PUIL 2011: Electrical Installation Guide
PUIL 2011: Electrical Installation Guide
PUIL 2011
(PERSYARATAN UMUM INSTALASI LISTRIK 2011)
                                              ICASEA strategic initiatives include a portfolio of market development programs that include raising
                                              the awareness of the advantages and versatility of copper applications in building industry with
                                              various stakeholders. They include the regulators, housing development bodies, private developers,
                                              contractors, consultants, engineers & architects etc. Our programs focus on enhancing safety,
                                              reliability, design, health and electrical efficiency. We also facilitate the setting up of building codes
                                              that use copper effectively, efficiently and safely.
                                              This PUIL 2011 handbook is thus put together to provide and share best practices for electrical
                                              installation and inspection. We are confident that this handbook will contribute to improving
                                              competitiveness and installation standards through enhanced knowledge and management of
                                              building wiring and cabling.
                                              Steven Sim
                                              Chief Executive Officer
                                              International Copper Association Southeast Asia Ltd.
B   Persyaratan Umum Instalasi Listrik 2011                                                                        Persyaratan Umum Instalasi Listrik 2011   i
                                               Sambutan Direktur Jenderal Ketenagalistrikan
                                               Bismillahirramanirrahim,
                                               Assalamu’alaikum warahmatullahii wabarakatuh
                                                                           Kerap kali kita membaca dan mendengar adanya berita kebakaran yang diduga
                                                                           diakibatkan oleh listrik pada beberapa media massa (surat kabar dan televisi) yang
                                                                           mengakibatkan kerugian harta benda bahkan menyebabkan kehilangan nyawa
                                                                           manusia. Oleh karena itu, menjadi tanggung jawab kita bersama sebagai pemangku
                                                                           kepentingan (stakeholders) ketenagalistrikan untuk berupaya mengurangi kebakaran
                                               yang diakibatkan oleh listrik.
                                               Untuk memenuhi keselamatan ketenagalistrikan sebagaimana diamanatkan Pasal 44 ayat (1) Undang-Undang
                                               Nomor 30 tahun 2009 tentang Ketenagalistrikan, Pemerintah mewajibkann setiap instalasi tenaga listrik terlebih
                                               dahulu diuji laik operasi.
                                               Pemerintah berupaya terus melengkapi regulasi keselamatan ketenagalistrikan termasuk regulasi instalasi listrik
                                               tegangan rendah yang diatur dalam PUIL. Badan Standarisasi Nasional telah menetapkan PUIL 2011 menjadi SNI
                                               0225 tahun 2011 dan Kementerian Energi dan Sumber Daya Mineral akan memberlakukan PUIL 2011 sebagai
                                               standar wajib, dengan demikian seluruh pemangku kepentingan wajib mengikuti ketentuan dalam PUIL 2011.
                                               PUIL 2011 memuat ketentuan spesifikasi teknis dan cara pemasangan instalasi listrik, namun demikian, dengan
                                               adanya buku “Penjelasan PUIL 2011” ini, dapat membantu masyarakat dalam pemilihan peralatan listrik, sebagai
                                               panduan pelaksana (instalatir) dalam pemasangan instalasi listrik dan membantu lembaga inspeksi teknis dalam
                                               pelaksanaan uji laik operasi. Dengan terbitnya buku ini diharapkan juga dapat mengurangi perbedaan pendapat
                                               dalam mengartikan persyaratan teknis dan besar-besaran listrik yang diatur dalam PUIl 2011.
                                               Kepada segenap tim penyusun buku ini kami ucapkan terima kasih, demikian juga kepada International Copper
                                               Assosiation Southeast Asia (ICA SEA) atas partisipasinya dalam penyusunan buku ini. Semoga buku ini bermanfaat
                                               dalam mewujudkan keselamatan ketenagalistrikan di Indonesia.
JARMAN
ii   Persyaratan Umum Instalasi Listrik 2011                                                                                Persyaratan Umum Instalasi Listrik 2011   iii
                                               Kata Pengantar
                                               Salah satu faktor penting bagi terpenuhinya keselamatan ketenagalistrikan adalah pemasangan
                                               instalasi listrik yang memenuhi ketentuan dan atau standar yang diatur dalam Persyaratan Umum
                                               Instalasi Listrik (PUIL) sebagai acuan untuk pemasangan instalasi listrik.
                                               PUIL sejak pertamakali diterbitkan pada tahun 1964 telah mengalami beberapa kali perubahan yaitu
                                               PUIL 1977, PUIL 1987, PUIL 2000 dan terakhir PUIL 2011. Sejak tahun 2000, PUIL sebagai Peraturan
                                               Umum Instalasi Listrik berubah menjadi Persyaratan Umum Instalasi Listrik dan diberlakukan secara
                                               wajib. Terbitnya PUIL 2011 (SNI 0225:2011), akan menjadi acuan baru pemasangan instalasi listrik,
                                               yang merevisi PUIL sebelumnya dalam rangka mengikuti perkembangan teknologi dan perkembangan
                                               standar Internasional.
                                               Mengingat PUIL berisikan persyaratan, spesifikasi teknik dan besaran listrik yang digunakan sebagai
                                               pegangan pemasangan instalasi listrik, maka untuk memudahkan masyarakat serta agar terhindar
                                               dari keraguan dalam hal pemilihan spesifikasi, jenis dan cara pemasangan peralatan listrik, disusunlah
                                               buku penjelasan PUIL 2011 yang berisi tentang keterangan tambahan, perhitungan dan jenis gambar
                                               peralatan listrik yang diperlukan, dengan nama: Penjelasan PUIL 2011. Buku ini merupakan buku
                                               pelengkap/tambahan yang menjelaskan hal-hal yang diatur dalam PUIL 2011, maka buku ini tidak
                                               dapat digunakan secara mandiri tanpa disertai dengan buku PUIL 2011, atau dengan kata lain buku
                                               ini harus digunakan bersama-sama dengan buku PUIL 2011.
                                               Buku ini merupakan rintisan, karena itu hanya sebagian ayat/subayat dalam PUIL 2011 yang
                                               dijelaskan. Diharapkan untuk masa mendatang akan lebih banyak lagi ayat/subayat dalam PUIL 2011
                                               yang perlu dijelaskan. Kami harapkan para pembaca dapat memberikan saran, usulan dan masukan
                                               untuk penyempurnaan buku ini.
                                               Untuk berhasilnya penerbitan buku ini kami ucapkan terimakasih sebesar-besarnya kepada:
                                               1. Direktur Jenderal Ketenagalistrikan Kementerian Energi dan Sumber Daya Mineral beserta
                                               jajarannya.
                                               2. CEO International Copper Association Southeast Asia Ltd. beserta jajarannya.
                                               Semoga buku ini bermanfaat bagi para pengguna dan pada akhirnya bermanfaat dalam mewujudkan
                                               keselamatan ketenagalistrikan di Indonesia.
Tim Penyusun
iv   Persyaratan Umum Instalasi Listrik 2011                                                                     Persyaratan Umum Instalasi Listrik 2011   v
                                               Tim Penyusun
                                               Pengarah
                                               Ir. Jarman, M.Sc (Direktur Jenderal Ketenagalistrikan)
                                               Ir. Agoes Triboesono, M.Eng (Direktur Teknik dan Lingkungan Ketenagalistrikan)
                                               Penanggungjawab
                                               Ir. Jisman P. Hutajulu, MM (Kasubdit Standardisasi Ketenagalistrikan)
                                               Penyusun
                                               Ir. Bartien Sayogo (HIMAPUIL), Ketua
                                               Ir. Fadjar Widjaja (HIMAPUIL), Anggota
                                               Ir. Sahala T. Sinaga (HIMAPUIL), Anggota
                                               Ir. Soemarjanto (HIMAPUIL), Anggota
                                               Ir. Djoni S. Soetarman (HIMAPUIL), Anggota
                                               Sahat Simangunsong, ST, MT (Ditjen Ketenagalistrikan), Anggota
vi   Persyaratan Umum Instalasi Listrik 2011                                                                    Persyaratan Umum Instalasi Listrik 2011   vii
                                                     Daftar Isi                                                                                 Daftar Isi
                                                     Bagian 4-43:                                                                        75
                                                     Proteksi untuk keselamatan – Proteksi terhadap arus lebih
                                                     Bagian 5-52:                                                                        89
                                                     Pemilihan dan pemasangan perlengkapan listrik – Sistem perkawatan
                                                     viii   Persyaratan Umum Instalasi Listrik 2011                                                                                                             Persyaratan Umum Instalasi Listrik 2011   ix
                                                                                                   Bagian 1
                                                                                                   Pendahuluan,
                                                                                                   prinsip fundamental
                                                                                                   dan definisi
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     x   Persyaratan Umum Instalasi Listrik 2011      Persyaratan Umum Instalasi Listrik 2011   1
                                                     10.1 Ketentuan terkait                                                                                 10.2.3 Pemberlakuan
                                                                                                                                                            PUIL diberlakukan untuk seluruh wilayah Republik Indonesia.
                                                     Di samping PUIL ini, harus pula diperhatikan ketentuan terkait dalam peraturan perundang-undangan
                                                     yang berlaku, antara lain:                                                                                 PENJELASAN
                                                     a) Undang-undang Nomor 1 Tahun 1970 tentang Keselamatan Kerja, beserta Peraturan
                                                         Pelaksanaannya;
                                                                                                                                                                Hal ini berarti PUIL diberlakukan di seluruh pelosok Indonesia, termasuk di setiap kompleks
                                                     b) Undang-undang Nomor 15 Tahun 1985 tentang Ketenagalistrikan, beserta Peraturan
                                                         Pelaksanaannya;                                                                                        atau lokasi milik asing di Indonesia, sepanjang masuk dalam ruang lingkup PUIL.
                                                     c) Undang-undang Nomor 23 Tahun 1997 tentang Pengelolaan Lingkungan Hidup beserta
                                                         Peraturan Pelaksanaannya;
                                                                                                                                                            10.3 Penafsiran dan penyimpangan
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                            10.3.2 Penyimpangan
                                                                                                                                                            Dalam hal khusus, instansi yang berwenang dapat menyetujui penyimpangan dari persyaratan dalam
                                                     10.2 Penamaan, penunjukan dan pemberlakuan
                                                                                                                                                            PUIL dan bisa memperhatikan pendapat Panitia Teknis terkait.
                                                     10.2.1 Penamaan
                                                     Persyaratan ini secara lengkap bernama Persyaratan Umum Instalasi Listrik Tahun 2011, disingkat PUIL       PENJELASAN
                                                     2011, untuk selanjutnya dalam standar ini disebut PUIL.
                                                                                                                                                                Lihat PENJELASAN 10.6.3.
                                                         PENJELASAN
                                                         Jika dalam penerbitan PUIL 1964, 1977 dan 1987 nama buku ini adalah Peraturan Umum                 10.6 Penyempurnaan
                                                         Instalasi Listrik, maka mulai penerbitan tahun 2000, namanya menjadi Persyaratan Umum
                                                         Instalasi Listrik dengan tetap mempertahankan singkatannya yang sama yaitu PUIL.                   10.6.1 Usulan untuk mengubah, menambah dan/atau menyempurnakan PUIL 2011 dapat diajukan
                                                         Penggantian “Peraturan” menjadi “Persyaratan” dianggap lebih tepat karena pada perkataan           kepada instansi yang berwenang.
                                                         “peraturan” terkait pengertian adanya kewajiban untuk mematuhi ketentuannya dan jika
                                                                                                                                                            Instansi yang berwenang saat ini adalah Departemen Energi dan Sumber Daya Mineral, Direktorat
                                                         tidak maka berlaku suatu sanksi; suatu peraturan hanya dapat diterbitkan oleh otoritas atau
                                                         regulator yang berwenang. PUIL sebagai Standar Nasional Indonesia (SNI) dengan Peraturan           Jendral Listrik dan Pemanfaatan Energi, dengan alamat:
                                                         Menteri ESDM diberlakukan sebagai SNI wajib (merupakan regulasi), sehingga menjadi                 Jl. H.R. Rasuna Said Blok X-2, Kav. 07-08, Kuningan, Jakarta 12950.
                                                         “peraturan” yang harus dipatuhi.
                                                     2    Persyaratan Umum Instalasi Listrik 2011                                                                                                                               Persyaratan Umum Instalasi Listrik 2011   3
                                                                                                                                                           11 Ruang lingkup
                                                     10.6.2 Usul pengubahan, penambahan dan/atau penyempurnaan PUIL oleh instansi berwenang                PUIL memberikan persyaratan untuk desain, pemasangan dan verifikasi instalasi listrik. Persyaratan
                                                     diajukan sebagai usul revisi atau amandemen kepada Panitia Teknis yang menangani PUIL.                ini dimaksudkan untuk menetapkan keselamatan manusia, ternak dan harta benda terhadap bahaya
                                                                                                                                                           dan kerusakan yang dapat timbul pada pemakaian secara wajar instalasi listrik dan untuk menetapkan
                                                     10.6.3 Setelah usul revisi atau amandemen tersebut pada 10.6.2 disahkan dan diberlakukan oleh Badan   fungsi yang tepat dari instalasi tersebut.
                                                     Standardisasi Nasional (BSN), persyaratan lama yang bersangkutan tidak berlaku lagi.
                                                                                                                                                           11.1 PUIL berlaku untuk desain, pemasangan dan verifikasi instalasi listrik sebagai berikut:
                                                                                                                                                           a) kompleks (premises) perumahan;
                                                         PENJELASAN                                                                                        b) kompleks komersial;
                                                                                                                                                           c) kompleks publik;
                                                         Yang dimaksud dengan instansi yang berwenang saat ini adalah Kementerian Energi dan               d) kompleks industri;
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                         Sumber Daya Mineral, Direktorat Jenderal Ketenagalistrikan, dengan alamat:                        e) kompleks pertanian dan perkebunan;
                                                                                                                                                           f) bangunan prafabrikasi;
                                                         Jl. H.R. Rasuna Said Blok X-2, Kav. 07-08, Kuningan, Jakarta 12950.                               g) karavan, lokasi karavan dan lokasi serupa;
                                                                                                                                                           h) lokasi pembangunan, pameran, bazar dan instalasi lain untuk keperluan temporer;
                                                         Yang dimaksud dengan Panitia Teknis yang menangani PUIL adalah Panitia Teknis PUIL                i) marina;
                                                         (Persyaratan Umum Instalasi Listrik) yang ditetapkan oleh Badan Standardisasi Nasional.           j) instalasi pencahayaan eksternal dan serupa (namun lihat 11.3e));
                                                                                                                                                           k) lokasi medik;
                                                                                                                                                           l) unit portabel (mobile) atau dapat diangkut;
                                                                                                                                                           m) sistem fotovoltaik;
                                                                                                                                                           n) set pembangkit voltase rendah.
                                                                                                                                                           CATATAN
                                                                                                                                                           “Kompleks” mencakup kawasan dan semua fasilitas termasuk bangunan di atasnya.
                                                                                                                                                           CATATAN
                                                                                                                                                           Persyaratan PUIL dimaksudkan berlaku untuk instalasi listrik secara umum, tapi dalam hal tertentu, mungkin perlu
                                                                                                                                                           ditambah dengan persyaratan atau rekomendasi standar SNI/IEC lain (misalnya untuk instalasi pada atmosfer gas
                                                                                                                                                           ledak, instalasi jaringan voltase rendah milik pelanggan dsb.).
                                                     4    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                          Persyaratan Umum Instalasi Listrik 2011   5
                                                                                                                                                                    13 Prinsip fundamental
                                                     6     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                               Persyaratan Umum Instalasi Listrik 2011   7
                                                     Proteksi harus disediakan terhadap bahaya yang dapat timbul karena sentuh dengan bagian aktif        CATATAN
                                                     instalasi oleh manusia atau ternak.                                                                  Untuk proteksi terhadap sambaran petir langsung, lihat seri IEC 62305.
                                                     Proteksi dapat dicapai dengan salah satu metode berikut:                                             131.6.3 Manusia dan ternak harus diproteksi dari cedera dan harta benda harus diproteksi dari
                                                     - mencegah mengalirnya arus gangguan melalui badan manusia atau ternak;                              kerusakan akibat adanya voltase kurang dan setiap pemulihan voltase sesudah itu.
                                                     - membatasi besarnya arus gangguan yang dapat mengalir melalui badan ke nilai yang tidak
                                                         membahayakan;                                                                                    131.6.4 Instalasi harus mempunyai tingkat imunitas yang memadai terhadap gangguan
                                                     - membatasi durasi arus gangguan yang dapat mengalir melalui badan hingga periode waktu yang         elektromagnetik sedemikian sehingga berfungsi secara benar pada lingkungan yang ditentukan.
                                                         tidak membahayakan.                                                                              Desain instalasi harus mempertimbangkan emisi elektromagnetik terantisipasi, yang ditimbulkan oleh
                                                                                                                                                          instalasi atau perlengkapan terpasang, yang harus sesuai untuk pemanfaat listrik yang digunakan
                                                     131.3 Proteksi terhadap efek termal                                                                  pada, atau dihubungkan dengan instalasi.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     Instalasi listrik harus disusun sedemikian untuk meminimalkan risiko kerusakan atau tersulutnya
                                                     bahan yang mudah terbakar karena tingginya suhu atau busur api listrik. Demikian pula tidak boleh        PENJELASAN
                                                     ada risiko luka bakar pada manusia maupun ternak selama perlengkapan listrik beroperasi secara
                                                     normal.
                                                                                                                                                              Subayat 131.1 hingga 131.6 merupakan persyaratan yang harus dipenuhi untuk proteksi
                                                     131.4 Proteksi terhadap arus lebih                                                                       terhadap keselamatan manusia, ternak dan harta benda. Hal ini akan dijelaskan secara lebih
                                                     Manusia atau ternak harus diproteksi dari cedera, dan harta benda harus diproteksi dari kerusakan        rinci dalam Bagian 4-41 hingga 4-44 PUIL.
                                                     karena suhu yang berlebihan atau stres elektromekanis karena arus lebih yang mungkin timbul pada
                                                     konduktor.
                                                                                                                                                          131.8 Proteksi perlengkapan dan instalasi listrik
                                                     Proteksi ini dapat dicapai dengan membatasi arus lebih ke nilai atau durasi yang aman.
131.6 Proteksi terhadap gangguan voltase dan tindakan terhadap pengaruh elektromagnetik
                                                     131.6.1 Manusia dan ternak harus diproteksi dari cedera dan harta benda harus diproteksi dari
                                                     setiap efek yang berbahaya akibat adanya gangguan antara bagian aktif sirkit yang disuplai pada
                                                     voltase yang berbeda.
                                                     131.6.2 Manusia dan ternak harus diproteksi dari cedera dan harta benda harus diproteksi dari
                                                     kerusakan akibat adanya voltase lebih sedemikian seperti yang berasal dari peristiwa atmosfer atau
                                                     dari penyakelaran.
                                                     8    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                  Persyaratan Umum Instalasi Listrik 2011   9
                                                                                                                                                        131.8.2.2 Instalasi listrik yang sudah memenuhi semua ketentuan tersebut dalam 131.8.2.1 dapat
                                                          PENJELASAN
                                                                                                                                                        dioperasikan setelah mendapat izin atau pengesahan dari instansi/lembaga yang berwenang yang
                                                                                                                                                        menyatakan laik operasi dengan syarat tidak boleh dibebani melebihi kemampuannya.
                                                          Perlengkapan listrik yang memenuhi persyaratan adalah yang memenuhi persyaratan
                                                          standar perlengkapan tersebut, sedangkan untuk perlengkapan listrik yang SNI nya
                                                                                                                                                            PENJELASAN
                                                          dinyatakan wajib, adalah perlengkapan listrik yang sudah lulus pengujian sesuai SNI terkait
                                                          dan mendapatkan sertifikat produk dari Lembaga Sertifikasi Produk yang sudah diakreditasi
                                                          oleh Komite Akreditasi Nasional (KAN), serta diberi label SNI pada produknya.                     Instalasi listrik terpasang harus diverifikasi oleh KONSUIL (Komite Nasional Keselamatan
                                                                                                                                                            untuk Instalasi Listrik) atau PPILN (Perkumpulan Pemeriksa Instalasi Listrik Nasional), yang
                                                                                                                                                            saat ini telah mendapat izin dan pengesahan dari instansi/lembaga yang berwenang,
                                                                                                                                                            yaitu Direktorat Jendral Ketenagalistrikan, Kementerian Energi dan Sumber Daya Mineral.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                            Setelah dinyatakan memenuhi syarat maka instalasi listrik dinyatakan laik operasi dan akan
                                                                                                                                                            diterbitkan Sertifikat Laik Operasi, sehingga instalasi listrik dapat dioperasikan.
                                                                                                                                                        132 Desain
                                                                                                                                                        132.1 Umum
                                                                                                     Gambar - Label SNI
                                                                                                                                                        Dalam desain instalasi listrik, faktor berikut harus diperhitungkan untuk memberikan:
                                                                                                                                                        - proteksi manusia, ternak dan harta benda sesuai dengan 131;
                                                     131.8.1.3 Setiap perlengkapan listrik tidak boleh dibebani melebihi kemampuannya.                  - fungsi yang tepat dari instalasi listrik sesuai dengan maksud penggunaannya.
                                                                                                                                                        Informasi yang disyaratkan sebagai dasar desain disebutkan dalam 132.2 hingga 132.5. Persyaratan
                                                          PENJELASAN                                                                                    yang harus dipenuhi oleh desain dinyatakan dalam 132.6 hingga 132.12.
                                                                                                                                                        132.2.1 Sifat arus: arus bolak-balik (a.b.) dan/atau arus searah (a.s.).
                                                     131.8.2.1 Instalasi yang baru dipasang atau mengalami perubahan harus diperiksa dan diuji dulu
                                                     sesuai dengan ketentuan mengenai :                                                                 132.2.2 Fungsi konduktor:
                                                     a) resistans insulasi (61.3.3);
                                                                                                                                                        - untuk a.b.: konduktor lin; konduktor netral; konduktor proteksi.
                                                     b) pengujian sistem proteksi dengan diskoneksi otomatis suplai (61.3.6);
                                                                                                                                                        - untuk a.s.: konduktor lin; konduktor titik tengah; konduktor proteksi.
                                                     c) pemeriksaan dan pengujian instalasi listrik (Bagian 6 dan 9.5.6).
                                                     10    Persyaratan Umum Instalasi Listrik 2011                                                                                                                           Persyaratan Umum Instalasi Listrik 2011   11
                                                     CATATAN                                                                                                      132.6 Luas penampang konduktor
                                                     Fungsi beberapa konduktor dapat digabungkan dalam konduktor tunggal.                                         Luas penampang konduktor harus ditentukan untuk kondisi operasi normal dan untuk kondisi
                                                                                                                                                                  gangguan sesuai dengan:
                                                                                                                                                                  a) suhu maksimum yang diizinkan;
                                                          PENJELASAN                                                                                              b) drop voltase yang diizinkan;
                                                                                                                                                                  c) stres elektromagnetik yang mungkin terjadi karena arus gangguan bumi dan hubung pendek;
                                                          Yang dimaksud dengan konduktor lin adalah konduktor fase.                                               d) stres mekanis lain yang mungkin mengenai konduktor;
                                                                                                                                                                  e) impedans maksimum berkaitan dengan berfungsinya proteksi hubung pendek;
                                                                                                                                                                  f) metode instalasi.
                                                     132.2.3 Nilai dan Toleransi :
                                                                                                                                                                  CATATAN
                                                     - voltase dan toleransi voltase;
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                                  Butir-butir di atas terutama memperhatikan keselamatan instalasi listrik. Luas penampang yang lebih besar dari
                                                     - pemutusan voltase, fluktuasi voltase dan kedip voltase;a                                                   yang diperlukan untuk keselamatan mungkin dikehendaki untuk operasi yang ekonomis.
                                                     - frekuensi dan toleransi frekuensi;
                                                     - arus maksimum yang diizinkan;
                                                                                                                                                                  132.6.1 Ukuran konduktor dinyatakan dalam satuan metrik.
                                                     - impedans lingkar gangguan bumi di hulu awal instalasi;
                                                     - arus hubung pendek prospektif.                                                                             132.6.2 Jika bahan konduktor tidak dijelaskan dalam PUIL, yang dimaksudkan adalah konduktor
                                                     Untuk voltase dan frekuensi standar, lihat IEC 60038 (SNI 04-0227-2003) dan IEC 60196 (SNI 04-               tembaga.
                                                     1922-2002).
                                                                                                                                                                  132.6.3 Jika digunakan konduktor nontembaga, ukurannya harus disesuaikan dengan kapasitas
                                                     132.5 Kondisi lingkungan                                                                                     hantar arus (KHA) nya.
                                                     Dalam menetapkan kondisi lingkungan penggunaan perlengkapan instalasi, perlu diperhitungkan
                                                     beberapa faktor dan parameter lingkungan terkait, dan dipilih tingkat keparahan akibat parameter
                                                                                                                                                                       PENJELASAN
                                                     lingkungan tersebut. Faktor dan parameter lingkungan tersebut, antara lain:
                                                     a) kondisi iklim                    : dingin/panas, kelembaban, tekanan, gerakan media                            Sesuai Tabel 52.F.2 dan 52.F.3 ukuran luas penampang untuk konduktor aluminium minimum
                                                                                            sekeliling, penguapan, radiasi dan air selain dari hujan;
                                                     b) kondisi biologis                                                                                               adalah 10 mm2.
                                                                                         : flora dan fauna seperti jamur dan rayap;
                                                     c) bahan kimia aktif                : garam, sulfur dioksida, hidrogen sulfit, nitrogen oksida,
                                                                                            ozon,                                                                 132.7 Jenis perkawatan dan cara pemasangan
                                                                                            amonia,klor, hidrogen klorida, hidrogen flor dan
                                                     d) bahan mekanis aktif                                                                                       Pada pemilihan jenis perkawatan dan metode instalasi, hal berikut harus diperhitungkan:
                                                                                         : hidrokarbon organic;                                                   - sifat lokasi;
                                                     e) cairan pengotor                  : pasir, debu, debu melayang, sedimen debu, lumpur dan                   - sifat dinding atau bagian lain bangunan yang menyangga perkawatan;
                                                                                            jelaga;                                                               - dapat teraksesnya perkawatan oleh manusia atau ternak;
                                                     f) kondisi mekanis                  : berbagai minyak, cairan pendingin, gemuk, bahan bakar                  - voltase;
                                                                                            dan air baterai;                                                      - stres elektromekanik yang mungkin terjadi karena arus gangguan bumi dan hubung pendek;
                                                     g) gangguan listrik dan             : getaran, jatuh bebas, benturan, gerakan berputar, deviasi              - interferens elektromagnetik;
                                                         elektromagnet                      sudut, percepatan, beban statis dan roboh;                            - stres lain yang mungkin mengenai perkawatan itu selama pemasangan instalasi listrik atau
                                                                                            medan magnet, medan listrik, harmonik, tegangan sinyal,                   waktu pelayanan.
                                                                                            variasi tegangan dan frekuensi, dan tegangan induksi dan
                                                                                            transien.
                                                     CATATAN
                                                     Desain instalasi listrik harus memperhitungkan kondisi lingkungan yang akan mengenainya, lihat Bagian 5-51
                                                     dan IEC 60721.
                                                     12    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                               Persyaratan Umum Instalasi Listrik 2011   13
                                                     133 Pemilihan perlengkapan listrik                                                                134 Pemasangan dan verifikasi Instalasi listrik
                                                                                                                                                       134.1.1.1 Pengawatan harus dilakukan sehingga bebas dari hubung pendek dan hubung bumi.
                                                          PENJELASAN
                                                                                                                                                       134.1.1.2 Perlengkapan listrik yang dipasang harus bermutu laik pasang dan/atau memenuhi
                                                          Umumnya perlengkapan listrik yang digunakan dalam instalasi listrik sudah ada SNI nya        persyaratan standar.
                                                          (khususnya untuk instalasi rumah tangga dan sejenis) dan sudah diberlakukan sebagai SNI
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                          wajib, misalnya untuk antara lain kabel PVC, kotak kontak dan tusuk kontak, sakelar, GPAS    134.1.1.3 Perlengkapan listrik harus dirawat dengan baik untuk mencegah kemungkinan
                                                          (gawai proteksi arus sisa), luminer. Jadi seharusnya digunakan perlengkapan listrik yang     menurunnya mutu perlengkapan listrik akibat proses tertentu dalam masa penyimpanan, persiapan,
                                                          bertanda SNI.                                                                                pelaksanaan pekerjaan dan masa penggunaan.
                                                                                                                                                       134.1.1.4 Jika tidak ada ketentuan lain, perlengkapan listrik tidak boleh ditempatkan di:
                                                                                                                                                       - daerah lembab atau basah;
                                                                                                                                                       - ruang yang mengandung gas, uap, debu, cairan, atau zat lain yang dapat merusakkan perlengkapan
                                                                                                                                                          listrik;
                                                                                                                                                       - ruang yang suhunya melampaui batas normal (lihat Bagian 8).
                                                                                                                                                       134.1.1.5 Selama masa pembangunan, perlengkapan listrik yang hanya boleh dipasang di ruang
                                                                                                                                                       kering harus dilindungi terhadap cuaca untuk mencegah perlengkapan tersebut mengalami kerusakan
                                                                                                                                                       yang permanen (lihat Bagian 8).
134.1.1.6 Perlengkapan listrik harus dipasang dengan rapi dan dengan cara yang baik dan tepat.
                                                                                                                                                       134.1.1.7 Perlengkapan listrik harus dipasang kokoh pada tempatnya sehingga letaknya tidak
                                                                                                                                                       berubah oleh gangguan mekanis.
                                                                                                                                                       134.1.1.8 Semua peranti listrik yang dihubungkan pada instalasi harus dipasang dan ditempatkan
                                                                                                                                                       secara aman dan, jika perlu, dilindungi agar tidak menimbulkan bahaya.
                                                                                                                                                       134.1.2 Karakteristik tertentu dari perlengkapan listrik seperti tersebut dalam 133, tidak boleh
                                                                                                                                                       memburuk selama pemasangannya.
                                                                                                                                                       134.1.3 Konduktor harus diidentifikasi sesuai IEC 60446. Bila identifikasi terminal diperlukan, terminal
                                                                                                                                                       harus diidentifikasi sesuai IEC 60445.
                                                     14    Persyaratan Umum Instalasi Listrik 2011                                                                                                                         Persyaratan Umum Instalasi Listrik 2011   15
                                                          PENJELASAN
                                                                                                                                                         4.1.2 Skema warna
                                                          Saat ini IEC 60445 dan IEC 60446 sudah direvisi dan digabung menjadi satu: IEC 60445, Basic    Skema warna yang lebih disukai untuk kabel fleksibel dan kabel inti tunggal adalah:
                                                          and safety principles for man-machine interface, marking and identification - Identification
                                                          of equipment terminals, conductor terminations and conductors                                  -   kabel inti tunggal : tidak ada skema warna yang lebih disukai;
                                                                                                                                                         -   kabel dua inti : tidak ada skema warna yang lebih disukai;
                                                          Sesuai SNI 6629.1:2011, “Kabel berinsulasi PVC dengan voltase pengenal sampai dengan           -   kabel tiga inti : hijau-kuning, biru, cokelat; atau cokelat, hitam, abu-abu;
                                                          450/750 V – Bagian 1: Persyaratan Umum”, maka warna konduktor lin adalah hitam, coklat,        -   kabel empat inti : hijau-kuning, cokelat, hitam, abu-abu; atau biru, cokelat, hitam, abu-
                                                          abu-abu.                                                                                                               abu;
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                         -   kabel lima inti : hijau-kuning, biru, cokelat, hitam, abu-abu; atau biru, cokelat, hitam,
                                                          Selengkapnya adalah sbb:                                                                                               abu-abu, hitam;
                                                          4.1 Identifikasi inti dengan warna                                                             Warna harus dapat diidentikasi dengan jelas dan tahan lama. Daya tahannya harus diperiksa
                                                                                                                                                         dengan pengujian sesuai 1.8 IEC 60227-2 (SNI 6629.2).
                                                          4.1.1 Persyaratan umum
                                                          identifikasi inti kabel harus dicapai dengan menggunakan insulasi berwarna atau dengan         CATATAN
                                                          metode lain yang sesuai.                                                                       Untuk konduktor proteksi dan konduktor netral, lihat PENJELASAN 134.1.10.2.
                                                          Setiap initi kabel hanya boleh mempunyai satu warna, kecuali inti yang diidentikasi dengan
                                                          kombinasi warna hijau-kuning.
                                                          Warna hijau dan kuning, jika tidak dikombinasikan, tidak boleh digunakan untuk setiap kabel
                                                          multiinti.
                                                          CATATAN
                                                          Warna merah dan putih sebaiknya dihindari.                                                                                         Gambar - Kabel dua inti
                                                     16     Persyaratan Umum Instalasi Listrik 2011                                                                                                                     Persyaratan Umum Instalasi Listrik 2011   17
                                                                                                                                134.1.4 Hubungan antara konduktor serta antara konduktor dan perlengkapan listrik lain harus
                                                                                                                                dilakukan sedemikian sehingga dipastikan kontak yang aman dan andal.
                                                                                                                                134.1.10.1 Setiap sirkit suplai, rel atau sirkit cabang pada titik sumbernya harus ditandai dengan
                                                                                                                                jelas maksud penggunaannya dengan tanda yang cukup awet terhadap pengaruh cuaca sekitarnya.
                                                                                                                                Penandaan yang demikian itu diperlukan pula bagi setiap sarana pemutus untuk motor dan peranti
                                                                                                                                listrik. Penandaan tidak diperlukan apabila maksud penggunaannya sudah jelas dari penempatannya.
                                                                                                    Gambar - Kabel empat inti   134.1.10.2 Konduktor proteksi dan konduktor netral harus bisa diidentifikasi dengan warna.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
PENJELASAN
                                                                                                                                    Konduktor proteksi harus berwarna loreng hijau-kuning, konduktor netral harus berwarna
                                                                                                                                    biru (lihat 5210 Bagian 5-52 PUIL).
                                                                                                                                134.1.10.3 Sakelar dipasang sehingga kedudukan kontak semua tuas sakelar atau tombol sakelar
                                                                                                                                dalam satu instalasi sebaiknya seragam arahnya, misalnya akan menghubung jika tuasnya didorong
                                                                                                                                ke atas atau tombolnya ditekan.
                                                                                                                                134.1.10.4 Fiting lampu jenis Edison harus dipasang dengan cara menghubungkan kontak dasarnya
                                                                                                                                pada konduktor fase, dan kontak luarnya pada konduktor netral (lihat juga Bagian 5-510).
                                                     18   Persyaratan Umum Instalasi Listrik 2011                                                                                                      Persyaratan Umum Instalasi Listrik 2011   19
                                                     134.1.10.5 Sekering jenis D (Diased) harus dipasang dengan kontak luarnya menghubung pada
                                                                                                                                                            PENJELASAN
                                                     konduktor yang menuju ke beban.
                                                     134.1.10.6 Kotak kontak fase tunggal, baik yang berkutub dua maupun tiga harus dipasang sehingga
                                                     kutub netralnya ada di sebelah kanan atau di sebelah bawah kutub voltase.
                                                          PENJELASAN
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     134.1.11.1 Semua sambungan listrik harus baik dan bebas dari gaya tarik.
                                                                                                                                                         134.1.11.6 Sambungan puntir hanya dapat dilaksanakan:
                                                     134.1.11.2 Sambungan antara konduktor serta antara konduktor dan perlengkapan listrik yang lain
                                                                                                                                                         a) dengan menggunakan kotak sambung dengan pita insulasi dan/atau lasdop;
                                                     harus dibuat sedemikian sehingga terjamin kontak yang aman dan andal.                               b) pada konduktor kabel berpenampang maksimum 2,50 mm2; dan
                                                                                                                                                         c) minimum sebanyak tiga puntiran.
                                                     134.1.11.3 Gawai penyambung seperti terminal tekan, penyambung puntir tekan, atau penyambung
                                                                                                                                                         Sambungan puntir tidak boleh dilakukan pada konduktor pembumian.
                                                     dengan solder harus sesuai dengan bahan konduktor yang disambungnya dan harus dipasang
                                                     dengan baik (lihat juga 2.5.4.4).
                                                                                                                                                            PENJELASAN
                                                     134.1.11.4 Dua konduktor logam yang tidak sejenis (seperti tembaga dan aluminium atau tembaga
                                                     berlapis aluminium) tidak boleh disatukan dalam terminal atau penyambung puntir kecuali jika alat      Persyaratan sambungan puntir ini harus dipenuhi semuanya. Jika salah satu tidak terpenuhi,
                                                     penyambung itu cocok untuk maksud dan keadaan penggunaannya.                                           maka dilarang menyambung dengan sambungan puntir.
                                                                                                                                                            Contoh sambungan puntir dengan lasdop:
                                                     134.1.11. Sambungan konduktor pada terminal harus terjamin kebaikannya dan tidak merusakkan
                                                     konduktor. Menyambung kabel fleksibel harus menggunakan sambungan tekan (termasuk jenis
                                                     sekrup), sambungan solder atau sambungan puntir. Sepatu kabel harus disambungkan dengan mur
                                                     baut secara baik.
                                                                                                                                                            Langkah 1
                                                                                                                                                            Kupas kira-kira 2,5 cm insulasi dari ujung kabel yang akan disambung.
                                                                                                                                                            Puntir ujung kawat tanpa insulasi sedikitnya satu setengah puntiran searah jarum jam.
                                                                                                                                                            Langkah 2
                                                                                                                                                            Potong puntiran kawat hingga sambungan kawat menjadi 1,25 cm.
                                                                                                                                                            Langkah 3
                                                                                                                                                            Tutup sambungan kawat dengan lasdop dengan memuntir searah jarum jam.
                                                                                                                                                                                         Gambar - Sambungan puntir dengan lasdop
                                                     20    Persyaratan Umum Instalasi Listrik 2011                                                                                                                          Persyaratan Umum Instalasi Listrik 2011   21
                                                     134.2 Verifikasi awal
                                                                                                                                                                Bagian 2
                                                          PENJELASAN
                                                     134.2.2 Instalasi dalam pabrik atau bengkel, instalasi dengan 100 titik beban atau lebih, dan instalasi
                                                     dengan daya lebih dari 5 kW, sebaiknya keadaan resistans insulasinya diperiksa secara berkala, dan
                                                     jika resistans insulasinya tidak memenuhi ketentuan atau terlihat adanya gejala penurunan, instalasi
                                                     itu harus diperbaiki.
PENJELASAN
                                                     22    Persyaratan Umum Instalasi Listrik 2011                                                                 Persyaratan Umum Instalasi Listrik 2011   23
                                                     2.3 Cara perhitungan kebutuhan maksimum di sirkit utama
                                                     dan sirkit cabang
                                                     2.3.1 Cara menentukan kebutuhan maksimum                                                              2.3.2.2 Instalasi rumah tunggal dan instalasi rumah ganda
                                                                                                                                                           Untuk instalasi rumah tunggal dan instalasi rumah ganda perhitungan kebutuhan maksimum untuk
                                                     2.3.1.1 Kebutuhan maksimum di sirkit utama dan sirkit cabang harus ditentukan dengan salah satu       tiap fase dari instalasi harus ditentukan dari Tabel 2.3-1 dengan mengambil jumlah dari nilai yang
                                                     cara yang diuraikan di bawah ini.                                                                     diperoleh dengan menerapkan petunjuk yang tepat dalam kolom 2, 3, 4 atau 5 pada kelompok beban
                                                     a) Dengan perhitungan, seperti dikemukakan dalam 2.3.2.                                               A, B dan sebagainya dalam kolom 1.
                                                     b) Dengan penaksiran, seperti dikemukakan dalam 2.3.3.
                                                     c) Dengan pengukuran atau pembatasan, seperti dikemukakan dalam 2.3.4.                                CATATAN
                                                                                                                                                           Contoh perhitungan kebutuhan maksimum untuk instalasi rumah tunggal dan banyak dilampirkan di bagian
                                                     2.3.1.2 Instansi Pemeriksa dapat menetapkan cara yang harus dipakai. Selain ketentuan dalam           belakang Bagian ini.
                                                     2.3.1.1 diberlakukan tambahan persyaratan berikut :
                                                     a) Bila nilai kebutuhan maksimum, yang diperoleh dari pengukuran, melampaui nilai yang                                   Tabel 2.3-1 Kebutuhan maksimum instalasi rumah tunggal dan rumah ganda
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                         diperoleh dari perhitungan atau penaksiran, maka nilai hasil pengukuran inilah yang diambil
                                                                                                                                                                        1                          2                       3                      4                          5
                                                         sebagai kebutuhan maksimum.
                                                                                                                                                            Kelompok beban               Instalasi rumah                               Gedung rumah petak(a,b)
                                                     b) Bagi sirkit utama atau sirkit cabang yang menyuplai sirkit akhir, yang diproteksi dengan pemutus
                                                                                                                                                                                         tunggal atau unit
                                                         daya arus lebih dengan setelan pada nilai tertentu, kebutuhan maksimumnya tidak boleh diambil                                                          2 sampai 5 unit petak 6 sampai 20 unit            21 atau lebih petak
                                                                                                                                                                                         petak per fase         per fase                petak per fase            per fase
                                                         lebih besar dari jumlah nilai setelan arus pemutus daya yang mengamankan sirkit akhir.
                                                                                                                                                                                                                                        Beban satuan hunian
                                                     2.3.2 Perhitungan kebutuhan maksimum di sirkit utama dan sirkit cabang                                 A. Pencahayaan               2 A untuk 1 sampai     6A                      5 A + 0,25 A tiap unit    0,5 A tiap unit petak
                                                                                                                                                            (i) Pencahayaan di           20 titik + 2 A untuk                           petak
                                                     2.3.2.1 Dasar perhitungan
                                                                                                                                                            luar kelompok (ii) dan       tiap tambahan 20
                                                                                                                                                            kelompok beban H di          titik atau bagian
                                                     2.3.2.1.1 Umum
                                                                                                                                                            Bawah (c, m)                 daripadanya
                                                     Kebutuhan maksimum harus dihitung sesuai dengan 2.3.2.2 sampai 2.3.2.3 untuk jenis instalasinya
                                                                                                                                                            (ii) Penca hayaan luar       75 % dari beban                Tidak ada perkiraan untuk tujuan kebutuhan maksimum
                                                     dan perlengkapan yang terpasang. Untuk maksud perhitungan, beban yang tersambung pada setiap
                                                                                                                                                            yang melebihi 1000 W (hl) tersambung
                                                     konduktor aktif harus diperlakukan terpisah.
