PROTECTION
Type VTT 11, 12
                                                                                            Definite Time Delay Relay
                                                VTT is a static time delay relay which is particularly suitable for applications
                                                requiring large number of operations and consistent accuracy with little or
                                                no maintenance over long periods. It is also commonly used in industrial
                                                processes.
                                                Type VTT 11 units have a delayed pick-          operation is maintained between 80% and
                                                up, i.e., timing is started by closing an       115% of rated voltage.
                                                initiating contact and the output relay is
                                                energised at the end of the set time. The       Timing ranges
Features
                                                unit resets when the initiating contact is      Models with the following setting ranges
	  Consistent accuracy                         reopened.                                       (in seconds) - continuously adjustable -
	  Reliability                                                                                 are available:
	  Low burden                                  Type VTT 12 units have a delayed drop-
	  Reduced maintenance                         off, i.e., the output relay is normally         0.05 - 0.5
	  Immunity to transients and surges;          energised. Timing is started by opening         0.10 - 1.0
    withstands 5 kv impulse voltage test        an initiating contact and the output            0.50 - 5.0
 	 Relays with heavy-duty magnetic             relay is deenergised at the end of the set      1.00 - 10.0
    blow-out contacts also available            time. The unit resets when the initiating       2.50 - 25.0
                                                contact is reclosed.
Description                                                                                     Accuracy
A stabilised voltage is applied to a            Technical data                                  Within 5% of setting or 10 milliseconds
resistance/capacitance       circuit.    The                                                    whichever is greater, at nominal voltage
potential developed across the capacitor        Voltage ratings                                 and at an ambient temperature within
is applied to a transistor switching circuit                                                    the range of 10C and 30C.
                                                DC supply
which, in turn, operates an attracted
armature relay when the potential                                                               Within 5% of setting or 25 milliseconds
                                                30, 48, 110 or 220V. Satisfactory
reaches the trigger level.                                                                      whichever is greater for supply voltage
                                                operation is maintained between 70% and
The time delay is varied by altering                                                            variation for 30%. Operating temperature
                                                130% of rated voltage.
the resistance value in the resistance/                                                         range -5C to +50C.
capacitance circuit by a potentiometer          Units for use on 110 or 220V are supplied
calibrated in seconds. A circuit is             with a suitable external resistor.
incorporated to protect the transistors
from damage due to high peak transients         AC supply
in the supply voltage. A diode is also fitted                                                        Customer Benefits
in the circuitry to take care of inadvertent    110, 240 or 415V at 50 Hz. Relays                     	 Accurate and Reliable
connection of supply with reversed              suitable for operation from ac supply                 	 Adjustable time delay
polarity.                                       have a built-in power pack. Satisfactory              	 Heavy duty magnetic blow
                                                                                                         out contacts on request
                                     GRID
                                                                                                                                       1
                                                            Type VTT 11, 12
             Type VTT with cover removed
    Figure 1: Basic circuit diagram for VTT 11 relay
Figure 2: Typical connection diagram for ac VTT 11 relays
                                                                         2
                                                                                               Type VTT 11, 12
                                   Figure 3: Typical connection diagram for dc VTT 11 relays
Contacts
Four pairs of self-reset contacts in any
combination of normally open or normally
closed with a maximum of 2 normally closed
contacts are provided on the output attracted
armature unit of VTT 11 relays. Hand reset
contacts can be provided. For VTT 12 relays
three pairs of selfreset contacts with maximum
of 2 normally closed contacts are available.
Note
Relays with heavy duty magnetic blowout
contacts are also available on request.
Operation indicator
A hand reset mechanical flag operation
indicator can be provided on the output relay.
Insulation
The relay meets the requirements of IS-3231/
IEC 255-5 Series-C-2 kV for 1 minute.
                                                                                                            3
                                                                                         Type VTT 11, 12
Impulse voltage
The relay complies with the requirements of IS-8686/
IEC 255-4, Appendix-E to Class III.
High frequency interference
The relay complies with IS-8686/ IEC 255-22-1,
Appendix-C to Class III.
Case
The VTT 11 and VTT 12 are supplied in 1/2N non-
drawout moulded cases suitable for flush mounting.
Non-drawout cases are finished bright black. Relays
can also be supplied in 1/2 N and 1D drawout cases
on request.
Burdens
(when energised)
               DC                         Burden (W)
               30V                               1.26
             110V                                4.46
             220V                                9.1
               AC                         Burden (VA)
             110V                                2.4
             240V                                2.3
             415V                                2.6
Dimensions and weights
       Relay                                       Maximum overall dimensions                  Approximate
                            Case size             Height mm         Width mm    Depth* mm    gross weight Kg
   VTT11 or VTT12          1/2N Horz.                   124            153         130            1.75
                                                                                                               4
                                                                                                                Type VTT 11, 12
Contact Ratings
          Make and carry continuously               Make and carry for 0.5 second               Break
 AC       1250 VA with maxima of 5A and 660V        7500 VA with maxima of 30A and 660V 1250VA with maxima of 5A and 660V
 DC       1250 W with maxima of 5A and 660V         7500 W with maxima of 30A and 660V          100W (resistive) 50W (inductive)
                                                                                                maxima of 5A and 660V
Information required with order
1. 	Relay type (delay on pick-up or delay on drop-off)
2. 	Timing range
3. 	Voltage rating
4. 	Contact combination
5. 	Case
                                                                   Figure 2 : Case and panel cut-out dimensions for case 1/2N (all dimensions in mm)
                                                                     Figure 3 : Case and panel cut-out dimensions for case 1D (all dimensions in mm)
                                                                                                                                                 5
                                                             19/1, G.S.T. Road,
                                                             Pallavaram Works
                                                             Tel: 91-44-2264 8000
                                                             Fax: 91-44-2264 0040
www.grid.alstom.com
                      Tel.: +44 (0) 1785 250 070
                                                             ALSTOM T&D INDIA LIMITED
                                                             Pallavaram, Chennai - 600 043
                      http://www.alstom.com/contactcentre/
                      ALSTOM T&D Worldwide Contact Centre:
          GRID
                               Alstom logo and any alternative version thereof are trademarks and service marks of Alstom. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in
                               the document are provided for information only. Neither ALSTOM, its officers nor employees accept responsibility for or should be taken as making any representation or warranty (whether express or implied) as to the accuracy or
                               completeness of such data or the achievements of any projected performance criteria where these are indicated. No liability is accepted for any reliance placed upon the information contained in this brochure. Alstom reserves the right to
6
                                                                                                                                                                                                                                                                               Type VTT 11, 12
                               revise or change these data at any time without further notice.