Motor Starter Protectors: Industrial Control Product Catalog 2021 Section
Motor Starter Protectors: Industrial Control Product Catalog 2021 Section
contents
1 SIRIUS
Section
1
Section Overview 1/2 – 1/3
PROTECTORS
MOTOR STARTER
Motor Starter Protectors
3RV20 MSP, Class 10/20 1/4 – 1/5
3RV21 MSP, Class 10 1/6 – 1/7
3RV10 MSP, Class 10 1/8
Circuit Breakers
3RV27, 3RV28 Circuit Breaker UL 489 1/9
Accessories
Auxiliary Switches 1/10
Auxiliary Releases 1/10
Busbars 1/11
Mounting Accessories 1/12 – 1/15
Rotary Operating Mechanisms 1/16 – 1/17
3RV29 Infeed System 1/18 – 1/21
General Data for Motor Starter Protectors
Manual Motor Starter Ratings 1/22
Group Installation Ratings 1/23
Combination Motor Controller Ratings 1/24
3RV27 and 3RV28 Circuit Breaker Ratings 1/25
Export Application Ratings 1/26 – 1/27
Rules for Mounting 1/28
Technical Data 1/29 – 1/32
Overview of MSP Functions & Applications 1/33
Application as a Combination Motor Controller 1/34
Application in DC Switching 1/35
Design 1/35
Characteristics 1/36
Circuit Diagrams 1/36
Dimensions 1/37 – 1/40
General Data for Accessories
Mountable Accessories
Overview 1/41 – 1/42
Circuit Diagrams 1/43 – 1/41
Dimensions 1/44
Busbar Accessories
Overview 1/45
Dimensions 1/46 – 1/47
Operating Mechanisms
Overview 1/48
Circuit Diagrams 1/49
Dimensions 1/49 – 1/50
Enclosures & Front Plates
Overview 1/51
Dimensions 1/52
Spring Terminal Infeed System
Design 1/53
Technical Data 1/53
Dimensions 1/54
(Section was last modified on 08/19/21) Smart Infrastructure, Industrial Control Catalog 2021 1/1
IEC Power Control SIRIUS
Motor Starter Protectors
contents
1
Size S00, S0
For motor protection For motor protection General data for SIRIUS
CLASS 10 CLASS 20 motor starter protectors
Selection and ordering data Selection and ordering data Page
Size Rated Current Page Size Rated Current Page Technical data 1/22
S00 up to 16 A 1/4 S2 up to 65 A 1/5 Overview 1/32
S0 up to 40 A 1/4 S3 up to 100 A 1/5 Characteristics 1/36
S2 up to 65 A 1/5 Circuit diagrams 1/36
S3 up to 100 A 1/5 Dimension drawings 1/37
1/2 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
IEC Power Control SIRIUS
Accessories
contents
1
Accessories for motor starter
3RV busbar and
PROTECTORS
MOTOR STARTER
protectors with Spring-Type Mounting Accessories
accessories
terminals
Page Page
Selection and ordering data 1/17 Selection and ordering data 1/17
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/3
3RV Motor Starter Protectors SIRIUS
For Motor Protection
3RV20 Class 10 — up to 40A
The 3RV20x MSPs are UL approved as Self Protected Combination Motor Controllers E ON/OFF rotary handle with lockout and
MOTOR STARTER
PROTECTORS
which are also called Type E. In this application, all the required functions for a motor visible trip indication.
branch are provided in one device: disconnect, short circuit protection, motor control and E Adjustment dial for setting to motor FLA.
overload protection. A type E terminal adaptor is required for screw terminal versions. E Class 10 overload trip characteristics.
3RV20x MSPs with spring terminal can only be applied as Type E when used in the E Short circuit trip at 13 times the maximum
3RV29 Infeed System. . The 3RV20x MSPs are also approved for use as follows: setting of the FLA adjustment dial.
– Manual Motor Controller: Motor starter, motor disconnect, control and overload— E Short circuit current rating:
protection. E Ambient compensated up to 140° F
– Group Installation: Motor starter only, motor disconnect, control and overload (applies to side by side mounting).
protection. E Phase loss sensitivity.
– Tap conductor Protection in Group Installation acc. NEC: Motor starter only; E Test trip function.
motor disconnect, control and overload protection. E Terminal versions: screw, spring, ring lug.
When the 3RV20x is used with one of the 3 above mentioned approvals, the 3RV20x can E Auxiliaries and Accessories
be installed downstream of one circuit breaker or fuse set. see pages 1/10–1/21.
E General Information see pages 1/33–1/36.
For more detailed application information and rules how to apply, size and rate the E Technical Data see pages 1/22–1/32.
3RV20x in control panels in general, in group installations or in accordance to interna- E Dimensions see page 1/37–1/40.
tional IEC standards visit our website: www.usa.siemens.com/controlpaneldesign
Note: Select MSP by motor Full Load Amperes. Horsepower ratings are for reference only.
Instant- UL short-
aneous circuit
Single-Phase Three-Phase
1) short breaking
HP Ratings HP Ratings
FLA circuit capacity Size S00 2) 4) Size S0 2) 4)
Adjustment release @ 277V/
Illustration Range [A] 115V 230V 200V 230V 460V 575V [A] 480V [kA] Order Number Order Number
0.11-0.16 — — — — — — 2.1 65 3RV2011-0AA●● 3RV2021-0AA●●
0.14-0.2 — — — — — — 2.6 65 3RV2011-0BA●● 3RV2021-0BA●●
0.18-0.25 — — — — — — 3.3 65 3RV2011-0CA●● 3RV2021-0CA●●
0.22-0.32 — — — — — — 4.2 65 3RV2011-0DA●● 3RV2021-0DA●●
0.28-0.4 — — — — — — 5.2 65 3RV2011-0EA●● 3RV2021-0EA●●
0.35-0.5 — — — — — — 6.5 65 3RV2011-0FA●● 3RV2021-0FA●●
0.45-0.63 — — — — — — 8.2 65 3RV2011-0GA●● 3RV2021-0GA●●
0.55-0.8 — — — — — — 10 65 3RV2011-0HA●● 3RV2021-0HA●●
0.7-1 — — — — — ½ 13 65 3RV2011-0JA●● 3RV2021-0JA●●
0.9-1.25 — — — — ½ ½ 16 65 3RV2011-0KA●● 3RV2021-0KA●●
1.1-1.6 — 1⁄10 — — ¾ ¾ 21 65 3RV2011-1AA●● 3RV2021-1AA●●
1.4-2 — 1⁄8 — — ¾ 1 26 65 3RV2011-1BA●● 3RV2021-1BA●●
1.8-2.5 — 1⁄6 ½ ½ 1 1½ 33 65 3RV2011-1CA●● 3RV2021-1CA●●
2.2-3.2 1⁄10 ¼ ½ ¾ 1½ 2 42 65 3RV2011-1DA●● 3RV2021-1DA●●
2.8-4 1⁄8 1⁄3 ¾ ¾ 2 3 52 65 3RV2011-1EA●● 3RV2021-1EA●●
3.5-5 1⁄6 ½ 1 1 3 3 65 65 3RV2011-1FA●● 3RV2021-1FA●●
4.5-6.3 ¼ ½ 1 1½ 3 5 82 65 3RV2011-1GA●● 3RV2021-1GA●●
5.5-8 1⁄3 1 2 2 5 5 104 65 3RV2011-1HA●● 3RV2021-1HA●●
7-10 ½ 1½ 2 3 5 7½ 130 65 3RV2011-1JA●● 3RV2021-1JA●●
9-12.5 ½ 2 3 3 7½ 10 163 65 3RV2011-1KA●● 3RV2021-1KA●●
10-16 1 2 3 5 10 — 208 65 3RV2011-4AA●● 3RV2021-4AA●●
13-20 1½ 3 5 5 10 — 260 65 — 3RV2021-4BA●●
16-22 1½ 3 5 7½ 15 — 286 65 — 3RV2021-4CA●●
18-25 2 3 5 7½ 15 — 325 65 — 3RV2021-4DA●●
23-28 2 5 7½ 10 20 — 364 50 — 3RV2021-4NA●●
27-32 2 5 7½ 10 20 — 400 50 — 3RV2021-4EA●●
3) 5)
30-36 3 5 10 10 25 — 432 12 — 3RV2021-4PA●●
3) 5)
34-40 3 7½ 10 10 30 — 480 12 — 3RV2021-4FA●●
Screw terminals, no auxiliary: ●● = 10
Screw Terminals, with 1NO/1NC Aux:●● = 15
Spring terminals, no auxiliary: ●● = 20
Spring Terminals, with 1NO/1NC Aux: ●● = 25
Ring Lug Terminals, no Auxiliary: ●● = 40
1) Select motor starter protector by motor full load amps. tion motor controller, a Type E terminal is required. 4) 3RV2 MSPs can only be used with Innovations
Horsepower ratings for reference only. See accessories page 1/10. contactors and accessories
2) The motor starter protectors rated up to 32 A can be 3) These products are NOT certified as Type E combi- 5) Spring and Ring Lug terminals are not available
used as manual motor controllers or as Type E combi- nation motor controllers. They can only be used as
nation motor controllers. For use as a Type E combina- manual motor controllers.
1/4 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
3RV Motor Starter Protectors SIRIUS
For Motor Protection
3RV10 Class 10 & 20 — up to 100A
1
The 3RV203 / 204 MSPs are UL approved as Self Protected Combination Motor Controllers E ON/OFF rotary handle with lockout and
PROTECTORS
MOTOR STARTER
which are also called Type E. In this application, all the required functions for a motor branch visible trip indication.
are provided in one device: disconnect, short circuit protection, motor control and overload E Adjustment dial for setting to motor FLA.
protection. A type E terminal adaptor is required for all screw terminal version S2 frame E Class 10 overload trip characteristics.
3RV2031 above 45A and all S2 frame 3RV2032 as well as for all S3 frame motor starter E Short circuit trip at 13 times the maximum
protectors. Spring terminal MSPs can only be applied as Type E when used in the 3RV29 setting of the FLA adjustment dial.
Infeed System. E Short circuit current rating:
E Ambient compensated up to 140° F
The 3RV203 / 204 MSPs are also approved for use as follows:
(applies to side by side mounting).
– Manual Motor Controller: Motor starter, motor disconnect, control and overload protection.
E Phase loss sensitivity.
– Group Installation: Motor starter only, motor disconnect, control and overload protection.
E Test trip function.
– Tap conductor Protection in Group Installation acc. NEC: Motor starter only; motor
E Auxiliaries and Accessories see
disconnect, control and overload protection.
pages 1/10–1/21.
When the 3RV203 / 204 is used with one of the 3 above mentioned approvals, they can be E General Information see pages 1/33–1/36.
installed downstream of one circuit breaker or fuse set. E Technical Data see pages 1/22–1/32.
E Dimensions see page 1/37–1/40.
For more detailed application information and rules how to apply, size and rate these MSPs in
control panels in general, in group installations or in accordance to international IEC standards
visit our website: www.usa.siemens.com/controlpaneldesign
Note: Select MSP by motor Full Load Amperes. Horsepower ratings are for reference only.
Single Phase 3 Phase UL short-
1) 1)
HP rating HP Rating Inst. circuit
FLA Short- breaking
Adjustment Circuit capacity Trip Class 10 Trip Class 20
Range Release @ 277V/
Illustration [A] 115V 240V 200V 230V 460V 575V [A] 480V [kA] 6) Order Number4) Order Number4)
1) Select motor starter protector by motor full load amps. 3) Shaded ratings apply for group installation only. These ratings 6) For 100kA SCCR rated MSPs, change the part
Horsepower ratings for reference only. do not apply as UL listed manual combination starters. number from 3RV2031 to 3RV2032. (applies to
2) Size S2 and S3 are listed as type E combination motor 4) Pre-assembled motor starter protector and transverse S2 frame only through 65A).
controllers. For required Type E terminals see page 1/13. auxiliary switch with 1NO + 1NC is available. Replace the last 7) Suitable for use with IE3/IE4 motors up to a
3RV2031 MSPs with a current setting limit of 45A or less digit of the order no. with a “5”. starting current of 720A. For higher starting
do not require a type E terminal and fulfill the spacing 5) 3RV1 MSPs can only be used with 3RT1 contactors currents use size S3.
requirements of UL508. and accessories. 3RV2 MSPs can only be used with 3RT2
contactors and accessories.
Refer to pages 1/22 to 1/24 when using an MSP in a Manual Motor Starter or a Manual Self-Protected Combination Motor Controller.
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/5
3RV Motor Starter Protectors SIRIUS
3RV2 Motor Starter Protectors/Circuit Breakers
3RV21 Class 10 — up to 32A with overload relay function (automatic RESET) IE3/IE4 ready
The 3RV21x MSPs are UL approved as Self Protected Combination Motor Controllers which E ON/OFF rotary handle with lockout and
MOTOR STARTER
PROTECTORS
are also called Type E. In this application, all the required functions for a motor branch are visible trip indication.
provided in one device: disconnect, short circuit protection, motor control and overload protec- E Adjustment dial for setting to motor FLA.
tion. A type E terminal adaptor is required for screw terminal versions. 3RV20x MSPs with E Class 10 overload trip characteristics.
spring terminal can only be applied as Type E when used in the 3RV29 Infeed System. The E Short circuit trip at 13 times the maximum
3RV21x MSPs are also approved for use as follows: setting of the FLA adjustment dial.
– Manual Motor Controller: Motor starter, motor disconnect, control and overload E Short circuit current rating:
protection. E Ambient compensated up to 140° F
– Group Installation: Motor starter only, motor disconnect, control and overload protection. (applies to side by side mounting).
– Tap conductor Protection in Group Installation acc. NEC: Motor starter only; E Phase loss sensitivity.
motor disconnect, control and overload protection. E Test trip function.
When the 3RV21x is used with one of the 3 above mentioned approvals, the 3RV21x E Terminal versions: screw only.
can be installed downstream of one circuit breaker or fuse set. E Auxiliaries and Accessories see
pages 1/10–1/21.