                                                                                                                                                            B. (i) KKB dan KK yang       5 A untuk 1 sampai     10 A + 5 A tiap unit    15 A +3,75 A tiap         0,5 A + 1,9 A
                                                     2.3.2.1.2 Pertimbangan khusus                                                                          tidak melebihi 10 A (e,      20 titik + 5A          petak                   unit petak                tiap unit petak
Disadari bahwa boleh jadi terdapat perbedaan yang besar dalam pembebanan dari satu instalasi m) Perlengkapan yang untuk tiap tambahan
dengan instalasi lain, termasuk yang dicakup dalam Tabel 2.3-1 dan 2.3-2 dan lainnya seperti tempat tersambung permanen 20 titik atau
ibadah, gedung umum, sekolah, komplek rekreasi dan komplek peristirahatan. Jika beberapa aspek dari tidak melebihi 10 A dan bagian daripadanya
2.3.2 dan Tabel 2.3-1 serta Tabel 2.3-2 dapat digunakan sebagai pedoman dengan memperhatikan tidak termasuk kelompok
semua informasi relevan yang tersedia, suatu cara perhitungan kebutuhan maksimum alternatif beban lain (n).
                                                     24   Persyaratan Umum Instalasi Listrik 2011                                                                                                                                          Persyaratan Umum Instalasi Listrik 2011        25
                                                                                                            Tabel 2.3-1 Lanjutan                                                                                                           Tabel 2.3-1 Lanjutan
                                                                       1                            2                     3                       4                      5                          1                          2                          3                         4                          5
                                                      (iii) Untuk instalasi yang         15 A                    15 A                   15 A                    15 A                    I. KKB dan KKK tidak         Tidak berlaku             2 A per titik             2 A per titik              1 A per titik
                                                      mencakup satu atau lebih                                                                                                          termasuk dalam kelompo
                                                      KK 20 A di luar KK yang                                                                                                           k
                                                      sudah terpasang untuk                                                                                                             J dan M di bawah (d..e.f
                                                      menyuplai perlengkapan                                                                                                            perlengkapan tersambun
                                                      Yang termasuk dalam                                                                                                               g Peranti dengan
                                                                                                                                                                                        J.                           Tidak berlaku             50 % beban                50 % beban                 50 % beban
                                                      kelompok C, D, E, F, G dan                                                                                                        tetap tidak melebihi
                                                                                                                                                                                        kemampuan            10 A.
                                                                                                                                                                                                     lebih dari                                tersambung                tersambung                 tersambung
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     26          Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                                    Persyaratan Umum Instalasi Listrik 2011   27
                                                     CATATAN 1                                                                                                         m) Suatu KK yang terpasang setinggi lebih dari 2,3 m di atas lantai untuk penyambungan ke suatu peranti rumah
                                                     Untuk Tabel 2.3-1:                                                                                                    tangga yang tidak lebih dari 100 W atau suatu luminer dapat dimasukkan sebagai titik pencahayaan dalam
                                                     a) Untuk sambungan multifase, jumlah rumah dibagi jumlah fase dari suplai, contoh: 16 unit rumah yang                 kelompok beban A (i). Suatu peranti tidak lebih dari 100 W, yang tersambung permanen atau tersambung
                                                         disuplai oleh fase tiga, 16/3 = 6 unit tersambung pada fase yang di bebani paling berat (Kolom 4).                pada KK yang terpasang lebih dari 2,3 m di atas lantai dapat dianggap sebagai titik pencahayaan.
                                                     b) Bila hanya sebagian dari jumlah unit dalam instalasi ganda yang dilayani oleh multifase dilengkapi dengan      n) Setiap bagian dari perlengkapan yang tidak melebihi 10 A, yang tersambung secara permanen, dapat
                                                         peranti rumah tangga yang tersambung permanen, misalnya peranti masak listrik atau perlengkapan                   dimasukkan dalam kelompok beban B (i) sebagai titik tambahan.
                                                         pemanas ruangan, jumlah peranti dari setiap kategori di bagi dengan jumlah fase, dan kebutuhan maksimum
                                                         ditentukan seperti dalam contoh –3 di bagian belakang.
                                                                                                                                                                            PENJELASAN
                                                     c) Sistem rel pencahayaan dianggap sebagai 2 titik per meter jalur.
                                                     d) Kelompok beban ini tidak berlaku untuk KK yang terpasang di daerah umum tapi tersambung pada unit
                                                                                                                                                                            Tabel di atas berlaku untuk instalasi dimana besar beban listriknya tidak dibatasi, seperti di
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                          1) Lampu pijar : 60 W atau watt yang sesungguhnya dari lampu yang terpasang, mana yang lebih besar,               Kotak kontak                                           2,5 mm2.
                                                             kecuali bila desain luminer lampu banyak yang terkait dengan fiting hanya memperkenankan lampu
                                                             yang kurang dari 60 W yang dapat dipasang pada fiting, maka beban tersambung dari fiting tersebut              Pengondisi udara (AC) untuk                               2,5 mm2.
                                                             harus sama dengan watt lampu terbesar yang dapat dilayani. Untuk luminer lampu banyak beban setiap
                                                                                                                                                                            rumah tangga dan sejenis
                                                             fiting lampu harus ditetapkan berdasarkan di atas.
                                                          2) Lampu TL dan lampu luah lainnya: Beban penuh tersambung, yaitu arus yang sesungguhnya diserap
                                                             oleh susunan pencahayaan, dengan memperhitungkan perlengkapan bantu seperti balas dan kapasitor.
                                                             Faktor daya dari lampu TL dan lampu luah lainnya tidak boleh kurang dari 0,85.
                                                          3) Rel pencahayaan: 0,5 A/m per fase per rel atau beban yang sesungguhnya tersambung, mana yang
                                                             lebih besar
                                                     28    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                 Persyaratan Umum Instalasi Listrik 2011   29
                                                                                                    Bagian 3
                                                                                                    Asesmen
                                                                                                    karakteristik umum
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     30   Persyaratan Umum Instalasi Listrik 2011     Persyaratan Umum Instalasi Listrik 2011   31
                                                     312.2 Jenis pembumian sistem
Huruf kedua – Berkaitan dengan bagian konduktif terbuka (BKT) instalasi ke bumi.
                                                     T = hubungan listrik langsung dari BKT ke bumi, tidak tergantung pada pembumian sembarang
                                                          titik sistem daya.
                                                     N = hubungan listrik langsung BKT ke titik sistem daya yang dibumikan (dalam sistem a.b., titik yang
                                                         dibumikan dari sistem daya secara normal adalah titik netral atau, jika titik netral tidak ada, konduktor lin).
Huruf berikutnya (jika ada) – Susunan konduktor netral dan konduktor proteksi.
                                                     S = fungsi proteksi diberikan oleh konduktor yang terpisah dari konduktor netral atau dari
                                                         konduktor lin yang dibumikan (atau dalam sistem a.b. fase yang dibumikan).
C = fungsi netral dan proteksi digabung dalam konduktor tunggal (konduktor PEN).
                                                                          Penjelasan simbol pada Gambar 31A1 hingga 31M menurut IEC 60617-11                                   CATATAN Pembumian tambahan dari PE pada instalasi dapat diberikan.
                                                                                                     Konduktor netral (N), konduktor titik tengah (M)
                                                                                                                                                                                 Gambar 31A1 - Sistem TN-S dengan konduktor netral dan konduktor proteksi terpisah pada seluruh sistem
                                                                                                     Konduktor proteksi (PE)
312.2.1 Sistem TN
                                                     32    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                  Persyaratan Umum Instalasi Listrik 2011   33
                                                          PENJELASAN                                                                                          PENJELASAN
                                                          Sistem ini merupakan sistem yang lengkap, karena mempunyai 5 konduktor untuk sistem                 Sistem ini adalah sistem yang paling lazim di Indonesia.
                                                          trifase atau 3 konduktor untuk sistem fase tunggal pada jaringan distribusinya. Sistem
                                                          ini tidak lazim dipakai, karena dianggap boros, karena itu sistem yang lazim adalah yang            Ciri-ciri sistem TN-C-S:
                                                          mempunyai 4 konduktor untuk sistem trifase dan 2 konduktor untuk sistem fase tunggal                - satu titik sumber dibumikan (kode T);
                                                          pada jaringan distribusi. Jadi konduktor PE dan netral sumber digabung pada satu konduktor          - BKT (Bagian Konduktif Terbuka) dihubungkan ke konduktor PE yang tergabung dengan
                                                          PEN. Contoh: jaringan distribusi PLN.                                                                    konduktor N, untuk kemudian dibumikan (kode N);
                                                                                                                                                              - konduktor proteksi PE dan konduktor netral N dari sumber (PLN) digabung menjadi satu
                                                                                                                                                                   konduktor PEN (kode C);
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     Pada sistem TN–C-S, fungsi konduktor netral dan konduktor proteksi digabungkan dalam konduktor           - konduktor PE dan konduktor N pada instalasi pelanggan terpisah (kode S), tapi
                                                     tunggal pada sebagian sistem (lihat Gambar 31B2).                                                             dihubungkan di satu titik, biasanya di panel pelanggan (biasa disebut “dijumper”). Pada
                                                                                                                                                                   Gambar dihubungkan di titik awal instalasi;
                                                     CATATAN                                                                                                  - jadi merupakan kombinasi antara sistem TN, C dan S, karena itu dinamakan TN-C-S.
                                                     Untuk simbol lihat penjelasan yang diberikan pada 312.2
                                                                                                                                                              BKT (Bagian Konduktif Terbuka - exposed conductive part) adalah bagian konduktif
                                                                                                                                                              perlengkapan yang dapat disentuh dan yang secara normal tidak bervoltase, tetapi dapat
                                                                                                                                                              menjadi bervoltase bila insulasi dasar gagal (terjadi hubung pendek). BKT dapat berupa
                                                                                                                                                              selungkup atau bodi peralatan/perlengkapan.
                                                                                                                                                         312.2.2 Sistem TT
                                                                                                                                                         Sistem TT hanya mempunyai satu titik yang dibumikan langsung dan BKT instalasi dihubungkan ke
                                                                                                                                                         elektrode bumi yang independen secara listrik dari elektrode bumi sistem suplai (lihat Gambar 31F1).
CATATAN Pembumian tambahan dari PEN pada distribusi dan PE pada instalasi dapat diberikan.
                                                                       Gambar 31B2 - Sistem TN-C-S trifase, 4-kawat dengan PEN terpisah menjadi PE dan
                                                                                            N di awal instalasi (lazim di Indonesia)
Gambar 31F1 – Sistem TT dengan konduktor netral dan konduktor proteksi terpisah di seluruh instalasi
                                                     34      Persyaratan Umum Instalasi Listrik 2011                                                                                                                                Persyaratan Umum Instalasi Listrik 2011   35
                                                          PENJELASAN                                                                                                                                  PENJELASAN
                                                          Sistem ini adalah sistem yang lazim di Eropa. Di Indonesia, terutama digunakan untuk                                                        Sistem IT juga lazim digunakan di Indonesia, khususnya digunakan untuk instalasi yang
                                                          instalasi yang banyak memakai perangkat elektronik atau komunikasi..                                                                        memerlukan kontinuitas pelayanan (misalnya pada sebagian instalasi rumah sakit). Pada
                                                                                                                                                                                                      sistem ini bila terjadi gangguan pertama, gawai proteksi tidak akan trip (terbuka).
                                                          Ciri-ciri sistem TT:
                                                          - satu titik sumber dibumikan (kode T);                                                                                                     Ciri-ciri sistem IT:
                                                          - BKT dihubungkan ke konduktor PE untuk kemudian langsung dibumikan tanpa                                                                   - sumber diisolasi atau dihubungkan dengan impedans yang cukup tinggi terhadap bumi,
                                                               dihubungkan ke konduktor N (kode T);                                                                                                        sehingga dapat dianggap diisolasi juga (kode I).
                                                          - konduktor PE dan konduktor N pada instalasi terpisah di seluruh instalasi. Karena itu ciri                                                - BKT dihubungkan ke konduktor PE untuk kemudian langsung dibumikan tanpa
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                               utama sistem TT terminal netral N dan terminal konduktor proteksi PE di dalam panel                                                         dihubungkan ke konduktor N (kode T);
                                                               pelanggan tidak dihubungkan.                                                                                                           - konduktor PE dan konduktor N instalasi terpisah di seluruh instalasi.
                                                                                                                                                                                                      - konduktor N dapat didistribusikan (lazim di Indonesia) atau tidak didistribusikan di
                                                                                                                                                                                                           seluruh instalasi.
                                                     312.2.3 Sistem IT
                                                     Sistem daya IT mempunyai semua bagian aktif diisolasi dari bumi atau satu titik dihubungkan ke
                                                     bumi melalui impedans. BKT instalasi listrik dibumikan secara independen atau secara kolektif atau ke                                            PENJELASAN
                                                     pembumian sistem menurut 411.6 Bagian 4-41 (lihat Gambar 31G1).
                                                                                                                                                                                                      Sistem pembumian TN-C-S, TT dan IT seperti di atas adalah sistem pembumian yang lazim di
                                                                                                                                                                                                      Indonesia, walaupun dalam PUIL 2011 dimungkinkan sistem pembumian lain.
                                                                                                                                                                                                      Misalnya TN-S, sistem ini tidak lazim di Indonesia karena mensyaratkan 5 konduktor dari
                                                                                                                                                                                                      sumber (3 konduktor lin, 1 konduktor netral dan 1 konduktor proteksi) untuk trifase atau 3
                                                                                                                                                                                                      konduktor (1 konduktor lin, 1 konduktor netral dan 1 konduktor proteksi), yang di Indonesia
                                                                                                                                                                                                      PLN tidak menyediakannya. PLN hanya menyediakan 4 konduktor (3 konduktor lin dan 1
                                                                                                                                                                                                      konduktor netral) untuk trifase dan 2 konduktor (1 konduktor lin dan 1 konduktor netral
                                                                                                                                                                                                      untuk fase tunggal.
                                                                                                                                                                                                      Rekomendasi pemilihan sistem TT, TN dan IT dijelaskan dalam Lampiran F Bagian 4-41 seperti
                                                                                                                                                                                                      di bawah ini.
                                                          CATATAN Pembumian tambahan dari PE pada instalasi dapat diberikan.
                                                          1)    Sistem dapat dihubungkan ke bumi melalui impedans yang cukup tinggi. Hubungan ini dapat dilakukan misalnya pada titik netral, titik
                                                                 netral buatan, atau konduktor lin.
                                                          2)    Konduktor netral dapat didistribusikan atau tidak didistribusikan.
                                                     36        Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                         Persyaratan Umum Instalasi Listrik 2011   37
                                                                                                                                                                            314 Pembagian instalasi
                                                                                                                                                                            314.1 Setiap instalasi harus dibagi dalam sirkit, jika diperlukan, untuk:
                                                                                          Rekomendasi pemilihan sistem TT, TN dan IT                                        -   mencegah bahaya dan meminimalkan kesulitan jika terjadi gangguan;
                                                                               Proteksi          Gawai
                                                                                                                                                                            -   memfasilitasi inspeksi, pengujian dan pemeliharan yang aman (lihat juga Bagian 5-53);
                                                                                                                Gawai                                                       -   memperhitungkan bahaya yang mungkin timbul dari kegagalan sirkit tunggal seperti sirkit
                                                                Jenis        tambahan           proteksi
                                                           pembumian          terhadap           untuk
                                                                                                              proteksi          Rekomendasi         Contoh penerapan            pencahayaan;
                                                                sistem         sentuh         sentuh tak
                                                                                                           untuk bahaya                                                     -   mengurangi kemungkinan trip yang tak diinginkan dari GPAS karena arus konduktor PE yang
                                                                              langsung         langsung
                                                                                                            kebakaran                                                           berlebihan
                                                                                                                                                                            -   yang tidak disebabkan gangguan;
                                                          1.Sistem TT      GPAS ≤ 30 mA GPAS               GPAS ≤ 500     Bila proteksinya lengkap Semua bangunan
                                                                                                                                                                            -   mengurangi efek EMI;
                                                                                                           mA             ,                        perkantoran dan
                                                                                                                                                                            -   mencegah energisasi tak langsung pada sirkit yang dimaksudkan akan diisolasi.
                                                                                                                          direkomendasikan untu industri yang
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                          k                         memerlukan instalasi
                                                                                                                          instalasi dengan risiko   yang handal,                PENJELASAN
                                                                                                                          bahaya dan gangguan       termasuk gedung
                                                                                                                          paling kecil, termasuk    pintar dan industri         Pembagian instalasi harus memperhatikan Subayat 511.2.5, Pengelompokan perlengkapan
                                                                                                                          masalah kesesuaian        komputer, elektronik,       sirkit dari Bagian 5-511 PUIL sbb:
                                                                                                                          elektromagnet             telekomunikasi.
                                                          2.Sistem TN-S    GPAS ≤ 30 mA GPAL atau          GPAS ≤ 500     (KEM atau
                                                                                                                          Seperti     EMC)
                                                                                                                                  sistem TT         Seperti sistem TT           “Pada PHBK yang mempunyai banyak sirkit keluar fase tunggal, dan fase tiga, baik untuk
                                                                                              GPAS         mA                                                                   instalasi daya maupun instalasi pencahayaan, gawai proteksi, sakelar, dan terminal yang
                                                          3.Sistem TN-C    Tidak bisa         GPAL         Tidak bisa     Dilarang karena risiko                                serupa harus dikelompokkan sehingga:
                                                                                                                          sentuh langsung dan
                                                                                                                          kebakaran tinggi serta
                                                                                                                                                                                a) kelompok perlengkapan instalasi daya sebaiknya terpisah dari kelompok perlengkapan
                                                                                                                          mempunyai masalah                                        instalasi pencahayaan;
                                                                                                                          KEM                                                   b) kelompok perlengkapan fase tunggal, fase dua, dan fase tiga merupakan kelompok
                                                          4.SistemTN-      GPAS ≤ 30 mA GPAL atau          GPAS ≤ 500     Dengan konduktor          Untuk rumah
                                                                                                                                                                                   sendiri sendiri yang terpisah”.
                                                          C-S                                 GPAS         mA             netral dihubungkan        tangga, industri dan
                                                                                                                          dengan konduktor          perkantoran yang
                                                                                                                          proteksi di PHBK          tidak peka terhadap
                                                                                                                          konsumen, serta           masalah KEM.
                                                                                                                          dibumikan, merupakan
                                                                                                                          sistem yang umum
                                                                                                                          berlaku di Indonesia
                                                          5.Sistem IT      GPAS ≤ 30 mA Gawai              GPAS ≤ 500     Direkomendasikan          Untuk ruang khusus
                                                                                              monitor      mA             jika kontinuitas suplai   di rumah sakit,
                                                                                              insulasi                    menjadi kebutuhan         dan industri atau
                                                                                              GPAL atau                   utama                     perkantoran khusus
                                                                                              GPAS
                                                          Keterangan
                                                          a) GPAS: Gawai Proteksi Arus Sisa; GPAL: Gawai Proteksi Arus Lebih.
                                                          b) Untuk proteksi dengan mempergunakan lebih dari satu jenis gawai proteksi, maka perlu diperha
                                                          tikan
                                                               koordinasinya.
                                                     38     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                          Persyaratan Umum Instalasi Listrik 2011   39
                                                                                                    Bagian 4 - 41
                                                                                                    Proteksi untuk
                                                                                                    keselamatan –
                                                                                                    Proteksi terhadap
                                                                                                    kejut listrik
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     40   Persyaratan Umum Instalasi Listrik 2011     Persyaratan Umum Instalasi Listrik 2011   41
                                                                                                                                                                 411 Tindakan proteksi : diskoneksi otomatis suplai
                                                     410.3.3 Dalam setiap bagian instalasi harus diterapkan satu atau lebih tindakan proteksi, dengan            411.1 Umum
                                                     memperhitungkan kondisi pengaruh eksternal.
                                                     Tindakan proteksi berikut biasanya diizinkan:                                                               Diskoneksi otomatis suplai adalah tindakan proteksi yang:
                                                     - diskoneksi otomatis suplai (Ayat 411),                                                                    - proteksi dasar diberikan dengan insulasi dasar bagian aktif atau dengan penghalang atau
                                                     - insulasi dobel atau diperkuat (Ayat 412),                                                                     selungkup, sesuai dengan Lampiran A, dan
                                                     - separasi listrik untuk suplai dari satu pemanfaat listrik (Ayat 413),                                     - proteksi gangguan diberikan dengan ikatan ekuipotensial proteksi dan diskoneksi otomatis dalam
                                                     - voltase ekstra rendah (SELV atau PELV) (Ayat 414).                                                            hal gangguan sesuai dengan 411.3 hingga 411.6.
                                                     Tindakan proteksi yang diterapkan dalam instalasi harus dipertimbangkan pada pemilihan dan
                                                     pemasangan perlengkapan.                                                                                    CATATAN 1
                                                     Untuk instalasi tertentu lihat 410.3.4 hingga 410.3.9.                                                      Jika tindakan proteksi ini diterapkan, dapat juga digunakan perlengkapan Kelas II.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     CATATAN                                                                                                     Jika ditentukan, proteksi tambahan diberikan dengan gawai proteksi arus sisa (GPAS) dengan arus operasi
                                                     Dalam instalasi listrik tindakan proteksi yang paling banyak digunakan adalah diskoneksi otomatis suplai.   sisa pengenal tidak melebihi 30 mA sesuai dengan 415.1.
                                                     410.3.5 Tindakan proteksi yang ditentukan dalam Lampiran B, yaitu penggunaan perintang dan
                                                                                                                                                                     PENJELASAN
                                                     penempatan di luar jangkauan, hanya digunakan dalam instalasi yang dapat diakses oleh
                                                     - personel terampil atau terlatih, atau
                                                     - personel yang diawasi oleh personel terampil atau terlatih.                                                   Mengapa nilai arus sampai sebesar 30 mA a.b., dianggap batas aman bagi manusia?
                                                     410.3.6 Tindakan proteksi, yang ditentukan dalam Lampiran C, yaitu                                              Acuannya adalah Technical Specification IEC/TS 60479-1, yang memberikan pedoman
                                                     - lokasi nonkonduktif,                                                                                          dasar pada efek arus kejut listrik pada manusia dan ternak, untuk digunakan menetapkan
                                                     - ikatan ekuipotensial lokal bebas bumi,                                                                        persyaratan keselamatan listrik.
                                                     - separasi listrik untuk suplai lebih dari satu pemanfaat listrikt,
                                                     dapat diterapkan hanya jika instalasi berada di bawah supervisi personel terampil atau terlatih                 Untuk menghindari kesalahan dalam interpretasi dokumen ini, harus ditekankan bahwa data
                                                     sedemikian sehingga perubahan tidak sah tidak dapat dilakukan.                                                  yang diberikan dalam dokumen utamanya berdasar pada eksperimen dengan hewan dan
                                                                                                                                                                     informasi yang tersedia dari observasi klinis. Hanya beberapa eksperimen dengan arus kejut
                                                                                                                                                                     berdurasi singkat dilakukan pada manusia hidup.
                                                          PENJELASAN
                                                                                                                                                                     Dalam bukti yang tersedia, kebanyakan berasal dari riset terhadap hewan, nilai-nilainya
                                                          Hal ini berarti tindakan proteksi sesuai Lampiran B dan C tidak dapat diterapkan pada                      sedemikian konservatif sehingga dokumen ini berlaku pada manusia dalam kondisi fisiologis
                                                          instalasi rumah tangga dan sejenis, karena tidak ada personel terampil atau terlatih.                      normal, termasuk anak-anak, tidak tergantung usia dan beratnya.
                                                                                                                                                                     Dari penelitian dalam IEC/TS 60479-1 itu, secara garis besar diperoleh data, antara lain
                                                                                                                                                                     sebagai berikut:
                                                     42    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                       Persyaratan Umum Instalasi Listrik 2011   43
                                                           -      jenis sumber daya (a.b. atau a.s.); dan                                                                          *Untuk durasi aliran arus kurang dari 10 ms, batas untuk arus melalui tubuh, untuk garis b tetap
                                                           -      besarnya voltase sentuh; dan                                                                                     konstan pada nilai 200 mA.
                                                           -      lintasan arus melalui tubuh (tangan ke tangan, atau kedua tangan ke kedua kaki, atau                             Dari grafik tersebut nampak bahwa nilai ambang batas arus aman (threshold current) = 30 mA.
                                                                  satu tangan ke kursi); dan                                                                                       Kurva c1, merupakan kurva yang paling penting, karena merupakan ambang batas pengaruh besar arus
                                                           -      luas area kontak dengan kulit; dan                                                                               yang mengalir dalam tubuh manusia yang mulai menimbulkan bahaya kejut listrik terhadap jantung
                                                           -      kondisi area kontak kulit (basah air garam, basah air dan kering).                                               manusia, yang dapat mengakibatkan kematian.
                                                           2. Berdasarkan penelitian atas ketahanan manusia dan ternak terhadap pengaruh besarnya
                                                              arus listrik yang mengalir pada tubuh manusia dan ternak diperoleh grafik: Durasi arus                           CATATAN
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                              yang mengalir (ms) vs Nilai arus yang mengalir (mA), sbb:                                                        Monitor arus sisa (MAS) bukan gawai proteksi tetapi gawai ini dapat digunakan untuk memantau arus
                                                                                                                                                                               sisa pada instalasi listrik. MAS menghasilkan sinyal bunyi atau sinyal bunyi dan viasual bila nilai arus
                                                                                                                                                                               sisa prapilih dilampaui.
                                                                Zona                   Batas                                      Efek Fisiologis                                  Pemasangan GPAS untuk keperluan proteksi ini, dapat dilakukan pada PHB diawal instalasi
                                                           AC-1              s /d 0,5 mA kurva a         Pada umumnya tidak ada reaksi atau kesemutan ringan                       (sesuai standar SNI 04-6956.1-2003 dan SNI 04-6956.2.1-2005, yang dinyatakan sebagai
                                                           AC-2              0,5 mA s/d kurva b*         Ada getaran kejut, tapi tidak ada efek fisiologis yang membahayakan
                                                                                                                                                                                   SNI wajib) maupun di setiap masing-masing kotak kontak (sesuai standar IEC 62640, Ed.1).
                                                           AC-3              Kurva b s/d kurva c1        Umumnya tidak ada kerusakan organis. Ada kejang otot dan kesulita         SNI 04-6956.1-2003 dan SNI 04-6956.2.1-2005 merupakan standar GPAS berjenis RCCB,
                                                                                                         n
                                                                                                         pernafasan                                                                yaitu GPAS tanpa proteksi arus lebih terpadu untuk pemakaian rumah tangga dan sejenisnya.
                                                           AC-4              Diatas kurva c1             Penambahan durasi waktu & nilai arus akan menambah efek
                                                                                                         patofisiologis yang berbahaya, semacam jantung berhenti, pernafasa
                                                                                                         n
                                                                                                         berhenti, terbakar parah dapat terjadi.
                                                           AC-4.1            c1 – c2                     Probabilitas jantung berhenti bertambah s/d 5 %.
                                                           AC-4.2            c2 – c3                     Probabilitas jantung berhenti s/d 50 %.
                                                           AC-4.3            Diatas kurva c3             Probabilitas jantung berhenti diatas 50 %.
                                                     44        Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                     Persyaratan Umum Instalasi Listrik 2011   45
                                                                                                                                                             PENJELASAN
                                                                                                                                                             Konduktor PEN hanya boleh digunakan untuk sirkit masuk, yaitu sirkit antara panel PLN dan
                                                                                                                                                             panel pelanggan.
                                                                                                                                                        411.4.4 Karakteristik gawai proteksi (lihat 411.4.5) dan impedans sirkit harus memenuhi
                                                                                                                                                        persyaratan berikut:
                                                                                                                                                                                                            Zs × Ia ≤ U0
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                        dengan
                                                                                                                                                        Zs adalah impedans dalam ohm (Ω) dari lingkar gangguan yang terdiri atas:
                                                                                                                                                        - sumber,
                                                                                                                                                        - konduktor lin hingga titik gangguan, dan
                                                                                                                                                        - konduktor proteksi antara titik gangguan dan sumber;
                                                                                 Gambar RCCB - Contoh GPAS untuk proteksi beban rumah tangga            Ia adalah arus dalam Ampere (A) yang menyebabkan operasi otomatis gawai diskoneksi dalam waktu
                                                                                                                                                        yang ditentukan dalam 411.3.2.2 atau 411.3.2.3. Bila GPAS digunakan, arus ini adalah arus sisa operasi
                                                          GPAS yang dipasang dapat yang berjenis ;                                                      menyebabkan diskoneksi dalam waktu yang ditentukan dalam 411.3.2.2 atau 411.3.2.3.
                                                          a. yang beroperasi tak bergantung pada voltase lin (jenis VI - Voltage Independent), atau
                                                          b. yang beroperasi bergantung pada voltase lin (jenis VD - Voltage Dependent).                U0 adalah voltase nominal dalam volt (V) a.b. atau a.s. lin ke bumi.
                                                          Selain jenis di atas, ada jenis lain yaitu RCBO, GPAS dilengkapi dengan proteksi arus lebih   CATATAN
                                                          terpadu (IEC 61009) dan GPAS yang biasa digunakan untuk industri yang dikenal sebagai CBR     Jika kesesuaian dengan subayat ini diberikan oleh GPAS, waktu diskoneksi sesuai Tabel 41.1 berkaitan dengan arus
                                                          berdasarkan IEC 60947-2.                                                                      gangguan sisa prospektif lebih tinggi secara signifikan dari arus sisa operasi GPAS (biasanya 5 I∆n )
                                                          Pada perlengkapan mobil pasangan luar, dapat dipasang GPAS sesuai dengan standar IEC          411.4.5 Dalam sistem TN, gawai proteksi berikut dapat digunakan untuk proteksi gangguan
                                                          61540, Ed 1.1                                                                                 (proteksi terhadap sentuh tak langsung):
                                                                                                                                                        - gawai proteksi arus lebih (GPAL);
                                                          Untuk pemilihan GPAS menurut metode penerapannya, lihat ayat 531.2.2 (6.7.2.2.2)              - gawai proteksi arus sisa (GPAS).
CATATAN 1
                                                     411.4.3 Pada instalasi magun, konduktor tunggal dapat berfungsi sebagai konduktor proteksi         Bila GPAS digunakan untuk proteksi gangguan sirkit sebaiknya juga diproteksi dengan GPAL sesuai IEC 60364-
                                                                                                                                                        4-43.
                                                     maupun sebagai konduktor netral (konduktor PEN) asalkan persyaratan 543.3 dari IEC 60364-5-54
                                                     dipenuhi. Tidak boleh disisipkan gawai sakelar atau gawai isolasi pada konduktor PEN.              GPAS tidak boleh digunakan dalam sistem TN-C
                                                     Sistem TN-C dilarang, maka tidak boleh digunakan konduktor PEN setelah PHBK, kecuali hanya untuk   Bila GPAS digunakan dalam sistem TN-C-S, konduktor PEN tidak boleh digunakan pada sisi beban.
                                                     sirkit masuk.                                                                                      Hubungan konduktor proteksi ke konduktor PEN harus dilakukan pada sisi sumber GPAS.
                                                     46    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                     Persyaratan Umum Instalasi Listrik 2011   47
                                                     CATATAN 2
                                                     Bila diperlukan diskriminasi antar GPAS, lihat 535.3 Bagian 5-53.                                          KETERANGAN :
                                                                                                                                                                Besarnya arus gangguan Id = 230 V/Zs , dimana pada umumnya nilai Zs sangat kecil, sehingga
                                                          Bila terjadi kegagalan insulasi, arus gangguan Id hanya dibatasi oleh impedans dari kabel             arus gangguan Id punya nilai besar, dalam kisaran diatas 1 000 A.
                                                          lingkar gangguan (lihat Gambar)
                                                                                                                                                                Bila dipasang GPAL sebagai gawai proteksi dan terjadi gangguan maka diperlukan arus
                                                                                                                                                                gangguan sebesar minimal sebesar 5 x In GPAL yang terpasang (untuk jenis C), agar GPAL
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
(MCB) tersebut dapat bekerja sebagai Gawai Proteksi Hubung Pendek sehingga trip.
                                                                                                                                                                               Tipe                                          Julat
                                                                                                                                                                                 B            Diatas 3 In sampai dengan 5 In
                                                                                                                                                                                 C            Diatas 5 In sampai dengan 10 In
                                                                                                                                                                                CL            Diatas 4 In sampai dengan 6 In
                                                                                                                                                                                D             Diatas 10 In sampai dengan 20 In a
                                                                                                                                                                    a   Untuk kasus khusus dapat digunakan nilai sampai 50 In
                                                                                                                                                                Diskoneksi dapat dilakukan dengan GPAL, dengan waktu pemutusan maksimum seperti
                                                                                                                                                                dalam Tabel 41.1.
                                                          Gambar 31B2 – Sistem TN-C-S trifase, 4 kawat dengan PEN terpisah menjadi PE dan N di awal instalasi   Selain itu harus dipasang proteksi dengan GPAS ≤ 30 mA, sesuai subayat 415.1
                                                                                                   (lazim di Indonesia)
                                                          dengan
                                                          - Rph    = impedans lin
                                                          - RPE   = impedans konduktor proteksi
                                                          - Rd    = impedans hubung pendek, dianggap = 0
                                                          - Zs     = impedans lingkar gangguan = Rs + Rph + RPE
                                                     48    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                   Persyaratan Umum Instalasi Listrik 2011   49
                                                     411.5 Sistem TT                                                                                               CATATAN 1
                                                                                                                                                                   Proteksi gangguan dalam hal ini dilengkapi juga jika impedans gangguan tidak dapat diabaikan.
                                                     Lihat Gambar 31F.1 Bagian 3.
                                                                                                                                                                   CATATAN 2
                                                                                                                                                                   Jika diperlukan diskriminasi antar GPAS lihat 535.3 dari IEC 60364-5-53.
                                                                                                                                                                   CATATAN 3
                                                                                                                                                                   Jika RA tidak diketahui, hal ini dapat diganti dengan ZS.
                                                                                                                                                                   CATATAN 4
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                                   Waktu diskoneksi sesuai Tabel 41.1 berkaitan dengan arus gangguan sisa lebih tinggi signifikan dari arus operasi
                                                                                                                                                                   sisa pengenal dari GPAS (biasanya 5 I∆n ).
PENJELASAN
                                                                                                                                                                        Bila terjadi kegagalan insulasi, arus gangguan Id dibatasi oleh impedans dari kabel gangguan
                                                                                                                                                                        dan Ra dan Rb, dimana Ra dan Rb jauh lebih besar dari impedans lingkar gangguan.
                                                     411.5.1 Semua BKT yang secara kolektif diproteksi oleh gawai proteksi yang sama harus dihubungkan
                                                     dengan konduktor proteksi ke elektrode bumi bersama pada semua bagian tersebut. Jika digunakan
                                                     beberapa gawai proteksi dalam seri, persyaratan ini berlaku secara terpisah pada semua BKT yang
                                                     diproteksi oleh masing-masing gawai.
                                                     Titik netral atau titik tengah dari sistem suplai daya harus dibumikan. Jika titik netral atau titik tengah
                                                     tidak ada atau tidak dapat diakses, konduktor lin harus dibumikan.
                                                     411.5.2 Dalam sistem TT, GPAS harus digunakan untuk proteksi gangguan (proteksi sentuh tak
                                                     langsung).
                                                                                                                                                                          Gambar 31F1 - Sistem TT dengan konduktor netral dan konduktor proteksi terpisah di seluruh instalasi
                                                     Selain GPAS untuk proteksi gangguan, sirkit harus juga diproteksi dengan GPAL sesuai Bagian 4-43.
                                                     CATATAN
                                                     Penggunaan gawai proteksi yang dioperasikan oleh voltase gangguan tidak tercakup dalam standar ini.
                                                     411.5.3 Bila digunakan GPAS untuk proteksi gangguan, kondisi berikut harus dipenuhi:
                                                     i) waktu diskoneksi seperti disyaratkan oleh 411.3.2.2 atau 411.3.2.4, dan
                                                     ii) RA × I∆n ≤ 50 V dengan RA adalah jumlah resistans dalam Ω dari elektrode bumi dan konduktor
                                                         proteksi untuk BKT, I∆n adalah arus operasi sisa GPAS.
                                                     50    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                               Persyaratan Umum Instalasi Listrik 2011   51
                                                          dengan                                                                                         Diperoleh grafik Waktu-Voltase sentuh yang bervariasi berdasarkan :
                                                          Uo    : voltase lin – netral                                                                   -      Kondisi kelembaban kulit di titik kontak (kering, basah air dan basah air garam);
                                                          Ud    : voltase gangguan – bumi                                                                -      Luas area kontak (besar, medium dan kecil);
                                                          Id     : arus gangguan                                                                         -      Lintasan arus dalam tubuh (tangan ke tangan, tangan ke kaki dan tangan ke kursi).
                                                          Ra   : resistans PE                                                                            Dalam penjelasan ini hanya diambil dua (2) contoh grafik Waktu-Voltase sentuh dalam
                                                          Rb   : resistans pembumian                                                                     kondisi kering dengan luas area kontak besar dan medium.
                                                          RA   : Ra + Rb
                                                                                                                                                         Diambil nilai grafik c1, pada durasi waktu maksimum yaitu t = 10 detik.
                                                          KETERANGAN :
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                          Dengan persyaratan RA × I∆n ≤ 50 V, maka hal ini dapat dipenuhi oleh GPAS, karena I∆n
                                                          sangat kecil, hanya 30 mA.
PERTANYAAN :
Mengapa voltase sentuh (UL) yang dianggap aman ,dalam kondisi kering adalah 50 V a.b ?
PENJELASAN:
                                                          Dari hasil penelitian dalam IEC/TS 60479-1, diperoleh nilai Impedans tubuh yang tidak linear
                                                          dan Grafik Waktu- Arus (Zona Waktu/Arus konvensional efek arus a.b. (15 Hz -100 Hz pada
                                                          orang untuk lintasan arus dari tangan kiri ke kaki).
                                                          Untuk lintasan arus melalui tubuh manusia, bahaya kepada manusia terutama tergantung
                                                          kepada besaran dan durasi aliran arus.
                                                          Namun, zona waktu-arus yang ditentukan dalam ayat-ayat berikut, dalam beberapa kasus,
                                                          tidak dapat diterapkan langsung dalam praktik untuk mendesain tindakan proteksi terhadap
                                                          kejut listrik.
                                                          Kriteria yang diperlukan adalah batas voltase sentuh yang diizinkan (yaitu perkalian arus
                                                          yang melalui tubuh, yang disebut arus sentuh dan impedans tubuh) sebagai fungsi waktu.
                                                          Dengan menggunakan data dari IEC/TS 60479-1, IEC/TS 60479-5 memberikan metodologi
                                                                                                                                                             Gambar 11 - (IEC 60479-5) Zona Waktu-Voltase konvensional dari efek arus a.b. (50/60 Hz) pada orang
                                                          yang digunakan untuk menghitung voltase sentuh, dengan menerapkan hukum Ohm antara
                                                                                                                                                                                          untuk kondisi kering dan area kontak besar.
                                                          ambang batas arus yang berbeda-beda berkaitan dengan efek fisiologis yang berbeda-
                                                          beda dan impedans tubuh terkait dengan variasi lintasan arus melalui tubuh, luas kontak,       Dari gambar diatas, pada kondisi kering dan area kontak besar (± 100 cm2), ambang batas
                                                          kelembaban kulit pada kontak tersebut dan pada jenis arus ( a.b. atau a.s.).                   voltase sentuh yang berbahaya pada kondisi yang “paling aman” , dibawah kurva c1, adalah
                                                                                                                                                         sebesar 35 V, pada lintasan arus dari “tangan ke kaki”
                                                          Dalam penjelasan ini hanya dibahas voltase a.b. dengan frekuensi 50/60 Hz.
                                                     52    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                 Persyaratan Umum Instalasi Listrik 2011   53
                                                                                                                                                                                                       Tabel 1 (IEC 61201)
                                                                                                                                                                           Contoh area kontak maksimum berkaitan dengan voltase sentuh a.b. yang diberikan.
                                                     54    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                        Persyaratan Umum Instalasi Listrik 2011   55
                                                                                                                                                          411.6 Sistem IT
                                                          Untuk lebih rinci dan lengkap lihat IEC 60479-5 dan IEC 61201.
                                                                                                                                                          Lihat Gambar 31G1 Bagian 3.
                                                          Sebagai pedoman maka batas voltase yang aman untuk manusia adalah 50 V untuk kondisi
                                                          kering dan 25 V untuk kondisi basah.
                                                                                                                                                             PENJELASAN
411.5.4 Untuk sistem TT, GPAL tidak boleh digunakan sebagai proteksi terhadap sentuh tak langsung.
                                                          PENJELASAN
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                          Bila dipasang GPAL sebagai gawai proteksi dan terjadi gangguan maka diperlukan arus
                                                          gangguan sebesar minimal 5 x In GPAL yang terpasang (untuk tipe C), agar GPAL (MCB)
                                                          tersebut dapat trip (Lihat PENJELASAN 411.4.5)
                                                          Misal instalasi mendapat suplai dari PLN, dimana GPAL PLN yang terkecil adalah In = 2 A,
                                                          sehingga GPAL tersebut akan trip pada arus sebesar 5 x In = 10 A.
RA × Id ≤ 50 V
                                                          Dengan demikian GPAL tidak dapat digunakan untuk proteksi sentuh tak langsung, dalam
                                                          system TT.
                                                                                                                                                               CATATAN
                                                                                                                                                               Pembumian tambahan dari PE pada instalasi dapat diberikan.
                                                                                                                                                               1. Sistem dapat dihubungkan ke bumi melalui impedans yang cukup tinggi. Hubungan ini dapat dilakukan misalnya pada titik
                                                                                                                                                                   netral, titik netral buatan, atau konduktor lin.
