2024 User Manual – AB_DO

3.3 LED Indicators

There are 12 light indicators (LED) on the front of the module:


Figure 19 – AB_DO LED Indicators

The information by the LED indicators includes:


• Acquisition and configuration status (Run and Fail)
• Indicate that the outputs are defined as SBO (SBO)
• Module in maintenance (Mnt)
• Status for each digital output (Digital Output x).
AB_DO’s LED provide the following information to the operator:

LED Status Description Recommended action

Run Module working properly.

Module not in acquisition mode. The module was not included into the
configuration, the module doesn't have an
address or according to the loaded
configuration, the type of the module is wrong.

SBO The outputs are defined as SBO

The outputs are defined as DO

Fail Module not configured or in abnormal state. Check the configuration loaded in the HU. The
module must be addressed and with the
correct type (AB_DO).

No fault has been detected in configuration or


hardware.

Failure in EEPROM.

Mnt The module is in maintenance (Flashing,


addressing, ...)

The module is in operation.

1..8 The corresponding output is active

The corresponding output is inactive

R&D Digital Seville


Pag 28
User Manual – AB_DO 19/04/2024

4 Configuration & Maintenance

R&D Digital Seville


Pag 29
19/04/2024 User Manual – AB_DO

Content
4 CONFIGURATION & MAINTENANCE ...................................................................29

4.1 ITB CONFIGURATION ............................................................................................31


4.2 AD_DO CONFIGURATION .....................................................................................33
4.2.1 INFORMATION OF LOCAL ACQUISITION ............................................................34
4.2.2 AB_DO SIGNALS ..........................................................................................35
4.2.3 LOCAL ACQUISITION COORDINATES................................................................36
4.2.4 INFORMATION IN TABLES STATUS AND COMMAND ...........................................37
4.3 MAINTENANCE OF MODULE VIA WEB ....................................................................38
4.3.1 WEBAPP VS WEBTOOL ...................................................................................38
4.4 USING WEBAPP ....................................................................................................39
4.4.1 HOME TAB ....................................................................................................40
4.5 USING WEBTOOL ..................................................................................................44
4.5.1 INFORMATION ...............................................................................................45
4.5.2 MONITORING ................................................................................................46
4.6 FIRMWARE UPDATE ..............................................................................................47

R&D Digital Seville


Pag 30
User Manual – AB_DO 19/04/2024

4.1 ITB Configuration

NOTICE
To perform the operations described in this chapter, the user must be familiar with the Easergy
Builder tool. Otherwise, please refer to the tool's manual.

In the Workspace of Easergy Builder, create a new RTU using button or pressing right button of
the mouse in an empty area of the RTUs tree:
Figure 20 - Adding new RTU

Pressing button next to the graphical ITB, you can add, remove or change the I/O modules
included on the default configuration.

The user needs understand some basic concepts about Saitel DR before configuring the
acquisition:
• An ITB is a set of acquisition blocks connected to a CPU (HU).
• An Acquisition Block or AB is a Saitel DR input/output module.
• Each acquisition block is allocated to a unique address in the ITB, the Node Number; this
number identifies both the module and its type.
• The procedure AAP (Automatic Addressing Procedure) is performed by the operator
every time an AB module is added, deleted, replaced or moved inside the ITB. It can be
launched manually or automatically depending on the configuration switches of the HU
(consult user manual of the HU).
Figure 21 - Acquisition modules in a default configuration.

The number under each module corresponds with its address. You can select any AB and use
buttons to change its physical position.

R&D Digital Seville


Pag 31
19/04/2024 User Manual – AB_DO

When “Auto Address” box is checked (by default), if you reorder, add or delete an AB, all
addresses are automatically recalculated matching their physical position in the rail. Address
number 1 is assigned to the AB closest to the HU module (for HU_AF or HU_BI, address number 1
will be attached to the HU itself).
If “Auto Address” box is unchecked, modules will retain the allocated address, ignoring any
changes made. If rechecked, the following message will appear:

Select an AB (click on the AB image) and use button to remove it. Use button to add a new
AB and select the type of module to include:
Figure 22 - Adding one (or several) AB.

