USER MANUAL FOR VATS FLOW METERS
Technical Specifications
Technical Specifications
FLUID MONITOR A/J 210
Function
Rate cum totalizer & batching optional
Supply Voltage
230 VAC + 10%
Meter Size
80mm dia X 100mm deep for field mounting
72 mm X 72 mm X 110 mm for panel mounting
Display
Standard
Optional
2 line 8 digit alpha-numeric LCD
Flow rate range
0.5 to 5 m/sec
Accuracy
+1% of full scale
Input Voltage
5-12 VDC
Output Signal
Square wave of 5 to 12 Volt amplitude
15 17.5 Hz/m/sec
Cable length
3 meters
Protection rating
IP 67
Material of construction
Body
Paddle
Pin
Oring
PP
PVDF
Metal
Viton
PVDF
PVDF
Metal
Viton
Wiring connections:
Red wire: Supply 5 12 VDC
Black wire: Output signal TTL
Shield wire: Common
Note: Sensor has been reverse
polarity protected.
Signal Input
TTL from JT 121
Calibration
Using front panel membrane keys
Output
Note: For lines above 100 NB SS
weld ON nozzle is provided with
the flow meter. The nozzle has a
small saddle piece to ensure no
mistake is made during welding to
the pipe line.
5A pot.free@230VAC
LENGTH
FLOW SENSOR JT 121 & FITTING
1
Fitting NB 15 25
40
50
65
80
100
VATS
METERS
GUIDE
LINES
Length
mmFLOW
250 175
235 INSTALLATION
300
350
450
500
MOC
-----ABS---------------------SS Tee
For fittings up to 100 NB with flow straighteners:
-----------------All flow-straightened fittings require a straight run of 10 D before and 5 D after them
3
for good results.
sensor
cap
Flow Direction
fitting
10 D
10 D
5D
5D
10 D
Incase of larger line sizes without the flow straighteners, the following straight
lengths must be provided
Sensor/Indicator mounting guidelines:
10 D
5D
15 D
5D
Straight pipe
20 D
The unique paddle wheel design of the sensor permits it to be mounted in any plane..i.e.
the unit can be installed in vertical as well as horizontal piping. Insert the blind plug supplied
along with the meter in the fitting and flush the line with water. Depressurize the line, remove
the blind plug and insert the flow sensor gently. Ensure that the sensor O-rings are in place and
slightly greased. Push the sensor in till the threaded cap touches the T fitting. Before tightening
the cap ensure the direction of the sensor is proper. Incase of panel mounted units the arrow on
the sensor should point in the direction of flow. In case of field mounted units the sensor must
be mounted such that the display becomes parallel to the pipe line. Start tightening the cap by
hand. For ensuring the sensor in correct position a male/female locking arrangement has been
provided in the sensor and the fitting respectively. While tightening the sensor cap, by a slight
angular motion, one can get an idea of proper locking properly locked sensor/fitting will not have
any angular motion.
Reducer
5D
50 D
DO NOT USE PIPE WRINCHES OR ANY OTHER TOOLS FOR TIGHTENING THE CAP
5D
90 deg. bend
Follow the ARROW marking on the Fitting while installing
Valve
Line Size Selection Chart [For Water]
25 D
5D
40 D
2 elbows in same plane
5D
5
Programming VATS TOTALISER
A/J210T:
2 elbows in different plane
GUIDE LINES FOR USE IN REVERSE OSMOSIS SYSTEMS:
Reject flow meter: The disturbances created in the flow/velocity profile are
maximum in this case. It is best recommended to provide an elbow immediately
after the reject control valve followed by the 10 D straight run. In case the outlet
is likely to be opened to atmosphere immediately after the sensor, mount the sensor
in a vertical plane with entry from the bottom.
Rej.Valve
Rej.Valve
Pipe Size (NB)
15
3
Min. Flow (m / hr) 0.2
Max. Flow (m 3 / hr) 2.1
25
0.8
8.0
40
1.9
19
50
3.5
35
65
5.8
58
The VATS Flowgauge is supplied along with its flow sensor and
80
7.5
75
100
14
140
installation fitting of the suitable line size duly calibrated.