                                                                                                                                                               2. Konduktor netral dapat didistribusikan atau tidak didistribusikan.
                                                     56    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                     Persyaratan Umum Instalasi Listrik 2011   57
                                                     Lampiran A (normatif)
                                                     Ketentuan untuk proteksi dasar
                                                     CATATAN                                                                                                 A.2.1 Bagian aktif harus berada di dalam selungkup atau di belakang penghalang yang memberikan
                                                     Ketentuan untuk proteksi dasar memberikan proteksi pada kondisi normal dan diterapkan jika ditentukan   tingkat proteksi sekurang-kurangnya IPXXB atau IP2X, kecuali jika terjadi lubang yang lebih besar
                                                     sebagai bagian tindakan proteksi yang dipilih.                                                          selama penggantian bagian, misalnya fiting lampu atau sekering tertentu, atau jika diperlukan lubang
                                                                                                                                                             yang lebih besar agar perlengkapan dapat berfungsi dengan baik menurut persyaratan relevan untuk
                                                     A.1 Insulasi dasar bagian aktif                                                                         perlengkapan tersebut, maka:
                                                                                                                                                             - harus diambil tindakan pencegahan yang sesuai untuk mencegah manusia atau ternak
                                                     CATATAN                                                                                                     menyentuh bagian aktif secara tidak sengaja, dan
                                                     Insulasi dimaksudkan untuk mencegah sentuh dengan bagian aktif.                                         - harus dapat dipastikan, sejauh dapat dipraktikkan, supaya manusia peduli bahwa bagian aktif
                                                                                                                                                                 dapat tersentuh melalui lubang dan sebaiknya tidak disentuh dengan sengaja, dan
                                                     Bagian aktif harus tertutup seluruhnya dengan insulasi yang hanya dapat dilepas dengan merusaknya.      - lubang harus sekecil mungkin, konsisten dengan persyaratan untuk berfungsinya secara baik dan
                                                     Untuk perlengkapan, insulasi harus memenuhi standar relevan untuk perlengkapan listrik.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                             A.2.2 Permukaan bagian atas horizontal penghalang atau selungkup yang mudah diakses harus
                                                          PENJELASAN
                                                                                                                                                             memberikan tingkat proteksi sekurang-kurangnya IPXXD atau IP4X.
                                                                                                                                                             A.2.3 Penghalang dan selungkup harus terpasang dengan kokoh di tempatnya dan mempunyai
                                                                                                                                                             kestabilan dan daya tahan yang memadai untuk mempertahankan tingkat proteksi yang disyaratkan
                                                                                                                                                             dan pemisahan yang memadai dari bagian aktif dalam kondisi pelayanan normal yang dikenal,
                                                                                                                                                             dengan memperhitungkan pengaruh eksternal yang relevan.
                                                                                                                                                             A.2.4 Jika diperlukan untuk melepaskan penghalang atau membuka selungkup atau melepaskan
                                                                                                                                                             bagian selungkup, hal ini hanya mungkin :
                                                                                                                                                             - dengan menggunakan kunci atau perkakas, atau
                                                                                                                                                             - setelah diskoneksi suplai ke bagian aktif yang diberi proteksi oleh penghalang atau selungkup
                                                                                                                                                                 tersebut, pemulihan suplai hanya dimungkinkan setelah penggantian atau penutupan balik
                                                                                                                                                                 penghalang atau selungkup, atau
                                                                                           Gambar - Contoh: konduktor berinsulasi (kabel).
                                                                                                                                                             - jika ada penghalang antara yang memberikan tingkat proteksi sekurang-kurangnya IPXXB atau
                                                                                                                                                                 IP2X untuk mencegah sentuh dengan bagian aktif, maka penghalang antara tersebut hanya
                                                                                                                                                                 dapat dilepas dengan menggunakan kunci atau perkakas.
                                                     A.2 Penghalang atau selungkup
                                                                                                                                                             A.2.5 Jika di belakang penghalang atau di dalam selungkup, perlengkapan yang terpasang dapat
                                                     CATATAN
                                                                                                                                                             menyimpan muatan listrik berbahaya setelah disakelar off (kapasitor, dsb.), diperlukan label
                                                     Penghalang atau selungkup dimaksudkan untuk mencegah sentuh dengan bagian aktif.
                                                                                                                                                             peringatan. Kapasitor kecil misalnya yang digunakan untuk pemadaman busur, untuk penundaan
                                                                                                                                                             respons relai, dsb. tidak dianggap berbahaya.
                                                                                                                                                             CATATAN
                                                                                                                                                             Sentuh tidak sengaja tidak dianggap berbahaya, jika voltase yang dihasilkan dari muatan statik turun di bawah
                                                                                                                                                             120 V a.s. dalam waktu kurang dari 5 detik setelah diskoneksi dari suplai daya.
                                                     58    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                         Persyaratan Umum Instalasi Listrik 2011   59
                                                                                                                                                     Lampiran B (normatif)
                                                                                                                                                     Rintangan dan penempatan diluar jangkauan
                                                          bagian yang memberikan proteksi terhadap sentuh langsung dari sembarang arah akses         Rintangan dimaksudkan untuk mencegah sentuh tak sengaja dengan bagian aktif tetapi tidak mencegah sentuh
                                                          yang biasa                                                                                 sengaja dengan cara menghindari rintangan secara sengaja.
                                                          (electrically) protective barrier
                                                                                                                                                     B.2.1 Rintangan harus mencegah:
                                                          IEV 826-12-23
                                                                                                                                                     - mendekatnya tubuh dengan tidak sengaja ke bagian aktif, dan
                                                                                                                                                     - sentuh tak disengaja dengan bagian aktif selama operasi perlengkapan aktif dalam pelayanan
                                                                                                                                                         normal.
                                                                                                                                                     B.2.2 Rintangan dapat dilepas tanpa menggunakan kunci atau perkakas, tetapi harus aman sehingga
                                                                                                                                                     tercegah lepasnya rintangan secara tidak sengaja.
B.3.1 Bagian terakses simultan yang berbeda potensial tidak boleh berada dalam jangkauan tangan.
                                                                                                                                                     B.3.2 Jika posisi yang biasa ditempati dihalangi pada arah horizontal oleh suatu rintangan (misalnya
                                                                                                                                                     rel tangga, kisi-kisi) yang memberikan tingkat proteksi kurang dari IPXXB atau IP2X, jangkauan
                                                                                                                                                     tangan harus diukur mulai dari rintangan tersebut. Ke arah atas, jangkauan tangan adalah 2,50
                                                                                                                                                     m dari permukaan S tanpa memperhitungkan setiap rintangan antara yang memberikan tingkat
                                                                                                                                                     proteksi kurang dari IPXXB.
                                                                                                                                                     CATATAN
                                                                                                                                                     Nilai jangkauan tangan berlaku untuk sentuh langsung dengan tangan telanjang tanpa bantuan (misalnya
                                                                                                                                                     perkakas atau tangga).
                                                                                                                                                     B.3.3 Di tempat dimana biasa digunakan benda konduktif yang besar atau panjang, jarak yang
                                                                                                                                                     disyaratkan dalam B.3.1 dan B.3.2 harus ditambah dengan memperhitungkan dimensi relevan dari
                                                                                                                                                     benda tersebut.
                                                     60    Persyaratan Umum Instalasi Listrik 2011                                                                                                                            Persyaratan Umum Instalasi Listrik 2011   61
                                                                                                                                                            PENJELASAN
                                                                                                                                         Dimensi dalam mm
                                                                                                                                                            Contoh: Pemasangan kabel sebaiknya diatas plafon ( terutama bila tinggi plafon kurang dari
                                                                                                                                                            2,5 m) atau menempel rapi pada plafon dengan pemagun ( lihat Tabel 52-1)
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     62   Persyaratan Umum Instalasi Listrik 2011                                                                                                                         Persyaratan Umum Instalasi Listrik 2011   63
                                                     Lampiran E
                                                     Penggunaan Gawai Proteksi Arus Sisa (GPAS)
                                                     CATATAN
                                                                                                                                                                     Keterangan
                                                     Persyaratan lebih rinci mengenai GPAS, termasuk arus pengenal dan voltase pengenalnya dapat dilihat dalam
                                                                                                                                                                     GPAL = Gawai proteksi arus lebih
                                                     IEC 60755, IEC 61008 dan IEC 61009.
                                                                                                                                                                     GPAS = Gawai proteksi arus sisa
E.1.2.2 Proteksi terhadap sentuh tak langsung : E.2.2 Pada sistem TT (lihat Gambar E.2).
PENJELASAN
                                                                                                                                                                     Baik pada sistem TN-C-S maupun sistem TT, GPAS dipasang pada konduktor lin dan konduktor
                                                                                                                                                                     netral.
                                                     64    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                            Persyaratan Umum Instalasi Listrik 2011   65
                                                                                                                                                   Bagian 4 - 42
                                                                                                                                                   Proteksi untuk
                                                                                                                                                   keselamatan -
                                                                                                                                                   Proteksi terhadap
                                                                                                                                                   efek termal
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     66   Persyaratan Umum Instalasi Listrik 2011   22   Persyaratan Umum Instalasi Listrik 2011     Persyaratan Umum Instalasi Listrik 2011   67
                                                     421 Proteksi terhadap kebakaran
                                                     CATATAN                                                                                                            CATATAN 1
                                                     Istilah kebakaran dan uji terkait dalam pertimbangan dengan kerjasama antara ISO dan IEC. Istilah yang digunakan   Contoh tindakan pencegahan tersebut adalah :
                                                     dalam ayat ini adalah sementara.                                                                                   - lubang drainase untuk menampung kebocoran cairan dan memastikan pemadamannya saat terjadi
                                                                                                                                                                            kebakaran, atau
                                                     421.1 Perlengkapan listrik tidak boleh menimbulkan bahaya kebakaran pada bahan yang berada di                      - pemasangan perlengkapan dalam kamar tahan api yang memadai dan perlengkapan penghalang atau sarana
                                                     dekatnya.                                                                                                              lain untuk mencegah cairan yang terbakar menyebar ke bagian bangunan lain, kamar tersebut berventalasi
                                                     Setiap petunjuk pemasangan relevan dari pabrikan harus diobservasi sebagai tambahan persyaratan                        hanya ke atmosfer luar.
                                                     PUIL.
                                                                                                                                                                        CATATAN 2
                                                     421.2 Jika perlengkapan magun dapat mencapai suhu permukaan yang dapat menyebabkan bahaya                          Batas terendah yang dapat diterima untuk jumlah yang signifikan umumnya adalah 25 liter.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     Bahan tahan busur api yang digunakan untuk tindakan proteksi ini harus tidak dapat terbakar,
                                                     berkonduktivitas termal rendah, dan mempunyai tebal yang memadai untuk memberikan kestabilan
                                                     mekanis.
                                                     421.4 Perlengkapan magun yang menyebabkan pemusatan atau konsentrasi bahang harus berada
                                                     pada jarak yang memadai dari setiap benda atau elemen bangunan magun, sedemikian sehingga benda
                                                     atau elemen bangunan tersebut dalam kondisi normal tidak dapat terkena suhu yang berbahaya.
                                                     421.5 Bila perlengkapan listrik dalam suatu lokasi tunggal berisi cairan yang mudah terbakar dalam
                                                     jumlah yang signifikan, maka harus diambil tindakan pencegahan untuk mencegah cairan yang terbakar
                                                     dan hasil pembakaran cairan (api, asap, gas beracun) menyebar ke bagian bangunan yang lain.
                                                     68    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                 Persyaratan Umum Instalasi Listrik 2011   69
                                                     422 Tindakan untuk proteksi terhadap kebakaran
                                                     CATATAN 2                                                                                                       1. penyambungan kabel yang buruk,yang dapat menimbulkan busur api listrik pada
                                                     Untuk risiko ledakan, lihat IEC 60079-14.                                                                          titik sambung tersebut;
                                                                                                                                                                     2. beban lebih dan terjadi hubung pendek, yang akan merusak insulasi kabel;
                                                     422.3.10 Untuk membatasi akibat arus gangguan pada sistem perkawatan dari titik pandang                         3. kualitas kabel atau perlengkapan/pemanfaat listrik yang tidak memenuhi standar;
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     risiko kebakaran, khususnya pada bangunan tempat masyarakat berkumpul yaitu: bangunan untuk                     4. penggunaan alat pemanas,yang tidak diproteksi dengan baik;
                                                     kepentingan umum (misalnya antara lain: stadion olah raga, perkantoran, tempat ibadah, rumah sakit),            5. fenomena penjaluran (tracking)
                                                     bangunan industri, bangunan komersial (misalnya antara lain: hotel, apartemen, mal, pertokoan, pasar,
                                                                                                                                                                  Keterangan fenomena penjaluran (tracking):
                                                     restoran, rumah susun), bangunan tinggi/pencakar langit, maka sirkit harus:
                                                     ·    diproteksi oleh GPAS (gawai proteksi arus sisa) dengan arus sisa operasi pengenalnya tidak              Menurut hasil uji laboratorium :
                                                          melampaui 0,5 A, atau.
                                                                                                                                                                  Arus bocor/sisa sebesar 500 mA cukup untuk menimbulkan busur api listrik, pada permukaan
                                                     ·    dipantau oleh gawai monitor insulasi kontinu yang menghidupkan alarm saat terjadi gangguan
                                                                                                                                                                  bahan penginsulasi yang terkontaminasi dan penuh polusi, terutama pada kondisi lembab.
                                                         insulasi
                                                     Ketentuan ini berlaku juga untuk perumahan dengan daya 3 500 VA dan lebih besar. Untuk perumahan
                                                     dengan daya di bawah 3 500 VA sangat dianjurkan.
PENJELASAN
                                                          Mengapa arus sisa sampai dengan 500 mA dianggap sebagai batas aman terhadap bahaya
                                                          kebakaran ?
                                                          Tiga unsur yang dapat memicu terjadinya kebakaran:
                                                          - adanya bahan-bahan yang mudah terbakar,
                                                          - adanya sumber bahang/api, dan
                                                          - adanya oksigen (udara).
                                                     70    Persyaratan Umum Instalasi Listrik 2011                                                                                                                           Persyaratan Umum Instalasi Listrik 2011   71
                                                                                                                                          PENJELASAN
                                                                                                                                          Mengapa hanya perumahan dengan daya terpasang ≥ 3 500 VA yang diharuskan memasang
                                                                                                                                          GPAS ≤ 500 mA?
                                                                                                                                          Namun karena alasan ekonomis dimana harga GPAS jenis Voltage Independent yang
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                          relatifmasih mahal dibandingkan dengan harga total instalasi untuk daya tersambung
                                                                                                                                          kurang dari 3 500 VA (pada saat PUIL 2011 disusun), maka untuk daya tersambung kurang
                                                                                                                                          dari 3 500 VA belum diwajibkan, hanya ”sangat dianjurkan”.
                                                     72   Persyaratan Umum Instalasi Listrik 2011                                                                                               Persyaratan Umum Instalasi Listrik 2011   73
                                                                                                    Bagian 4 - 43
                                                                                                    Proteksi untuk
                                                                                                    keselamatan –
                                                                                                    Proteksi terhadap
                                                                                                    arus lebih
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     74   Persyaratan Umum Instalasi Listrik 2011     Persyaratan Umum Instalasi Listrik 2011   75
                                                     430.1 Ruang lingkup                                                                                      431.3 Diskoneksi dan rekoneksi konduktor netral pada sistem multifase
                                                     Bagian 4-43 memberikan persyaratan untuk proteksi konduktor aktif dari efek arus lebih.                  Bila diskoneksi konduktor netral disyaratkan, diskoneksi dan rekoneksi harus sedemikian sehingga
                                                                                                                                                              konduktor netral tidak boleh didiskoneksi sebelum konduktor lin dan harus direkoneksi pada waktu
                                                                                                                                                              yang sama atau sebelum konduktor lin.
                                                          PENJELASAN
                                                          Arus lebih dapat terjadi ketika arus listrik melebihi kapasitas konduktor. Ini dapat terjadi            PENJELASAN
                                                          karena beban lebih atau hubung pendek. Manusia atau ternak harus dihindarkan dari
                                                          cedera, dan harta benda diamankan dari kerusakan karena suhu yang berlebihan atau stres                 Contoh: Gunakan gawai proteksi 4 kutub yang beroperasi secara serentak.
                                                          elektromekanis.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                          Karena itu diperlukan peralatan proteksi beserta persyaratannya untuk melindungi konduktor
                                                          aktif dari arus lebih. Proteksi dilakukan dengan cara memilih gawai proteksi yang tepat untuk
                                                          setiap sirkit. Juga mencakup koordinasi proteksi beban lebih dan proteksi hubung pendek.
                                                     431.1.1 Deteksi arus lebih harus disediakan untuk semua konduktor lin, kecuali dimana berlaku 431.1.2.
                                                     Hal itu harus menyebabkan diskoneksi konduktor dimana arus lebih terdeteksi tapi tidak perlu terjadi
                                                     diskoneksi pada konduktor aktif lainnya.
                                                     Jika diskoneksi fase tunggal dapat menyebabkan bahaya, misal pada kasus motor trifase, harus diambil
                                                     tindakan pencegahan yang sesuai.
PENJELASAN
                                                          Contoh tindakan pencegahan yang sesuai yaitu harus menggunakan GPAL 3 kutub yang
                                                          beroperasi secara serentak.
                                                     76    Persyaratan Umum Instalasi Listrik 2011                                                                                                                              Persyaratan Umum Instalasi Listrik 2011   77
                                                     432 Sifat gawai proteksi                                                                              433 Proteksi terhadap arus beban lebih
                                                     Gawai proteksi harus merupakan tipe yang sesuai yang ditunjukkan oleh 432.1 hingga 432.3.             433.1 Koordinasi antara konduktor dan Gawai Proteksi Beban Lebih (GPBL)
                                                     432.1 Gawai proteksi terhadap beban lebih dan arus hubung pendek                                      Karakteristik operasi gawai yang memproteksi terhadap beban lebih harus memenuhi dua kondisi
                                                                                                                                                           berikut ;
                                                     Kecuali seperti dinyatakan dalam 434.5.1, gawai yang memberikan proteksi terhadap beban lebih dan
                                                                                                                                                                                                                 IB ≤ In ≤ IZ
                                                     arus hubung pendek harus mampu memutuskan dan, untuk pemutus sirkit, menghubungkan setiap
                                                     arus lebih sampai dengan arus hubung pendek prospektif di titik tempat gawai tersebut dipasang.
                                                     Gawai tersebut dapat merupakan:                                                                                                                           I2 ≤ 1,45 × IZ
                                                                                                                                                           dengan
                                                     - pemutus sirkit yang dilengkapi pelepas beban lebih dan hubung pendek;
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     Karakteristik operasi GPAL harus memenuhi yang ditentukan misalnya dalam IEC 60898, IEC 60947-2,      CATATAN 5
                                                     IEC 60947-6-2, IEC 61009, IEC 60269-2, IEC 60269-3, IEC 60269-4 atau IEC 60947-3.                     Arus desain IB dapat dianggap sebagai arus aktual Ia sesudah menerapkan faktor koreksi. Lihat Ayat 311.
                                                     78    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                       Persyaratan Umum Instalasi Listrik 2011   79
                                                          PENJELASAN
                                                                                                                                                                Contoh:
                                                                                                                                                                Contoh ini mengarahkan cara memilih gawai proteksi beban lebih yang digunakan untuk
                                                                                                                     GPBL                                       memproteksi suatu kabel atau konduktor berinsulasi.
                                                              No
                                                                                       Pemutus sirkit                                    Sekering
                                                                                                                                                                A. Proteksi dengan pemutus sirkit (MCB)
                                                               1                                                   IB ≤ In ≤ IZ                                 Suatu instalasi fasa tunggal pada mulanya dengan 900 VA 220 V akan dikembangkan
                                                               2                                                 I2 ≤ 1,45 × IZ                                 bertahap ke 1300 VA , selanjutnya ke 2200 VA dan pengembangan terakhir menjadi 4400
                                                               3        1,13 Intidak boleh trip                          1,25 In tidak boleh leleh              VA fasa tunggal.
                                                                                                                                                                Tentukan arus pengenal GPAL yang sesuai dengan dayanya.
                                                               4        1,45 In harus trip                               1,6 In harus leleh
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     80     Persyaratan Umum Instalasi Listrik 2011                                                                                                                         Persyaratan Umum Instalasi Listrik 2011   81
                                                          4. Persyaratan pemutus sirkit yang harus dipenuhi.                                            Dalam contoh ini akan menggunakan MCB jenis C .Dari kurva pemutus sirkit (memenuhi SNI
                                                                                                                                                        IEC 60898-1:2009 ) didapat untuk kurva C sbb:
                                                                     Tahap                                                    Sistem
                                                                                                                                                        6. Memilih MCB
                                                                         1                                                   IB ≤ In ≤ IZl
                                                                                                                                                        1) Untuk daya 900 VA:
                                                                         2                                                 I2 ≤ 1,45 × IZ
                                                                                                                                                        IB = 4 A , IZ = 26 A . Nilai In harus dipilih antara IB dan IZ          dipilih yang sama atau terdekat
                                                                         3                                            1,13 In harus tidak trip          di atas IB dan di bawah KHA = IZ kabel) In = 6 A
                                                                         4                                 1,45 In harus trip< 1 jam (untuk In< 63 A)
                                                                                                                                                        Periksa persyaratan
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     82    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                  Persyaratan Umum Instalasi Listrik 2011   83
                                                          3) Untuk daya 1300 VA:                                                                                            5) Untuk daya 4400 VA:
                                                          IB = 6 A , IZ = 26 A . Nilai In harus dipilih antara IB dan IZ dipilih yang sama atau terdekat
                                                          di atas IB dan di bawah KHA = IZ kabel) In = 10 A                                                                 IB = 20 A , IZ = 26 A . Nilai In harus dipilih antara IB dan IZ                dipilih yang sama atau terdekat
                                                                                                                                                                            di atas IB dan di bawah KHA = IZ kabel) In = 20 A
                                                          Periksa persyaratan
                                                                                                                                                                            Periksa persyaratan
                                                            No     Formula           Kalkulasi             Syarat               Pemeriksaan Kurva                 Hasil
                                                             1    IB ≤ In ≤ IZ    6 A < 10 A <        6 A ≤ 10 A ≤ 26 A                        -                 Dipenuhi     No        Formula               Kalkulasi           Syarat              Pemeriksaan Kurva                   Hasil
                                                                                  26 A
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                           Kesimpulan:                                                                                                         4       I2 = 1,45 In      I2 = 29 A           harus trip (< 1 jam) trip pada t = 3000 detik= 0,83        Dipenuhi
                                                           Pemutus sirkit 10 A memenuhi persyaratan standar untuk daya 1300 VA.                                                                                                                   jam
                                                                                                                                                                             Kesimpulan:
                                                                                                                                                                             Pemutus sirkit 20 A memenuhi persyaratan standar untuk daya 4400 VA.
                                                          4) Untuk daya 2200 VA:
                                                          IB = 10 A , IZ = 26 A . Nilai In harus dipilih antara IB dan IZ    dipilih yang sama atau                         B. Proteksi dengan Sekering
                                                          terdekat di atas IB dan di bawah KHA = IZ kabel)           In = 10 A
                                                                                                                                                                            Persyaratan
                                                          Periksa persyaratan
                                                                                                                                                                                   No          Sekering
                                                            No     Formula           Kalkulasi             Syarat               Pemeriksaan Kurva                 Hasil            1           IB ≤ In ≤ IZ
                                                             1    IB ≤ I n ≤ IZ   10A = 10 A <        10 A ≤ 10 A ≤ 26 A                       -                 Dipenuhi          2           I2 ≤ 1,45 × IZ
                                                                                  26 A
                                                                                                                                                                                   3           1,25 In harus tidak leleh
                                                             2    I2 ≤ 1,45 IZ    I2 ≤ 37,7 A         harus trip (< 1 jam) trip pada t = 9,5 detik = 0,004 jam   Dipenuhi
                                                                                                                                                                                   4           1,6 In harus leleh
                                                             3    I2 = 1,13In     I2 = 11,3 A         tidak trip           kurva: tidak trip                     Dipenuhi
                                                             4    I2 = 1,45 In    I2 = 14,5 A         harus trip (< 1 jam) trip pada t = 3000 detik= 0,83 jam    Dipenuhi
                                                                                                                                                                            Contoh:
                                                           Kesimpulan:                                                                                                      Beban: IB = 20 A ,
                                                           Pemutus sirkit 10 A memenuhi persyaratan standar untuk daya 2200 VA.
                                                                                                                                                                            Kabel NYM 2,5 mm2 KHA = IZ = 26 A (Tabel 7.3-4 PUIL 2000 (Gawai Proteksi = 20 A untuk
                                                                                                                                                                            kabel 2,5 mm2)
                                                     84     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                         Persyaratan Umum Instalasi Listrik 2011   85
                                                          Penyelesaian
                                                                                                                                                  No    Formula           Kalkulasi         Syarat            Pemeriksaan Kurva                   Hasil
                                                          1. Cari arus beban: IB = 20 A                                                            1    IB ≤ I n ≤ IZ   20A = 20 A <   20A = 20 A <                       -                     Dipenuhi
                                                          2. Tentukan ukuran kabel (sama dengan penjelasan di atas) untuk                                               26 A           26 A
                                                             proteksi dengan MCB. Kabel NYM 2,5 mm2 dengan KHA = IZ = 26 A                         2                                   harus trip (< 1 jam) trip pada t = 250 detik =           Dipenuhi
                                                                                                                                                        I2 ≤ 1,45 IZ I2 ≤ 37,7 A
                                                          3. Cari arus pengenal tautan sekering:                                                                                                          0,07 jam
                                                             Dari standar IEC 60269-1ayat 5.3.1 nilai arus pengenal tautan sekering
                                                                                                                                                   3    I2 = 1,25 In I2 = 25 A         tidak trip         kurva: tidak trip                     Dipenuhi
                                                             adalah: 2 – 4 – 6 – 8 – 10 – 12 – 16 – 20 – 25 – 32 – 40 – 50 – 63 – 80
                                                             – 100 – 125 – 160 – 200 – 250 – 315 – 400 – 500 – 630 – 800 – 1 000                   4    I2 = 1,6 In     I2 = 32 A      harus trip (< 1 jam) trip pada t = 1000 detik=           Dipenuhi
                                                             – 1 250; Nilai If harus dipilih antara IB dan IZ dipilih yang terdekat di                                                                    0,28 jam
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                          Untuk ini akan digunakan tautan sekering jenis gG (misalnya sekering cartridge dengan
                                                          karateristik sbb):
Periksa persyaratan
                                                     86     Persyaratan Umum Instalasi Listrik 2011                                                                                                                Persyaratan Umum Instalasi Listrik 2011   87
                                                                                                    Bagian 5 - 52
                                                                                                    Pemilihan dan
                                                                                                    pemasangan
                                                                                                    perlengkapan
                                                                                                    listrik – Sistem
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
perkawatan
                                                     88   Persyaratan Umum Instalasi Listrik 2011      Persyaratan Umum Instalasi Listrik 2011   89
                                                     521 Jenis sistem perkawatan
                                                     521.1 Metode instalasi sistem perkawatan tentang jenis konduktor atau kabel yang digunakan harus        521.5 Sirkit a.b.
                                                     sesuai dengan Tabel 52-1, asalkan pengaruh eksternal dicakup oleh persyaratan standar produk yang       Konduktor sirkit a.b. yang dipasang dalam selungkup feromagnetik harus disusun sedemikian sehingga
                                                     relevan.                                                                                                semua konduktor setiap sirkit berada dalam selungkup yang sama.
                                                     521.2 Metode instalasi sistem perkawatan tentang situasi terkait harus sesuai dengan Tabel 52-2.        CATATAN
                                                                                                                                                             Jika kondisi ini tidak dipenuhi, pemanasan dan drop voltase berlebihan dapat terjadi karena efek induktif.
                                                     521.3 Contoh sistem perkawatan bersama-sama dengan acuan tabel kapasitas hantar arus (KHA) yang
                                                     sesuai diperlihatkan pada Tabel 52-3.                                                                                                         Tabel 52-1 Pemilihan sistem perkawatan
                                                     CATATAN 1
                                                                                                                                                                                                                     Metode Pemasangan
                                                     Jenis sistem perkawatan lain, yang tidak dicakup dalam standar ini, dapat digunakan asalkan memenuhi
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     Tabel 52-3 memberikan metode instalasi acuan jika dianggap bahwa KHA yang sama dapat digunakan dengan                            pemagun     langsung                pinggiran (skirt),   kabel        Rak kabel     insulator    penyangga
                                                     aman.                                                                                                                                                               berumbungbenam                   Braket kabel
                                                                                                                                                                                                                             di lantai)
                                                     521.4 Sistem berumbung rel (busbar trunking systems)
                                                                                                                                                              Konduktor polos            -           -           -               -               -              -             +                -
                                                                                                                                                              Konduktor berinsulasi      -           -           +               +               +              -             +                -
                                                     Sistem berumbung rel harus memenuhi IEC 60439-2 dan harus dipasang sesuai dengan petunjuk
                                                                                                                                                              Kabel         Multiinti     +            +          +               +              +              +             0                +
                                                     pabrikan. Pemasangan harus sesuai dengan persyaratan ayat 522 (dengan pengecualian 522.1.1,              berselubun
                                                     522.3.3, 522.8.7, 522.8.8 dan 522.8.9), 525, 526, 527 dan 528.                                           g             Inti
                                                                                                                                                              (termasuk     tunggal
                                                                                                                                                                                          0            +          +               +              +              +             0                +
                                                                                                                                                              berarmor
                                                                                                                                                              dan
                                                          PENJELASAN                                                                                          berinsulasi
                                                                                                                                                              mineral)
                                                                                                                                                              + Diizinkan.
                                                          Sistem berumbung rel saat ini sudah banyak digunakan terutama untuk bangunan gedung                 – Tidak diizinkan.
                                                                                                                                                              0 Tidak dapat diterapkan, atau tidak biasa digunakan dalam praktik.
                                                          komersial.
                                                          Keuntungan sistem berumbung rel dibandingkan dengan memakai kabel adalah:
                                                          a. Sistem berumbung rel merupakan seksi-seksi (berupa potongan lengkap) yang dapat
                                                                                                                                                                 PENJELASAN
                                                              disambung sesuai kebutuhan.
                                                          b. Bentuknya kompak, sehingga lebih mudah dipasang.
                                                          c. Kapasitas hantar arusnya besar dan mempunyai susut dan drop voltase yang relatif                    Konduktor polos adalah konduktor telanjang tanpa insulasi dan selubung. Hanya dapat
                                                                                                                                                                 dipasang di atas insulator. Saat ini tidak lazim di Indonesia.
                                                             lebih rendah.
                                                                                                                                                                 Konduktor berinsulasi adalah konduktor yang mempunyai insulasi tapi tanpa selubung (biasa
                                                                                                                                                                 dikenal sebagai kabel NYA), hanya diizinkan dipasang dalam konduit, berumbung atau talang
                                                                                                                                                                 kabel.
                                                                                                                                                                 Kabel berselubung (biasa dikenal sebagai kabel NYM dan NYY), dapat dipasang pada hampir
                                                                                                                                                                 semua metode pemasangan. Kecuali untuk kabel berselubung inti tunggal yang tidak
                                                                                                                                                                 diizinkan tanpa pemagun. Selain itu kabel berselubung tidak lazim dipasang di atas insulator.
                                                                                    Gambar - Sistem berumbung rel (busbar trunking systems)                      Yang dimaksud dengan inti adalah rakitan yang terdiri atas konduktor beserta insulasinya
                                                                                                                                                                 (dan skrin jika ada).
                                                     90    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                   Persyaratan Umum Instalasi Listrik 2011       91
                                                                                                                                                                                                         Tabel 52-3 Contoh metode instalasi yang memberikan pedoman untuk memperoleh KHA
                                                                                                                                                                                               CATATAN
                                                                                                                                                                                               Ilustrasi tidak dimaksudkan untuk menggambarkan produk aktual praktik instalasi, tetapi merupakan indikasi
                                                                                                                                                                                               metode yang diuraikan.
Metode pemasangan
                                                      Void bangunan            40, 46,        0       15, 16,               -                43         30, 31, 32,        -          -                                                      lasi
                                                                               15, 16                 41, 42                                             33, 34
                                                                                                                                                                                                                                             secara termala
                                                                                                                                                                                                                                             Konduktor berinsulasi atau kabel inti tunggal
                                                      Kanal kabel                56          56        54,55                0              44, 45       30, 31, 32,        -          -            4                                         dalam konduit pada dinding kayu atau tembok                    B1
                                                                                                                                                         33, 34
                                                                                                                                                                                                                                             atau berjarak kurang dari 0,3 x diameter kondui
                                                      Ditanam dalam tanah      72, 73         0        70,71                -               70,71           0              -          -                                                      t
                                                                                                                                                                                                                                             dari dinding
                                                      Ditanam dalam strukt     57, 58         3       1, 2, 59,      50, 51, 52, 53        44, 45           0              -          -
                                                      ur                                                 60                                                                                                                                  Kabel multiinti dalam konduit pada dinding ka
                                                                                                                                                                                                   5                                                                                                        B2
                                                      Ditanam dalam tanah      72, 73         0        70,71                -               70,71           0              -          -
Nomor dalam tabel adalah nomor metode instalasi yang dijelaskan dalam Tabel 52-3.
                                                     92     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                                            Persyaratan Umum Instalasi Listrik 2011   93
                                                      a   Permukaan bagian dalam dinding mempunyai konduktans termal tidak kurang dari 10 W/m2∙K.                                                        a Nilai yang diberikan untuk metode instalasi B1 dan B2 dalam Lampiran A adalah untuk sirkit tunggal. Jika terdapat lebih dari satu sirkit dalam
                                                      b Nilai yang diberikan untuk metode instalasi B1 dan B2 dalam Lampiran A adalah untuk sirkit tunggal. Jika terdapat lebih dari satu sirkit dalam        berumbung, faktor reduksi kelompok yang diberikan dalam Tabel A.52-17 dapat diterapkan, tidak tergantung dari adanya penghalang internal
                                                         berumbung, faktor reduksi kelompok yang diberikan dalam Tabel A.52-17 dapat diterapkan, tidak tergantung dari adanya penghalang internal             atau partisi.
                                                         atau partisi.                                                                                                                                   b Resistivitas termal selungkup diasumsikan buruk karena bahan konstruksi dan kemungkinan ruang udara. Jika konstruksi secara termal setara
                                                      c Harus diperhatikan jika kabel mengarah vertikal dan ventilasi terbatas. Suhu ambien pada puncak seksi vertikal dapat sangat meningkat.                dengan metode instalasi 6 atau 7, dapat digunakan metode acuan B1.
                                                      d Nilai untuk metode acuan B2 dapat digunakan.                                                                                                     c   Resistivitas termal selungkup diasumsikan buruk disebabkan bahan konstruksi dan kemungkinan adanya ruang udara. Jika konstruksi secara
                                                                                                                                                                                                              termal setara dengan metode instalasi 6, 7, 8, atau 9, dapat digunakan metode acuan B1 atau B2.
                                                                                                                                                                                                                                                               Berjarak lebih dari 0,3 kali diameter kabel dari     E atau F dengan nomor urut 4
                                                                                                                                                             C, dengan nomer urut 3 Tabel                    33
                                                           21                                             c. magun langsung di bawah plafon                                                                                                                    dinding                                              Tabel A.52-17 atau metode G
                                                                                                                                                                       52-17
                                                                                                                                                                                                                                                               g
                                                                                                                                                                                                                                                               dari atau dilengkapi kawat penyangga
                                                     94         Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                                                            Persyaratan Umum Instalasi Listrik 2011        95
                                                                                                                                                                                               a   V = dimensi terkecil atau diameter talang atau void tembok, atau kedalaman vertikal talang persegi, void lantai atau plafon.
                                                          36                                              Konduktor polos atau berinsulasi di atas insulat                 G                   b   De = diameter eksternal konduit atau kedalaman vertikal talang kabel.
                                                                                                                                                                                               c   Harus diperhatikan jika kabel mengarah vertikal dan ventilasi dibatasi. Suhu ambien pada puncak seksi vertikal dapat sangat meningkat.
                                                                                                      or
                                                      a     Untuk penerapan tertentu mungkin lebih sesuai untuk menggunakan faktor spesifik, misalnya Tabel A.52-20 dan A.52-21
                                                      (lihat A.52.4.2
                                                           Lampiran A).                                                                                                                                                                              Tabel 52-3 (lanjutan)
                                                      b     Harus diperhatikan jika kabel mengarah vertikal dan ventilasi dibatasi. Suhu ambien pada puncak seksi vertikal dapat sangat meni
                                                      ngkat.                                                                                                                                                                                                                                                Metode acuan instalasi
                                                      c     De = diameter eksternal kabel multiinti:                                                                                               No                                                                                                       yang digunakan untuk
                                                           - 2,2 x diameter kabel jika tiga kabel inti tunggal diikat dalam trefoil, atau
                                                                                                                                                                                                                     Metode instalasi                                     Uraian
                                                           - 3 x diameter kabel jika tiga kabel inti tunggal diletakkan pada formasi datar.                                                        urut                                                                                                    memperoleh KHA (lihat
                                                                                                          Tabel 52-3 (lanjutan)                                                                                                                                                                                   Lampiran A)
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     96         Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                                                    Persyaratan Umum Instalasi Listrik 2011   97
                                                      a   De = diameter eksternal konduit
                                                      b V= kedalaman internal kanal.
                                                                                                                                                                                                     80                                               Kabel inti tunggal atau multiinti berselubung         Dalam pertimbangan
                                                      c Harus diperhatikan jika kabel mengarah vertikal dan ventilasi dibatasi. Suhu ambien pada puncak seksi vertikal dapat sangat meningkat.
                                                      d Untuk kabel multiinti yang dipasang dengan metode 55, gunakan peringkat untuk metode acuan B2.                                                                                                terendam dalam air
                                                      e Direkomendasikan bahwa metode instalasi ini hanya digunakan dalam area yang aksesnya dibatasi untuk personel berwenang sedemikian
                                                         sehingga pengurangan KHA dan bahaya kebakaran karena akumulasi debu dapat dicegah.
                                                      f Untuk kabel yang mempunyai konduktor tidak lebih besar dari 16 mm2, KHA dapat lebih tinggi.                                              CATATAN
                                                      g Resistivitas termal tembok tidak lebih besar dari 2 K∙m/W                                                                                Masuknya kabel yang ditanam langsung akan memuaskan jika resistivitas termal tanah sekitar 2,5 K∙m/W. Untuk resistivitas ta
                                                                                                                                                                                                 nah yang lebih
                                                                                                                                                                                                 rendah, KHA untuk kabel yang ditanam langsung lumayan lebih tinggi daripada untuk kabel dalam talang.
                                                                                                          Tabel 52-3 (lanjutan)
                                                                                                                                                                                                 a    Resistivitas termal tembok tidak lebih besar dari 2 K∙m/W
                                                                                                                                                            Metode acuan instalasi
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                          g
                                                                                                          kabel dalam tanah
                                                                                                          m
                                                                                                          tanah
                                                                                                          - tanpa proteksi mekanis tambahan (lihat catata
                                                                                                          n)
                                                                                                          Kabel inti tunggal atau multiinti langsung dala
                                                           73                                                                                                         D
                                                                                                          m
                                                                                                          tanah
                                                                                                          - dengan proteksi mekanis tambahan (lihat
                                                                                                          catatan)
                                                     98         Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                                                 Persyaratan Umum Instalasi Listrik 2011   99
                                                     521.6 Konduit dan sistem berumbung
                                                                                                                                                           Jika lengkapan listrik dipasang dalam sistem berumbung atau talang yang dipasang dalam
                                                     Beberapa sirkit diizinkan dalam konduit atau berumbung yang sama asalkan semua konduktor diinsulasi   atau di bawah lantai, sebaiknya dipertimbangkan jenis perlakuan lantai yang mungkin
                                                     terhadap voltase nominal tertinggi yang ada.                                                          digunakan (basah atau kering).
                                                                                                                                                           Jika sistem berumbung kabel dipasang dalam posisi pinggiran (skirting), misalnya Item 6
                                                           PENJELASAN                                                                                      Tabel A52.3, kerusakan yang disebabkan masuknya air dapat dihindari dengan menempatkan
                                                                                                                                                           konduktor berinsulasi sedikitnya 10 mm di atas level lantai.
                                                           Di Indonesia pada praktiknya instalasi magun (fixed installation) voltase rendah biasanya
                                                           menggunakan voltase nominal 230/400 V a.b. Karena hanya ada satu voltase nominal, maka          Sistem berumbung kabel dan sistem talang kabel yang dimaksudkan untuk instalasi bawah
                                                                                                                                                           lantai dan pada lantai dicakup oleh IEC 61084-2-2.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                           pemasangan beberapa sirkit dalam konduit atau berumbung yang sama, setiap konduktornya
                                                           diinsulasi terhadap voltase nominal tertinggi yang sama, yaitu 230/400 V a.b.
                                                                                                                                                           Jika digunakan sistem rak kabel, atau alasan desain atau akses yang penutup dapat juga
                                                           Hal berikut mencakup rekomendasi untuk memudahkan pemasangan atau penggantian                   diperlukan, misalnya untuk proteksi mekanis atau mencegah akses (misalnya dalam kolam
                                                           sirkit yang dipasang dalam konduit (diterjemahkan dari IEC 61200-52):                           air mancur publik).
                                                           - Panjang konduit lurus antara titik akses sebaiknya tidak melebihi 25 m. Panjang konduit
                                                              yang mencakup perubahan arah sebaiknya tidak melebihi 15 m antara titik akses.
                                                              Sebaiknya tidak lebih dari tiga perubahan arah antara titik akses.
                                                           - Setiap radius belokan sebaiknya sebesar mungkin dan sesuai dengan petunjuk pabrikan
                                                              (lihat Lampiran E).
                                                           - Kabel atau konduktor berinsulasi sebaiknya tidak mencakup lebih dari sepertiga luas
                                                              penampang internal total konduit.
Untuk pemasangan di dalam konduit, lihat juga Subayat 7.13 Bagian 7 PUIL 2011.
                                                     100     Persyaratan Umum Instalasi Listrik 2011                                                                                                                     Persyaratan Umum Instalasi Listrik 2011   101
                                                     522 Pemilihan dan pemasangan sistem perkawatan berkaitan dengan
                                                         pengaruh eksternal
                                                     522.1.1 Sistem perkawatan harus dipilih dan dipasang sedemikian sehingga sesuai untuk suhu ambien            CATATAN
                                                     lokal tertinggi dan untuk memastikan bahwa suhu batas yang ditunjukkan dalam Tabel 54-4 tidak akan           Umumnya selubung dan insulasi kabel untuk instalasi magun, jika lengkap, dapat dianggap tahan terhadap
                                                     dilampaui.                                                                                                   penetrasi uap air. Pertimbangan khusus berlaku untuk kabel yang tahan terhadap pancaran air yang sering,
                                                                                                                                                                  pencelupan atau perendaman.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                           PENJELASAN
                                                                                                                                                                       PENJELASAN
                                                           Suhu ambien tertinggi di Indonesia adalah 40 °C luar ruang untuk kondisi ekstrim. Tapi
                                                           karena kabel dipasang dalam ruang di udara atau ditanam dalam tanah, maka dapat diacu                      Untuk uraian kode IP lihat Lampiran G Bagian 4-41 PUIL.
