Instructions for use
07897073EN01 Rev.15
08/2019
Legal Information
          The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in
          this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of
          their respective owners.
          This guide and its content are protected under applicable copyright laws and furnished for informational
          use only. No part of this guide may be reproduced or transmitted in any form or by any means (electronic,
          mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of
          Schneider Electric.
          Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a
          non-exclusive and personal license to consult it on an "as is" basis.
          Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by
          qualified personnel.
          As standards, specifications, and designs change from time to time, information contained in this guide may be
          subject to change without notice.
          To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its
          subsidiaries for any errors or omissions in the informational content of this material or consequences arising out
          of or resulting from the use of the information contained herein.
RM6 - Instructions for use
Table of Contents
                             Safety Information............................................................................ 6
                               Safety Instructions................................................................................................... 7
                               Disposal of the Equipment at End-of-Life................................................................ 7
                             General Description.......................................................................... 8
                               Circuit-breaker and Switch Function........................................................................ 8
                               RM6 Connected Advanced Circuit-breaker and Switch Function............................ 8
                               Switch-fuse Combination and Switch Function....................................................... 9
                               RM6 Connected Advanced Switch-fuse Combination and Switch Function........... 9
                               “Switchboard Coupling” Switch and Circuit-breakers.............................................. 9
                               RM6 Connected Advanced Circuit-breaker Function ........................................... 10
                               RM6 Connected Advanced Switch Function ........................................................ 10
                               Cable Connection Function................................................................................... 11
                               Metering Cubicle.................................................................................................... 11
                               Example of Single-line Diagrams.......................................................................... 12
                             Operating Instructions.................................................................... 40
                               Operating and Viewing Cubicle Condition............................................................. 40
                               Checking the Pressure.......................................................................................... 40
                               Operating Service.................................................................................................. 43
                               Operating Safety.................................................................................................... 44
                               Key-locking (optional)............................................................................................ 45
                               Padlocking............................................................................................................. 45
                               Smart Ready Cubicle............................................................................................. 47
                               Thermal Monitoring Sensors................................................................................. 52
                               Environmental Monitoring Option ......................................................................... 52
                               Fuse Blowing Indication (Optional Supply)............................................................ 54
                               Flooding Option..................................................................................................... 54
                               Anti-Intrusion Low Voltage Cabinet....................................................................... 56
                               Overcurrent Indicator............................................................................................. 57
                               LV Connection Indicator Flair 2xD......................................................................... 58
                               Detector Pending Fault ......................................................................................... 58
                               Ammeter................................................................................................................ 63
                               Connection of CTs to the 3 MV cables ................................................................. 64
                               Voltage Detection Relay........................................................................................ 65
                               Access to the Cable Compartments...................................................................... 67
07897073EN01-15                                                                                                                                        3
                                                                                                        RM6 - Instructions for use
                      Preventive Maintenance................................................................. 69
                        Standard Operating Conditions............................................................................. 69
                        Harsh Operating Conditions.................................................................................. 70
                      Corrective Maintenance................................................................. 71
                        Foreword............................................................................................................... 71
                        Maintenance Summary Table................................................................................ 71
                        Replacing a Voltage Presence Unit....................................................................... 71
                        Replacing a Fuse................................................................................................... 72
                        Replacing a Charging Motor.................................................................................. 76
                        Replacing a Printed Circuit.................................................................................... 78
                        Replacing the LV Contacts.................................................................................... 81
                        Processing of SF6 Gas when Dismantling the Equipment.................................... 82
4                                                                                                                  07897073EN01-15
RM6 - Instructions for use   Notes
07897073EN01-15                 5
Safety Information                                                                  RM6 - Instructions for use
Safety Information
Important Information
                                                            DANGER
                         DANGER indicates a hazardous situation which, if not avoided,
                         will result in death or serious injury.
                                                          WARNING
                         WARNING indicates a hazardous situation which, if not avoided,
                         could result in death or serious injury.
                                                           CAUTION
                         CAUTION indicates a hazardous situation which, if not avoided,
                         could result in minor or moderate injury.
                                                          NOTICE
                         NOTICE is used to address practices not related to physical injury. The safety
                         alert symbol shall not be used with this signal word.
Please Note
                        Electrical equipment should be installed, operated, serviced, and maintained only by
                        qualified personnel. No responsibility is assumed by Schneider Electric for any
                        consequences arising out of the use of this material.
                        A qualified person is one who has skills and knowledge related to the construction,
                        installation, and operation of electrical equipment and has received safety training to
                        recognize and avoid the hazards involved.
