gomc-rest

日本語 README

Release CI License: MIT Go Platform

gomc-rest is a small REST API server and HTTP gateway for Mitsubishi Electric PLCs using MC protocol 3E or 4E frames. It sits between HTTP clients and a PLC, brokering reads and writes for device strings such as D100.0, W100, and M0 while returning JSON values with automatic conversion: word devices become integers and bit devices become booleans.

The PLC transport is provided by gomcprotocol. The server uses only the Go standard library for HTTP handling.

A Python client library with no extra dependencies is also available: gomc-rest-client on PyPI

A lightweight debugging GUI is also available: gomc-rest-gui — a standalone HTTP client (Wails + React) for exercising gomc-rest's endpoints from a simple screen instead of curl.

Features

  • Read word and bit devices through a simple /read endpoint.
  • Write integer arrays or boolean arrays through /write.
  • Run, stop, pause, latch-clear, and reset the PLC remotely.
  • Configure by command-line flags, with environment variables as defaults.
  • Start in read-only mode to block write and remote-control endpoints.
  • Serialize PLC communication through a single in-process worker queue.
  • Keep a simple health endpoint that reports the current connection state.
  • Retry the PLC connection on demand when startup connection fails or a previous connection was cleared.

Network Scope

⚠️ Caution: Do not expose this server to the Internet, an office LAN, or any untrusted network.

This server is intended only for FA local networks, such as an isolated factory LAN, a trusted machine network, or localhost access from an operator PC. The API can read, write, run, stop, pause, latch-clear, and reset a PLC, and it does not provide authentication, authorization, TLS, or access control.

Recommended deployment:

  • Run it inside an isolated FA network or on localhost only.
  • Restrict access with network segmentation, firewall rules, or host-level controls.
  • Use -listen 127.0.0.1:8080 when only local access is required.
  • Do not place it behind a public reverse proxy or expose it through port forwarding.

Download

Download the latest gomc-rest.exe from the Releases page.

Published releases provide the Windows binary as gomc-rest.exe. Source builds use the output name from the build command below.

Quick Start (Windows)

1. Create a batch file

Create start-gomc-rest.bat in the same folder as gomc-rest.exe and edit the values at the top to match your environment:

@echo off
REM ============================================================
REM  Edit these values to match your environment
REM ============================================================
set PLC_HOST=192.168.0.1
set PLC_PORT=5007
set LISTEN_PORT=8080
REM ============================================================

gomc-rest.exe -host %PLC_HOST% -port %PLC_PORT% -listen %LISTEN_PORT%
pause

Double-click the batch file to start the server. To stop it, press Ctrl+C or close the window. The pause line keeps the window open after the server exits so you can read any error messages.

2. Verify the server is running

Open a browser and go to:

http://localhost:8080/health

You should see:

{"plc_status":"ok","connected":true}

If the PLC is not reachable yet, connected will be false. The server still starts and will retry the connection on the first PLC operation (/read, /write, or /remote/*).

Read-only mode

To block all write and remote-control operations (for monitoring only):

@echo off
set PLC_HOST=192.168.0.1
set PLC_PORT=5007
set LISTEN_PORT=8080

gomc-rest.exe -host %PLC_HOST% -port %PLC_PORT% -listen %LISTEN_PORT% -readonly
pause

Save logs to a file

@echo off
set PLC_HOST=192.168.0.1
set PLC_PORT=5007
set LISTEN_PORT=8080
set LOG_FILE=C:\gomc-rest.log

gomc-rest.exe -host %PLC_HOST% -port %PLC_PORT% -listen %LISTEN_PORT% -log-file %LOG_FILE%
pause

Logs are written to both the console and the file. The directory must already exist; the server does not create missing parent directories.

