Installer's Guide for HVAC Pros
Installer's Guide for HVAC Pros
CONDENSING UNITS
         X DRIVE SERIES
         Split System Air Conditioner 2-5 Tons R410A
         Up to 18 SEER
                                                        NOTE
 The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacturer’s
 split systems are AHRI rated only with TXV indoor systems. And the indoor units must be matched with TXV. Some of
 the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency, optimum
 performance and the best overall system reliability.
                                     CONTENTS
1 SAFETY                                                                                                             01
3 UNIT PREPARATION
      3.1 Prepare the Unit for Installation                                                                          04
9 EVACUATION
   9.1 Evacuate the Refrigerant Lines and Indoor Coil                       08
10 SERVICE VALVES
   10.1 Open the Service Valves                                             09
13 START UP
   13.1 System Start Up                                                     14
                                                              01
2 UNIT LOCATION                                                                  Maximum line equivalent length = 100 feet.
2.1 Unit Dimensions                                                              If the suction linesets are greater than 50 feet, do
                                                                                 not use a larger suction line than recommended.
 Unit Dimensions
 Models                                 H x W x L (Inches)
 24/36                             24-15/16 x 29-1/8 x 29-1/8
 48/60                              33-3/16 x 29-1/8 x 29-1/8
Table 2-1
                                                                                                           50' Max
                                                                                                           Line Lift
Figure 2-1
                                                                                                              50' Max
                                                                                                              Line Lift
2.2 Refrigerant Piping Limits
                      3/4 Std.     25        50        45            40
  2 Ton      3/8 *                                                             Figure 2-2
                     5/8 Opt.      25        50        45            40
                     5/8 Opt.      25        50        50            50
  3 Ton      3/8 *
                      3/4 Std.     25        50        50            50
                      7/8 Std.     25        50        50            40
  4 Ton      3/8 *
                     3/4 Opt.      25        50        50            40
7/8 Std. 25 50 50 40
Table 2-2
* Standard line size is recommended;
N/A: Application not recommended;
Refrigerant charge: refer to Sec. 14
                                                                          02
2.3 Location Restrictions
Ensure the top discharge area is unrestricted for at least
60 inches above the unit.
Do not locate outdoor unit near bedrooms since normal
operational sounds may be objectionable.
Position unit to allow adequate space for unobstructed
airflow, wiring, refrigerant lines, and serviceability.
Position the outdoor unit a minimum of 12" from any wall
or surrounding shrubbery to ensure adequate airflow.
24 inches clearance must be provided in front of the              Min. 12" to
control box (access panels) and any other side requiring          Shrubbery                                      Min. 12" to
service.                                                                                                         wall
                                                                      Snow
Min. 12" to                            Min. 24"                       barrier
Shrubbery                             Unrestricted
                                                                                                           Snow legs
                                     Access Panel
                                                                                                             3-12" Elevation
Pad
                                                                  Figure 2-5
Figure 2-3
                                                             03
3 UNIT PREPARATION
3.1 Prepare the Unit for Installation
  Check for damage and report promptly to the carrier
  any damage found to the unit (Fig. 3-1).
  The charge port can be used to ensure the refrigerant
  charge has been retained during shipment.
Figure 4-1
Figure 3-1
                        NOTE
   These instructions are intended to provide a
   method to tie-down a system to a cement slab as
   a securing procedure for high wind areas. Check
   local codes for tie-down methods and protocols.
                                                                1/4” Χ 1-1/2” Hex washer head concrete screws
                                                               (3/16” pilot hole needed. Pilot hole should be 1/4” deeper
                                                               than the fastener embedment)
Figure 4-2
                                                          04
5 REFRIGERANT LINE                                                    5.4 Reuse Existing Refrigerant
  CONSIDERATIONS                                                          Lines
Figure 5-1
                                                                                                  NOTE
                                                                         Take precautions to prevent noise within the
                                                                         building structure due to vibration transmission
5.3 Refrigerant Line Insulation                                          from the refrigerant lines. For example:
Figure 5-2
                                                                 05
                                                       8 Feet Maximum
Joist/Rafter
Isolator
   Side View
                                                                 8 Feet Maximum
                                                                                                                                        Lineset
                                Secure Suction Line from joists using isolators every 8 ft. Secure Liquid Line
                                directly to Suction Line using tape, wire, or other appropriate method every 8 ft.