How to view all the settings:
Press
key for 1 second, the unit displays
VIEW
SETTINGS
The display scrolls through all the settings of scale factor, exponent and finally
coming back to
VATS
TOTALISR
And then to the rate and totalised readings.
HOW TO SET THE TOTALIZER VIEW MODE
Press
key for 5 seconds, till the unit will display:
and
keys to set the display as
PASSWORD
0000012
Press
RESET
TOTAL?_
Key, the unit will display
keys to set the display as
key ,the display automatically rolls over to
key, the unit displays the scale factor
SETSCALE
0.-----Press
and
Press
VATS
TOTALISR
And then to the rate and totalised readings.
Note : Incase the
key is pressed and a wrong password is entered, the
8
unit displays
PASSWORD
ERROR
key for 5 seconds, the unit will display:
PASSWORD
0000000
Press the
and
Press
TOTAL
CLEARED
Else Press
For calibration/re-calibration of the instrument the previously programmed
scale factor can be increased in proportion to the difference in the reading
between the actual flow and the displayed reading.
PASSWORD
0000031
key, the unit displays
To reset the earlier totalised reading press
old settings.
Incase the
key is pressed and no password is entered for 10 seconds the
display automatically rolls to the
VATS
TOTALIZER
And then to the rate and totalised readings as per the old settings.
Press
PASSWORD
0000000
Press the
The display then automatically rolls to the
VATS
TOTALISR
And then to the rate and totalised readings as per the
keys to increase the scale factor if required.
key, the unit displays the exponent.
EXPONENT
10 e-x
The value of x can be changed from 3 to +3 by pressing the
Press
key, the unit displays
VATS
TOTALIZER
And then to the rate and totalised readings.
VATS BATCHER A050
key.
The vats batcher consists of the following three parts i.e.
1.The flow sensor 2. The electronic module 3. Installation fitting
Flow sensor: Refer JT 121 data sheet
Electronic module: The module basically consists of an LED bar graph of 10 LEDs, which
indicates the % of the output (set), completed. Once the desired output is attained the
unit shows all the ten LEDs ON and the relay inside the unit gets energized for 2
seconds. The relay output is fed to the auto valve actuator to initiate the regeneration
process. Since the unit is used to initiate regeneration process, the unit must be set for
AUTO reset mode i.e. the batcher would automatically reset after giving a 2 second
pulse. The four LEDs below the bar graph are used in the setting of the batch count.
Procedure:
Press
SET
key. The
mode press the
ENT
LED bar graph
Key , the
SET
100
SET
LED will start blinking. To be able to enter the program
key till the first FIVE LEDs of the BAR GRAPH light up. Press
LED would start glowing, press the
hundreds digit of the output in m3. Press
Membrane key pad
Technical Specifications:
Spply: 230 VAC
Display: % output with a 10 LED BAR GRAPH
Programming: Using the front panel membrane key pad.
Output: Potential free contact @ 5 A at 230 VAC Auto or Manually resettable.
Input: From VATS flow sensor
Least Count: 1 m3 (unless specified otherwise)
Protection: IP 65
Gland: PG7
Maximum Set point: 999 m3 (unless specified otherwise)
Relay output Pole/NO
Rear wiring connection
sensor
Power Supply
Fitting:
For easy installation a TEE type fitting is supplied with the batcher of the suitable pipe
size. This fitting has BUILT IN FLOW STRAIGHTENERS. These ensure that long
upstream/down stream straight lengths are not required. Standard fittings are available
with BS 10 table D drilling flanges.
HOW TO SET THE
OUTPUT/BATCH COUNT:
10%------------100%
10
SET
100
SET
SET
10
SET
1
SET
ENT
SET
Press
SET
ENT
key, the
10
key to set the
LED will start glowing.
Key to set the tens digit of the output in m3. Press
LED will start Glowing. Press
press
ENT
SET
SET
ENT
key, the
key to set the units digit of the output in m3.
key. All the LEDs will switch off except the SET LED which will stop
blinking indicating that the BATCHER is in service.