If “Auto Address” is checked, you can add several AB at one time. This window allows selecting
the quantity of modules to be added. If “Auto Address” in unchecked, you only can add one AB
each time and you have to select the address to be assigned.
To create a new configuration, select RTU in the tree and pulse right button of the mouse or use

button.
Figure 23 - Adding a configuration.

If the field "Create acquisition points defined in the RTU" is marked, all points of the local
acquisition of the acquisition blocks included in the default acquisition configuration associated with
the RTU will be included in coreDb.
For example, if a HUe has an ITB with an AB_DI module, if "Create acquisition points defined in
the RTU", 16 digital inputs signals will be included in the Status table.
Finally, the new configuration will appear in the RTUs tree.
Access to the configuration edition clicking on the configuration name in the tree:

R&D Digital Seville


Pag 32
User Manual – AB_DO 19/04/2024

Figure 24 – Configuration edition.

Double click on the claq Device open the window to configure/modify the ITB.
Selecting the module AB_DO, you can configure each field signal
Figure 25 – Changing the ITB configuration.

Other buttons in this window are explained in the user manual of Easergy Builder.

4.2 AD_DO Configuration

The local acquisition Device for Saitel DR is named “Local Acquisition Device Controller” (claq) and
it is created by default for each Saitel DP configuration.
The main functionality of claq is supporting the communication between field signals of each AB
and its linked coreDb points.
The first step to configure the acquisition settings is to assure that the ITB in the graphical interface
is according to the system. Each module must be addressed according its position in the ITB.
NOTICE
The graphical interface does not show if the ITB is mounted in one or multiple rows.

Modules AB_SER, TU nor XU aren’t included in the schematic

R&D Digital Seville


Pag 33
19/04/2024 User Manual – AB_DO

Figure 26 – Configuring local acquisition for Saitel DR

4.2.1 Information of Local Acquisition


The following figure shows the relationship between the field information received by the AB_DO
module and the related points in coreDb:
Figure 27 – Field signals and points in coreDb.

All signals in this picture are simple. If a signal is configured as double or counter its default name
will be different.

R&D Digital Seville


Pag 34
User Manual – AB_DO 19/04/2024

4.2.2 AB_DO signals


The following figure shows the configuration panel when the ITB is composed by an HUe and one
AB_DO module with address 1:
Figure 28 – AB_DO field signals.

Select the module in the ITB and all its field signals are shown (marked in red).
The first position of each row corresponds with the signal’s description (DO_OSIM_1 ..
DO_OSIM_8). In coreDb, each signal will be identified using its coordinate (see paragraph 4.2.3 ).
For each signal, the following parameters can be changed:
• Type of signal: The signal is configured as: Simple digital (DO_OSIM) or double digital
(DO_ODOB).
When a signal is configured as double digital this signal and the following are grouped together.
For example, if the signal 1 and 2 are configured as DO_ODOB then they must be considered as
two binary join digits, thus 00 – no signal On, 01 – first signal On, 10 – second signal On and 11 –
both signals On.
So, it is possible to control two signals form the same command.
The following parameters will be available or not depending on the type of signal:
• Latch:
o No: The digital output is configured as pulsing.
o Yes: The digital output is configured as latch.
• ExeTim(ms): In case latch option is not used ExeTim can be configured. It means the pulse
time duration when the digital output is activated.
Figure 29 – Configuring double output signal.

R&D Digital Seville


Pag 35
19/04/2024 User Manual – AB_DO

NOTICE
Setting a digital signal as a double groups that signal and the next one. For example, 7 and 8 are
chosen, and therefore should be taken as two digit binary sets. In this way, 00, 01, 10 or 11 (0, 1,
2 or 3 in WebApp or CoreDb), will turn on any signal, the first, the second or both at the same
time respectively. Therefore, you can control the behavior of two signals from the same
command.

4.2.3 Local Acquisition Coordinates


Each digital input is identified in coreDb by a name (it is stored in the field Description), but this
name is only used for information purpose. coreDb uses the signal’s coordinate in order to identify
a field signal.
The following picture shows digital outputs of the module AB_DO (address 1) in the command
table.

