NOVATEUR PUBLICATIONS
International Journal of Research Publications in Engineering and Technology [IJRPET]
                                                                                                   ISSN: 2454-7875
                                                                                       VOLUME 3, ISSUE 6, Jun.-2017
 INVESTIGATION OF FAULT CURRENT LIMITING TRANSFORMER USING
                     VARIABLE REACTANCE
                                              MR. KENDRE SOMNATH M.
                  ME (Power System) Scholar, Department of Electrical Engineering, GHRIET, Pune, India
                                                   PROF. LAKADE C.R.
                       Assistant Professor, Department of Electrical Engineering, GHRIET, Pune, India
ABSTRACT:                                                         beneficial effect of limiting the transformer current
        To demonstrate experimentally the capability              without dissipating energy.
of a reactive variable impedance transformer to limit                      The inductance is reliant on on the geometry of
the fault current and set a secondary voltage is the              the core and the windings. The change in the dispersion
goal of this task. This transformer is capable of                 inductance is effected by the addition of an additional path
changing its leakage reactance using a shift of a mobile          of the flow stream between the core legs. If the 100%
iron core block. It plays threerole that is voltage               inductive differential transformers design, the transformer
transformation, fault current limiting and voltage                will not burn, even after a short circuit in the secondary
regulation. A small test device was developed and                 winding. Design development approaches practically
tested almost these functions. Its features should go             oriented as a transformer for application in which a
ahead and they also explained.                                    variable current such as neon signs, gas discharge lamps,
KEYWORDS: Transformer, Faults, Variable Reactance,                and laboratory test instruments, etc. In addition, the
Current Limiting Transformer etc.                                 control arc welding sets, the average power control to
                                                                  motor conductors extension of electricity generating
I. INTRODUCTION:                                                  systems and isolated connection in electrical
           Our planet and our society evolve us, in many          systemssource an increase in fault current. Although many
cases, evolving ever-changing environment and                     types of fault current limiters have been proposed and
illustrations, we are forced to advance. All this comes out       some are ongoing, most only work for the current limit and
to fulfill the emergence of new desires emerging from this        the high cost and space required for their installation are
variant, global and regional trends and new technologies.         difficult problems. Moreover, a certain quantity of
What was able to come out dated as a rush, recently was           connection, causing voltage variations in the system
contemporary. Development will change quickly need to             standard voltage distribution system power quality.
recognize manufacturers to respond with new, advanced                      A solution in the middle of the supply line feed
products. Also when applied to product care, this is              distribution system is the construction of a step voltage
mature, transformer etc. In this document, the influence on       regulator (SVR), which nevertheless requires an additional
the major markets understands that the global trend is            cost, which does not limit the accuracy of the fault current.
acknowledged in the era of the transformer, and currently         These problems will be avoided by the introduction of a
includes innovative forerunner dry transformers and               large development and distributed generation. We
distribution, including liquid filled.                            propose the leakage resistance of the transformer, which
           Conventionally, the transformer in power system        can be controlled by moving the core block. A capacitor
was passive system, become active elements of the                 connected in parallel, consisting mainly of voltage
network to interact vigorously in the future, network             transformation and has three functions to limit the fault
capabilities, to ensure reliability and efficiency. In the new    current, voltage transformation, and voltage regulation.
design specification, taking into account in the design           Therefore, the additional fault current limit, the consumer
transformer has been improved in order to strengthen              power system and the transformer can be replaced by a
regulation and stability. Current control, plays an essential     transform substation to receive and SVR. In addition, it is
role in their own industrial units, variable current              used to control the loop current limit fault, the expected
transformer rating. These transformers have been                  power flow. Create a small transformer to try to improve
distributed to the primary and secondary windings. The            the performance and characteristics of the experiment.
primary coil A, B, C is in one half of the core, a, b, c are
positioned at the opposite end of the core. Another               II.LITERATURE SURVEY:
keymodification in the conventional design is a change in                  Junji Kondoh and Itaru Ishii explained the fault
inductance characteristics. Leakage inductance has the            current limiting transformer with variable reactance. They
                                                          33 | P a g e
                                                                                              NOVATEUR PUBLICATIONS
                               International Journal of Research Publications in Engineering and Technology [IJRPET]
                                                                                                         ISSN: 2454-7875
                                                                                           VOLUME 3, ISSUE 6, Jun.-2017
investigated on transformer reactance for fault current        Exciting circuit for the transformer is omitted from Fig.
limiting. Attest experimentally the proficiency of a           1(a).
transformer with variable reactance to restrict the fault
current and to regulate the secondary voltage [1].