6                                                                                           07897073EN01-15
RM6 - Instructions for use                                                                       Safety Information
Information Advice
                                       INFORMATION-ADVICE
                                       We draw your attention on this particular point.
Diffusion Rules               Total or partial reproduction of this manual is prohibited and only Schneider Electric
                             agents have an exclusive right to use.
Safety Instructions
Safety Rules
                                                                    DANGER
                              HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                              ● Apply appropriate personal protective equipment (PPE) and follow safe electrical
                                work practices.
                              ● This equipment must only be installed and serviced by qualified electrical
                                personnel.
                              ● Turn off all power supplies of the equipment before working on or inside
                                equipment.
                              ● Always use a properly rated voltage sensing device to confirm power is off.
                              ● Set all devices, doors and covers before turning on power to this equipment.
                              ● Do not use solvents and alcohol for cleaning.
                              ● Do not use high-pressure cleaner.
                              ● Beware of potential hazards, and carefully inspect the work area for tools and
                                objects that may have been left inside the equipment.
                              Failure to follow these instructions will result in death or serious injury.
                                                               WARNING
                              HAZARD OF MECHANICAL IMPACT
                              ● Apply appropriate personal protective equipment (PPE) and follow
                                safe work practices.
                              ● This equipment must only be dismantled by qualified personnel.
                              Failure to follow these instructions can result in death, serious injury
                              or equipment damage.
                             NOTE: This equipment contains SF6 gas. SF6 is a powerful greenhouse gas. Prior to
                             disposal of the equipment at end-of-life, the SF6 gas must be recovered in order for it
                             to be recycled, reclaimed or destroyed.
                             Schneider Electric offers a complete service to dismantle and recycle Medium Voltage
                             equipment and SF6 gas at end-of-life. This service is compliant with IEC 62271-4 and
                             conforms to local regulations.
                             Contact Schneider Electric for more information.
07897073EN01-15                                                                                                        7
General description                                                                                                                                                                                                                             RM6 - Instructions for use
General Description
 I = Switch & earthing switch                                              DE-Mt = Double extensible metering
 Q = Switch-fuse combination & earthing switch
 D = Circuit Breaker up to 200A & earthing switch
 B = Circuit breaker up to 630A & earthing switch                          NE = No Extensible
 Ic = Busbar coupling switch & earthing switch                             DE = Double Extensible
 Bc = Busbar coupling circuit breaker up to 630A & earthing switch         LE = Left Extensible
 O = Cable connection                                                      RE = Right Extensible
OFF
OFF
                                                                                                                                                                                                                                                                   DO NOT
                                                                               OK
ON
OK
ON
OK
ON
                                                                                                                                                                                                                                                                  OPERATE
                                                                                                                                                                                                                                                    GLI/LCD
                                                                                                                                                                                                                                                                VERY LOW
                                                                                                     L1   L2   L3                                                  L1   L2   L3                                     L1   L2   L3                                NOT   OK
                                                                                                                                                                                                                                                              TEST          DENSITY CHECK
Reset
M: designation plate
P: location of optimal pressure switch                         M
Q: switch control unit (SC150H module)                         H
R: RM6 Connected Advanced cabinet
IDI
8                                                                                                                                                                                                                                                                                               07897073EN01-15
RM6 - Instructions for use                                                                                                                                                                                                                                            General description
IQI
                                                                                                                                                                                   OFF
                                                                                                                                                                                                                                             DO NOT
                                                                     OK
ON
OK
                                                                                                                                                                              ON
                                                                                                                                                                                                                                            OPERATE
                                                                                                                                                                                                                              GLI/LCD
                                                                                                                                                                                                                                          VERY LOW
                                                                                            L1   L2   L3                                 L1   L2   L3                                         L1   L2   L3                                NOT   OK
                                                                                                                                                                                                                                        TEST          DENSITY CHECK
P: pressure switch L1 L2 L3 L1 L2 L3
IQI
07897073EN01-15                                                                                                                                                                                                                                                                        9
General description                                                                                                                                                                                                            RM6 - Instructions for use
                                                                                                                    OFF
                                                                                                          OK
                                                                                                               ON
                                                                                                                                                                                                  DO NOT
                                                                                                                                                                                                 OPERATE
                                                                                                                                         L1          L2          L3
                                                                                                                                                                                   GLI/LCD
                                                                                                                                                                                               VERY LOW
                                                                                                                                                                                               NOT   OK
                                                                                                                                                                                             TEST          DENSITY CHECK
Reset
                                                             L                                                                                                                                                             C
E: function (switch or circuit breaker) position indicator
F: voltage indicator
                                                             E
                                                                                                                                                                                                                           D
G: LV connection access trunking                             A                  L1                  L2
                                                                                                                                                  L3
DE-D
                                                                                                                                              DO NOT
                                                                                OK
ON
                                                                                                                                             OPERATE
                                                                                                                               GLI/LCD
                                                             A
E: function (switch or circuit breaker) position indicator                                                                                                                                                                 C
F: voltage indicator                                         E                                                                                                                                                             D
G: LV connection access trunking                             M                   L1                  L2                   L3
DE-I
10                                                                                                                                                                                                                                   07897073EN01-15
RM6 - Instructions for use                                             General description
A: nameplate
                                             A
B: designation plate
C: connection bushing access panel
                                             B
Metering Cubicle
1: LV cabinet
2: voltage transformer access panel
3: nameplate
4: access panel to current transformer
5: LV compartment
3 2 4 5 1
07897073EN01-15                                                                        11
General description                                                  RM6 - Instructions for use
12                                                                         07897073EN01-15
RM6 - Instructions for use   Notes
07897073EN01-15                13
Instructions for putting the RM6 into operation                                                             RM6 - Instructions for use
14                                                                                                                  07897073EN01-15
RM6 - Instructions for use                                                                      Instructions for putting the RM6 into operation
Presentation of VPIS
VPIS: Voltage Presence Indicating System,                    Identify which VPIS version you have.