A claq coordinate is a numerical identifier of 10 digits with the following structure:


1 XXX YY ZZZZ
Where:
• 1: First digit of the coordinate. In local acquisition signals, it must always be 1.
• XXX: Three digits to indicate the module’s address.

• YY: Type of signal. For digital input could be:


o 00: Diagnostic signals of the acquisition modules.
o 05: Simple digital output.
o 15: Double digital output.

• ZZZZ: Number of the signal within each type, that is, it does not need to match the physical
position. The first signal of a type will be 0000, the second will be 0001 ..., with all the types of
the previous point.
For example, if a coreDb point has associated the signal 1003050002 as destination, then it means
that this point of coreDb execute a single command (05) on signal (0002) of the module with
address 003.

R&D Digital Seville


Pag 36
User Manual – AB_DO 19/04/2024

4.2.4 Information in Tables Status and Command


Each AB_DO’s signal is associated to a coreDb register in the status table using its claq coordinate
as source:

Figure 30 – Information of digital outputs in Status coreDb

Each AB_DO’s signal is associated to a coreDb register in the command table using its claq
coordinate as destination:
Figure 31 – Information of digital outputs in Command coreDb

These points and other diagnostic points (D001_COMM_DIAG and D001_HW_DIAG) can be
created automatically when the module is included in the ITB, but they can be created manually
using the claq’s wizard.
In order to include a point manually, please create a new point, select claq as Source Device, click
right-button on the field Source Coordinates and select Launch Point wizard:

Select the module in which it wants to create these points and then select the point to be created.
NOTICE
Only not created point will be shown in the list.

The following point can be added for AB_DO module:


• 8 points for information from field. A coreDb point will be included in the Command table for
each field signal. The default name is: D00x_00000 ... D00x_0007, where 00x is the module’s
address.
R&D Digital Seville
Pag 37
19/04/2024 User Manual – AB_DO

• Two diagnostic points associated to the module:


o COMM_DIAG: Status of the communication with the HU. 0 → “Communication
FAIL”, 1 → “Communication OK”.
o HW_DIAG: Hardware diagnostic. 0 → No problem detected, 1→ Problem
detected in the hardware.
Figure 32 – Digital outputs local acquisition

4.3 Maintenance of Module via WEB

4.3.1 webApp vs webTool


webApp and webTool are remote user interfaces for consulting, monitoring and maintenance tasks.
Once the username and password have been entered, you can access to the main window and,
depending on the web tool, several sections are available.
NOTICE
webApp has been designed to work only with the cyber security brick. This functionality is not
available in systems that don’t include the cyber security brick and doesn’t work in systems
without the external web server either. Pages are loaded dynamically according to the user’s
roles.

When use webApp, the following message is shown previously to access the tool:

R&D Digital Seville


Pag 38
User Manual – AB_DO 19/04/2024

Figure 33 – Disclaimer information.

Please, read this information and take it into account.


In this manual, only the information about AB_DO is shown. For more information about these
tools, please, consult the user manual for each one.

4.4 Using webApp

Saitel webApp includes an access management allowing to control users who can login in the tool.
To access webApp, write https://< CPU IP address> in the navigation address bar, where <CPU
IP address> must be changed for the correct IP address:
Figure 34 – Access screen.

Write the Username and Password in orfer to access the webAppp’s mains window:

R&D Digital Seville


Pag 39
19/04/2024 User Manual – AB_DO

This screen contains 5 menus:


• Home
• Monitoring & Control
• Diagnostic
• Maintenance
• Settings

4.4.1 Home tab


Select Home in the main toolbar and the following information is shown:
Figure 35 –Home tab.

R&D Digital Seville


Pag 40
User Manual – AB_DO 19/04/2024

Some of this information can be filled in by the user.

• Device Information. It is possible to add the names of the operators who have used or
configured the equipment or a specific custom note that can be viewed each time a connection
is established to this RTU. This information can be changed using button “Edit”, next to “Device
information”.

• Location. The GPS coordinates for the RTU location (place, latitude, longitude, and altitude)
should be entered here by the installer. Location is not set automatically. The image must be
included manually by clicking button on the map.

• Image associated to the RTU. It could be useful to include a location map corresponding to the
GPS coordinates. Use button on the graphic zone to do it.

