Digital Controller: User's Manual
Digital Controller: User's Manual
Digital Controller
User's Manual
1 East Commerce Drive, Schaumburg, IL 60173
U.S.A.
Tel: (1)847-843-7900/Fax: (1)847-843-8568
OMRON ASIA PACIFIC PTE. LTD.
83 Clemenceau Avenue,
#11-01, UE Square,
239920 Singapore
Tel: (65)6835-3011/Fax: (65)6835-2711
OMRON CHINA CO., LTD. BEIJING OFFICE
Room 1028, Office Building,
Cat. No. H083-E1-02A
Preface
Thank you for your purchase of your E5AK, intelligent digital controller.
The E5AK allows the user to carry out the following:
· Select from many types of temperature and analog input (multiple input)
· Support position-proportional control (position-proportional type controllers only).
· Select output functions such as control output or alarm (output assignment)
· Use the HBA (heater burnout alarm) function (standard type controllers only).
· Use four setpoints (multi-SP function)
· Use remote SP input.
· Monitor the control loop by LBA (Loop Break Alarm)
· Use the communications function
· Calibrate input or transfer output
· It also features a watertight construction (NEMA4: equivalent to IP66)
This User’s Manual describes how to use the E5AK compact, high-function digital con-
troller.
Before using your E5AK, thoroughly read and understand this manual in order to
ensure correct use.
E OMRON, 1996
(1) All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,
in any form, or by any means, mechanical, electronic, photocopying, recording, recording, or otherwise, without
the prior written permission of OMRON.
(2) No patent liability is assumed with respect to the use of the information contained herein.
(3) Moreover, because OMRON is constantly striving to improve its high-quality products, the information in this
manual is subject to change without notice. Every precaution has been taken in the preparation of this manual.
Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for
damages resulting from the use of the information contained in this publication.
I
E5AK
J Meanings of Abbreviations
Sometimes the following abbreviations are used in parameter names, figures and in text
explanations. These abbreviations mean the following.
Abbreviation Term
PV Process value
SP Set point
RSP Remote set point
LSP Local set point
LBA Loop break alarm
HB Heater burnout
AT Auto-tuning
ST Self-tuning
A B C D E F G H I J K L M
N O P Q R S T U VW X Y Z
J “Reference” mark
This mark indicates that extra, useful information follows, such as supplementary explanations
and how to apply functions.
II
E5AK
J Notice:
OMRON products are manufactured for use according to proper procedures by a qualified opera-
tor and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always
heed the information provided with them. Failure to heed precautions can result in injury to
people or damage to the product.
! DANGER Indicates information that, if not heeded, is likely to result in loss of life
or serious injury.
! WARNING Indicates information that, if not heeded, could possibly result in loss
of life or serious injury.
! Caution Indicates information that, if not heeded, could result in relatively seri-
ous or minor injury, damage to the product, or faulty operation.
III
E5AK
D Setting up the E5AK Chapter 2 Preparations This chapter describes the opera-
tions that you must carry out
(e.g. installation, wiring and
switch settings) before you can
use the E5AK.
D Basic E5AK operations Chapter 3 Basic Operation These chapters describe how to
Chapter 5 Parameters use the front panel keys and how
to view the display when setting
the parameters of the major func-
tions for the E5AK.
D Applied E5AK operations Chapter 4 Applied Operation These chapters describe the
Chapter 5 Parameters important functions of the E5AK
and how to use the parameters
for making full use of the E5AK.
D Using a Position-propor- Chapter 4 Applied Opera- This chapter describes the func-
tion/4.1 Selecting the Control tions related specifically to posi-
tional Type Controller Method tion-proportional type control-
lers.
D Communications with a Chapter 6 Using the Commu- This chapter mainly describes
nications Function the communications commands,
host computer and gives program examples.
IV
E5AK
V
Table of Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I
Conventions Used in This Manual . . . . . . . . . . . . . . . II
Pay Attention to the Following when Installing
this Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
CHAPTER 1 INTRODUCTION
CHAPTER 1 1
INTRODUCTION
This chapter introduces the E5AK. First-time users should read this
chapter without fail.
For details on how to use the controller and parameter settings, see
Chapters 2 onwards.
1--1
E5AK
CHAPTER 1 INTRODUCTION
J Main parts
Terminals
P 2-8
Rear case
Front panel
This page
J Front panel
SV
Operation indicators
No.2 display
OUT1 OUT2 RMT RSP MANU SUB1 SUB2
SUB1 SUB2 OUT1 OUT2 STOP AT
MANU
STOP
RMT
RST
AT
E5AK
1--2
E5AK
F No.2 display Displays the set point, manipulated variable or parameter settings.
F Operation indica- · OUT1 : Lits when the pulse output function assigned to “control
tors output 1” is ON.
· OUT2 : Lits when the pulse output function assigned to “control
output 2” is ON.
· SUB1 : Lits when the output function assigned to “auxiliary output
1” is ON.
· SUB2 : Lits when the output function assigned to “auxiliary
output 2” is ON.
· MANU : Lits in the manual operation mode.
· STOP : Lits when operation has stopped.
· RMT : Lits during remote operation.
· RSP : Lits during remote SP operation.
· AT : Flashes during auto-tuning.
F Bar graph On a standard type controller (E5AK-AA2), this bar graph indicates the
manipulated variable (heat) in 10% increments per single segment. On a
position-proportional type controller (E5AK-PRR2), this bar graph indi-
cates the valve opening in 10% increments per single segment.
F A/M key Each press of this key switches between the auto and manual operations.
F key The functions of this key change according to how long it is pressed. If the
key is pressed for less than one second, the parameters are switched. If the
key is pressed for one second or more, the menu display appears. In key
operations from here on, “press the key” refers to pressing the key for less
than one second.
For details on parameter switching and menu display items, see page 1-8.
F key Each press of the key increments or advances the values or settings
on the No.2 display, while each press of the key decrements or returns
the values or settings on the No.2 display.
Functions vary, for example, when the A/M key is held down simulta-
neously with the display key, or a key is held down continuously. For
details, see page 1-8. Also, chapters 3 and 4 describe examples using vari-
ous key combinations.
1--3
E5AK
CHAPTER 1 INTRODUCTION
Alarm 3
LBA
Error 2
Error 3
J Input The E5AK supports following inputs: temperature input, current input,
voltage input, CT input/Potentiometer, remote SP input and event input.
F CT input/Poten- · Connect CT input when using the HBA (heater burnout alarm) function
tiometer on a standard type controller (E5AK-AA2).
· Connect the potentiometer when monitoring the valve opening on a
position-proportional type controller (E5AK-PRR2).
F Remote SP input When the remote SP function is enabled, inputs within the range 4 to 20
mA are used as the remote SP.
1--4
E5AK
F Event input When using event input, add on the input unit (E53-CKB).
You can select from the following five event inputs:
Multi-SP
Run/Stop
Remote/Local
Auto/Manual
SP mode
J Output
The E5AK supports the following five outputs.
Control output 1
Control output 2
Auxiliary output 1
Auxiliary output2
Transfer output
When using control outputs 1 and 2, set the output unit (sold separately).
Nine output units are available to suit the output circuit configuration.
When using transfer output, add on the communication unit (E53-AKF).
Note: The output functions of the E5AK do not operate for five seconds af-
ter the E5AK is turned ON.
F Output assign- The E5AK supports the following ten output functions.
ments Control output (heat)
Control output (cool)
Alarms 1 to 3
HBA
LBA
Error 1 (input error)
Error 2 (A/D converter error)
Error 3 (RSP input error)
Assign these output functions to control output 1, control output 2, auxil-
iary output1, and auxiliary output2.
However, note that as control output 1 is used as the open output and con-
trol output 2 is used as close output on a position-proportional type con-
troller (E5AK-PRR2), control outputs 1 and 2 cannot be used as assign-
ment destinations. Also, of the output functions, control output (heat),
control output (cool), HBA and LBA are disabled.
On a standard type controller, there are restrictions on how assignment
destinations (control output 1, control output2, auxiliary output1, and
auxiliary output2) can be used. For details, see 3.3 Setting Output Specifi-
cations.
In the example on the previous page, “control output (heat)” is assigned
to “control output 1”, “alarm 1” is assigned to “control output 2”, and
“alarm 2” is assigned to “auxiliary output 1”. Accordingly, the configura-
tion is such that heating control output is connected to control output 1,
and alarm output is connected to control output 2 and auxiliary output 1.
1--5
E5AK
CHAPTER 1 INTRODUCTION
Control Output 1/
Control Method Model
Control Output 2
Standard control E5AK-AA2 AC100-240 Control output (heat) /
E5AK-AA2 AC/DC24 Alarm, etc.,
Heating and cooling E5AK-AA2 AC100-240 Control output (heat) /
control E5AK-AA2 AC/DC24 Control output (cool)
Position-proportional E5AK-PRR2 AC100-240 Open/Close
control E5AK-PRR2 AC/DC24
F Transfer output The E5AK supports the following six transfer outputs.
Set point
Set point during SP ramp
Process value
Heating side manipulated variable
Cooling side manipulated variable
Valve opening
However, note that heating/cooling side manipulated variables can be out-
put only standard type controllers, and valve opening can be output on
position-proportional type controllers
These transfer outputs can be output after being scaled. Setting of an
upper limit value smaller than the lower limit value is allowed, so reverse
scaling can also be carried out.
1--6
E5AK
J Parameter types E5AK parameters are distributed between the following nine modes.
Protect mode
Manual mode
Level 0 mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
The settings of parameters in each of seven modes (excluding the protect
mode and manual mode) can be checked and modified by selection on the
menu display.
F Protect mode This mode is used to limit use of the menu and A/M keys. The protect func-
tion is for preventing unwanted modification of parameters and switching
between the auto and manual operation.
F Manual mode In this mode, the controller can be switched manual operation. The
manipulated variable can be manipulated manually only in this mode.
F Level 0 mode Set the controller to this mode during normal operation. In this mode, you
may change the set point during operation, and stop and start operation.
You can also monitor (not change) the process value, ramp SP and manip-
ulated variable.
F Level 1 mode This is the main mode for adjusting control. In this mode, you can execute
AT (auto-tuning), and set alarm values, the control period and PID param-
eters.
F Level 2 mode This is the auxiliary mode for adjusting control. In this mode, you can set
the parameters for limiting the manipulated variable, switch between the
remote and local modes, switch between the SP modes, and set the loop
break alarm (LBA), alarm hysteresis and the digital filter value of inputs.
F Setup mode This is the mode for setting the basic specifications. In this mode, you can
set parameters that must be checked or set before operation such as the
input type, scaling, output assignments and direct/reverse operation.
F Expansion mode This is the mode for setting expanded functions. In this mode, you can set
ST (self-tuning), SP setting limiter, selection of advanced PID or ON/OFF
control, specification of the standby sequence resetting method, time for
automatic return to the monitoring display.
F Option mode This is the mode for setting option functions. You can select this mode only
when the option unit is set in the controller. In this mode, you can set the
communications conditions, transfer output and event input parameters
1--7
E5AK
CHAPTER 1 INTRODUCTION
to match the type of option unit set in the controller. Heater burnout latch
function, position-proportional travel time and remote SP scaling param-
eters are also located in this mode.
F Calibration mode This mode is provided so that the user can calibrate inputs and transfer
output.
When calibrating input, the selected input type is calibrated. Whereas,
transfer output can be calibrated only when the communications unit
(E53-AKF) is set in the controller.
J Selecting modes The following diagram shows the order in which modes are selected.
Power ON
A/M
1 second min. 1 second min.
1 second min.
Level 2 mode A/M + A/M +
1 second min. 1 second min.
1 second min.
Setup mode
Protect mode
1 second min.
Expansion mode A/M +
1 second min.
1 second min.
Option mode
1 second min.
Calibration mode
F Menu display · To select the menu display in any of the above modes (excluding the pro-
tect mode and manual mode), press the key for 1 second minimum.
If you select the desired mode using the or keys and press the
key, the top parameter in the specified mode is displayed.
· When you have selected the menu display, the previous mode is selected.
For example, if you selected the menu display while in the level 0 mode,
the No.2 display changes to [ ] as shown on the left.
· Protected modes cannot be selected. Also, the menu display does not
appear when modes are protected up to the level 1 mode.
1--8
E5AK
F Protect mode · To set the controller to the protect mode or to return to the level 0 mode
from the protect mode, press the A/M key and key for 1 second mini-
mun simultaneously.
F Manual mode · To set the controller to the manual mode, press the A/M key for 1 second
minimun in the level 0 to 2 mode. To return to the level 0 mode from the
manual mode, press the A/M key for 1 second minimum.
J Selecting · When not in the manual mode, each press of the key switches the
parameter.
parameters
· If you press the key when at the final parameter, the display returns
to the first parameter.
J Fixing settings · When you have changed a parameter setting, specify the parameter
using the or keys, and either leave the setting for at least two
seconds or press the key. This fixes the setting.
· When another mode is selected, the content of the parameters before the
mode was selected is fixed.
· When turning the power OFF, you must first fix the settings and param-
eter contents (by pressing the key or selecting another mode). The
settings and parameter contents are sometimes not changed by merely
pressing the or keys.
1--9
E5AK
CHAPTER 1 INTRODUCTION
F RS-232C When using the communications function on the RS-232C interface, add
on the communications unit (E53-AK01).
F RS-422 When using the communications function on the RS-422 interface, add on
the communications unit (E53-AK02).
F RS-485 When using the communications function on the RS-485 interface, add on
the communications unit (E53-AK03).
1--10
E5AK
The E5AK controller is calibrated before shipment from the factory. So,
the user need not calibrate the E5AK controller during regular use.
However, if the E5AK controller must be calibrated by the user, use the
parameters provided for user to calibrate temperature input, analog input
(voltage, current) and transfer output.
Also, note that calibration data is updated to the latest value each time the
E5AK controller is calibrated. Calibration data set before shipment from
the factory cannot be returned to after calibration by the user.
F Calibrating The input type selected in the parameter is the item to be calibrated. The
inputs E5AK is provided with the following four calibration parameters.
· Thermocouple
· Platinum resistance thermometer
· Current input
· Voltage input
Two parameters are provided for thermocouple and voltage input.
F Calibrating trans- Transfer output can be calibrated when the communications unit
fer output (E53-AKF) is added on.
F Registering cal- When calibrating each item, the calibration data is temporarily regis-
ibration data tered. This data can be registered as final calibration data only when all
items have been newly calibrated. So, all items must be temporarily regis-
tered when calibrating the E5AK controller.
When registering data, information regarding whether or not calibration
has been carried out is also registered.
1--11
E5AK
CHAPTER 1 INTRODUCTION
1--12
E5AK
CHAPTER 2 PREPARATIONS
CHAPTER 2 2
PREPARATIONS
This chapter describes the operations you should carry out before turn-
ing the E5AK ON.
2--1
E5AK
CHAPTER 2 PREPARATIONS
2.1 Setting up
· On a standard type controller, set up the output units for control outputs
1 and 2 before mounting the controller.
· On a position-proportional type controller, the relay output unit is
already set. So, this setup operation unnecessary. (Do not replace with
other output units.)
· When setting up the output units, draw out the internal mechanism
from the housing and insert the output units into the sockets for control
outputs 1 and 2.
J Draw-out When drawing out the internal mechanism from the housing, prepare a
phillips screwdriver matched to the size of the screw on the lower part of
the front panel.
(1) Press down on the hook on the top of the front panel and turn the phil-
lips screwdriver to the left to loosen the screw on the lower part of the
front panel.
(2) Draw out the internal mechanism towards you holding both sides of
the front panel.
Fixing Screw for Tighten this screw by a torque of 0.3 to 0.5 N×m, or approx. 3 to 5 kgf×cm.
Front Panel
2--2
E5AK
2.1 Setting up
F Before setup · Check the type of the output unit you are about to set up.
· For details on types of output unit and main specifications, see page 2-9.
F Procedure (1) Check the positions of the sockets you are about to insert the output
units into as shown in the following diagram.
OUT1
OUT2
Bracket
(2) Insert the output unit for control output 1 into the socket “OUT1”
and the output unit for control output 2 into the socket “OUT2”.
(3) Fasten the output units with the bracket (accessory).
2--3
E5AK
CHAPTER 2 PREPARATIONS
F Before setup · Check the type of the option unit you are about to set up.
· For details on types of option unit and main specifications, see Appendix,
Model List (page A-11) and Appendix, Option Unit Ratings and Charac-
teristics (page A-4).
· For details on the relationship between units and terminals, see page
2-8.
F Procedure (1) Remove the power board and option boards in the order shown in the
following diagram.
(2) Insert the option units into the sockets for options 1 to 3. The follow-
ing diagram shows the relationship between option units and mount-
ing positions.
Option 1
E53--AKB: Event inputs 1/2
E53--AK01: RS--232C
E53--AK02: RS--422
Option 2 E53--AK03: RS--485
E53--AKF: Transfer output
Option 3
E53--AKB: Event inputs 3/4
(3) Mount the option boards and the power board in the order shown.
2--4
E5AK
2.2 Installation
2.2 Installation
J Dimensions
96j 13.5 100
PV
SV
112
91
RMT RSP MANU SUB1 SUB2
E5AK
J Panel cutout
110 mm min
Unit (mm)
2--5
E5AK
CHAPTER 2 PREPARATIONS
J Mounting (1) Insert the E5AK controller into the mounting hole in the panel.
(2) Fit the mounting bracket (accessory) into the fixing slots on the top
and bottom of the rear case.
2--6
E5AK
2.2 Installation
E5AK
E53-COV0809
· To remove the terminal covers, pull the edges of the snap pins.
2--7
E5AK
CHAPTER 2 PREPARATIONS
J Terminal arrangement
AC100-240V ~
(AC/DC24V ) EV1/2
10 RS232C
TRSF 30 31 32 20 RS422
SOURCE
9 29 19 RS485
8 28 18
OUT1
7 27 17
CT
6 26 16 PTMR
OUT2
5 EV3/4 25 15
4 24 14
SUB1 TC
3 23 13 Pt
2 12 I
SUB2 RSP 22
V
1 21 33 11
J Precautions · Use ducts to separate input leads and power lines in order to protect the
when wiring controller and its lines from external noise.
· We recommend using solderless terminals when wiring the controller.
· Tighten the terminal screws using a torque no greater than 0.78 N·m,
or 8 kgf·cm max. Take care not to tighten the terminal screws too tightly.
· Use the following type of solderless terminals for M3.5 screws.
7.2mm max.
7.2mm max.