For more detailed application information and rules how to apply, size and rate the 3RV21x E General Information see pages 1/33–1/36.
in control panels in general, in group installations or in accordance to international IEC stan- E Technical Data see pages 1/22–1/32.
dards visit our website: www.usa.siemens.com/controlpaneldesign E Dimensions see page 1/37–1/40.
Note: Select MSP by motor Full Load Amperes. Horsepower ratings are for reference only.
Single-Phase Three-Phase
Setting range 1) UL short-
HP Ratings HP Ratings
for thermal Instantaneous circuit break-
overload electronic ing capacity
Illustration release 115V 230V 200V 230V 460V 575V release [A] @ 480V [kA] Catalog Number
2) 3)
Size S00
0.11 ... 0.16 — — — — — — 2.1 100 3RV2111-0AA10
0.14 ... 0.2 — — — — — — 2.6 100 3RV2111-0BA10
0.18 ... 0.25 — — — — — — 3.3 100 3RV2111-0CA10
0.22 ... 0.32 — — — — — — 4.2 100 3RV2111-0DA10
0.28 ... 0.4 — — — — — — 5.2 100 3RV2111-0EA10
0.35 ... 0.5 — — — — — — 6.5 100 3RV2111-0FA10
0.45 ... 0.63 — — — — — — 8.2 100 3RV2111-0GA10
0.55 ... 0.8 — — — — — — 10 100 3RV2111-0HA10
0.7 ... 1 — — — — — ½ 13 100 3RV2111-0JA10
0.9 ... 1.25 — — — — ½ ½ 16 100 3RV2111-0KA10
1.1 ... 1.6 — 1⁄10 — — ¾ ¾ 21 100 3RV2111-1AA10
1.4 ... 2 — 1⁄8 — — ¾ 1 26 100 3RV2111-1BA10
3RV2111-4FA10 1.8 ... 3RV2111-0BA10
2.5 — 1⁄6 ½ ½ 1 1½ 33 100 3RV2111-1CA10
2.2 ... 3.2 1⁄10 ¼ ½ ¾ 1½ 2 42 100 3RV2111-1DA10
2.8 ... 4 1⁄8 1⁄3 ¾ ¾ 2 3 52 100 3RV2111-1EA10
3.5 ... 5 1⁄6 ½ 1 1 3 3 65 100 3RV2111-1FA10
4.5 ... 6.3 ¼ ½ 1 1½ 3 5 82 100 3RV2111-1GA10
5.5 ... 8 1⁄3 1 2 2 5 5 104 100 3RV2111-1HA10
7 ... 10 ½ 1½ 2 3 5 7½ 130 100 3RV2111-1JA10
9 ... 12.5 ½ 2 3 3 7½ 10 163 100 3RV2111-1KA10
105) ... 16 1 2 3 5 10 — 208 55 3RV2111-4AA10
Size S02) 3)
A10 3RV2111-0BA10 105) ... 16 1½ 3 5 5 10 — 208 55 3RV2121-4AA10
135) ... 20 1½ 3 5 7½ 15 — 260 55 3RV2121-4BA10
165) ... 22 2 3 5 7½ 15 — 286 55 3RV2121-4CA10
185) ... 25 2 5 7½ 10 20 — 325 55 3RV2121-4DA10
23 ... 284) 3 5 10 10 25 — 364 55 3RV2121-4NA10
27 ... 324) 5) 6) 3 7½ 10 10 30 — 400 55 3RV2121-4EA10
1) Select motor starter protector by motor full load amps. combination motor controller, a Type E terminal is 6) Suitable for use with IE3/IE4 motors up to a starting
Horsepower ratings are for reference only. required. See accessories page 1/10. current of 256 A. For higher starting currents we
2) Accessories for mounting on the right and 3RV2915 4) These products are NOT certified as Type E combination recommend using 3RV2 motor starter protectors size S2.
three-phase busbars cannot be used. Accessories can motor controllers. They can only be used as manual 7) 3RV2 MSPs can only be used with Innovations
be ordered separately. motor controllers. contactors and accessories.
3) The motor starter protectors rated up to 32 A can 5) The setting range of the thermal overload releases has
be used as manual motor controllers or as Type E been extended.
combination motor controllers. For use as a Type E
1
The 3RV2131/2142 MSPs are UL approved as Self Protected Combination Motor Controllers E ON/OFF rotary handle with lockout and
PROTECTORS
MOTOR STARTER
which are also called Type E. In this application, all the required functions for a motor visible trip indication.
branch are provided in one device: disconnect, short circuit protection, motor control and E Adjustment dial for setting to motor FLA.
overload protection. A type E terminal adaptor is required for all screw terminal version E Class 10 overload trip characteristics.
S2 frame 3RV2131 above 45A as well as for all S3 frame motor starter protectors. Spring E Short circuit trip at 13 times the maximum
terminal MSPs can only be applied as Type E when used in the 3RV29 Infeed System.
setting of the FLA adjustment dial.
The 3RV2131/2142 MSPs are also approved for use as follows: E Short circuit current rating:
– Manual Motor Controller: Motor starter, motor disconnect, control and overload E Ambient compensated up to 140° F
protection. (applies to side by side mounting).
– Group Installation: Motor starter only, motor disconnect, control and overload protection. E Phase loss sensitivity.
– Tap conductor Protection in Group Installation acc. NEC: Motor starter only; motor E Test trip function.
disconnect, control and overload protection.
E Terminal versions: screw only.
When the 3RV2131/2142 is used with one of the 3 above mentioned approvals, they can be E Auxiliaries and Accessories
installed downstream of one circuit breaker or fuse set. see pages 1/10–1/21.
For more detailed application information and rules how to apply, size and rate these E General Information see pages 1/33–1/36.
MSPs in control panels in general, in group installations or in accordance to international E Technical Data see pages 1/22–1/32.
IEC standards visit our website: www.usa.siemens.com/controlpaneldesign E Dimensions see page 1/37–1/40.
Note: Select MSP by motor Full Load Amperes. Horsepower ratings are for reference only.
Single-Phase Three-Phase
Setting range 1) UL short-
HP Ratings HP Ratings
for thermal Instantaneous circuit break-
overload electronic ing capacity
Illustration release 115V 230V 200V 230V 460V 575V release [A] @ 480V [kA] Catalog Number
2)
Size S2
9.5 ... 14 1.5 3 5 5 10 15 208 65 3RV2131-4SA10
12 ... 17 1.5 3 5 7.5 15 15 260 65 3RV2131-4TA10
14 ... 20 1.5 3 7.5 7.5 15 20 260 65 3RV2131-4BA10
18 ... 25 2 5 7.5 10 20 25 325 65 3RV2131-4DA10
22 ... 32 3 5 10 10 25 30 416 65 3RV2131-4EA10
28 ... 36 3 7.5 15 15 30 40 520 65 3RV2131-4PA10
32 ... 40 3 7.5 15 15 30 40 585 65 3RV2131-4UA10
35 ... 45 3 10 15 15 40 50 650 65 3RV2131-4VA10
42 ... 52 5 10 15 20 40 50 741 65 3RV2131-4WA10
49 ... 59 5 15 20 25 50 60 845 65 3RV2131-4XA10
54 ... 65 5 15 20 25 50 60 845 65 3RV2131-4JA10
3RV2131-4WB10 3RV2142-4FA10
62 ... 73 7.5 15 25 30 60 75 949 65 3RV2131-4KA10
70 ... 804) 7.5 15 25 30 60 75 1040 65 3RV2131-4RA10
Size S3 with increased switching capacity2)
28 ... 40 3 7.5 15 15 30 40 520 55 3RV2142-4FA10
36 ... 50 5 10 15 20 40 50 650 55 3RV2142-4HA10
45 ... 63 5 15 20 25 50 60 819 55 3RV2142-4JA10
57 ... 75 7.5 15 25 25 60 75 975 55 3RV2142-4KA10
65 ... 84 7.5 15 25 30 60 75 1170 55 3RV2142-4RA10
3)
75 ... 93 7.5 20 30 40 75 100 1300 55 3RV2142-4YA10
3)
80 ... 1005) 10 25 40 40 75 100 1300 55 3RV2142-4MA10
WB10 3RV2142-4FA10
1) Select motor starter protector by motor full load amps. 4) Suitable for use with IE3/IE4 motors up to a starting 6) Size S2 and S3 are listed as type E combination motor
Horsepower ratings are for reference only. current of 720 A. For higher starting currents we controllers. For required Type E terminals see page
2) Accessories for mounting on the right and 3RV2915 recommend using 3RV2 motor starter protectors size S3. 1/10. 3RV2031 MSPs with a current setting limit of 45A
three-phase busbars cannot be used. Accessories can 5) Suitable for use with IE3/IE4 motors up to a starting or less do not require a type E terminal and fulfill the
be ordered separately. current of 780 A. For higher starting currents we spacing requirements of UL508.
3) Shaded ratings apply for group installation only. These recommend using 3VA circuit breakers. 7) 3RV2 MSPs can only be used with 3RT2 contactors and
ratings do not apply as UL listed manual combination accessories.
starters.
The 3RV101 MSP’s, can be used as components in Group Installation E ON/OFF rocker mechanism with lockout.
MOTOR STARTER
PROTECTORS
per NEC 430-53(C) to turn motors on and off. Each device has built-in E Adjustment dial for setting to motor FLA.
heater elements that provide overload protection and magnetic trip E Class 10 overload trip characteristics.
elements to protect the motor. When the 3RV101 is used as a
E Short circuit trip at 12 times the maximum setting of the
FLA adjustment dial.
component in Group Installation, multiple MSP’s can be installed
E Short circuit current rating:
below one circuit breaker to protect its own motor. A contactor can E Ambient compensated up to 140° F
be mounted to the MSP to provide a remotely operated starter.
(applies to side by side mounting).
E Phase loss sensitivity.
E Test trip function.
E Cage Clamp version.
E Terminal versions: screw, spring, ring lug.
E Auxiliaries and Accessories see pages 1/10–1/21.
E General Information see pages 1/33–1/36.
E Technical Data see pages 1/22–1/32.
E Dimensions see page 1/37–1/40.
Note: Select MSP by motor Full Load Amperes. Horsepower ratings are for reference only.
Single-Phase Three-Phase
FLA HP Ratings HP Ratings1) Instantaneous UL short-circuit Screw
Adjustment short circuit breaking capacity connection
Illustration Range [A] 115V 230V 200V 230V 460V 575V release [A] @ 480V [kA] Catalog Number
1) Select MSP by motor full load amps. Horse power 3) Shaded ratings apply for group installation only.
ratings for reference only. These ratings do not apply as UL listed manual
2) Size S00 MSP are listed for group installation only. combination starters.
1
Selection and ordering data
For Motor For Transformer
Protection 2) Protection 3)
PROTECTORS
MOTOR STARTER
Thermal Short Circuit Instant- Instant-
overload breaking capacity aneous Order aneous Order
Rated release [kA] Over Number Over Number
Cur- (non-ad- Current Current
1)
rent justable) 480 480Y/ 600Y/ Release (Screw Weight Release (Screw Weight
[A] [A] VAC 277VAC 347VAC [A] Terminals) [kg] [A] Terminals) [kg]
Innovations Frame Size S00 4)
0.16 0.16 — 65 10 2.1 3RV2711-0AD10 0.390 3.3 3RV2811-0AD10 0.390
0.2 0.2 — 65 10 2.6 3RV2711-0BD10 0.390 4.2 3RV2811-0BD10 0.390
0.25 0.25 — 65 10 3.3 3RV2711-0CD10 0.390 5.2 3RV2811-0CD10 0.390
0.32 0.32 — 65 10 4.2 3RV2711-0DD10 0.390 6.5 3RV2811-0DD10 0.390
0.4 0.4 — 65 10 5.2 3RV2711-0ED10 0.390 8.2 3RV2811-0ED10 0.390
0.5 0.5 — 65 10 6.5 3RV2711-0FD10 0.390 10 3RV2811-0FD10 0.390
0.63 0.63 — 65 10 8.2 3RV2711-0GD10 0.390 13 3RV2811-0GD10 0.400
0.8 0.8 — 65 10 10 3RV2711-0HD10 0.390 16 3RV2811-0HD10 0.450
1 1 — 65 10 13 3RV2711-0JD10 0.450 21 3RV2811-0JD10 0.450
1.25 1.25 — 65 10 16 3RV2711-0KD10 0.450 26 3RV2811-0KD10 0.460
1.6 1.6 — 65 10 21 3RV2711-1AD10 0.460 33 3RV2811-1AD10 0.460
2 2 — 65 10 26 3RV2711-1BD10 0.460 42 3RV2811-1BD10 0.460
2.5 2.5 — 65 10 33 3RV2711-1CD10 0.460 52 3RV2811-1CD10 0.460
3.2 3.2 — 65 10 42 3RV2711-1DD10 0.460 65 3RV2811-1DD10 0.460
4 4 — 65 10 52 3RV2711-1ED10 0.450 82 3RV2811-1ED10 0.460
5 5 — 65 10 65 3RV2711-1FD10 0.460 104 3RV2811-1FD10 0.460
6.3 6.3 — 65 10 82 3RV2711-1GD10 0.460 130 3RV2811-1GD10 0.460
8 8 — 65 10 104 3RV2711-1HD10 0.460 163 3RV2811-1HD10 0.460
10 10 — 65 10 130 3RV2711-1JD10 0.460 208 3RV2811-1JD10 0.460
12.5 12.5 — 65 10 163 3RV2711-1KD10 0.460 260 3RV2811-1KD10 0.460
15 15 — 65 — 208 3RV2711-4AD10 0.470 286 3RV2811-4AD10 0.470
Innovations Frame Size S0 4)
20 20 — 50 — 260 3RV2721-4BD10 0.514 325 3RV2821-4BD10 0.516
22 22 — 50 — 286 3RV2721-4CD10 0.516 364 3RV2821-4CD10 0.528
Innovations Frame Size S3 5)
10 10 65 — 20 150 3RV2742-5AD10 0.460 — — —
15 15 65 — 20 225 3RV2742-5BD10 0.460 — — —
20 20 65 — 20 260 3RV2742-5CD10 0.460 — — —
25 25 65 — 20 325 3RV2742-5DD10 0.460 — — —
30 30 65 — 20 390 3RV2742-5ED10 0.460 — — —
35 35 — 65 20 455 3RV2742-5FD10 0.460 — — —
40 40 — 65 20 520 3RV2742-5GD10 0.460 — — —
45 45 — 65 20 585 3RV2742-5HD10 0.460 — — —
50 50 — 65 20 650 3RV2742-5JD10 0.460 — — —
60 60 — 65 20 780 3RV2742-5LD10 0.460 — — —
70 70 — 65 10 910 3RV2742-5QD10 0.460 — — —
1) 100 % rated value acc. to UL 489 and IEC 60947-2 4) Transverse and lateral auxiliary switches can be ordered busbars. Up until now it was limited to standard 3RV20
(100 % rated breaker). separately (see “Mountable accessories”). MSPs. These new approvals will greatly enhance appli-
2) Circuit breakers for system protection of motor and non- 5) Transverse auxiliary switches must not be mounted. cation flexibility for customers. Not only can they use the
motor loads. Requires use of separate overload protec- Lateral auxiliary switches can be ordered separately (see bus systems to feed motor loads, they can now feed
tion for motor applications. “Mountable accessories”). non-motor loads which should allow the bus systems
to feed complete control panel applications. Customers
3) Circuit breakers for system and transformer protection 6) Siemens now has UL/CSA approvals for using the
will need to remove the line side terminals on any 3RV27
according to UL/CSA. Specially designed for transform- 3RV27 and 3RV28 UL489 Circuit Breakers with the
or 28s that will be fed by the bus system. Contact your
ers with high inrush current. 3RV2917 Infeed System and with the 3RV1915 comb-
Siemens representative for more information.