• Notes. This zone allows the user to include notes that are shown to other users. Use button
too add new notes.

• Factory information: This zone shows the manufacturer, model and the version of the
software loaded on the HU module. Using button next to the text “Factory Information”, it is
also possible to include an image of the particular RTU or CPU for identification purposes.
This screen contains other menus:

• Monitoring & Control

• Diagnostic

• Maintenance

• Settings
This manual only includes relevant information for AB_DO. For more information about webApp,
please, consult the webApp user manual.

R&D Digital Seville


Pag 41
19/04/2024 User Manual – AB_DO

Monitoring and Control


This menu is used to monitor and control the information regarding to system status and coreDb
points.
Select “Monitoring & control → System information” and the following information the system is
displayed or not depending on whether the corresponding monitoring point was included or not in
coreDb. In the following image, for each data, the supervision point that must be included in coreDb
is indicated in a blue square.
Figure 36 - Monitoring and Control view - System information.

Please take into account that the correspondent supervision points must be installed, otherwise,
you will see a warning like the one in the example above (PLC information not available).
Selecting “Monitoring and control → Data” allows to monitor the information of each coreDb table.
For an AB_DO module, the showed points are the followings:
Figure 37 - Monitoring and Control – Status

Use buttons marked in blued to execute a command or button in red to change the associated
quality values.
Figure 38 – Executing a command
R&D Digital Seville
Pag 42
User Manual – AB_DO 19/04/2024

Using value 1 and pressing button OK, a command is sent to field, latched or pulsed depending on
the configuration of the local acquisition signal.
Figure 39 – Changing associated quality flags

For each signal, its quality information is shown in the table through icons in the column Quality. In
coreDb, this information is stored in hexadecimal format.
The quality information associated with a signal could include one or more of the following
messages:
Table 2 - Local quality bits

Values (Hexadecimal) Description

0x00000000 OK

0x00000001 There has been an overflow

0x00000002 There has been a carry on a counter or a roll-over.

0x00000004 There has been a counter adjustment.

0x00000008 Excessive changes in a digital input.

0x00000010 Locked Point (blocked)

0x00000020 Point manually replaced (manual)

0x00000040 The point has not yet been written into the database (No refresh)

0x00000080 Invalid value (Error)

0x00000100 The value of the item has exceeded Highest Limit Alarm.

R&D Digital Seville


Pag 43
19/04/2024 User Manual – AB_DO

Values (Hexadecimal) Description

0x00000200 The value of the item has exceeded High Limit Alarm.

0x00000400 The value of the point has fallen down of Low Limit Alarm.

0x00000800 The value of the point has fallen down of Lowest Limit Alarm.

0x00001000 Invalid time.

Table 3 - Quality bits from the Device

Values (Hexadecimal) Description

0x00000000 OK

0x00010000 There has been an overflow.

0x00020000 There has been a carry on a counter or a roll-over.

0x00040000 There has been a counter adjustment.

0x00080000 Excessive changes in a digital input.

0x00100000 Locked Point.

0x00200000 Point manually replaced.

0x00400000 The point has not yet been written into the database.

0x00800000 Invalid value.

0x10000000 Invalid time.

NOTICE

If more than one error is detected for a signal, the hexadecimal value monitored for quality bits
will result from the sum of all. For example:
0x00000001 indicates that an overflow has occurred and 0x00000002 indicates that there has
been a carry on a counter or a roll-over. The value 0x00000003 would appear monitored.

4.5 Using webTool

Saitel webTool is the tool used for maintenance and monitoring of Saitel RTUs which is supplied
with the baseline software platform. The values of all the coreDb signals in real-time can be
monitored through the Saitel Webtool as well as the quality data related to these values.
Saitel webTool has an access control that allows differentiating the users who are able to connect.
To get the window access, please write https://< CPU IP address> in the navigation address bar.
If the browser has been correctly configured, and the remote equipment is connected to the PC,
the login window will prompt:

R&D Digital Seville


Pag 44
User Manual – AB_DO 19/04/2024

Figure 40 - Saitel Webtool login window

Once the username and the password are introduced in the login window, the main workspace is
displayed:
Figure 41 - Initial screen of Saitel Webtool

This window shows:


• Information about the user who opened the session (Login: admin).
• Button “Exit” in order to close the current session.
• It is possible to select the language through the field “Language”.
• The main menu is located on the left side of the screen. Each button gives access to all the
information of the RTU:
o Information: General information about the CPU configuration.
o Monitoring: Gives access to the coreDb tables and the values for each register and
field.
o Bins: Gives access to the devices that have been configured in the RTU.
o Network configuration: Gives information about the physical devices and rooters.