J Wiring In the following wiring diagrams, the left side of the terminal Nos. indi-
cates the inside of the controller
F Power supply · Input power to terminal Nos. 9 and 10. Power specifications are as follows:
AC100-240V , 50/60Hz, 16VA
10 30 31 32 20
9 29 19 (AC/DC24V , 50/60Hz, 12VA, 8W)
8 28 18
7 27 17
6 26 16
5 25 15
4 24 14
3 23 13
2 22 12
1 21 33 11
2--8
E5AK
F Sensor input · Connect the sensor input to terminal Nos. 11 to 14 and 33 as follows
according to the input type.
10 30 31 32 20
9 29 19 +
14 14 14 14
8 28 18
13 13 13 V 13
7 27 17 --
6 26 16 12 12 12 12 --
--
5 25 15 11 11 11 11 mA
+
4 24 14 33 33 33 33 +
3 23 13 Thermocouple Platinum Voltage input Current input
resistance
2 22 12 thermometer
1 21 33 11
F Control output · Terminal Nos. 7 and 8 are for control output 1 (OUT1), and terminal Nos.
5 and 6 are for control output 2 (OUT2). The following diagrams show the
10 30 31 32 20
available output units and their internal equalizing circuits.
9 29 19
8 28 18
7 27 17
6 26 16
5 25 15
4 24 14
3 23 13
2 22 12
1 21 33 11
· With E53-VVV output units, about 2 V is output for one second after the
power is interrupted.
· The following table shows the specifications for each output unit.
Model Output Type Specifications
E53-R Relay 250 VAC, 5 A
E53-S SSR 75 to 250 VAC, 1 A
E53-Q Voltage (NPN) NPN : 12 VDC, 40 mA (with short-circuit protection)
E53-Q3 Voltage (NPN) NPN : 24 VDC, 20 mA (with short-circuit protection)
E53-Q4 Voltage (PNP) PNP : 24 VDC, 20 mA (with short-circuit protection)
E53-C3 4 to 20 mA 4 to 20 mA, Permissible load impedance: 600 W max., Resolution: Approx. 2600
E53-C3D 0 to 20 mA 0 to 20 mA, Permissible load impedance: 600 W max., Resolution: Approx. 2600
E53-V34 0 to 10 V 0 to 10 VDC, Permissible load impedance: 1 kW min., Resolution: Approx. 2600
E53-V35 0 to 5 V 0 to 5 VDC, Permissible load impedance: 1 kW min., Resolution: Approx. 2600
8 6
7 5
Open Close
2--9
E5AK
CHAPTER 2 PREPARATIONS
F Auxiliary output · Terminal Nos.3 and 4 are for auxiliary output 1 (SUB1) and terminal
10 30 31 32 20
Nos.1 and 2 are for auxiliary output 2 (SUB2).
9 29 19 · The internal equalizing circuits for the auxiliary outputs are as follows:
8 28 18
4 2
7 27 17
6 26 16
5 25 15 3 1
4 24 14 Auxiliary Auxiliary
3 23 13 output 1 output 2
2 22 12
· Output specifications are as follows:
1 21 33 11
SPST-NO, AC250V, 3A
F CT input/ · When using the HBA function on the E5AK-AA2 controller, connect CT
Potentiometer input (CT) to terminal Nos.15 to 17. When monitoring the valve opening
on the E5AK-PRR2 controller, connect the potentiometer (PTMR) to
10 30 31 32 20
terminal Nos.15 to 17. Connect each of these inputs as follows:
9 29 19
8 28 18 O
17 17
7 27 17 W
16 CT 16
6 26 16 C
5 25 15 15 15
4 24 14 CT input Potentiometer
3 23 13
2 22 12 · For details on CT inputs, see Appendix, About Current transformer.
1 21 33 11 · For details on the potentiometer, see the Instruction Manual for the
valve connected to the controller. The variable resistance range is 100
W to 2.5 kW.
F Remote SP input · Connect an input (RSP) to be used as the remote SP to terminal Nos.21
10 30 31 32 20 and 22.
9 29 19 · Only 4 to 20 mA inputs can be connected. Connect the input as follows:
8 28 18 +
22
7 27 17
6 26 16 4 to 20 mA
5 25 15 21
--
4 24 14
3 23 13
2 22 12
1 21 33 11
About the power The E5AK has independent power supplies for A B C
blocks each of the terminal blocks shown on the right.
10 30 31 32 20
9 29 19
8 28 18
B 7 27 17
6 26 16
5 C 25 15
4 24 14
E 3 23 13
2 22 12
1 21 33 11
F D
2--10
E5AK
F Event input · Connect event inputs 1 and 2 (EV1/2) to terminal Nos.18 to 20, and event
10 30 31 32 20
events 3 and 4 (EV3/4) to terminal Nos.24 to 26. However, note that ter-
9 29 19 minal Nos.18 to 20 cannot be used on controllers having a communica-
8 28 18 tions function.
7 27 17 · Connect the event inputs as follows:
6 26 16 + +
5 25 15 EV1 20 EV3 26
+ +
4 24 14 EV2 19 EV4 25
3 23 13 COM 18 -- COM 24 --
2 22 12
Event input 1 and 2 Event input 3 and 4
1 21 33 11
Terminals 18 and 24 (COM) are connected internally.
· Use event inputs under the following conditions:
COM 18 COM 24
-- --
Event input 1 and 2 Event input 3 and 4
F Transfer output · Connect transfer output (TRSF) to terminal Nos. 29 and 30.
· The internal equalizing circuit for transfer output is as follows:
+
30
4 to 20mA L
29
--
F Communications · Terminal Nos.18 to 20, 31 and 32 can be used only on controllers having
a communications units (E53-AK01/02/03).
· For details on wiring, see Chapter 6, Using the Communications Func-
tion.
2--11
E5AK
CHAPTER 2 PREPARATIONS
2--12
E5AK
CHAPTER 3 3
BASIC OPERATION
This chapter describes an actual example for understanding the basic
operation of the E5AK.
3--1
E5AK
F Basic Operation The following diagram shows the basic operation flow.
Flow Power ON
Setup
Setting input specifications
Protecting parameters
Operation
Start
Adjustment
Stop
Power OFF
3--2
E5AK
F Setup This description assumes that the controller is operated under the follow-
ing conditions.
· A humidity sensor of output 4 to 20 mA is connected to the controller.
The measuring range of the humidity sensor is set to 10 to 95%.
· A humidifier is controlled by pulse output to maintain humidity at a
constant 60%.
· An alarm is output when the humidity exceeds the upper limit value
(70%) or lower limit value (50%).
· Output unit: relay type (E53-R) for OUT1.
Humidity sensor
Humidifier
Control target
AC100-240V ~
(AC/DC24V )
SOURCE 10 30 31 32 20
9 29 19
OUT1 8 28 18
7 27 17
6 26 16
5 25 15
SUB1 4 24 14
Alarm 1
3 23 13
(deviation --
upper-and lower-limit) 2 22 12
1 21 33 11 4 to 20mA
E5AK-AA2 +
(OUT1 : E53-R)
3--3
E5AK
J Input type · Set the type No. (0 to 21) in the “input type” parameter. The factory set-
ting is “2: K1 (thermocouple).”
· For details on input types and setting ranges, see page 5-26.
J Scaling · When the voltage input and current input are selected, scaling matched
to the control is required.
· The “scaling upper limit”, “scaling lower limit” and “decimal point”
parameters (setup mode) are use for scaling.
· The “scaling upper limit” parameter sets the physical quantity to be
expressed by the upper limit value of input, and the “scaling lower limit”
parameter sets the physical quantity to be expressed by the lower limit
value of input. The “decimal point” parameter sets the number of digits
past the decimal point.
· The following figure shows scaling example of 4 to 20 mA input. After
scaling, the humidity can be directly read. In this case, the “decimal
point” parameter is set to “1”.
Readout (humidity)
Input (4 to 20 mA)
0
100%FS
F Input shift · When temperature input is selected, scaling is not required. This is
because input is treated as the “temperature” as it is matched to the
input type. However, note that the upper and lower limit values of the
sensor can be shifted. For example, if both the upper and lower limit val-
ues are shifted by 1.2_C, the process value (before shift) is regarded as
201.2_C after shift when input is 200_C before shift.
· To set input shift, set shift values in the “input shift upper limit” and
“input shift lower limit” parameters (level 2 mode).
Temperature
After shift
Before shift
About the tempera- To switch the temperature unit from “_C” to “_F” for temperature unit, switch the
ture unit setting of the _C/_F selection” parameter to [ ] from [ ].
3--4
E5AK
(1) Select the menu display, and select [ ] (setup mode) using the
or keys. For details on selecting the menu display, see page
1-8.
1 second min.
(2) Press the key to enter the setup mode. The top parameter in the
setup mode [ ] “input type” is displayed. The parameter default
is “2”.
(3) Press the key until the display indicates “17”.
(4) Press the key to fix the set value. The display changes to [ ]
(“scaling upper limit value” parameter). The parameter default is
“100”.
(5) Press the key until the display indicates “950”.
(6) Press the key to fix the set value. The display changes to [ ]
(“scaling lower limit value” parameter). The parameter default is “0”.
(7) Press the key until the display indicates “100”.
(8) Press the key to fix the set value. The display changes to [ ]
(“decimal point” parameter). The parameter default is “0”.
(9) Press the key until the display indicates “1”.
3--5
E5AK
J Output assignments
Output assignments are described according to controller type.
F Standard type · Ten output are supported :
control output (heat)
control output (cool)
alarm outputs 1 to 3
HBA
LBA, and
error 1 (input error)
error 2 (A/D converter error)
error 3 (RSP input error).
These functions are assigned to control outputs 1 and 2, and auxiliary
output 1 and 2.
· Restrictions on assignment destination are placed on some of the out-
puts. The following table shows where outputs may be assigned to.
Assignment Control Output Auxiliary Output
Destination
Output Function 1 2 1 2
Control output (heat) F F
Control output (cool) F F
Alarm 1 F F F F
Alarm 2 F F F F
Alarm 3 F F F F
HBA F F F F
LBA F F F F
Error 1; Input error F F
Error 2; A/D converter error F F
Error 3; RSP input error F F
With control output (cool), the conditions for switching from standard control
to heating and cooling control are reached when the output function is assigned
at the cooling side during heating and cooling control.
In other words, heating and cooling control is carried out when control
output (cool) is assigned, and standard control is carried out when out-
put is not assigned. For details on heating and cooling control, see 4.1
Selecting the Control Method (page 4-2).
3--6
E5AK
J Direct/reverse · “Direct operation” (or normal operation) refers to control where the
operation manipulated variable is increased according to the increase in the pro-
cess value. Alternatively, “reverse operation” refers to control where the
manipulated variable is decreased according to the decrease in the pro-
cess value.
For example, when the process value (PV), is lower than the set point
(SP), in a heating control system, the manipulated variable increases by
the difference between the PV and SP values.
Accordingly, this becomes “reverse operation” in a heating control system.
Alternatively, this becomes “direct operation” in a cooling control system.
· Direct/reverse operation is set in the [ ]“direct/reverse operation”
parameter (setup mode).
J Control period · When the output unit is pulse output such as relay output, set the pulse
output cycle (control period). Though a shorter pulse period provides
better control performance, the control period should be set taking the
life expectancy of the output unit into consideration when the output
unit is relay.
· The control period is set in the “control period (heat)” parameter (level
1 mode). Factory setting is “20:20 seconds.”
· The “control period (cool)” output function is not allocated. So, the
“control period (cool)” parameter cannot be set.
3--7
E5AK
(1) Select the menu display, and select [ ] (setup mode) using the
or keys. For details on selecting the menu display, see page
1 second min.
1-8.
(2) Press the key to enter the setup mode. The top parameter in the
setup mode [ ] “input type” is displayed. In this example, the
parameter setting is “17: 4 to 20 mA.”
(3) Press the key until [ ] (“control output 1 assignment”
parameter) is displayed. The parameter default is [ ].
(4) As the setting in this example is to be left as it is, press the key.
The display changes to [ ] (“control output 2 assignment”
parameter). The parameter default is [ ].
(5) As the setting in this example is to be left as it is, press the key
until [ ] (“direct/reverse operation” parameter) is displayed.
The parameter default is [ ].
1 second min. (6) As the setting in this example is to be left as it is, press the or
keys to select [ ] (level 1 mode). For details on selecting the menu
display, see page 1-8.
(7) Press the key to enter the level 1 mode. The top parameter in the
level 1 mode [ ] “AT execute/cancel” is displayed.
(8) Press the key until [ ] (“control period” parameter) is dis-
1 second min. played. The parameter default is “20”. As the setting in this example
is to be left as it is, quit key operation.
3--8
E5AK
J Alarm type · The following table shows the alarm types supported by the E5AK con-
troller and their respective operations.
Alarm Output Operation
Alarm Type
When X is positive When X is negative
Upper-and lower-limit alarm X X
1 ON Always ON
(deviation) OFF SP
X X
2 Upper-limit alarm (deviation) ON ON
OFF OFF
SP SP
X X
3 Lower-limit alarm (deviation) ON ON
OFF OFF
SP SP
Upper-and-lower-limit range X X
4 ON Always OFF
alarm (deviation) OFF
SP
Upper-and-lower-limit alarm X X
5 with standby sequence ON Always OFF
(deviation) OFF
SP
Absolute-value upper-limit X X
8 ON ON
alarm OFF OFF
0 0
Absolute-value lower-limit X X
9 ON ON
alarm OFF OFF
0 0
Absolute-value upper-limit X X
10 ON ON
alarm with standby sequence OFF OFF
0 0
Absolute-value lower-limit X X
11 alarm with standby sequence ON ON
OFF OFF
0 0
· Alarm types are set independently for each alarm in the “alarm 1 to 3”
parameters (setup mode). Factory setting is “2: Upper-limit alarm (devi-
ation)”.
J Alarm value · Alarm values are indicated by “X” in the table above. Alarm output
operation differs according to whether the value of the alarm is positive
or negative.
· Alarm values are set independently for each alarm in the “alarm value
1 to 3” parameters (level 1 mode). Factory setting is “0”.
3--9
E5AK
J Alarm hysteresis · The hysteresis of alarm outputs when alarms are switched ON/OFF can
be set as follows.
Upper limit alarm Lower limit alarm
ON ON
OFF OFF
Alarm value Alarm value
F Summary of The figure below visually summarizes the above description of alarm
alarm operations operations (when alarm type is set to “lower limit alarm (deviation) with
standby sequence”):
Alarm type: lower limit alarm (deviation)
with standby sequence
PV
Alarm value
Alarm hysteresis
Time
Standby sequence
canceled Close (ON)
Alarm output Open (OFF)
(close in alarm)
3--10
E5AK
When a set point for a temperature exceeds 10%, alarm1 will be output.
Setting Example
In this example, let’s set the parameters as follows:
“alarm type 1” = “1: (deviation upper-and lower-limit)”
“alarm value 1” = “10”
“alarm hysteresis” = “0.20”
“close in alarm/open in alarm”= “ : close in alarm”
1 second min.
About the Decimal The decimal point of the alarm value conforms to the setting of the “decimal point”
Point of the Alarm parameter (setup mode). In this example, the “decimal point” parameter is set to
Value “1”. (During temperature input, the decimal point of the alarm value conforms to
the set sensor.)
3--11
E5AK
J Security · This parameter allows you to protect until start of operation parameters
that do not change during operation to prevent unwanted modification.
· The set value of the “security” (protect) parameter specifies the range
of protected parameters.
· When this parameter is set to “0”, parameters are not protected.
· When this parameter is set to “1” to “3”, the number of modes that can
be displayed on the menu display is limited.
When set to “1”, level 0 to 2, setup, expansion and option modes only can
be selected. When set to “2”, only level 0 to 2 modes can be selected. When
set to “3”, only level 0 and 1 modes can be selected.
· When this parameter is set to “4” to “6”, operations in only the level 0
mode can be selected, and the mode is not displayed on the menu display.
· When this parameter is set to “5”, only the “PV/SP” parameter can be
used.
· When this parameter is set to “6”, only the “PV/SP” parameter can be
used. (The set point can not change.)
· Default is “1”.
J A/M key protect · This parameter disables use of the A/M key during operation. For exam-
ple, if you protect use of the A/M key by the “A/M key protect” parameter
(protect mode) during auto operation, the controller cannot be set to the
manual mode, preventing manual operation of the controller during
operation.
· Let’s protect the setup, expansion, option and calibration modes. Set the
Setting Example
parameters as follows:
“security” = “2: Usable only in level 0 to 2 modes”
A/M (1) Press for 1 second minium the A/M and keys simultaneously, the
controller enters the protect mode.
(2) In the protect mode, the top parameter in the protect mode “security”
is displayed. The parameter default is “1”. Press the key to change
the parameter setting to “2”.
(3) Press for 1 second minium the A/M and keys simultaneously, the
display changes to the “PV/SP monitor” parameter (level 0 mode).
A/M
3--12
E5AK
· You can start and stop operation by changing the setting of the “run/
stop” parameter (level 0 mode).
· You can switch the RUN/STOP function up to 100,000 times.
· To stop operation, set the “run/stop” parameter to [ ] (stop). In a
stop state, the “STOP” LED lights.
· Operation cannot be stopped during auto-tuning.
F Manipulated vari- · On a standard type controller, specify the manipulated variable (---5.0 to
able at stop 105.0%) in the “MV at stop” parameter (level 2 mode) to output the
manipulated variable during stop.
Factory-set to “0.0:0.0%”.
· On a position-proportional type controller, you can select either of the
open, close or hold status. In an open status, only control output 1 is ON.
In a close status, only control output 2 is ON. In a hold status, both con-
trol outputs 1 and 2 are OFF. Factory-set to “hold.”
(1) Select the menu display, and select [ ] (level 0 mode) using the
or keys. For details on selecting the menu display, see page
1-8.
1 second min.
(2) Press the key to enter the level 0 mode. The PV and SP are dis-
played.
(3) Press the key until [ ] (“run/stop” parameter) is displayed.
(4) Press the key to select [ ] (stop). The “STOP” LED lights,
and operation stops.
Using Event Input Using the E53-AKB, run/stop can be selected by event input. For details on how to
use event input, see 4.3 How to Use Event Input, page 4--- 8.
3--13
E5AK
J Changing the set · You can change the set point in the “set point” parameter (level 0 mode).
point · However, note that you cannot change the set point when the “security”
parameter (protect mode) is set to “6”.
· To change the set point, press the or keys to select the desired
value. If you leave the setting for two seconds, the set point is updated
to the new setting.
In the following example, let’s change the temperature set point from
Setting Example
“60_C” to “50_C”.
