FACTORY ACCEPTANCE TEST Date Issued : 16th January 2012
CHECKLIST FOR VISUAL INSPECTION OF LOW Revision : -
VOLTAGE ELECTRICAL BOARDS Revision Date : -
Page : 1/5
PROJECT NAME :
MANUFACTURER NAME :
Notes:
1. This form is to be used as a checklist for visual inspection acceptance only. Other acceptance criteria such as dielectric
properties test, insulation resistance test and functional test shall use the forms provided by the manufacturer. S.O Rep is
advised to begin the FAT with the visual inspection test ahead.
2. Prior departure to the factory, SO Representatives (SORs) are recommended to bring together:
Documents : Approved Shop Drawing of Switchboard, BQ & Material List as per contract
Tools : Digital Caliper, Measuring Tape, Torchlight, Digital Camera
3. Upon arrival and prior of any testing, SO Representatives are required to check/ensure:
a. Date of calibration status of the instruments to be used for testing. (Calibration validity: 2 years)
b. Certificate of the manufacturer’s competent person who will in charge for the testing. (Min. AO)
c. Brand & Model of the material installed had been approved during construction stage as referred to
material approval list (comply to J-MAL and material list as per contract).
d. Inspect thoroughly compliance of the manufactured switchboard with the approved shop drawing
particularly on the following criteria:
Rating, Number of Poles & Arrangement of EACH Switchgear and terminals
SPECIFICATION/JKR COMPLIANCE
NO. DESCRIPTION [√: Yes, X : No, - : Not REMARKS
REQUIREMENT Applicable]
Board Name:
SPECIFICATION/JKR COMPLIANCE
NO. DESCRIPTION [√: Yes, X : No, - : Not REMARKS
REQUIREMENT Applicable]
SPECIFICATION/JKR COMPLIANCE
NO. DESCRIPTION [√: Yes, X : No, - : Not REMARKS
REQUIREMENT Applicable]
F) Switchgears
1 Switchgears Current rating are accordance with
drawing and/or BQ
2 ACBs Withdrawable metal clad,
flush mounted & horizontal drawout
isolation, c/w shutter
2.1 No. of poles 3 or 4
2.2 Icw Minimum 50 kA at 415V for 1 sec. or
otherwise specified
2.3 Copper tape/bar from Tinned copper
frame (metal) of ACB
to SEB
2.4 Used as Bus-coupler 4 pole
3 MCCBs No. of poles are accordance with drawing
and/or BQ
3.1 Icu Minimum 50 kA at 415V for 1 sec. or
otherwise specified
3.2 Incoming Feeder Provided with panel mounting external If required
Circuit Breaker ≥ 400A operating handle with padlocking
facilities and door interlocking facilities
G) Current Transformers
1 Secondary Rating 5A
2 Rating ≥ 15 VA
3 Accuracy (for measuring & Class 1.0 or otherwise specified
metering)
4 Accuracy (for protection) Class 10P10 or otherwise specified
H) Surge Protection Device
1 Connecting Leads as short as possible Preferably not exceeding
0.5m for the total length.
2 2.1 Isolation of SPD : 4 pole MCCB or fuses or otherwise
MCCB / Fuse specified
2.2 Isolation of SPD : Separate compartment for SPD
Compartment
3 Transparent Window for At front cover of the SPD’s compartment
viewing the SPD indicator for viewing the SPD indicator
4 Label “Amaran” at SPD Sentences as in L-S1 with red lettering on
compartment a white background
I ) Distribution Board
1 Material Sheet steel
2 Thickness 1.2mm to 1.5 mm
3 Serrated Star Washer At front cover
4 Anti Rust Treatment Epoxy dry powder
5 Color Enamel Grey
6 Panels, Covers & Front Cylindrical knurled head (chromed type)
Doors c/w retaining clip
7 Comb / Fork Busbar Insulated type
SPECIFICATION/JKR COMPLIANCE
NO. DESCRIPTION [√: Yes, X : No, - : Not REMARKS
REQUIREMENT Applicable]
Note : For item J, K & L, the compliance of specification & JKR requirement for item Self-Contained Floor Mounted Cubicle Switchboard
and item Busbar are similar as LV Switchboard above. i.e: Thickness, size, material, etc.
J) Power Factor Correction Board (PFCB)
1 Enclosure Not form part of the switchboard it is
connected to (independent) but match the
height and depth.
1.1 Icu of MCCB / ACB Minimum 50 kA at 415V for 1 sec. or Icu:
otherwise specified Ics:
1.2 Access Front & rear
2 Capacitor
2.1 Category C (min. 40oC)
2.2 Rated Voltage 525V, 50Hz
2.3 Housing/Container Heavy metal sheet steel
2.4 Separation between Min. 80mm
capacitors
3 Reactor Installed in separate compartment of
PFCB c/w rubber pad to reduce noise due
to vibration etc.