4.5.1 Information
Clicking Information on the main menu, you can see general information about the system.
The following real-time information can be monitored on this menu:
• System’s Configuration
• Hardware Status
• Synchronization Status
• Software Versions
R&D Digital Seville
Pag 45
19/04/2024 User Manual – AB_DO

Figure 42 - Information section

4.5.2 Monitoring
The top area of the screen includes the following information for any signal type (go to “Monitoring
→ Status”, “Monitoring → Command”, “Monitoring → Analog” or “Monitoring → Setpoint”):
For each kind of modules, the information will be included in different tables. In the case of the
AB_DO module, the information for the acquisition points can be found in the Status and Analog
screen.
In the status table, two signals are automatically created.
▪ COMM_DIAG: CPU diagnosis communication variable. 0 the module cannot communicate
with the CPU. 1 the module is communicating properly with the CPU.
▪ HW_DIAG: Auto diagnosis hardware variable. 0 the module is correct. 1 the module has some
hardware problem.
In the command table, the command acquisition points can be monitored.
The information available for all types of signals is the following:
• Point name: Signal's name in coreDb.
• Value: Current value of the signal. This value is retrieved from the signal’s source and it is
updated in Saitel Webtool according to the refresh period specified in the RT field.
• QF: Current quality flags of the value displayed for this signal
NOTICE
If the value of the quality bit associated to the signal is “Unrefreshed” (0x00000040) or “Invalid”
(0x00000080), the signal value will be “???”.

Clinking in “Set”, the value and the quality flag can be modified.
Each code of quality bit has a different meaning. See next tables to know the description of each
one.
NOTICE
If more than one error is detected for a signal, the hexadecimal value monitored for quality bits
will result from the sum of all. For example:

0x00000001 indicates that an overflow has occurred and 0x00000002 indicates that there has
been a carry on a counter or a roll-over. The value 0x00000003 would appear monitored.

R&D Digital Seville


Pag 46
User Manual – AB_DO 19/04/2024

4.6 Firmware Update

Once the ITB is configured, the HU module (HU_A or HU_B) already knows the type of acquisition
blocks that are been installed and their corresponding addresses.
To update the software of the AB_DO module, you need:
• A console connection with the HU.
• AB_DO module must be correctly addressed and working fine in the ITB (LED Run must be
blinking).
• AB_DO.bin file with the new version. This file must be available in the flash folder of the HU. If
not, you can contact Schneider Electric in order to ask for it. Use an SFTP client and transfer
this binary file into the HU flash folder.
The console tool can be executed using any commercial tool for serial or SSH connection. In this
manual, PuTTy software is used.
Open a serial connection as follow:
Figure 43 – SSH connection.

SSH connection via Ethernet can be used too. More information about the console use in the HU
user manual. In the following picture, HUe is used as CPU:
Figure 44 – Console.

R&D Digital Seville


Pag 47
19/04/2024 User Manual – AB_DO

NOTICE
If the baseline includes the cybersecurity brick, you need to login in the console with Installer.
No other user has permissions to execute this operation. Please, consult the HU user manual
for more information.

If the file AB_DO.bin is available in the flash folder, use one of the following commands to upgrade
the software of AB_DO modules:
Table 4 – Upgrading AB_DO’s software.

Module File Command Description

All modules *.bin claqUpgrade “all” It updates all the acquisition AB


addressed in the ITB. You need to
use the adequate file for each block.

By position AB_DO.bin claqUpgrade It updates the module AB_DO with


“<position>” the <position> address.

AB_DO AB_DO.bin claqUpgrade “all It updates all the AB_DO modules


AB_DO” installed in the ITB.