                                                           Subayat A.52.2.1 yaitu :                                                                                   Contoh:
                                                           - untuk konduktor berinsulasi dan kabel di udara, tidak tergantung dari metode                             - tahan terhadap pancaran air: IPX5 atau IPX6 (pancaran air yang kuat);
                                                               pemasangan: 30°C;                                                                                      - tahan terhadap pencelupan (perendaman sementara): IPX7;
                                                           - untuk kabel tertanam, baik langsung dalam tanah atau dalam talang dalam tanah: 20 °C.                    - tahan terhadap perendaman (kontinu): IPX8.
                                                     522.1.2 Komponen sistem perkawatan termasuk kabel dan lengkapan perkawatan harus hanya                       522.3.2 Jika air dapat terkumpul atau kondensasi dapat terbentuk dalam sistem perkawatan, harus
                                                     dipasang dan ditangani pada suhu dalam batas yang dinyatakan dalam spesifikasi produk relevan atau           dibuat ketentuan untuk mengeluarkannya.
                                                     seperti diberikan oleh pabrikan.
                                                                                                                                                                  522.3.3 Jika sistem perkawatan dapat terkena gelombang (AD6), proteksi terhadap kerusakan mekanis
                                                     522.2 Sumber bahang (heat) eksternal                                                                         harus diupayakan dengan satu atau lebih metode 522.6, 522.7 dan 522.8.
                                                     Guna menghindari efek bahang dari sumber eksternal, salah satu metode berikut atau metode efektif            522.4        Keberadaan benda asing padat (AE)
                                                     yang sama harus digunakan untuk memproteksi sistem perkawatan:
                                                     - pemerisaian;                                                                                               522.4.1 Sistem perkawatan harus dipilih dan dipasang sedemikian sehingga meminimalkan bahaya
                                                     - penempatan yang cukup jauh dari sumber bahang;                                                             yang timbul dari masuknya benda asing padat. Sistem perkawatan lengkap harus memenuhi tingkat
                                                     - pemilihan sistem yang berkaitan untuk kenaikan suhu tambahan yang akan terjadi;                            proteksi IP yang relevan pada lokasi khusus tersebut.
                                                     - perkuatan lokal atau substitusi bahan insulasi.
                                                     CATATAN                                                                                                           PENJELASAN
                                                     Bahang dari sumber eksternal dapat diradiasi, dikonveksi atau dikonduksi, misalnya:
                                                                                                                                                                      Sistem manajemen kabel tidak akan diproteksi terhadap masuknya benda asing padat kecuali
                                                     - dari sistem air panas,
                                                     - dari peranti dan luminer pabrik,
                                                                                                                                                                      memenuhi tingkat proteksi sedikitnya IP2X. Untuk uraian kode IP lihat Lampiran G Bagian
                                                     - dari proses pabrikasi,
                                                                                                                                                                      4-41 PUIL 2011.g
                                                     - melalui bahan konduktor bahang,
                                                     - dari sinar matahari sistem perkawatan atau medium sekitarnya.
                                                     102     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                          Persyaratan Umum Instalasi Listrik 2011   103
                                                     522.4.2 Pada lokasi yang berdebu dengan jumlah yang signifikan (AE4), tindakan pencegahan              522.6         Tumbukan (AG)
                                                     tambahan harus diambil untuk mencegah akumulasi debu atau zat lain dalam jumlah yang dapat
                                                     mempengaruhi secara merugikan disipasi bahang dari sistem perkawatan.                                  522.6.1 Sistem perkawatan harus dipilih dan dipasang sedemikian sehingga meminimalkan kerusakan
                                                                                                                                                            yang timbul dari stres mekanis, misalnya karena tumbukan, penetrasi atau kompresi.
                                                     CATATAN
                                                     Mungkin perlu sistem perkawatan yang memfasilitasi penghilangan debu (lihat ayat 529).                 522.6.2 Pada instalasi magun jika tumbukan dengan keganasan medium (AG2) atau keganasan tinggi
                                                                                                                                                            (AG3) dapat terjadi, proteksi harus diupayakan dengan:
                                                     522.5 Keberadaan zat korosif atau polusi (AF)                                                          - karakteristik mekanis sistem perkawatan; atau
                                                                                                                                                            - lokasi terpilih; atau
                                                     522.5.1 Jika keberadaan zat korosif atau polusi, termasuk air, mungkin menyebabkan korosi atau         - ketentuan mengenai proteksi lokal tambahan atau mekanis umum; atau
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     pemburukan, bagian sistem perkawatan yang mungkin dipengaruhi harus diproteksi yang sesuai atau        - setiap kombinasi di atas.
                                                     dibuat dari bahan yang tahan terhadap zat tersebut.
                                                     CATATAN                                                                                                    PENJELASAN
                                                     Proteksi yang sesuai untuk penerapan selama pemasangan dapat mencakup pita proteksi, cat atau gemuk.
                                                                                                                                                               Sistem berumbung, talang dan konduit memberikan proteksi mekanis pada kabel, tapi rak
                                                     522.5.2 Logam berbeda yang dapat menimbulkan aksi elektrolitik tidak boleh ditempatkan sehingga           kabel dan rak kabel berpenutup tidak dapat memberikan proteksi mekanis tersebut, karena
                                                     dapat kontak satu sama lain, kecuali dilakukan susunan khusus untuk menghindari konsekuensi akibat        menurut standar produk memang tidak diuji untuk keperluan ini.
                                                     kontak tersebut.
                                                                                                                                                               Proteksi terhadap tumbukan pada selungkup dinyatakan dengan kode IK sesuai IEC 62262
                                                                                                                                                               sbb:
                                                           PENJELASAN
                                                                                                                                                               4.1 Susunan kode IK
                                                           Karena itu untuk sambungan logam yang berbeda, misalnya antara tembaga dan aluminium                         IK        05
                                                           biasanya digunakan bimetal (dwilogam).                                                              Huruf kode (proteksi mekanis internasional)
                                                                                                                                                               Angka kelompok karakteristik (00 hingga 10)
                                                           Pada kasus aluminium (Al) dan tembaga (Cu), karena letak Al di sebelah kiri Cu pada deret
                                                           Volta, maka Al akan lebih mudah melepas elektron dibandingkan Cu, jadi Al akan tergerus              4.2 Angka kelompok karakteristik dari kode IK dan artinya
                                                           lebih dulu bila kedua logam tersebut kontak secara listrik.                                          Setiap angka kelompok karakteristik mewakili nilai energi tumbukan seperti terlihat dalam
                                                           Deret Volta:                                                                                         Tabel1.
                                                     104     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                     Persyaratan Umum Instalasi Listrik 2011   105
                                                     522.7 Vibrasi (AH)                                                                                           522.8.5 Jika stres tarik permanen diterapkan pada sistem perkawatan (misalnya karena beratnya
                                                                                                                                                                  sendiri pada jalur vertikal), jenis kabel atau konduktor yang sesuai dengan luas penampang dan metode
                                                     522.521 Sistem perkawatan yang ditopang oleh atau magun ke struktur perlengkapan yang terkena                pemasangan yang sesuai harus dipilih sedemikian sehingga konduktor atau kabel tidak rusak karena
                                                     vibrasi dengan keganasan medium (AH2) atau keganasan tinggi (AH3) harus sesuai untuk kondisi                 beratnya sendiri.
                                                     tersebut, khususnya jika terkait dengan kabel dan hubungan kabel.
                                                                                                                                                                  522.8.6 Sistem perkawatan yang dimaksudkan untuk penarikan konduktor atau kabel masuk atau
                                                     CATATAN                                                                                                      keluar, harus mempunyai sarana akses yang memadai untuk memungkinkan operasi ini.
                                                     Perhatian khusus sebaiknya diberikan untuk hubungan ke perlengkapan vibrasi. Tindakan lokal dapat diadopsi
                                                     seperti sistem perkawatan fleksibel.                                                                         522.8.7 Sistem perkawatan yang ditanam dalam lantai harus diproteksi secara memadai untuk
                                                                                                                                                                  mencegah kerusakan yang disebabkan oleh penggunaan lantai yang dimaksudkan.
                                                     522.522 Instalasi magun dari perlengkapan pemanfaat gantung, misalnya luminer, harus dihubungkan
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     dengan kabel dengan inti fleksibel. Jika diperkirakan tidak ada vibrasi atau gerakan, dapat digunakan        522.8.8 Sistem perkawatan yang magun secara kaku dan ditanam dalam dinding harus dipasang
                                                     kabel dengan inti nonfleksibel.                                                                              horizontal atau vertikal atau paralel dengan tepi ruangan.
                                                     522.8 Stres mekanis lain (AJ)                                                                                Sistem perkawatan yang tersembunyi dalam struktur tapi tidak magun dapat mengikuti rute praktis
                                                                                                                                                                  terpendek.
                                                     522.8.1 Sistem perkawatan harus dipilih dan dipasang sedemikian sehingga selama pemasangan,
                                                     penggunaan atau pemeliharaan, mencegah kerusakan pada selubung atau insulasi kabel, konduktor                522.8.9 Sistem perkawatan fleksibel harus dipasang sedemikian sehingga dihindari stres tarik yang
                                                     berinsulasi dan terminasinya.                                                                                berlebihan pada konduktor dan hubungan.
                                                     522.8.2 Jika ditanam dalam struktur, konduit atau sistem talang kabel harus secara lengkap dipasang
                                                                                                                                                                      PENJELASAN
                                                     untuk setiap sirkit sebelum setiap konduktor berinsulasi atau kabel ditarik.
                                                     522.8.3 Radius setiap belokan dalam sistem perkawatan harus sedemikian sehingga konduktor atau                  Tambahan diadopsi dari IEC 61200-52.
                                                     kabel tidak boleh rusak (Lihat Lampiran 52E).
                                                                                                                                                                     522.8.101 Pengurangan risiko hubung pendek atau gangguan bumi
                                                           PENJELASAN                                                                                                Jika gawai untuk proteksi hubung pendek ditempatkan sesuai dengan 434.2.1, disyaratkan
                                                                                                                                                                     bahwa konduktor harus dipasang sedemikian sehingga mengurangi risiko hubung pendek
                                                                                                                                                                     menjadi minimum.
                                                           Lihat Tabel E.52.2 PUIL, Radius belokan minimum yang direkomendasikan pada suhu kabel.
                                                                                                                                                                     Hal ini menyatakan bahwa susunan konduktor sebaiknya dibuat sedemikian sehingga
                                                     522.8.4 Jika konduktor atau kabel tidak ditopang secara kontinu karena metode pemasangannya,                    meminimalkan risiko kontak antara konduktor serta kontak konduktor aktif dengan bagian
                                                                                                                                                                     dibumikan dan untuk memberikan proteksi terhadap kerusakan karena pengaruh eksternal
                                                     maka harus ditopang dengan sarana yang sesuai pada interval yang memadai sedemikian sehingga
                                                                                                                                                                     (misalnya kerusakan mekanis).
                                                     konduktor atau kabel tidak rusak karena beratnya sendiri (Lihat Lampiran 52E).
                                                                                                                                                                     Contoh susunan tersebut adalah sbb:
                                                           PENJELASAN
                                                                                                                                                                     - Susunan terdiri atas kabel inti tunggal sesuai dengan SNI IEC 60502-1, kabel berselubung
                                                           Lihat Tabel E.52.1PUIL, Jarak penyangga untuk kabel nonarmor pada posisi yang dapat                          nonlogam inti tunggal sesuai dengan SNI 04-6629.4 atau kabel fleksibel berinsulasi dan
                                                           diakses.                                                                                                     berselubung karet inti tunggal sesuai dengan SNI 04-6629.4 dan jika risiko kerusakan
                                                                                                                                                                        mekanis dicegah.
                                                     106     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                   Persyaratan Umum Instalasi Listrik 2011   107
                                                                                                                                                                       PENJELASAN
                                                           - Kabel dan kabel fleksibel berinsulasi dan berselubung karet diletakkan sedemikian
                                                              sehingga dapat diakses tapi tidak di dekat bahan mudah terbakar dan jika risiko                         Jika sistem perkawatan dipasang luar ruang, sebaiknya diberikan perhatian khusus pada efek
                                                              kerusakan mekanis dicegah.                                                                              radiasi matahari. Dua efek utama yang harus dipertimbangkan adalah efek pemanasan dan
                                                           - Kabel dengan selubung nonlogam yang dipasang dalam konduit kaku, fleksibel atau                          kestabilan ultraviolet (UV). Seperti ditunjukkan dalam 512.2.2 Bagian 5-51 dan Tabel 51A
                                                              pliabel (pliable – semifleksibel) sesuai dengan SNI IEC 61386-21, 61386-22 atau 61386-                  PUIL, jika produk karena konstruksinya tidak mempunyai karakteristik yang relevan pada
                                                              23.                                                                                                     pengaruh eksternal lokasinya, meskipun demikian dapat digunakan pada kondisi yang diberi
                                                           - Kabel dengan selubung nonlogam yang dipasang dalam sistem berumbung atau talang                          proteksi tambahan yang tepat pada pemasangan instalasi, misalnya seperti interposisi skrin.
                                                              sesuai dengan seri IEC 61084.
                                                                                                                                                                      CATATAN 1
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                           Berkaitan dengan keselamatan, susunan kabel atau konduktor berinsulasi yang dapat                          Seri IEC 60287 memberikan metode untuk menentukan kapasitas hantar arus dalam hal radiasi
                                                                                                                                                                      matahari.
                                                           terbakar tanpa membahayakan lingkungannya (misalnya kabel terpendam) dianggap setara
                                                           dengan sirkit yang dipasang sedemikian sehingga mengurangi risiko hubung pendek menjadi
                                                           minimum.
                                                                                                                                                                   522.12      Efek seismik (AP)
                                                     522.9 Keberadaan flora dan/atau pertumbuhan jamur (AK)                                                        522.12.1 Sistem perkawatan harus dipilih dan dipasang dengan memperhatikan bahaya seismik
                                                                                                                                                                   lokasi instalasi.
                                                     522.9.1 Jika kondisi yang dialami atau diperkirakan menyebabkan bahaya (AL2), sistem perkawatan
                                                                                                                                                                   522.12.2 Jika bahaya seismik yang dialami adalah keganasan rendah (AP2) atau lebih tinggi, harus
                                                     harus dipilih dengan tepat atau tindakan proteksi khusus harus diadopsi.
                                                                                                                                                                   diberikan perhatian khusus pada berikut:
                                                     CATATAN                                                                                                       - pemagun sistem perkawatan ke struktur bangunan;
                                                     Mungkin perlu metode instalasi yang memfasilitasi penghilangan pertumbuhan jamur tersebut (lihat ayat 529).   - hubungan antara perkawatan magun dan semua komponen peralatan penting, misalnya
                                                                                                                                                                       pelayanan keselamatan, harus dipilih berdasarkan mutu fleksibelnya.
                                                     522.10 Keberadaan fauna (AL)
                                                                                                                                                                   522.13      Angin (AR)
                                                     522.10.1 Jika kondisi yang dialami atau diperkirakan menyebabkan bahaya (AL2), sistem perkawatan
                                                     harus dipilih dengan tepat atau tindakan proteksi khusus harus diadopsi, misalnya dengan:                     522.13.1 Lihat 522.7, Vibrasi (AH) dan 522.8, Stres mekanis lain (AJ).
                                                     - karakteristik mekanis sistem perkawatan; atau
                                                     - lokasi terpilih; atau                                                                                       522.14      Sifat bahan yang diproses atau disimpan (BE)
                                                     - ketentuan mengenai proteksi lokal tambahan atau mekanis umum; atau
                                                     - setiap kombinasi di atas.                                                                                   522.14.1 Lihat 527, Pemilihan dan pemasangan sistem perkawatan untuk meminimalkan rambatan
                                                                                                                                                                   api.
                                                     522.11 Radiasi matahari (AN)
                                                                                                                                                                   522.15      Desain bangunan (CB)
                                                     522.11.1 Jika radiasi matahari signifikan (AN2) dialami atau diperkirakan, sistem perkawatan yang
                                                     sesuai untuk kondisi tersebut harus dipilih dan dipasang atau harus disediakan pelindung yang memadai.        522.15.1 Jika ada risiko karena gerakan struktur (CB3), penopang kabel dan sistem proteksi yang
                                                                                                                                                                   digunakan harus mampu membolehkan gerakan relatif sedemikian sehingga konduktor dan kabel
                                                     CATATAN                                                                                                       tidak terkena stres mekanis yang berlebihan.
                                                     Lihat juga 522.2.1 berkaitan dengan kenaikan suhu.
                                                                                                                                                                   522.15.2 Untuk struktur fleksibel atau tak stabil (CB4), harus digunakan sistem perkawatan fleksibel.
                                                     108     Persyaratan Umum Instalasi Listrik 2011                                                                                                                               Persyaratan Umum Instalasi Listrik 2011   109
                                                     523 Kapasitas Hantar Arus (KHA)
                                                           PENJELASAN                                                                                             523.3 Nilai KHA yang sesuai juga dapat ditentukan seperti diuraikan dalam IEC 60287, atau dengan
                                                                                                                                                                  pengujian, atau dengan perhitungan dengan menggunakan metode yang dikenal, asalkan metode itu
                                                                                                                                                                  dinyatakan Jika sesuai, harus diperhitungkan karakteristik beban dan untuk kabel tertanam, resistans
                                                           KHA kabel dipengaruhi oleh jenis bahan insulasi kabel, suhu ambien, metode pemasangan,
                                                                                                                                                                  termal efektif dari tanah.
                                                           pengelompokan dan adanya insulasi termal. Lihat CATATAN dalam 522.11.
                                                           Lampiran B mencakup tabel faktor reduksi untuk jumlah terbatas sirkit. Menambah jumlah
                                                                                                                                                                  523.4 Suhu ambien adalah suhu medium sekitar ketika kabel atau konduktor berinsulasi yang
                                                                                                                                                                  dalam pertimbangan dianggap tidak berbeban.
                                                           sirkit dalam kelompok (konduktor di dalam metode pemasangan tunggal) akan mensyaratkan
                                                           reduksi lebih lanjut pada KHA konduktor tersebut (faktor reduksi lebih kecil dari yang                 523.5 Kelompok yang terdiri atas lebih dari satu sirkit
                                                           ditentukan untuk jumlah maksimum sirkit atau konduktor), karena efek pemanasan yang
                                                           meningkat. Karena itu, direkomendasikan bahwa kelompok tersebut, dengan sirkit atau
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                                  Faktor reduksi kelompok dapat diterapkan pada kelompok konduktor berinsulasi atau kabel yang
                                                           konduktor lebih banyak dari maksimum yang ditunjukkan dalam tabel, dibagi menjadi
                                                                                                                                                                  mempunyai suhu operasi maksimum yang sama.
                                                           kelompok yang lebih kecil dari sirkit atau konduktor dengan jarak yang disediakan antara
                                                           kelompok.                                                                                              Untuk kelompok yang terdiri atas kabel atau konduktor berinsulasi yang mempunyai suhu operasi
                                                                                                                                                                  maksimum yang berbeda, KHA semua kabel atau konduktor berinsulasi pada kelompok harus
                                                     523.1 Arus yang dihantarkan oleh setiap konduktor untuk periode berkesinambungan selama operasi              didasarkan pada suhu operasi maksimum terendah dari setiap kabel dalam kelompok bersama-sama
                                                                                                                                                                  dengan faktor reduksi kelompok yang sesuai.
                                                     normal harus sedemikian sehingga batas suhu yang sesuai yang ditentukan dalam Tabel 52-4 tidak
                                                     dilampaui. Nilai arus harus dipilih sesuai dengan 523.2, atau ditentukan sesuai dengan 523.3.                Jika karena kondisi operasi yang diketahui, kabel atau konduktor berinsulasi diperkirakan
                                                                                 Tabel 52-4 Suhu operasi maksimum untuk jenis insulasi                            menghantarkan arus tidak lebih besar dari 30 % peringkat kelompoknya, hal itu dapat diabaikan
                                                                                                                                                                  untuk keperluan memperoleh faktor reduksi untuk sisa kelompok.
                                                                                                                                         Batas suhua
                                                      Jenis insulasi
                                                                                                                                             °C                   523.6 Jumlah konduktor berbeban
                                                      Polivinil klorida (PVC)                                                 70 pada konduktor                   523.6.1 Jumlah konduktor yang dipertimbangkan dalam suatu sirkit adalah yang menghantarkan
                                                      Polietilen ikat silang (XLPE) dan karet propilen etilen (EPR)           90 pada konduktor b
                                                      Mineral (ditutup PVC atau polos dapat disentuh)                                                             arus beban. Jika dapat diasumsikan bahwa konduktor dalam sirkit polifase menghantarkan arus
                                                                                                                              70 pada selubung                    seimbang, konduktor netral terkait tidak perlu dipertimbangkan. Pada kondisi ini kabel 4-inti diberi
                                                      Mineral (polos tidak dapat disentuh dan tidak kontak dengan bah 105 pada selubung b, c
                                                      an                                                                                                          kapasitas yang sama seperti kabel 3-inti yang mempunyai luas penampang yang sama untuk setiap
                                                      ayang
                                                                                                                                                                  konduktor fase. Kabel 4-inti dan 5-inti dapat mempunyai KHA lebih tinggi jika hanya tiga konduktor
                                                        Suhumudah    terbakar)
                                                              konduktor  maksimum yang diizinkan tercantum dalam Tabel 52-4 yang mendasari tabel KHA dal
                                                      am                                                                                                          yang dibebani.
                                                      Lampiran A, diambil dari IEC 60502 (1983) dan IEC 60702 (1981) dan diperlihatkan pada tabel ini
                                                                                                                             o
                                                                                                                                                                      PENJELASAN
                                                      b
                                                        Jika
                                                        yangkonduktor beroperasi pada suhu yang melebihi 70 C, maka harus ditegaskan bahwa perlengkapan
                                                      dihubungkan ke konduktor sesuai untuk suhu yang dihasilkan pada hubungan.
                                                      c Untuk kabel berinsulasi mineral, suhu operasi yang lebih tinggi dapat diizinkan tergantung pada peringk
                                                      at
                                                      suhu kabel, terminasinya, kondisi lingkungan dan pengaruh eksternal lain.
                                                     523.2 Persyaratan 523.1 dianggap dipenuhi jika arus untuk konduktor berinsulasi dan kabel tanpa
                                                     armor tidak melebihi nilai yang sesuai yang dipilih dari tabel pada Lampiran A dengan acuan Tabel
                                                     52-3, dikenai setiap faktor koreksi yang perlu yang diberikan dalam Lampiran A.
                                                     110     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                       Persyaratan Umum Instalasi Listrik 2011   111
                                                                                                                                                             524 Luas penampang konduktor
                                                     523.6.2 Jika konduktor netral pada kabel multiinti menghantarkan arus sebagai hasil ketakseimbangan     524.1 Luas penampang konduktor lin dalam sirkit a.b. dan konduktor aktif dalam sirkit a.s. tidak
                                                     dalam arus fase, kenaikan suhu karena arus netral diimbangi dengan reduksi pada bahang yang             boleh kurang dari nilai yang diberikan dalam Tabel 52-5.
                                                     ditimbulkan oleh satu atau lebih konduktor fase. Dalam hal ini ukuran konduktor harus dipilih
                                                     berdasarkan arus fase tertinggi.                                                                        CATATAN 1
                                                     Dalam semua hal konduktor netral harus mempunyai luas penampang yang memadai untuk                      Hal ini untuk alasan mekanis.
                                                     mendapatkan kesesuaian dengan 523.1.
                                                                                                                                                             CATATAN 2
                                                                                                                                                             Untuk batas dimensi konduktor bulat lihat Lampiran 52F.
                                                     523.6.3 Jika konduktor netral menghantarkan arus tanpa reduksi terkait pada beban konduktor fase,
                                                     konduktor netral harus memperhitungkan kepastian peringkat sirkit. Arus tersebut dapat disebabkan
                                                     oleh arus harmonik yang signifikan dalam sirkit trifase. Jika kadar harmonik lebih besar dari 10 %,         PENJELASAN
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     konduktor netral tidak boleh lebih kecil dari konduktor fase. Pengaruh termal karena keberadaan arus
                                                     harmonik dan faktor reduksi terkait untuk arus harmonik yang lebih tinggi diberikan dalam Lampiran D.       Yang dimaksud dengan konduktor aktif adalah konduktor atau bagian konduktif yang
                                                                                                                                                                 dimaksudkan untuk dienergisasi pada operasi normal, termasuk konduktor netral, tetapi
                                                                                                                                                                 dengan konvensi bukan konduktor PEN (gabungan konduktor proteksi PE dan konduktor
                                                                                                                                                                 netral N).
                                                                                                                                                                 CATATAN
                                                                                                                                                                 Konsep ini tidak perlu menyatakan risiko kejut listrik
                                                                                                                                                             524.2 Konduktor netral, jika ada, harus mempunyai luas penampang yang sama seperti konduktor
                                                                                                                                                             lin:
                                                                                                                                                             - dalam sirkit fase tunggal, dua kawat, berapapun penampangnya;
                                                                                                                                                             - dalam sirkit polifase dan fase tunggal tiga kawat, jika ukuran konduktor lin kurang dari atau
                                                                                                                                                                  sama dengan 16 mm² tembaga atau 25 mm² aluminium.
PENJELASAN
                                                                                                                                                                 Untuk sirkit trifase dan fase tunggal tiga kawat (yang lazim di Indonesia), maka luas
                                                                                                                                                                 penampang konduktor netral harus sama dengan luas penampang konduktor lin berukuran
                                                                                                                                                                 lebih kecil atau sama dengan 16 mm2 tembaga atau 25 mm2 aluminium.
                                                                                                                                                             524.3 Untuk sirkit polifase jika setiap konduktor fase mempunyai luas penampang lebih besar dari
                                                                                                                                                             16 mm2 tembaga atau 25 mm2 aluminium, konduktor netral dapat mempunyai luas penampang lebih
                                                                                                                                                             kecil dari konduktor lin, jika kondisi berikut secara serentak dipenuhi:
                                                                                                                                                             -   arus maksimum yang diperkirakan termasuk harmonik, jika ada, pada konduktor netral selama
                                                                                                                                                                  pelayanan normal tidak lebih besar dari KHA luas penampang konduktor netral yang dikurangi;
                                                     112   Persyaratan Umum Instalasi Listrik 2011                                                                                                                          Persyaratan Umum Instalasi Listrik 2011   113
                                                     CATATAN                                                                                                       CATATAN 1
                                                     Beban yang dihantarkan oleh sirkit pada kondisi pelayanan normal sebaiknya terdistribusi merata antar
                                                                                                                                                                   Konektor yang digunakan untuk terminasi konduktor aluminium harus diuji dan disahkan untuk penggunaan
                                                     fase.
                                                                                                                                                                   spesifik ini.
                                                     -     konduktor netral diproteksi terhadap arus lebih menurut persyaratan 431.2 Bagian 4-43;                  CATATAN 2
                                                     -     ukuran konduktor netral sekurangnya sama dengan 16 mm2 tembaga atau 25 mm² aluminium.                   Pada sirkit sinyal dan kendali yang dimaksudkan untuk perlengkapan elektronik, diizinkan menggunakan luas
                                                                                                                                                                   penampang minimum 0,1 mm2.
                                                           PENJELASAN
                                                                                                                                                                   a
                                                                                                                                                                     Pada kabel fleksibel multiinti yang berisikan tujuh inti atau lebih, berlaku Catatan 2.
                                                                                                                                                                     antar fase.
                                                           Khusus untuk sirkit trifase yang mempunyai konduktor lin dengan luas penampang lebih
                                                           besar dari 16 mm² tembaga atau 25 mm² aluminium, konduktor netral dapat mempunyai
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                                      PENJELASAN
                                                           luas penampang yang lebih kecil dari luas penampang konduktor lin (dikurangi), asalkan
                                                           ketiga persyaratan ini dipenuhi:
                                                           - arus maksimum termasuk arus harmonik tidak melebihi KHA konduktor netral yang luas                       Dengan mempertimbangkan pertumbuhan beban pada instalasi, maka kabel dan konduktor
                                                               penampangnya dikurangi;                                                                                berinsulasi yang digunakan untuk sirkit daya dan pencahayaan magun sebaiknya mempunyai
                                                           - konduktor netral diproteksi terhadap arus lebih;                                                         luas penampang minimum 2,5 mm2 untuk tembaga, dan sesuai SNI IEC 60228:2009: 10 mm²
                                                           - luas penampang konduktor netral minimum 16 mm² tembaga atau 25 mm² aluminium.                            untuk aluminium.
                                                               Dengan persyaratan di atas, terutama jika perhitungan arus harmonik sulit dilakukan,
                                                               sebaiknya luas penampang konduktor netral minimum sama dengan luas penampang
                                                               konduktor lin.
                                                                                                                                         Konduktor
                                                         Jenis sistem perkawatan                    Penggunaan sirkit                       Luas penampang
                                                                                                                               Bahan
                                                                                                                                                  mm2
                                                                           Kabel dan Sirkit daya dan                         Tembaga                1,5
                                                         Instalasi         konduktor pencahayaan                             Aluminium     2,5 (lihat Catatan 1)
                                                         magun             berinsulasi Sirkit sinyal dan kendali             Tembaga       0,5 (lihat Catatan 2)
                                                         (terpasang                                                          Tembaga                 10
                                                         tetap)            Konduktor Sirkit sinyal dan kendali
                                                                                                                             Aluminium               16
                                                                           polos
                                                                                     Sirkit sinyal dan kendali               Tembaga                 4
                                                                                                                                            Seperti ditentukan
                                                                                              Untuk peranti spesifik                        dalam standar IEC
                                                         Hubungan fleksibel
                                                                                                                             Tembaga          yang relevan
                                                         dengan konduktor                                                                         0,75a
                                                                                              Untuk setiap penerapan lai
                                                         berinsulasi dan kabel
                                                                                              n
                                                                                              Sirkit voltase ekstra rendah                        0,75
                                                                                              untuk penerapan khusus
                                                     114      Persyaratan Umum Instalasi Listrik 2011                                                                                                                                        Persyaratan Umum Instalasi Listrik 2011   115
                                                     525 Drop voltase dalam instalasi pelanggan                                                                      526 Hubungan listrik
                                                     CATATAN 1                                                                                                       526.1 Hubungan antara konduktor dan antara konduktor dan perlengkapan lain harus memberikan
                                                     Direkomendasikan bahwa secara praktis drop voltase antara awal instalasi pelanggan dan perlengkapan sebaiknya   kontinuitas listrik yang awet serta kuat mekanis dan proteksi yang memadai.
                                                     tidak lebih dari 4 % dari voltase nominal instalasi.
                                                                                                                                                                     CATATAN
                                                                                                                                                                     Lihat IEC 61200-52.
                                                     Pertimbangan lain mencakup waktu asut untuk motor dan perlengkapan dengan arus bandang
                                                     (inrush current) tinggi.                                                                                        526.2 Pemilihan sarana hubungan harus memperhitungkan, jika sesuai, untuk:
                                                                                                                                                                     a.    bahan konduktor dan insulasinya;
                                                     Kondisi temporer seperti transien voltase dan variasi voltase karena operasi abnormal dapat diabaikan.          b.    jumlah dan bentuk kawat yang membentuk konduktor;
                                                                                                                                                                     c.    luas penampang konduktor; dan
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                                     CATATAN
                                                                                                                                                                     Penggunaan hubungan solder sebaiknya dihindari pada perkawatan daya. Jika digunakan, hubungan sebaiknya
                                                                                                                                                                     dirancang dengan memperhitungkan stres rambat dan mekanis (lihat 522.6, 522.7 dan 522.8).
                                                                                                                                                                     526.3 Semua hubungan harus dapat diakses untuk inspeksi, pengujian dan pemeliharaan, kecuali
                                                                                                                                                                     untuk berikut:
                                                                                                                                                                     a. sambungan kabel tertanam;
                                                                                                                                                                     b. sambungan berisi kompon atau berkapsul;
                                                                                                                                                                     c. hubungan antara ujung dingin (cold tail) dan elemen pemanas seperti sistem pemanasan plafon,
                                                                                                                                                                         lantai dan teras (terrace).
                                                                                                                                                                     526.4 Jika perlu, tindakan pencegahan harus diambil sedemikian sehingga suhu yang dicapai pada
                                                                                                                                                                     hubungan dalam pelayanan normal tidak boleh mengurangi keefektifan insulasi konduktor yang
                                                                                                                                                                     dihubungkan padanya atau menopangnya.
                                                     116    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                          Persyaratan Umum Instalasi Listrik 2011   117
                                                           PENJELASAN
                                                                                                                                                         - Jarak antara peralatan guna memperbaiki ventilasi alami. Jarak antara peralatan yang
                                                                                                                                                            berdekatan memungkinkan disipasi bahang yang lebih baik. Perlu untuk mengcu pada
                                                           Tambahan diadopsi dari IEC 61200-52.                                                             petunjuk pabrikan. Penyelesaian ini khususnya direkomendasikan bila sejumlah besar
                                                                                                                                                            item peralatan dipasang pada selungkup (kubikel atau lemari) yang sama.
                                                           526.4 Suhu maksimum terminal pada kondisi layanan normal
                                                                                                                                                         - Susunan peralatan yang tepat untuk mendisipasi bahang di dalam selungkup.
                                                           526.4.101 Umum
                                                                                                                                                           Direkomendasikan bahwa peralatan yang mendisipasi bahang dipasang dengan
                                                           Suhu terminal adalah jumlah suhu ambien dan kenaikan suhunya dalam layanan normal.              cara yang tepat sedemikian sehingga operasi yang benar dari peralatan lain tidak
                                                                                                                                                           terganggu. Sarana lain, seperti misalnya interposisi skrin atau deflektor, dapat
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                           Standar produk memberikan nilai batas konvensional untuk kenaikan suhu pada kondisi uji         digunakan untuk keperluan ini.
                                                           yang ditentukan. Untuk kondisi pemasangan yang berbeda dari kondisi uji yang ditentukan,
                                                           faktor peringkat mungkin perlu diterapkan dan petunjuk sebaiknya diperoleh dari pabrikan.     - Ventilasi alami atau paksa atau pengondisi udara kubikel, lemari atau lokasi. Ventilasi
                                                           Standar relevan terkait hal ini adalah seri IEC 61439 dan IEC 60890.                            paksa peralatan dapat diperlukan, untuk alasan selain pendinginan, pada penerapan
                                                                                                                                                           spesifik, misalnya untuk memproteksi terhadap masuknya debu.
                                                           Suhu pada terminal dipengaruhi oleh bahang yang didisipasikan oleh peralatan dalam
                                                           layanan normal. Bahang ini dapat disebabkan oleh susut internal yang didisipasikan dalam      - Penurunan peringkat peralatan dengan penggunaan peralatan yang mempunyai arus
                                                           peralatan dan oleh sumber bahang internal dan eksternal yang berdekatan, jika ada. Sumber       pengenal yang lebih tinggi, akibatnya mendisipasi bahang lebih rendah. Penurunan
                                                           bahang eksternal yang mungkin adalah kabel sistem perkawatan yang dihubungkan ke                peringkat peralatan dapat digunakan untuk mengurangi suhu terminal, asalkan
                                                           terminal peralatan.                                                                             penurunan peringkat tersebut diizinkan untuk peralatan.
                                                           Kompatibilitas antara suhu yang dicapai pada terminal peralatan dan suhu yang diizinkan       - Pemilihan bahan untuk selungkup atau kubikel dimana terminal dipasang guna
                                                           untuk insulasi konduktor dan kabel sebaiknya diperoleh dengan susunan yang memadai              memperbaiki disipasi termal. Selungkup logam tipis akan mendisipasi bahang lebih siap
                                                           selama desain/pemasangan.                                                                       darpada selungkup berdinding tebal yang dibuat dari bahan insulasi.
                                                           Tabel nilai KHA konduktor dihitung sedemikian sehingga suhu pada inti tidak melebihi          - Pemeliharaan pengkleman yang benar dari konduktor pada terminal. Susunan
                                                           suhu yang dapat diizinkan yang ditentukan dengan pemilihan insulasi. KHA ini tidak              sebaiknya dibuat untuk memastikan pemeliharaan tekanan klem konduktor pada
                                                           memperhitungkan setiap kenaikan suhu pada terminasi.                                            terminalnya. Susunan tersebut dapat inheren (misalnya menggunakan hubungan
                                                                                                                                                           berpegas (resilient connections) atau hasil dari petunjuk untuk inspeksi instalasi.
                                                           526.4.201       Pembatasan suhu pada terminal
                                                           Perlu untuk membatasi suhu pada terminal sedemikian sehingga batas suhu puncak atau           - Penggunaan terminal antara (dengan suhu operasi pengenal yang tepat) di luar
                                                           keadaan tunak (steady-state) maksimum insulasi dari konduktor yang dihubungkan ke               pemanfaat listrik yang memungkinkan konduktor berluas penampang lebih besar atau
                                                           terminal dan dari setiap bahan insulasi yang digunakan untuk menopang hubungan tidak            jenis kabel bersuhu lebih tinggi dihubungkan.
                                                           dilampaui. Suhu pada terminal dapat dibatasi dengan salah satu atau lebih tindakan berikut:
                                                                                                                                                         - Jika kabel yang diizinkan bersuhu melebihi 70 oC (misalnya kabel berinsulasi taut
                                                           - Pembatasan isi selungkup (kubikel, lemari, berumbung, konduit).                                silang) dihubungkan ke peralatan atau lengkapan yang didesain untuk beroperasi
                                                             Pembatasan isi berumbung dan konduit direkomendasikan bila jumlah sirkit yang besar            pada suhu tidak melebihi 70 oC, ukuran konduktor sebaiknya dipilih berdasarkan pada
                                                             keluar dari panel yang sama; dalam hal ini, lebih disukai untuk membagi sirkit antara          peringkat arus untuk kabel 70 oC atau kontruksi serupa.
                                                             jalur berumbung atau konduit.
                                                     118     Persyaratan Umum Instalasi Listrik 2011                                                                                                               Persyaratan Umum Instalasi Listrik 2011   119
                                                                                                                                                         527 Pemilihan dan pemasangan sistem perkawatan untuk
                                                                                                                                                         meminimalkan rambatan api
                                                           -     Hubungan panjang konduktor yang pendek pada terminasi, yang luas penampangnya           527.1.2 Sistem perkawatan harus dipasang sedemikian sehingga kinerja struktur bangunan umum dan
                                                                 lebih besar dari yang disyaratkan untuk arus, akan mengurangi suhu terminasi.           keselamatan kebakaran tidak berkurang.
                                                                 Penambahan luas penampang konduktor untuk alasan lain (drop voltase, ketahanan          527.1.3 Kabel yang memenuhi sekurangnya persyaratan IEC 60332-1 dan produk yang mempunyai
                                                                 arus hubung pendek, pengurangan impedans lingkar gangguan) memperbaiki
                                                                                                                                                         ketahanan api yang diperlukan yang ditentukan dalam IEC 60614 dan standar IEC lain untuk sistem
                                                                 ketahanan termal konduktor dan karena itu mengurangi kemungkinan suhu terminal
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                         527.1.4 Kabel yang tidak memenuhi, sebagai minimum, persyaratan perambatan nyala api IEC 60322-
                                                           -    Pemilihan insulasi konduktor dengan tetap memperhatikan suhu terminal. Suhu
                                                                                                                                                         1 jika digunakan harus dibatasi panjangnya sependek mungkin untuk hubungan peranti ke sistem
                                                                yang diizinkan pada layanan keadaan tunak untuk beberapa jenis insulasi konduktor
                                                                                                                                                         perkawatan permanen dan dalam semua hal tidak melintas dari salah satu kompartemen pemisah api
                                                                ditentukan oleh TC 20: Electric cables. Jika digunakan kabel dengan insulasi elastomer
                                                                                                                                                         ke kompartemen lain.
                                                                daripada termoplastik, guna memanfaatkan suhu operasinya yang lebih tinggi, mungkin
                                                                perlu menurunkan peringkat peralatan dimana kabel dipasang. Dalam hal ini minta
                                                                nasehat dari pabrikan peralatan. Suhu untuk bahan insulasi yang biasa digunakan               PENJELASAN
                                                                diberikan di bawah ini:
                                                                1. termoplastik (PVC):                    70 °C;                                             Semua kabel voltase rendah berinsulasi PVC sesuai seri SNI 04-6629, “Kabel berinsulasi
                                                                2. taut silang (XLPE, EPR)                90 °C;                                             PVC dengan tegangan pengenal sampai dengan 450/750 V” dan kabel sesuai SNI IEC 60502-
                                                                3. taut silang (silikon)                 120 °C.                                             1:2009, “Kabel daya dengan insulasi terekstrusi dan lengkapannya untuk voltase pengenal
                                                                                                                                                             dari 1 kV (Um = 1,2 kV) sampai dengan 30 kV (Um = 36 kV) – Bagian 1: Kabel untuk voltase
                                                           -    Penguatan atau penggantian insulasi konduktor di dekat terminal dengan selongsong
                                                                                                                                                             pengenal 1 kV (Um = 1,2 kV) dan 3 kV (Um = 3,6 kV)” yang digunakan dalam instalasi listrik
                                                                (sleeve) yang mengizinkan suhu yang lebih tinggi akan mengurangi risiko degradasi            (semuanya merupakan SNI wajib) harus memenuhi persyaratan lulus uji hambat api (fire
                                                                termal insulasi pada terminal. Konduktor berinsulasi yang mengizinkan suhu sedikitnya        retardant) menurut IEC 60332-1.
                                                                sama dengan 110 °C direkomendasikan untuk menyuplai peralatan yang beroperasi
                                                                pada suhu tinggi, seperti misalnya peranti pemanas.