3.1 Class H
3.2 kVAR Rating Min. 6%
(Reactance)
3.3 Rated Voltage 440V
4 MCCB
4.1 Icu of MCCB / ACB Minimum 50 kA at 415V for 1 sec. or Icu:
otherwise specified. Ics:
Ics = 100% Icu
4.2 Minimum Continuous Min. 155% of rated capacitor currents
Current Ratings
5 Switching Contactor
5.1 Utilization Category AC-6B
5.2 Minimum Continuous Min. 135% of rated capacitors currents
Current Rating
5.3 Ventilation Van Heavy duty type* c/w filter and *Air Exchange :
automatic shutter Min.200 cubic meter
perhour
6 All secondary wiring Properly labelled with number sleeves
K) Generator Set Switchboard [Essential Board]
1 Enclosure Not form part of the switchboard it is
connected to (independent) but match the
height and depth.
2 Automatic Transfer Transparent protection screen of full
Switching Equipment compartment size shall be provided in front
(ATSE) of automatic changeover contactors / ATSE
2.1 Contactor Utilization AC-33B
Category
2.2 MCCB / ACB type 4 pole
3 Tinned Copper Earthing 25mm x 6mm
Bar
4 All secondary wiring Properly labelled with number sleeves
L) Generator Set Control Board (GSCB) [AMF Board]
1 Enclosure Not form part of the switchboard it is
connected to (independent) but match the
height and depth.
2 Emergency Stop Push- Provided and c/w self-latching mushroom
Button head type
3 Alarm Bell Min.250mm diameter
4 All secondary wiring Properly labelled with number sleeves
Signature : Position :
Name : Date :
(CAPITALS)
On behalf of :
Signature : Position :
Name : Date :
(CAPITALS)
On behalf of :
ELECTRICAL CONTRACTOR
Signature : Position :
Name : Date :
(CAPITALS)
On behalf of :
MANUFACTURER
Signature : Position :
Name : Date :
(CAPITALS)
On behalf of :
LOCATION/PROJECT :
FLOOR/BLOCK NO. :
DATE OF TEST :
MSB SSB
DB Feeder Pillar
REMARKS:
Tested by (Name) :
Signature :
Date :
This Record Of Continuity and Insulation Resistance Test form shall be used for the reporting on the condition of All Final Circuit Wiring
(except Ring Final Circuits) for New Installation before final connection of the switches, sockets, electrical accessories, fittings and DB.
A. PARTICULARS OF THE INSTALLATION [Please tick (√ ) the relevant boxes and enter details as appropriate]
Project Name
Drawing No./Installation
Address
Block No./Floor
C. TEST RESULTS (Please X where not applicable. Please refer to Page 2 for notes and test procedures)
Circuit Number And Phase
Type of Wiring [see note 2]
Circuit Reference [see note 3]
Number of Points
Phase (mm²)
Cable Size
CPC (mm²)
C1. CONTINUITY TEST (Choose either Test Method 1 or 2)
Neutral & CPC,
(ohms)
[see Test Method 1]
Phase & CPC,
(ohms)
[see Test Method 2]
Confirmation of CPC in the circuit is continous
(Mark Y for YES and N for NO)
C2. INSULATION RESISTANCE TEST
Phase to Neutral (L-N) (Mohms)
Phase to CPC (L-E) (Mohms)
Neutral to CPC (N-E) (Mohms)
Phase & Neutral to G.I Conduit/Trunking (Mohms)
A. NOTES
1.2 Test method 2 (CPC terminated at the switch panel and using the phase conductor as a return lead)
1.2.1 Connect the phase conductor (phase wire) to the CPC conductor (earth wire) at the switch panel.
1.2.2 Test between the phase and earth of the circuit at the DB.
1.2.3 Record the test result obtained.
1.2.4 The readings should be compared with the "Resistance of copper conductors" table for a particular length
and size.
2.2 Test method (CPC conductor terminated at the last point of the circuit)
2.2.1 Test between the phase (join together all phase conductors at the switch panel) and the neutral at the DB.
2.2.2 Repeat the test for phase to CPC.
2.2.3 Test between the neutral and the CPC at the DB.
2.2.4 A value of less than 100MΩ on a final circuit is to be unacceptably low and require further investigation.
This Record Of Continuity and Insulation Resistance Test form shall be used for the reporting on the condition of Ring Final Circuit
Wiring only for New Installation before final connection of the switches, sockets, electrical accessories, fittings and DB.