Enable remote control

Remote-control endpoints (/remote/run, /remote/stop, etc.) are disabled by default. Add -enable-remote to turn them on:

gomc-rest.exe -host %PLC_HOST% -port %PLC_PORT% -listen %LISTEN_PORT% -enable-remote

Troubleshooting

Symptom Likely cause Fix
{"connected":false} on /health PLC is off or IP/port is wrong Check PLC_HOST and PLC_PORT in the batch file
403 forbidden on /write Server started with -readonly Remove -readonly from the batch file
403 forbidden on /remote/* -enable-remote is not set Add -enable-remote to the batch file
503 busy Too many simultaneous requests Increase -queue-size (default: 32)
Port already in use Another process is using the port Change LISTEN_PORT to a free port
Window closes immediately Startup error Run from Command Prompt to see the error message

Run

For the Windows release binary:

.\gomc-rest.exe -host 192.168.0.1 -port 5007 -mode binary -listen :8080

For source builds or non-Windows environments:

./gomc-rest -host 192.168.0.1 -port 5007 -frame 3e -transport tcp -mode binary -queue-size 32 -timeout 5s -listen :8080

For read-only operation, add -readonly. In read-only mode, /health and /read remain available, while POST operations on /write and /remote/* return 403 forbidden.

.\gomc-rest.exe -host 192.168.0.1 -port 5007 -mode binary -listen 127.0.0.1:8080 -readonly

On startup, the server attempts to connect to the PLC. If the PLC is not reachable, startup continues and the server retries on the first PLC request.

Build from source

git clone https://github.com/moge800/gomc-rest
cd gomc-rest
go build -o gomc-rest .

Configuration

Flags take priority. Environment variables provide the default values for those flags.

Flag Environment variable Default Notes
-host GOMCR_HOST 192.168.0.1 PLC host or IP address
-port GOMCR_PORT 5007 PLC port, 1 to 65535
-frame GOMCR_FRAME 3e MC protocol frame, 3e or 4e
-transport GOMCR_TRANSPORT tcp tcp or udp; 4e supports tcp only
-mode GOMCR_MODE binary binary or ascii
-queue-size GOMCR_QUEUE_SIZE 32 Number of PLC requests that can wait while one request is active
-timeout GOMCR_TIMEOUT 5s PLC connect and I/O timeout
-listen GOMCR_LISTEN :8080 HTTP listen address
-readonly GOMCR_READONLY false Set to true to reject POST operations on /write and /remote/*
-enable-remote GOMCR_ENABLE_REMOTE false Set to true to enable remote-control endpoints (/remote/*)
-log-file GOMCR_LOG_FILE (none) Path to log file; if set, logs are written to both the file and stderr
-log-level GOMCR_LOG_LEVEL info Terminal log level: debug, info, warn, or error
-log-file-level GOMCR_LOG_FILE_LEVEL warn File log level: debug, info, warn, or error; only used with -log-file

API Reference

All successful write and remote-control operations return:

{"ok":true}
Method Path Parameters / body Response
GET /openapi.yaml none OpenAPI 3.1 specification (YAML)
GET /version none {"version":"v0.9.0"} or {"version":"dev"} for local builds
GET /info none {"version":"v0.9.0","gomcprotocol_version":"v0.3.0","host":"192.168.0.1","port":5007,"frame":"3e","transport":"tcp","mode":"binary","listen_addrs":["192.168.1.10:8080"],"readonly":false,"enable_remote":false}
GET /metrics none {"client_request_count":0,"busy_count":0,"client_avg_latency_ms":0,"client_recent_avg_latency_ms":0,"queue_length":0,"request_count":0,"reconnect_count":0,"timeout_count":0,"plc_error_count":0,"avg_latency_ms":0,"recent_avg_latency_ms":0}
GET /health none {"plc_status":"ok","connected":true} or {"plc_status":"disconnected","connected":false}
GET /read query: addr required, count optional and defaults to 1, dword optional and defaults to false, sint optional and defaults to false {"values":[100,200]} or {"values":[true,false]}
POST /write query: addr required, dword optional and defaults to false, sint optional and defaults to false; body: {"values":[1,2,3]} or {"values":[true,false]} {"ok":true}
POST /random-read body: {"words":["D100","D200"],"dwords":["D300"]} {"words":[100,200],"dwords":[300]}
POST /random-write body: {"words":[{"addr":"D100","value":1}],"dwords":[{"addr":"D300","value":65536}],"bits":[{"addr":"M0","value":true}]} {"ok":true}
POST /remote/run requires -enable-remote; query: clear=0/1/2 optional, force=true/false optional {"ok":true}
POST /remote/stop requires -enable-remote; none {"ok":true}
POST /remote/pause requires -enable-remote; query: force=true/false optional {"ok":true}
POST /remote/latch-clear requires -enable-remote; none {"ok":true}
POST /remote/reset requires -enable-remote; none {"ok":true}