J Manual operation · On standard type controller, the manipulated variable is controlled, and
on a position-proportional type controller, the valve opening is con-
trolled.
· To set manual operation and manually set the manipulated variable or
the valve opening, press for 1 second minimum the A/M key. The control-
ler enters the manual mode.
F Standard type · The process value is displayed on the No.1 display, and the manipulated
variable is displayed on the No.2 display. The manipulated variable
Process value
(heat) is also displayed on the bar graph in 10% increments.
Manipulated · To change the manipulated variable, press the or keys. After
variable
two seconds, the manipulated variable is updated to the new setting.
Bar graph [MANU] LED
· Other modes cannot be selected while in the manual mode. To select
other modes, press for 1 second minimum the A/M key. The manual mode
is quit.
· The automatic return of display function does not work while in the
manual mode.
· When switching between manual and auto operation, the manipulated
variable is subject to balance-less, bump-less operation.
· If the power is interrupted during manual operation, manual operation
is resumed at the manipulated variable at power interruption when the
power is reset.
· You can switch the AUTO/MANUAL function up to 100,000 times.
Balance-less, To prevent sudden changes in the manipulated variable when switching between
Bump-less Opera- manual and auto operation, operation is resumed using the value that was active
tion immediately before operation was switched, and the value is brought gradually
closer to the value immediately after operation was switched.
3--14
E5AK
Time
0
Manipulated variable OFF ON
Manual switched
Power inter-
A/M ruption
Auto
F Position-proportional type
· When a potentiometer is connected to the controller, the process value
is displayed on the No.1 display, and the valve opening is displayed on the
No.2 display. The valve opening is also displayed on the bar graph in 10%
increments.
When a potentiometer is not connected to the controller, [----] is dis-
played on the No.2 display, and nothing is displayed on the bar graph.
Potentiometer connected Potentiometer not connected
· When you press the key, the open side becomes ON. When you press
the key, the close side becomes ON.
· Other modes cannot be selected while in the manual mode. To select
other modes, press for 1 second minimum the A/M key. The manual mode
is quit.
· The automatic return of display function does not work while in the
manual mode.
· You can switch the AUTO/MANUAL function up to 100,000 times.
3--15
E5AK
F 40%AT In order to set the limit cycle of MV change width to 40%, select 40%AT
to execute auto-tuning with fluctuations in the process value kept to a
minimum. However, note that auto-tuning takes longer to execute
compared with 100%AT.
The timing by which limit cycles are generated varies according to wheth-
er or not the deviation (DV) at the start of AT execution is 10% full-scale
or less.
Time Time
Start of AT End of AT Start of AT End of AT
execution execution
F 100%AT In order to set the limit cycle of MV change width to 100%, select 100% AT
to shorten the AT execution time without worrying about fluctuations in
the process value.
Limit cycle of MV
change width 100%
Set point
Time
Start of AT End of AT
execution
3--16
E5AK
1 second min.
(2) Press the key to enter the level 1 mode. The top parameter in the
setup mode [ ] “AT execute/cancel” is displayed. In this example,
the parameter setting is [ ] “AT cancel”
(3) Press the key to specify [ ].
(4) The AT LED flashes, and AT execution starts. When the AT LED goes
out (end of AT execution), the parameter automatically returns to
[ ] (“AT cancel”).
AT execute
About PID Parame- When control characteristics are already known, the PID parameters can be set
ters directly to adjust control.
PID parameters are set in the “proportional band” (P), “integrated time” (I) and
“derivative time” (D) parameters (level 1 mode).
For details on the setting ranges of these parameters, see chapter 5 Level 1 Mode
(page 5-13).
3--17
E5AK
3--18
E5AK
CHAPTER 4 4
APPLIED OPERATION
This chapter describes each of the parameters required for making full
use of the features of the E5AK. Read this chapter while referring to the
parameter descriptions in chapter 5.
4--1
E5AK
When selecting the control method, set the parameters according to the
following table. (Parameters are factory-set to heating control.)
Parameter
Control output 1 Control output 2 Direct/Reverse
Control assignment assignment operations
Method
Heating control
(Standard)
Control output (heat) - Reverse operation
Cooling control
(Standard)
Control output (heat) - Direct operation
F Cooling coeffi- If the heating and cooling characteristics of the control target greatly dif-
cient fer, preventing satisfactory control characteristics from being obtained by
the same PID parameters, adjust the proportional band (P at cooling side)
using the cooling coefficient to balance control between the heating and
cooling sides. In heating and cooling control, P at the heating or cooling
side is calculated by the following formula:
Heating side P = P; Cooling side P = cooling coefficient ¢ P
F Manipulated vari- · In heating and cooling control, the manipulated variable output that is
able at stop output when controller operation is stopped is dependent on the set
value of the “MV at stop” parameter (level 2 mode) in the same way as
for standard control.
· However, note that in heating and cooling control, the manipulated vari-
able at the cooling side is treated as a negative value for the sake of conve-
nience. When the manipulated variable at STOP is a negative value, the
manipulated variable is output to only the cooling side, and when a posi-
tive value, the manipulated variable is output to only the heating side.
The factory setting is “0”. If the controller is operated using the factory
setting, the manipulated variable is not output to both the heating and
cooling sides.
Switching with When the overlap band is set, the bumpless function that operates when switching
Manual operation between manual and automatic operation may not work.
4--2
E5AK
F Valve opening · The valve opening can be monitored when a potentiometer is connected
monitor to the controller. However, be sure to execute motor calibration after
connecting the potentiometer.
· The monitored valve opening is displayed on the bar graph in 10% incre-
ments.
F Manipulated vari- · Open, close or hold can be selected as output at stop or PV error. Set these
able at stop/PV outputs in the “manipulated variable at stop” or “manipulated variable
error at PV error” parameters (level 2 mode).
F Other functions · Set the dead band in the “position-proportional dead band” parameter
(level 1 mode).
· Set the open/close hysteresis in the “open/close hysteresis” parameter
(level 1 mode).
Open/close hysteresis
Dead band
ON
OFF
MV--Valve opening
-100% 0 100%
4--3
E5AK
J ON/OFF control · Switching between advanced PID control and ON/OFF control is car-
ried out by the “PID / ON/OFF” parameter (expansion mode). When this
parameter is set to [ ], advanced PID control is selected, and when
set to [ ], ON/OFF control is selected. Default is [ ].
· During position-proportional control, ON/OFF control cannot be
selected.
F Hysteresis · In ON/OFF control, hysteresis is provided in the program when switch-
ing between ON and OFF to stabilize operation. The hysteresis width
provided during ON/OFF control is simply referred to as “hysteresis.”
Control output (heat) and control output (cool) functions are set in the
“hysteresis (heat)” and “hysterisis (cool)” parameters, respectively.
· In standard control (heating or cooling control), hysteresis can be set
only for the heating side.
Hysteresis (heat)
ON
OFF PV
Set point
· In heating and cooling control, a dead band can be set. So, 3-position con-
trol is made possible.
Dead band
4--4
E5AK
J Manipulated vari- The upper-and lower-limit values of the manipulated variable can be
restricted by the MV limiter, and the change rate of the manipulated vari-
able restrictions able can be restricted by the MV change rate limiter.
F MV limiter The upper-and lower-limit values of the manipulated variable are set in
the “MV upper limit” and “MV lower limit” parameters (level 2 mode).
When the manipulated variable calculated by the E5AK is outside of the
range of the MV limiter, actual outputs are dependent on the set value of
these parameters.
Output (%)
100
MV upper limit value
MV lower
limit value
0
PV
Output (%)
100
Set point
F MV change rate The “MV change rate limit” parameter (level 2 mode) sets the maximum
limiter permissible change width per second of the manipulated variable. If a
change in the manipulated variable exceeds this parameter setting, the
value calculated by the E5AK is reached while changing the value by the
per-second value set in this parameter.
Output (%)
100
MV change rate
limit value
1 second
0
Time
Switching point
4--5
E5AK
F Limiter operation The limiters are invalid or cannot be set when any of the following condi-
conditions tions occurs:
· During ON/OFF control
· During ST execution
· During AT execution (only by MV change rate limiter)
· During manual operation
· When operation is stopped
· When an error has occurred.
· During position-proportional control (manipulated variable limiter
only)
J Set point limiter The setting range of the set point is limited by the set point limiter. The
upper-and lower-limit values of this set point limiter are set in the “Set
point upper limit” and “Set point lower limit” parameters (expansion
mode), respectively. However, note that when the set point limiter is reset,
the set point is forcibly changed to the upper-or lower-limit value of the set
point limiter if the set point is out of the limiter range. Also, when the in-
put type, temperature unit and scaling (sensor) range are changed, set
point limiter is forcibly reset to the scaling (sensor) range.
Scaling (sensor) range
Set point limiter
Setting range SP
Changed to A B
the new up- ○ ×
per limit
value
Changed to upper
SP
limit value
J SP ramp With the SP ramp function, the controller operates according to the value
(set point during SP ramp) limited by a change rate, instead of the changed
set point when set point is changed. The interval in which the set point
during SP ramp is limited is referred to as the “SP ramp”.
SP
SP ramp
Set point
SP ramp set
value
SP ramp time unit
Time
Switching point
4--6
E5AK
The change rate during the SP ramp is specified by the “SP ramp set value”
and “SP ramp time unit” parameters. At the “SP ramp set value” default
“0”, the SP ramp function is disabled.
The set point changing in SP ramp can be monitored in the “Set point dur-
ing SP ramp” parameter (level 0 mode).
F Operation at start The limiters are invalid or cannot be set when any of the following condi-
tions occurs:
If the SP ramp function is enabled when the power is turned ON, and when
“run” is switched to from “stop,” process value may reach the set point af-
ter SP ramp in the same way as when the set point is changed. In this case,
operation is carried out with the process value regarded as the set point
before the change was made.
The direction of the SP ramp changes according to the relationship be-
tween the process value and the set point.
PV < SP PV > SP
SP SP
SP ramp
SP ramp
Set point
PV
Same change
rate
Set point
PV
Time Time
Power ON Power ON
Parameters
Symbol Parameter Name: Mode Description
MV upper limit : Level 2 Manipulated variable restrictions
MV lower limit : Level 2 Manipulated variable restrictions
MV change rate limit : Level 2 Manipulated variable restrictions
SP setting upper limit: Expansion SP setting restrictions
SP setting lower limit : Expansion SP setting restrictions
SP ramp set value : Level 2 SP changing restrictions
SP ramp time unit : Level 2 SP changing restrictions
4--7
E5AK
· When using event input, mount the option unit (E53-AKB). Up to two
E53-AKB units can be mounted on the E5AK, and two event inputs can
be used for each E53-AKB unit.
E53-AKB × 1 unit : 2 event inputs
E53-AKB × 2 units : 4 event inputs
· Event inputs can be switched up to 100,000 times.
J Event input · You can choose from the following five event input functions:
assignments Multi-SP
Run/Stop
Remote/Local
Auto/Manual
SP mode
· In the case of the multi-SP function, the number of event inputs (event
input 1 or 2) set in the “multi-SP function” parameter (option mode) are
used. When four event inputs are used, the multi-SP function is auto-
matically assigned to event inputs 1 and 2 for the designated number.
When two event inputs are used, the multi-SP function is automatically
assigned to event inputs 3 and 4 for the designated number.
· Other functions are assigned to event inputs 1 to 4 not used for the mul-
ti-SP function according to the setting of the “event input assignment 1 to
4” parameters (option mode). However, note that “event input assignment
1/2” parameters cannot be used when only one unit of the E53-AKB is
installed.
4 event inputs 2 event inputs
Event input 1 2 3 4 3 4
0
Multi-SP function
· The following table shows the relationship between the settings and
functions of the “event input assignment 1 to 4” parameters.
Setting Function
Event input disabled
ON : Stop /OFF : Run
ON : Remote /OFF : Local
ON : Manual /OFF : Auto
ON : RSP /OFF : LSP
4--8
E5AK
F Assignment · In this example, set four event inputs are used, the multi-SP function to
example “2”, and event input 3 to “Run/Stop” and event input 4 to “Auto/
Manual”. Set as follows:
(1) Set “multi-SP function” parameter to “2”
(2) Set “event input assignment 3” parameter to “ ”
(3) Set “event input assignment 4” parameter to “ ”
Event input 1 2 3 4
Multi-SP Auto/Manual
Run/Stop
J Multi-SP · Set points 0 to 3 are set as the set point according to event input. How-
ever, note that these parameters can not be set when the multi-SP func-
tion is not selected. The following table shows the relationship between
event inputs and set points 0 to 3.
Multi-SP Function 1 2
Event Input 1 (3)* 1 (3)* 2 (4)*
Set Point 0 OFF OFF OFF
Set Point 1 ON ON OFF
Set Point 2 - OFF ON
Set Point 3 - ON ON
set point 0
Time
Event input OFF ON
4--9
E5AK
key.
· There is no order of priority in event input and key operations. However,
run/stop or auto/manual event inputs must be set to either of ON or OFF.
So, parameters will always follow event input even if you try to switch
settings by key operation.
F Run/Stop · When event input is set to “ON”, controller operation is stopped and the
“STOP” LED lights. The content of event input is reflected in the “run/
stop” parameter (level 0 mode).
F Remote/Local · This function is supported only when E53-AK01/02/03, the option unit
for serial communications, is installed.
· When event input is set to “ON”, parameters can be written only by
using the communications function, and the “RMT” LED lights. The
content of event input is reflected in the “remote/local” parameter (level
2 mode).
F Auto/Manual · When event input is set to “ON”, the controller is switched for manual
operation, and the “MANU” LED lights.
· Turn event input ON/OFF while the controller is ON.
F SP mode · This function is enabled only when the “SP mode enable” parameter
(option mode) is set to “ON”.
· When event input is set to “ON”, the remote SP (RSP) is taken as the set
point, and the “RSP” LED lights. When event input is set to “OFF”, the
local SP (LSP) is taken as the set point. The content of event input is
reflected in the “SP mode” parameter (level 2 mode). For details on RSP/
LSP, see 4.4 How to Use the Remote SP (page 4-11).
4--10
E5AK
F Relationship with · When the “Set point upper limit” or “Set point lower limit” parameters
set point limiter are changed, the remote SP upper-and lower-limit values are forcibly
changed to the set poimt upper-and lower-limit values. The following
example shows how the remote SP upper-and lower-limit values are
changed when the set point upper limit value is changed from A to B.
Set point limiter
RSP scaling range
A
Before change Set point
J SP mode · The set point held internally by the E5AK controller is referred to as the
“local SP (LSP).”
LSP · If the multi-SP function is enabled, set points 0 to 3 are enabled for use
SP mode
as the local SP.
· Use the “SP mode” parameter to switch between the remote SP and local
RSP SP. When the SP mode parameter is set to “ ” (remote SP), the
RSP enable
“RSP” LED lights. When the SP mode parameter is set to “ ”, the
controller is in the local SP mode.
4--11
E5AK
J Remote SP · In the remote SP mode, the remote SP can be monitored on the No.2 dis-
play for PV/SP. In the local SP mode, the remote SP can be monitored in
monitor the “remote SP monitor” parameter.
J SP tracking · When the local SP is switched to from the remote SP when the SP track-
ing function is enabled, the local SP is changed so that the remote SP
value is held at the SP value used immediately before switching.
To use the SP tracking function, set the “SP tracking” parameter to
“ON”.
· The following figure shows how SP tracking works when the SP mode
is switched.
RSP input
LSP1
LSP2
RSP2
(1) When the remote SP is switched to when the set point is “LSP1”, the
SP is switched to “RSP2”.
(2) The SP shifts according to remote SP input.
(3) When the local SP is switched to, the set point becomes “LSP2” if the
SP tracking function is enabled. If this function is disabled, the SP
will be switched to “LSP1”.
· When the local SP is switched to the remote SP, the SP ramp will operate
if the SP ramp function is enabled.
J Operating · When the SP function is set to “ON”, the “SP mode” parameter is forci-
bly changed to [ ] and the local SP is taken as the set point.
conditions
· During auto-tuning, remote SP input is not accepted. Auto-tuning is
executed on the set point at the start of auto-tuning.
· Remote SP is not subject to the standby sequence reset conditions.
4--12
E5AK
F HBA · When the HBA latch function is set to “ON”, the heater burnout alarm
latch/release is held until either of the following measures is taken:
a Set the heater burnout set value to “0.0”.
b Reset the controller.
(Turn the controller’s power OFF then back ON again.)
· To enable the HBA latch function, set the “HBA latch” parameter to
“ON”.
J Operating · Turn the heater power supply ON at the same time as or before turning
the E5AK power supply ON. If the heater power supply is turned ON
conditions after turning the E5AK power supply On, the heater burnout alarm is
output.
· Control is continued even when the heater burnout alarm is output.
(That is, the controller attempts to control the heater as if the heater
burnout alarm has not occurred.) So, remedy the condition such as
repairs which are caused by the heater burnout alarm.
· The heater burnout alarm is detected only if the control output is contin-
uously ON for 190 ms or more.
· The rated current value may sometimes differ slightly from the actual
current value flowing to the heater. Check the current value in an actual
operating status in the “heater current monitor” parameter.
· If there is little difference between the current in a normal status and the
current in a burnout status, detection may become unstable. On a heater
of current 10.0 A or less, maintain a difference of 1.0 A or more. On a
heater of current 10.0 A or more, maintain a difference of 2.5 A or more.
· Heater burnout alarm function cannot be used when controlling the
heater by a phase control method or by a cycle control method. Also,
3-phase heaters cannot be used.
4--13
E5AK
J How to calculate · Calculate the set value nby the following formule:
the heater burn- Set value =
(current value at normal operation + current value at burnout)
2
out set value
· Set the current value at burnout when two or more heaters are con-
nected to the CT to the value at the time that the heater having the small-
est current value burns out (the value when one of the heaters burns out
with all heaters at the same current).
· Make sure that the following condition is satisfied:
Heater of current 10.0 A or less
Current value at normal operation --- current value at heater burn-
out ≧ 1 A
When resultant current is less than 1 A, detection is unstable.
Heater of current 10.0 A or more
Current value at normal operation --- current value at heater burn-
out ≧ 2.5 A
When resultant current is less than 2.5 A, detection is unstable.
· The setting range is 0.1 to 49.9 A. Heater burnout is not detected when
the setting is “0.0” or “50.0”. When the setting is “0.0”, the heater burn-
out alarm is set to “OFF”, and when the setting is “50.0”, the heater
burnout alarm is set to “ON”.
· Set the total current value at normal heater operation to 50 A or less.