Refer to page 1/25 when using as upstream protection of a Manual Motor Controller or a Manual Motor Controller Suitable for Tap Conductor Protection in
Group Installations.
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/9
3RV Motor Starter Protectors SIRIUS
Accessories
Auxiliaries and Accessories
1
Auxiliary switches 3)
mm Innovations
3RV2901-1E Transverse auxiliary 1 CO S00, S0, S2, 3RV2901-1D
switches 1 NO + 1 NC S3 1), 2) 3RV2901-1E
2 NO 1) 3RV2901-1F
1) This product is also available with spring terminals. The 3) Each motor starter protector can be fitted with one 5) One auxiliary release can be mounted at the right of
order no. must be changed in the 8th position to a transverse and one lateral auxiliary switch. The lateral each MSP. motor starter protector.
“2”:e.g. 3RV1901-2E or 3RV2901-2E auxiliary switch 2 NO + 2 NC is used without trans-
6) The response voltage at the lower limit of the voltage
verse auxiliary switch.
2) This product is also available with ring lug terminals. The range at 0.85 (Tu=60°C) is valid for 100% (infinite)
order no. must be changed in the 8th position to a “4”: 4) One signaling switch can be mounted at the left of the
7) The response voltage at the lower limit of the voltage
e.g. 3RV2901-4E motor starter protector. This accessory cannot be used
range at 0.9 (Tu=60°C) applies for a duty cycle of 5
on the 3RV27 and 3RV28 circuit breakers.
seconds at AC 50/60 Hz and DC.
1/10 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
3RV Motor Starter Protectors SIRIUS
Accessories
Mounting accessories
1
Modu- Number of motor starter Rated For motor Order No. Order Weight
lar protectors that can be current starter quantity approx.
PROTECTORS
MOTOR STARTER
spac- connected In at protectors
ing Without Incl. With 690 V Size
lateral lateral auxil-
acces- auxil- iary trip
sories iary unit
switch
mm A kg
Three-phase busbar systems for Classic and Innovations
For feeding several motor starter protectors with screw
terminals, mounted side-by-side on standard mounting
rails, insulated, with touch protection.
3RV19 15-1AB
45 2 -- -- 63 S00, S01)2) 3RV19 15-1AB 1 unit 0.044
3 S00, S01)2) 3RV19 15-1BB 1 unit 0.071
4 S00, S01)2) 3RV19 15-1CB 1 unit 0.099
5 S00, S01)2) 3RV19 15-1DB 1 unit 0.124
3RV19 15-1BB 55 -- 2 -- 63 S00, S01)2) 3RV19 15-2AB 1 unit 0.048
3 S00, S01)2) 3RV19 15-2BB 1 unit 0.079
4 S00, S01)2) 3RV19 15-2CB 1 unit 0.111
5 S00, S01)2) 3RV19 15-2DB 1 unit 0.140
63 -- -- 2 63 S00, S01)2) 3RV19 15-3AB 1 unit 0.052
3RV19 15-1CB
4 S00, S01)2) 3RV19 15-3CB 1 unit 0.120
55 2 -- -- 108 S23) 3RV19 35-1A 1 unit 0.150
3 S23) 3RV19 35-1B 1 unit 0.214
4 S23) 3RV19 35-1C 1 unit 0.295
3RV19 15-1DB 75 -- 2 2 108 S2 3RV19 35-3A 1 unit 0.161
3 3 S2 3RV19 35-3B 1 unit 0.262
4 4 S2 3RV19 35-3C 1 unit 0.369
1) Not suitable for 3RV21 motor starter protectors with overload relay 2) Not suitable for 3RV UL 489 circuit breakers.
function. The 3RV1915-5DB connecting piece is available for connecting 3) Auxiliary trip units and lateral auxiliary switches cannot be used in combi-
motor starter protectors from size S0 to size S00. nation.
1) Do not mix 3RV1 Classic Accessories with 3RV2 2) Do not mix 3RV2 Innovations Accessories with 3RV1 3) This terminal is connected in place of a switch, please
Innovations MSPs Classic MSPs take the space requirement into account.
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/11
3RV Motor
Motor Starter
Starter Protectors
Protectors/Circuit Breakers
SIRIUS
SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80 A
Accessories
Accessories
Mounting accessories
Mounting accessories
Overview
1
00
408 3RW30 soft S00 S00 3RA2921- 3RA2911-
1_
IC0 starters 1BA00 2GA00
S0 S00 --
3RW30/ S0 S0 3RA2921- 3RA2921-
SIRIUS 3RV2938-1K phase barrier* 3RW40 1BA00 2GA00
soft starters S00 S0 --
* These accessories are only for screw terminals and mount on top of MSPs
S22) S22) 3RA2931- --
and are not for use on spring terminals which are located on the front of MSPs. 1AA00
If screw terminal MSPs and spring terminal contactors are preferred, a 3RF34 solid- S00/S0 S00 3RA2921- --
hybrid link module can be utilized. See note 3. state contac- 1BA00
tors
Motor starter Size Essential accessories Hybrid link modules for connecting contactors with spring-type
protectors/ for "Self-Protected Combination terminals to 3RV2 motor starter protectors/circuit breakers with
circuit breakers Motor Controllers (Type E)" according screw terminals3)
to UL 508/UL 60947-4-1
3RT2 contac- S00 S00 3RA2911- --
3RV201., 3RV202. S00/S0 3RV2928-1H terminal block or tors with AC or 2FA00
3RV2928-1K phase barrier DC coil S0 S0 3RA2921- --
3RV2031-4B1., S2 -- 2FA00
3RV2031-4D.1.,
3RV2031-4E1., -- Version not possible
3RV2031-4P.1., 1)
The link modules cannot be used for the 3RV2.21-4PA1., 3RV2.21-4FA1.,
3RV2031-4S.1., 3RV2.31-4K.1., 3RV2.31-4R.1., 3RV2.32-4K.1., 3RV2.32-4R.1., 3RV27 and
3RV2031-4T.1., 3RV28 motor starter protectors/circuit breakers.
3RV2031-4U.1., 2)
3RV2031-4V.1. To assemble the feeder between a motor starter protector and a soft starter
in size S2, the 3RA2932-1AC00 standard mounting rail adapter must be
3RV2031-4J.1., S2 3RV2938-1K phase barrier used.
3RV2031-4K.1., 3)
3RV2031-4R.1., The motor starter protector to contactor hybrid link modules cannot be
3RV2031-4W.1., used for the 3RV2.21-4PA1., 3RV2.21-4FA1., 3RV27 and 3RV28 motor
3RV2031-4X.1., starter protectors/circuit breakers. They are only suitable for constructing
3RV2032 direct-on-line starters.
3RV204 S3 3RT2946-4GA07 terminal block Note:
-- No accessories needed • Link modules can be used in
- Sizes S00 and S0: up to max. 32 A
Special 3-phase infeed terminals are required for constructing - Size S2: up to max. 65 A
“Type E Starters” with an insulated 3-phase busbar system
• Hybrid link modules can be used in
(see page 1/11). These infeed terminals are only available for 3RV20
- Sizes S00 and S0: up to max. 32 A
motor starter protectors with screw terminals.
The 3RV29 infeed system also enables the assembly of “Type E
Starters”, see page 1/18 onwards.
Note:
According to CSA, these terminal blocks and the phase barriers
can be omitted when the device is used as a "Self-Protected
Combination Motor Controller (Type E)".
1/12 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
7/38 Siemens IC 10 · 2015
maintaining the required voltage clearances
and as touch protection if box terminal is
removed (2 units can be mounted per motor
3RV Motor Starter Protectors
starter protector/circuit breaker) SIRIUS
Accessories
3RV2 (size S3) with
3RT1946-4EA1 (left)
Mounting accessories
Scale covers 3RV20, 3RV21, } 3RV2908-0P 100 10 units 41E
Sealable, 3RV24:
for covering the set current scale S00 ... S3
Selection and ordering data
1
3RV2908-0P
Covers for devices with screw terminals For motorScrew
starterterminalsInnovations Order
PROTECTORS
MOTOR STARTER
Version
(box terminals) protector size 3RV2/3RT2 Order No. Quantity
Terminal blocks andAdditional touch protection
phase barriers to be fitted at theCombination
for “Self-Protected
box terminals
Motor Controllers (Type E)” according to UL 508 / UL 60947-4-1
(2 units required per device)
3RT2936-4EA2 Note:
• Main current level }
S2 clearance and 2-inch3RT2936-4EA2 1 1 unit 41B
7
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/13
LV1N_05_04.fm Page 30 Friday, September 27, 2013 2:28 PM
Mounting accessories
Selection and ordering data
1
Single-unit packaging
S00 S00 3RA29 11-2GA00 1 1 unit 0.038
S0 S0 3RA29 21-2GA00 1 1 unit 0.072
Multi-unit packaging
S00 S00 3RA29 11-2G 1 10 units 0.380
3RA29 21-2GA00 S0 S0 3RA29 21-2G 1 10 units 0.720
5
1) The link modules for motor starter protector to soft starter and for motor Note:
starter protector to solid-state contactor cannot be used for the S0 link modules can be used up to max. 32 A.
3RV2. 21-4PA1., 3RV2. 21-4FA1., 3RV27 and 3RV28 motor starter
protectors. S2 link modules can be used up to max. 65 A.
3RA29 11-2FA00
Multi-unit packaging
AC/DC S00 S00 3RA29 11-2F 1 10 units 0.290
AC2)/DC S0 S0 3RA29 21-2F 1 10 units 0.560
Spacers2)
for compensating the height on AC contactors
Single-unit packaging S0 S0 3RA29 11-1CA00 1 1 unit 0.001
Multi-unit packaging S0 S0 3RA29 11-1C 1 5 units 0.001
3RA29 21-2FA00
1) The hybrid link modules for motor starter protector to contactor cannot be Note:
used for the 3RV2. 21-4PA1., 3RV2. 21-4FA1., 3RV27 and 3RV28 motor Hybrid link modules can be used up to max. 32 A.
starter protectors or reversing starters.
2) A spacer for height compensation on AC contactors size S0 is optionally
available. See 3RA2911-1CA00
3) To assemble the starter between a motor starter protector and a soft starter
in size S2, the 3RA2932-1AC00 standard mounting rail adapter must be used.
4) It is only permissible to assemble the feeder between the motor starter
protector and the soft starter in Size S3 on a mounting plate.
1/14 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
1
Weight
For SIRIUS Order approx.
PROTECTORS
MOTOR STARTER
Type Design MSP size Order No. Quantity (kg)
Isolator module 1)
3RV2938-1A 3RV29 28-1A Visible isolating distance for S00, S0 3RV29 28-1A 1 unit 0.132
without padlock without padlock
isolating individual motor starter
protectors from the network,
1)
lockable in isolating position. S2 3RV29 38-1A 1 unit 0.368
Covers
3RV1 (size S3) with
3RT19 46-4EA1 Terminal cover Additional touch guard
for box terminals to be fitted at the box terminals S2 3RT29 36-4EA2 1 unit 0.014
(2 units can be mounted per MSP)
S3 3RT29 46-4EA2 1 unit 0.019
Fixing Material
3RB1900-0B Push-in lugs Two units are required for
For screwing the each motor starter protector. S00 3RB19 00-0B 10 units 0.10
motor starter protector
onto mounting plates.
1) The isolator module for size S2 can be used only with 3RV2 motor 2) Compatible with 3RV20 motor starter protectors.
starter protectors/circuit breakers up to max. 65 A. Similarly, it cannot
3) Compatible with 3RV20, 3RV21, and 3RV24 motor
be used with the transverse auxiliary switch or three-phase busbars.
starter protectors.
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/15
© Siemens 2021
Protection
3RV equipment
Motor Starter Protectors SIRIUS
Motor starter protectors/circuit breakers
Accessories
SIRIUS 3RV2 motor starter protectors/circuit breakers
Rotary operating mechanisms
Accessories > Rotary operating mechanisms
Version Color of Version of For motor starter SD Article No. Price PU PS* PG
MOTOR STARTER
PROTECTORS
The door-coupling rotary operating mechanisms consist of a actuator, a coupling driver and a 130/330 mm long extension shaft
(6 mm x 6 mm).