Figure 6-1
                                                              8 Feet Maximum
                                                                                                                               Wall
Isolator
                                                                                                                                  Linesets
    Side View                                                         8 Feet Maximum
                               Secure Suction Line using isolators every 8 ft. Secure Liquid Line directly to
                               Suction Line using tape, wire, or other appropriate method every 8 ft.
Isolation On Walls
Figure 6-2
Wall
                                    Sealant
                                                                                                                             Ductwork
Insulation
Suction Line
Isolator
Lineset
Figure 6-3
                                                                       06
7 REFRIGERANT LINE BRAZING                                      4. Wrap a wet rag around the valve body to avoid heat
                                                                   damage and continue the dry nitrogen purge (Fig.
                                                                   7-4).
7.1 Braze The Refrigerant Lines                                    Braze the refrigerant lines to the service valves.
1. Remove caps or plugs. Use a deburring tool to                   Continue the dry nitrogen purge. Do not remove the
   deburr the pipe ends. Clean both internal and                   wet rag until all brazing is completed.
   external surfaces of the tubing using an emery cloth.
                                                                                          NOTE
                                                                   Remove the wet rag before stopping the dry
                                                                   nitrogen purge.
Figure 7-1
Figure 7-2
This pipe
must have
a thimble
Figure 7-3
                                                           07
8 REFRIGERANT LINE LEAK                                        9 EVACUATION
  CHECK
                                                               9.1 Evacuate the Refrigerant Lines
8.1 Check For Leaks                                                and Indoor Coil
1. Pressurize the refrigerant lines and evaporator coil
   to 150 PSIG using dry nitrogen.                                                      NOTE
                                                                   Do not open the service valves until the
                  150 PSIG                                         refrigerant lines and indoor coil leak check and
                                                                   evacuation are complete.
                                                                                   0350
                                                                                    Microns
Figure 9-1
                                                                                  1 MIN.
Figure 8-2
Figure 9-2
                                                          08
10 SERVICE VALVES                                                        Cap
                                                                                        5/16" Hex Wrench
10.1 Open the Service Valves                                                            for Suction Service Valve
                           NOTE
    Leak check and evacuation must be completed                          Service Port
    before opening the service valves. The brazed
    lineset valves should be used for leak checking
    and vacuuming. Using the separate suction port
    for this process will result in loss of charge.             Figure 10-1
                                                           09
11 ELECTRICAL - LOW VOLTAGE
                                                                              NOTES:
                                                                              - Low voltage connection must be made inside the
                                                                                outdoor unit control board access panel.
                                                                              - There is no terminal block for low voltage connections,
                                                                                wires must be spliced using field supplied wire nuts
                                                                              - Field supplied wire nuts should be 22-16 gauge.
                             Control                                          - Refer to unit wiring diagram for more information.
                             Board
                             Access
                             Panel
                                                                10
  Support 3H and 2C thermostat
W/E
Y2
                  O/B
                 H/DH
                                                                                                       WHITE/BLACK
                                                                             YELLOW
                                                                                                                                      YELLOW
                                                                                      PURPLE
                                                       BROWN
                                                                                                                          BROWN
              TH E RM O S TAT
GREEN
WHITE
                                                                                                                                                          WHITE
                                        GRAY
BLUE
                                                                                                                                                   BLUE
                                                                       RED
 Note: Any time the electric heat          Dh      B      C       G      R      Y1         Y2 W1 W2                               C            Y      B       W
 elements are active, the indoor fan
 will run in high stage.