When set to 55.0 A or more, [ ] is displayed in the “heater current
monitor” parameter.
E5AK 17 15
4--14
E5AK
4.6 LBA
4.6 LBA
· The LBA (Loop Break Alarm) function can be used only on standard
type controllers.
· The LBA function can be used only when assigned as an output. Also, the
LBA function does not work when a memory error or A/D converter
error results.
· LBA (Loop Break Alarm) is a function for judging that an error has
occurred somewhere on the control loop and outputting an alarm when
the process value does not change with the manipulated variable at a
maximum or minimum state. Accordingly, the LBA function can be used
as a means for detecting a malfunctioning control loop.
F LBA detection · Normally, when output is set to maximum or minimum, the process
time value rises or falls after the dead time has elapsed. LBA is output if the
process value does not change in the predicted direction after a fixed
amount of time has elapsed. This fixed amount of time is the “LBA detec-
tion time.”
F LBA detection · LBA operation sometimes becomes unstable when the process value
width fluctuates considerably due to the control characteristics. The LBA
detection width is provided so that changes with respect to output can
be correctly detected. Changes smaller than the detection width due to
LBA detection timing are not regarded as changes.
F LBA detection · The following example describes what happens when a heater burnout
example at maximum output.
LBA detection time LBA detection time
PV
Output
Time
Heater burnout LBA=ON
· LBA judgment is carried out at each LBA detection time from the point
of maximum output. In above figure, the process value (PV) is changing
greatly at the 1st judgment timing, so LBA remains OFF.
· At the 2nd judgment timing, the process value increases as indicated by
the broken line of the process value is normal. This means that the
change width exceeds the LBA detection width, and LBA output remains
OFF.
· If the heater burns out at the point shown in the above figure, the process
value “decreases.” Accordingly, it is judged that “the process value is not
changing in the increasing direction” at the 2nd judgment timing and
the LBA output becomes ON.
4--15
E5AK
F Setting the LBA · The LBA detection time is automatically set by auto-tuning (except in
detection time heating and cooling control).
· If the optimum LBA detection time cannot be obtained by auto-tuning,
set the time in the “LBA detection time” parameter (level 2 mode).
PV
0.2%FS
Output
Time
LBA detection time = Tm x 2
(4) In the case of ON/OFF operation, set the LBA detection time to a val-
ue longer than the control period.
Parameters
Symbol Parameter Name: Mode Application
AT Execute/Cancel : Level 1 Automatic setting of LBA detec-
tion time
LBA detection time : Level 2 Setting of LBA detection time
LBA detection width : Expansion Changing of LBA detection
width
4--16
E5AK
F Transfer output · You can select the following data items in the “transfer output type”
type parameter (option mode) as the transfer outputs:
Set point
Set poing during SP ramp
Process value
Manipulated variable (heat)
Manipulated variable (cool), and
Valve opening.
However, note that heating/cooling side manipulated variables can be
output only standard type controllers, and valve opening can be output
on position-proportional type controllers
· If the output assignment is changed when either ”manipulated variable
(heat)” or ”manipulated variable (cool)” parameter is selected, the
default ”set point” is returned to.
F Transfer output · These transfer outputs can be scaled according to the settings of the
scaling “transfer output upper limit” and “transfer output lower limit” param-
eters before output. Setting of an upper limit value smaller than the
lower limit value is allowed, so reverse scaling can also be carried out.
Also, the scale can be enlarged by the upper-and lower-limit width speci-
fied for each data item. The following example shows scaling of the read-
ing side manipulated variable.
Transfer output Transfer output
(mA) Reverse scaling (mA) Enlarged scale
20 20
4 4
Manipu- Manipulated
lated 0 variable (%)
Transfer output Transfer Transfer Transfer 100
variable output lower output upper
upper limit: 0 output lower (%)
limit: 100 limit: 10 limit: 80
4--17
E5AK
SP limitter
Transfer type scaling range
A
Change value Set point
4--18
E5AK
CHAPTER 5 PARAMETERS
CHAPTER 5 5
PARAMETERS
This chapter describes the parameters of the E5AK. Use this chapter as
a reference guide.
5--1
E5AK
CHAPTER 5 PARAMETERS
Function
Comment
Example
of use
See
Describes models of the E5AK or option units supporting the parameter being
described.
Model
Conditions of Use
AT Execute/cancel The controller must
be in operation.
5--2
E5AK
Protect Mode
· The protect mode is for disabling (protecting) the functions of the menu key or A/M
key. Before changing parameters in this mode, first make sure that protecting the
menu key or A/M key will not cause any problems in operation.
· To select this mode, press the A/M key and key simultaneously for 1 second mini-
mum. To exit this mode, press the A/M key and key down again simultaneously
for 1 second minimum.
· The following table shows the parameters supported in this mode and the page where
the parameter is described.
Symbol Parameter Name Page
Security 5-3
[A/M] key protect 5-4
Security
· This parameter specifies which parameters are protected. However, note that the
protect mode and manual mode cannot be protected.
Function
· When this parameter is set to “0” to “3”, only the modes indicated by the “f” mark
in the table below can be selected on the menu display. For example, when this param-
Comment
eter is set to “2”, only level 0 to 2 modes can be selected.
Set value
Mode
0 1 2 3 4 5 6
Calibration f
Option f f
Expansion f f
Setup f f
Level 2 f f f
Level 1 f f f f
Level 0 f f f f f f *
· When this parameter is set to “4” to “6”, operations in only the level 0 mode can be
selected, and the mode is not displayed on the menu display.
· When this parameter is set to “5”, only the “PV/SP” parameter in the level 0 mode
can be used.
· When this parameter is set to “6”, only the “PV/SP” parameter in the level 0 mode
can be used. (The set point cannot change.)
· Default is “1”. (Only the calibration mode is protected.)
F Related article
3.5 Protect Mode (page 3-12)
See
5--3
E5AK
CHAPTER 5 PARAMETERS
Protect Mode
· Invalidate the function of the key. In other words, you cannot switch between the
auto and manual operations by key operation.
Function
F Related article
3.5 Protect Mode (page 3-12)
See
5--4
E5AK
Manual Mode
· In this mode, manual operations are possible, and the “MANU” LED lights.
· When this mode is selected, the manipulated variable that was active immediately
before the mode was switched to is output. When changing the manipulated variable,
change it using the or keys.
If this mode is switched to during auto-tuning, auto-tuning is canceled.
· To select this mode when in the level 0 to 2 modes, press the A/M key for 1 second mini-
mum. To exit this mode, press the A/M key for 1 second minimum. The mode changes
to the level 0 mode.
· “Manual MV” is the only parameter available in this mode.
Manual MV
· Sets the manipulated variable for manual operation or the valve opening. On a standard
type controller when you press the or keys, the manipulated variable is
Function
changed. On a position-proportional type controller when you press the key, the
open side becomes ON, and when you press the key, the close side becomes ON.
· On a standard type controller, the process value is displayed on the No.1 display and
the manipulated variable is displayed on the No.2 display. The manipulated variable
on the heating side is also displayed on the bar graph in 10% increments.
Process value
Manipulated variable
· On standard type controllers, the manual MV is held when the power is interrupted.
· Standard type
Control Method Setting Range Unit Default
Comment Standard -5.0 to 105.0 % 0
Heating and cooling -105.0 to 105.0 % 0
· Position-proportional type
Control Method Monitor Range Unit
Position-proportional -10.0 to 110.0 %
F Related article
3.7 Adjusting Control Operation (page 3-14)
See
5--5
E5AK
CHAPTER 5 PARAMETERS
Level 0 Mode
· The parameters in this mode can be used only when the “security” parameter (pro-
tect mode) is set to “0” to “4”.
· The “PV/SP” parameter can be used when the “security” parameter is set to “5” or
“6”. However, note that the SP cannot be changed when it is set to “6”.
· This mode is used for monitoring the process value, set point and manipulated vari-
able during operation, and for checking and setting the SP setting value. It is also
used for starting and stopping controller operation.
· To select this mode when in the levels 1 and 2, setup, expansion, option and calibra-
tion modes, press the key for 1 second minimum. The display changes to the
menu display. If you select [ ] then press key for 1 second minimum, the
controller enters the level 0 mode.
· To select parameters in this mode, press the key. To change parameter settings,
use the or keys.
· The following table shows the parameters supported in this mode and the page where
the parameter is described.
Symbol Parameter Name Page
PV/SP 5-6
Remote SP monitor 5-7
Set point during SP ramp 5-8
MV monitor (heat) 5-8
MV monitor (cool) 5-8
Vavle opening monitor 5-9
Run/Stop 5-9
PV/SP
· The process value is displayed on the No.1 display, and the set point is displayed on
the No.2 display. The set point can be set.
Function
· Either of the local SP or remote SP is displayed as the set point depending on the SP
mode. In the remote SP mode, the set point is only monitored.
Local SP mode Remote SP mode
Process value
· The selected set point is linked when the multi-SP function is in use in the local SP
mode. For example, when set point 1 is selected, set point 1 is displayed on the No.2
display, and the setting of the “set point 1” parameter (level 1 mode) also is changed
when the value of set point 1 is changed.
· The decimal point position is dependent on the selected sensor during temperature
input and on the results of scaling during analog input.
5--6
E5AK
Level 0 Mode
· Process value
Monitor Range Unit
Scaling lower limit -10%FS to scaling upper limit +10%FS EU
Comment
During temperature input, the range of the currently selected sensor is taken as the
monitor range.
· Set point
Setting Range/Monitor Range Unit Default
Local SP : Local SP lower limit to local SP setting upper limit EU 0
Remote SP: Remote SP lower limit to remote SP upper limit EU -
F Related article
3.7 Adjusting Control Operation (page 3-14)
F Related parameters
See
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode)
“SP setting upper limit” “SP setting lower limit” (expansion mode)
“SP mode” (level 2 mode)
“Remote SP enable” “Remote SP upper limit” “Remote SP lower limit” (option
mode)
Function
F Related article
4.2 Operating Condition Restrictions/SP ramp (page 4-6)
F Related parameters
See
“SP mode” (level 2 mode)
“Remote SP enable” “Remote SP lower limit” “Remote SP upper limit” (option
mode)
5--7
E5AK
CHAPTER 5 PARAMETERS
Level 0 Mode
F Related article
4.2 Operating Condition Restriction/SP ramp (page 4-6)
F Related parameters
See “PV/SP” (level 0 mode)
“SP ramp time unit” “SP ramp set value” (level 2 mode)
“Set point upper limit” “Set point lower limit” (expansion mode)
“SP mode” (level 2 mode)
“Remote SP enable” “Remote SP upper limit” “Remote SP lower limit” (option
mode)
· MV monitor (heat)
Control Monitor Range Unit
Standard -5.0 to 105.0 %
Monitor
Heating and cooling 0.0 to 105.0 %
· MV monitor (cool)
Control Monitor Range Unit
Heating and cooling 0.0 to 105.0 %
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
5--8
E5AK
Level 0 Mode
Function
Monitor
F Related article
4.1 Selecting the Control Methed/Position-proportional control (page 4-3)
See
E5AK-PRR2 AC100-240
E5AK-PRR2 AC/DC24
Model
Run/Stop
· This parameter is used for checking the operating status of the controller, and for
specifying start and stop of operation.
Function · When the “run/stop” function is assigned to event input, “stop” is set when event in-
put is ON, and “run” is set when event input is OFF. There is no order of priority in
key operations.
F Related article
3.6 Starting and Stopping Operation (page 3-13)
See
5--9
E5AK
CHAPTER 5 PARAMETERS
Level 1 Mode
· The parameters in this mode can be used only when the “security” parameter (pro-
tect mode) is set to “0” to “3”.
· This mode contains the main parameters for adjusting control. These parameters
include parameters for executing AT (auto-tuning), setting the alarm values, setting
the control period, and setting PID parameters.
· To select this mode when in the levels 0 and 2, setup, expansion, option and calibra-
tion modes, press the key for 1 second minimum. The display changes to the
menu display. If you select [ ] then press the key for 1 second minimum, the
controller enters the level 1 mode.
· To select parameters in this mode, press the key. To change parameter settings,
use the or keys.
· The following table shows the parameters supported in this mode and the page where
the parameter is described.
Symbol Parameter Name Page
AT Execute/Cancel 5-11
5--10
E5AK
Level 1 Mode
· Selects the limit cycle of MV change width (40% or 100%) for execution. After AT
execution, the “PID” and the “LBA detection time” (LBA: Loop Break Alarm) param-
eters are set automatically.
Function
· During heating and cooling control or position-proportional control, only 100%AT
can be executed.
F Related article
3.7 Adjusting Control Operation (page 3-16)
F Related parameters
See
“Run/Stop” (level 0 mode)
“Proportional band” “Integral time” “Derivative time” (level 1 mode)
“LBA detection time” (level 2 mode)
Conditions of Use
The controller must be in the local SP
mode with the multi-SP function enabled.
· Switches set points 0 to 3 by event input for use as the set point (local SP).
· Of set points 0 to 3, the number of valid set points is designated by the “multi-SP func-
tion” parameter.
Function
· The following table shows the relationship between event input and the selected
parameter.
Multi-SP Function 1 2
Event Input 1 1 2
Set Point 0 OFF OFF OFF
Set Point 1 ON ON OFF
Set Point 2 - OFF ON
Set Point 3 - ON ON
· When the set point has been changed, the setting of whichever is selected in event
input, “set point 0” to “set point 3”, is linked and changed.
· The decimal point position is dependent on the selected sensor during temperature
input and on the results of scaling during analog input.
5--11
E5AK
CHAPTER 5 PARAMETERS
Level 1 Mode
Comment
F Related article
4.3 How to Use Event Input (page 4-8)
F Related parameters
See
“Multi-SP function” “Remote SP enable” (option mode)
“Set point” (level 0 mode) “SP mode” (level 2 mode)
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup
mode)
F Option unit
E53-AKB
Model
· This parameter is used for monitoring or changing the alarm values of alarm outputs
1 to 3.
· During temperature input, the decimal point position is dependent on the currently
Function
selected sensor, and during analog input on the results of scaling.
Comment
F Related article
3.4 Setting Alarm Type (page 3-9)
F Related parameters
See
“Input type” “Scaling upper limit” “Scaling lower limit” Decimal point” “Control
output 1 assignment” “Control output 2 assignment” “Auxiliary output 1 assign-
ment” “Auxiliary output 2 assignment” “Alarm 1 type” “Alarm 2 type” “Alarm 3
type” “Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm”
(setup mode)
“Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode)
“Standby sequence reset method” (expansion mode)
5--12
E5AK
Level 1 Mode
Derivative time
· Sets the PID parameters. However, note that the PID parameter settings are changed
to optimum values when auto-tuning is executed, and self-tuning is selected.
Function
F Related parameter
“AT Execute/Cancel” (level 1 mode)
See
· In heating and cooling control, P at the cooling side is calculated by the following for-
mula:
Cooling side P = cooling coefficient ¢ P
Function
Comment
F Related article
4.1 Selecting the Control Method (page 4-2)
F Related parameter
See
“Proportional band” (level 1 mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
5--13
E5AK
CHAPTER 5 PARAMETERS
Level 1 Mode
· Sets the output dead band width in a heating and cooling control system. A negative
setting sets an overlap band.
Function
Comment
F Related article
4.1 Selecting the Control Method (page 4-2)
See
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
· Sets the output hold width during position-proportional control (ON/OFF switching
point for open and close output).
Dead band
ON
OFF
MV--Valve opening
-100% 0 100%
Comment
F Related article
4.1 Selecting the Control Method/Position-proportional Control (page 4-3).
F Related parameter
See
“Open/close hysteresis” (Level 2 mode)
E5AK-PRR2 AC100-240
E5AK-PRR2 AC/DC24
Model
5--14
E5AK
Level 1 Mode
Comment
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
F Related article
4.1 Selecting the Control Method/ON/OFF control (page 4-4)
F Related parameters
See
“Control output 1 assignment” “Control output 2 assignment” (setup mode)
“PID / ON/OFF” (expansion mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
5--15
E5AK
CHAPTER 5 PARAMETERS
Level 1 Mode
· Sets the pulse output period. Set the control period taking the control characteristics
and life expectancy of the controller into consideration.
Function · In standard control, use the “control period (heat)” parameter. The “control period
(cool)” parameter cannot be used.
· In heating and cooling control, the control period can be set independently for heat-
ing and cooling. Use the “control period (heat)” parameter to set the heating side con-
trol period, and use the “contrlo period (cool)” parameter to set the cooling side con-
trol period.
F Related article
3.3 Setting Output Specifications (page 3-6)
See F Related parameters
“Control output 1 assignment” “Control output 2 assignment” (setup mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
5--16
E5AK
Level 1 Mode
Function
F Related article
4.5 How to Use the Heater Burnout Alarm (page 4-13)
See
F Related parameters
“Heater burnout” (level 1 mode) “HBA latch” (option mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
· Outputs the heater burnout alarm when the heater current value falls below this
parameter setting.
Function · When the set value is “0.0”, the heater burnout alarm is “OFF”. When the set value
is “50.0”, the heater burnout alarm is “ON”.
Comment
F Related article
4.5 How to Use the Heater Burnout Alarm (page 4-13)
See
F Related parameters
“Heater current monitor” (level 1 mode) “HBA latch” (option mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
5--17
E5AK
CHAPTER 5 PARAMETERS
Level 2 Mode
· The parameters in this mode can be used only when the “security” parameter (pro-
tect mode) is set to “0” to “2”.
· This mode contains the auxiliary parameters for adjusting control. These parame-
ters include parameters for limiting the manipulated variable and set point, parame-
ters for switching between remote and local operation, and parameters for setting the
LBA (Loop Break Alarm), alarm hysteresis, and input digital filter values.
· To select this mode when in the levels 0 and 1, setup, expansion, option and calibra-
tion modes, press the key for 1 second minimum. The display changes to the
menu display. If you select [ ] using the key then press the key for
1 second minimum, the controller enters the level 2 mode.
· To select parameters in this mode, press the key. To change parameter settings,
use the or keys.
· The following table shows the parameters supported in this mode and the page where
the parameter is described.