The door-coupling rotary operating mechanisms are dimensioned for degree of protection IP64. For UL/CSA applications, they are
approved for Enclosure Types 1, 3R and 12. The door interlocking prevents accidental opening of the control cabinet door in the
ON position of the motor starter protector. The OFF position can be locked with up to three padlocks.
With the optional 3RV2926-0Q tolerance compensation, an offset can be compensated when installing the door-coupling rotary
operating mechanism.
Door-coupling Gray 130 S001) ... S3 X 3RV2926-1B 1 1 unit 41E
rotary 330 S001) ... S3 X 3RV2926-1K 1 1 unit 41E
operating
3RV2926-1B mechanisms
EMERGENCY Red/ 130 S001) ... S3 X 3RV2926-1C 1 1 unit 41E
OFF door- yellow 330 S001) ... S3 X 3RV2926-1L 1 1 unit 41E
coupling
rotary
operating
mechanisms
3RV2926-1C
Optional accessories
7
3RV2926-0Q
1) Not for 3RV1011 motor starter protectors.
1/16 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
Version Color of Version of For motor starter SD Article No. Price PU PS* PG
1
actuator extension shaft protectors/circuit per PU (UNIT,
breakers SET, M)
PROTECTORS
MOTOR STARTER
mm Size d
Door-coupling rotary operating mechanisms for harsh conditions
The door-coupling rotary operating mechanisms consist of a actuator, a coupling driver, an extension shaft of 300 mm in length
(8 mm x 8 mm), a spacer and two metal brackets into which the motor starter protector/circuit breaker is inserted.
The door-coupling rotary operating mechanisms are designed to degree of protection IP65. For UL/CSA applications, they are
approved for Enclosure Types 1, 3R and 12. The door interlocking reliably prevents opening of the control cabinet door in the
ON position of the motor starter protector/circuit breaker. The OFF position can be locked with up to three padlocks.
Laterally mountable auxiliary releases and 2-pole auxiliary switches can be used.
The door-coupling rotary operating mechanisms thus meet the requirements for isolating functions according to IEC 60947-2.
With the optional 3RV2926-2Q tolerance compensation, an offset can be compensated when installing the door-coupling rotary
operating mechanism for harsh conditions.
Door-coupling Gray 300 S001), S0 NEW NEU
X 3RV2926-3B 1 1 unit 41E
3RV2946-3B
rotary S2 NEW NEU
X 3RV2936-3B 1 1 unit 41E
operating
mechanisms S3 NEW NEU
X 3RV2946-3B 1 1 unit 41E
EMERGENCY Red/ 300 S001), S0 NEW NEU
X 3RV2926-3C 1 1 unit 41E
OFF door- yellow S2 NEW NEU
X 3RV2936-3C 1 1 unit 41E
coupling
rotary S3 NEW NEU
X 3RV2946-3C 1 1 unit 41E
operating
mechanisms
3RV2946-3C
Optional accessories
Tolerance -- -- S00 ... S3 NEW NEU
X 3RV2926-2Q 1 1 unit 41E
compensation
7
3RV2926-2Q
Necessary accessories for mounting one main switch in size S3 according to UL 508A and NFPA 79
(see also page 7/55)
Shaft supports -- -- S3 NEW NEU
X 3RV2926-0P 1 1 unit 41E
3RV2926-0P
Supplementary
handles
• Standard Gray -- S3 2 3VA9137-0GC01 1 1 unit 12P
3VA9137-0GC01
• EMERGENCY Red/ -- S3 2 3VA9137-0GC05 1 1 unit 12P
OFF yellow
3VA9137-0GC05
1) Not for 3RV1011 motor starter protectors.
Overview
The 3RV29 infeed system is a convenient means of energy two sockets onto each of which a motor starter protector can
supply and distribution for a group of several motor starter
MOTOR STARTER
PROTECTORS
be snapped.
protectors or complete motor starters with a screw or spring-
type connection in sizes S00 and S0 (exception: this system Expansion modules are available for extending the system
cannot be used for the 3RV21). (three-phase busbars for system expansion). The individual
modules are connected through an expansion plug.
Siemens now has UL/CSA approvals for using the 3RV27 and
3RV28 UL489 Circuit Breakers with the 3RV2917 Infeed System The electrical connection between the three-phase busbars and
and with the 3RV1915 comb-busbars. Up until now it was lim- the motor starter protectors is implemented through plug-in
ited to standard 3RV20 MSPs. These new approvals will greatly connectors. The complete system can be mounted on a TH 35
enhance application flexibility for customers. Not only can they standard mounting rail to EN 60715 and can be expanded as
use the bus systems to feed motor loads, they can now feed required up to a maximum current carrying capacity of 63 A.
non-motor loads which should allow the bus systems to feed The system is mounted extremely quickly and easily thanks to
complete control panel applications. Customers will need to the simple plug-in technique. Thanks to the lateral infeed, the
remove the line side terminals on any 3RV27 or 28s that will be system also saves space in the control cabinet. The additional
fed by the bus system. overall height required for the infeed unit is only 30 mm. The
The 3RV29 infeed system is approved in accordance with alternative infeed possibilities on each side offer a high degree
IEC to 500V. It is also UL approved and authorized for “Self- of flexibility for configuring the control cabinet: Infeed on left-
Protected Combination Motor Controller” (Type E starter) as hand or right-hand side as well as infeed on one side and out-
well as for Type F starter (Type E starter + contactor). The feed on the other side to supply further loads are all possible.
system is based on a basic module complete with a lateral A terminal block with spring-type connections in combination
incoming unit (three-phase busbar with infeed). This infeed with with a standard mounting rail enables the integration of not only
spring-type terminals is mounted on the right or left depending SIRIUS motor starter protectors but also single-phase, 2-phase
on the version and can be supplied with a maximum conductor and 3-phase components such as 5SY miniature circuit breakers
cross-section of 4 AWG (with end sleeve). A basic module has or SIRIUS relay components.
55
3b
3b
5
5 3a
3a
5
5
1
1
2
2
4
4
7
7
6
6
NSB0_02078
NSB0_02078
1 3-phase busbar with infeed 3a Expansion plug 4 End cover 6 Contactor base
1 3-phase busbar with infeed 3a Expansion plug 4 End cover 6 Contactor base
2 3-phase busbar for system expansion 3b Extra-wide expansion plug 5 Plug-in connector 7 Terminal block
2 3-phase busbar for system expansion 3b Extra-wide expansion plug 5 Plug-in connector 7 Terminal block
1/18 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
SIRIUS Innovations Supplement 2012 5/23
SIRIUS Innovations Supplement 2012 5/23
3RV Motor Starter Protectors SIRIUS
SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A
Accessories
Accessories
3RV29 infeed system
3RV29 infeed system
$ Three-phase busbars with infeed * Contactor base
1
A three-phase busbar with infeed unit is required for connecting Motor starters can be assembled in the system using the contac-
the energy supply. This module comprises one infeed module tor base. The contactor bases are suitable for contactors sizes
PROTECTORS
MOTOR STARTER
and 2 sockets which each accept one motor starter protector. A S00 and S0 with spring-type and screw terminals and are simply
choice of two versions with infeed on the left or right is available. snapped onto the three-phase busbars. Direct-on-line starters
The infeed is connected using spring-type terminals. The and reversing starters are possible. One contactor base is re-
spring-type terminals permit conductor cross-sections of up to quired for direct-on-line starters and two are required for revers-
25 mm2 with end sleeves. An end cover is supplied with each ing starters.
module.
To assemble motor starters for reversing starters, the contactor
% Three-phase busbars for system expansion bases can be arranged alongside each other (90 mm overall
width). In this case the mechanical interlocking of the contactors
The three-phase busbars for system expansion allow the system is possible. The contactor bases are also suitable for soft start-
to be expanded. There is a choice of modules with 2 or 3 sock- ers size S00 and S0 with screw connection.
ets. The system can be expanded as required up to a maximum
current carrying capacity of 63 A. An expansion plug is supplied The infeed system is designed for mounting on a 35 mm stan-
with each module. dard mounting rail with 7.5 mm overall depth. This standard
mounting rail gives the contactor base a stable mounting sur-
&a Expansion plug face to sit on. If standard mounting rails with a depth of 15 mm
are used, the spacer connected to the bottom of the contactor
The expansion plug is used for electrical connection of adjacent base must be knocked out and plugged into the mating piece
three-phase busbars. The current carrying capacity of this plug that is also on the underside. Then the contactor base also has
equals 63 A. One expansion plug is supplied with each three- a stable mounting surface. When standard mounting rails with a
phase busbar for system expansion. Additional expansion plugs depth of 7.5 mm are used, the spacer has no function and can
are therefore only required as spare parts. be removed.
&b Extra-wide expansion plug The link modules are used for direct start motor starters, in which
The wide expansion plug makes the electrical connection be- case the use of a contactor base is not absolutely necessary.
tween two three-phase busbars, thus performing the same func- Motor starter protector and contactor assemblies can then be di-
tion as the 3RV29 17-5BA00 expansion plug; the electrical char- rectly snapped onto the sockets of the three-phase busbars. For
acteristics (e.g. a current carrying capacity of 63 A) are starters of size S00 and S0, the corresponding 3RA19 21-1....,
5
) Plug-in connector
The plug-in connector is used for the electrical connection be-
tween the three-phase busbar and the 3RV2 motor starter pro-
tector. These plug-in connectors are available in versions for
screw or spring-type terminals.
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/19
5/24 SIRIUS Innovations Supplement 2012
SIRIUS
SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A
3RV Motor Starter Protectors
Accessories Accessories
3RV29 infeed system
3RV29 infeed system
3RV29 17-1A
Three-phase busbars for system expansion
Three-phase For motor starter
busbars protectors with
incl. 3RV29 17- screw connection or
5BA00 expansion spring-type
plug terminals
• For 2 motor starter S00, S0 3RV29 17-4A 1 unit 0.229
protectors
• For 3 motor starter S00, S0 3RV29 17-4B 1 unit 0.328
protectors
5
3RV29 17-4A
Plug-in connectors
Plug-in • For spring-type Spring-type
connectors terminals terminals
to make contact - Single-unit S001) 3RV29 17-5AA00 1 unit 0.046
with the motor packaging S02) 3RV29 27-5AA00 1 unit 0.059
starter protectors
- Multi-unit S001) 3RV29 17-5A 10 units 0.046
packaging S02) 3RV29 27-5A 10 units 0.059
3RV29 17-5AA00
• For screw Screw terminals
terminals
- Single-unit S001) 3RV29 17-5CA00 1 unit 0.029
packaging S02) 3RV19 27-5AA00 1 unit 0.040
- Multi-unit S001) 3RV29 17-5C 10 units 0.029
packaging 2) 3RV19 27-5A 10 units 0.036
S0
3RV29 17-5CA00
3RV29 27-7AA00
1) I > 14 A, note derating; see the system manual "SIRIUS Innovations",
Chapter "Motor Starter Protectors".
2) I > 16 A, note derating; see the system manual "SIRIUS Innovations",
Chapter "Motor Starter Protectors".
1
Type Version Order No. Standard Weight
Pack approx.
Quantity
PROTECTORS
MOTOR STARTER
kg
Terminal blocks
Terminal blocks Single-unit packaging 3RV29 17-5D 1 unit 0.049
For integration of
single-phase, two-phase
and three-phase
components
3RV29 17-5D
45 mm standard mounting rails
45 mm standard Single-unit packaging 3RV19 17-7B 1 unit 0.261
mounting rails
for mounting onto
bus bar adapters
3RV19 17-7B
Extra-wide expansion plugs
Extra-wide expansion Single-unit packaging 3RV29 17-5E 1 unit 0.037
plugs as accessory
5
3RV29 17-5E
Expansion plugs
Expansion plugs1) Single-unit packaging 3RV29 17-5BA00 1 unit 0.026
as spare part
3RV29 17-5BA00
End covers
End covers2) Multi-unit packaging 3RV29 17-6A 10 units 0.005
as spare part
3RV29 17-6A
Terminal blocks for device infeed
Terminal blocks for Single-unit packaging 3RV29 17-5FA00 1 unit 0.010
device infeed
3RV29 17-FA00
1) The expansion plug is included in the scope of supply of the 3RV29 17-4
three-phase busbars for system expansion.
2) The end cover is included in the scope of supply of the 3RV29 17-1 three-
phase busbars with infeed system.
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/21
* You can order this quantity or a multiple thereof.
5/26 SIRIUS Innovations Supplement 2012 Illustrations are approximate
3RV Motor Starter Protectors SIRIUS
General Data
3RV — up to 100 A (Domestic applications)
Motor starter protectors of the 3RV2 series are approved for These motor starter protectors can be used as "Manual Motor
Motor starter protectors of the 3RV2 series are approved for These motor starter protectors can be used as "Manual Motor
UL/CSA, and according to UL508/UL 60947-4-1 and CSA C22.2 Controllers" for "Group Installations", as "Manual Motor Control-
UL/CSA, and according to UL508/UL 60947-4-1 and CSA C22.2 Controllers" for "Group Installations", as "Manual Motor Control-
No. 14/CSA C22.2 No. 60947-4-1 they can be used on their own lers Suitable
Suitable for Tap Conductor Protection in Group Installations"
MOTOR STARTER
PROTECTORS
No. 14/CSA C22.2 No. 60947-4-1 they can be used on their own lers for Tap Conductor Protection in Group Installations"
and as "Self-Protected Combination Motor Controllers" (Type E).
or as load feeders in combination with a contactor. and as "Self-Protected Combination Motor Controllers" (Type E).
or as load feeders in combination with a contactor.
1/22 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
3RV Motor Starter Protectors SIRIUS
General Data
3RV — up to 100 A (Domestic applications)
1
3RV motor starter protectors as "Manual Motor Controllers Suitable for Tap Conductor Protection in Group Installations"
The application as "Manual Motor Controllers Suitable for Tap protector according to UL 489 can be used.
PROTECTORS
MOTOR STARTER
Conductor Protection in Group Installations" is only available These devices must be dimensioned according to the National
from UL. Electrical Code.
CSA does not
3RV motor recognize
starter this as
protectors approval!