Notes:

  • count must be between 1 and 1024.
  • values must be present and contain between 1 and 1024 items.
  • The /write request body must be 1 MiB or smaller.
  • Word devices require integer values in the range 0..65535. Bit devices require boolean values.
  • When dword=true, each value is an unsigned 32-bit integer in the range 0..4294967295. The low 16 bits are stored in the register at addr and the high 16 bits in the next register (addr+1). Only word devices support dword=true. With dword=true, count must be 512 or less and values must contain 512 items or less (so that the actual word count sent to the PLC does not exceed 1024).
  • When sint=true, values are interpreted as signed integers. For word devices the range is -32768..32767; for dword=true the range is -2147483648..2147483647. Only word devices support sint=true. The PLC register bits are unchanged — sint only affects how values are converted between JSON and the 16-bit register representation.
  • /random-read accepts words and dwords arrays of device address strings. Both default to empty; at least one must be non-empty. Only word devices (D, W, R, etc.) are allowed. Returns {"words":[...],"dwords":[...]} where word values are integers (0..65535) and dword values are unsigned 32-bit integers (0..4294967295).
  • /random-write accepts words, dwords, and bits arrays. Each entry is {"addr":"...","value":...}. words and dwords require word devices; bits requires bit devices. Internally calls RandomWrite for words/dwords and RandomWriteBits for bits within one serialized job. Maximum 255 entries per array.
  • /remote/* endpoints are disabled by default and return 403 forbidden unless the server is started with -enable-remote. This is separate from read-only mode.
  • When read-only mode is enabled, POST operations on /write and /remote/* return 403 forbidden. Read-only mode is a safety aid, not a replacement for network isolation, authentication, authorization, firewall rules, or PLC-side protection.
  • Boolean query flags (dword, sint, force) accept true or false (case-insensitive, exactly once). Any other value (including empty or duplicated) returns 400 bad_request. All endpoints reject unknown query parameters with 400 bad_request (when the request passes earlier checks such as method, read-only, and remote-enabled validation).
  • GET /health always returns HTTP 200, even when the PLC is disconnected.
  • /remote/reset clears the TCP connection because the PLC closes it after reset.
  • /metrics PLC fields (request_count, avg_latency_ms, recent_avg_latency_ms) measure only the PLC wire time. Client fields (client_request_count, client_avg_latency_ms, client_recent_avg_latency_ms) measure the full round-trip including queue wait time. busy_count counts requests rejected because the queue was full; these are excluded from the client latency averages. timeout_count counts requests that returned context.DeadlineExceeded (timed out before, during, or after queuing).

Device Addressing

Device addresses are case-insensitive and may include surrounding whitespace. The device prefix determines whether the API reads or writes words or bits.

Type Devices JSON value type Examples
Word D, W, R, ZR, TN, STN, CN, Z, SW, SD integer D100, ZR512, TN10, CN5
Bit X, Y, M, L, B, F, V, SB, SM, S, DX, DY, TC, TS, STC, STS, CC, CS boolean M0, TC10, CC5, STC3

Timer and counter contacts and coils use two-letter prefixes: TC (timer contact), TS (timer coil), CC (counter contact), CS (counter coil). The single-letter forms T and C are not valid device names and return 400 bad_request.

The numeric address must be a non-negative integer. Unknown devices, missing numbers, non-numeric numbers, and negative numbers return 400 bad_request. The devices X, Y, B, SB, W, SW, ZR, DX, and DY use hexadecimal address numbers (e.g. X4F, Y12D2, W1D).

Word Device Bit Access

Append .N (single hex digit, 0F) to a word device address to read or write a single bit within the 16-bit register.

D3500.0   ← bit 0 (LSB) of D3500
D3500.F   ← bit 15 (MSB) of D3500
W1D.7     ← bit 7 of W1D (hex address 0x1D)
  • Read returns {"values": [true]} or {"values": [false]}.
  • Write body must be {"values": [true]} or {"values": [false]} (exactly one element). The server performs a read-modify-write internally.
  • dword=true or sint=true combined with bit access returns 400 bad_request.
  • count must be 1; count=2 or higher returns 400 bad_request.
  • Appending .N to a bit device (e.g. M0.0) returns 400 bad_request.