          S. Blair and brilliant team investigate the future
basic need to limit the fault current in the United
Kingdom’s electrical system and a part of the technical
implications of this change. It is expected that
approximately 300-400 electrical distribution substations
will be led to limit the fault current, especially in light of
the static evaluation of the alleged violation of the failure
level. A case study on distributed generation (DG) through
a superconducting fault current limiter (SFCL) is exploited
topotential guard and control problems. In particular, it
                                                                     Fig. 1(b) VECTOR DIAGRAM FOR EQUIVALENT CIRCUIT
addresses DG fault ride-through, auto shut-off and the
current input of the adapter may be unacceptable for SFCL
                                                                        The relationship of each voltage vector is shown in
that need recovery period[2].
                                                               Fig.1 (b). Impedance Zs of the transformer and transmitted
          Professor KK. Kulkarni innovation introduced in
                                                               apparent power St are andimpedance angles ϕ and a
the varactor transformer (Variable reactance coil) recently
                                                               power-factor angle θ.
introduced VRT or power supplies. It has an irresistible
contact between primary and secondary. Host belongs to
                                                               B. FAULT CURRENT LIMITATION:
the DC link signal line can be considered the best core
                                                                  A short-circuit in secondary side is considered and it is
saturation transformer is not the voltage control device,
                                                               presumed that V2 drops to zero. In this fault situation, the
however, no one can get secondaryside ampere.[3].
                                                               secondary current I2fc is greater than 10 pu in the case of a
                                                               conventional transformer, whose impedance ZS is set to
III. PRINCIPLE:
                                                               less than 0.1 pu in order to evade large voltage fluctuation
      The principles of the three tasks (voltage
                                                               at the normal situation. On the other hand, I2fc may be set
transformation, limiting fault current and voltage
                                                               below a given level in the case of the transformer with
regulation) and the role of a capacitor connected in
                                                               variable reactance, since its minimum reactance Xsmin can
parallel are designated in this section with an equivalent
                                                               be selected much higher than ZS of a conventional
circuit for this system.
                                                               transformer because of the control function mentioned.
  A. EQUIVALENT CIRCUIT:
                                                                 C. ROLE OF PARALLEL-CONNECTED CAPACITOR:
                                                                    Since the current flow to a power system is delayed, a
                                                                secondary V2 voltage is lower than V1R in general.
                                                                However, this can be changed to lead by connecting a
                                                                capacitor with an appropriate capacity. Under this
                                                                condition, V2 may be higher or lower than V1R.
                                                                IV.DESIGN METHODOLOGY:
                                                                         A small trial apparatus was manufactured in order
                                                                to demonstrate experimentally the functions described in
  Fig. 1(a) EQUIVALENT CIRCUIT OF PROPOSED TRANSFORMER
                                                                Section II.
                  REFERRED IN SECONDARY
        Fig.1(a) shows the equivalent circuit of this
system, which is valued in secondary side of the
transformer. Turn ratio, voltage, current, resistance, and
leakage reactance are denoted by a, V, I, R and X and
subscripts 1 and 2 show the primary side and secondary
side, respectively. Symbols in Fig. 1(b) are defined as
V1r=V1/a , I1r=aI1 , Rs=R1/a2+R2, Xs=X1/a2+X2 The variable         Fig.2 (a) STRUCTURE OF PROPOSED TRANSFORMER (LATERAL
range of the reactance Xsis represented as Xsmin≤ Xs≤ Xsmax.                                VIEW)
                                                        34 | P a g e
                                                                                              NOVATEUR PUBLICATIONS
                              International Journal of Research Publications in Engineering and Technology [IJRPET]
                                                                                                         ISSN: 2454-7875
                                                                                          VOLUME 3, ISSUE 6, Jun.-2017
                                                              fixed iron core completely. A plan view of the mobile
                                                              portion of the actuator shown in the figure.2 (b).
                                                                       The drive unit comprises of a settling positioning
                                                              mechanism and a protection mechanism. The position
                                                              adjustment mechanism is a linear variable direct current
                                                              (DC) power supply actuator and adjusted in position on a
                                                              moving block that is in the state. The control supply This
                                                              DC is provided by a DC source that is controlled by a
                                                              microcontroller. This supply is controlled by the fault
                                                              current level. When an overcurrent flows through the
                                                              transformer winding, the mobile block is strongly pulled to
 Fig. 2 (b) STRUCTURE OF PROPOSED TRANSFORMER (TOP VIEW)
                                                              the right in Fig. 2 (b) with a linear actuator. This internal
                                                              operation of the mobile core and the inductive reactance of
         A side view of the same shown in the figure. 2 (A).