                                                     120       Persyaratan Umum Instalasi Listrik 2011                                                                                                                                 Persyaratan Umum Instalasi Listrik 2011   121
                                                                                                                                                           528 Kedekatan sistem perkawatan ke instalasi lain
                                                     527.1.5 Bagian sistem perkawatan selain kabel yang tidak memenuhi persyaratan minimum                 528.1       Kedekatan ke instalasi listrik
                                                     perambatan nyala api IEC 60614 dan standar IEC lain untuk sistem perkawatan, tetapi memenuhi semua
                                                     yang berkaitan dengan IEC 60614 dan standar IEC lain untuk sistem perkawatan, jika digunakan harus    Sirkit voltase rentang I dan rentang II tidak boleh digabung dalam sistem perkawatan yang sama kecuali
                                                     secara utuh terselungkup dalam bahan bangunan yang tak mudah terbakar.                                setiap kabel diinsulasi untuk voltase tertinggi yang ada atau salah satu metode berikut diadopsi:
                                                                                                                                                           - setiap konduktor kabel multiinti diinsulasi untuk voltase tertinggi yang ada pada kabel; atau
                                                           PENJELASAN                                                                                      - kabel diinsulasi untuk voltase sistemnya dan dipasang dalam kompartemen terpisah pada sistem
                                                                                                                                                                 talang atau berumbung kabel; atau
                                                                                                                                                           - digunakan sistem konduit terpisah.
                                                           Seri IEC 60614 sudah ditarik dan dibatalkan oleh IEC, digantikan oleh seri IEC 61396, Conduit
                                                           systems for cable management.                                                                   CATATAN
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                           Pertimbangan khusus interferens listrik, elektromagnetik dan elektrostatik, dapat berlaku untuk sirkit
                                                                                                                                                           telekomunikasi, sirkit transfer data dan sejenis.
PENJELASAN
                                                                                                                                                              Berdasarkan Tabel 1 IEC 60449, yang dimaksud dengan rentang voltase I dan II adalah sbb:
                                                                                                                                                              Rentang I
                                                                                                                                                              Rentang I mencakup:
                                                                                                                                                              - instalasi dengan proteksi terhadap kejut yang diberikan pada kondisi tertentu berdasarkan
                                                                                                                                                                  nilai voltase;
                                                                                                                                                              - instalasi dengan voltase yang dibatasi karena alasan operasional (misalnya instalasi
                                                                                                                                                                  telekomunikasi, sinyal, bel, kendali dan alarm).
                                                                                                                                                              Rentang II
                                                                                                                                                              Rentang II mencakup voltase untuk menyuplai instalasi rumah tangga, komersial dan industri.
                                                                                                                                                              Rentang ini mencakup semua voltase sistem distribusi publik.
                                                     122      Persyaratan Umum Instalasi Listrik 2011                                                                                                                               Persyaratan Umum Instalasi Listrik 2011   123
                                                                                                                                                                 529 Pemilihan dan pemasangan sistem perkawatan berkaitan dengan
                                                                                                                                                                 kemampuan pemeliharaan termasuk pembersihan
                                                     528.2 Kedekatan dengan instalasi nonlistrik                                                                 529.1 Pengetahuan dan pengalaman personel yang mungkin melakukan pemeliharaan harus
                                                                                                                                                                 diperhitungkan pada pemilihan dan pemasangan sistem perkawatan.
                                                     528.2.1 Sistem perkawatan tidak boleh dipasang di dekat instalasi yang menghasilkan bahang, asap
                                                     atau uap yang mungkin merusak perkawatan, kecuali diproteksi dari efek berbahaya dengan perisai             529.2 Jika perlu melepas setiap tindakan proteksi guna melakukan pemeliharaan, harus dibuat
                                                     yang disusun sedemikian sehingga tidak mempengaruhi disipasi bahang dari perkawatan.                        ketentuan sedemikian sehingga tindakan proteksi dapat dikembalikan lagi tanpa mengurangi tingkat
                                                                                                                                                                 proteksi yang pada mulanya dimaksudkan.
                                                     528.2.2 Jika sistem perkawatan mempunyai rute di bawah instalasi yang dapat menyebabkan
                                                     kondensasi (seperti instalasi air, uap panas atau gas), harus diambil tindakan pencegahan untuk             529.3 Harus dibuat ketentuan untuk akses yang aman dan memadai ke semua bagian sistem
                                                     memproteksi sistem perkawatan dari efek yang mengganggu.                                                    perkawatan yang mungkin memerlukan pemeliharaan.
                                                     528.2.3 Jika instalasi listrik akan dipasang berdekatan dengan instalasi nonlistrik, maka harus disusun     CATATAN
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     sedemikian sehingga setiap operasi yang dapat diketahui yang dilakukan pada instalasi lain tidak akan       Pada beberapa situasi, mungkin perlu menyediakan sarana akses yang permanen dengan tangga, gang dsb.
                                                     menyebabkan kerusakan pada sistem instalasi listrik atau sebaliknya.
                                                                                                                                                                 5210 Identifikasi kabel dengan warna
                                                     CATATAN
                                                     Hal ini dapat dicapai dengan:                                                                               5210.1 Ketentuan umum
                                                     - jarak yang sesuai antara instalasi; atau                                                                  Persyaratan warna insulasi inti kabel berlaku untuk semua instalasi magun atau fleksibel, termasuk
                                                     - penggunaan perisai mekanis atau termal.                                                                   instalasi dalam perlengkapan listrik. Hal tersebut di atas diperlukan untuk mendapatkan kesatuan
                                                                                                                                                                 pengertian mengenai penggunaan sesuatu warna atau warna loreng yang digunakan untuk
                                                     528.2.4 Jika instalasi listrik terletak sangat dekat dengan instalasi nonlistrik, kedua kondisi berikut     mengidentifikasi inti kabel, guna keseragaman dan mempertinggi keamanan.
                                                     harus dipenuhi:
                                                                                                                                                                 CATATAN
                                                     - sistem perkawatan harus cukup diproteksi terhadap bahaya yang mungkin timbul dari adanya instalasi lain
                                                        pada penggunaan normal; dan                                                                              Lihat 134.1.3 Bagian 1.
                                                     - proteksi terhadap sentuh tak langsung harus digunakan sesuai dengan persyaratan Ayat 411.3 Bagian 4-41,
                                                                                                                                                                 5210.2 Penggunaan warna loreng hijau-kuning
                                                           instalasi logam nonlistrik akan dianggap sebagai BKE.
                                                                                                                                                                 Warna loreng hijau-kuning hanya boleh digunakan untuk menandai konduktor pembumian, konduktor
                                                                                                                                                                 proteksi, dan konduktor yang menghubungkan ikatan ekuipotensial ke bumi.
                                                           PENJELASAN
                                                                                                                                                                     PENJELASAN
                                                           Khusus untuk kabel tanah (misalnya NYY), lihat Subayat 7.14 Bagian 7 PUIL 2011.
                                                           Tambahan diadopsi dari IEC 61200-52.                                                                      Sesuai SNI 6629.1:2011 maka pembagian warna untuk inti berwarna hijau-kuning harus
                                                                                                                                                                     memenuhi kondisi berikut (sesuai dengan IEC 60173): untuk setiap 15 mm panjang inti, salah
                                                           Kedekatan dengan kabel komunikasi.
                                                                                                                                                                     satu warna tersebut harus mencakup sekurang-kurangya 30 % dan tidak lebih dari 70 %
                                                           Jika kabel daya yang ditanam dalam tanah dekat dengan komponen bawah tanah lin                            permukaan inti, warna lain mencakup sisanya.
                                                           telekomunikasi saluran udara termasuk penambat, penguat dan hubungan buminya,
                                                           direkomendasikan jarak bebas minimum 800 mm. Jarak bebas ini dapat dikurangi jika
                                                           kabel daya mempunyai proteksi tambahan terhadap kerusakan mekanis. Proteksi sebaiknya
                                                           menjangkau sedikitnya 500 mm pada kedua sisi di luar titik kedekatan.
                                                     124      Persyaratan Umum Instalasi Listrik 2011                                                                                                                               Persyaratan Umum Instalasi Listrik 2011   125
                                                                                                                                                            Lampiran A (normatif)
                                                                                                                                                            Kapasitas Hantar Arus (KHA)
A.52.1 Pendahuluan
                                                                                                                                                            Persyaratan lampiran ini dimaksudkan untuk memberikan umur konduktor dan insulasi yang
                                                                                                                                                            memuaskan yang terkena efek termal hantar arus untuk periode waktu yang lama dalam pelayanan
                                                                                                                                                            normal. Pertimbangan lain mempengaruhi pilihan kuas penempang konduktor, seperti persyaratan
                                                                                                                                                            untuk proteksi terhadap kejut listrik (Bagian 4-41), proteksi terhadap efek termal (Bagian 4-42), proteksi
                                                                                                                                                            arus lebih (Bagian 4-43), drop voltase (Ayat 525 standar ini), dan pembatasan suhu untuk terminal
                                                                                          Gambar - Contoh konduktor pembumian/proteksi                      perlengkapan yang konduktor dihubungkan padanya (Ayat 526 standar ini).
                                                                                                                                                            Untuk saat ini, lampiran ini hanya tentang kabel dan konduktor berinsulasi nonarmor yang mempunyai
                                                     5210.3 Penggunaan warna biru
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                            voltase nominal tidak melebihi 1 kV a.b. atau 1,5 kV a.s. Lampiran ini tidak berlaku untuk kabel inti
                                                     Warna biru digunakan untuk menandai konduktor netral atau kawat tengah, pada instalasi listrik
                                                     dengan konduktor netral. Untuk menghindarkan kesalahan, warna biru tersebut tidak boleh digunakan      tunggal berarmor.
                                                     untuk menandai konduktor lainnya. Warna biru hanya dapat digunakan untuk maksud lain, jika pada        CATATAN
                                                     instalasi listrik tersebut tidak terdapat konduktor netral atau kawat tengah. Warna biru tidak boleh
                                                                                                                                                            Jika digunakan kabel inti tunggal berarmor, dapat disyaratkan pengurangan KHA yang cukup besar yang diberikan
                                                     digunakan untuk menandai konduktor pembumian.
                                                                                                                                                            dalam lampiran ini. Pemasok kabel sebaiknya dikonsultasi. Hal ini juuga dapat diterapkan untuk kabel inti tunggal
                                                                                                                                                            nirarmor dalam talang logam jalur tunggal (lihat 521.5).
                                                           PENJELASAN
                                                                                                                                                            Nilai dalam Tabel A.52-2 hingga A.52-13 berlaku untuk kabel nirarmor dan telah didapatkan sesuai
                                                                                                                                                            dengan metode yang diberikan dalam IEC 60287 dengan menggunakan dimensi yang ditentukan dalam
                                                                                                                                                            IEC 60502 dan resistans konduktor yang diberikan dalam IEC 60228. Variasi praktis yang diketahui dalam
                                                                                                                                                            konstruksi kabel (misalnya bentuk konduktor) dan hasil toleransi pembuatan pada rentang dimensi
                                                                                                                                                            yang mungkin dan karena itu KHA untuk setiap ukuran konduktor. Tabel KHA telah dipilih sedemikian
                                                                                                                                                            sehingga memperhitungkan keselamatan rentang nilai KHA ini dan menempatkan pada kurva yang rata
                                                                                                                                                            jika diplot terhadap luas penampang konduktor.
                                                                                                                                                            Untuk kabel multiinti yang mempunyai konduktor dengan luas penampang 25 mm2 atau lebih besar,
                                                                                                                                                            diizinkan konduktor bulat atau sektor (shaped). Nilai tabel telah didapatkan dari dimensi yang sesuai
                                                                                                   Gambar - Contoh konduktor netral                         untuk konduktor sektor.
                                                     126     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                     Persyaratan Umum Instalasi Listrik 2011   127
                                                     A.52.2 Suhu ambien                                                                                                 A.52.4 Kelompok konduktor berinsulasi / kabel
                                                     A.52.2.1 Tabel KHA dalam lampiran ini berasumsi suhu ambien acuan berikut:                                         A.52.4.1 Jenis instalasi A hingga D dalam Tabel A.52-1
                                                     - untuk konduktor berinsulasi dan kabel di udara, tidak tergantung dari metode pemasangan: 30 °C;                  KHA yang diberikan dalam Tabel A.52-2 hingga A.52-7 berkaitan dengan sirkit tunggal yang tyerdiri atas
                                                     - untuk kabel tertanam, baik langsung dalam tanah atau dalam talang dalam tanah: 20 °C.                            jumlah konduktor berikut:
                                                                                                                                                                        - dua konduktor berinsulasi atau dua kabel inti tunggal, atau satu kabel inti kembar;
                                                     A.52.2.2 Jika suhu ambien pada lokasi yang dimaksudkan dari konduktor berinsulasi atau kabel,                      - tiga konduktor berinsulasi atau tiga kabel inti tunggal, atau satu kabel 3-inti.
                                                     berbeda dari suhu ambien acuan, faktor koreksi yang sesuai yang diberikan dalam Tabel A.52-14 dan                  Jika lebih banyak konduktor berinsulasi atau kabel dipasang dalam kelompok yang sama, faktor reduksi
                                                     A.52-15 harus diterapkan untuk nilai KHA yang ditentukan dalam A.52-2 hingga A.52-13. Untuk kabel                  kelompok yang ditentukan dalam Tabel A.52-17 hingga A.52-19 harus diterapkan.
                                                     tertanam, koreksi tidak diperlukan jika suhu tanah melebihi 25 °C hanya untuk beberapa minggu per
                                                                                                                                                                        CATATAN
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     tahun.
                                                                                                                                                                        Faktor reduksi kelompok telah dihitung berdasarkan operasi keadaan tunak yang lama pada faktor beban 100 %
                                                     CATATAN                                                                                                            untuk semua konduktor aktif. Jika pembebanan kurang dari 100 % sebagai hasil dari kondisi operasi instalasi,
                                                     Untuk kabel atau konduktor berinsulasi di udara, jika suhu ambien adakalanya melebihi suhu ambien acuan,           faktor reduksi kelompok dapat lebih tinggi.
                                                     kemungkinan penggunaan tabel KHA tanpa koreksi dalam pertimbangan.
                                                                                                                                                                        A.52.4.2 Jenis instalasi E dan F dalam Tabel A.52-1
                                                     A.52.2.3 Faktor koreksi dalam Tabel A.52-14 dan A.52-15 tidak memperhitungkan peningkatan, jika                    KHA Tabel A.52-8 hingga A.52-13 berkaitan dengan metode instalasi acuan.
                                                     ada, karena matahari atau radiasi infra merah lain. Jika kabel atau konduktor berinsulasi terkena radiasi          Untuk instalasi di atas rak, begel (cleat) dan sejenis, KHA untuk sirkit tunggal maupun sirkit kelompok
                                                     tersebut, KHA harus didapatkan dengan metode yang ditentukan dalam IEC 60287.                                      harus diperoleh dengan mengalikan kapasitas yang diberikan untuk susunan yang relevan dari konduktor
                                                                                                                                                                        berinsulasi atau kabel di udara bebas, seperti ditunjukkan dalam Tabel A.52-8 hingga A.52-13, dengan
                                                     A.52.3 Resistivitas termal tanah                                                                                   faktor reduksi instalasi dan kelompok yang diberikan dalam Tabel A.52-20 hingga A.52-21.
                                                     Tabel KHA dalam lampiran ini untuk kabel dalam tanah berkaitan dengan resistivitas termal tanah 2,5
                                                     K∙m/W. Nilai ini dianggap perlu sebagai tindakan untuk penggunaan di seluruh dunia jika jenis tanah                Catatan berikut mengenai A.52.4.1 dan A.52.4.2:
                                                     dan lokasi geografis tidak ditentukan (lihat IEC 60287-3-1).
                                                                                                                                                                        CATATAN 1
                                                     Di lokasi jika resistivitas termal tanah efektif lebih tinggi dari 2,5 K∙m/W, pengurangan KHA yang sesuai          Faktor reduksi kelompok telah dihitung sebagai rata-rata untuk julat ukuran konduktor, jenis kabel dan kondisi
                                                     harus dilakukan atau tanah di sekeliling kabel harus diganti dengan bahan yang lebih sesuai. Kasus                 instalasi yang dipertimbangkan. Perlu diperhatikan catatan di bawah setiap tabel. Dalam beberapa hal, dapat
                                                     tersebut biasanya dapat ditemui pada kondisi tanah yang sangat kering. Faktor koreksi untuk resistivitas           diinginkan perhitungan yang lebih tepat.
                                                     termal tanah selain 2,5 K∙m/W diberikan dalam Tabel A.52-15.
                                                                                                                                                                        CATATAN 2
                                                     CATATAN                                                                                                            Faktor reduksi kelompok telah dihitung berdasarkan kelompok yang terdiri atas konduktor berinsulasi atau kabel
                                                     Tabel KHA dalam lampiran ini untuk kabel dalam tanah dimaksudkan hanya berkaitan dengan jalur dalam dan            berbeban serupa. Jika kelompok terdiri atas berbagai ukuran kabel atau konduktor berinsulasi, harus diperhatikan
                                                     sekitar bangunan. Untul instalasi lain, jika penyelidikan menentapkan nilai resistivitas termal tanah yang lebih   pembebanan arus dari yang terkecil (lihat A.52.5).
                                                     akurat sesuai untuk beban yang dihantarkan, nilai KHA dapat didapatkan dengan metode perhitungan yang
                                                     diberikan dalam IEC 60287 atau diperoleh dari pabrikan kabel.                                                      A.52.5 Kelompok yang terdiri atas ukuran berbeda
                                                                                                                                                                        Faktor reduksi kelompok dalam tabel dapat diterapkan pada kelompok yang terdiri atas kabel berbeban
                                                                                                                                                                        serupa. Perhitungan faktor reduksi untuk kelompok yang terdiri atas ukuran berbeda dari konduktor
                                                                                                                                                                        berinsulasi atau kabel berbeban serupa tergantung pada jumlah total dalam kelompok dan campuran
                                                                                                                                                                        dari ukuran. Faktor tersebut tidak dapat ditabelkan tetapi harus dihitung untuk setiap kelompok. Metode
                                                                                                                                                                        perhitungan faktor tersebut di luar ruang lingkup standar ini. Beberapa contoh spesifik perhitungan
                                                                                                                                                                        tersebut yang dapat disarankan, diberikan di bawah ini.
                                                     128    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                   Persyaratan Umum Instalasi Listrik 2011   129
                                                     CATATAN
                                                     Kelompok yang terdiri atas ukuran konduktor yang merentang julat lebih dari tiga ukuran standar yang berdekatan      Tambahan diadopsi dari IEC 61200-52.
                                                     dapat dianggap sebagai kelompok yang terdiri atas ukuran berbeda. Kelompok kabel serupa dapat diterima
                                                     merupakan kelompok jika KHA semua kabel berdasarkan pada suhu konduktor maksimum diizinkan yang sama                 Jika kabel digelar pada ruang dimana insulasi termal mungkin diterapkan, kabel sebaiknya, jika
                                                     dan jika julat ukutan konduktor dalam rentang kelompok tidak lebih dari tiga ukuran standar yang berdekatan.         dapat dipraktikkan, dimagun pada posisi sedemikian sehingga tidak akan ditutup oleh insulasi
                                                                                                                                                                          termalnya. Jika pemagunan pada posisi tersebut tidak dapat dipraktikkan, luas penampang
                                                     A.52.5.1 Kelompok dalam konduit, berumbung kabel dan talang kabel                                                    kabel sebaiknya dinaikkan yang sesuai.
                                                     Faktor reduksi kelompok yang berada pada sisi aman, untuk kelompok yang terdiri atas ukuran
                                                     berbeda dari konduktor berinsulasi atau kabel dalam konduit, berumbung kabel atau talang kabel                       Untuk kabel yang dipasang pada dinding berinsulasi termal atau di atas plafon berinsulasi
                                                     adalah:                                                                                                              termal, kabel yang akan kontak dengan permukaan konduktif termal pada salah satu sisi,
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                       F=
                                                                                                            1                                                             metode acuan yang tepat adalah A1 dan A2.
                                                                                                            n                                                             Untuk kabel tunggal yang mungkin dikelilingi secara total oleh bahan insulasi termal sepanjang
                                                     dengan                                                                                                               lebih dari 0,5 m, bila tidak ada informasi yang lebih tepat, KHA dapat diambil sebagai 0,5 kali
                                                     F adalah faktor reduksi kelompok                                                                                     KHA untuk kabel, diklip langsung ke permukaan dan terbuka (metode acuan C).
                                                     n adalah jumlah kabel atau konduktor berinsulasi dalam kelompok.
                                                                                                                                                                          Jika kabel dikelilingi secara total oleh insulasi termal untuk kurang dari 0,5 m, KHA kabel harus
                                                     Faktor reduksi kelompok yang diperoleh dari persamaan ini akan mengurangi bahaya beban lebih ukuran
                                                                                                                                                                          dikurangi, tergantung pada ukuran kabel, panjang insulasi dan sifat termal insulasi. Faktor
                                                     terkecil tetapi dapat mengarah pada utilisasi kurang dari ukuran terbesar. Utilisasi kurang tersebut dapat           derating pada Tabel 52A cocok untuk ukuran konduktor sampai dengan 10 mm2 pada insulasi
                                                     dihindari jika ukuran yang besar dan kecil dari kabel atau konduktor berinsulasi tidak dicampur dalam                termal yang mempunyai konduktivitas termal lebih besar dari 0,0625 Wm-1K-1.
                                                     kelompok yang sama.
                                                     Penggunaan metode perhitungan yang khusus dimaksudkan untuk kelompok yang terdiri atas ukuran                                            Tabel 52A – Kabel yang dikelilingi oleh insulasi termal
                                                     berbeda dari konduktor berinsulasi atau kabel dalam konduit menghasilkan faktor reduksi kelompok
                                                     yang lebih tepat.                                                                                                                     Panjang pada insulasi mm                  Faktor derating
                                                                                                                                                                                                                                                           a
                                                                                                                                                                                                        50                                 0,89
                                                     A.52.5.2 Kelompok di atas rak
                                                     Jika kelompok terdiri atas ukuran berbeda dari konduktor berinsulasi atau kabel, harus diperhatikan                                               100                                   0,81
                                                     pembebanan arus pada ukuran terkecil. Lebih disukai untuk menggunakan metode perhitungan yang                                                     200                                   0,68
                                                     khusus dimaksudkan untuk kelompok yang terdiri atas ukuran berbeda dari konduktor berinsulasi atau                                                400                                   0,55
                                                     kabel.                                                                                                                           a   Faktor derating harus diterapkan untuk KHA menurut metode acuan C.
                                                     Faktor reduksi kelompok yang diperoleh sesuai dengan A.52.5.1 akan memberikan nilai pada sisi aman.
                                                                                                                                                                       A.52.6.1 Metode acuan
                                                     A.52.6 Metode instalasi                                                                                           Metode acuan adalah metode instalasi yang KHA telah ditentukan dengan pengujian atau perhitungan.
                                                                                                                                                                       Metode acuan A1, butir 1 Tabel 52-3 (konduktor berinsulasi dalam konduit dalam dinding berinsulasi
                                                           PENJELASAN
                                                                                                                                                                       secara termal) dan A2, butir 2 Tabel 52-3 (kabel multiinti dalam konduit dalam dinding berinsulasi
                                                                                                                                                                       secara termal).
                                                           Berbeda dengan Tabel 7, penentuan KHA pada Bagian 5-52 sangat ditentukan oleh metode
                                                           instalasinya (metode pemasangannya). Jadi saat mendesain sistem perkawatan, tentukan
                                                           lebih dulu metode instalasinya, sehingga dapat diketahui KHA kabel yang dipilih.
                                                     130     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                       Persyaratan Umum Instalasi Listrik 2011   131
                                                     Dinding terdiri atas lapisan luar tahan cuaca, insulasi termal dan permukaan bagian dalam dari kayu              Penopang tangga: ini adalah konstruksi yang menawarkan impedans minimum ke aliran udara
                                                     atau bahan serupa kayu yang mempunyai konduktans termal sekurangnya 10 W/m2. K. Konduit                          sekeliling kabel, yaitu logam penopang di bawah kabel menempati kurang dari 10 % luas rencana.
                                                     dimagunkan sedemikian sehingga berdekatan dengan, tetapi tidak perlu menyentuh permukaan bagian                  Begel dan gantungan: penopang kabel yang memegang kabel pada interval seluruh panjangnya dan
                                                     dalam. Bahang dari kabel dianggap hanya keluar melalui permukaan bagian dalam. Konduit dapat dari                memungkinkan aliran udara terbuka penuh sekeliling kabel.
                                                     logam atau plastik.                                                                                              Catatan umum untuk Tabel A.52-1 hingga A.52-21
                                                     Metode acuan B1, butir 4 Tabel 52-3 (konduktor berinsulasi dalam konduit pada dinding kayu) dan B2,              CATATAN 1
                                                                                                                                                                      Tabel KHA untuk jenis konduktor berinsulasi dan kabel, dan metode instalasi yang biasa digunakan untuk instalasi
                                                     butir 5 Tabel 52-3 (kabel multiinti dalam konduit pada dinding kayu).
                                                                                                                                                                      listrik magun. Tabel KHA berkaitan dengan operasi keadaan tunak kontinu (faktor beban 100 %) untuk a.s. atau
                                                     Konduit dipasang pada dinding kayu sedemikian sehingga celah antara konduit dan permukaan kurang
                                                                                                                                                                      a.b. dengan frekuensi nominal 50 Hz.
                                                     dari 0,3 kali diameter konduit. Konduit dapat dari logam atau plastik. Jika konduit dimagunkan ke
                                                                                                                                                                      CATATAN 2
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     dinding tembok, KHA kabel atau konduktor berinsulasi dapat lebih tinggi.
                                                                                                                                                                      Tabel A.52-1 menampilkan jenis metode instalasi acuan yang diacu tabel KHA. Hal ini tidak berarti bahwa semua
                                                     Metode acuan C, butir 20 Tabel 52-3 (kabel inti tunggal atau multiinti pada dinding kayu)                        jenis ini perlu dicantumkan dalam persyaratan nasional semua negara.
                                                     Kabel dipasang pada dinding kayu sedemikian sehingga celah antara kabel dan permukaan kurang dari                CATATAN 3
                                                     0,3 kali diameter kabel. Jika kabel dimagunkan ke atau ditanam dalam dinding tembok, KHA nya dapat               Untuk baiknya, jika metode desain instalasi dengan bantuan komputer digunakan, KHA dalam Tabel A.52-2 hingga
                                                     lebih tinggi.                                                                                                    A.52-13 dapat berkaitan dengan konduktor yang diukur dengan rumus sederhana. Rumus ini dengan koefisien
                                                                                                                                                                      yang sesuai diberikan dalam Lampiran C.
                                                     CATATAN
                                                     Istilah “tembok” diambil untuk mencakup batu bata, beton, plesteran atau serupa (selain dari bahan berinsulasi           Tabel A.52-1 Daftar metode instalasi acuan yang membentuk dasar tabel KHA
                                                     secara termal).
                                                                                                                                                                                                                                                     Tabel dan kolom
                                                     Metode acuan D, butir 70 Tabel 52-3 (kabel multiinti dalam talang dalam tanah)                                                                                               KHA untuk sirkit tunggal
                                                                                                                                                                                  Metode instalasi acuan
                                                     Kabel ditarik dalam talang plastik, tembikar atau logam yang kontak langsung dengan tanah yang                                                                   Berinsulasi PVC      Berinsulasi XLPE/      Berinsulasi    Faktor          Faktor
                                                                                                                                                                                                                                                 EPR               mineral
                                                     mempunyai resistivitas termal 2,5 K∙m/W dan dalam 0,7 m (lihat juga A.52..3).                                                                                                                                               suhu        reduksi
                                                                                                                                                                                                                                         Jumlah inti                            ambien      kelompok
Metode acuan E, F dan G, butir 32 dan 33 Tabel 52-3 (kabel inti tunggal dan multiinti di udara 2 3 2 3 1,2 dan 3
terbuka) 1 2 3 4 5 6 7 8 9
                                                     Kabel ditopang sedemikian sehingga disipasi bahang total tidak terhalang. Pemanasan karena radiasi                                      Konduktor
                                                                                                                                                                                             berinsulasi
                                                     matahari dan sumber lain harus diperhitungkan. Harus diperhatikan bahwa konveksi udara alami tidak                                      dalam konduit     A1   A.52-2      A.52-4      A.52-3      A.52-5         -        A.52-14      A.52-17
                                                     terhalang. Dalam praktik jarak bebas antara kabel dan setiap permukaan yang berdekatan sekurangnya                                      dalam dinding
                                                                                                                                                                                             berinsulasi
                                                                                                                                                                                                                     Kol. 2     Kol. 2      Kol. 2       Kol. 2
                                                     0,3 kali diameter eksternal kabel untuk kabel multiinti atau 1 kali diameter kabel untuk kabel inti tunggal                             secara termal
                                                     cukup untuk memungkinkan penggunaan KHA yang memadai untuk kondisi udara terbuka.                                                       Kabel multiinti
                                                                                                                                                                                             dalam konduit          A.52-2      A.52-4      A.52-3      A.52-5
                                                                                                                                                                                                               -                                                       -        A.52-14      A.52-17
                                                                                                                                                                                             dalam dinding
                                                     A.52.6.2 Metode lain                                                                                                                    berinsulasi
                                                                                                                                                                                                                     Kol. 3     Kol. 3      Kol. 3       Kol. 3
                                                                                                                                                                                             secara termal
                                                     Kabel di atas lantai atau di bawah plafon: hal ini serupa dengan metode acuan C kecuali bahwa                                           Konduktor
                                                                                                                                                                                             berinsulasi            A.52-2      A.52-4      A.52-3      A.52-5
                                                     peringkat untuk kabel di atas plafon sedikit berkurang (lihat Tabel A.52-17) dari nilai untuk dinding atau                              dalam konduit
                                                                                                                                                                                                               B1                                                      -        A.52-14      A.52-17
                                                                                                                                                                                                                     Kol. 4     Kol. 4      Kol. 4       Kol. 4
                                                     lantai karena berkurangnya konveksi alami.                                                                                              pada dinding
                                                                                                                                                                                             kayu
                                                     Rak kabel: rak berlubang mempunyai pola lubang regular sedemikian untuk memfasilitasi penggunaan                                        Kabel multiinti
                                                                                                                                                                                             dalam konduit     B2   A.52-2      A.52-4      A.52-3      A.52-5         -        A.52-14      52 7A-17
                                                     pemagun kabel. Peringkat kabel untuk rak berlubang telah didapatkan dari kerja uji yang menggunakan                                     pada dinding            Kol. 5     Kol. 5      Kol. 5       Kol. 5
                                                     rak dengan lubang 30 % dari luas dasar. Jika lubang kurang dari 30 % luas dasar, rak dianggap nirlubang.                                kayu
                                                     132    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                    Persyaratan Umum Instalasi Listrik 2011            133
                                                                                                     Tabel A.52-1 (lanjutan)                                                                               Tabel A.52-2 KHA dalam ampere untuk metode instalasi dalam Tabel A.52-1 –
                                                                                                                                                                                                                  Insulasi PVC/dua konduktor berbeban/tembaga atau aluminium –
                                                                                                                                           Tabel dan kolom                                                    Suhu konduktor: 70 oC/Suhu ambien: 30 oC di udara, 20 oC dalam tanah
                                                                                                                         KHA untuk sirkit tunggal
                                                              Metode instalasi acuan                                                                                                                                                           Metode instalasi Tabel 7.A-1
                                                                                                                                 Berinsulasi XLPE/      Berinsulasi    Faktor    Faktor
                                                                                                       Berinsulasi PVC
                                                                                                                                       EPR               mineral       suhu      reduksi    Luas penampang              A1            A2             B1             B2                 C                     D
                                                                                                                               Jumlah inti                            ambien    kelompok   nominal konduktor
                                                                                                        2                3          2             3     1,2 dan 3                                      2
                                                                                                                                                                                                  mm
                                                                     1                       2          3                4          5             6          7           8          9
                                                                                                                                                        Selubung
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                          Kabel inti                                                                    70 o C                                     1                    2              3             4               5                 6                     7
                                                                                             C        A.52-2        A.52-4        A.52-3      A.52-5    52-C5         A.52-14   A.52-17
                                                                          tunggal atau
                                                                          multiinti pada              Kol. 6        Kol. 6        Kol. 6       Kol. 6                                           Tembaga
                                                                                                                                                        Selubung                                                       14,5            14           17,5           16,5               19,5               22
                                                                          dinding kayu                                                                                                            1,5
                                                                                                                                                        105 o C                                   2,5                  19,5           18,5           24             23                 27                29
                                                                                                                                                        52-C6
                                                                                                                                                                                                   4                    26             25            32             30                 36                38
                                                                                                                                                                                                   6                    34             32            41             38                 46                47
                                                                          Kabel multiinti             A.52-2        A.52-4        A.52-3      A.52-5                                               10                   46             43            57             52                 63                63
                                                                                             D                                                               -        A.52-14   A.52-19
                                                                          dalam talang                                                                                                            16                    61             57            76             69                 85                 81
                                                                                                      Kol. 7        Kol. 7        Kol. 7       Kol. 7
                                                                          dalam tanah                                                                                                             25                    80             75           101             90                112                104
                                                                                                                                                                                                  35                    99             92           125            111                138                125
                                                                                                                                                                                                  50                   119            110           151            133                168                148
                                                                                                                                                        Selubung
                                                                                                             Tembaga                    Tembaga                                                    70                  151            139           192            168                213                183
                                                                                                                                                        70 o C
                                                                          Kabel multiinti
                                                                                                             A.52 - 10                  A.52-12         A.52-8                                    95                   182            167           232            201                258                216
                                                                                             E                                                                        A.52-14   A.52-17           120                  210            192           269            232                299
                                                                          pada udara                                                                                                                                                                                                                     246
                                                                          terbuka                           Alumu-nium               Aluminium          Selubung                                  150                  240            219             -              -                344                278
                                                                                                             A.52 - 11                A.52-13           105 o C                                   185                  273            248             -              -                392                312
                                                                                                                                                        A.52 - 9                                  240                  321            291             -              -                461                361
                                                                                                                                                                                                  300                  367            334             -              -                530                408
                                                                                                                                                        Selubung
                                                                          Kabel inti                        Tembaga                  Tembaga              70°C                                 Aluminium
                                                                          tunggal,                          A.52 - 10                A.52 - 12           A.52 - 8                                 2,5                  15             14.5          18,5           17,5                21                22
                                                                                             F                                                                    A.52-14       A.52-17
                                                                          bersentuhan                                                                                                              4                   20             19,5           25             24                28                 29
                                                                          pada udara                     Alumunium                  Alumunium           Selubung                                   6                   26              25            32             30                36                 36
                                                                          terbuka                         A.52 - 11                  A.52 - 13                   o                                 10                  36              33            44             41                49                 48
                                                                                                                                                         105 C
                                                                                                                                                         A.52-9                                   16                   48              44            60             54                66                 62
                                                                                                                                                                                                  25                   63              58            79             71                83                 80
                                                                                                                                                        Selubung                                  35                   77              71            97             86                103                96
                                                                                                            Tembaga                  Tembaga                 o
                                                                                                                                                          70 C                                    50                   93              86           118            104                125                113
                                                                          Kabel inti
                                                                                             G              A.52 - 10                A.52 - 12           A.52 - 8 A.52-14           -              70                  118            108           150            131                160                140
                                                                          tunggal,
                                                                          berjarak pada
                                                                                                                                                                                                  95                   142            130           181            157                195                166
                                                                                                         Alumunium                  Alumunium           Selubung                                  120                  164            150           210            181                226                189
                                                                          udara terbuka
                                                                                                          A.52 - 11                  A.52 - 13           105 C
                                                                                                                                                                 o                                150                  189            172             -              -                261                213
                                                                                                                                                         A.52-9                                   185                  215            195             -              -                298                240
                                                                                                                                                                                                  240                  252            229             -              -                352                277
                                                                                                                                                                                                  300                  289            263             -              -                406                313
                                                                                                                                                                                           CATATAN
                                                                                                                                                                                           Pada Kolom 3, 5 ,6 dan 7 konduktor bulat dianggap berukuran sampai dengan 16 mm². Nilai untuk ukuran yang lebih
                                                                                                                                                                                           besar
                                                                                                                                                                                           berkaitan dengan bentuk kompak dan secara aman dapat diterapkan untuk konduktor bulat
                                                     134   Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                                 Persyaratan Umum Instalasi Listrik 2011       135
                                                                         Tabel A.52-3 KHA dalam ampere untuk metode instalasi dalam Tabel A.52-1 –                                      Tabel A.52-4 KHA dalam ampere untuk metode instalasi dalam Tabel A.52-1 –
                                                                           Insulasi XLPE atau EPR/dua konduktor berbeban/tembaga atau aluminium –                                             Insulasi PVC/tiga konduktor berbeban/ tembaga atau aluminium –
                                                                             Suhu konduktor: 90 oC/Suhu ambien: 30 oC di udara, 20 oC dalam tanah                                          Suhu konduktor: 70 oC/Suhu ambien: 30 oC di udara, 20 oC dalam tanah
                                                                 1                     2                  3           4              5         6              7                 1                   2              3               4              5                 6                 7
                                                              Tembaga                                                                                                        Tembaga
                                                                1.5                    19                18.5        23             22         24            26                1.5                 13.5            13             15.5           15               17.5               18
                                                                2.5                    26                 25          31            30         33            34                2.5                  18            17.5             21            20                24                24
                                                                 4                     35                 33         42             40         45            44                 4                   24             23              28            27                32                 31
                                                                 6                     34                 42         54              51        58            56                 6                   31             29              36            34                41                39
                                                                 10                    45                 57         75             69         80            73                 10                  42             39              50            46                57                52
                                                                16                     61                 76         100             91        107           95                16                   56             52              68            62                76                67
                                                                25                     81                 99         133            119        138           121               25                   73             68              89            80                96                86
                                                                35                    106                121         164            146        171           146               35                   89             83             110            99               119                103
                                                                50                    131                145         198            175        209           173               50                  108             99             134            118              144                122
                                                                 70                   158                183         253            221        269           213                70                 136            125             171            149              184                151
                                                                95                    200                220         306            265        328           252               95                  164            150             207            179              223                179
                                                                120                   241                243         354            305        382           287               120                 188            172             239            206              259                203
                                                                150                   278                290           -              -        441           324               150                 216            196               -             -               299                230
                                                                185                   318                329           -              -        506           363               185                 245            223               -             -               341                258
                                                                240                   362                386           -              -        599           419               240                 286            261               -             -               403                297
                                                                300                   424                442           -              -        693           474               300                 328            298               -             -               464                336
                                                             Alumunium                                                                                                      Alumunium
                                                                2,5                   20                 19.5         25            23         26            26                2,5                  14            13.5            16.5           15.5             18.5               18.5
                                                                 4                    27                  26          33             31        35            34                  4                 18.5           17.5             22             21               25                 24
                                                                 6                    35                  33          43            40         45            42                  6                  24             23              28             27               32                 30
                                                                 10                   48                  45          59            54         62            56                 10                  32             31              39             36               44                 40
                                                                 16                   64                  60          79            72         84            73                 16                  43             41              53             48               59                 52
                                                                 25                   84                  78         105            94         101           93                 25                  57             53              70             62               73                 66
                                                                 35                   103                 96         130            115        126           112                35                  70             65              86             77               90                 80
                                                                 50                   125                115         157            138        154           132                50                  84             78             104             92              110                 94
                                                                 70                   158                145         200            175        198           163                70                 107             98             133            116              140                117
                                                                 95                   191                175         242            210        241           193                95                 129            118             161            139              170                138
                                                                120                   220                201         281            242        280           220               120                 149            135             186            160              197                157
                                                                150                   253                230           -              -        324           249               150                 170            155               -              -              227                178
                                                                185                   288                262           -              -        371           279               185                 194            176               -              -              259                200
                                                                240                   338                307           -              -        439           322               240                 227            207               -              -              305                230
                                                                300                   387                352           -              -        508           364               300                 261            237               -              -              351                260
                                                      CATATAN                                                                                                           CATATAN
                                                      Pada Kolom 3, 5 ,6 dan 7 konduktor bulat dianggap berukuran sampai dengan 16 mm². Nilai untuk ukuran yang lebih   Pada Kolom 3, 5 ,6 dan 7 konduktor bulat dianggap berukuran sampai dengan 16 mm². Nilai untuk ukuran yang lebih b
                                                      besar                                                                                                             esar
                                                      berkaitan dengan bentuk kompak dan secara aman dapat diterapkan untuk konduktor bulat                             berkaitan dengan bentuk kompak dan secara aman dapat diterapkan untuk konduktor bulat
                                                     136       Persyaratan Umum Instalasi Listrik 2011                                                                                                                                          Persyaratan Umum Instalasi Listrik 2011     137
                                                                         Tabel A.52-5 KHA dalam ampere untuk metode instalasi dalam Tabel A.52-1 –                                      Tabel A.52-6 KHA dalam ampere untuk metode instalasi C Tabel A.52-1 –
                                                                          Insulasi XLPE atau EPR/tiga konduktor berbeban/ tembaga atau aluminium –                                                 Insulasi mineral/konduktor tembaga dan selubung –
                                                                            Suhu konduktor: 90 oC/Suhu ambien: 30 oC di udara, 20 oC dalam tanah                                               Selubung PVC atau polos terkena sentuhan (lihat catatan 2)
                                                                                                                                                                                                  Suhu selubung logam: 70 oC/Suhu ambien acuan: 30 oC
                                                                                                                Metode instalasi Tabel 7.A-1
                                                           Luas penampang                                                                                                                                       Jumlah dan susunan konduktor untuk metode C Tabel 7.A-1
                                                                                      A1                 A2          B1              B2        C              D
                                                       nominal konduktor                                                                                                                                                                         Tiga konduktor berbeban
                                                                                                                                                                                                 Dua konduktor berbeda
                                                                     2                                                                                                   Luas penampang                                            Multiinti atau inti                 Inti tunggal dalam
                                                               mm                                                                                                                               kembar atau inti tunggal
                                                                                                                                                                                                                              tunggal dalam formasi trefoil               formasi rata
                                                                                                                                                                        nominal konduktor
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                                                    2
                                                                 1                     2                  3           4              5         6              7                mm
                                                              Tembaga
                                                                1.5                    17                16.5        20             19.5       22             22
                                                                2.5                    23                 22         28              26        30             29
                                                                 4                     31                 30         37              35        40             37
                                                                 6                     40                 38         48              44        52             46                1                          2                                3                                    4
                                                                 10                    54                 51         66              60         71            61
                                                                16                     73                 68         88              80        96                             500 V
                                                                                                                                                              79                                          23                               19                                   21
                                                                25                     95                 89         117            105        119           101               1.5
                                                                35                    117                109         144            128        147           122               2.5                        31                               26                                   29
                                                                50                    141                130         175            154        179           144                4                         40                               35                                   38
                                                                 70                   179                164         222            194        229           178              750 V
                                                                95                    216                197         269            233        278           211               1.5                        25                                21                                 23
                                                                120                   249                227         312            268        322           240               2.5                        34                               28                                   31
                                                                150                   285                259          -               -        371           271                4                         45                               37                                   41
                                                                185                   323                295          -               -        424           304                6                         57                               48                                  52
                                                                240                   380                346          -               -        500           351                10                        77                               65                                   70
                                                                300                   435                396          -               -        576           396               16                         102                              86                                  92
                                                             Alumunium                                                                                                         25                         133                              112                                 120
                                                                2,5                    19                18           22             21        24             22               35                         163                              137                                 147
                                                                 4                     25                24           29            28         32             29               50                         202                              169                                 181
                                                                 6                     32                 31          38            35          41            36                70                        247                              207                                 221
                                                                 10                    44                 41          52            48         57             47               95                         296                              249                                 264
                                                                 16                    58                55           71            64         76             61               120                        340                              286                                 303
                                                                 25                    76                 71          93            84         90             78               150                        388                              327                                 346
                                                                 35                    94                87          116            103        112            94               185                        440                              371                                 392
                                                                 50                   113                104         140            124        136           112               240                        514                              434                                 457
                                                                 70                   142                131         179            156        174           138        CATATAN 1
                                                                 95                   171                157         217            188        211           164        Untuk Kabel inti tunggal, selubung kabel sirkit dihubungkan bersama - sama pada kedua ujungnya
                                                                120                   197                180         251            216        245           186        CATATAN 2
                                                                150                   226                206           -              -        283           210        Untuk kabel polos yang saling bersentuhan nilai sebaiknya dikalikan 0.9
                                                                185                   256                233           -              -        323           236
                                                                240                   300                273           -              -        382           272
                                                                300                   344                313           -              -        440           308
                                                      CATATAN
                                                      Pada Kolom 3, 5 ,6 dan 7 konduktor bulat dianggap berukuran sampai dengan 16 mm². Nilai untuk ukuran yang lebih
                                                      besar
                                                      berkaitan dengan bentuk kompak dan secara aman dapat diterapkan untuk konduktor bulat
                                                     138       Persyaratan Umum Instalasi Listrik 2011                                                                                                                                            Persyaratan Umum Instalasi Listrik 2011   139
                                                                         Tabel A.52-7 KHA dalam ampere untuk metode instalasi C Tabel A.52-1 –                                             Tabel A.52-8 KHA dalam ampere untuk metode instalasi E, F dan G Tabel A.52-1 –
                                                                                    Insulasi mineral/konduktor tembaga dan selubung –                                                                     Insulasi mineral/Konduktor tembaga dan selubung/
                                                                                      Polos tidak terkena sentuhan atau tidak kontak                                                                  Selubung PVC atau polos terkena sentuhan (lihat catatan 2)
                                                                                             dengan bahan yang mudah terbakar                                                                           Suhu selubung logam: 70 °C/Suhu ambien acuan: 30 °C
                                                                                 Suhu selubung logam: 105 °C/Suhu ambien acuan: 30 °C
                                                                                                                                                                                                                Jumlah dan susunan konduktor untuk metode E,F dan G Tabel 7.A-1
                                                                                                     Jumlah dan susunan konduktor untuk metode C Tabel 7.A-1
                                                                                                                                                                                                                                              Tiga konduktor berbeban
                                                                                                                                                                                                   Dua konduktor
                                                                                                                                     Tiga konduktor berbeban                                                                               Inti tunggal
                                                                                    Dua konduktor berbeda                                                                                            berbeban        Multiinti atau inti                             Inti               Inti tunggal
                                                                                                                                                                            Luas penampang                                                    dalam
                                                           Luas penampang                                               Multiinti atau inti            Inti tunggal dalam                         kembar atau inti
                                                                                   kembar atau inti tunggal                                                                                                           tunggal dalam                              tunggal rata            horizontal
                                                                                                                   tunggal dalam formasi trefoil          formasi rata                               tunggal                               bersentuhan
                                                                                                                                                                                nominal                               formasi trefoil                          vertikal berjarak          berjarak
                                                       nominal konduktor
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                 1                              2                               3                              4
                                                               500 V
                                                                                               28                              24                              27                  1                     2                   3                  4                      5                      6
                                                                1.5
                                                                2.5                            38                              33                              36                500 V
                                                                 4                             51                              44                              47                 1.5                   25                   21                23                      26                     29
                                                                                                                                                                                  2.5                   33                   28                31                      34                     39
                                                               750 V
                                                                                                31                             26                              30                  4                    44                   37                41                      45                     51
                                                                1.5
                                                                2.5                            42                              35                               41               750 V
                                                                 4                             55                              47                              53                 1.5                   26                  22                26                      28                     32
                                                                 6                              70                             59                              67                 2.5                   36                  30                34                      37                     43
                                                                 10                            96                               81                              91                 4                    47                  40                45                      49                     56
                                                                16                             127                             107                             119                 6                    60                   51               57                      62                      71
                                                                25                             166                             140                             154                 10                   82                  69                77                      84                     95
                                                                35                             203                             171                             187                16                    109                 92                102                     110                    125
                                                                50                             251                             212                             230                25                    142                 120               132                     142                    162
                                                                 70                            307                             260                             280                35                    174                 147               161                     173                    197
                                                                95                             369                             312                             334                50                    215                 182               198                     213                    242
                                                                120                            424                             359                             383                 70                   264                 223               241                     259                    294
                                                                150                            485                             410                             435                95                    317                 267               289                     309                    351
                                                                185                            550                             465                             492                120                   364                 308               331                     353                    402
                                                                240                            643                             544                             572                150                   416                 352               377                     400                    454
                                                                                                                                                                                  185                   472                 399               426                     446                    507
                                                      CATATAN 1
                                                                                                                                                                                  240                   552                 466               496                     497                    565
                                                      Untuk Kabel inti tunggal, selubung kabel sirkit dihubungkan bersama - sama pada kedua ujungnya
                                                      CATATAN 2                                                                                                             CATATAN 1
                                                      Tidak ada koreksi untuk pengelompokan yang perlu diterapkan                                                           Untuk Kabel inti tunggal, selubung kabel sirkit dihubungkan bersama - sama pada kedua ujungnya
                                                      CATATAN 3                                                                                                             CATATAN 2
                                                      Untuk tabel ini, metode acuan C mengacu pada dinding tembok, karena suhu selubung yang tinggi biasanya tidak dap      Untuk kabel polos yang bersentuhan, nilai sebaliknya dikalikan 0.9
                                                      at                                                                                                                    CATATAN 3
                                                      diterima untuk dinding kayu                                                                                           Deadalah diameter external kabel
                                                     140       Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                    Persyaratan Umum Instalasi Listrik 2011      141
                                                                      Tabel A.52-9 KHA dalam ampere untuk metode instalasi E, F dan G Tabel A.52-1 –                               Tabel A.52-10 KHA dalam ampere untuk metode instalasi E, F dan G Tabel A.52-1 –
                                                                                     Insulasi mineral/konduktor tembaga dan selubung/                                                                      Insulasi PVC/Konduktor tembaga
                                                                                       Polos tidak terkena sentuhan (lihat catatan 2)                                                              Suhu konduktor: 70°C/Suhu ambien acuan: 30°C
                                                                                  Suhu selubung logam: 105 °C/Suhu ambien acuan: 30 °C
                                                                                                                                                                                                                            Metode instalasi Tabel 7.A-1
                                                                                            Jumlah dan susunan konduktor untuk metode E,F dan G Tabel 7.A-1
                                                                                                                                                                                               Kabel multiinti                                 Kabel inti tunggal
                                                                                                                          Tiga konduktor berbeban                                                                         Dua           Tiga               Tiga konduktor berbeban rata
                                                                              Dua konduktor                                                                                   Luas           Dua           Tiga
                                                                                berbeban                               Inti tunggal                                                                                    konduktor     konduktor
                                                      Luas penampang                             Multiinti atau inti                         Inti          Inti tunggal                   konduktor     konduktor                                                               Berjarak
                                                                             kembar atau inti                             dalam                                           penampang                                     berbeban      berbeban     Bersentuhan
                                                                                                  tunggal dalam                          tunggal rata       horizontal                     berbeban      berbeban
                                                                                 tunggal                               bersentuhan                                         nominal                                    bersentuhan      trefoil                       Horizontal        Vertikal
                                                            nominal                               formasi trefoil                      vertikal berjarak     berjarak     konduktor
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                                               1              2              3             4              5                6              7                  8
                                                              1                     2                    3                  4                 5                  6            1.5            22            18.5            -             -               -                -                 -
                                                                                                                                                                              2.5            30             25             -             -               -                -                 -
                                                            500 V
                                                                                   31                    26                29                33                 37             4             40             34             -             -               -                -                 -
                                                             1.5                                                                                                               6              51            43             -             -               -                -                 -
                                                             2.5                   41                    35                39                43                 49             10             70            60             -             -               -                -                 -
                                                              4                    54                    46                51                56                 64            16             94             80             -             -               -                -                 -
                                                            750 V                                                                                                             25             119           101           131            110             114              146               130
                                                             1.5                   33                   28                 32                35                 40            35             148           126           162            137             143              181               162
                                                             2.5                   45                   38                 43                47                 54            50             180           153           196            167             174              219               197
                                                              4                    60                   50                 56                 61                 70            70            232           196           251            216             225              281               254
                                                              6                    76                   64                 71                78                 89            95             282           238           304            264             275              341               311
                                                              10                   104                  87                 96                105                120           120            328           276           352            308             321              396               362
                                                             16                    137                  115               127                137                157           150            379           319           406            356             372              456               419
                                                             25                    179                  150               164                178                204           185            434           364           463            409             427              521               480
                                                             35                    220                  184               200                216                248           240            514           430           546            485             507              615               569
                                                             50                    272                  228               247                266                304           300            593           497           629            561             587              709               659
                                                              70                   333                  279               300                323                370           400              -             -           754            656             689              852               795
                                                             95                    400                  335               359                385                441           500              -             -           868            749             789              982               920
                                                             120                   460                  385               441                441                505           630              -             -           1005           855             905              1138              1070
                                                             150                   526                  441               469                498                565       CATATAN
                                                             185                   596                  500               530                557                629                                                           2
                                                                                                                                                                          Konduktor
                                                                                                                                                                          duktor    bulat dianggap berukuran sampai dengan 16 mm . Nilai untuk ukuran yang lebih besar berkaitan dengan kon
                                                             240                   697                  584               617                624                704
                                                                                                                                                                          kompak dan dengan aman dapat diterapkan untuk konduktor bulat.
