IgnitionTimingAdjust
SMCS1550025
Usethefollowingproceduretoadjustthebasetimingoftheengine:
Note:Datafromafuelanalysisisrequiredforthisprocedure.
1.ConnecttheCaterpillarElectronicTechnician(ET)totheengine.
2.Verifythatthevaluesofthe"FirstDesiredTiming"and"SecondDesiredtiming"parametersare
correctaccordingtotherecommendedtimingintheEnginePerformance,"FuelUsageGuide".Enter
thecorrectvaluesiftheexistingvaluesareincorrect.
RefertoSystemsOperation,"ElectronicControlSystemParameters"foradditionalinformationonthe
"DesiredTiming"parameters.
3.Verifythattheinputfortheselectionofthebasetimingisappropriateforthetypeofgasthatisused.
IfterminalJ120isnotconnectedtoground,theElectronicControlModule(ECM)willusethe
valueofthe"FirstDesiredTiming"parameterasthebasetiming.
IfterminalJ120isconnectedtoground,theECMwillusethevalueofthe"SecondDesired
Timing"parameterasthebasetiming.
Iftheinputisnotcorrect,troubleshootthecircuitfortheinput.Refertotheelectricalschematicforthe
engine.
4.Starttheengine.Runtheengineatratedspeedandload.
5.UseCatETtoviewthe"ActualEngineIgnitionTiming"statusparameter.Thisparameterisin
"GeneralSystemParameters".Verifythattheactualtimingisapproximatelyequaltothedesired
timing.
Note:Theactualtimingmayvaryaccordingtotheengineload,speed,andthedetonationlevel.