                                                          INDOOR UNIT                                                             OUTDOOR UNIT
Figure 11-2
W2
W/E
Y2
O/B
                 H/DH
                                                                                                       WHITE/BLACK
                                                                             YELLOW
                                                                                                                                      YELLOW
                                                                                      PURPLE
                                                       BROWN
BROWN
              THERMOSTAT
                                                               GREEN
WHITE
                                                                                                                                                          WHITE
                                        GRAY
BLUE
                                                                                                                                                   BLUE
                                                                       RED
Figure 11-3
                                                                       11
  Wiring for 3H and 1C thermostat
W2
W/E
               O/B
               H/DH
                                                                                                                            WHITE/BLACK
                                                                                              YELLOW
                                                                                                                                                       YELLOW
                                                                                                         PURPLE
                                                            BROWN
                                                                                                                                          BROWN
      THERMOSTAT
GREEN
WHITE
                                                                                                                                                                               WHITE
                                       GRAY
BLUE
                                                                                                                                                                    BLUE
                                                                                    RED
Note: Because Y1 and Y2 are
jumped, the indoor fan will only run      Dh        B          C           G          R          Y1          Y2        W1 W2                      C             Y          B       W
in high stage.
                                                               INDOOR UNIT                                                                         OUTDOOR UNIT
Note: Any time the electric heat
elements are active, the indoor fan
will run in high stage.
Figure 11-4
Y2
                 O/B
                 H/DH
                                                                                                YELLOW
                                                                                                                                                        YELLOW
                                                                                                           PURPLE
                                                              BROWN
BROWN
              THERMOSTAT
                                                                          GREEN
                                         GRAY
BLUE
                                                                                                                                                                    BLUE
                                                                                     RED
Figure 11-5
                                                                                    12
              Wiring for 1H and 1C thermostat
                  O/B
                  H/DH
YELLOW
                                                                                                                                                            YELLOW
                                                                                                              PURPLE
                                                                BROWN
                                                                                                                                              BROWN
          THERMOSTAT
                                                                            GREEN
                                         GRAY
BLUE
                                                                                                                                                                        BLUE
                                                                                        RED
 Note: Because Y1 and Y2 are                   Dh          B           C           G         R        Y1             Y2 W1 W2                         C            Y          B           W
 jumped, the indoor fan will only run
 in high stage.
                                                                       INDOOR UNIT                                                                       OUTDOOR UNIT
Figure 11-6
W/E
                 O/B
                 H/DH
                                                                                                                               WHITE/BLACK
                                                                                                 YELLOW
                                                                                                                                                          YELLOW
                                                                                                            PURPLE
                                                               BROWN
BROWN
 THERMOSTAT
                                                                           GREEN
WHITE
                                                                                                                                                                                  WHITE
                                        GRAY
BLUE
                                                                                                                                                                       BLUE
                                                                                       RED
Figure 11-7
                                                                                       13
12 ELECTRICAL - HIGH                                               12.3 High Voltage Ground
   VOLTAGE
                                                                   Ground the outdoor unit per National, State, and Local
                                                                   code requirements.
12.1 High Voltage Power Supply
                        WARNING
    LIVE ELECTRICAL COMPONENTS!
    During installation, testing, servicing, and trouble
    shooting of this product, it may be necessary to
    work with live electrical components. Failure to
    follow all electrical safety precautions when
    exposed to live electrical components could
    result in death or serious injury.
                           NOTE
                                                                   13 START UP
    Power wiring must comply with National, State,
    and Local codes.
                                                                   13.1 System Start Up
                                                                   1. Ensure Sections 7, 8, 9, 10, 11, and 12 have been
Follow instructions on unit wiring diagram located on the
                                                                      completed.
inside of the control box access panel and refer to wiring
diagram in this IOM.