                                                      CATATAN 1
                                                      Untuk Kabel inti tunggal, selubung kabel sirkit dihubungkan bersama - sama pada kedua ujungnya
                                                      CATATAN 2
                                                      Tidak ada koreksi untuk pengelompokan yang perlu diterapkan
                                                      CATATAN 3
                                                      Deadalah diameter external kabel
                                                     142     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                               Persyaratan Umum Instalasi Listrik 2011        143
                                                                    Tabel A.52-11 KHA dalam ampere untuk metode instalasi E, F dan G Tabel A.52-1 –                                           Tabel A.52-12 KHA dalam ampere untuk metode instalasi E, F dan G Tabel A.52-1 –
                                                                                           Insulasi PVC/Konduktor aluminium                                                                                      Insulasi XLPE atau EPR/Konduktor tembaga
                                                                                    Suhu konduktor: 70 °C/Suhu ambien acuan: 30 °C                                                                            Suhu konduktor: 90 °C/Suhu ambien acuan: 30 °C
Kabel multiinti Kabel inti tunggal Kabel multiinti Kabel inti tunggal
                                                                                                           Dua          Tiga               Tiga konduktor berbeban rata              Luas                                        Dua           Tiga               Tiga konduktor berbeban rata
                                                           Luas              Dua           Tiga                                                                                                        Dua          Tiga
                                                                                                        konduktor    konduktor                                                                                                konduktor     konduktor
                                                                          konduktor     konduktor                                                              Berjarak          penampang          konduktor    konduktor                                                            Berjarak
                                                       penampang                                         berbeban     berbeban     Bersentuhan                                                                                 berbeban      berbeban     Bersentuhan
                                                                           berbeban      berbeban                                                                                 nominal            berbeban     berbeban
                                                        nominal                                        bersentuhan     trefoil                        Horizontal      Vertikal                                               bersentuhan      trefoil                        Horizontal        Vertikal
                                                                                                                                                                                 konduktor
                                                       konduktor
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                                                          2
                                                                2                                                                                                                   mm
                                                           mm
                                                                                                                                                                                      1                 2             3           4             5               6                7                   8
                                                            1                2               3             4             5               6                7               8
                                                                                                                                                                                     1.5               26           23            -             -              -                 -                 -
                                                           2.5              23              19.5           -             -              -                 -                 -        2.5               36           32            -             -              -                 -                 -
                                                            4                31              26            -             -              -                 -                 -         4                49           42            -             -              -                 -                 -
                                                            6               39               33            -             -              -                 -                 -         6                63           54            -             -              -                 -                 -
                                                            10              54               46            -             -              -                 -                 -         10               86           75            -             -              -                 -                 -
                                                           16               73               61            -             -              -                 -                 -        16                115          100           -             -              -                 -                 -
                                                           25               89               78           98            84             87                112               99        25                149          127          161          135             141              182                161
                                                           35               111              96           122           105            109               139              124        35                185          158         200           169             176              226                201
                                                           50               135             117           149           128            133               169              152        50                225          192         242           207             216              275               246
                                                            70              173             150           192           166            173               217              196         70               289          246          310          268             279              353                318
                                                           95               210             183           235           203            212               265              241        95                352          298         377           328             342              430               389
                                                           120              244             212           273           237            247               308              282        120               410          346         437           383             400              500               454
                                                           150              282             245           316           274            287               356              327
                                                                                                                                                                                     150               473          399         504           444             464              577               527
                                                           185              322             280           363           315            330               407              376
                                                                                                                                                                                     185               542          456         575            510            533              661               605
                                                           240              380             330           430           375            392               482              447
                                                                                                                                                                                     240               641          538         679           607             634              781                719
                                                           300              439             381           497           434            455               557              519
                                                           400                -               -           600           526            552               671              629        300               741          621         783           703             736              902               833
                                                           500                -               -           694           610            640               775              730        400                -            -          940           823             868              1085              1008
                                                           630                -               -           808           711            746               900              852        500                -            -          1083          946             998              1253              1169
                                                                                                                                                                                     630                -            -          1254          1088            1151             1454              1362
                                                      CATATAN
                                                      Konduktor
                                                                                                          2
                                                                bulat dianggap berukuran sampai dengan 16 mm . Nilai untuk ukuran yang lebih besar berkaitan dengan kon          CATATAN
                                                      duktor                                                                                                                     Konduktor
                                                                                                                                                                                                                                     2
                                                                                                                                                                                           bulat dianggap berukuran sampai dengan 16 mm . Nilai untuk ukuran yang lebih besar berkaitan dengan kon
                                                      kompak dan dengan aman dapat diterapkan untuk konduktor bulat.                                                             duktor
                                                                                                                                                                                 kompak dan dengan aman dapat diterapkan untuk konduktor bulat.
                                                     144     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                       Persyaratan Umum Instalasi Listrik 2011        145
                                                                    Tabel A.52-13 KHA dalam ampere untuk metode instalasi E, F dan G Tabel A.52-1 –                                                 Tabel A.52-14 Faktor koreksi untuk suhu udara ambien selain 30˚C
                                                                                      Insulasi XLPE atau EPR/Konduktor aluminium                                                                                 yang diterapkan pada KHA kabel di udara
                                                                                    Suhu konduktor: 90 °C/Suhu ambien acuan: 30 °C
                                                                                                                                                                                                                                             Insulasi
                                                       konduktor
                                                                                                                                                                                        25                1,06               1,04                       1,07                            1,04
                                                                2                                                                                                                       35                0,94               0,96                       0,93                            0,96
                                                           mm                                                                                                                           40                0,87               0,91                       0,87                            0,92
                                                                                                                                                                                        45                0,79               0,87                       0,85                            0,88
                                                                                                                                                                                        50                0,71               0,82                       0,67                            0,84
                                                                                                                                                                                        55                0,61               0,76                       0,57                            0,80
                                                                                                                                                                                        60                0,51               0,71                       0,45                            0,75
                                                                                                                                                                                        65                 –                 0,65                        –                              0,70
                                                            1               2                3             4             5                 6            7                8
                                                                                                                                                                                        70                 –                 0,58                        –                              0,65
                                                           2.5              28              24             -             -              -               -                -              75                 –                 0,50                        –                              0,60
                                                            4               38              32             -             -              -               -                -              80                 –                 0,41                        –                              0,54
                                                            6               49              42             -             -              -               -                -              85                 –                  –                          –                              0,47
                                                            10              67              58             -             -              -               -                -              90                 –                  –                          –                              0,40
                                                           16                91             77             -             -              -               -                -              95                 –                  –                          –                              0,32
                                                           25               108             97            121           103            107            138               122    a   Untuk suhu ambien yang lebih tinggi, hubungi pabrikan.
                                                           35               135             120           150           129            135            172               153
                                                           50               164             146           184           159            165            210               188
                                                            70              211             187           237           206            215            271               244               Tabel A.52-15 Faktor koreksi untuk suhu tanah ambien selain 20 °C yang diterapkan
                                                           95               257             227           289           253            264            332               300
                                                           120              300             263           337           296            308            387               351                                      pada KHH kabel dalam talang dalam tanah
                                                           150              346             304           389           343            358            448               408
                                                           185              397             347           447           395            413            515               470
                                                                                                                                                                                             Suhu Tanah                                                 Insulasi
                                                           240              470             409           530           471            492             611              561
                                                           300              543             471           613           547            571            708               652                      ºC
                                                                                                                                                                                                                                    PVC                                   XLPE dan EPR
                                                           400                -              -            740           663            694            856               792
                                                           500                -              -            856           770            806            991               921                        10                               1,10                                        1,07
                                                           630                -              -            996           899            942            1154              1077                       15                               1,05                                        1,04
                                                      CATATAN                                                                                                                                      25                               0,95                                        0,96
                                                                                                          2                                                                                        30                               0,89                                        0,93
                                                      Konduktor
                                                      duktor    bulat dianggap berukuran sampai dengan 16 mm . Nilai untuk ukuran yang lebih besar berkaitan dengan kon
                                                                                                                                                                                                   35                               0,84                                        0,89
                                                      kompak dan dengan aman dapat diterapkan untuk konduktor bulat.                                                                               40                               0,77                                        0,85
                                                                                                                                                                                                   45                               0,71                                        0,80
                                                                                                                                                                                                   50                               0,63                                        0,76
                                                                                                                                                                                                   55                               0,55                                        0,71
                                                                                                                                                                                                   60                               0,45                                        0,65
                                                                                                                                                                                                   65                                –                                          0,60
                                                                                                                                                                                                   70                                –                                          0,53
                                                                                                                                                                                                   75                                –                                          0,46
                                                                                                                                                                                                   80                                –                                          0,38
                                                     146     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                      Persyaratan Umum Instalasi Listrik 2011   147
                                                                             Tabel A.52-16 Faktor koreksi untuk kabel dalam talang tertanam                                                      CATATAN 4
                                                                                   untuk resistivitas termal tanah selain 2,5 K∙ m/W yang                                                        Jika sistem terdiri atas kabel 2-inti dan 3-inti, jumlah total kabel diambil sebagai jumlah sirkit, dan faktor terkait diterapkan pada tabel untuk du
                                                                                                                                                                                                 a
                                                                                       diterapkan pada KHA untuk metode acuan D
                                                                                                                                                                                                 konduktor berbeban untuk kabel 2-inti, dan pada tabel untuk tiga konduktor berbeban untuk kabel 3-inti.
                                                                                                                                                                                                 CATATAN 5
                                                      Resistivitas termal, K∙ m/W                                            1             1,5            2             2,5            3         Jika kelompok terdiri atas n kabel inti tunggal, maka dapat dianggap sebagai n/2 sirkit dari dua konduktor berbeban atau n/3 sirkit dari tiga
                                                                                                                                                                                                 konduktor berbeban.
                                                      Faktor koreksi                                                        1,18           1,1           1,05            1           0,96        CATATAN 6
                                                                                                                                                                                                 Nilai yang diberikan telah dirata-rata terhadap julat ukuran konduktor dan jenis instalasi yang termasuk dalam Tabel A.52-2 hingga A.52-13,
                                                      CATATAN 1
                                                                                                                                                                                                 keakuratan total nilai tabel adalah ± 5 %.
                                                      Faktor koreksi yang diberikan telah dirata-rata terhadap julat ukuran konduktor dan jenis instalasi yang termasuk dalam
                                                                                                                                                                                                 CATATAN 7
                                                      Tabel
                                                                                                                                                                                                 Untuk beberapa instalasi dan untuk metode lain yang tidak diberikan dalam tabel di atas, mungkin tepat untuk menggunakan faktor yang dihitung
                                                      A.52-2 hingga A.52-5. Keakuratan total faktor koreksi adalah ± 5 %.
                                                                                                                                                                                                 untuk hal khusus, lihat misalnya Tabel A.52-20 hingga A.52-21.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                      CATATAN 2
                                                      Faktor koreksi dapat diterapkan pada kabel yang ditarik dalam talang tertanam; untuk kabel yang terletak langsung da
                                                      lam                                                                                                                                        Tabel A.52-18 Faktor reduksi untuk lebih dari satu sirkit, kabel diletakkan langsung dalam tanah –
                                                      tanah, faktor koreksi untuk resistivitas termal kurang dari 2,5 K∙m/W akan lebih tinggi. Jika diperlukan nilai yang lebih t                                    Metode instalasi D dalam Tabel A.52-2 hingga A.52-5 –
                                                      epat,
                                                      dapat dihitung dengan metode yang diberikan dalam IEC 602852
                                                                                                                                                                                                                                 Kabel inti tunggal atau multiinti
                                                                                                                                                                                                                                                               Jarak bebas kabel ke kabel (a) a
                                                      CATATAN 3                                                                                                                                        Jumlah sirkit
                                                      Faktor koreksi dapat diterapkan pada talang yang ditanam pada kedalaman sampai dengan 0,8 m.                                                                           Nol (kabel           Satu diameter            0,125 m                 0,25 m                 0,5 m
                                                     Tabel A.52-17 Faktor reduksi untuk kelompok lebih dari satu sirkit atau lebih dari satu kabel multiinti                                                                bersentuhan)              kabel
                                                                         yang digunakan dengan KHA Tabel A.52-2 hingga A.52-13                                                                              2                     0,75                  0,80                  0,85                  0,90                   0,90
                                                                   Susunan                                    Jumlah sirkit atau kabel multiinti                                  Digunakan                 3                     0,65                  0,70                  0,75                  0,80                   0,85
                                                       No.       (persentuhan                                                                                                    dengan KHA,                4                     0,60                  0,60                  0,70                  0,75                   0,80
                                                                    kabel)             1      2      3       4       5      6       7      8       9      12      16     20         acuan                   5                     0,55                  0,55                  0,65                  0,70                   0,80
                                                                                                                                                                                                            6                     0,50                  0,55                  0,60                  0,70                   0,80
                                                               Disatukan diudara,
                                                                                                                                                                                   A.52-2 –
                                                           1   pada permukaan,        1,00   0,80   0,70    0,65   0,60    0,57    0,54   0,52    0,50   0,45    0,41    0,38
                                                                                                                                                                                                 a   Kabel multiinti
                                                                                                                                                                                  A.52-13
                                                               tertanam atau
                                                                                                                                                                                 Metode A – F
                                                               terselungkup
                                                               Lapisan tunggal
                                                           2   pada dinding, lantai   1,00   0,85   0,79    0,75   0,73    0,72    0,72   0,71    0,70
                                                                                                                                                                                   A.52-2 –
                                                               atau rak berlubang                                                                                                                a   Kabel inti tunggal
                                                                                                                                                                                   A.52-7
                                                               Lapisan tunggal                                                                                                    Metode C
                                                           3   magun langsung di      0,95   0,81   0,72    0,68   0,66    0,64    0,63   0,62    0,61      Tidak ada faktor
                                                               bawah plafon kayu
                                                               Lapisan tunggal                                                                            reduksi untuk lebih
                                                               pada rak berlubang                                                                         dari sembilan sirkit
                                                           4                          1,00   0,88   0,82    0,77   0,75    0,73    0,73   0,72    0,72
                                                               horizontal atau                                                                            atau kabel multiinti     A.52-8 –
                                                               vertical                                                                                                           A.52-13        CATATAN
                                                               Lapisan tunggal                                                                                                    Metode E       Nilai yang diberikan berlaku untuk kedalaman instalasi 0,7 m dan resistivitas termal tanah 2,5 K∙ m/W. Nilai adalah nilai rer
                                                               pada penopang                                                                                                       dan F         ata
                                                           5                          1,00   0,87   0,82    0,80   0,80    0,79    0,79   0,78    0,78
                                                               tangga atau paku                                                                                                                  untuk julat ukuran dan jenis kabel yang diberikan untuk Tabel A.52-2 hingga A.52-5. Proses rerata, bersama-sama deng
                                                               dsb.                                                                                                                              an
                                                      CATATAN 1
                                                                                                                                                                                                 pembulatan, dalam beberapa hal dapat menyebabkan eror sampai dengan ± 10 %.
                                                                                                                                                                                                 (JIka diperlukan nilai yang lebih tepat, maka dapat dihitung dengan metode yang diberikan dalam IEC 602852-1).
                                                      Faktor ini dapat diterapkan untuk kelompok kabel seragam, berbeban sama.
                                                      CATATAN 2
                                                      Jika jarak bebas horizontal antara kabel yang berdekatan melebihi dua kali diameter totalnya, tidak ada faktor reduksi yang perlu ditera
                                                      pkan.
                                                      CATATAN 3
                                                      Faktor yang sama diterapkan untuk:
                                                      - kelompok dua atau tiga kabel inti tunggal;
                                                      - kabel multiinti.
                                                     148       Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                                                  Persyaratan Umum Instalasi Listrik 2011       149
                                                                        Tabel A.52-19 Faktor reduksi untuk lebih dari satu sirkit, kabel diletakkan                                   B) Kabel inti tunggal dalam talang jalur tunggal
                                                                                              dalam talang dalam tanah –
                                                                                                                                                                                                                                                 Jarak bebas talang ke talang (a) a
                                                                                 Metode instalasi D dalam Tabel A.52-2 hingga A.52-5 –                                                       Jumlah sirkit inti
                                                                                                                                                                                           tunggal dari dua atau
                                                                                                                                                                                                                        Nol (talang               0,25 m                    0,5 m                      1,0 m
                                                                                                                                                                                                tiga kabel
                                                     A) Kabel multiinti dalam talang jalur tunggal                                                                                                                     bersentuhan)
                                                                                                                                                                                                    2                      0,80                     0,90                     0,90                       0,95
                                                                                                                Jarak bebas talang ke talang (a) a                                                  3                      0,70                     0,80                     0,85                       0,90
                                                              Jumlah kabel                                                                                                                          4                      0,65                     0,75                     0,80                       0,90
                                                                                          Nol (talang            0,25 m                    0,5 m                   1,0 m                            5                      0,60                     0,70                     0,80                       0,90
                                                                                         bersentuhan)                                                                                               6                      0,60                     0,70                     0,80                       0,90
                                                                    2                         0,85                 0,90                     0,95                    0,95               a   Kabel multiinti
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                                                       CATATAN
                                                                                                                                                                                       Nilai yang diberikan berlaku untuk kedalaman instalasi 0,7 m dan resistivitas termal tanah 2,5 K∙ m/W. Nilai adalah nilai rer
                                                                                                                                                                                       ata
                                                                                                                                                                                       untuk julat ukuran dan jenis kabel yang diberikan untuk Tabel A.52-2 hingga A.52-5. Proses rerata, bersama-sama deng
                                                                                                                                                                                       an
                                                      CATATAN
                                                                                                                                                                                       pembulatan, dalam beberapa hal dapat menyebabkan eror sampai dengan ± 10 %.
                                                      Nilai yang diberikan berlaku untuk kedalaman instalasi 0,7 m dan resistivitas termal tanah 2,5 K∙ m/W. Nilai adalah nilai rer    JIka diperlukan nilai yang lebih tepat, maka dapat dihitung dengan metode yang diberikan dalam IEC 602852-1.
                                                      ata
                                                      untuk julat ukuran dan jenis kabel yang diberikan untuk Tabel A.52-2 hingga A.52-5. Proses rerata, bersama-sama deng
                                                      an
                                                      pembulatan, dalam beberapa hal dapat menyebabkan eror sampai dengan ± 10 %.
                                                      JIka diperlukan nilai yang lebih tepat, maka dapat dihitung dengan metode yang diberikan dalam IEC 602852-1.
                                                     150       Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                                 Persyaratan Umum Instalasi Listrik 2011   151
                                                       Tabel A.52-20 Faktor reduksi untuk kelompok lebih dari satu kabel multiinti yang diterapkan pada                                            Tabel A.52-21 Faktor reduksi untuk kelompok lebih dari satu sirkit kabel inti tunggal (Catatan 2)
                                                                            peringkat acuan untuk kabel multiinti di udara bebas –                                                                                          yang diterapkan pada peringkat acuan untuk
                                                                           Metode instalasi E dalam Tabel A.52-8 hingga A.52-13                                                                                             satu sirkit kabel inti tunggal di udara bebas –
                                                                                                                                                                                                                       Metode instalasi F dalam Tabel A.52-8 hingga A.52-13
                                                                                                                                                            Jumlah Kabel
                                                                  Metode instalasi dalam Tabel 52B2                      Jumlah rak                                                                                                                              Jumlah sirkit trifase
                                                                                                                                                                                                                                                     Jumlah                                     Digunakan sebagai
                                                                                                                                            1        2         3        4        6         9                 Metode instalasi dalam Tabel 523                       (catatan 5)
                                                                                                                                                                                                                                                                                                  pengali untuk
                                                                                                                                                                                                                                                       rak
                                                                                               Bersentuhan                     1          1,00      0,88     0,82     0,79      0,76     0,73                                                                    1           2          3        peringkat untuk
                                                                                                                               2          1,00      0,87     0,80     0,77      0,73     0,68                                       Bersentuhan         1       0,98        0,91       0,87
                                                                                                                                                                                                   Rak berlubang                                                                                  Tiga kabel dalam
                                                        Rak berlubang                                                                                                                                               31
                                                                             31                                                3          1,00      0,86     0,79     0,76      0,71     0,66                                                           2       0,96        0,87       0,81
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                      CATATAN 1                                                                                                                                           Lampiran ini dimaksudkan untuk menggambarkan salah satu metode yang mungkin sehingga Tabel
                                                      Nilai yang diberikan adalah rerata untuk jenis kabel dan julat ukuran konduktor dipertimbangkan dalam Tabel A.52-8 hingga A.52-13. Perbedaan        A.52-2 hingga A.52-5 (52-C1 hingga 52-C4), A.52-10 hingga A.52-13 (52-C9 hingga 52-C12) dan
                                                      nilai umumnya kurang dari 5 %.
                                                                                                                                                                                                          A.52-17 hingga A.52-21 (52-E1 hingga 52-E5) dapat disederhanakan.
                                                      CATATAN 2
                                                      Faktor diberikan untuk lapisan tunggal kabel (atau kelompok trefoil) seperti diperlihatkan dalam tabel dan tidak berlaku jika kabel dipasang pada
                                                      lebih dari satu lapisan yang bersentuhan satu sama lain. Nilai untuk instalasi tersebut dapat secara signifikan lebih rendah dan harus ditentukan                                       Tabel B.52-1 KHA dalam ampere
                                                      dengan metode yang sesuai.
                                                                                                                                                                                                             Metode
                                                      CATATAN 3                                                                                                                                               acuan                               Jumlah konduktor berbeban dan jenis insulasi
                                                      Nilai yang diberikan untuk jarak vertikal antara rak 300 mm. Untuk jarak yang lebih dekat, faktor sebaiknya dikurangi.                               dalam Tabel
                                                                                                                                                                                                             A.52-1
                                                      CATATAN 4
                                                                                                                                                                                                                                Tiga   Dua              Tiga     Dua
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                      Nilai yang diberikan untuk jarak horizontal antara rak 225 mm dengan rak dipasang beradu punggung dan sekurang-kurangnya 20 mm antara rak                A1
                                                      dan setiap dinding . Untuk jarak yang lebih dekat, fakotr sebaiknya dikurangi.                                                                                            PVC    PVC              XLPE     XLPE
1 2 3 4 5 6 7 8 9 10 11 12 13
                                                                                                                                                                                                              Ukuran
                                                                                                                                                                                                                   2
                                                                                                                                                                                                              (mm )      13     13,5   14,5      15,5    17      18,5    19,5     22         23       24         26        –
                                                                                                                                                                                                             Tembaga
                                                                                                                                                                                                               1,5       17,5    18    19,5       21     23      25      27       30         31       33        36         –
                                                                                                                                                                                                               2,5        23     24     26       28       31     34      36       40        42        45        49         –
                                                                                                                                                                                                                4         29     31     34       36      40      43      46        51       54        58        63         –
                                                                                                                                                                                                                6         39     42     46       50      54      60      63        70       75        80        86         –
                                                                                                                                                                                                                10        52     56     61       68      73      80      85       94        100       107       115        –
                                                                                                                                                                                                                16        68     73     80       89      95      101     110      119       127       135       149       161
                                                                                                                                                                                                                25        –      –      –        110     117     126     137      147       158       169       185       200
                                                                                                                                                                                                                35        –      –      –        134     141     153     167      179       192       207       225       242
                                                                                                                                                                                                                50        –      –      –        171     179     196     213      229       246       268       289       310
                                                                                                                                                                                                                70        –      –      –        207     216     238     258      278       298       328       352       377
                                                                                                                                                                                                                95        –      –      –        239     249     276     299      322       346       382       410       437
                                                                                                                                                                                                               120        –      –      –         –      285     318     344      371       395       441       473       504
                                                                                                                                                                                                               150        –      –      –         –      324     362     392      424       450       506       542       575
                                                                                                                                                                                                               185        –      –      –         –      380     424     461      500       538       599       641       679
                                                                                                                                                                                                               240
                                                     154      Persyaratan Umum Instalasi Listrik 2011                                                                                                                                                                           Persyaratan Umum Instalasi Listrik 2011        155
                                                       Aluminium
                                                                                                                                                                                           Tabel B.52-2 KHA (dalam ampere)
                                                          2,5          13,5       14       15         16,5   18,5   19,5    21   23     24       26      28       –
                                                           4           17,5      18,5      20          22     25     26    28     31    32       35      38       –                                             Jumlah konduktor berbeban dan jenis insulasi
                                                           6            23        24       26          28     32     33    36    39     42       45      49       –     Metode instalasi              2
                                                                                                                                                                                           Ukuran mm
                                                           10           31        32       36          39     44     46    49    54     58       62      67       –                                           Dua PVC        Tiga PVC       Dua XLPE        Tiga XLPE
                                                           16           41        43       48          53     58     61    66    73     77       84       91      –
                                                           25           53        57       63          70     73     78    83    90     97       101     108     121                        Tembaga
                                                           35           –         –        –           86     90     96    103   112    120      126     135     150                          1,5                22             18              26                 22
                                                           50           –         –        –          104    110    117    125   136    146      154     164     184                          2,5               29              24              34             29
                                                           70           –         –        –          133    140    150    160   174    187      198     211     237                           4                38               31             44             37
                                                           95           –         –        –          161    170    183    195   211    227      241     257     289
                                                                                                                                                                                               6                47              39              56             46
                                                          120           –         –        –          186    197    212    226   245    263      280     300     337
                                                          150           –         –        –                 226    245    261   283    304      324     346     389                           10               63              52              73              61
                                                                                                                                                                                              16                 81             67              95             79
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     156    Persyaratan Umum Instalasi Listrik 2011                                                                                                                      Persyaratan Umum Instalasi Listrik 2011        157
                                                                                                                                                                     Lampiran C (informatif)
                                                                                                                                                                     Rumus yang menyatakan KHA
                                                                        Tabel B.52-3 Faktor reduksi untuk kelompok beberapa sirkit atau beberapa                     Nilai yang diberikan dalam Tabel A.52-2 hingga A.52-13 terbentang pada kurva rata berkaitan KHA
                                                                                kabel multiinti (yang digunakan dengan KHA Tabel B.52-1)                             dan luas penampang konduktor.
                                                                                                                 Jumlah sirkit atau kabel multi inti                 Kurva ini didapatkan dengan menggunakan rumus berikut:
                                                       Nomor                Susunan
                                                                                                     1     2      3      4       6       9      12     16     20
                                                                                                                                                                                                                I = A x Sm – B x Sn
                                                                    Tertanam atau
                                                           1                                       1,00   0,80   0,70   0,70    0,55    0,50    0,45   0,40   0,40
                                                                    terselungkup                                                                                     dengan
                                                                    Lapisan tunggal pada
                                                           2        dinding, lantai atau           1,00   0,85   0,80   0,75    0,70    0,70     -      -      -     I adalah KHA, dalam ampere;
                                                                    pada rak berlubang
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                                     S adalah luas penampang nominal konduktor, dalam millimeter kuadrat (mm2); dalam hal ukuran
                                                                    Lapisan tunggal                                                                                  nominal 50 mm2, untuk kabel dengan insulasi diekstrusi, sebaiknya digunakan nilai 47,5 mm2. Untuk
                                                           3        magun langsung di              0,95   0,80   0,70   0,70    0,65    0,60     -      -      -
                                                                                                                                                                     semua ukuran lain dan untuk semua ukuran kabel berinsulasi mineral, nilai nominal cukup tepat.
                                                                    bawah plafon
                                                                    Lapisan tunggal                                                                                  A dan B adalah koefisien sedangkan m dan n adalah pangkat menurut kabel dan metode instalasi.
                                                           4        pada rak berlubang             1,00   0,90   0,75   0,75    0,75    0,70     -      -      -
                                                                    horizontal atau                                                                                  Nilai koefisien dan pangkat diberikan dalam tabel yang menyertainya. KHA sebaiknya dibulatkan ke
                                                                    vertikal                                                                                         0,5 A terdekat untuk nilai tidak melebihi 20 A dan ampere terdekat untuk nilai lebih besar dari 20 A.
                                                                    Lapisan tunggal pada
                                                           5        penopang tangga        1,00           0,85   0,80   0,80    0,80    0,80     -      -      -     Angka bilangan signifikan yang diperoleh tidak diambil sebagai indikasi KHA yang akurat.
                                                                    kabel atau paku kabel,
                                                                    dsb.                                                                                             Praktis untuk semua hal, hanya istilah pertama yang diperlukan. Istilah kedua diperlukan hanya untuk
                                                                                                                                                                     delapan kasus jika digunakan kabel inti tunggal besar.
                                                                                                                                                                     Tidak disarankan untuk menggunakan koefisien dan pangkat ini untuk ukuran konduktor di luar julat
                                                                                                                                                                     yang sesuai yang digunakan dalam Tabel A.52-2 hingga A.52-13.
                                                     158       Persyaratan Umum Instalasi Listrik 2011                                                                                                                                  Persyaratan Umum Instalasi Listrik 2011   159
                                                                                          Tabel C.52-1 Tabel koefisien dan eksponen                                     Tabel C.52-1 Tabel koefisien dan eksponen (lanjutan)
                                                     160     Persyaratan Umum Instalasi Listrik 2011                                                                                                             Persyaratan Umum Instalasi Listrik 2011    161
                                                                                                                                                                Lampiran D (informatif)
                                                                                                                                                                Efek arus harmonik pada sistem trifase yang seimbang
                                                                                   Tabel C.52-1 Tabel koefisien dan eksponen (lanjutan)                         D.1 Faktor reduksi untuk arus harmonik dalam kabel 4-inti dan 5-inti dengan empat inti
                                                                                                                                                                menghantarkan arus
                                                                                                            Konduktor tembaga             Konduktor alumunium
                                                           Tabel KHA                    Kolom
                                                                                                                                                                Subayat 523.6.3 menyatakan bahwa jika konduktor netral menghantarkan arus tanpa pengurangan
                                                                                                            A             m                A             m
                                                                                                  2
                                                                                                                                                                beban terkait pada konduktor fase, arus yang mengalir dalam konduktor netral harus diperhitungkan
                                                                                      2 ≤ 16 mm2            20,5        0,623             –              –
                                                                                                           18,6         0,646             –              –
                                                                                                                                                                dalam memastikan KHA sirkit.
                                                                                     2 > 16 mm2
                                                                                      3 ≤ 16 mm            17,8         0,623             –              –
                                                                                     3 > 16 mm
                                                                                               2
                                                                                                           16,4         0,637             –              –      Lampiran ini dimaksudkan untuk mencakup situasi dimana arus mengalir dalam netral sistem trifase
                                                           A.52-12                         4               20,8         0,636             –              –
                                                                                     5 ≤ 300 mm2           16,0         0,6633            –              –      seimbang. Arus netral tersebut adalah karena arus fase yang mempunyai kandungan harmonik yang
                                                                                     5 > 300 mm2
                                                                                                2
                                                                                                           16,0         0,6633        6 x 10-4         1,793    tidak hilang dalam netral. Harmonik yang paling signifikan yang tidak hilang dalam netral biasanya
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                     6 ≤ 300 mm            16,57        0,665             –              –      adalah harmonik ketiga. Besarnya arus netral karena harmonik ketiga dapat melebihi besarnya arus
                                                                                                2
                                                                                     6 > 300 mm            16,57        0,665         3 x 10-4         1,876
                                                                                           7               22,9         0,644             –              –      fase frekuensi daya. Dalam hal ini arus netral akan mempunyai efek yang signifikan pada KHA kabel
                                                                                           8               19,1         0,662             –              –      dalam sirkit.
                                                                                     2 ≤ 16 mm2            16,0          0,625             –             –
                                                                                     2 > 16 mm
                                                                                              2
                                                                                              2
                                                                                                           13,4          0,649             –             –      Faktor reduksi yang diberikan dalam lampiran ini berlaku pada sirkit trifase seimbang; diketahui
                                                                                     3 ≤ 16 mm2            13,7          0,623             –             –
                                                           A.52-13                   3 > 16 mm             12,6          0,635             –             –      bahwa situasi lebih berat jika hanya dua dari tiga fase yang dibebani. Pada situasi ini, konduktor
                                                                                          4                14,7          0,654             –             –      netral akan menghantarkan arus harmonik sebagai tambahan ke arus tak seimbang. Situasi tersebut
                                                                                          5                11,9          0,671             –             –      dapat mengarah pada pembebanan lebih konduktor netral.
