JP1500
STANDARD SPECIFICATIONS
                                                                                                                                       1. ENGINE
                                                                                                                                       Perkins four stroke heavy duty high performance
                                                                                                                                       industrial type diesel engine.
                                                                                                                                       2. ENGINE FILTRATION SYSTEM
                                                                                                                                       • Two Cartridge type dry air filters.
                                                                                                                                       • Cartridge type fuel filter.
                                                                                                                                       • Six Full flow lube oil filters.
                                                                                                                                       All filters have replaceable elements.
                                                                                                                                       3. TROPICAL COOLING RADIATOR
                                                                                                                                       Radiator and cooling fan, complete with safety
                                                                                                                                       guards, designed to cool the engine at high ambient
                                                                                                                                       temperatures (consult your dealer for de-ration factors)
                                                                                                                                       4. EXHAUST SYSTEM
                                                                                                                                       Heavy duty Industrial Exhaust Silencer
                                                                                                                                        Silencer noise reduction level             10 (dB)
                                                                                                                                        Maximum allowable back pressure            5.0 (kPa)
  POWERED BY:
                                                                                                                                       5. CIRCUIT BREAKER TYPE
                                                                                                                                       ABB 3 pole ACB (supplied disconnected and without
                                                                                                                                       cables)*. (4 pole is optional)
Generating Set pictured may include optional accessories                                                                                                                                          (contd.)
GENERATING SET MODEL (JP1500)                                                                                                          ALTERNATOR DATA
Output Ratings                                             Prime                                        Standby                        Make                         Leroy Somer
380-415 V, 3 ph, 50 Hz, 1500 rpm                           1500 KVA                                     1650 KVA                       Model                          LSA50.2L8
                                                           1200 KW                                      1320 KW                        No. of bearings                     1
                                                                                                       Ratings at 0.8 Power Factor     Insulation class                    H
ENGINE / TECHNICAL DATA                                                                                                                Total Harmonic Content           <3.5%
Engine Make                                                                            Perkins                                         Wires                               6
Engine Model                                                                      4012 - 46TAG2A                                       Ingress Protection                IP23
Governing Type                                                                          Digital                                        Excitation System                 AREP
Number of Cylinders                                                                       12                                           Winding Pitch                  2/3 (n° 6S)
Cylinder Arrangement                                                                60° Vee form                                       AVR Model                         R450
Bore and Stroke mm                                                                    160 x 190                                        Overspeed                      2250 mn-1
Displacement / Cubic Capacity litres                                                   45.842                                          Voltage Regulation (steady)      ± 0.5%
Induction System                                                      Turbocharged and air to air charge cooled                        Short Circuit Capacity      300% (3 In):10s
Cycle                                                                                  4 stroke                                        PMG Excitation System Available as Optional.
Combustion System                                                                  Direct Injection
Compression Ratio                                                                       13.6:1                                       CONTROL PANEL
Rotation                                                              Anti-clockwise, viewed from flywheel end                        Make                                          Deep Sea
Cooling System                                                                     Water - cooled                                    Model                                         DSE7320
Frequency and Engine Speed                                                       50Hz & 1500rpm
                                                                         Prime                      Standby                          DSE7320 is an Auto Mains (Utility) Failure
Gross Engine Power kW (hp)                                            1331 (1785)                  1459 (1957)                       Control Module. It is operated via the START,
                                                                                                                                     STOP, AUTO and MANUAL soft touch membrane
Fuel Consumption @ 50% load L/hr                                          162                           -                            buttons on the front panel. DSE7320 can be
                   @ 75% load L/hr                                        237                           -                            controlled remotely using either a GSM Modem,
                   @ 100% load L/hr                                       301                         335                            Ethernet via DSE860/865 or via RS485.
Total Lubrication System Capacity litres                                  177                         177                            Protection:
Total Coolant Capacity litres                                             210                         210                            • Fail to start
Boost Pressure Ratio                                                       3.1                         3.4                           • Low oil pressure
Exhaust Temperature: °C                                                   455                         455                            • High engine temperature
Radiator Cooling Air Flow (Min): m3/sec                                   32.4                        32.4                           • U/O Voltage shutdown
Combustion Air Flow: m3/min                                               120                         128                            • U/O Frequency shutdown
Exhaust Gas Flow: m3/min                                                  320                         320                            • Underspeed, Overspeed
Fuel Tank Capacity: litres                                                                                                           • Loss of engine speed detection
                                                                          N/A                         N/A
                                                                                                                                     • High/Low battery voltage
                                                                                                                                     • kW overload
                                                                                                                                     • Unbalanced load
DIMENSIONS AND WEIGHT                                                                                                                • Low fuel alarm (if fitted)
Length cm                                     Width cm                Height cm                   Weight* kg (wet)                   • Battery charger failure (if fitted)
     530                                        220                     240                               10550                                       (Please refer to DSE7320 brochure for more details)
* For skid mounted genset without enclosure                                                 wet weight = with lube oil and coolant    AN INSPIRED DESIGN TO MEET YOUR NEEDS
                                                                                                                                                       JP1500
                                                                                                                                      AN INSPIRED DESIGN TO MEET YOUR NEEDS
                                                                                                                                            STANDARD SPECIFICATIONS
                                                                                                                                      6. FUEL SYSTEM
                                                                                                                                      On Generating Sets up to 700 KVA, the baseframe
                                                                                                                                      design is incorporated with an integral fuel tank with
                                                                                                                                      a capacity of approx. 8 hours running at Full Load.