                                                                   2. Set System Thermostat to OFF.
Figure 13-1
ON
                                                                                            OFF
Figure 12-1
Figure 13-2
                                                              14
4. Upon initial unit installation, wait one (1) hour before            New Installations — Calculating additional charge for
   starting the unit if compressor crankcase heater is                 lineset greater than 15 ft.
   used and the outdoor ambient temperature is below
   70 ºF.                                                              1. Total Line Length (ft)                 = _________(a)
                                                                       2. Standard Lineset (ft)                       15
                                                                                                                 = _________(b)
                                                                       3. (a) minus (b)                          = _________(c)
                                                                       4. Refrigerant Multiplier                     0.6 oz/ft
                                                                                                                 = _________(d)
                     60 MIN.                                           5. Refrigerant Adder (c*d)                = _________(e)*
                                                                       *If lineset is less than 15 ft, (e) = 0
   2 Ton           7 lbs 2 oz               0.6 oz/ft                      For outdoor ambient temperatures below 55ºF use
                                                                           weigh-in charge method.
   3 Ton           7 lbs 2 oz               0.6 oz/ft
   4 Ton          10 lbs 3 oz               0.6 oz/ft
   5 Ton          10 lbs 3 oz               0.6 oz/ft                                              NOTE
Table 14-1                                                                 It is important to return in the spring or summer
                                                                           to accurately charge the system in the cooling
                                                                           mode when outdoor ambient temperature is
                          NOTE                                             above 55ºF.
                                                                  15
         Outdoor                       Outdoor                     Compressor Frequency in Force Mode in Cooling
         Temperature                   Temperature           ODU Capacity      2TON       3TON       4TON       5TON
         Above 55ºF                    Below 55ºF
                                                             Frequency (HZ)      56         76         56          66
                                                             Table 14-2
 120ºF
  55ºF                              55ºF
                                                                                 20 MIN.
Figure 14-1
                                                             4. Calculate superheat value (According to Table 14-3)
   For best results, the indoor temperature should be            Measured Suction Line Temp = ________ºF
   kept between 70ºF and 80ºF during the install.                Measured Suction Line Pressure = _______ PSIG
                                                                 Calculate superheat value = ________ºF
                                                                                       NOTE
              80 ºF                                             Check the superheat and select correct
                                                                subcooling according to superheat, refer to
              70ºF                                              Table 14-5. It is recommended to keep the
                                                                superheat at 10-18°F if a third party indoor unit is
                                                                used.
                           NOTE
                                                             Figure 14-4
   After a twenty (20) minute stabilization period
   operating at 100% capacity (i.e. once the
   compressor reaches the frequency shown in                                           NOTE
   Table 14-2), maintain continuous operation while
   adjusting refrigerant charge. After adjusting,                If calculated subcooling value is lower than the
   operate system for a minimum of five (5) minutes              design subcooling value (Table 14-5), please
   for system to stabilize, otherwise repeat step 3.             add refrigerant. Repeat steps 3 through 5.
                                                        16
Suction                        Final Superheat (°F)                               Connect gauges to refrigerant bottle and unit as
 Temp       6         8     10     12   14    16 18     20        22              illustrated (Fig. 14-5).
  (°F)                     Suction Gauge Pressure (PSI)
                                                                                  Purge all hoses.
  40       105       101     97    93     89     86    82    78    75
  42       109       105    101    97     93     89    86    82    78             Open tank.
  44       114       109    105   101     97     93    89    86    82
                                                                                  Stop adding refrigerant when subcooling matches
  46       118       114    109   105    101     97    93    89    86
                                                                                  the design value (Table 14-5).
  48       123       118    114   109    105    101    97    93    89
  50       128       123    118   114    109    105   101    97    93
  52       133       128    123   118    114    109   105   101    97                                       NOTE
  54       138       133    128   123    118    114   109   105   101
  56       143       138    133   128    123    118   114   109   105              Recover refrigerant if the subcooling reading
  58       148       143    138   133    128    123   118   114   109              from Table 14-4 is higher than the design value
  60       153       148    143   138    133    128   123   118   114              (Table 14-5).