A. PARTICULARS OF THE INSTALLATION [Please tick (√ ) the relevant boxes and enter details as appropriate]
Project Name
Drawing No./Installation
Address
Block No./Floor
C. TEST RESULTS (Please X where not applicable. Please refer to Page 2 for notes and test procedures)
Circuit Number And Phase
Type of Wiring [see note 2]
Circuit Reference [see note 3]
Number of Points
Phase (mm²)
Cable Size
CPC (mm²)
C1. CONTINUITY TEST (See Test Procedure 1.0)
Phase (ohms)
Neutral (ohms)
CPC (ohms)
Confirmation of Ring Final Phase &
(ohms)
Circuit is wired in a Ring Neutral
(Mark Y for YES and N for NO) Phase &
(ohms)
(See Test Procedure 2.0) CPC
C2. INSULATION RESISTANCE TEST
Phase to Neutral (L-N) (Mohms)
Phase to CPC (L-E) (Mohms)
Neutral to CPC (N-E) (Mohms)
Phase & Neutral to G.I Conduit/Trunking (Mohms)
A. NOTES
3.0 For Ring Final Circuits, Regulations 612.2.2 of BS7671:2008 calls for the continuity of EACH live conductor (phase
and neutral) and the protective conductor to be verified.
B. TEST PROCEDURES
2.0 CONFIRMATION OF RING FINAL CIRCUIT IS WIRED IN A RING (4 ends joined method)
2.1 Phase and neutral conductors cross-connected.
2.1.1 Connect the outgoing phase (P1) conductor to the returning neutral (N2) conductor. (P1 to N2)
2.1.2 Connect the returning phase (P2) conductor to the outgoing neutral (N1) conductor. (P2 to N1)
2.1.3 Measure the resistance across (P1 to N2) and (P2 to N1) and record the reading.
2.1.4 Measure the resistance at each socket on the ring between phase & neutral.
2.1.5 If the readings obtained from those Sockets wired into the ring are all the same and equal to the resistance
across (P1 to N2) and (P2 to N1) then the ring final circuit is confirmed.
2.1.6 If the readings are different, this will indicate the presence of a bridge or maybe due to incorrect
connections of the ends of the ring.
2.1.7 If they are connected P1 to N1 and P2 to N2 then the readings will increase or decrease as successive
measurements round the ring are taken.
This Record of Insulation Resistance and Continuity Test form shall be used for the reporting on the condition of three phase points,
Submain Cables, Armoured Cables and Street Lighting Cables.
C. TEST RESULTS
INSULATION RESISTANCE
CONTINUITY
Neutral / OF CPC
Phase / Earth Phase / Neutral Phase / Phase
No. Earth (Ohms)
(Mohms) (Mohms) (Mohms)
Circuit Reference (From – To) (Mohms)
Cable Size and Cable Type RE YE BE NE RN YN BN RY YB BR
10
A. PARTICULARS OF THE INSTALLATION [Please tick (√ ) the relevant boxes and enter details as appropriate]
Project Name
Drawing No./Installation
Address
Block No./Floor
C. TEST RESULTS (Please X where not applicable. Please refer to notes for test procedures)
Circuit No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Lighting
Circuits
Sockets
POLARITY (Radial)
Mark P for
Pass and F for Sockets
Fail. (Ring)
Others
(Please
State)
D. REMARKS
NOTES:
1. Regulation 612.6 of BS7671 : 2008 calls for a polarity test to be carried out to establish that :
1.1 All fuses, circuit breakers and single pole switches are connected in the phase conductor only.
1.2 The centre contact of Edison Screw (ES) lampholders are connected to the phase conductor.
1.3 The polarity of socket outlets, other accessories and points of utilisation (eg luminaires) is correct.
2. The polarity of all circuits must be verified before connection to the supply.
3. Polarity testing must be carried with the supply isolated from the installation.
5. Of all of the above ways, the visual check is usually the easiest and this test is one that is best carried out by the person
installing and terminating cables, rather than by the 'test technicians.
A. PARTICULARS OF THE INSTALLATION [Please tick (√ ) the relevant boxes and enter details as appropriate]
Project Name
Drawing No./Installation
Address
Block No./Floor
D. TEST RESULTS (Please X where not applicable. Please refer to Page 2 for notes and test procedures)
Circuit Number And Phase
Circuit Reference
Mark S for Socket and L for Lighting. Others (specify)
Number of Points
RCCB Rated Tripping Current, I∆n (mA)
TEST TP X X X X X X X X X X X X
RCCB Test Button
(i)
(Mark T for Trip & NT for No Trip)
½ I Trip
(ii)
(Mark T for Trip & NT for No Trip)
I Trip at 00 (ms) (iii)
RCCB
0
Trip I Trip at 180 (ms) (iii)
Time 5I Trip at 00 (ms) (if applicable) (iv)
at 0
5I Trip at 180 (ms) (if applicable) (iv)
RCCB Test Button
(after completion of the above tests) (v)
(Mark T for Trip and NT for No Trip)
RCCB Trip Current Test (Ramp Test) (mA) (vi)
E. COMMENTS BY JKR (IF ANY) AND DEPARTURES FROM SPECIFICATION & REGULATIONS
A. NOTES
1. This Test Form is for RCCB, without time-delayed operation to IEC 61008.
2. This Test Form is to be used for testing a two (2) POLE-RCCBs and NOT applicable for four (4) POLE RCCBs.
4. The RCCB should be tested with the load switch off or the load disconnected from the circuit.