NOTE:
If the batcher is to be set in an auto-reset mode then all Leds must be ON, where as if only 50% of
LEDs are kept ON then the unit would operate on a MANUAL RESET MODE .i.e. once the desired
quantity of the liquid passes through the meter, the relay would get energised.
Press ENT key to RESET the Relay. In an Auto reset mode the relay would get reset after 2 seconds.
For setting any digit, the SET key is pressed such that the number of LEDs that glow in the bar graph 0
to 9 correspond to the value of the digit. During normal service the Last LED of the Bar graph would
keep blinking whenever flow takes place. The % completion of the output would get displayed in the
BAR GRAPH.
For setting the relay mode auto/manual, press set key and enter a
password of nine. Press enter key. The bar graph will either show all
LEDs ON(auto reset) or 5 LEDs ON (manual reset).Press set key to
toggle to the required setting. Press enter key. Relay MODE is set.
Programing VATS BATCHER A / J 210 B :
The VATS Flowgauge is supplied along with its flow sensor and installation
fitting of the suitable line size duly calibrated.
Press
How to view all the settings:
Press
key for 1 second, the unit displays
VIEW
SETTINGS
The display scrolls through all the settings of scale factor, relay and reset
Modes and finally coming back to
VATS
BATCHER
And then to the rate and totalised readings.
HOW TO SET THE BATCHER VIEW MODE
Press
key for 5 seconds, till the unit will display:
and
RESET
TOTAL?_
To reset the earlier totalised reading press
TOTAL
CLEARED
Else Press
key, the unit will display
key, the display automatically rolls over to
VATS
BATCHER
And then to the rate and totalised readings.
Incase the
displays
keys to set the display as
key is pressed and a wrong password is entered, the unit
PASSWORD
ERROR! _
The display then automatically rolls to the
PASSWORD
0000012
Press
key, the unit will display
Note:
PASSWORD
0000000
Press the
DISPLAY
BATCH?_
VATS
BATCHER
key, the unit displays
MANUAL
RESET?_
And then to the rate and totalised readings as per the old settings.
To reset the relay automatically once the batch count is achieved
press
key
Incase the
key is pressed and no password is entered for 10 seconds the
display automatically rolls to the
The unit displays
VATS
BATCHER
AUTO
RESET?
Press
key, the unit will display
And then to the rate and totalizer readings as per the old setting
DISPLAY
TOLAL?_
For viewing only the cumulative flow of the batch press
displays
SETTING THE BATCH
key, the unit
Press
key, the unit will display
Press the
PASSWORD
0000000
Press the
and
Press
PASSWORD
0000011
Press
key, the unit displays batch setting
Press
key, the unit displays batch count
i.e. the total number of times the relay was energised.
BAT.CNT.
0000000
Press
key, the unit asks whether the batch count should be cleared
RESET
BAT.CNT.
key the unit displays
key the display automatically rolls to the
VATS
BATCHER
And then to the rate and totalised readings as per the
old settings.
For calibration/re-calibration of the instrument the previously programmed
scale factor can be increased in proportion to the difference in the reading
between the actual flow and the displayed reading.
Press
key for 5 seconds, the unit will display:
PASSWORD
0000000
key, the unit displays the scale factor
SETSCALE
0.------
SETRELAY
000000.0
Each of the above digits can be changed to set the batch quantity/value
at which the relay is to be energised by using the
and
keys.
BAT.CNT.
CLEARED
else press
keys to set the display as
PASSWORD
0000031
keys to set the display as
For resetting the count to zero press
and
Press
and
keys to increase the scale factor if required.
Press
key, the unit displays the exponent.
EXPONENT
10 e-x
The value of x can be changed from 3 to +3 by pressing the
key.
Press
key, the unit displays
VATS
BATCHER
And then to the rate and totalised readings .
RESET
TOTAL?_
To reset the earlier totalised reading press
Programing VATS PULSER ( A /J210 )
PULSER MODE
key, the unit will display
TOTAL
CLEARED
else Press
key, the unit displays
VATS
PULSER
And then to the rate and totalised readings.
Note:
The VATS Flowgauge is supplied along with its flow sensor and installation
fitting of the suitable line size duly calibrated.