  62       159       153    148   143    138    133   128   123   118
  64       164       159    153   148    143    138   133   128   123
  66       170       164    159   153    148    143   138   133   128
  68       176       170    164   159    153    148   143   138   133
  70       182       176    170   164    159    153   148   143   138
  72       188       182    176   170    164    159   153   148   143
Table 14-3 R-410A Refrigerant chart - Final Superheat
                                  NOTE
   Add refrigerant if the subcooling reading from
   Table 14-4 is lower than the designed value
   (Table 14-5).
                                                                          17
15 SYSTEM OPERATION AND                                                15.2 Sensors (Thermistors
   TROUBLESHOOTING                                                          /Pressure Transducer)
                                                                  18
   2. After “Minimum Run Time” (MRT) is achieved.                           CCH operation energizes:
      MRT is based on outdoor ambient temperature
                                                                            1. First time line voltage is applied and compressor
      (T4), for example:
                                                                               discharge temperature T5 < 53.6°F.
       — MRT is 4 hours when: T4 < 23°F
                                                                            2. Compressor stops running for 3 hours (outdoor
       — MRT is 2 hours when: 23°F ≤ T4 < 40°F                                 ambient temperature T4 < 41°F OR compressor
                                                                               discharge temperature T5 < 53.6°F).
   3. After the high pressure saturation temperature
      drops below 82°F for 20 minutes.                                      CCH operation de-energizes:
   Defrost will terminate once outdoor coil temperature                     1. Compressor discharge temperature T5 ≥ 60.8°F.
   (T3) reaches 64°F for a period of 1 minute or defrost                    2. Compressor starts running.
   time has exceeded 8 minutes.
                                                                                                   NOTE
                                                                             During a heat call on first time operation the unit
          SW5                                                                will run about 1 minute in cooling to build up
 ON                                                                          pressure for reversing valve to change.
 OFF   1     2
                                                                      19
15.8 Fault Code Table
Table 15-3
                                                               20
15.9 Parameter Point Check Table
  To display system parameters, press the “Check” button to index through the series of parameters available. The first time
  you press the “Check” button, it will display the sequence, and after 1 second it will display the value of the parameter. If
  you press the “Check” button again, it will display the next sequence. Refer to Figure 15-3 and 15-4 for check button
  location on the control board.
  Normal Status, last two digits will display under the following conditions
  i. Unit not operating (Standby Mode); “outdoor ambient temperature”.
  ii. Unit operating; displays “compressor operating frequency”.
After 20 seconds on same parameter, the display will revert back to normal status.
Table 15-4
                                                                  21
        (Heat Pump Only)
19
                                                           18
                                                           17
                                              21           16
                        24     23     22      20           15                     No.      Function description
                                                                                  1        Pressure equalizer valve port
                                                                                  2        Compressor crankcase heater port
                                                                                  3        Reversing valve port(Heat Pump Only)
                                                                            14    4        Thermostat wire connections
*The photo is provided for reference purposes only, Layout and components will vary according to the unit specification.