Symbol Parameter Name Page
Remote/Local 5-19
SP mode 5-19
MV at stop 5-21
MV at PV error 5-21
5--18
E5AK
Level 2 Mode
Comment
F Related article
Chapter 6 Using the Communications Function
F Related parameters
See
“Communication stop bit” “Communication data length” “Communication parity”
“Communication baud rate” “Communication unit No.” “Event input assignment
1” “Event input assignment 2” “Event input assignment 3” “Event input assign-
ment 4” (option mode)
F Option units
E53-AK01/02/03
Model
Comment
F Related article
4.4 How to Use the Remote SP (page 4-11)
F Related parameters
See
“Remote SP enable”
“Event input assignment 1” “Event input assignment 2” “Event input assignment
3” “Event input assignment 4” (option mode)
5--19
E5AK
CHAPTER 5 PARAMETERS
Level 2 Mode
· Specifies the change rate during SP ramp operation. Set the maximum permissible
change width per unit of time (minute or hour) as the “SP ramp set value”. However,
Function
note that when set to “0”, the SP ramp function is disabled.
· The time unit and SP ramp set value are independent of each other. For example,
when setting “30 per minute”, set the “SP ramp set value” parameter to “30” and the
“SP ramp time unit” parameter to [ ] (“minute”). However, if you change the
time unit only to [ ] (“hour”), the set time becomes “30 per hour.”
· During temperature input, the decimal point position of the SP ramp set value is
dependent on the currently selected sensor, and during analog input on the results
of scaling.
During temperature input, the range of the currently selected sensor it taken as the
setting range for the “SP ramp set value” parameter.
F Related article
4.2 Operating Condition Restrictions/SP ramp (page 4-6)
See F Related parameters
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup
mode)
5--20
E5AK
Level 2 Mode
Comment
F Related article
4.4 LBA (page 4-9)
7.3 How to Use Error Output (page 7-5)
See
F Related parameters
“AT Execute/Cancel” (level 1 mode)
“Control output 1 assignment” “Control output 2 assignment” “Auxiliary output 1
assignment” (setup mode)
· The “MV at stop” parameter sets the manipulated variable when operation stops on
a standard type controller. On a position-proportional type controller, this parameter
sets the action (close/hold/open) when operation stops.
Function
· The “MV at PV error” parameter sets the manipulated variable when an input error
occurs. On a position-proportional type controller, this parameter sets the action
(close/hold/open) when an input error occurs.
· Standard type
Control Method Setting Range Unit Default
Standard -5.0 to 105.0 % 0
Comment Heating and cooling -105.0 to 105.0 % 0
The manipulated variable at the cooling side during heating and cooling control is
expressed as a negative value.
· Position-proportional type
Setting Range Unit Default
[ ]: Hold/[ ]: Open/[ ]: Close None
F Related articles
MV at stop : 3.6 Starting and Stopping Operation (page 3-13)
MV at PV error : 8.2 How to Use the Error Display (page 8-3)
See
5--21
E5AK
CHAPTER 5 PARAMETERS
Level 2 Mode
· The “MV upper limit” and “MV lower limit” parameters set the upper and lower lim-
its of the manipulated variable. When the manipulated variable calculated by the
Function
E5AK controller is outside of the upper-and lower-limit range, the upper limit or
lower limit set to these parameters is output, respectively.
However, note that these parameters are disabled during position-proportional con-
trol.
· The “MV change rate limit” parameter sets the maximum permissible change width
per second of the manipulated variable (on the position-proportional control, valve
opening). If a change in the manipulated variable (on the position-proportional con-
trol, valve opening) causes this parameter setting to be exceeded, the calculated value
is reached while changing the value by the per-second value set in this parameter.
This function is disabled when the set value is “0.0”.
· MV upper limit
The setting ranges during standard control and heating and cooling control are dif-
Comment
ferent. Also, the manipulated variable at the cooling side during heating and cooling
control is expressed as a negative value.
· MV lower limit
The setting ranges during standard control and heating and cooling control are dif-
ferent. Also, the manipulated variable at the cooling side during heating and cooling
control is expressed as a negative value.
F Related article
4.2 Operating Condition Restrictions/Manipulated variable restrictions (page 4-5)
See
5--22
E5AK
Level 2 Mode
· Sets the time constant of the input digital filter. The following figures shows the effect
on data after passing through the digital filter.
Function PV before passing through filter
A
PV after passing through filter
0.63A
Time
constant Time
Comment
Comment
F Related article
4.1 Selecting the Control Method/Position-proportional Control (page 4-3)
See
E5AK-PRR2 AC100-240
E5AK-PRR2 AC/DC24
Model
5--23
E5AK
CHAPTER 5 PARAMETERS
Level 2 Mode
Function
Comment
F Related article
3.4 Setting Alarm Type (page 3-9)
See F Related parameters
“Alarm 1 type” “Alarm 2 type” “Alarm 3 type” “Alarm 1 open in alarm” “Alarm 2 open
in alarm” “Alarm 3 open in alarm” (setup mode)
“Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode)
· Sets each of the shift amounts for the input shift upper and lower limit values.
Function
Comment
F Related article
3.2 Setting Input Specifications (page 3-4)
See F Related parameter
“Input type” (setup mode)
5--24
E5AK
Setup Mode
· The parameters in this mode can be used only when the “security” parameter (pro-
tect mode) is set to “0” and “1”.
· This mode contains the parameters for setting the basic specifications of the E5AK
controller. These parameters include parameters for specifying the input type, scal-
ing, output assignments, and direct/reverse operation.
· To select this mode when in the levels 0 to 2, expansion, option and calibration modes,
press the key for 1 second minimum. The display changes to the menu display.
If you select [ ] using the key then press the key for 1 second mini-
mum, the controller enters the setup mode.
· To select parameters in this mode, press the key. To change parameter settings,
use the or keys.
· The following table shows the parameters supported in this mode and the page where
the parameter is described.
Symbol Parameter Name Page
Input type 5-26
5--25
E5AK
CHAPTER 5 PARAMETERS
Setup Mode
Input type
Function
· Set the code according to the following table. Default is “2: K1 thermocouple”.
Set value Input Type
0 JPt -199.9 to 650.0 (_C) /-199.9 to 999.9 (_F)
Comment Platinum resistance thermometer
1 Pt -199.9 to 650.0 (_C) /-199.9 to 999.9 (_F)
2 K1 -200 to 1300 (_C) /-300 to 2300 (_F)
3 K2 0.0 to 500.0 (_C) /0.0 to 900.0 (_F)
4 J1 -100 to 850 (_C) /-100 to 1500 (_F)
5 J2 0.0 to 400.0 (_C) /0.0 to 750.0 (_F)
6 T -199.9 to 400.0 (_C) /-199.9 to 700.0 (_F)
7 E 0 to 600 (_C) /0 to 1100 (_F)
8 L1 -100 to 850 (_C) /-100 to 1500 (_F)
9 L2 0.0 to 400.0 (_C) /0.0 to 750.0 (_F) Thermocouple
10 U -199.9 to 400.0 (_C) /-199.9 to 700.0 (_F)
11 N -200 to 1300 (_C) /-300 to 2300 (_F)
12 R 0 to 1700 (_C) /0 to 3000 (_F)
13 S 0 to 1700 (_C) /0 to 3000 (_F)
14 B 100 to 1800 (_C) /300 to 3200 (_F)
15 W 0 to 2300 (_C) /0 to 4100 (_F)
16 PLII 0 to 1300 (_C) /0 to 2300 (_F)
17 4 to 20mA
Current input
18 0 to 20mA
19 1 to 5V
20 0 to 5V Voltage input
21 0 to 10V
F Related article
3.2 Setting Input Specifications (page 3-4)
See F Related parameters
When input type is set to temperature input:
“_C/_F selection” (setup mode)
When input type is set to voltage input or current input:
“Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode)
5--26
E5AK
Setup Mode
Decimal point
· This parameter can be used only when voltage input or current input is selected as
the input type.
· When voltage input or current input is selected as the input type, scaling is carried
Function
out. Set the scaling upper limit in the “scaling upper limit” parameter and the scaling
lower limit in the “scaling lower limit” parameter.
· The “decimal point” parameter specifies the decimal point position of parameters
(set point, etc.) whose unit is set to EU (Engineering Unit).
F Related article
3.2 Setting Input Specifications (page 3-4)
F Related parameter
See
“Input type” (setup mode)
Parameter initialize
· Returns parameter settings to their defaults. However, note that the following
parameters are not affected by execution of this parameter:
“input type”, “scaling upper limit”, “scaling lower limit”, “decimal point” and
Function
“_C/_F selection”.
Example
of use
5--27
E5AK
CHAPTER 5 PARAMETERS
Setup Mode
Comment
F Related article
3.2 Setting Input Specifications (page 3-4)
F Related parameter
See
“Input type” (setup mode)
Symbol
Control output Control output
Function Alarm 1 Alarm 2 Alarm 3 HBA LBA
(heat) (cool)
Comment
Defaults:
“Control output 1” = [ ], “Control output 2” = [ ]
F Related article
3.3 Setting Output Specifications (page 3-6)
F Related parameters
See
· Alarm-related parameters
· Heating and cooling related parameter
“LBA detection time” (level 2 mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
5--28
E5AK
Setup Mode
Symbol
Function Alarm 1 Alarm 2 Alarm 3 HBA LBA Error 1 Error 2 Error 3
F Related article
3.3 Setting Output Specifications (page 3-6)
See F Related parameter
· Alarm-related parameter
“LBA detection time” (level 2 mode)
5--29
E5AK
CHAPTER 5 PARAMETERS
Setup Mode
· “Alarm 1 to 3 type” parameters specify the operation of the alarm by the one of the
set values in the following table. For details of operation at an alarm, see page 3-9.
Function
F Related article
3.4 Setting Alarm Type (page 3-9)
See F Related parameters
“Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode)
“Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode)
“Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” “Control
output 1 assignment” “Control output 2 assignment” “Auxiliary output 1 assign-
ment” “Auxiliary output 2 assignment” (setup mode)
5--30
E5AK
Setup Mode
Comment
F Related article
3.4 Setting Alarm Type (page 3-9)
See F Related parameters
“Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode)
“Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode)
“Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm”
“Control output 1 assignment” “Control output 2 assignment” “Auxiliary output 1
assignment” “Auxiliary output 2 assignment” (setup mode)
Direct/Reverse operation
· “Direct operation” (or normal operation) refers to control where the manipulated
variable is increased according to the increase in the process value. Alternatively,
Function
“reverse operation” refers to control where the manipulated variable is increased
according to the decrease in the process value.
Comment
F Related article
3.3 Setting Output Specifications/Direct/reverse operation (page 3-7)
See
5--31
E5AK
CHAPTER 5 PARAMETERS
Expansion Mode
· The parameters in this mode can be used only when the “security” parameter (pro-
tect mode) is set to “0” and “1”.
· This mode contains the parameters for setting expanded functions. These parame-
ters include parameters for setting ST (self-tuning), setting the SP setting limiter,
selecting advanced PID and ON/OFF control, specifying the standby sequence reset
method, and automatic return of display mode.
· To select this mode when in the levels 0 to 2, setup, option and calibration modes,
press the key for 1 second minimum. The display changes to the menu display.
If you select [ ] using the key then press the key for 1 second mini-
mum, the controller enters the expansion mode.
· To select parameters in this mode, press the key. To change parameter settings,
use the or keys.
· The following table shows the parameters supported in this mode and the page where
the parameter is described.
Symbol Parameter Name Page
Set point upper limit 5-33
ST 5-34
a 5-34
AT hysteresis 5-36
5--32
E5AK
Expansion Mode
· Limits the upper and lower limits of the set point. When the set point exceeds the set-
tings of the “Set point upper limit” and “Set point lower limit” parameters, the E5AK
controller regards the settings of the “Set point upper limit” and “Set point lower
Function
limit” parameters as the set points.
· When the input type is changed to temperature input, the set point upper and lower
limits are changed to the upper and lower limits of the currently selected sensor. And
when the input type is changed to analog input, the set point upper and lower limits
are changed to the scaling upper and lower limits.
· During temperature input, the decimal point position is dependent on the currently
selected sensor, and during analog input on the results of scaling.
F Related article
4.2 Operating Condition Restrictions (page 4-5)
F Related parameters
See
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup
mode)
Function
Setting Range Default
[ ] : advance PID/ [ ] :ON/OFF [ ]
Comment
F Related article
4.1 Selecting the Control Method/ON/OFF control (page 4-4)
F Related parameters
See
“Hysteresis (heat)” “Hysteresis (cool)” (level 1 mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
5--33
E5AK
CHAPTER 5 PARAMETERS
Expansion Mode
ST Conditions of Use
The input type must be set to temperature
input, and the control must be standard
ST stable range control and advanced PID control.
· When the “ST” parameter is set to “ON”, the self-tuning (ST) function is active. Dur-
ing operation of the ST function, the power on the load side connected to the control
Function
output must be turned ON at the same time or before start of E5AK operation.
· The “ST stable range” parameter sets the stable range width during self-tuning.
However, note that this parameter cannot be used when the “ST” parameter is set to
“OFF”.
F Related article
Fuzzy self-tuning (page A-14)
See F Related parameters
“Input type” (setup mode)
“PID / ON/OFF” (expansion mode)
a Conditions of Use
The control must be advanced PID con-
trol, and ST must be set to OFF.
Comment
F Related parameter
“PID / ON/OFF” (expansion mode)
See
5--34
E5AK
Expansion Mode
Comment
F Related parameters
“AT Execute/Cancel” (level 1 mode)
See
“PID / ON/OFF” (expansion mode)
· Selects the conditions for enabling reset after the standby sequence of the alarm has
been canceled.
Function · Condition A:
Control started (including power ON), and alarm value, input shift value or set point
(except for changing SP mode or during Remote SP) changed.
· Condition B:
Power ON
Comment
F Related parameters
“Alarm 1 type” “Alarm 2 type” “Alarm 3 type” (setup mode)
See
5--35
E5AK
CHAPTER 5 PARAMETERS
Expansion Mode
· If you do not operate any of the controller keys for the time set in this parameter when
in levels 0 to 2 modes, the display automatically returns to the PV/SP display.
Function · When this parameter is set to “0”, this function is disabled.
· This parameter is invalid while the menu is displayed.
Comment
Comment
Comment
5--36
E5AK
Option Mode
· The parameters in this mode can be used only when the “security” parameter (pro-
tect mode) is set to “0” and “1”.
· You can select this mode only when the option unit is set in the controller. In this
mode, you can set the communications conditions, transfer output and event input
parameters to match the type of option unit set in the controller.
· To select this mode when in the levels 0 to 2, setup, expansion and calibration modes,
press the key for 1 second minimum. The display changes to the menu display.
If you select [ ] using the key then press the key for 1 second mini-
mum, the controller enters the option mode.
· To select parameters in this mode, press the key. To change parameter settings,
use the or keys.
· The following table shows the parameters supported in this mode and the page where
the parameter is described.
Symbol Parameter Name Page
Multi-SP function 5-38
Event input assignment 1 5-39
Event input assignment 2 5-39
5--37
E5AK
CHAPTER 5 PARAMETERS
Option Mode
· This parameter specifies the number of event inputs when switching set points (SP)
0 to 3.
Function · When set to “0”, the set point cannot be switched by event input.
· When this parameter is set to “1”, set points 0 and 1 can be used. When set to “2”, set
points 0 to 3 can be used.
Comment
F Related article
4.3 How to Use Event Input (4-8)
See F Related parameter
“Event input assignment 1” (option mode)
F Option unit
E53-AKB
Model
5--38
E5AK
Option Mode
Conditions of Use
Event input other than the multi-SP func-
tion must be specified when the event
input function is in use.
· When one E53-AKB unit is mounted, only “Event input assignment 3” and “Event
input assignment 4” can be used.
Function · This parameter specifies event input other than the multi-SP function. The following
four functions can be specified:
Run/Stop, Remote/Local, Auto/Manual, SP mode.
The Remote/Local function can be used on E53-AK01/02/03 option units. The SP
mode functions can be used only when the ”Remote SP enable” parameter is ON.
· Event input (Run/Stop, Manual/Auto, and SP mode) is disabled while the menu is dis-
played.
It is also disabled in set up, expantion, option and calibration modes.
· Default
E53-AKB×1 E53-AKB×2
Event input assignment 1 --
Event input assignment 2 --
Event input assignment 3
Event input assignment 4
F Related article
4.3 How to Use Event input (page 4-8)
See F Related parameters
“remote SP enable” “multi-SP function” (option mode)
F Option unit
E53-AKB
Model
5--39
E5AK
CHAPTER 5 PARAMETERS
Option Mode
· These parameters set the communications conditions. Make sure that the stop bit,
data length, parity and baud rate of the host computer and the E5AK controller are
Function
matching. These parameters are valid when the power is turned ON again or when
level 0 to 2 modes are switched.
· When connecting two or more E5AK controllers to the host computer, set unit Nos.
that will not conflict with the unit Nos. of other controllers.
Setting Default
[ ]: None/ [ ]:Even/[ ]:Odd [ ]
F Related article
Chapter6 USING THE COMMUNICATIONS FUNCTION
See F Related parameter
“Remote/Local” (level 2 mode)
F Option unit
E53-AK01/02/03
Model
5--40
E5AK
Option Mode
· Default : [ ]
· The output ranges of the set point, set point during SP ramp or process value when
temperature input is selected are the ranges supported by the selected sensor.
· When you have selected the “manipulated variable (heat)” parameter, the transfer
output lower limit during heating and cooling control becomes “0.0”.
F Related article
4.7 How to Use Transfer Output (page 4-17)
See
F Option unit
E53-AKF
Model
5--41
E5AK
CHAPTER 5 PARAMETERS
Option Mode
· When this parameter is set to ON, the heater burnout alarm is held until either of the
following conditions is satisfied:
Function
a Set the heater burnout set value to “0.0”.
b Reset the controller. (Turn the controller’s power OFF then back ON again.)
Comment
F Related article
4.5 How to Use the Heater Burnout Alarm (page 4-13)
See F Related parameters
“Control output assignment 1” “Control output assignment 2” “Auxiliary output
assignments 1” “Auxiliary output assignments 2” (setup mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
· Executes motor calibration. Be sure to execute this parameter when monitoring the
valve opening. (Displays cannot be switched while motor calibration is being
executed.)
Function
· The “travel time” parameter is also reset when this parameter is executed.
F Related article
4.1 Selecting the Control Method/Position-proportional Control (page 4-3)
F Related parameter
See
“Travel time” (option mode)
E5AK-PRR2 AC100-240
E5AK-PRR2 AC/DC24
Model
5--42
E5AK
Option Mode
· Sets the time from valve fully opened to valve fully closed.
· The travel time is automatically set when the “motor calibration” parameter is
Function
executed.
Comment
F Related article
4.1 Selecting the Control Method/Position-proportional Control (page 4-3)
See
F Related parameter
“Motor Calibration” (option mode)
E5AK-PRR2 AC100-240
E5AK-PRR2 AC/DC24
Model
Process value
· This function is for use to reduce valve movement, but consequently reduces control
performance within the PV deadband.
