FORM III
(Installations of voltage exceeding 650V)
Report No. __________
Date of inspection by Electrical Inspector or self-certification by owner _____________
Date of last inspection or self-certification __________________
 Sl.   Regulation       Requirements                                          Report
 No.   Nos
 1.    Regulation-3     Is the register of the designated persons properly    Yes/No
                        made and kept up to date duly attested?
 2.    Regulation-      (i) Is/Are there any visible sign(s) of overloading   Yes/No
       12                     in respect of any apparatus?
                        (ii) Whether any unauthorised temporary               Yes/No
                              installation exist?
                        (iii) Whether the motors and controlling              Yes/No
                              equipment are being over hauled
                              periodically and record kept of the same in
                              a register?
                        (iv) Whether the transformer oil samples are          Yes/No
                              being tested periodically and results
                              recorded in a register?
                        (v) Whether suitable lightning arrestors have         Yes/No
                              been provided near the transformers for
                              protection against lightning?
                        (vi) Whether earth resistance is being measured       Yes/No
                              periodically and results recorded in a
                              register?
                        (vii) Any other defect or condition which may         Yes/No
                              be a source of danger. If Yes please
                              explain?
                        (viii) Whether operation and maintenance              Yes/No
                              data has been clarified, categorized and
                              computerized for prompt and easy
                              retrieval?
                        (ix) Whether predictive maintenance is being          Yes/No
                              performed for installation of voltage
                              exceeding 650V?
                        (x) Whether residual life assessment and life         Yes/No
                              extension      programmes        are    being
                              undertaken for installations or equipment of
                              voltage exceeding 650V (applicable for
                              installations or equipment more than 15
                              years old)?
                        (xi) Whether all required type and routine tests at Yes/No
                              factory done for equipments. Deficiencies and
                              Discrepancies in above test report and results,
                              if any, shall be reported?
                        (xii) Are there deficiencies in construction with Yes/No
                              reference to Indian Standard requirements.
                             Please specify.
3.    Regulation-       Give report on condition of service lines, cables,   Satisfactory/Not
      13                wires, apparatus and such other fittings placed      Satisfactory
                        by the supplier or owner of the premises. If not
                        satisfactory give details.
4.    Regulation-       Whether suitable cut-outs provided by the            Yes/No
      14                supplier at the consumer’s premises are within
                        enclosed fire proof receptacle?
5.    Regulation-       (i) Whether switches are provided on live            Yes/No
      15                      conductors?.
                        (ii) Whether indication of a permanent nature is     Yes/No
                              provided as per Regulation so as to
                              distinguish neutral conductor from the live
                              conductor?.
                        (iii) Whether a direct line is provided on the       Yes/No
                              neutral in the case of single phase double
                              pole iron clad switches instead of fuse ?
6.    Regulation-       (i) Whether earthed terminal is provided by the      Yes/No
      16                      supplier?.
                        (ii) General visible condition of the earthing       Satisfactory/Not
                              arrangement.                                   Satisfactory
7.    Regulation-       (i) Are bare conductors in building inaccessible?    Yes/No
      17                (ii) Whether readily accessible switches have
                              been provided for rendering them dead?         Yes/No
8.    Regulation-   13. Whether “Danger Notice” in Hindi and the local       Yes/No
      18                language of the district and of a design as per
                        relevant Indian Standard is affixed permanently
                        in conspicuous position?.
9.    Regulation-      (i) Whether the practice of working on live lines     Yes/No
      19                     and apparatus is adopted ? If so, have the
                             safety measure been adopted as per
                             Schedule-III ?
                       (ii) Whether insulating floor or mats conforming      Yes/No
                             to IS-15652:2006 have been provided?
                       14. (iii) Whether identification of panel has
                             been provided on the front and the rear of      Yes/No
                             the panel?
10.   Regulation-      Whether flexible cables used for portable or          Yes/No
      21               transportable equipment covered under the
                       Regulation, are heavily insulated and adequately
                       protected from mechanical injury?.
11.   Regulation-      State the condition of metallic coverings             Satisfactory/Not
      22               provided for various conductors.                      Satisfactory
12.   Regulation-       Whether the circuits or apparatus intended for       Yes/No
      24               operating     at    different    voltage(s)   are
                       distinguishable by means of indication(s) of
                       permanent nature?.