Figure 15-4
                                                             23
15.11 Error Code Troubleshooting
                                                                    P5 (Condenser coil temperature (T3) protection in cooling)
                                                                           Diagnosis                       Handling
Error Code Description (Sensor)
    P1        High pressure switch (HPS) protection
                                                                                                  NO
                                                                     Check whether the service
              Condenser coil temperature (T3)                                                           Open the service valves
    P5                                                               valves are open
              protection in cooling
    P3        Compressor over current protection                                   YES
YES NO
YES YES
YES YES
Figure 15-5
                                                             24
          P3 (Compressor over current protection)                                P0 (Control board temperature (TF) protection)
                                  NO                                                                         YES
    Check whether the service                                                   Check for dust or debris
                                       Open the service valve                                                       Clean all the dust and debris
    valves are open                                                             blocking radiator
YES NO
YES YES
No YES
YES
Figure 15-9
                                                                     25
  P4 (High compressor discharge temperature (T5) protection)                 Error Code Description
          Diagnosis                            Handling                                    Temperature sensor fault
                                                                                 E4
                                                                                           (T3, T4, T5, TF)
                                      NO                                         H8        Pressure transducer (PT) fault
    Check whether the service
                                           Open the service valve
    valves are open
                                                                                 F1        High pressure switch (HPS) fault
                   YES
    Check whether the EEV/TXV is NO   Re-power and check                          Unplug the sensor, Check
                                                                                                               NO
    normal for throttle             again,if the same, replace                    whether the resistance of
                                                                                                                      Replace the fault T5
    (wire seated .coil)                   the EEV/TXV.                            T5/Tf is in the range of
                                                                                                                             sensor
                                                                                  Table 15-15
                   YES                                                                         YES
YES
                                                                                                               NO
                                                                                  Check whether there is the
                                                                                                                          Keep running
                                                                                  same fault
YES
Figure 15-12
                                                                       26
               F1 (High pressure switch (HPS) fault                       E7 (Compressor discharge sensor (T5) is seated fault)
           Diagnosis                        Handling                             Diagnosis                         Handling
     Check whether high pressure NO                                       Check whether the sensor of NO  Wire according to the
                                    Wiring according to the               T3/T5 are connected
     switch (HPS)wiring is seated                                                                        wiring diagram correctly
                                      diagram correctly                   according to wiring diagram
     and normal
YES YES
YES YES
YES YES
Figure 15-13                                                                                            NO
                                                                          Check whether there is the             Keep running
                                                                          same fault
     Check whether the T3/T4     NO  Wire according to the                 Check whether DC motor
     sensors are connected          wiring diagram correctly                                            NO       Reseat the wiring
                                                                           wiring is reliably connected
     according to wiring diagram                                                                                   according to
                                                                           according to the wiring
                                                                                                                  wiring diagram
                   YES                                                     diagram
                                                                                        YES
     Check whether the             NO
                                           Replace the fault
     resistance of T3/T4 is in                                                                          NO
                                            T3/T4 sensor                   Check whether outdoor coil
     the range of Table 15-14                                                                                Remove all the barriers
                                                                           air return is blocked
                   YES
                                                                                        YES
     Check whether there are       NO
     other heat sources around           Remove all the other              Check whether the voltage    NO
     T3/T4                                  heat sources                   between +15V&N is in the          Replace the control board
                                                                           range 14-18Vdc
                   YES
                                                                                        YES
                                                                 27
Error Code Description                                                                       E5 (High/low voltage protection)
                                                                                        Diagnosis                         Handling
     E9        EEPROM fault
Figure 15-17
YES
YES
Figure 15-18
                                                                         28
 Error Code Description                                                   Error Code Description
                    YES
                                                                             No action is necessary.
                                                                             Try to restart the system.
        Check whether there is the NO
                                               Keep running
        same fault
                                                                         Figure 15-21
                    YES
YES
Figure 15-20
                                                                    29
15.12 Temperature and Resistance Relationship Tables (for Sensors)
                                                 30
15.13 Temperature and Resistance Relationship Tables (for T5 Sensor )
                                                      31
                                            PO W
                                             LOW
                                              RE S
                                               TXV
                                                  VO L
                                                   UPP
                                                    STU
                                                      TAG
                                                       LY O
                                                        CK O
                                                          CON
                                                           E WIR
                                                            R HIG
PEN
                                                             SER
           SYSTEM FAULTS
                                                              REF
                                                               TRO
                                                               WHA
ING
INEF
                                                                  VICE
                                                                  H VO
REF
                                                                   OF N
                                                                    .CIR
                                                                    INEF
RES
                                                                     REF
                                                                     L BO
                                                                      T TO
                                                                      HPS
                                                                      REV
                                                                      RES
                                                                      EEV
                                                                       OR T
RES
.UND DIATOR
                                                                        PT S
                                                                        FICIE
                                                                        T3 S
                                                                        T4 S
                                                                        T5 S
                                                                         LTAG
EED
                                                                         Tf SE R DEF.