"ManualWhen Motorthe motor starter
Controllers Suitable for Tap Conductor Protection in Group Installations"
protector is used as a "Manual Motor Controller Suitable for Tap The 3RV motor starter protectors are approved as "Manual
The application
Conductor as "Manual
Protection Motor
in Group Controllers itSuitable
Installations", for Tap
must always be Motor Controllers
protector accordingSuitable for Tap
to UL 489 canConductor
be used. Protection in
Conductor
combined withProtection in Group
upstream Installations"
short-circuit is only
protection. Asavailable
short-cir- Group Installations"
These devices mustunder the following
be dimensioned file number:
according to the National
from UL.
cuit-protection device, approved fuses or a motor starter •Electrical
UL File Code.
No. 47705, CCN: NLRV.
CSA does not recognize this approval! When the motor starter
protector is used as a "ManualhpMotor The 3RV motor starter protectors are approved as "Manual
Motor starter ratingController
1) for FLA2) Suitable for Tap
Rated 240 V AC
Motor Up tofor
Controllers Suitable 480Y/277V AC
Tap Conductor UpProtection
to 600Y/347V
in AC
Conductor
protectors Protection in Group Installations", it must always
max. In
current be
combined with upstream short-circuit protection. As short-cir- Group
UL Installations" under
UL the following file ULnumber:
cuit-protection device, approved fuses or a motor starter I•bcUL
3)
Ibc3) NLRV.
File No. 47705, CCN: Ibc3)
1)
HP rating = Power rating in horse power (maximum motor rating).
2) FLA = Full Load Amps/Motor full load current.
3) Complies with "short-circuit breaking capacity" according to UL.
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/23
3RV Motor Starter Protectors SIRIUS
General Data
3RV — up to 100 A (Domestic applications)
3RV motor starter protectors as "Self-Protected Combination Motor Controllers (Type E)"
1
UL 508/UL 60947-4-1 approval demands 1-inch clearance and when the device is used as a “Self-Protected Combination Motor
2-inch creepage distance at line side for “Self-Protected Combination Controller”.
MOTOR STARTER
PROTECTORS
3RV motor
Motor starter
Controller protectors
Type E”. as "Self-Protected Combination Motor Controllers (Type E)"
The 3RV20 motor starter protectors are approved as “Self-Protected
Therefore, 3RV20 motor starter protectors of sizes S00 to S2 are Combination Motor Controllers” under the following file numbers:
approved according to UL 508/UL 60947-4-1 in combination with the • UL File No. E156943, CCN: NKJH
terminal blocks listed below.
• CSA Master Contract 165071, Product Class: 3211 08
CSA does not require these extended clearances and creepage
distances. According to CSA, these terminal blocks can be omitted
Motor starter hp rating1) for FLA2) Rated current Up to 240 V AC Up to 480 Y/277 V AC Up to 600 Y/347 V AC
protectors max. In UL/CSA Ibc3) UL/CSA Ibc3) UL/CSA Ibc3)
Type V 1-phase 3-phase A kA kA kA
Size S00
Motor starter hp rating1) for FLA2) Rated current Up to 240 V AC Up to 480 Y/277 V AC Up to 600 Y/347 V AC
protectors max. In UL/CSA Ibc3) UL/CSA Ibc3) Ibc3)
3RV2011 + 3RV29 28-1H4) 5) 0.16 ... 12.5 65 65 UL/CSA
30
Type2) V 1-phase 3-phase A
16 kA
65 kA
65 kA
—
FLA max. 16 A 115 1 2
Size S00
480 V 200 2 3
3RV2011 + 3RV29 28-1H4) 5) 0.16 ... 12.5 65 65 30
NEMA size 0 230 2 5
16 65 65 —
FLA2) max. 16 A 230
115 —
1 10
2
480 V 575/600
200 —
2 10
3
Size S0
NEMA size 0 230 2 5
3RV2021 + 3RV29 28-1H2304) 5) — 10 0.63 ... 1.6 65 65 30
575/600 — 10 2 65 65 30
FLA 2) max. 2.5 65 65 30
Size S0 115 2 5
25 A, 480 V 2004) 5) 3 7.5 3.2 65 65 30
3RV2021 + 3RV29
12.5 A, 600 V 28-1H
230 3 10 0.63
4 ... 1.6 65
65 65
65 30
30
2 65
65 65
65 30
2) max. 460 — 20 5 30
FLA 115 2 5 2.5 65 65 30
NEMA size 1 575/600 — — 6.3 65 65 30
25 A, 480 V 200 3 7.5 3.2 65 65 30
8 65 65 30
12.5 A, 600 V 230 3 10 4 65
65 65
65 30
10 30
460 — 20 5 65 65 30
NEMA size 1 575/600 — — 12.5 65 65 30
6.3 65
65 65
65 30
16 —
8 65
65 65
65 30
20 —
10 65
65 65
65 30
—
22
12.5
25 65 65 30
—
16
32 65
50 65
50 —
20 65 65 —
Size S2 22 65
3RV2031 3RV2032 65
3RV2031 3RV2032 —
3RV2031 3RV2032
25
14 65
65 100 6565 100 —
25 25
Size S2 32 50 50 —
3RV2031/3RV2032 + 3RV2938-1K 4) 17 65 100 65 100 25 25
3RV2031/3RV2032 + 3RV2938 16 65 65 25
20
20 6565 100 6565 100 25
25 25
FLA 2)
2) MAX. 65A 115/120 5 10 25
25 6565 100 6565 100 25
25 25
Size S2
FLA
600V
max. 115
200/208
3
10
--
20 32 65 100 65 100 25 25
50 A, 600 V 200 7 1/2 15 32 65 65 25
3RV2031/3RV2032
NEMA
NEMA size
size 22 + 3RV2938
230/240
230 15
10 25
20 16
36
40 65
6565 100 65
6565 100 25
25
25 25
460/480
460 —
-- 50
40 20
40
45 65
6565 100 65
6565 100 25
22
25 22
2)
FLA max. 115
575/600 3
-- --
50 25
50 65 65 25
575/600 — 60 45 6565 100 6565 100 25
22 22
50 A, 600 15
Size S3 V 200 7 1/2 32
52 6565 100 6565 100 25
22 22
NEMA size 2 230 10 20 40 65 65 25
3RV2041 + 3RT2946-4GA07 4) 59
16 6565 100 2065 30 —30 —
460 -- 40 45 25
575/600 -- 50 20
65
50 6565 100 2065 30 —30
25 —
2) 25 65 65 30
Size S3
FLA max. 115 10 --
100 A, 480 V 200 4) 20 30 32 65 65 30
3RV2041 + 3RT2946-4GA07
230 20 40 16
40 65
65 65
65 30
30
75 A, 600 V 20 65 65 30
460 -- 75 50 65 65 30
FLA2) max.
NEMA size 3 115
575/600 10
-- --
75 25 65 65 30
200 20 30 63 65 65 30
100 A, 480 V 32
75 65
65 65
65 30
30
75 A, 600 V 230 20 40 40
90 65
65 65
65 30
—
460 -- 75 50
100 65
65 65
65 30
—
NEMA size 3 575/600 -- 75 63 65 65 30
Ratings of the auxiliary switches Lateral auxiliary65
75 switch with Transverse
65 auxiliary Transverse
30
and alarm switches 1 NO + 1 NC, 2 NO,
90 65 2 NC, switch
65 with auxiliary
— switch with
2
100 NO + 2 NC and signalling
65 switch 1 changeover
65 contact 1—NO + 1 NC, 2 NO
Ratings
Max. ratedof the auxiliary
voltage switches
• to NEMA u AC V 600
Lateral auxiliary switch with Transverse auxiliary 250
Transverse
and alarm switches • to NEMA s AC V 1600
NO + 1 NC, 2 NO, 2 NC, switch with 250
auxiliary switch with
Uninterrupted current A 210NO + 2 NC and signalling switch 1
5 changeover contact 1 NO + 1 NC, 2 NO
2.5
Breaking
Max. rated capacity
voltage • to NEMA u AC V A600
600 B600 C300
250
Q300 R300 R300
• to NEMA s AC V 600 250
1) HP rating = Power rating in horse power (maximum motor rating). 3) Corresponds to "short-circuit breaking capacity" according to UL/CSA.
U n i n t e r r u p t e d c u rre n t
2) FLA = Full Load Amps/Motor full load current. A 10 5
4) Not required for CSA. 2.5
Breaking capacity A600 B600 C300
5) Alternatively, the 3RV2928-1K phase barrier can also be used.
Q300 R300 R300
1) HP rating = Power rating in horse power (maximum motor rating). 3) Corresponds to "short-circuit breaking capacity" according to UL/CSA.
2) FLA = Full Load Amps/Motor full load current. 4) Not required for CSA.
5) Alternatively, the 3RV2928-1K phase barrier can also be used.
1/24 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
3RV Motor Starter Protectors SIRIUS
General Data
3RV27/28 circuit breakers
1
These circuit breakers are approved according to UL 489 and The 3RV27/28 circuit breakers are approved under the
CSA C22.2 No. 5-02 for 100 % rated current (100 % rated following file numbers:
PROTECTORS
MOTOR STARTER
breaker). They can be used therefore as upstream short-circuit • UL File No. E235044, CCN: DIVQ,
protective devices for "Manual Motor Controllers" and "Manual
Motor Controllers Suitable for Tap Conductor Protection in • CSA Master Contract 165071, Product Class: 1432 01.
Group Installations".
Circuit breakers Rated 240 V AC 480 Y/277 V AC 480 V AC 600 Y/347 V AC
current In UL/CSA UL/CSA UL/CSA UL/CSA
Type A I bc1) kA Ibc1) kA Ibc1) kA Ibc1) kA
Size S00/S0
3RV27 11 / 3RV28 11 0.16 … 1.25 65 65 — 10
3RV27 21 / 3RV28 21 1.6 65 65 — 10
2 65 65 — 10
2.5 65 65 — 10
3.2 65 65 — 10
4 65 65 — 10
5 65 65 — 10
6.3 65 65 — 10
8 65 65 — 10
10 65 65 — 10
12.5 65 65 — 10
15 65 65 — --
20 50 50 — --
22 50 50 — --
Size S3
3RV27 42 10 65 65 65 20
15 65 65 65 20
20 65 65 65 20
25 65 65 65 20
30 65 65 65 20
35 65 65 — 20
40 65 65 — 20
45 65 65 — 20
50 65 65 — 20
60 65 65 — 20
70 65 65 — 10
1) Complies with "short-circuit breaking capacity" according to UL.
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/25
3RV Motor Starter Protectors SIRIUS
General Data
3RV — up to 100 A (Export applications)
Technical specifications
1
Short-circuit breaking capacity Icu, Ics acc. to IEC 60947-2 table, a back-up fuse is required. It is also possible to install an
MOTOR STARTER
PROTECTORS
This table shows the rated ultimate short-circuit breaking upstream motor starter protector/circuit breaker with a limiter
capacity Icu and the rated service short-circuit breaking function.
capacity Ics of the 3RV2 motor starter protectors/circuit breakers
with different inception voltages dependent of the rated current The maximum rated current for the back-up fuse is specified in
In of the motor starter protectors/circuit breakers. the tables. The rated ultimate short-circuit breaking capacity
then applies as specified on the fuse.
Power can be supplied to the motor starter protectors/circuit
Fuseless construction
breakers via the terminals at the top or at the bottom without
restricting the rated data. If the short-circuit current at the place Motor starter protector contactor combinations for short-circuit
of installation exceeds the rated short-circuit breaking capacity currents up to 150 kA can be ordered in the form of fuseless load
of the motor starter protector/circuit breaker as specified in the feeders according to Chapter 6.
Type A kA kA A kA kA A kA kA A kA kA A kA kA A
Size S00
3RV2.11 0.16 ... 1 100 100 ° 100 100 ° 100 100 ° 100 100 ° 100 100 °
1.25; 1.6 100 100 ° 100 100 ° 100 100 ° 100 100 ° 100 100 °
2; 2.5 100 100 ° 100 100 ° 100 100 ° 100 100 ° 10 10 25
3.2; 4 100 100 ° 100 100 ° 50 10 ° 100 100 ° 10; 6 10; 4 32
5; 6.3 100 100 ° 100 100 ° 50 10 ° 100 100 ° 6 4 32
8 100 100 ° 50 12.5 ° 50 50 63 42 42 63 6 4 50
10 100 100 ° 50 12.5 ° 50 50 80 42 42 63 6 4 50
12 100 100 ° 50 12.5 ° 50 50 80 42 42 80 4 4 63
16 100 100 ° 55 30 100 50 10 80 10 5 80 4 4 63
Size S0
3RV2.21 16 100 100 ° 55 25 100 50 10 80 10 5 80 4 2 63
20 100 100 ° 55 25 125 50 10 80 10 5 80 4 2 63
22 100 100 ° 55 25 125 50 10 100 10 5 80 4 2 63
25 100 100 ° 55 25 125 50 10 100 10 5 80 4 2 63
28 100 100 ° 55 25 125 30 10 125 10 5 100 4 2 100
32 100 100 ° 55 25 125 30 10 125 10 5 100 4 2 100
36 100 100 ° 20 10 125 12 8 125 6 3 100 3 2 100
40 100 100 ° 20 10 125 12 8 125 6 3 100 3 2 100
Size S2
3RV2.31 14; 17 100 100 ° 65 30 100 50 25 100 12 6 63 5 3 63
20 100 100 ° 65 30 100 50 25 100 12 6 80 5 3 80
25 100 100 ° 65 30 100 50 15 100 12 6 80 5 3 80
32; 36 100 100 ° 65 30 125 50 15 125 10 5 100 4 2 100
40; 45 100 100 ° 65 30 160 50 15 125 10 5 100 4 2 100
52 100 100 ° 65 30 160 50 15 125 10 5 125 4 2 125
59 ... 80 Values on request
Size S2, with increased
switching capacity
3RV2.32 14; 17 100 100 ° 100 50 ° 65 30 100 18 10 63 8 5 63
20; 25 100 100 ° 100 50 ° 65 30 100 18 10 80 8 5 80
32 ... 45 100 100 ° 100 50 ° 65 30 125 15 8 100 6 4 100
52 100 100 ° 100 50 ° 65 30 125 15 8 125 6 4 125
59 ... 80 Values on request
Size S3
3RV2. 41 40 100 100 ° 50 25 125 50 20 125 12 6 100 6 3 63
50 100 100 ° 50 25 125 50 20 125 12 6 100 6 3 80
63 100 100 ° 50 25 160 50 20 160 12 6 100 6 3 80
75 100 100 ° 50 25 160 50 20 160 8 4 125 5 3 100
90; 100 100 100 ° 50 25 160 50 20 160 8 4 125 5 3 125
1/26 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
3RV Motor Starter Protectors SIRIUS
General Data
3RV — up to 100 A (Export applications)
Short-circuit breaking capacity IcuIT in the IT system In the colored areas, IcuIT is 100 kA, or in some ranges it is
1
(IT network) according to IEC 60947-2 50 kA. Therefore the motor starter protectors are short-circuit re-
sistant in these ranges.