                                                              the outer envelope acquire the change of the overcurrent
The moving iron core block and the magnetic track located
                                                              control.
between the two windings. There are two air spaces
                                                                                  V. MATLAB SIMULATION
between the core portion of mobile iron and the fixed iron
                                                                       Fig. 3 (a) shows the simulation diagram of
core and the sum of them is defined as the total length (l g)
                                                              MATLAB. This simulation tries to implement a variable
empty. When it moves to lock moving core iron core in the
                                                              transformer resistor to limit current flow. Transformer
vertical position, as shown in Fig. 2 (a). The moving block
                                                              load resistance in this simulation varies depending on the
and fixed iron core stationary in the distance. The position
                                                              test and error. The inductance L varies in the test base and
of the mobile block is defined as X = 0 mm when the
                                                              the failure of the value change induction so that the total
mobile block is completely inserted in the fixed core and
                                                              faultcurrent enters the limit and the waveform input and
the total depth when the mobileblock is projected from the
                                                              output voltage and current characteristics are analyzed.
                              Fig.3 (a) MATLAB SIMULATION MODEL OF PROPOSED TRANSFORMER
                                       Fig. 3(b) WAVEFORM OF VOLTAGE BEFORE FAULT
                                                       35 | P a g e
                                                                                         NOVATEUR PUBLICATIONS
                             International Journal of Research Publications in Engineering and Technology [IJRPET]
                                                                                                  ISSN: 2454-7875
                                                                                      VOLUME 3, ISSUE 6, Jun.-2017
                                        Fig. 3(c) WAVEFORM OF CURRENT BEFORE FAULT
         Fig.3 (b) and Fig.3(c) shows waveform of voltage and current before fault respectively. The phase voltage applied
is 210V, 50Hz.
                                    Fig. 3(d) WAVEFORM OF VOLTAGE AFTER FAULT AT L=1H
                                    Fig. 3(e) WAVEFORM OF CURRENT AFTER FAULT AT L=1H
         Fig.3 (d) and Fig.3 (e) shows waveform of voltage and current after fault at L=1H respectively. Here L=1H is
transformer inductance at first and as seen in Fig 3(d), this waveform voltage deeps is very high after fault occurs. As seen
in Fig 3(e), this waveform current is extremely high after fault occurs.
                                                        36 | P a g e
                                                                                         NOVATEUR PUBLICATIONS
                             International Journal of Research Publications in Engineering and Technology [IJRPET]
                                                                                                  ISSN: 2454-7875
                                                                                      VOLUME 3, ISSUE 6, Jun.-2017
                                  Fig. 3(f) WAVEFORM OF VOLTAGE AFTER FAULT AT L=3.14H
                                  Fig. 3(g) WAVEFORM OF CURRENT AFTER FAULT AT L=3.14H
        Fig.3 (f) and Fig.5 (g) shows waveform of voltage       REFERENCES:
and current after fault at L=3.14H respectively. Here           1) JunjiKondoh and Itaru Ishii, “Fault Current Limiting
L=3.14H is transformer inductance after fault and as seen          Transformer With Variable Reactance,” IEEE
in Fig 3(d), this waveform voltage deeps is very low as            TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY,
compared to L=1H after fault occurs as seen in fig.3(d). As        VOL. 14, NO. 2, JUNE 2004.
seen in Fig 5(e), this waveform current is very low as          2) S. M. Blair; A. J. Roscoe ; C.D. Booth ; G.M. Burt ; A.
compared to L=1H after fault occurs as seen in fig.3               Teo ; C.G. Bright, “Implications of fault current
(e).Hence as a result it is determined that if inductance is       limitation for electrical distribution networks,”
increased after fault then fault current can be restricted.        Developments in Power System Protection (DPSP
                                                                   2010). Managing the Change, 10th IET International
VI. CONCLUSION:                                                    Conference, ISBN: 978-1-84919-212-5DOI: 10.1049/
          It is confirmed that the fault current limiting          cp.2010.0355.
transformer with variable reactance has the following           3) Prof. S. M. Kulkarni, “VARIABLE REACTANCE
abilities:                                                         TRANSFORMER AN EMERGING TECHNOLOGY 1,”
 It transforms the voltage for wide extent of output              National Conference on Recent Research in
     current.                                                      Engineering and Technology (NCRRET -2015)
 It restricts the fault current enough because of high            International Journal of Advance Engineering and
     reactance without any action                                  Research Development (IJAERD) e-ISSN: 2348 - 4470,
 The voltage is regulated by the reactance adjustment.            print-ISSN: 2348-6406.
                                                        37 | P a g e