                                                                         .RES
                                                                         VALV EAKING
                                                                          .OVE
                                                                          FICIE
                                                                           O.D.R
                                                                           ARD
                                                                            SEN
                                                                            OR C
                                                                            OR C DEF.
                                                                            O.D.A LOW
                                                                            CHE
                                                                            REV
                                                                             HER
                                                                             ENS
                                                                             ENS
                                                                             ENS
                                                                             ENS
                                                                             I.D.A
                                                                              ERC
                                                                              NT O
                                                                               TO A
                                                                               TRIC
                                                                               NSO
                                                                               E WIR
                                                                               E LE
                                                                                RCH
                                                                                NT C
                                                                                OR W .
                                                                                 SOR
                                                                                 A
                                                                                 CK M
I.D.F
                                                                                  L
                                                                                  OIL
                                                                                   OIL D
                                                                                   MOS
                                                                                   OR D
                                                                                   OR D
                                                                                   O
                                                                                   OR D
                                                                                   IRFL
                                                                                    IRF
                                                                                    HAR
                                                                                     .D.FA
DJU
                                                                                     R DE
                                                                                     TION
                                                                                      AKIN
                                                                                      ARG
                                                                                       OMP
                                                                                       INGS
                                                                                        DEF
                                                                                        RES
                                                                                        USE
                                                                                        ODE
TAT
OW
GE
                                                                                         EF.
                                                                                         EF.
                                                                                         EF.
                                                                                          EF.
                                                                                          ST
                                                                                           E
                                                                                           F.
                                                                                           S
                                                                                           N
                                                                                            .
                                                    C   P               S
              Display shows nothing
                                                    H   P               S
                                                    C       P P         S                                                                 S
              System won't start SS
                                                    H       P P         S                                                                 S
  SYSTEM                                            C                       P P     P     P           S           S S             S
              Capacity is insuffciency
                                                    H                       P P     P     P               S       S S             S
                                                    C                   P
              Display is not normal when running
                                                    H                   P
              Cool when heating requirement         H       P                                                 S
                                                    C                           P P           S   P
              P1                                    H                       P                 S   P
                                                    C           P                         P           S             S
              P2/H5                                 H           P                         P           S             S
                                                    C                               P P       S   P
              P3                                    H                       P                 S   P
                                                    C                           P P           S   S                         S
              P5                                    H                                             S
 REFRIGER
                                                    C                           P   P S
    ANT       P0                                                                P   P S
                                                    H
  CIRCUIT                                           C                                     P           S                           S
              P4
                                                    H                                     P               S                       S
                                                    C                                         P       P                     S     S
              PH
                                                    H                                         P           P                       S
              C3(T3 is seated fault)                C                                                                       P             S
                                                    C                                                                       S     P
              E7(T5 is seated fault)                                                                                    S         P
                                                    H
                                                    C                                                                         S
              ATL(Ambient temp. beyond the license)                                                                           S
                                                    H
                                                    C                                                                       P P   P   P
              E4
                                                    H                                                                       P P   P   P
                                                    C                                                                   P
              H8
                                                    H                                                                   P
                                                    C                                                                       S             P
              F1
                                                    H                                                                                     P
                                                    C                   S           P
              E6                                    H                   S           P
 ELECTRIC                                           C                               P
              P6                                    H                               P
   AL OR                                            C
              P8
 CONTROL                                            H
                                                    C               S   P
              L0-L9                                 H               S   P
                                                    C                   P
              E9                                    H                   P
                                                    C                   P
              H0                                    H                   P
                                                    C   P               S
              E5                                    H   P               S
Table 15-16
                                                        32
16123000A31011 V1.0
印刷技术要求
材质   80g双胶纸
规格 210*297(双面)
颜色 黑白
其他    /
设计更改记录表(仅做说明用,不做菲林)
                                 涉及更改页面
版本升级      更改人    更改日期   更改主要内容
                                 (印刷页码)