PROTECTORS
MOTOR STARTER
3RV motor starter protectors are suitable for operation in
IT systems. Values valid for triple-pole short-circuit are Icu up to If the short-circuit current at the place of installation exceeds the
Ics. In case of double ground fault on different phases at the in- rated short-circuit breaking capacity of the motor starter protec-
put and output side of a motor starter protector, the special tor as specified in the table, a back-up fuse is required. The max-
short-circuit breaking capacity IcuIT applies. The specifications imum rated current for the back-up fuse is specified in the ta-
in the table below apply to 3RV motor starter protectors. bles. The rated short-circuit breaking capacity then applies as
specified on the fuse.
Motor starter Rated current Up to 240 V AC1) Up to 400 V1)/415 V AC2) Up to 500 V1)/525 V AC2) Up to 690 V AC1) 5)
protectors In IcuIT Max. fuse IcuIT Max. fuse IcuIT Max. fuse IcuIT Max. fuse
(gL/gG)3) (gL/gG)3)4) (gL/gG)3) (gL/gG)3)
Type A kA A kA A kA A kA A
Size S00
3RV20, 0.16 ... 0.63 100 ° 100 ° On request On request On request On request
3RV26 11-0BD10 0.8; 1 100 ° 100 °
1.25; 1.6 100 ° 100 °
2; 2.5 100 ° 8 25
3.2; 4 100 ° 8;4 32
5; 6.3 100 ° 4 32:50
8; 10 100 ° 4 50
12.5 100 ° 4 63
16 55 80 4 63
Size S0
3RV2.21 16 55 80 4 63 2 50 1.5 40
20 55 80 4 63 2 50 1.5 50
22 55 80 4 63 2 50 1.5 50
25 55 80 4 63 2 50 1.5 50
28 55 80 2 63 2 63 1.5 63
32 55 80 2 63 2 63 1.5 63
36 20 80 2 63 2 63 1.5 63
40 20 80 2 63 2 63 1.5 63
Size S2
3RV2.31 14...25 100 ° 8 100 6 80 4 63
32...45 100 ° 6 125 4 100 3 80
52 100 ° 4 160 3 125 2 100
59 ... 80 Values on request
Size S2, with increased
switching capacity
3RV2.32 14 ... 25 100 ° 8 100 6 80 4 63
32 ... 45 100 ° 6 125 6 100 4 80
52 100 ° 6 160 6 125 4 100
59 ... 80 Values on request
Size S3
3RV2. 41 40 50 125 10 63 5 50 5 50
50 50 125 8 80 3 63 3 63
63 50 160 6 80 3 63 3 63
75 50 160 5 100 2 80 2 80
90; 100 50 160 5 125 2 100 2 100
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/27
3RV Motor Starter Protectors SIRIUS
General Data
3RV — up to 100 A
Technical data
1
When mounting MSPs, the following clearance must be maintained to grounded or live
parts.
SIRIUS MSP Clearance to grounded or live parts Minimum clearance between MSPs and grounded
Y X at the side Z or live parts
Type size mm mm mm
3RV2.1 S00 up to 690 V 30 70 9
3RV2. 2 S0 2) up to 500 V 30 90 9
up to 690 V 50 1) 90 30
3RV2. 3 S2 up to 690 V 50 — 10
3RV2. 4 S3 up to 240 V 50 167 10
up to 440 V 70 167 10
up to 500 V 110 167 10
up to 690 V 150 167 30
3RV27 42 S3 up to 240 V 90 167 10
up to 400 V 90 167 10
1) Up to and including the setting range of 32 A. For the 36/40 A setting range the clearance is 70 mm.
2) In conjunction with the type E terminal block 3RV2928-1H the applicable lateral clearance is 30 mm for all voltages.
Wiring module
1/28 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
© Siemens AG 2015
3RV Motor Starter Protectors SIRIUS
Motor Starter
General Data Protectors/Circuit Breakers
SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80 A
3RV — up to 80 A
General data
General data
1
Type 3RV2.1. 3RV2.2. 3RV2.3. 3RV27, 3RV28
PROTECTORS
MOTOR STARTER
Size S00 S0 S2 S00, S0
H
Dimensions (W x H x D)
• Screw terminals mm 45 x 97 x 91 45 x 97 x 91 55 x 140 x 149 45 x 144 x 92
D
W
• Spring-type terminals mm 45 x 106 x 91 45 x 119 x 91 -- --
Standards
• IEC 60947-1, EN 60947-1 (VDE 0660 Part 100) Yes
• IEC 60947-2, EN 60947-2 (VDE 0660 Part 101) Yes
• IEC 60947-4-1, EN 60947-4-1 (VDE 0660 Part 102) Yes Yes Yes --
• UL 508/UL 60947-4-1, CSA C22.2 No. 14/CSA C22.2 No. 60947-4-1 Yes Yes Yes --
• UL 489, CSA C22.2 No. 5 -- -- -- Yes
Number of poles 3
Max. rated current In max A 16 40 80 22
(= max. rated operational current Ie)
Permissible ambient temperature
• Storage/transport °C –50 ... +80
• Operation In: 0.16 ... 32 A °C –20 ... +70 --
(current reduction above +60 °C)
In: 36 ... 40 A °C -- –20 ... +40 --
(the devices must
not be mounted
side-by-side and
they must not be
assembled with
link modules with
contactors.
A lateral clear-
ance of 9 mm is
required.)
In: 14 ... 80 A °C -- –20 ... +70 --
7
(current reduction
above +60 °C)
Permissible rated current at inside temperature of control cabinet
• +60 °C % 100
• +70 °C % 87
Permissible rated current at ambient temperature of enclosure
(applies for motor starter protector/circuit breaker inside enclosure ≤ 32 A)
• +35 °C % 100 On 100
• +60 °C % 87 request 87
Rated operational voltage Ue
• Acc. to IEC V AC 690 (when a molded-plastic enclosure is used only 500 V)
• Acc. to UL/CSA V AC 600
Rated frequency Hz 50/60
Rated insulation voltage Ui V 690
Rated impulse withstand voltage Uimp kV 6
Utilization category
• IEC 60947-2 (motor starter protector/circuit breaker) A
• IEC 60947-4-1 (motor starter) AC-3
Trip class CLASS Acc. to IEC 60947-4-1 10 10/20 --
DC short-circuit breaking capacity (time constant t = 5 ms)
• 1 conducting path 150 V DC kA 10 On 10
• 2 conducting paths in series 300 V DC kA 10 request 10
• 3 conducting paths in series 450 V DC kA 10 10
Power loss Pv for each motor starter In: 0.16 ... 0.63 A W 5 -- 5
protector/circuit breaker In: 0.8 ... 6.3 A W 6 -- 6
Dependent on In: 8 ... 16 A W 7 -- 7
the rated current In In: 16 A W -- 7 10 7
(upper setting range)
In: 17 ... 25 A W -- 8 12 8
P In: 28 ... 32 A
R per conducting path = -------------- W -- 11 14 --
Ι 2× 3 In: 36 ... 40 A W -- 14 15 --
In: 45 ... 52 A W -- -- 17 --
In: ... 80 A W -- -- On request --
Shock resistance Acc. to IEC 60068-2-27 g/ms 25/11 (square and sine pulse)
Protection class IP on the front Acc. to IEC 60529 IP20
Touch protection Acc. to EN 50274 Finger-safe for vertical contact from the front
Temperature compensation Acc. to IEC 60947-4-1 °C –20 ... +60
Phase failure sensitivity Acc. to IEC 60947-4-1 Yes (only for 3RV23 motor starter protectors) No
Explosion protection – Safe operation of motors with Yes (only for 3RV20 motor starter protectors)
"increased safety" type of protection
EC type test certificate number according to DMT 02 ATEX F 001 II (2) GD On request No
directive 94/9/EC (ATEX)
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/29
7/16 Siemens IC 10 · 2015
© Siemens AG 2015
3RV Motor Starter Protectors SIRIUS
General Data Motor Starter Protectors/Circuit Breakers
SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80 A
3RV — up to 80 A
General data
3RV2.31-4E.1., 3RV2.31-4R.1.,
3RV2.31-4P.1., 3RV2.31-4W.1.,
3RV2.31-4S.1., 3RV2.31-4X.1.,
3RV2.31-4T.1., 3RV2431-4VA1.,
3RV2.31-4U.1., 3RV2.32
3RV2.31-4V.1.
Size S00 S0 S2 S00, S0
Connection type Screw terminals
7
1 or 2 conductors can be connected
• Solid or stranded mm2 2 x (0.5 ... 4) 2 x (1 ... 10) --
• Finely stranded without end sleeve mm2 2 x (0.5 ... 2.5) 2 x (1 ... 6) --
• Finely stranded with end sleeve (DIN 46228-11) mm2 2 x (0.5 ... 2.5) 2 x (1 ... 6) --
• AWG cables, solid or stranded AWG 2 x (20 ... 12) 2 x (18 ... 8) --
Max. external diameter of the conductor insulation mm 3.6 3.6 --
Connection type Ring terminal lug connections
1/30 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
Siemens IC 10 · 2015 7/19
© Siemens AG 2015
3RV Motor Starter Protectors SIRIUS
General Data Motor Starter Protectors/Circuit Breakers
SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80 A
3RV — up to 80 A
General data
1
3RV2.1. 3RV2.2. 3RV2.3. 3RV27, 3RV28
S00 S0 S2 S00, S0
Front transverse auxiliary switches
PROTECTORS
MOTOR STARTER
Switching capacity for different voltages
1 CO 1 NO + 1 NC, 2 NO
Rated operational current Ie
• At AC-15, alternating voltage
- 24 V A 4 2
- 230 V A 3 0.5
• At AC-12 = Ith, alternating voltage
- 24 V A 10 2.5
- 230 V A 10 2.5
• At DC-13, direct voltage L/R 200 ms
- 24 V A 1 1
- 48 V A -- 0.3
- 60 V A -- 0.15
- 110 V A 0.22 --
- 220 V A 0.1 --
Minimum load capacity V 17
mA 1
Front transverse solid-state compatible auxiliary switches
Switching capacity for different voltages
1 CO
Rated operational voltage Ue Alternating voltage V 125
Rated operational current Ie/AC-14 at Ue = 125 V A 0.1
Rated operational voltage Ue Direct voltage L/R 200 ms V 60
7
Rated operational current Ie/DC-13 at Ue = 60 V A 0.3
Minimum load capacity V 5
mA 1
Lateral auxiliary switches with signaling switch
Switching capacity for different voltages:
Lateral auxiliary switch with 1 NO + 1 NC, 2 NO, 2 NC, 2 NO + 2 NC
Signaling switch
Rated operational current Ie
• At AC-15, alternating voltage
- 24 V A 6
- 230 V A 4
- 400 V A 3
- 690 V A 1
• At AC-12 = Ith, alternating voltage
- 24 V A 10
- 230 V A 10
- 400 V A 10
- 690 V A 10
• At DC-13, direct voltage L/R 200 ms
- 24 V A 2
- 110 V A 0.5
- 220 V A 0.25
- 440 V A 0.1
Minimum load capacity V 17
mA 1
Auxiliary releases
Undervoltage releases Shunt releases
Power consumption
• During pick-up
- A C vo lt a g es VA/W 20.2/13 20.2/13
- DC voltages W 20 13 ... 80
• During uninterrupted duty
- A C vo lt a g es VA/W 7.2/2.4 --
- DC voltages W 2.1 --
Response voltage
• T ripping V 0.35 ... 0.7 x Us 0.7 ... 1.1 x Us
• Pick-up V 0.85 ... 1.1 x Us --
Opening time maximum ms 20
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/31
Siemens IC 10 · 2015 7/17
© Siemens AG 2015
3RV Motor Starter Protectors SIRIUS
Motor Starter
General Data Protectors/Circuit Breakers
SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80 A
3RV — up to 80 A
General data
1/32 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
7/20 Siemens IC 10 · 2015
3RV Motor Starter Protectors SIRIUS
General Data
3RV — up to 100 A
Overview
1
S00 MSP with laterally mounted Construction
undervoltage release with leading 3RV Motor Starter Protectors The motor starter protectors are • Size S2 - 3RV203
PROTECTORS
MOTOR STARTER
auxiliary switch
(MSPs) are built for a world of available in four sizes: Maximum rated current is 50
applications while meeting the Amps. Suitable for motors up
requirements of control users to 50 HP at 600V.
worldwide. Each MSP features • Size S00 - 3RV201
a manual ON/OFF switch, a Maximum rated current is 16 • Size S3 - 3RV204
Class 10 adjustable bimetallic Amps. Suitable for motors up Maximum rated current is
overload relay (Class 20 avail- to 10 HP at 600V. Available in 100 Amps. Suitable for
able in the two largest frame both screw terminal and spring- motors up to 100 HP at 600V.
sizes), and magnetic trip ele- type terminal versions.
ments for short circuit protec- • Size S0 - 3RV202
tion. Maximum rated current is 40
Amps. Suitable for motors up
to 20 HP at 600V. Available in
both screw terminal and spring-
type terminal verisons.