NOTICE
Console commands are case-sensitive, and quotation marks must be included when are
indicated.

After running the command, the console will show some messages indicating the process status.
Finally, if no problem is found, we will have updated the firmware of the modules.

R&D Digital Seville


Pag 48
User Manual – AB_DO 19/04/2024

5 Technical Specifications Table

R&D Digital Seville


Pag 49
19/04/2024 User Manual – AB_DO

Hardware Specifications
Number of outputs 8 (independents)
DO switching power input 24 VDC (±20%) (Ordering option A2)
48 VDC (±20%) (Ordering option A3)
Number of operations resistive load > 30*106
(L/R = 80 ms, 24 V/1.25 A) > 2*105
Maximum output current 5A
Contact type Voltage-free (Normally Open)
Consumption 0.75 W (Typical)
0.4 W/relay
Weight 530 g
Dimensions 94 x 129 x 60 mm
Coating AVR80 (depending on P/N)
Range of temperature Operation: From -40º C to +70º C
Storage: From -40º C to +125º C

Interfaces
Switching power input (B2) 3-pole terminal block
Wire: 2.5 mm² (13 AWG)
Digital outputs (B1 and B3) Two 8-pole terminal blocks
B1 → DO1 to DO4 and B3 → DO5 to DO8
Wire: 2.5 mm² (13 AWG)

Software
Switching power input test Automatic
Type of module (all signals) Select Before Operate (SBO) or Direct Operate (DO)
Type of signals (each signal) Pulsing or latching
Single or Double

CE Mark
Standards, Directives and LVD – Low Voltage Directive Directive 2006/95/CE
harmonized norms. Directive 2004/108/CE
EMC – Electromagnetic Compatibility
RoHS 3 – Restriction of Hazardous Directive 2015/863/EU.
Substances
Directive 2010/30/EU according to RD
ErP – Eco-Design 187/2011
WEEE – Waste Electrical and Electronic Directive 2012/19/UE according to RD
Equipment 110/2015
Power supply and EMC
EMC tests according to
IEC-EN 60870-2-1:1996
Immunity for equipment in power station and substation environment - IEC 61000-6-5
and EN 50121-5:2017 /A1:2019
Immunity standard for industrial environments - IEC 61000-6-2 and EN 50121-5:2017
/A1:2019
Emission standard for industrial environments - IEC 61000-6-4 and EN 50121-5:2017
/A1:2019
Emission EMC tests Radiated emissions
From 30 to 6000 MHz (Class A)
EN 55022:2006 + A1:2007

R&D Digital Seville


Pag 50
User Manual – AB_DO 19/04/2024

Conducted emissions
From 0.15 to 30 MHz (Class A)
EN 55022:2006 + A1:2007
Immunity EMC tests Electrostatic discharges (ESD) By air ±8 kV and by contact (direct and
IEC-EN 61000-4-2 (1995) / A1 (1998) / indirect) ±6 kV (Level 3)
A2 (2001)
Radiated, RF, EMC field
From 80 to 6000 MHz (Level 3)
IEC-EN 61000-4-3:2006
Fast transient common mode Power port: ±4 kV, 5kHz.
Communications ports: ±4 kV 5kHz and
IEC-EN 61000-4-4:2012 2.5kHz.
I/O ports: ±4 kV 5kHz and 2.5kHz
Power port: ±4 kV common and differential
Surge, line to line and line to ground mode
Other ports: ±2 kV differential mode, ±4
IEC-EN 61000-4-5:2006
kV common mode
Conducted disturbances, RF fields
10 VRMS 0.15-80MHz 80% AM (Level 3)
IEC-EN 61000-4-6:1996 + A1:2001
Power frequency, magnetic field 100 A/m, 1000 A/m 3s (Level 4).
IEC-EN 61000-4-8:2010. 300 A/m >10s

Damped oscillatory wave Power, Communications and I/O:


1kV symmetrical, 2.5kV asymmetrical,
IEC-EN 61000-4-18:2007 + A1:2010
(f=1MHz)

Electrical Safety
General requirements Meets all the requirements indicated in the
normative
IEC 60950-1
Insulation and dielectric rigidity
Isolation >100 MΩ, 2 kVAC
IEC 60255-5