· The decimal point is dependent on scaling.
Comment
F Related parameters
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode)
See
E5AK-PRR2 AC100-240
E5AK-PRR2 AC/DC24
Model
5--43
E5AK
CHAPTER 5 PARAMETERS
Option Mode
· When this parameter is set to “ON”, the remote SP and local SP can be switched for
use. (That is, to the SP mode can be specified.). Also, the “set point during SP ramp”
Function
parameter is enabled at all times.
· When this parameter is set to “OFF”, only the local SP can be used. The set point dur-
ing SP ramp is enabled only when the SP ramp function is enabled.
Comment
F Related article
4.4 How to Use the Remote SP (page 4-11)
See F Related parameters
“Set point during SP ramp” (level 0 mode)
“SP mode” (level 2 mode)
· Sets the remote SP upper and lower limit values. The upper limit value is the equiva-
lent to 20 mA, and the lower limit value is equivalent to 4 mA. Set the upper limit
Function
value in the “remote SP upper limit” parameter and the lower limit value in the
“remote SP lower limit” parameter.
RSP (%)
· When the “SP setting upper limit” or “SP setting lower limit” parameters are
changed, the remote SP upper and lower limit values are forcibly changed to the SP
setting upper and lower limit values.
5--44
E5AK
Option Mode
F Related article
4.4 How to Use the Remote SP (page 4-11)
See F Related parameters
“Decimal point” (setup mode)
“SP setting upper limit” “SP setting lower limit” (expansion mode)
“Remote SP enable” (option mode)
· Specifies the operation when the remote SP mode is switched to the local SP mode.
· When this parameter is set to “ON”, the local SP is changed to the remote SP value
Function used immediately before switching.
· When this parameter is set to “OFF”, the local SP is not influenced by the remote SP.
Comment
F Related article
4.4 How to Use the Remote SP (page 4-11)
See F Related parameters
“Set point during SP ramp” (level 0 mode)
“SP mode” (level 2 mode)
5--45
E5AK
CHAPTER 5 PARAMETERS
Calibration Mode
· The parameters in this mode can be used only when the “security” parameter (pro-
tect mode) is set to “0”. When selecting this mode for the first time after the E5AK
has left the factory, return the “security” parameter to “0”.
· This mode contains the parameters for user calibration of inputs and outputs. Only
parameters relating to input types specified in the “input type” parameter (setup
mode) can be used. Also, related output parameters can be used only when the com-
munications unit (E53-AKF) is added on.
· To select this mode when in the levels 0 to 2, setup, expansion and option modes, press
the key for 1 second minimum. The display changes to the menu display. If you
select [ ] using the key then press the key for 1 second minimum,
the controller enters the calibration mode.
· For details on parameters in the calibration mode, see Chapter 7 Calibration.
5--46
E5AK
CHAPTER 6 6
USING THE
COMMUNICATIONS
FUNCTION
This chapter mainly describes communications with a host computer
and communications commands.
6.1 Outline of
the Communications Function . . . . . . . . . . 6-2
Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Transfer procedure . . . . . . . . . . . . . . . . . . . . . 6-2
Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.2 Preparing for Communications . . . . . . . . . . 6-3
Cable connections . . . . . . . . . . . . . . . . . . . . . . 6-3
Setting the communications specifications 6-4
6.3 Command Configuration . . . . . . . . . . . . . . . . 6-5
6.4 Commands and Responses . . . . . . . . . . . . . . 6-6
Reading/writing parameters . . . . . . . . . . . . . 6-6
Issuing special commands . . . . . . . . . . . . . . . 6-10
6.5 How to Read Communications
Error Information . . . . . . . . . . . . . . . . . . . . . 6-12
End code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
Undefined error . . . . . . . . . . . . . . . . . . . . . . . . 6-13
6.6 Program Example . . . . . . . . . . . . . . . . . . . . . . 6-14
How to use programs . . . . . . . . . . . . . . . . . . . 6-14
Program list (language:
IBM PC COMPATIBLE MACHINE) . . . . . 6-15
Examples of use . . . . . . . . . . . . . . . . . . . . . . . . 6-16
6--1
E5AK
J Outline The communications function allows you to monitor and set E5AK
parameters by a program prepared and running on a host computer con-
nected to the E5AK controller. This chapter describes operations as
viewed from the host computer.
When using the communications function, the option unit for RS-232C,
RS-422 or RS-485 communications must be added on. The E5AK commu-
nications function allows you to carry out the following:
· Reading/writing of parameters;
· Operation instructions; and
· Selecting the setting level.
J Transfer The host computer sends a “command frame” to the controller, and the
controller returns a “response frame” corresponding to the content of the
procedure
command sent by the host computer. In other words, a response frame is
returned for each command frame sent.
The following diagram shows command frame/response frame opera-
tions.
Command frame Command frame
Host computer
E5AK
Response frame
6--2
E5AK
For details on wiring when using the communications, see Chapter 2 Prep-
arations.
J Cable connections
F RS-232C · Only one controller can be connected to the host computer.
· The cable length should not exceed 15 meters.
· Use shielded twisted-pair cables (AWG28 or more) for the cables.
25 pins 9 pins
E5AK E5AK
IBM-PC/XT IBM-PC/AT
DE-25 DE-25
Female Female
DTE RS-232C DTE RS-232C
No. No.
(SD) TXD 2 (RD) RXD 2
20 SD 20 SD
(RD) RXD 3 19 RD (SD) TXD 3 19 RD
18 SG 18 SG
(RS) RTS 4 (ER) DTR 4
(CS) CTS 5 (SG) COMMON 5
(DR) DSR 6 (DR) DSR 6
6--3
E5AK
-
+
Terminator
(120W 1/2W)
FG
E5AK (No.0) E5AK (No.30)
RS-485 RS-485
No. No.
32 A 32 A
31 B 31 B
19 A 19 A
20 B 20 B
J Setting the com- Match the communications specifications of the host computer and E5AK
munications controller. When two or more controllers are connected to the host com-
specifications puter, make sure that the communications specifications of all controllers
are the same.
This section describes how to set the communications specifications of the
E5AK controller. For details on the host computer, see the relevant manual
supplied with the host computer.
6--4
E5AK
2B 1B 2B 4B 2B 2B
Unit Command Data FCS
Command
No. code
@ * CR
Command type
No data sections in the read commands.
2B 1B 2B 2B 4B 2B 2B
Unit Command End Data FCS
Response code
No. code
@ * CR
End code = 00
Command type
2B 1B 2B 2B 2B 2B
Unit Command End FCS
Response
No. code code
@ * CR
End code = 00
Command type
· “@”
The start character. This character must be inserted before the leading
byte.
· Unit No.
Specifies the “unit No.” of the E5AK. If there are two or more transmis-
sion destinations, specify the desired destination using “unit No.”
· Command type
Specifies the command type by codes “1” to “3”: parameter read, param-
eter write and special commands.
· Command code
Specifies the command for each command type. With parameter read/
write commands, this becomes the parameter No.
· Data
Specifies the set value or setting content. In the parameter read com-
mand, set dummy data “0000”. In the response, this is inserted only
when the end code is “00”.
· End code
Sets the communication results. For details on the types and meanings
of end codes, see 6.5 How to Read Communications Error Information
(page 6-12).
· FCS (Frame Check Sequence)
Set the frame check results from the start character to the data section.
For details on the frame check, see 6.6 Program Example (page 6-14).
· “*” “CR (Carriage Return) code”
Indicates the end (terminator) of the command or response block.
6--5
E5AK
J Reading/writing parameters
F Reading parameters
2B 2B 4B 2B 2B
Unit Parameter FCS
Command No.
No.
@ 1 X X X X * CR
X: Any value acceptable
2B 2B 2B 4B 2B 2B
Unit Parameter End Read data FCS
Response No. No.
code
@ 1 * CR
F Writing parameters
2B 2B 4B 2B 2B
Unit Parameter Write data FCS
Command No.
No.
@ 2 * CR
2B 2B 2B 4B 2B 2B
Unit Parameter End Write data FCS
Response No. No.
code
@ 2 * CR
6--6
E5AK
*1 L
Level
l0
42 MV monitor (cool) 0.0 to 105.0
24 Remote SP monitor *1 Scaling lower limit to scaling upper limit
14 Valve opening monitor *1 -10.0 to 110.0
01 Set point SP lower limit to set point upper limit
10 Set point 0 SP lower limit to SP upper limit
11 Set point 1 SP lower limit to SP upper limit
12 Set point 2 SP lower limit to SP upper limit
13 Set point 3 SP lower limit to SP upper limit
02 Alarm value 1 -1999 to 9999
03 Alarm value 2 -1999 to 9999
41 Alarm value 3 -1999 to 9999
19 Proportional band 0.1 to 999.9
0 to 3999 *4
20 Integral time
21 Derivative time 0 to 3999
22 Cooling coefficient 0.01 to 99.99 Level 1
About invalid Currently, if a command is used for invalid parameters (parameters that do not sat-
parameters isfy the conditions of use in Chapter 5), the “undefined” error (end code: 1C) is out-
put.
6--7
E5AK
-5.0 to 105.0 *1
48 MV at PV error
MV lower limit +0.1 to 105.0 *2
50 MV upper limit
-5.0 to MV upper limit -0.1 *3
49 MV lower limit
51 MV change rate limit 0.0 to 100.0 Level 2
56 Input digital filter 0 to 9999
88 Open/close hysteresis 0.1 to 20.0
25 Alarm 1 hysteresis 0.01 to 99.99
26 Alarm 2 hysteresis 0.01 to 99.99
52 Alarm 3 hysteresis 0.01 to 99.99
53 Input shift upper limit -199.9 to 999.9
54 Input shift lower limit -199.9 to 999.9
0 to 21 *4
57 Input type
59 Scaling upper limit Scaling lower limit +1 to 9999
58 Scaling lower limit -1999 to scaling upper limit -1
60 Decimal point 0 to 3
30 _C/_F selection 0 : _C, 1 : _F
0 to 6 *5
61 Control output 1 assignment
0 to 6 *5
62 Control output 2 assignment
2 to 9 *5
63 Auxiliary output 1 assignment
*5
Setup
64 Auxiliary output 2 assignment 2 to 9
1 to 11 *6
65 Alarm 1 type
66 Alarm 1 open in alarm 0: closed in alarm, 1: open in alarm
1 to 11 *6
67 Alarm 2 type
68 Alarm 2 open in alarm 0: closed in alarm, 1: open in alarm
1 to 11 *6
69 Alarm 3 type
70 Alarm 3 open in alarm 0: closed in alarm, 1: open in alarm
71 Direct/Reverse operation 0: Reverse operation, 1: Direct operation
*1 During heating and cooling control, the range becomes -105 to 105.0. During position-proportional control, you can select between
*1 0: Hold/1: Open/2: Close. (Default is 0: Hold.)
*2 During heating and cooling control, the range becomes 0.0 to 105.0.
*3 During heating and cooling control, the range becomes -105.0 to 0.0
*4 See page 5-26.
*5 0: Control output (heat), 1: Control output (cool), 2: to 4: Alarms 1 to 3, 5: HBA, 6: LBA, 7 to 9: Errors 1 to 3
*6 See page 5-30.
6--8
E5AK
--1 to 3 *3
78 Event input assignment 4
0 to 5 *4
79 Transfer output type
*4
81 Transfer output upper limit
*4
80 Transfer output lower limit
82 HBA latch 0: OFF, 1: ON Option
p
89 Travel time 1 to 999
38 PV dead band 0 to 9999
29 Remote SP enable 0: Enabled, 1: Disabled
91 Remote SP upper limit SP setting lower limit to SP setting upper limit
90 Remote SP lower limit SP setting lower limit to SP setting upper limit
39 SP tracking 0: OFF, 1: ON
*1 During temperature input, the range becomes the range of use of the selected sensor instead of the scaling upper/lower limit values
*2 See page 5-35.
*3 - -1: No specification, 0: Run/Stop, 1: Remote/Local, 2: Auto/Manual, 3: SP mode
*4 The following table shows the output ranges of the Transfer output lower and upper limits.
3: Manipulated variable (heat) -5.0% to 105.0% (Standard control), 0.0 to 105.0% (heat-
ing and cooling control)
4: Manipulated variable (cool) 0.0% to 105.0%
6--9
E5AK
6--10
E5AK
F A group
Bit Description [1] [0]
0 Heating side output *3 ON OFF *1
F B group
Bit Description [1] [0]
0 Setting level 1 0
1 RAM write mode RAM Backup
2 Control output 1 type Linear Pulse
3 Control output 2 type Linear Pulse
4 EEPROM RAM¸EEPROM RAM = EEPROM
5 Input error ON OFF
6 A/D converter error ON OFF
7 CT overflow ON OFF
8 CT hold ON OFF
9 Potentiometer error ON OFF
10 RSP input error ON OFF
11
12
13
14
15
To return to setting level 0 from setting level 1, issue the “software reset” command.
About Setting Levels If the parameter write command is issued for the setup and expansion modes in set-
ting level 0, an error occurs, and the end code (0D = Command cannot be executed)
is returned.
6--11
E5AK
The result of communications on the E5AK can be checked by the end code in the response frame. Use this
end code to remedy errors that may occur.
J End code Communications are normal when the end code in the response is “00”.
If the end code is not “00”, this indicates that an error other that is not an
undefined error has occurred. The end code format is as follows and does
not contain a data area.
2B 1B 2B 2B 2B 2B
Unit Command End FCS
No. code code
@ * CR
Command type
About the unit No. Responses are not returned unless the target unit for communications and the unit
No. in the command match.
6--12
E5AK
F Description The received command length does not match the length defined in the
frame format.
F Description Numerical values or code values in the data are not within the setting
range.
F Action Check the parameter and read or write data of special commands.
J Undefined error
2B 2B 2B 2B
Unit FCS
No.
@ I C * CR
6--13
E5AK
2B 1B 2B 4B 2B 2B
Unit Command Data FCS
No. code
@ * CR
Command type
The output format is as follows. The content of the response frame is displayed as it is.
2B 1B 2B 2B 4B 2B 2B
Unit Command End Data FCS
No. code code
@ * CR
Command type
F Procedure
(1) Read the program.
(2) Enter “RUN”.
(3) When “send data:” is displayed, enter the command data (from @ to the command
string).
(4) The content of the response frame is displayed following “receive data:”.
6--14
E5AK
1000 ’
1010 ’ PROGRAM : E5AK Communication Program
1020 ’ For IBM PC COMPATIBLE MACHINE
1050 ’
1060 ’ RS-232C SPEED: 9600BPS, PARITY: EVEN, DATA: 7, STOP: 2
1070 OPEN ”COM: 9600, E, 7, 2, CD0, CS0, DS0, RB256, RS ”FOR RANDAM AS #1 LEN=256
1080 REPEAT
1090 ’ Make Command
1100 PRINT ”send data : ” ;
1110 INPUT SEND$
1120 ’ FCS calculation
1130 FCS=0
1140 FOR IFCS=1 TO LEN (SEND$)
1150 FCS=FCS XOR ASC (MID$ (SEND$, IFCS, 1))
1160 NEXT
1170 FCS$=RIGHT$ (”0”+HEX$ (FCS), 2)
1180 ’ Send data to communication port
1190 PRINT #1, SEND$+FCS$+”*”
1200 ’ Receive data from communication port
1210 RECCNT=0: TMP$=””
1220 DRECLOOP:
1230 IF LOC (1) <> 0 THEN DREC1
1240 RECCNT=RECCNT+1
1250 IF RECCNT=5000 THEN *DRECERR ELSE DRECLOOP
1260 ‘DREC1
1270 TMP$=TMP$+INPUT$ (LOC (1), #1)
1280 IF RIGHT$ (TMP&, 1)=CHR$ (13) THEN DRECEND
ELSE RECCNT=0: GOTO DRECLOOP
1290 DRECERR:
1300 TMP$=”No response !!”
1310 DRECEND:
1320 RECV$=TMP$
1330 PRINT ”response: ”; RECV$
1340 ’ Repeat to make Command
1350 ’ GOTO REPEAT
1360 ’ END
1370 CLOSE #1
1380 END
6--15
E5AK
J Examples of use
F Set the unit No. to “00”
· In the following examples, data is shown in individual blocks to make the examples
easier to understand. However, when actually creating programs, do not leave spaces
between frame items. Also, response are displayed without spaces between frame
items.
· Response
@ 00 2 01 00 3000 (FCS) *
Normal end
F Start running
· Input data
@ 00 3 00 0000
Run
Run/Stop
Special command
· Response
@ 00 3 00 00 0000 (FCS) *
Normal end
· Response
@ 00 1 00 00 2000 (FCS) *
Process value = 2000
Normal end
6--16
E5AK
CHAPTER 7 CALIBRATION
CHAPTER 7 7
CALIBRATION
This chapter describes procedures for each calibration operation.
Read this chapter only when the controller must be calibrated.
7--1
E5AK
CHAPTER 7 CALIBRATION
Platinum resistance
Thermocouple thermometer Current input Voltage input
Transfer output
· To select the desired parameter, press the key. Parameters are dis-
played in the following order:
Calibration of inputs ® Calibration of transfer output ®
Saving of calibration data
If the E5AK controller does not support the transfer output function,
calibration of transfer output is automatically deleted from the calibra-
tion procedure as follows:
Calibration of inputs ® Saving of calibration data
· Only inputs that have been set in the “input type” parameter (setup
mode) can be calibrated. To temporarily save data for each of the calibra-
tion parameters, press the key for 1 second.
· Transfer output can be calibrated only when the communications unit
(E53-AKF) is set in the controller. To adjust data items, press the
or keys.
· The data save menu is displayed only when all calibration items have
temporarily been saved.
· After calibrating input, you must always check indication accuracy. For
details, see page 7-12.
7--2
E5AK
F Calibration item · Parameters are displayed on the No.1 display, and the process value is
menu displayed in Hexadecimal on the No.2 display.
Calibration item · Normally, the process value changes by several digits. The process value
parameter flashes, for example, when a sensor error causes the process value to
Process value stray from the calibration target range.
· When the process value display is flashing, the process value is not saved
as data even if the key is pressed.
F Calibration save · Once the E5AK controller has been calibrated by the user, [ ] is pre-
mark ceded by the “.” mark when the calibration mode is selected.