Functions
Releases Release classes Operating mechanisms
3RV motor starter protectors The release classes of thermally S00, S0, S2 and S3 MSPs are In the case of MSPs with
are equipped with bimetallic- delayed releases are based on actuated via a rotary operating rotary operating mechanisms,
based, inverse-time delayed the tripping time (tA) at 7.2 times mechanism. If the MSP trips, an electrical signal can be out-
overload releases - electromag- the operational current in cold the rotary operating mechanism put via a signalling switch to
netic short-circuit releases. state (excerpt from IEC 60 947- switches to the tripped position indicate that the MSP has
4): to indicate this. Before the MSP tripped.
The overload releases can be
set in accordance with the load • CLASS 10 A 2 s < tA < 10 s is reclosed, the rotary operating All operating mechanisms can
current. The overcurrent re- • CLASS 10 4 s < tA < 10 s mechanism must be reset man- be locked in 0 position with a
leases are permanently set to a • CLASS 20 6 s < tA < 20 s ually to 0 position, in order to padlock (shackle diameter
value 13 times the rated current • CLASS 30 9 s < tA < 30 s prevent the former from closing 3.5 to 4.5 mm).
and thus enable trouble-free by mistake before the fault has
start-up of motors. The release must trip within this
been cleared.
time!
The scale cover can be sealed
to prevent unauthorized adjust-
ments to the set current.
Application
Operating conditions Motor Protection
3RV MSPs are suitable for use 3RV MSPs use bimetallic Each MSP has a fourth bimetal- A built-in differential trip bar
in any climate. They are heater elements to provide lic strip that reacts only to the causes the MSP to trip faster
designed for operation in class 10 or 20 overcurrent pro- ambient temperature inside the on a phase loss condition, to
closed rooms under normal tection for both AC and DC control panel. This ambient help reduce motor damage
conditions (e.g. no dust, corro- motors. The bimetallic heaters compensation prevents the from phase loss.
sive vapours or harmful gases). sense the motor current MSP from nuisance tripping
Suitable enclosures must be directly, so the overloads are when the panel temperature is Magnetic trip elements in each
higher than the ambient tem- MSP take the device off line
provided for installation in dusty insensitive to high frequencies,
or damp rooms. harmonic waves and sinusoi- perature of the motor. when it senses currents of 13
dal currents and voltages. times the maximum FLA dial
setting.
3RT2 0 1 1 - 0 A A 1 0
SIRIUS MSP or Application Frame Size Standard Amperage Range Class Terminal Type Auxiliary
Circuit Breaker 0 = Motor Protection 3 = S2 Possible choices listed below see A = 10 1 = Screw Switch
7 = UL 489 4 = S3 page 1/4-1/7 for an entire listing 2 = Spring Loaded
0, 1, 4 B through K 4 = Ring Lug
3RV2 0 1 1 - 0 A A 1 0
SIRIUS Application Frame Size Standard Amperage Range Class Terminal Type Auxiliary
Innovations 0 = Motor Protection 1 = S00 Possible choices listed below see A = 10 1 = Screw Switch
MSP or 7 = UL 489 2 = S0 page 1/4-1/7 for an entire listing B = 20 2 = Spring Loaded
Circuit Breaker
3 = S2 0, 1, 4 B through K 4 = Ring Lug
4 = S3
Note: MPSs and Contactors of the same frame size are made to easily fit together with the use of a link module.
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/33
3RV Motor Starter Protectors SIRIUS
General Data
Mounting accessories
Applications:
1
As a manual starter As a Self-protected manual As part of a Combination As a circuit breaker for export
combination starter, Type E. Motor Contoller, Type F When exporting to many coun-
All 3RV MSPs are UL listed as
Manual Motor Controllers per Most 3RV MSPs have also been When a 3RT contactor is con- tries outside of the U.S. and
UL508. This makes them ideal UL listed as UL508 Type E, Self- nected to the load side of a 3RV North America, the 3RV can be
for applications requiring sim- protected Manual Combination device that is rated as a "Man- applied as a thermal magnetic
ple manual starting and stop- Starters. This UL listing allows ual Self-protected Combination circuit breaker for use in motor
ping of motors. A separate the MSP to be mounted in a Motor Controller, Type E", the branch circuits.
short circuit protective device, manually operated machine assembly can be applied as a 3RV29 28-1K 3RV29 38-1K
such as a circuit breaker or without having to add separate "Combination Motor Controller,
fuses, is still required ahead of short circuit protection Type F". This versions allows
the MSP. This up-stream pro- upstream. for remote starting and stopping
tective device should be sized of the motor load.
per NEC code, not to exceed These devices have a short cir-
400% of the maximum FLA cuit current rating of 65 kA @ These assemblies have a short
adjustment dial setting. 240V, 480Y/277V and up to circuit current rating of 65 kA @
30kA @ 600Y/347V. 240V, 480Y/277V and up to 30
As a component in a group kA @ 600Y/347V.
installation Terminals for "Combination Motor Controller Type E" to UL 508
A group motor installation indi- The 3RV MSP for motor protec- The terminal block 3RT29 46- 3RV29 28-1H
cates multiple motor controllers tion is approved according to 4GA07 must be used for size
under one short circuit protec- UL 508 as "Combination Motor S3. The standard box terminal is
tive device, such as a circuit Controller Type E". to be replaced by this terminal
breaker. 3RV MSPs have a block.
group installation short-circuit As of July, 2001, UL 508
current rating of 65 kA at 480V demands at line-side of the According to CSA, these termi-
and up to 30kA at 600V. By device used for this purpose an nal blocks can be omitted when
using a link module, a 3RT con- increased clearance and creep- the device is used as "Combina-
tactor can be directly mounted age distance (1" or 2"). tion Motor Controller Type E".
to the load side of the MSP. 3RT29 46-4GA07
Here, the terminal block 3RV29 By using a link module, a 3RT
3RV MSPs have been UL 28-1H must be used for size S0. contactor can be directly mount-
tested with and without 3RT The block is simply screwed to ed to the load side of a 3RV MSP.
contactors for group installa- the basic unit. This assembly of a 3RV and a
tion. 3RT provides a complete, re-
Basic units of size S2 are motely operated, combination
already compliant with new starter, Type F.
clearance and creepage dis-
tance requirements.
1/34 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
3RV Motor Starter Protectors SIRIUS
General Data
3RV — up to 100 A
1
3RV motor starter protectors fo r alternating currents are also The response values of the overload release remain unchanged;
suitable for DC switching. the response values of a short-circuit release increase by ap-
PROTECTORS
MOTOR STARTER
proximately 30 % for DC. The example circuits for DC switching
The maximum permissible DC voltage per conducting path can be seen in the table below.
must, however, be adhered to. Higher voltages require a series
connection with 2 or 3 conducting paths.
Example circuit for size S00 to S3 3RV motor starter protectors
Example circuit for size S00 Maximum permitted Notes
to S3 3RV motor starter protectors DC voltage Ue
1)
It is assumed that this circuit always provides safe disconnection even in
the event of a double ground fault that bridges two contacts.
Design
Mounting Screw connection The box terminals of the S3 MSP with Spring-type terminal
MSPs can be removed in order connection
The motor starter protectors are 3RV MSPs of sizes S00 and
to connect conductors with
secured in position by snap- S0 are fitted with terminals with
cable lugs or connecting bars.
ping them onto 35 mm standard captive screws and clamping
A terminal cover is available to
mounting rails according to DIN pieces, allowing the connection
help prevent contact with shock
EN 50 022. A mounting rail with of 2 conductors with different
protection and to ensure that
a height of 15 mm is required cross-sections.
the required clearances and
for S3 MSPs. A 75-mm mount- creepage distances are main-
The box terminals of the S2 and
ing rail can be used as an alter- tained if the box terminals are
native here. S3 MSPs also enable 2 con-
ductors with different cross- removed.
S2 and S3 MSPs can also be sections to be connected. With
screwed directly onto a base- the exception of S3 MSPs Spring-type connection 2)
plate. which are equipped with 4 mm
hexagon socket terminal As an alternative to screw ter-
The push-in lugs 3RV29 28-0B screws, all terminal screws are minals, S00 and S0 devices are
are available for screw mount- tightened with a Pozidriv screw- also available with Spring-type
ing of S00 and S0 MSPs. driver size 2. terminal connection.
This screwless Spring-type
3RV2928-0B terminal technique, as known
for modular terminal blocks,
offers shock-proof and vibration
proof connection of conductors.
Devices with Spring-type con-
nection allow independent con-
nection of two conductors per
terminal.
1) It is assumed that this circuit always provides safe cut-out, even in the event of a
double earth fault that bridges two contacts.
2) For notes on Spring-type terminal connection, see section 19.
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/35
3RV Motor Starter Protectors SIRIUS
General Data
3RV — up to 100 A
Characteristics
1
The time/current characteristic, (short-circuit releases, ’N’ re- Typical time/current characteristic of 3RV
the current limiting characteris- leases) are based on the rated
MOTOR STARTER
PROTECTORS
Circuit diagrams
Internal connections
Motor starter protectors
3RV.
1/36 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
3RV Motor Starter Protectors SIRIUS
General Data
3RV — up to 100 A
Dimension drawings
1
3RV2 MSP, size S00 3RV2 MSP, size S0
PROTECTORS
MOTOR STARTER
3RV20 11 3RV20 21
45 49 96.9 45 96.9
49
97
97
5 5
1/ L1 3/ L2 5/ L3
70
140
130
2/ T1 4/ T2 6/ T3
5
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/37
3RV Motor Starter Protectors SIRIUS
General Data
3RV — up to 100 A
149.3
55 144.3 12.4 30
MOTOR STARTER
PROTECTORS
4.8
1/ L1 3/ L2 5/ L3 70
140
130
2/ T1 4/ T2 6/ T3
5
3RV2.4 size S3
176
70 171 30
1 / L1 3 / L2 5 / L3
83
165
155
2 / T1 4 / T2 6 / T3
5
20
45 96.9
49
97
1
65
45 96.9
PROTECTORS
MOTOR STARTER
49
97
149.4
4.8
1 / L1 3 / L2 5 / L3
95
96
70
NC
140
130
NO
98
97
2 / T1 4 / T2 6 / T3
5
1 / L1 3 / L2 5 / L3
83
95
96
NC
165
155
NO
98
97
2 / T1 4 / T2 6 / T3
5
20
75
45 70
MOTOR STARTER
PROTECTORS
1 / L1 3 / L2 5 / L3
45
90
2 / T1 4 / T2 6 / T3
2) Drilling pattern.
Ø5
126
112
45
144
106
2)
3RV1011-1AA10 1) 11/22/2019
Subject to change without notice
© Copyright Siemens
Page 6/7
17
NSB0_01726b
14 14 55
45 79
92
155
45
2)
1)
NSB0_01531c
5
70 132
7 153
157
169
Overview
1
Mounting location and function
PROTECTORS
MOTOR STARTER
The 3RV2 motor starter protectors/circuit breakers have three These components are easily fitted to the switches without the
main contact elements. In order to achieve maximum flexibility, use of any tools according to requirements.
auxiliary switches, signaling switches, auxiliary releases and
isolator modules can be supplied separately. Overview graphic, see page 7/7.
Front side Transverse auxiliary An auxiliary switch block can be inserted transversely on the front.
Note: switches, solid-state The overall width of the motor starter protectors/circuit breakers remains
compatible transverse unchanged.
• A maximum of four auxiliary contacts with auxiliary switches
auxiliary switches can be mounted on each
motor starter protector/circuit breaker. 1 NO + 1 NC
or
2 NO
or
1 CO
Left-hand side Lateral auxiliary switches One of the three lateral auxiliary switches can be mounted on the left side
Notes: (2 contacts) per motor starter protector/circuit breaker. The contacts of the auxiliary
1 NO + 1 NC switch close and open together with the main contacts of the motor starter
• A maximum of four auxiliary contacts with protector/circuit breaker.
auxiliary switches can be mounted on each or
motor starter protector/circuit breaker. 2 NO The width of the lateral auxiliary switch with two contacts is 9 mm.
• Lateral auxiliary switches (two contacts) or
and signaling switches can be mounted 2 NC
separately or together. Lateral auxiliary switches One lateral auxiliary switch with four contacts can be mounted on the left
• The signaling switch cannot be used for the (4 contacts) side per motor starter protector/circuit breaker. The contacts of the auxiliary
3RV27 and 3RV28 circuit breakers. switch close and open together with the main contacts of the motor starter
2 NO + 2 NC
protector/circuit breaker.
The width of the lateral auxiliary switch with four contacts is 18 mm.
Signaling switches One signaling switch can be mounted on the left side of each motor starter
7
Tripping 1 NO + 1 NC protector.
Short circuit 1 NO + 1 NC The signaling switch has two contact systems.
One contact system always signals tripping irrespective of whether this was
caused by a short circuit, an overload or an auxiliary release. The other
contact system only switches in the event of a short circuit. There is no
signaling as a result of switching off with the actuator.
In order to be able to switch on the motor starter protector again after a short
circuit, the signaling switch must be reset manually after the error cause has
been eliminated.
The overall width of the signaling switch is 18 mm.
Right-hand side Auxiliary releases
Notes: Shunt releases For remote-controlled tripping of the motor starter protector/circuit breaker.
• One auxiliary release can be mounted per The release coil should only be energized for short periods (see circuit
motor starter protector/circuit breaker. diagrams).
• Accessories cannot be mounted at the or
right-hand side of the 3RV21 motor starter
protectors for motor protection with overload Undervoltage releases Trips the motor starter protector/circuit breaker when the voltage is inter-
relay function. rupted and prevents the motor from being restarted accidentally when the
voltage is restored. Used for remote-controlled tripping of the motor starter
protector/circuit breaker.