How to view all the settings:
Press
key for 1 second, the unit displays
VIEW
SETTINGS
The display scrolls through all the settings of scale factor, relay and reset
Modes and finally coming back to
And then to the rate and totalised readings.
HOW TO SET VIEW MODE
key for 5 seconds, the unit will display:
PASSWORD
0000000
Press the
and
And then to the rate and totalised readings as per the old settings.
VATS
PULSER
And then to the rate and totalizer readings as per the old setting
SETTING THE BATCH
keys to set the display as
PASSWORD
0000012
Press
The display then automatically rolls to the
VATS
PULSER
Incase the
key is pressed and no password is entered for 10 seconds the
display automatically rolls to the
VATS
PULSER
Press
Incase the
key is pressed and a wrong password is entered, the unit
displays
PASSWORD
ERROR! _
key, the unit displays
Press
key, the unit will display
PASSWORD
0000000
Press the
and
keys to set the display as
PASSWORD
0000011
Press
key, the unit displays batch setting
Press the
Each of the above digits can be changed to set the batch quantity/value
at which the relay is to be give pulse by using the
and
keys.
After every programmed Qty of liquid is passed through , the unit will give a
pulse out to the Dosing / Metering pump.
Press
key, the unit displays batch count
i.e. the total number of times the relay was energised.
BAT.CNT.
0000000
Press
key, the unit asks whether the batch count should be cleared
RESET
BAT.CNT.
For resetting the count to zero press
BAT.CNT.
CLEARED
else press
keys to set the display as
PASSWORD
0000031
Press
SETRELAY
000.0000
and
key, the unit displays the scale factor
SETSCALE
0.-----Press
and
Press
keys to increase the scale factor if required.
key, the unit displays the exponent.
EXPONENT
10 e-x
The value of x can be changed from 3 to +3 by pressing the
key.
Press
key, the unit displays
VATS
PULSER
And then to the rate and totalised readings .
key the unit displays
key the display automatically rolls to the
VATS
PULSER
And then to the rate and totalised readings as per the old settings.
For calibration/re-calibration of the instrument the previously programmed
scale factor can be increased in proportion to the difference in the reading
between the actual flow and the displayed reading.
Press
key for 5 seconds, the unit will display:
PASSWORD
0000000
Programming VATS RATE SWITCH ( A/J210) :
And then to the rate and totalised readings.
Note:
The VATS Flow gauge is supplied along with its flow sensor and installation
fitting of the suitable line size duly calibrated.
How to view all the settings:
Press
key for 1 second, the unit displays
Incase the
displays
key is pressed and a wrong password is entered, the unit
PASSWORD
ERROR! _
The display then automatically rolls to the
VIEW
SETTINGS
VATS
RATE SW.
And
then toback
the rate
The display scrolls through all the settings of scale factor, relay and reset modes and finally
coming
to and totalised readings as per the old settings.
VATS
RATE SW.
Incase the
key is pressed and no password is entered for 10 seconds the
display automatically rolls to the
And then to the rate and totalised readings.
VATS
RATE SW.
HOW TO RESET THE TOTALISER READING
Press
key for 5 seconds, the unit will display:
PASSWORD
0000000
Press the
and
keys to set the display as
key, the unit displays the scale factor
To reset the earlier totalised reading press
key, the unit will display
TOTAL
CLEARED
key, the display automatically rolls over to
VATS
RATE SW.
and
keys to set the display as
PASSWORD
0000011
Press
TOTAL?_
key, the unit will display
PASSWORD
0000000
Press the
RESET
Press
SETTING THE RELAY
Press
PASSWORD
0000012
Press
And then to the rate and totalised readings as per the old settings.
key, the unit displays flow setting
SETRATE
00000.00
Each of the above digits can be changed to set the low flow rate
value below which the relay will remain energised by using the
and
keys.
Press
key, the unit asks for the hysterysis .
HYSTERIS
And then to the rate and totalised readings.
--%
The hysterysis value can be set from 0 to 10% by pressing the
Press
key.
key, the display automatically rolls to the
VATS
RATE SW.