Environmental
Environmental tests Cold
-40ºC during 16h (Cold start)
EN 60068-2-1:2007
Dry heat
+70ºC during 16h
EN 60068-2-2:2007
Acceleration: 250 m/s2;
Bump test (1 vertical axis) Duration of pulse: 6 ms;
Number of shocks: 100
EN 60068-2-29
shocks/axis/polarity
Random vibration test (3 axes) Range: From 10 Hz to 500 Hz
Test duration: 30 minutes
UNE-EN 60068-2-64

WARNING
According to the standard 60950-1, all electrical safety tests have been done in an
environmental temperature range of -40 ºC to 60 ºC. For higher temperature (> 60 ºC), the
module must be handled with care, since the metal surface could reach a dangerous
temperature for the user.

R&D Digital Seville


Pag 51
19/04/2024 User Manual – AB_DO

Ordering Options

R&D Digital Seville


Pag 52
User Manual – AB_DO 19/04/2024

Index of Figures
Figure 1 - Barrier of protection for elements with dangerous voltages. ........................................................................9
Figure 2 - Yellow and Green cable for earthing. .........................................................................................................11
Figure 3 - Terminal for functional earth (EMC). ..........................................................................................................11
Figure 4 - Example of earthing for EMC. ....................................................................................................................12
Figure 5 - Technical label. ..........................................................................................................................................13
Figure 6 – Saitel DR ..................................................................................................................................................17
Figure 7 – AB_DO Module ..........................................................................................................................................17
Figure 8 – Functional block diagram ..........................................................................................................................18
Figure 9 – AB_DO P/N description .............................................................................................................................19
Figure 10 – AB_DO - Hardware block diagram ..........................................................................................................20
Figure 11 - Mount bracket on DIN rail ........................................................................................................................25
Figure 12 Saitel DR module on a DIN rail ..................................................................................................................25
Figure 13 Remove Module .........................................................................................................................................25
Figure 14 – AB_DO – B1 and B3 terminal blocks wiring. ...........................................................................................26
Figure 15 – Digital outputs wiring. ..............................................................................................................................26
Figure 16 – Switching power input wiring. ..................................................................................................................27
Figure 17 – AB_DO - B1 and B2 terminal blocks wiring. ............................................................................................27
Figure 18 – Example of wiring digital inputs and digital outputs. ................................................................................27
Figure 19 – AB_DO LED Indicators ............................................................................................................................28
Figure 20 - Adding new RTU ......................................................................................................................................31
Figure 21 - Acquisition modules in a default configuration. ........................................................................................31
Figure 22 - Adding one (or several) AB. .....................................................................................................................32
Figure 23 - Adding a configuration. ............................................................................................................................32
Figure 24 – Configuration edition................................................................................................................................33
Figure 25 – Changing the ITB configuration. ..............................................................................................................33
Figure 26 – Configuring local acquisition for Saitel DR ..............................................................................................34
Figure 27 – Field signals and points in coreDb. .........................................................................................................34
Figure 28 – AB_DO field signals.................................................................................................................................35
Figure 29 – Configuring double output signal. ............................................................................................................35
Figure 30 – Information of digital outputs in Status coreDb .......................................................................................37
Figure 31 – Information of digital outputs in Command coreDb .................................................................................37
Figure 32 – Digital outputs local acquisition ...............................................................................................................38
Figure 33 – Disclaimer information. ............................................................................................................................39
Figure 34 – Access screen. ........................................................................................................................................39
Figure 35 –Home tab. .................................................................................................................................................40
Figure 36 - Monitoring and Control view - System information. .................................................................................42
Figure 37 - Monitoring and Control – Status...............................................................................................................42
Figure 38 – Executing a command .............................................................................................................................42
Figure 39 – Changing associated quality flags ...........................................................................................................43
Figure 40 - Saitel Webtool login window ....................................................................................................................45
Figure 41 - Initial screen of Saitel Webtool .................................................................................................................45
Figure 42 - Information section ...................................................................................................................................46
Figure 43 – SSH connection. ......................................................................................................................................47
Figure 44 – Console. ..................................................................................................................................................47