13.   Regulation-       Whether all circuits and apparatus are so Yes/No
      26               arranged that there is no danger of any part(s)
                       becoming accidentally charged to any voltage
                       beyond the limits of voltage for which it/they
                       is/are intended ?
14.   Regulation-   (i) In the case of generating         stations and   Yes/No
      27                  enclosed sub stations, whether fire-buckets
                          filled with clean dry sand have been
                          conspicuously marked and kept in
                          convenient situations in addition to fire-
                          extinguishers suitable for dealing with
                          electric fires ?
                     (ii) Whether First Aid Boxes or cupboards           Yes/No
                          conspicuously marked and properly
                          equipped are provided and maintained?.
                    (iii) Is adequate staff trained in First Aid         Yes/No
                          Treatment and fire fighting?
15.   Regulation-   (i) Whether instructions in English or Hindi and     Yes/No
      28                  the local language of the district and where
                          Hindi is the local language, in English and
                          Hindi, for the resuscitation of persons
                          suffering from electric shock have been
                          affixed in a “conspicuous place” ?.
                    (ii) Are the designated persons able to apply        Yes/No
                          instructions for resuscitation of persons
                          suffering from electric shock ?
16.   Regulation-   Leakage on premises:
      34            State insulation resistance between conductors       ----- M Ohms
                    and earth in Mega Ohms.
17.   Regulation-   (i) Whether a suitable linked switch, or circuit     Yes/No
      35                  breaker, or emergency tripping device is
                          placed near the point of commencement of
                          supply so as to be readily accessible and
                          capable of being easily operated to
                          completely isolate the supply?
                    (ii) Whether suitable linked switch or a circuit     Yes/No
                          breaker to carry and break the full load
                          current on the secondary side of a
                          transformer?
                    (iii) Whether every distinct circuit is protected    Yes/No
                          against excess electricity by means of a
                          suitable circuit breaker or cut-out?
                    (iv) Whether linked switch or circuit breaker or     Yes/No
                          emergency tripping device is provided near
                          the motor or other apparatus at voltage
                          exceeding 650V but not exceeding 33kV          Yes/No
                          for controlling supply to the motor or
                          apparatus?
                    (v) Whether adequate precautions are taken to        Yes/No
                          ensure that no live parts are so exposed as
                          to cause danger?
18.   Regulation-   (i) Whether clear space of 100 cm is provided        Yes/No
      37                  in front of the main switchboard?.
                    (ii) Whether the space behind the switchboard        Yes/No
                          exceeds 75 cm in width or is less than 20
                          cm?.
                    (iii) In case the clear space behind the             Yes/No
                          switchboard exceeds 75 cm. State whether
                          a passage way from either end of the
                          switchboard to a height of 1.80 meters is
                          provided.
19.   Regulation-   (i) Whether all conductors and apparatus               Yes/No
      44                  including     live    parts    thereof     are
                          inaccessible?
                    (ii) Whether all windings of motors or other           Yes/No
                          apparatus are suitably protected?
                    (iii) State in case of transformers or reactors or     Yes/No
                          switches or static condensers involving the
                          use of more than 2,000 litres of oil in one
                          chamber, if suitable oil soak pits are
                          provided?
                    (iv) Where 9,000 litres or more of oil is used in      Yes/No
                          any one oil tank, has provision, been made
                          for draining away or removal of oil which
                          may leak or escape from such tank(s)?
                    (v) Whether trenches inside sub-station                Yes/No
                          containing cables are filled with non-
                          inflammable material or completely
                          covered with non- inflammable slabs?
                    (vi) Are conductors and apparatus so arranged          Yes/No
                          that they may be made dead in sections for
                          carrying out work thereon?
20.   Regulation-   Whether protections and interlocks have been           Yes/No
      45            provided? If not, give details.
21.   Regulation-   (i)      Have the frames of every generator,           Yes/No
      48                  stationary motor, and so far as practicable
                          portable motor and metallic parts not
                          intended as conductors of all transformers
                          and any other apparatus used for regulating
                          or controlling electricity and all electricity
                          consuming apparatus at voltage exceeding
                          650V but not exceeding 33kV been earthed
                          by two separate and distinct connections
                          with earth ?
                    (ii) Is the earth wire free from any mechanical        Yes/No
                          damage ?