And then to the rate and totalised readings as per the old settings.
For calibration/re-calibration of the instrument the previously programmed
scale factor can be increased in proportion to the difference in the reading
between the actual flow and the displayed reading.
Press
key for 5 seconds, the unit will display:
PASSWORD
0000000
Press the
and
TROUBLE SHOOTING OF VATS FLOW METERS:
During commissioning:
keys to set the display as
Trouble
Display remains zero
even when actual flow
is there
PASSWORD
0000031
Press
Probable cause
Flow less than the minimum
sensing value.
key, the unit displays the scale factor
SETSCALE
0.-----press
and
Press
key, the unit displays the exponent.
Sensor not inserted in the
correct plane.
keys to increase the scale factor if required.
Paddle not moving freely
EXPONENT
10 e-x
The value of x can be changed from 3 to +3 by pressing the
Press
Wrong sensor wiring.
(mainly applicable for panel
mounted meters or field
mounted units where sensor
wire is extended.)
key.
key, the unit displays
VATS
RATE SW.
Meter and sensor are not
matching.( applicable for
panel mounted meters)
Reading getting
Adequate straight run is not
Action required
Check if any downstream
valve is closed. Open valve.
Remove the sensor from the
fitting and check change in
reading by physically rotating
the paddle. If meter shows
reading check the actual flow.
Change the fitting if the
normal flow is lower than the
minimum sensing velocity.
Ensure that the arrow on the
sensor is in direction of flow.
Remove the sensor clean the
paddle/pin and ensure free
movement of paddle
Connect the sensor wires as
per wiring connection details
on the meter.
Ensure that the meters
connected
to
corresponding sensor
fitting only.
Provide straight run as
are
its
and
per
displayed but not
correct.
provided upstream
downstream of sensor.
PS: Presence of a pressure
reducing valve very close
(upstream) of the sensor can
result in error
Scale factor disturbed
No display
No supply
guidelines. OR adjust the
scale factor to match the
actual flow. Provide a bend
between the valve and the
sensor. Try use of fittings with
strengtheners
whenever
possible.
Check factor. Correct factor
as mentioned on meter/sensor.
Checks input supply and
make proper connections.
During normal service:
Probable cause
Action required
Display remains zero
even when actual flow
is there
Flow less than the minimum
sensing value.
Check if any downstream
valve is closed. Open valve.
Remove the sensor from the
fitting and check change in
reading by physically rotating
the paddle. If meter shows
reading check the actual flow.
Change the fitting if the
normal flow is lower than the
minimum sensing velocity.
Paddle not moving
Remove the sensor clean the
paddle/pin and ensure free
movement of paddle
Paddle not moving freely
Remove the sensor clean the
paddle/pin and ensure free
movement of paddle
No display
General
17
Date:
Name of Client/Dealer:
165
Trouble
Reading getting
displayed but not
correct.
VATS FLOW METER
Check Sheet
Scale factor disturbed
Check factor. Correct factor
as mentioned on meter sensor.
No supply
Checks input supply and
make proper connections.
Micro-Processor hanged
Switch off supply for 1
minute and then switch ON
supply.
Serial Number:
No. of months in use:
Model: Ultraflo Rate Indicator(field mounted) A110
[ ]
Fluid monitor LCD indicator cum totaliser A210
[ ] / J210 [ ]
LED bargraph batcher model A050 [ ]
Flow transmitter model J510 [ ]
OR
Model: Rate Indicator (field Mounted)
IP 110 [ ]
Rate cum electromechanical totaliser IP 210 [ ]
Rate indicator panel mounted JT110 [ ] / JT 111 [ ]
Rate cum total panel JT 210 [ ]
Installation fitting Type:
Polypropylene wafer fitting [ ] , Plastic Tee fitting [ ] ,
Stainless steel weld on fitting.[ ] , Flow straightened pipe fitting [ ].
Installation/Location: Outdoor [ ] /Indoor [ ]
Application: Deminraliser [ ], RO [ ], Blending- Mineral water [ ]
Other specify __________
Line pressure: ________ kg/cm2 max.