                                                                                          6                12,3          0,673             –             –
                                                                                          7                16,5          0,659             –             –
                                                                                          8                13,8          0,676             –             –      Perlengkapan yang mungkin menyebabkan arus harmonik yang signifikan misalnya adalah gugus
                                                                                                                                                                lampu fluoresen dan suplai daya a.s. yang digunakan di komputer. Informasi lebih lanjut mengenai
                                                                                                                                                                gangguan harmonik dapat ditemukan dalam IEC 61000.
                                                                                                                                                                Faktor reduksi yang diberikan dalam Tabel D.52-1 hanya berlaku untuk kabel yang konduktor netral
                                                                                                                                                                merupakan kabel 4-inti atau 5-inti dan berbahan dan berluas penampang sama sebagai konduktor
                                                                                                                                                                fase. Faktor reduksi ini telah dihitung berdasarkan arus harmonik ketiga. Jika harmonik yang lebih
                                                                                                                                                                tinggi misalnya ke 9, ke 12 dsb diperkirakan signifikan, yaitu lebih dari 10 %, maka faktor reduksi yang
                                                                                                                                                                lebih rendah dapat diterapkan.
                                                                                                                                                                Faktor reduksi dalam tabel jika diterapkan pada KHA kabel dengan tiga konduktor berbeban, akan
                                                                                                                                                                memberikan KHA kabel dengan empat kondukor berbeban dengan arus pada konduktor keempat
                                                                                                                                                                adalah karena harmonik. Faktor reduksi juga memperhitungkan efek pemanasan arus harmonik
                                                                                                                                                                dalam konduktor fase.
                                                                                                                                                                Jika arus netral diperkirakan lebih tinggi dari arus fase maka ukuran kabel sebaiknya dipilih
                                                                                                                                                                berdasarkan arus netral.
                                                                                                                                                                Jika pemilihan ukuran kabel didasarkan pada arus netral yang tidak secara signifikan lebih tinggi dari
                                                                                                                                                                arus fase, maka perlu untuk mengurangi tabel KHA untuk tiga konduktor berbeban.
                                                     162     Persyaratan Umum Instalasi Listrik 2011                                                                                                                              Persyaratan Umum Instalasi Listrik 2011   163
                                                     Jika arus netral lebih dari 135 % arus fase dan ukuran kabel dipilih berdasarkan arus netral, maka           Jika ada harmonik ketiga 50 %, ukuran kabel dipilih lagi berdasarkan arus netral, yang adalah:
                                                     tiga konduktor fase tidak akan dibebani penuh. Pengurangan bahang yang ditimbulkan oleh
                                                     konduktor fase mengimbangi bahang yang ditimbulkan oleh konduktor netral sehingga tidak perlu                                                         39 x 0,5 x 3 = 58,5 A
                                                     memberlakukan adanya faktor reduksi pada KHA tiga konduktor berbeban.
                                                                                                                                                                  dalam hal ini faktor peringkat adalah 1 dan diperlukan kabel 16 mm2.
                                                                  Tabel D.52-1 Faktor reduksi untuk arus harmonik dalam kabel 4-inti dan 5-inti
                                                                                                                                                                  Semua pemilihan kabel di atas didasarkan pada KHA kabel; drop voltase dan aspek lain desain tidak
                                                           Kandungan harmonik ketiga                                       Faktor reduksi                         dipertimbangkan.
                                                                  arus fase                         Pemilihan ukuran didasarkan     Pemilihan ukuran didasarkan
                                                                     %                                     pada arus fase                 pada arus netral
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                      0 – 15                                   1,0                              –
                                                                      15 – 33                                  0,86                             –
                                                                      33 – 45                                   –                              0,86
                                                                       > 45                                     –                              1,0
                                                     Pertimbangkan sirkit trifase dengan beban desain 39 A yang dipasang dengan menggunakan kabel
                                                     berinsulasi PVC 4-inti diklip ke dinding, metode instalasi C.
                                                     Dari Tabel A.52-4 kabel 6 mm2 dengan konduktor tembaga mempunyai KHA 41 A dan karena itu
                                                     cocok jika harmonik tidak ada dalam sirkit.
Jika ada harmonik ketiga 20 %, maka diterapkan faktor reduksi 0,86 dan beban desain menjadi:
39/0,86 = 45 A
Jika ada harmonik ketiga 40 %, pemilihan ukuran kabel didasarkan pada arus netral yang adalah:
39 x 0,4 x 3 = 46,8 A
dan faktor reduksi 0,86 diterapkan, mengarah pada beban desain menjadi:
46,8/0,86 = 54,4 A
                                                     164      Persyaratan Umum Instalasi Listrik 2011                                                                                                                               Persyaratan Umum Instalasi Listrik 2011   165
                                                     Lampiran E (normatif)
                                                     Jarak maksimum penyangga kabel dan radius belokan maksimum kabel
                                                     Kabel yang telah digunakan dapat rusak jika terganggu. Hal ini timbul dari efek penuaan alami
                                                     pada sifat fisik bahan yang digunakan untuk insulasi kabel dan pelindung yang dapat menimbulkan
                                                     pengerasan pada bahan ini.
Tabel E.52.1 Jarak penyangga untuk kabel nonarmor pada posisi yang dapat diakses
                                                     166       Persyaratan Umum Instalasi Listrik 2011                                                                                                                                      Persyaratan Umum Instalasi Listrik 2011   167
                                                     Lampiran F (informatif)
                                                     Pedoman batas dimensi konduktor bulat
                                                     CATATAN
                                                                                                                                                             PENJELASAN
                                                     Lampiran ini mengacu pada IEC 60228 Lampiran C.
                                                     F.1 Tujuan                                                                                              Yang dimaksud konduktor pilin bulat kompak (stranded compacted circular conductors)
                                                     Lampiran ini dimaksudkan sebagai pedoman bagi pabrikan kabel dan konektor kabel untuk membantu          adalah yang penampangnya berbentuk sbb:
                                                     memastikan bahwa konduktor dan konektor kompatibel secara dimensi. Lampiran ini memberikan
                                                     pedoman batas dimensi untuk tipe konduktor berikut yang tercakup dalam standar ini:
                                                     a) konduktor padat bulat, (kelas 1) dari tembaga, aluminium atau paduan aluminium;
                                                     b) konduktor pilin bulat dan pilin bulat kompak, (kelas 2), dari tembaga, aluminium dan paduan
                                                         aluminium;
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     Jika diameter minimum untuk konduktor tembaga bulat kelas 1 diperlukan, dapat mengacu pada
                                                     diameter minimum untuk konduktor aluminium atau paduan aluminium bulat padat yang ditunjukkan
                                                     pada Tabel F.52.3.
                                                                                                                                                                                           Gambar - Contoh konduktor pilin bulat kompak
                                                     F.3 Batas dimensi untuk konduktor tembaga, aluminium dan paduan aluminium, pilin bulat
                                                                                                                                                             (Disalin dari buku: “Power Cables & Wires, Technical Manual”, edisi 2010, Institute of Integrated Electrical
                                                          kompak                                                                                             Engineers of the Philippines, Inc. dengan inisiatif International Copper Association – South East Asia.
                                                     Diameter konduktor tembaga, aluminium dan paduan aluminium pilin, bulat kompak sebaiknya tidak
                                                     melebihi nilai maksimum dan sebaiknya tidak kurang dari nilai minimum yang diberikan pada Tabel
                                                     F.52.2.                                                                                             Pada kasus pengecualian untuk konduktor aluminium atau paduan aluminium pilin bulat nonkompak,
                                                                                                                                                         diameter maksimum sebaiknya tidak melebihi nilai terkait untuk konduktor tembaga yang diberikan
                                                                                                                                                         pada kolom 3, Tabel F.52.1.
                                                                                                                                                         Diameter konduktor aluminium dan paduan aluminium padat bulat sebaiknya tidak melebihi nilai
                                                                                                                                                         maksimum dan sebaiknya tidak kurang dari nilai minimum yang diberikan pada Tabel F.52.3.
                                                     168    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                Persyaratan Umum Instalasi Listrik 2011   169
                                                                              Tabel F.52.1 Diameter maksimum konduktor tembaga bulat –
                                                                                                                                                                       PENJELASAN
                                                                                           padat, pilin nonkompak dan fleksibel
                                                                      1                                   2                   3                          4             Untuk diameter konduktor tembaga bulat padat, yang sangat penting adalah diameter
                                                                                                                                                                       minimum, sehingga memudahkan untuk verifikasi diameter minimum konduktor dengan
                                                            Luas penampang                       Konduktor pada kabel untuk instalasi            Konduktor fleksibel   alat ukur yang lazim digunakan di pasar atau lapangan.
                                                                nominal                             Padat                   Pilin                  (kelas 5 and 6)
                                                                    mm2                           (kelas 1)               (kelas 2)                     mm             Diameter minimum konduktor dapat dihitung dengan rumus sbb:
                                                                                                     mm                     mm
                                                                                                                                                                       Mencari diameter minimum dengan R30:
                                                                     0,5                             0,9                     1,1                        1,1
                                                                     0,75                            1,0                     1,2                        1,3            Rumus dasar:
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     170        Persyaratan Umum Instalasi Listrik 2011                                                                                                                       Persyaratan Umum Instalasi Listrik 2011   171
                                                           Jadi D ≈ 3,4 mm.                                                                             Jadi D ≈ 3,4 mm. Ternyata tidak ada perbedaan antara suhu 20 ºC dan 30 ºC.
                                                           Sesuai PENJELASAN 52.1.1, untuk konduktor berinsulasi dan kabel di udara, tidak tergantung   Dengan cara yang sama maka Tabel F.52.1 dapat disempurnakan dan disederhanakan sbb:
                                                           dari metode pemasangan: suhu ambien = 30°C.
                                                                                                                                                        (Luas penampang konduktor minimum untuk konduktor tembaga sesuai dengan Tabel 52.5
                                                                                                       R30 = R20 {1 + α (30-20)}                        untuk instalasi daya magun adalah 1,5 mm2 dan dibatasi sampai dengan 16 mm2 dengan
                                                                                                                                                        pertimbangan luas penampang inilah yang terbanyak dipakai di instalasi, bahkan luas
                                                           Untuk tembaga α 0,00393.                                                                     penampang ≥ 25 mm2 sesuai CATATAN 3 dalam tabel digunakan bukan untuk keperluan
                                                                                                                                                        umum).
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     172     Persyaratan Umum Instalasi Listrik 2011                                                                                                                      Persyaratan Umum Instalasi Listrik 2011   173
                                                                       Tabel F.52.2 Diameter maksimum dan minimum konduktor tembaga,                                         Tabel F.52.3 Diameter maksimum dan minimum konduktor aluminium bulat padat
                                                                                 aluminium, paduan aluminium, pilin bulat kompak
                                                                                                                                                                                  1                              2                                       3
                                                                       1                                     2                                    3
                                                                                                                                                                            Luas penampang                      Konduktor pilin bulat kompak (kelas 1)
                                                              Luas penampang                                Konduktor pilin bulat kompak (kelas 2)
                                                                                                                                                                                 mm2                     Diameter minimum                   Diameter maksimum
                                                                           2                          Diameter minimum                  Diameter maksimum                                                       mm                                 mm
                                                                     mm                                      mm                                mm                                  10                           3,4                                    3,7
                                                                       10                                   3,6                                  4,0                              16                            4,1                                    4,6
                                                                      16                                    4,6                                  5,2                              25                            5,2                                    5,7
                                                                      25                                    5,6                                  6,5                              35                            6,1                                    6,7
                                                                                                                                                                                  50                            7,2                                    7,8
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                      35                                    6,6                                  7,5
                                                                      50                                    7,7                                  8,6                               70                           8,7                                    9,4
                                                                       70                                   9,3                                  10,2                             95                            10,3                                   11,0
                                                                      95                                    11,0                                 12,0                             120                           11,6                                   12,4
                                                                      120                                   12,3                                 13,5                             150                           12,9                                   13,8
                                                                      150                                   13,7                                 15,0                             185                           14,5                                   15,4
                                                                      185                                   15,3                                 16,8                             240                           16,7                                   17,6
                                                                      240                                   17,6                                 19,2                             300                           18,8                                   19,8
                                                                      300                                   19,7                                 21,6                             400                           21,2                                   22,2
                                                                      400                                   22,3                                 24,6                             500                           24,0                                   25,1
                                                                      500                                   25,3                                 27,6                             630                           27,3                                   28,4
                                                                      630                                   28,7                                 32,5                             800                           30,9                                   32,1
                                                                                                                                                                                 1 000                          34,8                                   36,0
                                                      CATATAN 1                                                                                                                  1 200                          37,8                                   39,0
                                                                                                                            2
                                                      Batas
                                                      pakandimensi konduktor aluminium dengan luas penampang lebih dari 630 mm tidak diberikan karena teknologi pengom
                                                      umumnya belum mantap.
                                                      CATATAN 2
                                                                                                                                                                         PENJELASAN
                                                      Tidak ada nilai yang diberikan untuk konduktor tembaga kompak pada julat ukuran 1,52 mm hingga2 6 mm .
                                                                                                                                                                         Berdasarkan Tabel di atas, maka sesuai SNI IEC 60228, luas penampang kabel aluminium
                                                                                                                                                                         minimum yang diizinkan adalah 10 mm2 Al, yang kira-kira setara dengan luas penampang
                                                                                                                                                                         6 mm2 Cu.
                                                                                                                                                                         Hal ini tentu sudah mempertimbangkan banyak faktor, terutama karena konduktivitas
                                                                                                                                                                         tembaga memang lebih tinggi dari aluminium. Sehingga untuk penampang kecil, kabel
                                                                                                                                                                         aluminium mempunyai drop voltase dan susut yang lebih besar. Jadi luas penampang
                                                                                                                                                                         minimum 10 mm2 Al adalah luas penampang optimum dengan mempertimbangkan faktor
                                                                                                                                                                         ekonomis jangka panjang.
                                                     174    Persyaratan Umum Instalasi Listrik 2011                                                                                                                              Persyaratan Umum Instalasi Listrik 2011   175
                                                                                                     Bagian 5 - 53
                                                                                                     Pemilihan dan
                                                                                                     pemasangan
                                                                                                     perlengkapan
                                                                                                     listrik - Isolasi,
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                     penyakelaran
                                                                                                     dan kendali
                                                     176   Persyaratan Umum Instalasi Listrik 2011      Persyaratan Umum Instalasi Listrik 2011   177
                                                     530 Pendahuluan
                                                     persyaratan yang sesuai untuk pengaruh eksternal yang diperkirakan. Setiap jenis perlengkapan
                                                     harus dipilih dan dipasang sedemikian untuk memberikan kesesuaian dengan persyaratan yang                                         Gambar - Sistem pembumian TN-S
                                                     dinyatakan dalam ayat berikut dari Bagian 5-53 dan persyaratan relevan dalam bagian lain PUIL.
                                                     Persyaratan Bagian 5-53 merupakan tambahan persyaratan bersama yang diberikan dalam IEC
                                                     60364-5-51.
                                                     530.3.1 Kontak gerak semua kutub dari gawai multikutub harus dikopel secara mekanis
                                                     sedemikian sehingga dapat menghubungkan dan memutus secara bersama-sama, kecuali kontak
                                                     tersebut hanya dimaksudkan untuk netral, dapat menutup sebelum dan membuka setelah kontak
                                                     yang lain.                                                                                                                      Gambar - Sistem pembumian TN-C-S
                                                     530.3.2 Kecuali seperti diberikan dalam 536.2.2.7, dalam sirkit multifase, gawai kutub tunggal
                                                     tidak boleh disisipkan pada konduktor netral.                                                    531.1.2 Sistem TT
                                                                                                                                                      Dalam pertimbangan.
                                                     Pada sirkit fase tunggal, gawai kutub tunggal tidak boleh disisipkan pada konduktor netral,
                                                     kecuali GPAS yang memenuhi 531.2.1.1 yang disediakan pada sisi suplai.                           531.1.3 Sistem IT
                                                     530.3.3 Gawai yang mewujudkan lebih dari satu fungsi harus memenuhi semua persyaratan            Jika BKT diinterkoneksi, GPAL untuk proteksi pada saat gangguan kedua harus memenuhi 531.1.1
                                                     Bagian ini yang sesuai untuk masing-masing fungsi yang terpisah.                                 dengan memperhitungkan persyaratan 411.6.4 Bagian 4-41.
                                                     531 Gawai untuk proteksi dari sentuh tak langsung dengan diskoneksi otomatis suplai              531.2 GPAS (Gawai Proteksi Arus Sisa)
                                                                                                                                                      531.2.1 Kondisi umum instalasi
                                                     531.1 GPAL (Gawai Proteksi Arus Lebih)
                                                                                                                                                      GPAS dalam sistem a.s. harus secara khusus didesain untuk mendeteksi arus sisa a.s. dan untuk
                                                     531.1.1 Sistem TN                                                                                memutuskan arus sirkit pada kondisi normal dan kondisi gangguan.
                                                     Pada sistem TN, GPAL harus dipilih dan dipasang menurut kondisi yang ditentukan dalam 434.2
                                                     dan 431 serta dalam 533.3 untuk GPHP dan harus memenuhi persyaratan 411.4.4 Bagian 4-41.         531.2.1.1 Suatu GPAS harus memastikan diskoneksi semua konduktor aktif pada sirkit yang
                                                                                                                                                      diproteksi. Pada sistem TN-S, netral tidak perlu didiskoneksi jika kondisi suplai sedemikian
                                                                                                                                                      sehingga konduktor netral dapat dianggap berada pada potensial bumi.
                                                     178   Persyaratan Umum Instalasi Listrik 2011                                                                                                                      Persyaratan Umum Instalasi Listrik 2011   179
                                                     CATATAN
                                                     Kondisi untuk verifikasi bahwa konduktor netral berada pada potensial bumi dalam pertimbangan.       Pada dasarnya setiap peranti/pemanfaat yang tersambung pada instalasi memiliki
                                                                                                                                                          arus bocor (yang diizinkan) sesuai standar produk dari peranti/pemanfaat tersebut.
                                                     531.2.1.2 Konduktor proteksi tidak boleh menerobos sirkit magnetik GPAS.
                                                                                                                                                          Jika jumlah peranti/pemanfaat yang tersambung pada operasi normal terlalu banyak,
                                                                                                                                                          sehingga total arus bocornya melebihi Nilai standar arus nonoperasi sisa pengenalnya
                                                     531.2.1.3 GPAS harus dipilih sedemikian dan sirkit listrik dibagi sedemikian sehingga setiap arus
                                                                                                                                                          (I∆no), maka GPAS tersebut akan trip.
                                                     bocor bumi yang dapat diperkirakan terjadi selama operasi normal dari beban terhubung akan
                                                     tidak mungkin menyebabkan trip yang tak perlu.                                                       Menurut IEC 60335, arus bocor peranti/pemanfaat yang diizinkan tidak boleh melebihi
                                                     CATATAN                                                                                              nilai berikut:
                                                     GPAS dapat beroperasi pada sebarang nilai arus sisa yang melebihi 50 % dari arus operasi pengenal.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                           GPAS beroperasi pada arus sisa > 50 % arus sisa pengenal, lihat SNI 04-6956.1-2003,
                                                           Ayat 5.3.4
                                                     180     Persyaratan Umum Instalasi Listrik 2011                                                                                                             Persyaratan Umum Instalasi Listrik 2011   181
                                                     533 Gawai untuk proteksi terhadap arus lebih
                                                           PENJELASAN
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     533.1.2 Rumah sekering untuk pembawa sekering tusuk harus disusun sedemikian sehingga
                                                     tidak memungkinkan pembawa sekering membuat kontak antara bagian konduktif dari dua
                                                     rumah sekering yang berdekatan.
                                                     182     Persyaratan Umum Instalasi Listrik 2011                                                                                      Persyaratan Umum Instalasi Listrik 2011   183
                                                                                                     Bagian 5 - 54
                                                                                                     Pemilihan dan
                                                                                                     pemasangan
                                                                                                     perlengkapan listrik
                                                                                                     - Susunan
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                     pembumian,
                                                                                                     konduktor proteksi
                                                                                                     dan konduktor
                                                                                                     ikatan proteksi
                                                     184   Persyaratan Umum Instalasi Listrik 2011     Persyaratan Umum Instalasi Listrik 2011   185
                                                     542 Susunan pembumian
                                                     542.1 Persyaratan umum                                                                                        Tabel 54.1 Ukuran minimum biasa untuk elektrode bumi dari bahan
                                                                                                                                                                         yang biasa digunakan dari titik pandang korosi dan kuat
                                                      Susunan pembumian dapat digunakan tersambung atau terpisah untuk keperluan proteksi                                           mekanis jika ditanam dalam tanah
                                                     dan fungsional menurut persyaratan instalasi listrik. Persyaratan untuk keperluan proteksi
                                                                                                                                                                                                                               Ukuran minimum
                                                     harus selalu lebih diutamakan.
                                                                                                                                                                                                                                                          Tebal lapisan/
                                                                                                                                                      Bahan       Permukaan                Bentuk                       Luas            Tebal
                                                     542.1.2 Elektrode bumi pada instalasi harus dihubungkan pada terminal pembumian utama                                                            Diameter                                              selubung
                                                                                                                                                                                                                     penampang
                                                                                                                                                                                                         mm                              mm            Nilai          Nilai
                                                     dengan menggunakan konduktor pembumian.                                                                                                                            mm²
                                                                                                                                                                                                                                                     individu        rerata
                                                     Elektrode bumi ialah penghantar yang ditanam dalam bumi dan membuat kontak langsung                                                                                 90               3             63                70
                                                                                                                                                                                       c
                                                                                                                                                                                    Pita
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     186     Persyaratan Umum Instalasi Listrik 2011                                                                                                                            Persyaratan Umum Instalasi Listrik 2011           187
                                                     CATATAN 2                                                                                              542.2.6 Pipa logam untuk cairan atau gas yang mudah terbakar tidak boleh digunakan
                                                     Untuk elektrode bumi jenis pipa, panjang minimum 1,5 m.                                                sebagai elektrode bumi.
                                                     CATATAN 3                                                                                              CATATAN
                                                     Jika keadaan tanah sangat korosif atau jika digunakan elektrode baja nongalvanis, dianjurkan untuk     Persyaratan ini tidak menghalangi ikatan proteksi pipa tersebut untuk kesesuaian dengan Bagian 4-41.
                                                     menggunakan luas penampang atau tebal sekurang-kurangnya 150 % dari yang tertera dalam Tabel 54.1.
                                                                                                                                                            542.2.8 Resistans jenis tanah dan resistans pembumian
                                                     CATATAN 4
                                                     Jika elektrode pita hanya digunakan untuk mengatur gradien voltase, luas penampang minimum pada baja   542.2.8.1 Nilai resistans jenis tanah sangat berbeda-beda bergantung pada jenis tanah
                                                     galvanis atau berlapis tembaga harus 16 mm2 dan pada tembaga 10 mm2.                                   seperti ditunjukkan pada Tabel 54.2.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                           PENJELASAN
                                                                                                                                                                                             Tabel 54.2 Resistans jenis tanah (tipikal)
                                                           Pada kondisi apapun, elektrode bumi harus dipasang, terutama untuk sistem TT. Lihat                      1                2               3                4                5                  6                   7
                                                           542.2.8.2.
                                                                                                                                                                                                  Tanah liat         Pasir           Kerikil          Pasir dan             Tanah
                                                                                                                                                                Jenis tanah     Tanah rawa        dan tanah
                                                                                                                                                                                                   ladang            basah           basah           kerikil kering        berbatu
                                                                                                                                                                Resistans
                                                                                                                                                                  jenis             30               100             200              500               1000                3000
                                                                                                                                                                  (Ω-m)
                                                     188     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                    Persyaratan Umum Instalasi Listrik 2011      189
                                                                     Tabel 54.3 Resistans pembumian pada resistans jenis                     ρ1   = 100Ωmeter
                                                                                                                                                                             Pada sistem TN-C-S;
                                                            1              2           3           4        5       6          7        8           9      10        11      Kondisi pada saat terjadi gangguan di dalam BKT digambarkan sbb:
                                                                                                                                                            Pelat vertikal
                                                                                                                                                               dengan
                                                                                Pita atau konduktor pilin                  Batang atau pipa
                                                                                                                                                          sisi atas ±1m di
                                                                                                                                                         bawah permukaan
                                                                                                                                                                tanah
                                                           Jenis
                                                       Resistans          20          10           5        3       70         40       30          20      35       25
                                                      pembumia
                                                      n                                                                                                                                     Gambar - Lintasan arus ketika terjadi gangguan hubung pendek ke BKT
                                                         (Ω)                                                                                                                                                         pada sistem TN-C-S
                                                                                                                                                                             Arus gangguan mengalir melalui konduktor lin L1, tempat terjadi hubung pendek pada BKT,
                                                     KETERANGAN :
                                                     Untuk resistans jenis yang lain (), maka besar resistans pembumian adalah perkalian nilai di atas                      dan kemudian melalui konduktor proteksi PE mengalir ke titik O dari sumber. Arus gangguan
                                                     dengan.                                                                                                                 tidak mengalir melalui elektrode bumi karena resistans konduktor sangat kecil dibandingkan
                                                                                                                                                                             resistans elektrode bumi. Jadi berapapun nilai resistens pembumian tidak akan mempengaruhi
                                                                                                             ρ/ρ1 atau ρ/100                                                 besar arus gangguan. Karena itu, tanpa elektrode pembumianpun, arus gangguan dapat
                                                                                                                                                                             mengalir melalui lingkar gangguan untuk mengaktifkan gawai proteksi (GPAS) agar trip.
                                                           PENJELASAN
                                                                                                                                                                             Berbeda pada sistem TT sbb:
                                                           Dalam PUIL 2011, besar resistans pembumian tidak ditentukan, tetapi elektrode bumi harus
                                                           dipasang. Hal ini harus dibuktikan dengan pengukuran resistans elektrode bumi, sebagaimana
                                                           dijelaskan dalam Subayat 61.3.6.2 dan Subayat B.1 Lampiran B dari Bagian 6 PUIL. Hal ini
                                                           sangat penting, terutama untuk sistem TT.
                                                     190        Persyaratan Umum Instalasi Listrik 2011                                                                                                                                       Persyaratan Umum Instalasi Listrik 2011   191
                                                                                                                                                             542.3 Konduktor pembumian
                                                           Arus gangguan mengalir melalui konduktor lin L1, tempat terjadi hubung pendek pada BKT,
                                                           dan kemudian melalui konduktor proteksi PE mengalir ke bumi, melalui elektrode bumi A
                                                                                                                                                               PENJELASAN
                                                           dan B, mengalir ke titik sumber. Karena itu elektrode bumi A harus ada pada sistem TT. Tanpa
                                                           elektrode bumi A, gawai proteksi (GPAS) tidak akan bekerja.
                                                                                                                                                               Konduktor pembumian adalah konduktor yang memberikan lintasan konduktif atau bagian
                                                           Pada sistem TT kondisi berikut harus dipenuhi:                                                      lintasan konduktif antara titik tertentu dalam suatu sistem atau dalam suatu instalasi atau
                                                                                                                                                               dalam perlengkapan dengan suatu elektrode bumi dan suatu jaringan elektrode bumi
                                                           - dalam sistem a.b. RA × Id ≤ 50 V
                                                                                                                                                               CATATAN
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                           dengan
                                                                                                                                                               Untuk PUIL, konduktor pembumian adalah konduktor yang menghubungkan elektrode bumi ke titik dalam
                                                                                                                                                               sistem ikatan ekuipotensial, biasanya terminal pembumian utama.
                                                           RA adalah jumlah resistans (dalam Ω) dari elektrode bumi dan konduktor proteksi untuk BKT;          Terminal pembumian utama adalah terminal yang merupakan bagian susunan pembumian suatu instalasi
                                                           Id adalah arus gangguan (dalam A) dari gangguan pertama dengan impedans yang dapat                  dan yang memungkinkan hubungan listrik sejumlah konduktor untuk keperluan pembumian. Lihat 442.4.
                                                           diabaikan antara konduktor lin dan BKT. Nilai Id memperhitungkan arus bocor dan impedans
                                                           pembumian total instalasi listrik.
                                                           Bila RA mendekati tak terhingga, atau besar sekali (misalnya 1 MΩ, maka Id akan sangat kecil,
                                                           yaitu 50/1.000.000 = 0,00005 A atau 0,05 mA. GPAS 30 mA tidak akan bekerja.
                                                           Kondisi ini sangat berbahaya bila ada orang yang menyentuh BKT yang terhubung pendek
                                                           tersebut, karena tubuhnya akan menjadi konduktor pembumian ke bumi, sehingga merupakan
                                                           sentuh langsung. Kalaupun hubung pendek yang terjadi tidak total (artinya masih ada
                                                           resistans yang cukup besar pada titik gangguan), tetap sangat berbahaya, karena merupakan
                                                           sentuh langsung.
                                                           Karena itu pembumian pada sistem TT sangat diperlukan, supaya GPAS dapat trip pada kondisi
                                                           gangguan bumi.
                                                           Karena GPAS 30 mA diperbolehkan trip pada arus di atas 50 % arus operasi sisa nominalnya,
                                                           yaitu di atas 15 mA, maka resistans elektrode bumi maksimum RA = 50/0,015 Ω = 3333 Ω.
                                                           Batas atas GPAS 30 mA bekerja adalah 30 mA, maka resistans elektrode bumi maksimum RA
                                                           = 50/0,030 Ω = 1666 Ω.
                                                           Jadi resistans elektrode bumi maksimum untuk sistem TT adalah dalam julat 1666 – 3333 Ω.                                        Gambar - Contoh terminal pembumian
                                                           Angka yang paling aman adalah 1666 Ω.
                                                           Dari Tabel 54.2, resistans jenis tanah ρ yang paling tinggi adalah di tanah berbatu, yaitu 3000
                                                           Ω.m. Dari Tabel 54.3, dengan ρ = 3000 Ω.m dan elektrode bumi batang/pipa 1,5 m, didapat
                                                           resistans pembumian = 3000/100 x 55 Ω = 1650 Ω. (Angka 55 Ω adalah antara 40 Ω dan 70
                                                           Ω). Karena < 1666 Ω, maka aman.
                                                           Untuk jenis tanah yang lain, karena ρ < 3000 Ω.m dengan cara perhitungan di atas, akan
                                                           didapat resistans pembumian < 1650 Ω. Jadi lebih aman.
                                                     192      Persyaratan Umum Instalasi Listrik 2011                                                                                                                           Persyaratan Umum Instalasi Listrik 2011   193
                                                                                                                                                                      CATATAN 1
                                                           Contoh pemasangan konduktor pembumian dapat dilihat pada gambar berikut:                                   Klem pada elektrode pipa harus menggunakan baut dengan diameter minimal 10 mm.
                                                                                                                                                                      CATATAN 2
                                                                                                                                                                      Gawaihubungataufitingyanghanyatergantungpadasolder,tidakdapatdiandalkanuntukmemberikankuatmekanisyang
                                                                                                                                                                      memadai.
                                                                                                                                                                      542.3.3 Konduktor pembumian harus dilindungi jika menembus plafon atau dinding, atau
                                                                                                                                                                      berada di tempat dengan bahaya kerusakan mekanis.
                                                                                                                                                                      542.3.4 Konduktor pembumian harus diberi warna hijau-kuning sesuai dengan 5210.2.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                                      542.3.5 Pada konduktor pembumian harus dipasang hubungan yang dapat dilepas untuk
                                                                                                                                                                      keperluan pengujian resistans pembumian, pada tempat yang mudah dicapai, dan sedapat
                                                                                                                                                                      mungkin memanfaatkan hubungan yang karena susunan instalasinya memang harus ada.
                                                                  Gambar - Contoh terminal pembumian utama yang dipasang langsung dalam panel distribusi.             542.3.6 Hubungan dalam tanah harus dilindungi terhadap korosi.
                                                                                                                                                                          PENJELASAN
                                                     542.3.1 Konduktor pembumian harus memenuhi 543.1 dan jika ditanam dalam tanah, luas
                                                     penampangnya harus sesuai dengan Tabel 54.2.
                                                                                                                                                                           Bila tidak dilindungi terhadap korosi, maka luas penampang konduktor pembumian harus
                                                     Pada sistem TN, jika tidak tampak adanya arus gangguan yang diperkirakan melalui elektrode                            sesuai dengan Tabel 54.4, yaitu 25 mm2 tembaga atau 50 mm2 aluminium.
                                                     bumi, konduktor pembumian dapat didimensi menurut 544.1.1
Tabel 54.4 Luas penampang minimum konduktor pembumian yang ditanam dalam tanah 542.3.7 Konduktor pembumian di atas tanah harus memenuhi ketentuan sebagai berikut:
                                                                                                        Diproteksi secara mekanis   Tidak diproteksi secara mekanis   a) Mudah terlihat dan jika tertutup harus mudah dicapai;
                                                                                                                     2                              2                 b) Harus dilindungi dari bahaya mekanis atau kimiawi;
                                                      Diproteksi terhadap korosi                               2,5 mm Cu                      16 mm Cu
                                                                                                                     2
                                                                                                               10 mm Fe
                                                                                                                                                   2
                                                                                                                                              16 mm Fe                c) Tidak boleh ada sakelar atau hubungan yang mudah di lepas tanpa menggunakan
                                                                                                                                    2                                    perkakas;
                                                      Tidak diproteksi terhadap korosi                                         25 mm Cu
                                                                                                                               50 mm2 Fe
                                                                                                                                                                      d) Konduktor pembumian untuk kapasitor peredam interferens radio harus diinsulasi sama
                                                                                                                                                                         seperti konduktor fase dan harus dipasang dengan cara yang sama pula, jika arus yang
                                                                                                                                                                         dialirkan melebihi 3,5 mA.
                                                     542.3.2 Hubungan konduktor pembumian ke elektrode bumi harus dibuat dengan kuat dan
                                                     secara listrik memuaskan. Hubungan harus dengan pengelasan eksotermik, konektor tekan,
                                                     klem, atau konektor mekanis lain. Konektor mekanis harus dipasang sesuai dengan petunjuk
                                                     pabrikan. Jika klem digunakan, tidak boleh merusak elektrode atau konduktor pembumian.
                                                     194      Persyaratan Umum Instalasi Listrik 2011                                                                                                                                       Persyaratan Umum Instalasi Listrik 2011   195
                                                                                                                                                           543 Konduktor proteksi
                                                     542.3.8 Sambungan dan hubungan antara konduktor pembumian utama, konduktor                            543.1 Luas penampang minimum
                                                     pembumian, dan semua cabangnya satu sama lain harus dilaksanakan demikian sehingga
                                                     terjaminlah hubungan listrik yang baik, dapat diandalkan dan tahan lama.                              543.1.1 Luas penampang setiap konduktor proteksi harus memenuhi kondisi untuk
                                                                                                                                                           diskoneksi otomatis suplai yang disyaratkan dalam 411 Bagian 4-41 dan mampu menahan
                                                     CATATAN
                                                                                                                                                           arus gangguan prospektif.
                                                     Sambungan dan hubungan yang dibolehkan adalah sambungan dan hubungan yang menggunakan
                                                     las, baut, klem dan juga sambungan selongsong jika menggunakan konduktor pilin. Sambungan dan         Luas penampang konduktor proteksi harus dihitung sesuai dengan 543.1.2 atau dipilih sesuai
                                                     hubungan dengan baut harus dilindungi dari kemungkinan terjadinya korosi                              dengan Tabel 54.3. Pada kedua hal tersebut, persyaratan 543.1.3 harus diperhitungkan.
                                                     542.4.1 Pada setiap instalasi jika ikatan proteksi digunakan, suatu terminal pembumian
                                                     utama harus disediakan dan yang berikut harus dihubungkan padanya:                                        Ralat: Bukan Tabel 54.3 tapi Tabel 54.5.
                                                     196      Persyaratan Umum Instalasi Listrik 2011                                                                                                                      Persyaratan Umum Instalasi Listrik 2011   197
                                                     S adalah luas penampang, dalam mm2.                                                                   543.2 Jenis konduktor proteksi
                                                     I adalah nilai efektif arus gangguan propektif dalam ampere untuk gangguan dengan
                                                     impedans yang dapat diabaikan, yang dapat mengalir melalui gawai proteksi (lihat IEC                  543.2.1 Konduktor proteksi dapat terdiri atas salah satu satu lebih berikut ini:
                                                     60909-0);
                                                                                                                                                           -   konduktor pada kabel multiinti;
                                                     t adalah waktu operasi gawai proteksi untuk diskoneksi otomatis dalam detik;                          -   konduktor berinsulasi atau polos dalam selungkup bersama dengan konduktor aktif;
                                                                                                                                                           -   konduktor polos atau berinsulasi terpasang magun;
                                                     CATATAN 1                                                                                             -   selubung kabel logam, skrin kabel, perisai kabel, anyaman kawat, konduktor konsentris,
                                                     EfekpembatasanarusdariimpedanssirkitdanpembatasanI2tdarigawaiproteksiharusdiperhitungkan.                  konduit logam yang terkena kondisi yang dinyatakan dalam 543.2.2 a) dan b).
                                                     k adalah faktor yang tergantung pada bahan konduktor proteksi, insulasi dan bagian lain
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                           543.2.2 Jika instalasi terdiri atas perlengkapan yang mempunyai selungkup logam sedemikian
                                                     serta suhu awal dan akhir (untuk penghitungan k, lihat Lampiran 54.A).                                seperti rakitan PHBK voltase rendah atau sistem berumbung (trunking) rel, selungkup atau
                                                                                                                                                           rangka logam dapat digunakan sebagai konduktor proteksi jika secara simultan memenuhi
                                                     CATATAN 2                                                                                             tiga persyaratan berikut:
                                                     Untuk pembatasan suhu untuk instalasi berpotensi atmosfer ledak, lihat IEC 60079-0..
                                                                                                                                                           a) kontinuitas listriknya harus dipastikan dengan konstruksi atau dengan hubungan yang
                                                     CATATAN 3
                                                                                                                                                              sesuai sedemikian untuk memastikan proteksi terhadap pemburukan mekanis, kimia atau
                                                     Karena selubung logam kabel berinsulasi mineral menurut IEC 60702-1 mempunyai kapasitas gangguan         elektrokimia;
                                                     bumi lebih besar dari konduktor lin, maka tidak perlu menghitung luas penampang selubung logam jika   b) selungkup itu memenuhi persyaratan 543.1;
                                                     digunakan sebagai konduktor proteksi.                                                                 c) selungkup itu harus memungkinkan hubungan konduktor proteksi lain pada setiap titik
                                                                                                                                                              sadapan yang ditentukan sebelumnya.
                                                     543.1.3 Luas penampang setiap konduktor proteksi yang tidak membentuk bagian kabel
                                                     atau tidak pada selungkup yang sama dengan konduktor lin tidak boleh kurang dari:                     543.2.3 Bagian logam berikut tidak diizinkan untuk digunakan sebagai konduktor proteksi
                                                                                                                                                           atau sebagai konduktor ikatan proteksi:
                                                     - 2,5 mm2 Cu/16 mm2 Al jika disediakan proteksi terhadap kerusakan mekanis,
                                                     - 4 mm2 Cu/16 mm2 Al jika tidak disediakan proteksi terhadap kerusakan mekanis.                       -   pipa air logam;
                                                                                                                                                           -   pipa yang mengandung gas atau cairan yang mudah terbakar;
                                                     543.1.4 Jika konduktor proteksi digunakan bersama pada dua sirkit atau lebih, luas
                                                                                                                                                           -   bagian konstruksi yang terkena stres mekanis dalam pelayanan normal;
                                                     penampangnya harus didimensi sebagai berikut:                                                         -   konduit logam fleksibel atau mudah dibengkokkan, kecuali didesain untuk keperluan itu;
                                                                                                                                                           -   bagian logam fleksibel;
                                                     - dihitung menurut 543.1.1 untuk arus gangguan prospektif dan waktu operasi paling
                                                                                                                                                           -   kawat penyangga.
                                                        berat yang ditemui pada sirkit ini; atau
                                                     - dipilih menurut Tabel 54.3 sedemikian sehingga berkaitan dengan luas penampang
                                                        konduktor lin terbesar dari sirkit.
PENJELASAN
                                                     198     Persyaratan Umum Instalasi Listrik 2011                                                                                                                     Persyaratan Umum Instalasi Listrik 2011   199
                                                     Lampiran B (informatif)
                                                     Gambar susunan pembumian, konduktor proteksi dan konduktor ikatan
                                                     proteksi
Keterangan:
                                                                                                                                                         M          BKT
                                                                                                                                                                    bagian konduktif perlengkapan yang dapat disentuh dan yang secara normal tidak
                                                                                                                                                                    bervoltase, tetapi dapat menjadi bervoltase bila insulasi dasar gagal
                                                                                                                                                                    [IEV 195-06-10]
                                                                                                                                                         C          BKE
                                                                                                                                                                    bagian konduktif yang bukan merupakan bagian instalasi listrik dan dapat
                                                                                                                                                                    menimbulkan suatu potensial listrik, biasanya potensial listrik dari bumi lokal
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
[IEV 195-06-11]
C4 Pengondisi udara
C5 Sistem pemanas
                                                                                                                                                         T          Elektrode bumi
                                                                                                                                                                         bagian konduktif yang dapat ditanam dalam suatu media konduktif spesifik,
                                                                                                                                                         misalnya
                                                                                                                                                                    beton atau kokas, dalam kontak listrik dengan bumi
                                                                                                                                                                    [IEV 195-02-01]
                                                                   Gambar B.54.1 - Susunan pembumian, konduktor proteksi dan konduktor ikatan proteksi
                                                                                                                                                         T1     Bumi fondasi
                                                     200   Persyaratan Umum Instalasi Listrik 2011                                                                                                                    Persyaratan Umum Instalasi Listrik 2011   201
                                                     1         Konduktor proteksi
                                                                                                                                                   Bagian 5 - 55
                                                               konduktor yang disediakan untuk keperluan keselamatan, misalnya proteksi
                                                               terhadap kejut listrik
                                                               [IEV 195-02-09]
                                                     2         Konduktor ikatan proteksi
                                                               konduktor proteksi yang disediakan untuk ikatan ekuipotensial proteksi              Pemilihan dan
                                                     3
                                                               [IEV 195-02-10]
                                                               Konduktor ikatan proteksi untuk ikatan suplemen                                     pemasangan
                                                     4
                                                     5
                                                               Konduktor turun sistem proteksi petir (SPP)
                                                               Konduktor pembumian                                                                 perlengkapan listrik
                                                                                                                                                   - Perlengkapan Lain
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     CATATAN
                                                     Untuk PUIL, konduktor pembumian adalah konduktor yang menghubungkan elektrode bumi ke titik
                                                     sistem ikatan ekuipotensial bersama, biasanya terminal pembumian utama.