                    (iii) Has the neutral point at the transformer and     Yes/No
                          generator been earthed by two separate and
                          distinct connections with earth?
                    (iv) Have the metal casings or metallic                Yes/No
                          coverings containing or protecting any
                          electric supply line or apparatus been
                          properly earthed and so joined and
                          connected across all junction boxes as to
                          make good mechanical and electrical
                          connections throughout their whole length?
                    (v) Whether earthing has been properly
                          executed and has been tested. If yes, give       Yes/No
                          value of earth resistance.                       ------Ohms
22.   Regulation-   Is the outdoor (except pole type) sub-station          Yes/No
      49            efficiently protected by fencing not less than
                    1.8 metres in height?
23    Regulation-   (i) Where platform type construction is used for       Yes/No
      50                  pole type sub-station, has sufficient space
                          for a man to stand on the platform been
                          provided?
                    (ii) Has hand-rail been provided and connected         Yes/No
                          with earth (if metallic and if sub-station has
                          not been erected on wooden supports and
                          wooden plateform)?
24.   Regulation-   Has suitable provision been made for immediate         Yes/No
      51            and automatic or manual discharge of every
                    static condenser on disconnection of supply ?
25    Overhead
      Lines         (i) What is the minimum size of the conductors         Size of
                          of overhead lines used ? State the type of       Conductor ---
                          conductors.
                    (ii) Whether clearances above ground of the            Yes/No
                          lowest conductor of overhead lines are as
                          per regulation 58?
                    (iii) On the basis of maximum sag, Whether             Yes/No
                          vertical clearances where the line of voltage
                          exceeding 650V passes above or adjacent to
                          any building or part of a building are as per
                          regulation 61?
                     (iv) On the basis of maximum deflection due to        Yes/No
                          wind pressure, whether horizontal
                          clearances between the nearest conductor
                          and any part of such building are as per
                          regulation 61?
                    (v) Where conductors forming parts of system at        Yes/No
                          different voltages are erected on the same
                          supports, whether adequate provision has
                          been made as per regulation 62 to guard
                          against danger to linemen and others from
                          the lower voltage system being charged
                          above its normal working voltage by
                          leakage from or contact with the higher
                          voltage system ?
                    (vi) Where overhead lines cross or are in              Yes/No
                          proximity to each other whether they have
                          been suitably protected to guard against
                          possibility of their coming in contact with
                          each other as per regulation 69?
                    (vii) Has every guard wire been properly               Yes/No
                          earthed as per regulation 70 at each point at
                          which its electrical continuity is broken?
                    (viii)(a) Whether metal supports of overhead
                          lines and metallic fittings attached thereto     Yes/No
                          are permanently earthed as per regulation
                          72?
                         (b) Has each stay-wire (except in case where     Yes/No
                         an insulator has been placed in it at a height
                         not less than 3 meters from the ground)
                         been earthed as per regulation 72?
                    (ix)(a) Whether overhead line is suitably
                         protected with a device for rendering the        Yes/No
                         line electrically harmless in case it breaks
                         as per regulation 73?
                         (b) Whether anti-climbing devices have
                         been provided at each support as per             Yes/No
                         regulation 73?
                    (x) (a) Has the owner of overhead lines adopted
                         efficient means for diverting to earth any       Yes/No
                         electrical surges due to lightning in every
                         overhead line which is so exposed as to be
                         liable to injury from lightning as per
                         regulation 74?
                        (b) Whether earth lead from the lightning
                         arrestors is connected to a separate earth       Yes/No
                         electrode as per regulation 74?
                    (xi) Whether unused overhead lines are
                         maintained in a safe mechanical condition        Yes/No
                         as per regulation 75?
                    (xii) Whether statutory clearances from
                         Authorities             i.e.            Forest   Yes/No
                         Department/Railways/         PTCC/Defence
                         (AHQ)/Civil Aviation have been taken as
                         per Indian standard. If yes, enclose copies
                         of the same.
                    (xii) Any other remarks.
Date:                                                  Signature of the Inspecting Officer/
                                                       Self-certifying supplier or owner
                                                            Name ______________________
                                                            Designation _________________
                                                            File No. ____________________
Copy forwarded to Electrical Inspector/Chief Electrical Inspector for …………………………