Types of Problems
A)
B)
C)
D)
E)
No display [ ]
Reading remains Zero [ ]
Fluctuating reading [ ]
steady but erroneous reading [ ]
Breakage [ ]
F ) Gradual fading of display [ ]
G ) meter shows reading even at no flow (applicable for IP/JT series only)
H ) any other- specify [ ]
A ) No Display
19likely cause for the sameSpecify the component broken and the
F)
Gradual fading of display:
The unit is exposed to direct sunlight. Y/N
Check for power supply using multi meter/test lamp [ ]
18 proper neutral or adequate voltage)
(Use of tester does not confirm
Water deposition inside the meter housing Y/N
For Ultraflo, remove the front cover and replace the battery by an Alkaline
9VBattery the unit started displaying flow Y/N
The back light gets on (for A110/A210/J210/J510) Y/N
The last led of the BAR Graph ( for A050) blinks when the paddle is rotated Y/N
B ) Reading remains zero
Checked actual flow and found it higher than the minimum capacity of the meter
Y/N
Removed the flow sensor from the fitting and checked free rotation of paddle
wheel Y/N
Meter showed reading when paddle rotated by hand Y/N
For panel mounted meters checked the sensor wiring to the terminal strip. All the
three wires were connected to the respective terminals Y/N
(If the same site has more than one panel meters) Connected another sensor of the
working unit to the meter. Meter shows reading Y/N
The last led of the BAR Graph ( for A050) blinks when the paddle is rotated Y/N
Checked scale factor programmed and found it to be same as written on the
meter Y/N
If straight run inadequate adjust scale factor to match the actual flow. Readings
found OK Y/N
E ) Breakage:
G)
Meter shows reading even at no flow (applicable for IP and JT series only):
There is an induction motor/coil very close to meter/sensor Y/N
For JT series.
The T-50/Cal key is in released position Y/N
The extra sensor cable is kept looped near the
Sensor Y/N
The plant piping was properly grounded. Y/N
Sensor removed from fitting. Meter reading
became zero Y/N
Disconnect the sensor wires from meter. Reading
becomes zero Y/N
H ) Any other: Specify_____
C ) Fluctuating reading:
Is the sensor located just after any valve/reducer? Y/N
Removed the sensor found the paddle moving freely Y/N
Did not find any air bubbles in the water line Y/N
(For panel meters) checked the sensor wiring and tightened all the three wires to
the respective terminals of the strip. Y/N
Is the sensor wiring is extended. Y/N
The wiring is properly extended and there is no shorting of wires Y/N
D ) Steady but erroneous reading:
Mention the flow rate indicated w.r.t. actual ____________.
The Serial number of the meter, sensor and fitting were matching Y/N
Line size mentioned on the indicator same as the fitting Y/N
Scale factor of the meter same as that mentioned on the sticker Y/N
There is an adequate straight run on the inlet/ outlet of the sensor ( refer guidelines
enclosed) Y/N
Checklist filled by:
Company name:
Manufacturer & Marketed by:
VATTURKAR INDUSTRIAL
B14/3 , Bandhan Society ,
Kothrud, Pune- 29
Tel-091-020-25430897, Telfax- 25432157.
E-mail-vatsmeter@vsnl.net
WEB- www.vatsmeter.com
20
TEST REPORT
Vatturkar Industrial
B 14/3 Bandhan Society,
Kothrud Pune-29
Standard
Product:
Setting
Model:
S.No:
Size:
This is to certify that the products mentioned above have been tested and calibrated
at our works and have been found working satisfactorily as per the technical
specifications of the product.
GUARANTEE CERTIFICATE
We certify that the instrument mentioned above has been tested by us and is
guaranteed for a period of 12 months from the date of dispatch.
We undertake to make good by replacement or repair defects arising due to
Faulty design, material or workmanship within the above mentioned period.
Provided that the part in respect to which the complaint is made, is sent at the
purchaser`s expense.
The warrantee is valid subject to :
The meter or part there of not being subjecty to alteration, accident abuse
or misuse
The installation having been done as per guide lines in the manual.
Client:
Date of dispatch:
for VATTURKAR INDUSTRIAL
Authorised Signatory