                                                                                                                                      The tank is supplied complete with fill cap breather,
                                                                                                                                      fuel feed and return lines to the Engine and drain
                                                                                                                                      plug.
                                                                                                                                      7. ALTERNATOR
                                                                                                                                      7.1 INSULATION SYSTEM
                                                                                                                                      • The insulation system is Class H.
                                                                                                                                      • All windings are impregnated in either a triple dip
                                                                                                                                      thermosetting liquid, oil and acid resisting polyester
                                                                                                                                      varnish or vacuum pressure impregnated with a
                                                                                                                                      special polyester resin.
                                                                                                                                      • Heavy coat of antitracking varnish additional
                                                                                                                                      protection against moisture or condensation.
                                                                                                                                      7.2 AUTOMATIC VOLTAGE REGULATOR (AVR)
                                                                                                                                      The fully sealed Automatic Voltage Regulator
                                                                                                                                      maintains the Voltage Regulation at ±0.5%. Nominal
                                                                                                                                      adjustment by means of a trim pot incorporated on
                                                                                                                                      the AVR.
                                                                                                                                      7.3 MOTOR STARTING
                                                                           Generating Set pictured may include optional accessories   An overload capacity equivalent to 300% of the Full
                                                                                                                                      Load impedance at zero Power Factor can be
                                                                                                                                      sustained for 10 seconds.
RATINGS DEFINITION
                                                                                                                                      8. MOUNTING ARRANGEMENT
Prime Power                                                                                                                           8.1 BASE FRAME
These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of                                  The complete Generating Set is mounted as a whole
commercially purchased power. 10% overload power is available for 1 hour in 12 hours continuous                                       on a heavy duty fabricated steel Baseframe.
operation.
                                                                                                                                      8.2 COUPLING
Standby Power                                                                                                                         The Engine and Alternator are directly coupled by
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a                           means of an SAE flange. The Engine flywheel is
utility power failure. No overload is permitted on these ratings.                                                                     flexibly coupled to the Alternator rotor.
                                                                                                                                      8.3 ANTI-VIBRATION MOUNTING PADS
STANDARD REFERENCE CONDITIONS                                                                                                         Anti-Vibration pads are affixed between the Engine /
                                                                                                                                      Alternator feet and the Baseframe thus ensuring
Output ratings are presented at 25°C air inlet temperature, barometric pressure 100 kPa, relative humidity                            complete vibration isolation of the rotating assembly.
30%. This generating set is designed to operate at high ambient temperatures (up to 55°C), humidity (up to
99%) and higher altitudes. De-ration may apply, please consult your dealer for specific site ratings.                                  8.4 SAFETY GUARDS
                                                                                                                                      The Fan & Fan Drive along with the Battery Charging
Some of the specifications are not standard on all Genset models.                                                                      Alternator are Safety Guard protected for personnel
                                                                                                                                      protection.
AVAILABLE OPTIONS & ACCESSORIES
                                                                                                                                      9. FACTORY TESTS
We offer a range of optional features and accessories to tailor our generating sets to meet your power needs.                         • The Generating set is load tested before dispatch
                                                                                                                                      • All protective devices control functions and site
OPTIONS                                                                                           ACCESSORIES                         load conditions are simulated. The generator and it’s
• A variety of generating set control and synchronizing panels                                    • Genuine spare parts               systems are checked before dispatch.
• Additional protection alarms and shutdowns                                                      • Load banks
                                                                                                                                      10. EQUIPMENT FINISHING
• Water fuel seperator                                                                            • Auxiliary fuel tanks              All mild steel components are fully degreased and
• Water jacket heater                                                                             • Manual & automatic transfer       painted with powder coated paint to ensure
                                                                                                                                      maximum scuff resistance and durability.
• Battery charger                                                                                   switches
                                                                                                                                      11. DOCUMENTATIONS
                                                                                                                                      Operation & Maintenance manual, Circuit wiring
                                                                                                                                      diagrams and Commissioning / Fault Finding instruction
                                                                                                                                      leaflets are accompanied with the Generator.
       Distributed and Serviced by:
                                                                                                                                      12. QUALITY STANDARDS
                                                                                                                                      The equipment meets the following standards:
                                                                                                                                      BS4999, BS5000, BS5514 IEC 60034, VDE0530,
                                                                                                                                      NEMA MG 1.22 and ISO 8528.
                                                                                                                                      13. WARRANTY
For further information on all of the standard and optional features accompanying this product please
                                                                                                                                      All of the Generating Sets are covered under a
contact your local dealer or visit www.taklairaq.com                                                                                  warranty policy for a period of 12 months. Warranty
                                                                                                                                      of the equipment is in line with manufacturers
                                                                                                                                      warranty terms & conditions.
                                                                                                                                      (check warranty statement for more details, as it may vary for different countries)
                     JET Generators are assembled            All information in this document is substantially correct
                    in facilities certified to ISO 9001        at time of printing and may be altered subsequently.
                                                                                                                                      In line with continuous product development, we reserve the
 ISO 9001: 2008
                                                                                                                                      right to change specifications without notice.
    FM 56710
                                                                                                                         2023