CheckMK Wiseways UPS SNMP Plugin

A CheckMK SNMP plugin for monitoring Wiseways UPS devices (6000VA, 10kVA and compatible models).

Features

  • 19 specialized services for granular monitoring and alerting
  • Automatic unit conversion (decivolts→volts, minutes→seconds)
  • Dynamic thresholds from device configuration when available
  • Maintenance expiration warnings
  • Support for RFC 1628 UPS MIB and Wiseways enterprise OIDs (44782)
  • THS environmental sensor support (temperature/humidity)

Installation

From MKP Package (Recommended)

# Download from https://github.com/oposs/cmk-oposs_wiseways_ups/releases
cmk -P install oposs_wiseways_ups-<version>.mkp
cmk -II <hostname>

Manual Installation

cp -r local/* ~/local/
cmk -R
cmk -II <hostname>

SNMP Setup

  1. Configure SNMP community string on the UPS
  2. Add the UPS as a host in CheckMK with SNMP monitoring enabled
  3. Set the appropriate SNMP community in CheckMK host properties

Services and Thresholds

Configure thresholds under "Setup" > "Services" > "Service monitoring rules" > "OPOSS Wiseways UPS".

Service Description Default Thresholds (Warn/Crit)
UPS System Info Model, serial, firmware, maintenance dates Warns on expired maintenance
UPS Battery Status Battery state and alarms
UPS Power Status Power source, mode, line failures
UPS Alarm Status System-wide alarm monitoring
UPS Battery Charge Battery charge % Lower: 20%/10%
UPS Battery Runtime Remaining runtime Lower: 10min/5min
UPS Battery Voltage DC battery voltage Lower: 180V/170V
UPS Battery Current Charging/discharging current
UPS Battery Temperature Battery temperature Upper: 40°C/45°C, Lower: 10°C/5°C
UPS Input Voltage AC input voltage Upper: 250V/260V, Lower: 210V/200V
UPS Output Voltage AC output voltage Upper: 250V/260V, Lower: 210V/200V
UPS Bypass Voltage Bypass line voltage Upper: 250V/260V, Lower: 210V/200V
UPS Input Frequency Input frequency Upper: 51Hz/52Hz, Lower: 49Hz/48Hz
UPS Output Frequency Output frequency Upper: 51Hz/52Hz, Lower: 49Hz/48Hz
UPS Bypass Frequency Bypass frequency Upper: 51Hz/52Hz, Lower: 49Hz/48Hz
UPS Output Load Load percentage Upper: 80%/90%
UPS Output Power Power consumption (W)
UPS Output Current Output current (A)
UPS Environment THS sensor temp/humidity Temp: 35°C/40°C (upper), 10°C/5°C (lower); Humidity: 70%/80% (upper), 20%/10% (lower)

Services marked "—" have no default thresholds but can be configured. Bypass and Environment services only appear when hardware is present.

Graphs

Each service has its own graph. Additional combined graphs at host level:

  • UPS All Voltages / UPS AC Voltages: Compare voltage sources
  • UPS Frequencies: All frequencies together
  • UPS Currents: Output and battery currents
  • UPS Battery Time: Runtime and time-on-battery
  • UPS Environment: Temperature and humidity

Requirements

  • CheckMK 2.3 or later
  • SNMP v1/v2c access to the UPS
  • Wiseways UPS with SNMP support

Troubleshooting

No services discovered:

# Verify SNMP connectivity (should return string containing "Wiseway3")
snmpwalk -v2c -c <community> <ups_ip> .1.3.6.1.2.1.33.1.1.5.0

# Debug discovery
cmk -vvI --detect-plugins=oposs_wiseways_ups <hostname>

Fewer than 19 services: Normal - bypass, environment, and some battery metrics only appear when supported by hardware.

Incorrect values: The plugin handles enterprise string formats and special value -99998 (unavailable data) automatically.

License

This plugin is provided as-is for monitoring Wiseways UPS devices in CheckMK environments.