Error Responses

Errors are returned as JSON. Every error response includes both the HTTP status code and a machine-readable code in the body.

Scenario HTTP code Example
Invalid parameter, body, address, count, or method 400 or 405 bad_request {"status":400,"error":"addr is required","code":"bad_request"}
/remote/* endpoint called without -enable-remote 403 forbidden {"status":403,"error":"remote-control operations are disabled (use -enable-remote to enable)","code":"forbidden"}
Operation rejected by read-only mode 403 forbidden {"status":403,"error":"operation not allowed in read-only mode","code":"forbidden"}
/write body is too large 413 bad_request {"status":413,"error":"body must not be larger than 1048576 bytes","code":"bad_request"}
PLC MC protocol error with an end code 502 plc_error {"status":502,"error":"MC error 0x4000","code":"plc_error","end_code":"0x4000"}
PLC connection error 503 connection_error {"status":503,"error":"connect: refused","code":"connection_error"}
PLC communication queue is full 503 busy {"status":503,"error":"PLC communication queue is full","code":"busy"}
PLC communication queue is closed during shutdown 503 queue_closed {"status":503,"error":"PLC communication queue is closed","code":"queue_closed"}
HTTP request context was canceled before completion 499 request_canceled {"status":499,"error":"request canceled","code":"request_canceled"}
HTTP request context deadline expired 504 request_timeout {"status":504,"error":"request timed out","code":"request_timeout"}

Connection Behavior

  • PLC requests are serialized through one shared in-process worker queue and one client connection.
  • The worker executes one PLC request at a time. HTTP handlers do not call the PLC client directly.
  • -queue-size controls how many PLC requests can wait while one request is active. When the queue is full, the server immediately returns 503 busy with Retry-After: 1.
  • -timeout controls the PLC connect and I/O deadline. It does not cancel HTTP request contexts that are already disconnected; queued requests are skipped before execution if their request context is canceled.
  • If initial connection fails, the HTTP server still starts.
  • If there is no active connection, the next PLC request attempts to reconnect.
  • Connection-level MC protocol errors clear the connection so a later request can reconnect.

Examples

The /health endpoint can be used without a PLC. The other examples require a reachable PLC.

curl http://localhost:8080/health
curl "http://localhost:8080/read?addr=D100&count=3"
curl "http://localhost:8080/read?addr=M0&count=4"
curl "http://localhost:8080/read?addr=D100&count=2&dword=true"
curl "http://localhost:8080/read?addr=D100&count=3&sint=true"

curl -X POST "http://localhost:8080/write?addr=D100" \
  -H "Content-Type: application/json" \
  -d '{"values":[10,20,30]}'

curl -X POST "http://localhost:8080/write?addr=D100&dword=true" \
  -H "Content-Type: application/json" \
  -d '{"values":[100000,200000]}'

curl -X POST "http://localhost:8080/write?addr=D100&sint=true" \
  -H "Content-Type: application/json" \
  -d '{"values":[-1,-32768,32767]}'

curl -X POST "http://localhost:8080/write?addr=M0" \
  -H "Content-Type: application/json" \
  -d '{"values":[true,false]}'

# Random read/write — multiple non-contiguous addresses in one request
curl -X POST "http://localhost:8080/random-read" \
  -H "Content-Type: application/json" \
  -d '{"words":["D100","D200"],"dwords":["D300"]}'

curl -X POST "http://localhost:8080/random-write" \
  -H "Content-Type: application/json" \
  -d '{"words":[{"addr":"D100","value":10},{"addr":"D200","value":20}],"bits":[{"addr":"M0","value":true}]}'

# Remote-control endpoints require -enable-remote at startup
curl -X POST "http://localhost:8080/remote/run?clear=0&force=false"
curl -X POST "http://localhost:8080/remote/stop"
curl -X POST "http://localhost:8080/remote/pause?force=false"
curl -X POST "http://localhost:8080/remote/latch-clear"
curl -X POST "http://localhost:8080/remote/reset"