7--3
E5AK
CHAPTER 7 CALIBRATION
F Preparations
AC100-240V ~
(AC/DC24V )
10 30 31 32 20
SOURCE
9 29 19
8 28 18
7 27 17
6 26 16
5 25 15 STV
4 24 14
3 23 13 Cold junction
2 22 12 compensator
1 21 33 11 0_C/32_F
Compensating
DMM conductor
· Set the cold junction compensator to 0_C. However, make sure that
internal thermocouples are disabled (tips are open).
· In the above figure, STV refers to a standard DC current/voltage source,
and DMM refers to a precision digital multimeter.
However, note that DMM is required only when the transfer output
function is supported.
· Use the compensating conductor selected thermocouple. However, note
that when thermocouple R, S, E, B, W or PLII is used, the cold junetion
compensator and the compensating conductor can be substituted with
the cold junction compensator and the compensating conductor for
thermocouple K.
Connecting the Correct process values cannot be obtained if you touch the contact ends of the com-
Cold Junction Con- pensating conductor during calibration of a thermocouple. Accordingly, short
ductor (enable) or open (disable) the tip of the compensating conductor inside the cold junc-
tion compensator as shown in the figure below to create a contact or non-contact
state for the cold junction compensator.
Cold junction Cold junction
compensator compensator
Short
E5AK E5AK
controller 0°C/32°F controller 0°C/32°F Open
7--4
E5AK
F Calibration: This example describes how to calibrate a thermocouple when the transfer
thermocouple 1 output function is supported. If the transfer output function is not sup-
ported, skips steps (7) to (10).
(1) When [ ] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) First, calibrate the main input. Press the key to display [ ]
(50mV calibration display). Set STV output to 50mV. When the value
on the No.2 display has stabilized (changes of several digits max.),
press the key to temporarily save the calibration data.
(3) Press the key to display [ ] (0mV calibration display). Set
STV output to 0mV. When the value on the No.2 display has stabilized
(changes of several digits max.), press the key to temporarily save
the calibration data.
(4) Next, calibrate the cold junction compensator. Press the key to
display [ ] (310mV calibration display). Set STV output to
310mV. When the value on the No.2 display has stabilized (changes of
several digits max.), press the key to temporarily save the calibra-
tion data.
(5) Press the key to display [ ] (0mV calibration display). Set
STV output to 0mV. When the value on the No.2 display has stabilized
(changes of several digits max.), press the key to temporarily save
the calibration data.
(6) Finally, calibrate the bias compensation value. Disconnect the STV,
and enable the thermocouple of the cold junction compensator. When
carrying this out, make sure that the wiring on the STV is discon-
nected.
Make sure that the cold junction compensator is set to 0_C and press
the key. The display changes to [ ] (calibration display for the
bias compensation value). When the value on the No.2 display has sta-
bilized (changes of several digits max.), press the key to tempo-
rarily save the calibration data.
(7) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (11). Press the key. The dis-
play changes to [ ] (20mA calibration display).
(8) Set the output to 20mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “20mA”.
(9) Press the key. The display changes to [ ] (4mA calibration
display).
(10) Set the output to 4mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “4mA”.
(11) Press the key until the display changes to the data save display.
Press the key. The No.2 display changes to [ ], and two
seconds later the calibration data is saved to internal memory. If you
press the key when the No.2 display reads [ ], the calibration
data is invalidated.
(12) This completes calibration of the thermocouple 1 group. Press the
key to return the display to [ ].
7--5
E5AK
CHAPTER 7 CALIBRATION
F Calibration: This example describes how to calibrate a thermocouple when the transfer
thermocouple 2 output function is supported. If the transfer output function is not sup-
ported, skips steps (7) to (10).
(1) When [ ] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) First, calibrate the main input. Press the key to display [ ]
(20mV calibration display). Set STV output to 20mV. When the value
on the No.2 display has stabilized (changes of several digits max.),
press the key to temporarily save the calibration data.
(3) Press the key to display [ ] (0mV calibration display). Set
STV output to 0mV. When the value on the No.2 display has stabilized
(changes of several digits max.), press the key to temporarily save
the calibration data.
(4) Next, calibrate the cold junction compensator. Press the key to
display [ ] (310mV calibration display). Set STV output to
310mV. When the value on the No.2 display has stabilized (changes of
several digits max.), press the key to temporarily save the calibra-
tion data.
(5) Press the key to display [ ] (0mV calibration display). Set
STV output to 0mV. When the value on the No.2 display has stabilized
(changes of several digits max.), press the key to temporarily save
the calibration data.
(6) Finally, calibrate the bias compensation value. Disconnect the STV,
and enable the thermocouple of the cold junction compensator. When
carrying this out, make sure that the wiring on the STV is discon-
nected.
Make sure that the cold junction compensator is set to 0_C and press
the key. The display changes to [ ] (calibration display for
the bias compensation value). When the value on the No.2 display has
stabilized (changes of several digits max.), press the key to tempo-
rarily save the calibration data.
(7) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (11). Press the key. The dis-
play changes to [ ] (20mA calibration display).
(8) Set the output to 20mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “20mA”.
(9) Press the key. The display changes to [ ] (4mA calibration
display).
(10) Set the output to 4mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “4mA”.
(11) Press the key until the display changes to the data save display.
Press the key. The No.2 display changes to [ ], and two
seconds later the calibration data is saved to internal memory. If you
press the key when the No.2 display reads [ ], the calibration
data is invalidated.
(12) This completes calibration of the thermocouple 2 group. Press the
key to return the display to [ ].
7--6
E5AK
F Preparation
AC100-240V ~
(AC/DC24V )
10 30 31 32 20
SOURCE
9 29 19
8 28 18
7 27 17
6 26 16
5 25 15
4 24 14
3 23 13
2 22 12 6-dial
1 21 33 11
DMM
· Use leads of the same thickness when connecting to the platinum resis-
tance thermometer.
· In the above figure, 6-dial refers to a precision resistance box, and DMM
stands for a digital multimeter. However, note that the DMM is required
only when the transfer output function is supported.
· Connect (short) the leads from terminal Nos. 11 and 12.
7--7
E5AK
CHAPTER 7 CALIBRATION
From previous page (6) Press the key to display [ ] (0W calibration display, Short ter-
minal Nos. 11 to 13. When the value on the No.2 display has stabilized
(changes of several digits max.), press the key to temporarily
store the calibration data.
(7) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (11). Press the key. The dis-
play changes to [ ] (20mA calibration display).
(8) Set the output to 20mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “20mA”.
(9) Press the key. The display changes to [ ] (4mA calibration
display).
(10) Set the output to 4mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “4mA”.
(11) Press the key until the display changes to the data save display.
Press the key. The No.2 display changes to [ ], and two
seconds later the calibration data is saved to internal memory. If you
press the key when the No.2 display reads [ ], the calibration
data is invalidated.
(12) This completes calibration of the platinum resistance thermometer.
Press the key to return the display to [ ].
7--8
E5AK
F Preparation AC100-240V ~
(AC/DC24V )
10 30 31 32 20
SOURCE
9 29 19
8 28 18
7 27 17
6 26 16
5 25 15
4 24 14
3 23 13
--
2 22 12
1 21 33 11
+
DMM STV
This example describes how to calibrate a current input when the transfer
output function is supported. If the transfer output function is not sup-
ported, skips steps (4) to (7).
(1) When [ ] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) Press the key. The display changes to [ ] (20mA calibration
display). Set the STV output to 20mA. When the value on the No.2 dis-
play has stabilized (changes of several digits max.), press the key
to temporarily store the calibration data.
(3) Press the key. The display changes to [ ] (0mA calibration
display). Set the STV output to 0 mA. When the value on the No.2 dis-
play has stabilized (changes of several digits max.), press the key
to temporarily store the calibration data.
(4) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (8). Press the key. The dis-
play changes to [ ] (20mA calibration display).
(5) Set the output to 20mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “20mA”.
(6) Press the key. The display changes to [ ] (4mA calibration
display).
(7) Set the output to 4mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “4mA”.
(8) Press the key until the display changes to the data save display.
Press the key. The No.2 display changes to [ ], and two
seconds later the calibration data is saved to internal memory. If you
press the key when the No.2 display reads [ ], the calibration
data is invalidated.
(9) This completes calibration of current input. Press the key to
return the display to [ ].
7--9
E5AK
CHAPTER 7 CALIBRATION
F Preparation
AC100-240V ~
(AC/DC24V )
10 30 31 32 20
SOURCE
9 29 19
8 28 18
7 27 17
6 26 16
5 25 15
4 24 14 +
3 23 13
2 22 12
1 21 33 11 -- STV
DMM
F Calibration: This example describes how to calibrate voltage input when the transfer
0 to 5 V, 1 to 5 V output function is supported. If the transfer output function is not sup-
ported, skips steps (4) to (7).
(1) When [ ] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) Press the key. The display changes to [ ] (5 V calibration dis-
play). Set the STV output to 5V. When the value on the No.2 display
has stabilized (changes of several digits max.), press the key to
temporarily store the calibration data.
(3) Press the key. The display changes to [ ] (0V calibration dis-
play). Set the STV output to 0V. When the value on the No.2 display
has stabilized (changes of several digits max.), press the key to
temporarily store the calibration data.
(4) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (8). Press the key. The dis-
play changes to [ ] (20mA calibration display).
(5) Set the output to 20mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “20mA”.
(6) Press the key. The display changes to [ ] (4mA calibration
display).
(7) Set the output to 4mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “4mA”.
Cont’d on next page
7--10
E5AK
From previous page (8) Press the key until the display changes to the data save display.
Press the key. The No.2 display changes to [ ], and two
seconds later the calibration data is saved to internal memory. If you
press the key when the No.2 display reads [ ], the calibration
data is invalidated.
(9) This completes calibration of voltage input (0 to 5V, 1 to 5V). Press the
key to return the display to [ ].
F Calibration : This example describes how to calibrate voltage input when the transfer
output function is supported. If the transfer output function is not sup-
0 to 10V
ported, skips steps (4) to (7).
(1) When [ ] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) Press the key. The display changes to [ ] (10V calibration
display). Set the STV output to 10V. When the value on the No.2 dis-
play has stabilized (changes of several digits max.), press the key
to temporarily store the calibration data.
(3) Press the key. The display changes to [ ] (0V calibration dis-
play). Set the STV output to 0V. When the value on the No.2 display
has stabilized (changes of several digits max.), press the key to
temporarily store the calibration data.
(4) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (8). Press the key. The dis-
play changes to [ ] (20mA calibration display).
(5) Set the output to 20mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “20mA”.
(6) Press the key. The display changes to [ ] (4mA calibration
display).
(7) Set the output to 4mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “4mA”.
(8) Press the key until the display changes to the data save display.
Press the key. The No.2 display changes to [ ], and two
seconds later the calibration data is saved to internal memory. If you
press the key when the No.2 display reads [ ], the calibration
data is invalidated.
(9) This completes calibration of voltage input (0 to 10V). Press the
key to return the display to [ ].
7--11
E5AK
CHAPTER 7 CALIBRATION
· After calibrating input, make sure that you check indication accuracy to
make sure that the E5AK controller has been correctly calibrated.
· Operate the E5AK controller in the PV/SP monitor (level 0 mode) mode.
· Check the indication accuracy at the upper and lower limits and mid-
point.
F Thermocouple · Preparation
The following figure shows the required device connection. Make sure
that the E5AK controller and cold junction compensator are connected
by a compensating conductor for the input type that is to be used during
actual operation.
AC100-240V ~
(AC/DC24V )
10 30 31 32 20
SOURCE
9 29 19
8 28 18
7 27 17
6 26 16
5 25 15
Cold junction
4 24 14 compensator
3 23 13
2 22 12
STV
1 21 33 11
Compensation
conductor
· Operation
Make sure that the cold junction compensator is at 0_C, and set STV out-
put to the voltage equivalent to the starting power of the check value.
· Operation
Set the 6-dial to the resistance equivalent to the check value.
7--12
E5AK
STV
· Operation
Set the STV to the current value equivalent to the check value.
· Operation
Set the STV to the voltage value equivalent to the check value.
7--13
E5AK
CHAPTER 7 CALIBRATION
7--14
E5AK
CHAPTER 8 TROUBLESHOOTING
CHAPTER 8 8
TROUBLESHOOTING
This chapter describes how to find out and remedy the cause if the E5AK
does not function properly.
8--1
E5AK
CHAPTER 8 TROUBLESHOOTING
8--2
E5AK
When an error has occurred, the No.1 display alternately indicates error
codes together with the current display item.
This section describes how to check error codes on the display, and the
actions you must be taken to remedy the problem.
Input error
F Action Check the wiring of inputs, disconnections, and shorts, and check the in-
put type.
F Operation at For control output functions, output the manipulated variable matched to
error the setting of the “MV at PV error” parameter (level 2 mode). Alarm out-
put functions are activated when the upper limit is exceeded.
Memory error
F Action First, turn the power OFF then back ON again. If the display remains the
same, the E5AK controller must be repaired. If the display is restored to
normal, then a probable cause can be external noise affecting the control
system. Check for external noise.
F Operation at Control output functions turn OFF (2mA max. at 4 to 20mA output, and
error output equivalent to 0% in case of other outputs). Alarm output functions
turn OFF.
F Action First, turn the power OFF then back ON again. If the display remains the
same, the E5AK controller must be repaired. If the display is restored to
normal, then a probable cause can be external noise affecting the control
system. Check for external noise.
F Operation at Control output functions turn OFF (2mA max. at 4 to 20mA output, and
error output equivalent to 0% in case of other outputs). Alarm output functions
turn OFF.
8--3
E5AK
CHAPTER 8 TROUBLESHOOTING
F Operation at Both control output functions and alarm output functions operate. How-
error ever, note that readout accuracy is not assured.
F Meaning Though not an error, this is displayed when the process value exceeds the
display range when the control range (setting range ±10%) is larger than
the display range (-1999 to 9999).
· When less than “-1999” [ ]
· When greater than “9999” [ ]
F Action First, correctly connect the wiring for the potentiometer, open output, and
close output.
Execute the motor calibration again.
F Operation proce-
dure
F Operation at When motor calibration is executed, open output will operate and then
error close output will operate. However, as the value is incorrect, the result
turns out to be an error.
8--4
E5AK
The E5AK controller allows you to assign error output to terminals as out-
puts.
For details on output assignments, see 3.3 Setting Output Specifications
(page 3-6).
F LBA · LBA (Loop Break Alarm) can be used as a means for detecting loop
breaks when the control loop is not functioning normally. For details, see
page 4-15.
· LBA allows you to detect the following errors:
(1) Heater burnout
(2) Output error (contact weld, damaged transistors, etc.)
(3) Sensor error (constant input values, etc.)
· If you use the LBA function, set the loop break detection time matched
to the control characteristics in the “LBA detection time” parameter
(level 2 mode).
F Input errors · If you assign error 1 as the output, an error can be output to auxiliary
output 1 or auxiliary output 2 when input is in error. When this error
occurs, remedy by following the description for “Input error” (page 8-3).
F A/D converter · If you assign error 2 as the output, an error can be output to auxiliary
error output 1 or auxiliary output 2 when the A/D converter is in error. When
this error occurs, remedy by following the description for “A/D converter
error” (page 8-3).
F Remote SP input · If you assign error 3 as the output, an error can be output to auxiliary
error output 1 or auxiliary output 2 when the remote SP input error occurs
while the remote SP function is enabled. For details on error displays
and meanings, see Chapter 4 Applied Operation/4.4 How to Use the
Remote SP (page 4-11).
· When an error occurs, check the state of the remote SP connection. If the
lead is broken or disconnected, the remote SP scaling lower limit is dis-
played blinking on the PV/SP display or remote SP monitor display.
8--5
E5AK
CHAPTER 8 TROUBLESHOOTING
Items marked by a “x” indicates combinations of conditions not acceptable during ST or AT execution.
Items marked by “ ---” are impossible combinations.
8--6
E5AK
APPENDIX
APPENDIX
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . A-2
ABOUT CURRENT TRANSFORMER (CT) . . . A-5
CONTROL BLOCK DIAGRAM . . . . . . . . . . . . . . A-6
SETTING LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8
MODEL LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-11
PARAMETER OPERATIONS LIST . . . . . . . . . . A-12
FUZZY SELF-TUNING . . . . . . . . . . . . . . . . . . . . . A-14
X FORMAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-17
ASCII CODE LIST . . . . . . . . . . . . . . . . . . . . . . . . . . A-20
A--1
E5AK
APPENDIX
SPECIFICATIONS
J Ratings
AC100-240V type AC/DC24V type
Supply Voltage AC100-240V ~ , 50/60 Hz AC/DC24V , 50/60Hz
Power Consumption 16VA 12VA, 8W
Oprating Voltage Range 85% to 110% of rated supply voltage
Thermocouple : K, J, T, E, L, U, N, R, S, B, W, PLII *1, *2
Platinum resistance thermometer : JPt100, Pt100
Main Input
Voltage input : 4 to 20mA, 0 to 20mA (Input impedance 150W)
Current input : 1 to 5V, 0 to 5V, 1 to 10V (Input impedance 1MW)
CT input: E54-CT1, E54-CT3
Sub-Input Potentiometer: 100Ω to 2.5kΩ
Remote SP input: 4 to 20mA (Input impedance 150Ω)
Control Output According to output unit (see “Output Unit Ratings and Characteristics”)
Auxiliary Output SPST-NO, 3A at 250 VAC (resistive load)
Control Method Advanced PID or ON/OFF control
Setting Method Digital setting using front panel keys
Indication Method 7-segment digital display, Bar graph and LEDs
Other Functions According to option unit (see ”Option Unit Ratings and Characteristics”)
Operating : -10°C to 55°C (with no icing)/3-year warranty period: -10°C to 50°C
Ambient Temperature
Storage : -25°C to 65°C (with no icing)
Ambient Humidity 35% to 85%
*1 Thermocouple W is W/Re5-26.
*2 The following table shows the setting ranges and indication ranges for each of the inputs.
A--2
E5AK
SPECIFICATIONS
J Characteristics
Thermocouple:
(±0.3% of indication value or ± 1°C, whichever greater) ± 1 digit max. (*1)
Platinum resistance thermometer:
(±0.2% of indcation value or± 0.8°C whichever greater)± 1 digit max.
Indication Accuracy
Analog input: ±0.2%± 1 digit max.
CT input: 5%FS 1 digit max.
Potentiometer: 5%FS 1 digit max.
Remote SP: 0.2%FS 1 digit max.