provides light indication image of MV voltage presence
with 3 built-in lights.
                                                                                                  DANGER
                                                              HAZARD OF ELECTRICAL SHOCK
                                                              To ensure that the system is de-energized do not rely on only the indication provided
                                                              by a VPIS alone.
                                                              Failure to follow these instructions will result in death or serious injury.
                                                             NOTE: When the ambient lighting is particularly bright, it may be necessary to improve
                                                             visibility by protecting the indication.
07897073EN01-15                                                                                                                                  15
Instructions for putting the RM6 into operation                                                                          RM6 - Instructions for use
Test
          1                        2
Result                                                  Action
The 3 light indicators of each VPIS                     The 2 functional units are energized, the VPIS units
are on.                                                 are operating and the check can continue.
V1 V1 OK
PCU V1 Ref. 51191954FA Phase Concordance Unit V1 can be used between 2 VPIS V1 only.
                                                             V2
 PCU V2 without adapter                                                                             Use an adapter if VPIS V2 or upgrade both units
                                       V1                    or                          OK
 Ref. VPI62421                                               V3                                     to VPIS V3.
16                                                                                                                               07897073EN01-15
RM6 - Instructions for use                                                   Instructions for putting the RM6 into operation
                                legend
                                légende
                                                                                                 phase
                                                                                                 LED duconcordance
                                                                                                        comparateurunit LED lit
                                                                                                                    allumée
                                                                                                 LED unlit
                                                                                                     éteinte
L1
L2 Wiring is ok.
L3
L1
L3
L1
L3
L1
L3
                                                   L1
                                                                                 Change the position of each MV cable on
                                                                                 one of the 2 functional units.
                                                   L2
                                                                                                                          L1
                                                                                                                     L2        L3
                                                   L3
                                                   L1
                                                                                 Change the position of each MV cable on
                                                                                 one of the 2 functional units.
                                                   L2
                                                                                                                          L1
                                                                                                                     L2        L3
                                                   L3
07897073EN01-15                                                                                                                17
Instructions for putting the RM6 into operation                                                                   RM6 - Instructions for use
Characteristics
                                                      The voltage detecting system equipping your RM6 is of the separate VDS type, HR
                                                      system. It complies with standard IEC 61243-5.
                                                                                         WARNING
                                                       HAZARD OF ELECTRIC SHOCK
                                                       ● Use only the accessories complying with standard IEC 61243-5.
                                                       ● Follow the instructions of the accessory manufacturer.
                                                       Failure to follow these instructions can result in death, serious injury or
                                                       equipment damage.
Functional principle
                                                      The Wega 1.2 C is used to detect the presence or absence of medium voltages. Use a
                                                      suitable detection device (for example, Horstmann Orion 3.1 or Orion M1) to test both
                                                      the interface and voltage and to perform a phase comparison. Connect the detection
                                                      device to the LRM test sockets.
18                                                                                                                      07897073EN01-15
RM6 - Instructions for use                                         Instructions for putting the RM6 into operation
Display indication
                             There is a display indication on the front face of the device.
                             Indication        Definition
                                               Voltage present
                                               Threshold values for voltage presence indication:
                                               0.1 - 0.45 x Service Voltage.
                                               INSTALLATION NOTE: the voltage signal is too low when
                                               operating the system at nominal voltage.