Particularly suitable for EMERGENCY-STOP disconnection by way of corre-
sponding EMERGENCY-STOP pushbuttons according to DIN EN 60204-1.
or
Undervoltage releases with Function and use as for the undervoltage release without leading auxiliary
leading auxiliary contacts contacts, but with the following additional function: the auxiliary contacts will
2 NO open in switch position OFF to deenergize the coil of the undervoltage
release, thus interrupting energy consumption. In the "tripped" position,
these auxiliary contacts are not guaranteed to open. The leading contacts
permit the motor starter protector/circuit breaker to reclose.
The overall width of the auxiliary release is 18 mm.
Top Isolator modules Isolator modules can be mounted to the upper connection side of the motor
Notes: starter protectors.
• The isolator module cannot be used for the The supply cable is connected to the motor starter protector through the
3RV27 and 3RV28 circuit breakers. isolator module.
• The isolator module for size S2 The plug can only be unplugged when the motor starter protector is open
- can only be used with 3RV2 motor starter and isolates all 3 poles of the motor starter protector from the network.
protectors/circuit breakers up to max. 65 A The shock-protected isolation point is clearly visible and secured with a
- cannot be used with the transverse auxiliary padlock to prevent reinsertion of the plug.
switch
• The isolator module covers the terminal screws
of the transverse auxiliary switch. If the isolator
module is used, we therefore recommend that
either the lateral auxiliary switches be fitted or
that the isolator module not be mounted until For a complete overview of which accessories can be used for. the
the auxiliary switch has been wired. various motor starter protectors/circuit breakers, see page 7/2
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/41
Siemens IC 10 · 2015 7/31
3RV Motor Starter Protectors SIRIUS
General Data
Mountable accessories
Overview
1
8
S00 and S0 motor starter protectors with mountable accessories
MOTOR STARTER
PROTECTORS
NSB0_02076
4
6.1
Mountable accessories for all sizes S00 ... S3 Mountable accessories for sizes Mountable accessories for sizes
1 Transverse auxiliary switch 6.1 Undervoltage release with S00, S0 7 Signaling switch (can not be S00 ... S3
leading auxiliary contacts used with 3RV27 and 3RV28
2 Lateral auxiliary switch with 2 contacts
(can not be used with 3RV21 S2, S3 circuit breakers)
3 Lateral auxiliary switch with 4 contacts circuit breakers) 8 Isolator module (can not be S0 and S2
4 Shunt release 6.2 Undervoltage release with used with 3RV27 and 3RV28
leading auxiliary contacts circuit breakers)
5 Undervoltage release
9 Terminal block E
1/42 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
3RV Motor Starter Protectors SIRIUS
General Data
Mountable accessories
Circuit diagrams
1
Internal connections
PROTECTORS
MOTOR STARTER
Shunt release Undervoltage Undervoltage release Lateral auxiliary switch
release with leading auxiliary contacts with 4 contacts
3RV19 02-1D / 3RV29 02-1D 3RV19 02-1A / 3RV29 02-1A 3RV19 01-1J / 3RV29 01-1J
3RV19 22-1C / 3RV29 22-1C
External connections
Shunt release Undervoltage release
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/43
3RV Motor Starter Protectors SIRIUS
General Data
Mountable accessories
Circuit diagrams
1
Typical circuits
MOTOR STARTER
PROTECTORS
F1 Fuses (gL/gG)
H2: "Overload" or "Tripped by max. 10 A
auxiliary release" signal
Q1 MSP
S1 Signalling switch
Dimension drawings
Isolator modules
3RV29 28-1A 3RV29 38-1A
for MSPs size S00, S0 for MSPs size S2
54.8 144.7
56.9
107.9
1/44 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
3RV Motor Starter Protectors SIRIUS
3RV Motor Starter Protectors up to 100 A
Accessories – Busbar accessories
Overview
1
Busbar adapters
PROTECTORS
MOTOR STARTER
The MSPs are mounted directly The MSPs are snapped onto SIRIUS MSPs and combination starters with FastBus-busbar adapters
with the aid of busbar adapters the adapter and connected on snapped onto busbars
on FastBus-busbar systems with the line side. This prepared unit
40 mm and 60 mm centerline is then plugged directly onto the
spacing, in order to save space busbar system, and is thus con-
and to reduce wiring times and nected both mechanically and
costs. electrically at the same time.
FastBus-busbar adapters for Refer to page 1/10 for busbar
busbar systems with 40 mm adapters for specific MSPs and
centerline spacing are suitable accessories.
for copper busbars with a width
of 12 mm to 15 mm, while those Further busbar adapters for
with 60 mm centerline spacing snap-mounting direct-on-line
are suitable for widths of 12 mm starters and reversing starters,
to 30 mm. The busbars can be as well as additional accesso-
4 to 5 mm or 10 mm thick. ries such as line terminals and
outgoing terminals, busbar
copper, etc., can be found in
Section 5.
The busbars are suitable for between 2 and 5 circuit break- The motor starter protectors are snapped onto the adapter and
ers/motor starter protectors. However, any kind of extension is connected on the line side. This prepared unit is then plugged
possible by clamping the tags of an additional busbar (rotated directly onto the busbar system, and is thus connected both me-
by 180°) underneath the terminals of the respective last motor chanically and electrically at the same time.
starter protector. For further busbar adapters for snap-mounting direct-on-line
A combination of motor starter protectors of different sizes is starters and reversing starters as well as additional accessories
possible. The motor starter protectors are supplied by appropri- such as line terminals and outgoing terminals, flat copper profile,
ate feeder terminals. etc., can be found in Section 5.
3RV29 25-5AB
3RV19 15-1CB
3RV29 15-5B
NSB0_02079
NSB0_02080
3RV19 15-6AB
SIRIUS three-phase busbar system size S00/S0 SIRIUS load feeders with busbar adapters snapped onto busbars
The three-phase busbar systems are finger-safe. They are de- The three-phase busbar systems can also be used to construct
signed for any short-circuit stress which can occur at the output “Type E Starters” according to UL/CSA. Special feeder terminals
side of connected motor starter protectors. must be used for this purpose however (see “Selection and
Ordering Data” on page 1/11).
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/45
3RV Motor Starter Protectors SIRIUS
General Data
Busbar accessories
Dimension drawings
1
55
110
168
1/46 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
3RV Motor Starter Protectors SIRIUS
General Data
Busbar accessories
Dimension drawings
1
3RV19 35-3. . 3-phase busbar
for S2 MSP, modular spacing 75 mm
PROTECTORS
MOTOR STARTER
for 2 MSPs with accessories 3RV19 35-3A
for 3 MSPs with accessories 3RV19 35-3B
for 4 MSPs with accessories 3RV19 35-3C
15
33
98
75
130
168
3RV29 25-5AB. 3-phase line-side terminals 3RV29 25-5EB 3-phase line-side terminal
connection from above, 3RV29 35-5B a) 3RV1. 1 19 mm connection from above,
size S00 and S0 connection from above, 3RV1. 2 23 mm size S0
size S00 and S0
91
161
54.5 76.5
55,3
44 33,8
30,8
78,8
65.8
NSB0_02012
127,8
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/47
© Siemens 2021
Protection
3RV equipment
Motor Starter Protectors SIRIUS
Motor starter protectors/circuit breakers
General Data
SIRIUS 3RV2 motor starter protectors/circuit breakers
Busbar accessories
Accessories > Rotary operating mechanisms
Overview
1
Door-coupling rotary operating mechanisms Door-coupling rotary operating mechanism for mounting one
main switch in size S3 according to UL 508A and NFPA 79
MOTOR STARTER
PROTECTORS
1 Actuator
3 Coupling driver
7
2 Plastic cover
4 Extension shaft (6 mm x 6 mm),
130 mm long 3 Coupling driver
5 Coupling enclosure 5 4 Extension shaft (8 mm x 8 mm), 300 mm long
5 Spacer
6 Control cabinet door
IC01_00713
4
6 Metal brackets for inserting
3 motor starter protector/circuit breaker
4
Comprising:
1 Actuator
3
2 Plastic cover
3 Coupling driver 6
2
4 Extension shaft (8 mm x 8 mm),
300 mm long 7
5 Spacer 5
1
6 Metal brackets for inserting
motor starter protector/circuit
breaker 4 SIRIUS 3RV2946-3C EMERGENCY OFF door-coupling rotary operating
mechanism for harsh operating conditions according to UL 508A and
7 Control cabinet door NFPA 79 with optional shaft support and supplementary handle
3 (EMERGENCY OFF version)
7
1
1/48 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
Siemens IC 10 · 2021
3RV Motor Starter Protectors SIRIUS
General Data
Rotary operating mechanisms
Circuit diagrams
1
Typical circuits
3RV MSP with 3RV19 36/3RV19 46 remote-controlled motorized
PROTECTORS
MOTOR STARTER
operating mechanism
US
~ ~
- +
1
O 2
M
3
4
5
L I T
v
NSB00024a
Dimensional drawings
Door coupling rotary mechanism
3RV29 26-0B/3RV29 26-0C short shaft 4), for MSP sizes S00, S0, S2 and S3
66
45 19 25
15
1...4 1) Lockable in 0 position, with
shackle diameter max. 8 mm
2) Mounting with screw cap
1) 3) Supplied with a shaft length of
330 mm; adaptable by shortening
of the shaft.
4) Supplied with a shaft length of
5 2) 130 mm; adaptable by shortening
of the shaft.
max 127 33 17 5) Grounding terminal 35 mm2 and
min 55 bracket for 330 mm shaft.
3
4)
24.3
Ø2
2.5
NSB01108
max 130
min 56
3RV29 26-0K/3RV29 26-0L long shaft (with bracket) 3), for MSP sizes S00, S0, S2 and S3
66
16 45 19 25
15
1...4
I ON
1)
0 OFF
NSB01090a
5 2)
5) max 327 33 17
min 55
3
3)
24.3
Ø2
2.5
NSB01108
max 330
min 56
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/49
3RV Motor Starter Protectors SIRIUS
General Data
Rotary operating mechanisms
Dimension drawings
1
65
75
B
A
40
6
max. 341
D E F 62 14 H C
min. 42
1/50 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
3RV Motor Starter Protectors
Motor Starter ProtectorsSIRIUS
General Data SIRIUS 3RV1 Motor Starter Protectors up to 100 A
Accessories — Enclosures and front plates
Accessories
Enclosures and front plates
Overview
1
Enclosure Front plates
PROTECTORS
MOTOR STARTER
For stand-alone installation of motor starter protector size S2 Motor starter protectors are frequently required to be actuated in
( In max = 65 A), molded-plastic enclosures for surface mounting any enclosure. Front plates equipped with a rotary operating
are available. mechanism for motor starter protector sizes S2 and S3 are avail-
able for this purpose.
When installed in a molded-plastic enclosures the motor starter
protectors have a rated operational voltage Ue of 500 V.
The molded-plastic enclosures are designed to degree of pro-
tection IP55.
NSB0_02194
NSB0_02193
7
Enclosures for surface mounting
All enclosures are equipped with N and PE terminals. There are
two knock-out cable entries for cable glands at the top and two
at the bottom; also on the rear corresponding cable entries are
scored. There is a knockout on the top of the enclosure for indi-
cator lights that are available as accessories.
In the enclosure for motor starter protector size S2 there is also
room for the laterally mounted auxiliary release. There is no pro-
vision for installing a motor starter protector with a signaling
switch.
The molded-plastic enclosures of the size S2 motor starter pro-
tectors are fitted with a rotary operating mechanism.
The enclosures can be supplied with either a black rotary oper-
ating mechanism or with an EMERGENCY-STOP rotary operat-
ing mechanism with a red/yellow knob.
The rotary operating mechanisms can be locked in the Open po-
sition with up to 3 padlocks.
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/51
Siemens IC 10 · 2012 7/61
3RV Motor Starter Protectors SIRIUS
General Data
Mounting accessories
Dimension drawings
1
1/52 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC
3RV Motor Starter Protectors SIRIUS
General Data
3RV Spring-type terminal infeed system
Design
1
Installation guidelines
PROTECTORS
MOTOR STARTER
Distance in Y direction from live, earthed or insulated parts ac-
cording to IEC 60947-4: 10 mm.
In addition, the installation guidelines for motor starter protectors
or fuseless load feeders including the clearances must be com-
plied with.
Technical specifications
Type 3RV29 .7
Rated operational voltage Ue
• IEC
- 10 % overvoltage V 500
- 5 % overvoltage V 525
• UL/CSA V 600
Rated frequency Hz 50/60
Rated current In A 63
Permissible ambient temperature
• During storage/transport °C -50 ... +80
• During operation °C -20 ... +60
Permissible rated current of the 3RV10 11 motor starter protectors
(size S00) at control cabinet internal temperature
• +60 °C % 100
Permissible rated current of the 3RV10 21 motor starter protectors
(size S0) up to 16 A at control cabinet internal temperature
• +60 °C % 100
Permissible rated current for 3RV1. 21 motor starter protectors (size S0)
from 16 A at control cabinet internal temperature
• +40 °C % 100
• +60 °C % 87
Degree of protection acc. to IEC 60529 IP201)
Touch protection acc. to IEC 61140 Finger-safe
Conductor cross-sections for main circuit infeed
• Solid, stranded: mm2 4 ... 25
• Finely stranded with end sleeve mm2 4 ... 25
• Finely stranded without end sleeve mm2 6 ... 25
• AWG cables, solid or stranded AWG 10 ... 3
Conductor cross-sections of terminal block
• Solid mm2 1.5 ... 6
• Finely stranded with end sleeve mm2 1.5 ... 4
• Finely stranded without end sleeve mm2 1.5 ... 6
• AWG cables, solid or stranded AWG 15 ... 10
1)
In infeed terminal compartment without a conductor connected: IP00.
Product Category IEC Smart Infrastructure, Industrial Control Catalog 2021 1/53
3RV Motor Starter Protectors SIRIUS
General Data
3RV Cage clamp infeed system
3RV29 17-1.
108
75 108 a
70
80
128
128
45
4,5
NSB0_01248
278
15
7,5
75
S00 S0
a 104 125
128
128
128
45
4,5
278
NSB0_01249
15
7,5
75
S00 S0
a 104 125
1/54 Smart Infrastructure, Industrial Control Catalog 2021 Product Category IEC