PENJELASAN
                                                           Gambar di atas hanya contoh tipikal saja. Dalam praktik disesuaikan dengan kondisi
                                                           instalasi setempat.
                                                     202     Persyaratan Umum Instalasi Listrik 2011                                                 Persyaratan Umum Instalasi Listrik 2011   203
                                                     551 Set pembangkit voltase rendah                                                                    559 Luminer dan instalasi pencahayaan
                                                     CATATAN
                                                     Isolasi sebaiknya mencakup suplai ke sirkit kendali generator.
PENJELASAN
                                                           Hal ini berarti set pembangkit hanya boleh dihubungkan ke instalasi melalui panel distribusi
                                                           pelanggan dengan memakai sistem yang dijelaskan di atas.
                                                                                                                                                                                            Gambar - Contoh luminer
                                                     204     Persyaratan Umum Instalasi Listrik 2011                                                                                                                  Persyaratan Umum Instalasi Listrik 2011   205
                                                     Persyaratan untuk jenis spesifik instalasi pencahayaan dicakup dalam berbagai bagian IEC 60364-7
                                                                                                                                                        PENJELASAN
                                                     (misalnya 7-713, 7-714 dan 7-715).
                                                     Persyaratan ayat ini tidak berlaku untuk pencahayaan hias temporer.
                                                                                                                                                        Untuk kabel berinsulasi PVC sesuai seri IEC60227 atau seri SNI 04-6629, suhu maksimum
                                                     CATATAN                                                                                            untuk kabel biasa adalah 70°C, sedangkan untuk jenis tahan panas (heat resistant) adalah
                                                     Persyaratan keselamatan untuk luminer dicakup dalam IEC 60598.                                     90°C.
                                                     559.4 Persyaratan umum untuk instalasi                                                             Untuk kabel berinsulasi karet sesuai seri IEC 60245, suhu maksimum untuk kabel biasa
                                                     Luminer harus dipilih dan dipasang sesuai dengan petunjuk pabrikan dan IEC 60598.                  (termasuk kabel lift) adalah 60°C, sedangkan untuk jenis tahan panas (heat resistant)
                                                                                                                                                        adalah 110°C, bahkan untuk kabel berinsulasi silikon tahan panas sesuai IEC 60245-3
                                                     559.6 Sistem perkawatan
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     559.6.1 Jika dipasang luminer gantung, lengkapan pemagun harus mampu menahan lima kali
                                                     massa luminer terhubung, tapi tidak kurang dari 25 kg. Kabel atau kabel senur antara gawai
                                                     gantung dan luminer harus dipasang sedemikian sehingga dihindari stres tarik dan torsi yang
                                                     berlebihan pada konduktor dan terminasi.
                                                     CATATAN
                                                     Lihat juga 522.8 Bagian 5-52.
                                                     559.6.2 Jika kabel dan/atau konduktor berinsulasi ditarik melalui luminer oleh instalatur
                                                     (perkawatan tembus - through-wiring), harus dipilih kabel dan/atau konduktor berinsulasi yang
                                                     sesuai seperti ditentukan dalam 559.6.3 dan harus digunakan hanya luminer yang sesuai untuk
                                                     perkawatan tembus.
                                                     559.6.3 Kabel harus dipilih sesuai dengan penandaan suhu pada luminer, sebagai berikut:
                                                     - untuk luminer yang memenuhi IEC 60598 tapi tanpa penandaan suhu, tidak disyaratkan
                                                        kabel tahan api;
                                                     - untuk luminer yang memenuhi IEC 60598 dengan penandaan suhu, harus digunakan
                                                        kabel yang sesuai untuk suhu yang ditandakan;
                                                     - untuk luminer tak ditandai untuk memenuhi IEC 60598, harus diikuti petunjuk pabrikan;
                                                     - jika tidak ada informasi, harus digunakan kabel dan/atau konduktor berinsulasi sesuai
                                                        dengan IEC 60245-3 atau tipe setara.
                                                     206    Persyaratan Umum Instalasi Listrik 2011                                                                                                              Persyaratan Umum Instalasi Listrik 2011   207
                                                                                                     Bagian 5 - 510
                                                                                                     Pemilihan dan
                                                                                                     pemasangan
                                                                                                     perlengkapan listrik
                                                                                                     - Perlengkapan
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
listrik
                                                     208   Persyaratan Umum Instalasi Listrik 2011     Persyaratan Umum Instalasi Listrik 2011   209
                                                     510.3 Armatur pencahayaan, fiting lampu, lampu dan roset
PENJELASAN
                                                           Yang dimaksud dengan armatur pencahayaan adalah luminer. Lihat 559 Luminer dan
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                             - Untuk tusuk kontak yang digunakan dalam industri: seri IEC 60309, Plugs, socket-outlets
                                                                                                                                             and
                                                                                                                                               couplers for industrial purposes.
PENJELASAN
Tusuk kontak harus memenuhi persyaratan standar sbb: Gambar - Contoh tusuk kontak yang digunakan dalam Industri
                                                     210    Persyaratan Umum Instalasi Listrik 2011                                                                                                          Persyaratan Umum Instalasi Listrik 2011   211
                                                     510.4.1 Konstruksi tusuk kontak                                                                                 510.4.1.6 Tusuk kontak untuk voltase instalasi listrik domestik tidak boleh dipakai untuk
                                                                                                                                                                     menjalankan dan mematikan mesin atau peranti portabel dengan daya lebih dari 2 kW
                                                     510.4.1.1 Tusuk kontak harus didesain sedemikian sehingga ketika dihubungkan tidak                              dan arus pengenal lebih dari 16 A.
                                                     mungkin terjadi sentuh tak sengaja dengan bagian aktif.
                                                     510.4.1.2.1 Tusuk kontak harus terbuat dari bahan yang tidak mudah terbakar, tahan lembab                           Untuk itu harus menggunakan tusuk kontak dan kotak kontak sesuai seri IEC 60309, Plugs,
                                                     dan secara mekanis cukup kuat.                                                                                      socket-outlets and couplers for industrial purposes.
                                                     510.4.1.2.2 Tusuk kontak yang tidak terlindung tidak boleh dibuat dari bahan yang mudah
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
pecah.
                                                     510.4.1.2.3 Sebagai pengecualian dari 510.4.1.2.1 di atas, tusuk kontak untuk kuat arus 16
                                                     A ke bawah pada voltase rumah, boleh terbuat dari bahan insulasi yang tahan terhadap
                                                     arus rambat.
                                                                                                                                                                                        Gambar - Contoh Tusuk Kontak dan Kotak Kontak untuk Industri
                                                     510.4.1.3 Sambungan antara tusuk kontak dan kabel fleksibel harus baik untuk
                                                     menghindari kerusakan mekanis.
                                                     510.4.1.4 Menghindari hubungan tusuk kontak tertukar                                                            510.4.2.4 Kotak kontak yang ditempatkan pada lantai harus tertutup dalam kotak lantai
                                                                                                                                                                     yang khusus diizinkan untuk penggunaan ini.
                                                     510.4.1.4.1 Dalam suatu instalasi, lubang kotak kontak dengan voltase pengenal
                                                     tertentu tidak boleh dapat dimasuki tusuk kontak dengan voltase pengenal yang lebih
                                                     rendah (lihat 414.4.3).
                                                     510.4.1.4.2 Lubang kotak kontak dengan arus pengenal tertentu tidak boleh dapat
                                                     dimasuki tusuk kontak dengan arus pengenal yang lebih besar, kecuali bagi kotak kontak
                                                     atau tusuk kontak dengan arus pengenal setinggi-tingginya 16 A.
                                                     CATATAN
                                                     Untuk menghindari kesalahan memasukkan tusuk kontak ke dalam lubang kotak kontak tidak semestinya, dianjurkan
                                                     agar:
                                                     a. Dalam satu instalasi hanya ada satu macam kotak kontak saja;
                                                     b. Kotak kontak dan tusuk kontak diberi tanda dengan menggunakan tulisan atau tanda lain yang
                                                         jelas, yang membedakan voltase/arus pengenal masing-masing;
                                                     c. Kotak dari tusuk kontak mempuny ai konstruksi yang berlainan sehingga lubang kotak kontak tidak
                                                         dapat dimasuki oleh tusuk kontak yang voltase/arus pengenalnya berlainan.
                                                     510.4.1.5 Pada kotak kontak dan tusuk kontak harus tercantum voltase tertinggi dan
                                                     arus terbesar yang diperbolehkan.
                                                     212    Persyaratan Umum Instalasi Listrik 2011                                                                                                                                    Persyaratan Umum Instalasi Listrik 2011   213
                                                           PENJELASAN                                                                           PENJELASAN
                                                           Lihat 510.4.4 dan PENJELASANNYA.                                                      Harus digunakan kotak kontak dengan kontak pembumian samping sesuai SNI 04-3892.1.1,
                                                                                                                                                 Tusuk-kontak dan kotak-kontak untuk keperluan rumah tangga dan sejenisnya – Bagian 1-1:
                                                                                                                                                 Persyaratan umum – Bentuk dan Ukuran.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
Gambar - Contoh tusuk kontak dan kotak kontak dengan pembumian samping
                                                                                  Gambar - Contoh kotak kontak untuk dipasang pada lantai       Untuk menghindari terjadinya beban lebih yang dapat menyebabkan panas dan kebakaran,
                                                                                                                                                maka pemasangan kotak kontak secara bertumpuk dengan menggunakan tusuk kontak
                                                           510.4.3 Penyambungan BKT perlengkapan listrik melalui tusuk kontak dan kotak         dan kotak kontak T sebaiknya dihindari. Kalau hal ini dilakukan karena keterbatasan
                                                                    kontak                                                                      kotak kontak dalam ruangan, maka sebaiknya digunakan kotak kontak portabel dengan
                                                           Contoh penyambungan BKT perlengkapan listrik melalui tusuk kontak dan kotak kontak   multikontak dengan pembumian samping.
                                                           dapat dilihat pada Gambar 510.4-1.
Gambar - Contoh tusuk kontak dan kotak kontak portabel dengan pembumian samping
                                                     214    Persyaratan Umum Instalasi Listrik 2011                                                                                                            Persyaratan Umum Instalasi Listrik 2011   215
                                                     510.4.4 Penempatan kotak kotak
                                                                                                                                                              PENJELASAN
                                                     Kotak kontak pasangan dinding di instalasi listrik domestik (rumah tangga) harus dipasang dengan
                                                     ketinggian sekurang-kurangnya 1,25 m dari lantai, kecuali kotak kontak dari jenis putar atau tutup.       Peranti kelas 0 adalah peranti dimana proteksi terhadap kejut listrik tergantung hanya
                                                                                                                                                               pada insulasi dasar, karena itu tidak ada sarana untuk hubungan bagian konduktif dapat
                                                                                                                                                               diakses, jika ada, ke konduktor proteksi pada perkawatan magun instalasi, ketika terjadi
                                                           PENJELASAN
                                                                                                                                                               kegagalan insulasi dasar tergantung pada lingkungan.
                                                           Karena itu kotak kontak yang dipasang di dinding kurang dari 1,25 m dari lantai harus dari          Peranti kelas 0I adalah peranti yang memopunyai sekutrang-kurangnya insulasi dasar
                                                           jenis putar (jenis shutter) atau jenis tutup dan kotak kontak yang ditanam pada lantai harus        menyeluruh dan dilengkapi terminal pembumian, tapi mempunyai kabel senur suplai
                                                           tertutup dalam kotak lantai yang dapat dibuka ketika akan digunakan. Lihat 510.4.2.4.               tanpa konduktor pemnbumian dan tusuk kontak tanpa kontak pembumian.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                           Pemanfaat listrik yang memakai penggerak elektromekanis hanya boleh dihubungkan dengan
                                                                                                                                                           sistem voltase rendah.
                                                                                          Gambar - Contoh kotak kontak jenis tutup                         Pemanfaat listrik yang tujuannya untuk dipakai oleh anak-anak harus disambung dengan voltase
                                                                                                                                                           rendah setinggi-tingginya 25 V.
PENJELASAN Sesuai IEC 60479-1, voltase rendah 25 V adalah voltase aman pada kondisi basah.
                                                           Peranti portabel sebaiknya merupakan peranti kelas I, yaitu peranti dimana proteksi
                                                           terhadap kejut listrik tidak tergantung hanya pada insulasi dasar, tapi mencakup
                                                           tindakan percegahan tambahan, dimana bagian konduktif dapat diakses dihubungkan ke
                                                           konduktor pembumian proteksi pada perkawatan magun instalasi, sedemikian sehingga
                                                           bagian konduktif dapat diakses tidak dapat menjadi bervoltase ketika terjadi kegagalan
                                                           insulasi dasar.
Jadi peranti portabel sebaiknya dilengkapi tusuk kontak dengan pembumian samping.
                                                           Hal di atas tidak berlaku untuk peranti portabel yang bodi atau selungkupnya bukan
                                                           merupakan BKT, yaitu misalnya terbuat dari bahan nonlogam. Dalam hal ini peranti
                                                           portabel boleh merupakan peranti kelas 0 atau 0I.
                                                     216     Persyaratan Umum Instalasi Listrik 2011                                                                                                                   Persyaratan Umum Instalasi Listrik 2011   217
                                                                                                     Bagian 5 - 511
                                                                                                     Pemilihan dan
                                                                                                     pemasangan
                                                                                                     perlengkapan listrik
                                                                                                     - Perlengkapan
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     218   Persyaratan Umum Instalasi Listrik 2011     Persyaratan Umum Instalasi Listrik 2011   219
                                                           PENJELASAN
                                                                                                                                                       Pemilihan PHBK didasarkan pada:
                                                                                                                                                       a. kemampuan dari berbagai komponen untuk melakukan fungsi dasar.
                                                           Perlengkapan Hubung Bagi dan Kendali (PHBK):
                                                           Perlengkapan listrik yang dimaksudkan untuk dihubungkan ke sirkit listrik untuk keperluan                                                               Kendali                                      Proteksi listrik
                                                           melaksanakan satu fungsi atau lebih berikut: proteksi, kendali, isolasi, penyakelaran                                Isolasi                                                Penyakelaran
                                                                                                                                                         Item PHBK                                                       Berhenti
                                                           switchgear and controlgear                                                                                                     Fungsional
                                                                                                                                                                                                       Penyakelaran
                                                                                                                                                                                                                          darurat
                                                                                                                                                                                                                                          untuk        Beban      Hubung           Kejut
                                                           Standar PHBK adalah seri IEC 601439 yang terdiri atas:                                        Isolator (atau
                                                                                                                                                                          (4)    Ya
                                                                                                                                                        diskonektor)
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                           - IEC 61439-1: General rules, sudah diterjemahkan menjadi SNI IEC 61439-1
                                                                                                                                                                    (5)
                                                                                                                                                                                 Ya          Ya                                            Ya
                                                                                                                                                                                                             (1)              (1)(2)
                                                                                                                                                           Sakelar                                        Ya                 Ya
                                                           - IEC 61439-2: Power switchgear and controlgear assemblies, sudah diterjemahkan                Gawai Sisa
                                                                                                                                                                                 Ya          Ya
                                                                                                                                                                                                             (1)              (1)(2)
                                                                                                                                                                                                                                           Ya                                       Ya
                                                                                                                                                                    (5)                                   Ya                 Ya
                                                              menjadi SNI IEC 61439-2                                                                      (RCBB)
                                                                                                                                                        Sirkuit breaker
                                                           a. Proteksi listrik terhadap:                                                                                                     Ya
                                                                                                                                                                                                             (1)              (1)(2)
                                                                                                                                                                                                                                           Ya           Ya           Ya
                                                                                                                                                           (pemutus                                       Ya                 Ya
                                                              1. Arus beban lebih                                                                            sirkit)
                                                              2. Arus hubung pendek                                                                     Sirkuit breaker
                                                                                                                                                                                 Ya          Ya                                            Ya           Ya           Ya
                                                                                                                                                                                                             (1)              (1)(2)
                                                     220     Persyaratan Umum Instalasi Listrik 2011                                                                                                                                        Persyaratan Umum Instalasi Listrik 2011          221
                                                           b. Besar arus yang akan mengalir masuk dan keluar di PHB tersebut:
                                                              1. Peringkat arus rel
                                                              2. Peringkat arus saluran masuk
                                                              3. Peringkat arus saluran keluar
                                                              4. Peringkat kemampuan rel dalam menahan arus hubungan singkat
                                                              2. Metode instalasinya
                                                              3. Jumlah muka operasinya
                                                              4. Peralatan ukur untuk proteksi
                                                              5. Bahan selungkupnya
                                                           Pemasangan:
                                                           a. Ruang PHBK harus sesuai gambar 511.2.1
                                                           b. Penataan PHBK:                                                                                                  Gambar 511.2-1 - Ruang pelayanan
                                                              1. harus ditata dan dipasang rapi dan teratur, dan ditempatkan dalam ruang
                                                                 yang cukup leluasa.sehingga pemeliharaan dan pelayanan mudah dan aman,         511.2.1.4 Penyambungan saluran masuk dan saluran keluar pada PHBK harus menggunakan
                                                                 dan bagian yang penting mudah dicapai                                          terminal sehingga penyambungannya dengan komponen dapat dilakukan dengan mudah, teratur
                                                              2. Semua instrumen ukur, tombol dan sakelar, harus dapat dilayani dengan          dan aman. Ketentuan ini tidak berlaku bila komponen tersebut letaknya dekat saluran keluar atau
                                                                 mudah dan aman dari depan tanpa bantuan tangga, meja atau perkakas             saluran masuk.
                                                                 yang tidak lazim lainnya.
                                                              3. PHBK tertutup pasangan luar harus dipasang di tempat yang cukup tinggi
                                                                 sehingga tidak akan terendam pada waktu banjir, dan juga harus cukup kuat          PENJELASAN
                                                              4. PHBK tertutup pasangan dalam yang ditempatkan dalam ruang khusus
                                                                 harus memenuhi ketentuan untuk ruang tersebut dalam Bagian 8.                      Penyambungan saluran masuk dan saluran keluar harus menggunakan terminal.
                                                              5. Lemari hubung bagi, kotak hubung bagi dan meja hubung bagi harus                   Penggunaan sambungan puntir dilarang.
                                                                 dipasang pada tempat yang sesuai, kering dan berventilasi cukup. Bila tidak,
                                                                 perlengkapan tersebut harus diamankan terhadap udara lembab
                                                                                                                                                511.2.5 Pengelompokan perlengkapan sirkit
                                                                                                                                                Pada PHBK yang mempunyai banyak sirkit keluar fase tunggal, dan fase tiga, baik untuk instalasi
                                                                                                                                                daya maupun instalasi pencahayaan, gawai proteksi, sakelar, dan terminal yang serupa harus
                                                                                                                                                dikelompokkan sehingga:
                                                                                                                                                a) kelompok perlengkapan instalasi daya sebaiknya terpisah dari kelompok perlengkapan
                                                                                                                                                    instalasi pencahayaan;
                                                                                                                                                b) kelompok perlengkapan fase tunggal, fase dua, dan fase tiga merupakan kelompok
                                                                                                                                                    sendiri sendiri yang terpisah.
                                                     222     Persyaratan Umum Instalasi Listrik 2011                                                                                                             Persyaratan Umum Instalasi Listrik 2011   223
                                                           PENJELASAN                                                                                       PENJELASAN
                                                           Pemisahan instalasi daya dan instalasi pencahayaan sebaiknya dilakukan, karena instalasi         Logam untuk rel (busbar) harus sama dengan logam konduktor atau gawai yang
                                                           pencahayaan tidak memerlukan kotak kontak, sedangkan instalasi daya harus memerlukan             tersambung padanya. Bila berbeda maka harus memakai bimetal (dwilogam).
                                                           kotak kontak, kecuali untuk peranti listrik yang dihubungkan langsung ke panel dengan MCB
                                                           sebagai gawai proteksinya.                                                                       Bila misalnya konduktor aluminium dihubungkan dengan rel tembaga dari PHBK
                                                                                                                                                            tanpa bimetal, akan terjadi korosi galvanik yaitu korosi yang terjadi pada dua logam
                                                                                                                                                            berbeda jenis jika dihubungkan.
                                                     CATATAN
                                                                                                                                                            Sesuai deret Volta, unsur logam dengan potensial elektrode lebih negatif
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     Lampu yang terhubung ke kotak kontak bukan merupakan instalasi pencahayaan, tapi merupakan pemanfaat
                                                     listrik untuk pencahayaan.                                                                             ditempatkan di bagian kiri, sedangkan unsur dengan potensial elektrode yang lebih
                                                                                                                                                            positif ditempatkan di bagian kanan.
                                                     511.6 Komponen yang dipasang pada PHBK
                                                                                                                                                            Semakin ke kiri kedudukan suatu logam dalam deret tersebut, maka:
                                                     511.6.1.3 Komponen yang dipasang pada PHBK harus memenuhi persyaratan standar yang                     a. Logam semakin reaktif (semakin mudah melepas elektron).
                                                     berlaku.
                                                                                                                                                            Sebaliknya, semakin ke kanan kedudukan suatu logam dalam deret tersebut, maka:
                                                                                                                                                            b. Logam semakin kurang reaktif (semakin sulit melepas elektron);
                                                           PENJELASAN
                                                                                                                                                            Deret Volta:
                                                           Contoh komponen:
                                                           - MCB untuk rumah tangga atau sejenis harus memenuhi seri IEC 60898.                             Li-K-Ba-Ca-Na-Mg-Al-Mn-Zn-Cr-Fe-Cd-Co-Ni-Sn-Pb-(H)-Cu-Hg-Ag-Pt-Au
                                                           - GPAS untuk rumah tangga atau sejenis harus memenuhi seri IEC 61008 (RCCB)
                                                              atau seri IEC 61009 (RCBO).                                                                   Pada kasus aluminium (Al) dan tembaga (Cu), karena letak Al di sebelah kiri Cu pada deret
                                                           - Sekering untuk industri maupun untuk rumah tangga atau sejenis harus                           Volta, maka Al akan lebih mudah melepas elektron dibandingkan Cu, jadi Al akan tergerus
                                                              memenuhi seri IEC 60269.                                                                      lebih dulu bila kedua logam tersebut kontak secara listrik.
                                                           - MCB untuk industri harus memenuhi seri IEC 60947-2.
                                                           - Kabel PVC harus memenuhi seri IEC 60227 atau seri SNI 04-6629.
                                                     511.6.3.1 Rel yang digunakan pada PHBK harus terbuat dari tembaga atau logam lain yang
                                                     memenuhi persyaratan sebagai konduktor listrik.
                                                     224      Persyaratan Umum Instalasi Listrik 2011                                                                                                                Persyaratan Umum Instalasi Listrik 2011   225
                                                                                                     Bagian 6
                                                                                                     Verifikasi
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     226   Persyaratan Umum Instalasi Listrik 2011     Persyaratan Umum Instalasi Listrik 2011   227
                                                                                                                                                        61 Verifikasi awal
                                                     apakah instalasi dan semua bagian perlengkapannya berada dalam kondisi yang memuaskan                   Kementerian Energi dan Sumber Daya Mineral. Setelah dinyatakan memenuhi syarat maka instalasi
                                                     untuk digunakan dan menentukan persyaratan untuk pelaporan hasil verifikasi periodik, sejauh            listrik dinyatakan laik operasi dan akan diterbitkan Sertifikat Laik Operasi, sehingga instalasi listrik dapat
                                                     dapat dipraktikkan dengan wajar.                                                                        dioperasikan.
                                                                                                                                                             Sesuai Lampiran VII Peraturan Menteri Energi dan Sumber Daya Mineral Republik Indonesia Nomor 05
                                                                                                                                                             tahun 2014 tentang Tata Cara Akreditasi dan Sertifikasi Ketenagalistrikan, Mata Uji Sertifikasi Instalasi
                                                                                                                                                             Pemanfaatan Tenaga Listrik Tegangan Rendah, maka mata uji yang harus dilakukan pada verifikasi
                                                                                                                                                             adalah sebagai berikut:
                                                     228   Persyaratan Umum Instalasi Listrik 2011                                                                                                                                      Persyaratan Umum Instalasi Listrik 2011   229
                                                                                                     61.3.1 Resistans insulasi instalasi listrik
                                                           Lampiran VII
                                                                                                     Resistans insulasi harus diukur antara konduktor aktif dan konduktor proteksi yang dihubungkan ke
                                                                                                     susunan pembumian. Untuk keperluan pengujian ini, konduktor aktif dapat dihubungkan bersama.
                                                                                                     Resistans insulasi, yang diukur dengan voltase uji yang tercantum dalam Tabel 6A adalah memenuhi
                                                                                                     bila setiap sirkit, dengan peranti didiskoneksi, mempunyai resistans insulasi tidak kurang dari nilai
                                                                                                     yang sesuai yang tercantum dalam Tabel 6A.
PENJELASAN
                                                                                                         Persyaratan resistans insulasi untuk voltase sirkit nominal sampai dengan 500 V, termasuk
                                                                                                         FELV, dinaikkan menjadi ≥ 1,0 MΩ dari sebelumnya ≥ 0,5 MΩ.
                                                     230   Persyaratan Umum Instalasi Listrik 2011                                                                      Persyaratan Umum Instalasi Listrik 2011   231
                                                     62 Verifikasi periodik
terdapat risiko yang lebih tinggi dan periode yang lebih singkat mungkin diperlukan;
                                                                                                                                                                  pemasangannya
                                                     - tempat atau lokasi kerja dimana terdapat risiko kejut listrik, kebakaran atau ledakan
                                                        karena degradasi;
                                                     - tempat atau lokasi kerja dimana terdapat instalasi voltase tinggi maupun voltase rendah;
                                                     - fasilitas umum;
                                                     - tempat konstruksi;
                                                     - instalasi keselamatan (misalnya luminer darurat)
                                                     Untuk rumah tinggal, periode lebih lama (misalnya 10 tahun) mungkin sesuai. Bila penghuni perumahan
                                                     telah berganti, verifikasi instalasi listrik sangat disarankan.
                                                     Hasil dan rekomendasi laporan terdahulu, bila dapat diperoleh, harus diperhatikan.
                                                     CATATAN 4
                                                     Bila tidak ada laporan terdahulu, maka diperlukan investigasi lebih lanjut.
PENJELASAN
                                                           Sesuai Pasal 22 Ayat (7) Peraturan Menteri Energi dan Sumber Daya Mineral Republik Indonesia
                                                           Nomor 05 tahun 2014 tentang Tata Cara Akreditasi dan Sertifikasi Ketenagalistrikan, Sertifikat Laik
                                                           Operasi instalasi pemanfaatan tenaga listrik tegangan rendah berlaku untuk jangka waktu 15 (lima
                                                           belas) tahun dan dapat diperpanjang.
                                                           Sesuai Pasal 22 Ayat (8) Peraturan Menteri Energi dan Sumber Daya Mineral Republik Indonesia
                                                           Nomor 05 tahun 2014 tentang Tata Cara Akreditasi dan Sertifikasi Ketenagalistrikan, Sertifikat Laik
                                                           Operasi instalasi pemanfaatan tenaga listrik tegangan rendah sebagaimana dimaksud pada ayat (5)
                                                           tidak berlaku apabila terdapat perubahan kapasitas, perubahan instalasi, atau direkondisi.
                                                           Jadi verifikasi periodik harus dilakukan setelah umur instalasi mencapai 15 tahun.
                                                           Bila instalasi diubah atau direkondisi sebelum 15 tahun, harus diverifikasi ulang sebelum dinyatakan
                                                           laik operasi.
                                                     232     Persyaratan Umum Instalasi Listrik 2011                                                                Persyaratan Umum Instalasi Listrik 2011   233
                                                           PENJELASAN
                                                           Bagian 7 merupakan revisi Bagian 7 PUIL 2000 dan bukan merupakan standar IEC. Karena itu
                                                           bila menggunakan persyaratan Bagian 7 harus diperhatikan persyaratan yang dicakup Bagian
                                                           5-52 PUIL 2011 (diadopsi dari IEC 60364-5-52), terutama bila akan menggunakan tabel KHA.
                                                           Bila ada pertentangan atau keragu-raguan harus digunakan angka dalam Bagian 5-52 PUIL
                                                           2011.
                                                     7.8.3 Konduit
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
7.8.3.1 Konduit harus memenuhi ketentuan dan persyaratan sesuai standar yang berlaku. Gambar - Contoh sistem konduit fleksibel
PENJELASAN
Konduit harus memenuhi persyaratan dalam seri IEC 61386 atau seri SNI IEC 61386 sbb:
                                                           IEC 61386-1, Conduit systems for cable management – Part 1: General requirements
                                                           IEC 1386-21, Conduit systems for cable management – Part 21: Particular requirements –Rigid
                                                           conduit systems
                                                           IEC 1386-22, Conduit systems for cable management – Part 22: Particular requirements –
                                                           Pliable conduit systems
                                                           IEC 1386-23, Conduit systems for cable management – Part 23: Particular requirements –
                                                           Flexible conduit systems
                                                           IEC 1386-24, Conduit systems for cable management – Part 24: Particular requirements –
                                                           Conduit systems buried underground
                                                                                                                                                                                   Gambar - Contoh sistem konduit ditanam bawah tanah
                                                                                                                                                         Konduktor aluminium harus dihubungkan dengan penjepit jenis khusus yang dibuat demikian rupa
                                                                                                                                                         sehingga tekanan pada konduktor dapat tersebar merata dan lapisan oksida dapat dihilangkan dari
                                                                                                                                                         permukaan konduktor.
                                                                                                                                                         Konduktor aluminium tidak boleh dihubungkan dengan terminal dari kuningan atau logam lain
                                                                                                                                                         berkadar tembaga tinggi, kecuali bila terminal itu telah diberi lapisan yang tepat atau telah diambil
                                                                                                                                                         tindakan lain untuk mencegah korosi.
                                                                                                  Gambar - Contoh sistem konduit kaku
                                                     234     Persyaratan Umum Instalasi Listrik 2011                                                                                                                            Persyaratan Umum Instalasi Listrik 2011   235
                                                           PENJELASAN                                                                                          PENJELASAN
                                                           Misalnya dengan menggunakan terminal dwilogam (bimetal).                                            Kabel NYM dalam standar IEC dicakup dalam seri IEC 60227 atau SNI 04-6629, “Kabel
                                                                                                                                                               berinsulasi PVC dengan voltase pengenal sampai dengan 450/750 V”. Dalam pedoman
                                                                                                                                                               penggunaannya, yang mengacu pada IEC 62440, Electric cables with a rated voltage not
                                                                                                                                                               exceeding 450/750 V – Guide to use, ditegaskan dalam Subayat 4.1 sbb: “Kabel tidak boleh
                                                                                                                                                               ditanam langsung dalam tanah, dan kecuali dinyatakan lain tidak boleh digunakan untuk
                                                                                                                                                               setiap keperluan selain daripada transmisi dan distribusi listrik”.
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
Dua konduktor atau lebih hanya boleh dihubungkan bersama pada satu terminal dengan menggunakan Gambar - Contoh kabel NYM
                                                     sepatu kabel, selosong atau alat hubung lain yang telah diizinkan, apabila terminal tersebut berbentuk
                                                     demikian rupa sehingga semua konduktor terjepit dengan baik, tanpa menyebabkan terpotongnya
                                                     kawat konduktor.
                                                     Jika terminal tersebut tidak cukup untuk dimasuki semua konduktor, maka harus digunakan terminal
                                                     majemuk dengan penjepit yang cukup untuk menjepit dengan baik semua konduktor tersebut.
                                                     7.12.2.1 Kabel instalasi berselubung yang tercantum dalam Tabel 7.1-3 boleh dipasang dengan
                                                     pertolongan penjepit langsung pada, di dalam, atau di bawah plesteran; atau dalam ruangan lembab.
                                                     Kabel instalasi tersebut boleh juga di pasang langsung pada bagian bangunan, konstruksi, rangka,
                                                     dan sebagainya, asalkan lapisan pelindungnya tidak menjadi rusak karena cara pemasangannya
                                                     (tergencet, sobek, dan sebagainya). Bila kabel jenis ini dipasang di dalam beton, harus digunakan
                                                     konduit yang memenuhi syarat.
                                                     CATATAN
                                                     Kabel instalasi jenis NYM bukanlah jenis kabel tanah, karena itu dalam keadaan bagaimanapun tidak boleh
                                                     ditanam di dalam tanah.
                                                     236     Persyaratan Umum Instalasi Listrik 2011                                                                                                                      Persyaratan Umum Instalasi Listrik 2011   237
                                                                                                     Bagian 8
                                                                                                     Ketentuan untuk
                                                                                                     berbagai ruang dan
                                                                                                     instalasi khusus
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                     238   Persyaratan Umum Instalasi Listrik 2011     Persyaratan Umum Instalasi Listrik 2011   239
                                                     8.1 Ruang lingkup
                                                     Untuk instalasi dalam ruang khusus dan instalasi listrik khusus berlaku juga ketentuan dalam bab         8.23.2    Klasifikasi zone
                                                     lain persyaratan ini, sepanjang dalam bab ini tidak ditetapkan lain.
                                                                                                                                                              Persyaratan ini didasarkan pada dimensi untuk empat zone (lihat contoh penentuan zone pada
                                                     Ruang khusus adalah ruang dengan sifat dan keadaan tertentu seperti ruang lembab, ruang berdebu,         Gambar 8.23-1 dan 8.23-2).
                                                     ruang dengan bahaya kebakaran dan ledakan, atau ruang yang memerlukan pengaturan lebih khusus
                                                     untuk instalasinya.                                                                                      Zone 0 merupakan bagian dalam dari bak rendam, bak mandi atau bak pancuran mandi.
                                                     Instalasi khusus adalah instalasi listrik dengan karakteristik tertentu sehingga penyelenggaraannya      Zone 1 dibatasi oleh bidang vertikal mengeliling bak rendam dan bak pancuran air, dan untuk
                                                     memerlukan ketentuan tersendiri, misalnya instalasi derek, instalasi lampu pencahayaan tanda dan         pancuran air tanpa bak , dan bak mandi, masing-masing merupakan bidang vertikal 0,60 m dari
                                                     bentuk, dan lain-lain.                                                                                   kepala pancuran dan dari pinggir bak mandi, dan oleh lantai serta bidang horisontal 2,25 m di atas
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                              lantai.
                                                     8.23         Instalasi listrik di dalam kamar mandi
                                                                                                                                                              Zone 2 dibatasi oleh bidang vertikal di luar zone 1 dan suatu bidang vertikal yang paralel dan berjarak
                                                     8.23.1       Umum                                                                                        0,60 m di luar Zone 2,
                                                     Persyaratan dalam pasal ini meliputi persyaratan untuk instalasi listrik yang dipasang di dalam kamar    Zone 3 dibatasi oleh bidang vertikal di luar Zone 2 dan sebuah bidang vertikal yang paralel dan
                                                     mandi, dimana dimungkinkan terdapat bak rendam (bath tub), pancuran air untuk mandi dan daerah di        berjarak 2,40 m di luar Zone 2, dan oleh lantai serta bidang paralel 2,25 m di atas lantai.
                                                     sekelilingnya, dimana terdapat bahaya terkena kejut listrik yang lebih tinggi disebabkan oleh turunnya
                                                     resistans tubuh manusia dan kontak tubuh dengan potensial bumi.
                                                                                                                                                                  PENJELASAN
                                                           PENJELASAN                                                                                             Di Indonesia di perumahan biasanya digunakan bak mandi, karena itu zonenya merupakan bentuk segi
                                                                                                                                                                  empat (bentuk yang terbanyak digunakan). Jaraknya dari bak mandi untuk zone 1 adalah 0,6 m. Jarak ini
                                                           Risiko mandi adalah:                                                                                   sudah memperhitungkan jarak air yang disiramkan ke tubuh dengan memakai gayung.
                                                     CATATAN                                                                                                      PENJELASAN
                                                     Khusus untuk lokasi kamar mandi untuk pelayanan kesehatan, mungkin perlu persyaratan khusus.
                                                                                                                                                                  Jadi walaupun memakai voltase ekstra rendah, misalnya 12 V (lihat 8.23.5), persyaratan ini tetap berlaku.
                                                     240      Persyaratan Umum Instalasi Listrik 2011                                                                                                                                     Persyaratan Umum Instalasi Listrik 2011   241
                                                     8.23.4 Ikatan ekuipotensial suplemen                                                                   8.23.6 Pemilihan dan pemasangan perlengkapan listrik
                                                     Ikatan ekuipotensial suplemen lokal harus menghubungkan semua bagian konduktif terbuka dalam           Perlengkapan listrik paling sedikit harus mempunyai tingkat proteksi sebagai berikut :
                                                     Zone 1, 2 dan 3 dengan konduktor proteksi pada BKT yang terdapat dalam semua zone.                     Zone 0 :           IPX7
                                                                                                                                                            Zone 1 :           IPX5
                                                                                                                                                            Zone 2 :           IPX4
                                                           PENJELASAN
                                                                                                                                                            Zone 3 :           IPX1
                                                                                                                                                            Khusus Zone 2 dan Zone 3 untuk kamar mandi dengan bak mandi dan yang digunakan untuk
                                                           BKT dalam zone 1, 2 atau 3 biasanya berupa pemanas air berselungkup logam, jadi harus memenuhi   pemandian umum harus menggunakan IPX5.
                                                           persyaratan ini. Bila ada, bodi atau selungkup logam sebaiknya dihindari.
                                                                                                                                                            8.23.7 Perkawatan
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                            Perkawatan yang dipasang di luar atau tertanam dalam dinding kurang dari 5 cm, harus dipasang
                                                                                                                                                            perkawatan yang sesuai tanpa menggunakan selubung logam (misalnya, dengan menggunakan pipa
                                                                                                                                                            dari bahan insulasi).
                                                                                                                                                            Untuk Zone 0, 1 dan 2, perkawatan diperbolehkan hanya untuk keperluan suplai perlengkapan yang
                                                                                                                                                            terdapat dalam zone tersebut.
PENJELASAN
                                                     Dalam Zone 0, dan juga dalam kamar mandi dengan bak mandi dalam Zone 1 dan Zone 2, hanya
                                                     diizinkan menerapkan proteksi dengan voltase ekstra rendah dengan voltase nominal tidak melebihi
                                                     12 V, dan sumber proteksi terpasang di luar zone tersebut.
                                                     Tindakan proteksi dengan memasang rintangan (lihat 3.4.3) dan menempatkan perlengkapan di luar
                                                     jangkauan (lihat 3.4.4) tidak diizinkan.
                                                     Tindakan proteksi dengan menempatkan perlengkapan pada lokasi nonkonduktif (lihat 3.9) dan ikatan
                                                     ekuipotensial bebas bumi (lihat 3.10) tidak diizinkan.                                                                    Gambar - Contoh sambungan kabel yang tidak memenuhi syarat
                                                     242     Persyaratan Umum Instalasi Listrik 2011                                                                                                                           Persyaratan Umum Instalasi Listrik 2011   243
                                                     8.23.8 Perlengkapan Hubung Bagi dan Kendali (PHBK)
                                                     a) Dalam Zone 0, 1 dan 2, dan juga dalam Zone 3 kamar mandi dengan bak mandi dan
                                                        pancuran, PHBK serta lengkapannya tidak boleh dipasang;
                                                     b) Dalam Zone 3, pemasangan kotak kontak hanya diizinkan jika:
                                                           1) setiap kotak kontak dilengkapi dengan transformator pemisah (lihat 3.11.2.1), atau
                                                           2) disuplai dengan voltase ekstra rendah (lihat 3.3.1), atau
                                                           3) diproteksi dengan GPAS dengan arus operasi sisa tidak melebihi 30 mA
                                                     c) Setiap sakelar dan kotak kontak harus berjarak minimum 0,60 m dari lubang pintu untuk
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
PENJELASAN
                                                           Pada kamar mandi di sebagian hotel, biasanya antara kamar mandi dan wastafel dipasang
                                                           dinding pemisah, dan di dekat wastafel dipasang kotak kontak. Walaupun demikian,
                                                           persyaratan di atas tetap berlaku. Karena pemasangan GPAS sudah merupakan persyaratan
                                                           wajib, maka persyaratan di atas otomatis sudah tercakup (lihat 41.3.3 dari Bagian 4-41).
Persyaratan berikut tidak berlaku untuk alat yang disuplai dengan voltase ekstra rendah.
                                                     Dalam Zone 0, hanya diizinkan untuk menggunakan perlengkapan listrik yang khusus diperuntukkan
                                                     untuk digunakan dalam bak rendam.
                                                                                                                                                      Gambar 8.23-1 - Klasifikasi zone dalam kamar mandi (tampak atas)
                                                     Dalam Zone 1, hanya diizinkan memasang pemanas air, kecuali dalam kamar mandi dengan bak
                                                     mandi.
                                                     Dalam Zone 2, hanya diizinkan memasang pemanas air dan lampu dengan Kelas II, kecuali dalam
                                                     kamar mandi dengan bak mandi.
                                                     244     Persyaratan Umum Instalasi Listrik 2011                                                                                                     Persyaratan Umum Instalasi Listrik 2011   245
                                                                                                                                                    PENJELASAN
                                                                                                                                                    Gambar ini sudah direvisi sesuai SNI IEC 60364-7-701 sebagai berikut :
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
                                                                                                                                                                Gambar 701.1 - Dimensi zona dalam lokasi berisi bak mandi rendam atau dus
                                                                                                                                                                                              dengan basin
                                                     246   Persyaratan Umum Instalasi Listrik 2011                                                                                                                   Persyaratan Umum Instalasi Listrik 2011   247
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
Gambar 701.2 - Dimensi zona 0 dan 1 dalam lokasi berisi dua tanpa basin
                                                     248   Persyaratan Umum Instalasi Listrik 2011                                                                                               Persyaratan Umum Instalasi Listrik 2011   249
Tidakdiperkenankanuntukdicetakataudiperjualbelikan
Tidakdiperkenankanuntukdicetakataudiperjualbelikan