R&D Digital Seville


Pag 53
19/04/2024 User Manual – AB_DO

Index of Tables
Table 1 – Symbols ........................................................................................................................................................8
Table 2 - Local quality bits ..........................................................................................................................................43
Table 3 - Quality bits from the Device ........................................................................................................................44
Table 4 – Upgrading AB_DO’s software. ....................................................................................................................48

R&D Digital Seville


Pag 54
User Manual – AB_DO 19/04/2024

Glossary
A
A: Ampere.
AAP: Automatic Addressing Procedure.
AB: Saitel DR Acquisition Block.
AB_AC: Direct measurements Acquisition Block.
AB_AI: Analog Inputs Acquisition Block.
AB_AO: Analog Outputs Acquisition Block.
AB_DI: Digital Inputs Acquisition Block.
AB_DIDO: Digital Inputs and Outputs Acquisition Blocks.
AB_DO: Digital Outputs Acquisition Blocks.
AB_MIO: Multiple Inputs and Outputs Acquisition Block.
AB_SER: Communication module for expansion.
AC: Alternate Current.
AI: Analog Input.
AO: Analog Output.
AWG: American Wire Gauge.

B
Bps: Bits per second.

C
ºC: Celsius degree.
COM: Communication port.
CPU: Central Processing Unit.
CTS: Clear to Send.

D
DC: Direct Current.
DI: Digital Input.
DIN: Deutsches Institut für Normung.
DO: Digital Output.
DRAM: Dynamic Random Access Memory.

E
EMC: Electro Magnetic Compatibility.
EPROM: Erasable Programmable Read Only Memory

F
FTP: File Transfer Protocol.

R&D Digital Seville


Pag 55
19/04/2024 User Manual – AB_DO

G
g: Gram.
GPS: Global Positioning System.

H
HU: Head Unit. Saitel DR CPU.
HU_A: Saitel DR Advanced Head Unit.
HU_AF: Saitel DR Advanced Head Unit with acquisition.
HU_B: Saitel DR Basic Head Unit.
HUe: Saitel DR High-Performance Head Unit.
Hz: Hertz.

I
IED: Intelligent Electronic Device.
I/O: Input / Output.
IRIG: Inter Range Instrumentation Group.
IRIG-B: Mode B of the standard IRIG.
ISO 9001: International standard for Quality Systems.
ITB: Intelligent Terminal Block.

K
KB: Kilobyte.
kHz: Kilohertz.

L
LAN: Local Area Network.
LED: Light Emitting Diode.

M
mA: Milliampere.
MHz: Megahertz.
MB: Megabyte.
Mbps: Megabits per second.
m: Meter.
mm: Millimeter.
ms: Millisecond.

N
N/A: Non-Application.

P
PC: Personal Computer.
PPS: Pulses per Second.
PS: Power Supply.

R&D Digital Seville


Pag 56
User Manual – AB_DO 19/04/2024

PWR: Power.

R
RAM: Random Access Memory.
RS-232: Communication standard.
RS-485: Multipoint differential Bus.
RTDB: Real Time DataBase.
RTS: Request To Send.
RTU: Remote Terminal Unit.
Rx: Reception

S
s: Second.
SCADA: Supervisory Control And Data Acquisition.
SNTP: Simple Network Time Protocol.
SRAM: Static Random Access Memory.

T
TCP/IP: Transmission Control Protocol/Internet Protocol.
TFTP: Trivial File Transfer Protocol.
TU: Terminal Unit.
Tx: Transmission.

V
VAC: Volt of Alternate Current.
VDC: Volt of Direct Current.

W
W: Watt.

X
XU: Expansion Unit.

R&D Digital Seville


Pag 57
Printed in:
Wednesday, April 24, 2024

Schneider Electric
C/ Charles Darwin s/n
Parque Científico y Tecnológico de la Cartuja
Seville, Spain

©2020 All rights reserved. The information contained in this document is


confidential and is owned by Schneider Electric. It cannot be copied or distributed
in any way, unless there is express written authorization by Schneider Electric.
Although this information was verified at the time of publication, may be subject to change without notice.

SE- M554-USR-04 11/2023

Internal

You might also like