Hysteresis 0.01 to 99.99%FS (in units of 0.01%FS)
Proportional Band (P) 0.1 to 999.9% FS (in units of 0.1%FS)
Integral (reset) Time (I) 0 to 3999 s (in units of 1 second) (*2)
Vibration Malfunction 10 to 55 Hz, 10 m/s2 (approx.1G) for 10 min each in X, Y, and Z directions
Resistance Destruction 10 to 55 Hz, 20 m/s2 (approx.2G) for 2hrs each in X, Y, and Z directions
200 m/s2 min. (approx.20G), 3 times each in 6 directions (100 m/s2 (approx.10G)
Shock Resis- Malfunction
applied to the relay)
tance
Destruction 300 m/s2 min. (approx.30G), 3 times each in 6 directions
Weight Approx. 450 g, mounting bracket: approx. 65 g
Front panel: NEMA4 for indoor use (equivalent to IP66)
Enclosure Ratings Rear case: IEC standard IP20
Terminals: IEC standard IP00
Memory Protection Non-volatile memory (number of writings:100000 operations)
*1The indication accuracy of the K1, T, and N thermocouples at a temperature of -100°C or less is ±2°C ±1 digit maximum. The
indication accuracy of the U, L1 and L2 thermocouples at any temperature is ±2°C ±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.
The indication accuracy of the W thermocouple is ±1 digit max. of whichever is the greater of ±0.3% or ±3°C of the indicated
value.
The indication accuracy of the PLII thermocouple is ±1 digit max. of whichever is the greater of ±0.3% or ±2°C of the indicated
value.
*2On a position-proportional control type, 1 to 3999.
Note: 1. Use the K2CU-FVVA-VGS (with gate input terminals) for the detection of three-phase heater burnout.
2. The heater burnout alarm is always OFF if the alarm is set to 0.0A and always ON if the alarm is set to 50.0A.
3. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less
than 190ms.
A--3
E5AK
APPENDIX
A--4
E5AK
F Specifications
Item Specifications
Type E54-CT1 E54-CT3
Max.continuous current 50A 120A (*1)
Dielectric Strength AC 1000V (1min)
Vibration Resistance 50Hz, 98m/s2 [10G]
Weight Approx. 11.5g Approx. 50g
Armature (2)
Accessory -
Plug (2)
*1 The maximum continuous current of the E5AK is 50 A.
F Dimensions
E54-CT1 21 2.8
15
7.5
f5.8
25
10.5
3
40
2-f3.5
10
30
E54-CT3 30 f2.36
9
f12
40
2-M3 depth 4
15
30
A--5
E5AK
APPENDIX
J Standard type
Temperature Analog input
input
SP mode
LSP Process
SP ramp
value
RSP
RSP enable Control method
Heating Cooling
Process/function side side
MV change MV change
rate limiter rate limiter
Control
MV limiter MV limiter
Data
Dead band
Heating Cooling
side side
Error MV at Error
PV error
D D
DStop Manipulated
DStop Manipulated
variable at variable at
heating side cooling side
A--6
E5AK
J Position-proportional type
Temperature Analog input
input
SP mode
LSP Process
SP ramp value
RSP
RSP enable PID control
MV change
rate limiter
Position-
proportional
dead band
Process/function
Open side Close side
Control
Data Operation at
Error Error
PV error
Operation at
Stop Stop
stop
Open Close
output output
A--7
E5AK
APPENDIX
SETTING LIST
Mode Parameter Name Setting Range Unit Default Remarks Setting
Security 0 to 6 None 1
Protect
[A/M] key protect ON/OFF None OFF
Manual Manual MV -5.0 to 105.0 *1 % 0.0
Set point Set point lower limit to Set point upper limit EU 0
Level 0
Run/Stop Run/Stop None RUN
Set point 1 Set point lower limit to Set point upper limit EU 0 Multi-SP
Set point 2 Set point lower limit to Set point upper limit EU 0 Multi-SP
Set point 3 Set point lower limit to Set point upper limit EU 0 Multi-SP
Input shift upper limit -199.9 to 999.9 °C/°F 0.0 Temperature input
Input shift lower limit -199.9 to 999.9 °C/°F 0.0 Temperature input
*1 During heat and cooling control, the lower limit becomes -105.0%.
During position-proportional control, the setting becomes HOLD, OPEN or CLOS.
*2 During heat and cooling control, the setting range becomes 0.0 to 105.0%.
*3 During heat and cooling control, the setting range becomes -105.0 to 0.0%.
A--8
E5AK
SETTING LIST
A--9
E5AK
APPENDIX
*5 Set the transfer output type parameter according to the following table.
Transfer Output Type Transfer Output Lower Limit to Transfer Output Upper Limit
SP :Set point Set point lower limit to Set point upper limit
SP-M :Set point during SP ramp Set point lower limit to Set point upper limit
PV :Process value Scaling lower limit to scaling upper limit
O :Manipulated variable -5.0 to 105.0%
(heat)
C-O :Manipulated variable 0.0 to 105.0%
(cool)
V-M :Value opening -10.0 to 110.0%
D Default : SP
D The output ranges of the SP setting, set point or process value when temperature input is selected are the ranges supported
by the selected sensor.
D When the heating side manipulated variable or cooling side manipulated variable is selected, the transfer output lower limit in
a heating and cooling control becomes “0.0”.
A--10
E5AK
MODEL LIST
MODEL LIST
A--11
E5AK
APPENDIX
· Switching to modes other than manual or protect mode is carried out by mode selection in the menu
display.
· The figure below shows all parameters in the order that they are displayed. Some parameters are
not displayed depending on the protect mode setting and conditions of use.
Power ON
A/M
1 second min. 1 second min.
1 second min.
Level 2 mode A/M + A/M +
1 second min. 1 second min.
1 second min.
Setup mode
Protect mode
1 second min.
Expansion
mode A/M +
1 second min.
1 second min.
Option mode
Parameters in a mode can be
1 second min.
switched by the key. The param-
Calibration eter following the last parameter is the
mode top parameter.
A--12
E5AK
Expansion
Setup mode Option mode
mode
Calibration
mode
Transfer
output
A--13
E5AK
APPENDIX
FUZZY SELF-TUNING
Fuzzy self-tuning is a function that enables the E5AK to calculate the most
suitable PID constants for the controlled object.
J Features
· The E5AK determines by itself when to perform fuzzy self-tuning.
· At the time of fuzzy self-tuning, the E5AK does not output any signal
that disturbs the temperature or output value.
F Startup SRT will start if the following conditions are satisfied simultaneously
Conditions of when the E5AK is turned on or the set point is changed.
SRT At the time the E5AK starts operation At the time set point is changed
1) The set point at the time the E5AK 1) The new set point is different from the
starts operating is different from the set point used at the time SRT was
set point used at the time SRT was executed last (see note).
last executed (see note). 2) The process value is in stable condi-
2) The process value at the time the tion before the set point is changed.
E5AK starts operating is smaller than 3) A larger set point value is set in
the set point in reverse operation and reverse operation and a smaller set
larger than the set point in normal point is set in normal operation.
operation.
Note: The last SRT-executed set point is set to 0 before shipping and when
changing from advanced PID control to advanced PID control with
fuzzy self-tuning.
A--14
E5AK
FUZZY SELF-TUNING
F PID Constant If the step control amount is applied before the maximum temperature
Refreshing slope (R) is obtained, SRT will not renew any PID constant. If the propor-
tional band obtained from the R and L values that were measured before
Conditions
the imposition had been completed is larger than the present proportional
band, the PID constants will be renewed because the measured value is in
the direction towards the suitable proportional band value, and the set
point at that time will be the SRT-executed set point.
Slope (R)
Temperature
Stable range
SP
Time
Stable range
Set point
Stable range
(Set to 15.0_C
before shipping)
Stability judgement time
Stable Stable
F Balanced Status
If the process value is within the stable range for 60s when there is no out-
put,it is deemed that the temperature is balanced.
A--15
E5AK
APPENDIX
F Startup Conditions of DT
(1) DT will start if the temperature that has been stable varies due to ex-
ternal disturbance and the deflection of the temperature exceeds the
stable range, and then the temperature becomes stable, provided that
the number of maximum temperature values is less than four.
(2) DT will start if the set point is changed under the condition that SRT
does not start and the temperature becomes stable, provided that the
number of maximum temperature values is less than four. If there are
four or more maximum temperature values, HT will start.
Set point change
Extreme value 2
Temperature
SP
Extreme value 1
Time
F Startup Conditions of HT
HT will be ON when there is hunting with four or more maximum temper-
ature values(extreme values) while SRT is not being executed.
Extreme value 2 Extreme value 4
Temperature
SP
Extreme Extreme
value 1 value 3
Time
A--16
E5AK
X FORMAT
X FORMAT
J Format Commands are structured as follows and are paired with a response.
2B 2B 2B 4 to 8B 2B 2B
Unit Header Data Data FCS
F Command No. code code
@ * CR
2B 2B 2B 4 to 8B 2B 2B
Unit Header End Data FCS
F Response No. code code
@ * CR
· “@”
The start character. This character must be inserted before the lead-
ing byte.
· Unit No.
Specifies the “unit No.” of the E5AK. If there are two or more trans-
mission destinations, specify the desired destination using “unit
No.”
· Header code/Data code
Specifies the command type. For details on the command type, see
page A-18.
· Data
Specifies the set value or setting content. The data length varies
according to the command.
· End code
Sets the communication results. For details on the types and mean-
ings of end codes, see 6.5 How to Read Communications Error
Information (page 6-12).
· FCS (Frame Check Sequence)
Set the frame check results from the start character to the data sec-
tion. For details on the frame check, see 6.6 Program Example (page
6-14).
· “*” “CR (Carriage Return) code”
Indicates the end (terminator) of the command or response block.
A--17
E5AK
APPENDIX
A--18
E5AK
X FORMAT
2B 2B 4B 4B 2B 2B
Unit End Process value Status FCS
Response No. code
@ R X * CR
A--19
E5AK
APPENDIX
Lower 4 bits
A--20
E5AK
INDEX
100%AT . . . . . . . . . . . . . . . . . . . . . . . . . . . 3---16 B
40%AT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3---16 B group . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6---11
A Balance---less, Bump ---less Operation . . 3---14
Balanced Status . . . . . . . . . . . . . . . . . . . . A ---15
A group . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6---11 Bar graph . . . . . . . . . . . . . . . . . . . . . . . . . . . 1---3
A/D converter error . . . . . . . . 3---6, 8---3, 8---5 Basic Operation Flow . . . . . . . . . . . . . . . . . 3---2
A/M key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1---3 Before setup . . . . . . . . . . . . . . . . . . . . 2---3, 2---4
A/M key protect . . . . . . . . . . . . . . . . . . . . . 3---12
About Calibration . . . . . . . . . . . . . . . . . . . 1---11
C
ABOUT CURRENT Cable connections . . . . . . . . . . . . . . . . . . . . 6---3
TRANSFORMER (CT) . . . . . . . . . . . A ---5 Calibrating Current Input . . . . . . . . . . . . 7---9
About invalid parameters . . . . . . . . . . . . . 6---7 Calibrating inputs . . . . . . . . . . . . . . . . . . 1---11
About parameter display . . . . . . . . . . . . . . 5---2 Calibrating Platinum
About PID Parameters . . . . . . . . . . . . . . 3---17 Resistance Thermometer . . . . . . . . . . . 7---7
About the Communications Function . 1---10 Calibrating Thermocouple . . . . . . . . . . . . 7---4
About the Decimal Point Calibrating transfer output . . . . . . . . . . 1---11
of the Alarm Value . . . . . . . . . . . . . . . 3---11 Calibrating Voltage Input . . . . . . . . . . . . 7---10
About the displays . . . . . . . . . . . . . . . . . . . 1---3 Calibration . . . . . . . . . . . . . . . . . . . . . 7---7, 7---9
About the power blocks . . . . . . . . . . . . . . 2---10 Calibration : 0 to 10V . . . . . . . . . . . . . . . . 7---11
About the temperature unit . . . . . . . . . . . 3---4 Calibration data error . . . . . . . . . . . . . . . . 8---4
About the unit No. . . . . . . . . . . . . . . . . . . 6---12 Calibration item menu . . . . . . . . . . . . . . . 7---3
Adjusting Control Operation . . . . . . . . . 3---14 Calibration Mode . . . . . . . . . 1---8, 1---9, 5---46
Alarm 1 hysteresis . . . . . . . . . . . . . . . . . . 5---24 Calibration save mark . . . . . . . . . . . . . . . . 7---3
Alarm 1 open in alarm . . . . . . . . . . . . . . . 5---31 Calibration: 0 to 5 V, 1 to 5 V . . . . . . . . . 7---10
Alarm 1 type . . . . . . . . . . . . . . . . . . . . . . . 5---30 Calibration: thermocouple 1 . . . . . . . . . . . 7---5
Alarm 2 hysteresis . . . . . . . . . . . . . . . . . . 5---24 Calibration: thermocouple 2 . . . . . . . . . . . 7---6
Alarm 2 open in alarm . . . . . . . . . . . . . . . 5---31 Changing the set point . . . . . . . . . . . . . . . 3---14
Alarm 2 type . . . . . . . . . . . . . . . . . . . . . . . 5---30 Characteristics . . . . . . . . . . . . . . . . . . . . . A ---3
Alarm 3 hysteresis . . . . . . . . . . . . . . . . . . 5---24 Checking Indication Accuracy . . . . . . . . 7---12
Checking Operation Restrictions . . . . . . 8---6
Alarm 3 open in alarm . . . . . . . . . . . . . . . 5---31
Close in alarm/open in alarm . . . . . . . . . 3---10
Alarm 3 type . . . . . . . . . . . . . . . . . . . . . . . 5---30
Command . . . . . . . . . . . . . . . . . . . . . . . . . A ---17
Alarm hysteresis . . . . . . . . . . . . . . . . . . . . 3---10
Command Configuration . . . . . . . . . . . . . . 6---5
Alarm type . . . . . . . . . . . . . . . . . . . . . . . . . . 3---9
Command List . . . . . . . . . . . . . . . . . . . . . . 6---10
Alarm value . . . . . . . . . . . . . . . . . . . . . . . . . 3---9
Commands and Responses . . . . . . . . . . . . 6---6
Alarm value 1 . . . . . . . . . . . . . . . . . . . . . . 5---12
Communication baud rate . . . . . . . . . . . 5---40
Alarm value 2 . . . . . . . . . . . . . . . . . . . . . . 5---12
Communication data length . . . . . . . . . . 5---40
Alarm value 3 . . . . . . . . . . . . . . . . . . . . . . 5---12
Communication parity . . . . . . . . . . . . . . . 5---40
Alfa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5---34
Communication stop bit . . . . . . . . . . . . . 5---40
ASCII CODE LIST . . . . . . . . . . . . . . . . . A ---20 Communication unit No. . . . . . . . . . . . . . 5---40
Assignment example . . . . . . . . . . . . . . . . . 4---9 Communications . . . . . . . . . . . . . . . . . . . . 2---11
AT calculated gain . . . . . . . . . . . . . . . . . . 5---35 Communications parameters . . . . . . . . . . 6---4
AT Execute/Cancel . . . . . . . . . . . . . . . . . . 5---11 Conditions when running a program . . 6---14
AT hysteresis . . . . . . . . . . . . . . . . . . . . . . . 5---36 Connecting the Cold
Auto ---tuning (A.T.) . . . . . . . . . . . . . . . . . 3---16 Junction Conductor . . . . . . . . . . . . . . . 7---4
Auto ---turning key . . . . . . . . . . . . . . . . . . . 1---3 CONTROL BLOCK DIAGRAM . . . . . . . A ---6
E5AK
INDEX
INDEX
INDEX
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer
to previous version.
Revision code Date Revised content
1 July 1996 Original production
Page 1--7: Modified the diagram of mode.
Page 2--6: Modified the power specifications in “Terminal arrange-
ment”.
2 April 1997 Page V: Changed “100 to 240 VAC” to AC100--240V ~or AC/DC24V
Page 1--6: Modified the item of “Model” on the table.
Page 2--8: Modified the diagram in “Terminal arrangement”.
Changed the Power specifications in “Power supply”.
Page 3--3: Modified the diagram in “Setup”.
Page 3--8: Added “run/stop”= “run” to Setting Example.
Page 5--8: Added “Model” and “Power specifications” to MV monitor.
Page 5--9: Added “Model” and “Power specifications” to Valve opening mon-
itor.
Page 5--13: Added “Model” and “Power specifications” to Cooling coefficient.
Page 5--14: Added “Model” and “Power specifications” to Dead band and
Position--proportional dead band.
Page 5--15: Added “Model” and “Power specifications” to Manual reset value
and Hysteresis.
Page 5--16: Added “Model” and “Power specifications” to Control period.
Page 5--17: Added “Model” and “Power specifications” to Heater current
monitor and Heater burnout.
Page 5--23: Added “Model” and “Power specifications” to Open/close hyster-
esis.
Page 5--28: Added “Model” and “Power specifications” to Control output as-
signment.
Page 5--33: Added “Model” and “Power specifications” to PID/ON/OFF.
Page 5--42: Added “Model” and “Power specifications” to HBA latch.
Added “Model” and “Power specifications” to Motor Calibration.
Page 5--43: Added “Model” and “Power specifications” to Travel Time.
Added “Model” and “Power specifications” to PV dead band.
Page 6--3: Modified the diagram in “RS--232C”.
Page 7--4: Modified the diagram in “Preparations”.
Page 7--7: Modified the diagram in “Preparation”.
Page 7--9: Modified the diagram in “Preparation”.
Page 7--10: Modified the diagram in “Preparation”.
Page 7--12: Modified the diagram in “Thermocouple” and “Platinum resis-
tance thermometer”.
Page 7--13: Modified the diagram in “Current input” and “Voltage input”.
Page 8--4: Added “Motor calibration error”.
Page A--2: Modified “Ratings specifications”.
Page A--11: Changed “Type Name” and “Specification” in “Base unit”.
Page A--14: Deleted 2) of “At the time the E5AK starts operation” in “Startup
Conditions of SRT”.
Deleted 2) of “At the time set point is changed”.
Page A--15: Deleted “Imposition Completion Condition of Step Control
Amount”.
Modified the diagram in “PID Constant Refreshing Conditions”.
02A December 2003 Page 2--9: Modified the diagram in “Control output”.
Page 4--8: Changed the title from ”Input assignments” to ”Event input as-
signments and deleted the flowchart below.
Page 4--9: Modified the table contents for “Event input” and added a note
below the table.
Page 5--3: Modified the tabel.
Page A--8: Changed the unit from “%” to “%FS” for Alram 1 hysteresis,
Alarm 2 hysteresis, and Alarm 3 hysteresis.