                                               The causes are usually:
                                               - a wrong ordered service voltage or,
                                               - the operation of the switchgear at a nominal voltage which is
                                                 lower than the one for which the device was originally rated.
                                               Voltage present and integrated maintenance test passed
                                               The current flowing through the indication device complies
                                               with the requirements for current monitoring according to
                                               IEC 61243-5 (VDE 0682 Part 415), Section 5.28
                                               (maintenance test on the integrated VDS).
                                               A maintenance test is not necessary due to the continuous
                                               monitoring and indication.
                                               Voltage present and integrated maintenance test
                                               passed, however the voltage signal is too high
                                               INSTALLATION NOTE: Voltage signal too high.
                                               The cause is usually:
                                               - a wrong ordered service voltage or,
                                               - the operation of the switchgear at a nominal voltage which is
                                               higher than the one for which the device was originally rated.
                                               Voltage not present
                                               All symbols are in off-state while the switchgear is
                                               de-energized. Presence of voltage <0.1 x Service Voltage.
Functional test
                             A functional test is possible while the unit is energized (indication of arrow and dot
                             symbols) or while the unit is de-energized.
Energized state
                             Perform the functional test by short-circuiting one of the three test sockets with the
                             earth socket. The displayed symbol (L1, L2 or L3) disappears. The short-circuit jumper
                             must be removed after the test.
De-energized state
                             There are two possibilities to perform the functional test in the de-energized state:
                             1: Display test
                             b Press the ‘Display’ button.
                             b All symbols on the LCD indication are activated momentarily.
                             2: Functional test using the "function tester for Wega".
                             b Connect the measuring leads of the function tester to one of the three test sockets
                               and the earth socket of the Wega 1.2 C.
                             b Switch on the function tester.
                             b The appropriate arrow and dot symbols appear (see table above). The wrench tool
                               symbol is not activated.
                                                                       DANGER
                              HAZARD OF ELECTRIC SHOCK OR EXPLOSION
                              ● If the specified indication does not appear, the VDS component is defected and
                                has to be replaced.
                              ● Without appropriate voltage detection, access to the cable compartment is
                                forbidden.
                              Failure to follow these instructions will result in death or serious injury.
07897073EN01-15                                                                                                       19
Instructions for putting the RM6 into operation                                                               RM6 - Instructions for use
                                                  When the VDS unit is defective it has to be replaced. During dismounting and
                                                  installation, follow safe electrical work practices.
                                                                                       WARNING
                                                   HAZARD OF ELECTRIC SHOCK
                                                   ● DO NOT dismount or install the VDS while the functional unit is energized.
                                                   ● Make sure that all medium voltage cables of the functional unit are de-energized.
                                                   ● Make sure that the switch of the functional unit is in open position.
                                                   Failure to follow these instructions can result in death or serious injury.
Voltage detection
                                                  The Wega 1.2 C is designed for continuous operation. The voltage is continuously
                                                  detected after the installation of the Wega 1.2 C in the switchgear.
                                                  The voltage state is displayed for each phase via the LCD indication (see table
                                                  page 19).
Phase comparison
                                                  Perform a phase comparison using a phase comparator for LRM systems available as
                                                  an option according to VDE 0682 Part 415 (for example, Horstmann Orion 3.1 or Orion
                                                  M1). Connect the phase comparator’s connection leads to one of the three LRM test
                                                  sockets and the earth socket. The test sockets are accessible once the protective cap
                                                  has been removed.
                                                  b The corresponding indication for the Wega 1.2 C may be weaker or may even go off.
                                                  b Attach the protective cap after the phase comparison.
                                                                                     WARNING
                                                   HAZARD OF WRONG FUNCTIONNALITY
                                                   Disable all automation using voltage presence signal before carrying out the phase
                                                   concordance test.
                                                   Failure to follow these instructions can result in death, serious injury
                                                   or equipment damage.
Voltage detection
                                                  When testing the cable sheath or during DC tests on switchgears equipped with the
                                                  Wega 1.2 C, Schneider Electric advises connecting the three measuring sockets for
                                                  L1, L2 and L3 to the earth socket using short leads (max. 25 cm). The 4-pole Wega
                                                  short-circuit plug available as an accessory can also be used as an alternative (Order
                                                  no.51-9904-001).
                                                                                     NOTICE
                                                   HAZARD OF COMPONENT DAMAGE
                                                   DO NOT perform medium voltage cable testing without connecting the three
                                                   measuring sockets to the earthing socket.
                                                   Failure to follow these instructions can result in equipment damage.
20                                                                                                                    07897073EN01-15
RM6 - Instructions for use                                                    Instructions for putting the RM6 into operation
                                   The rating of the fuses to be fitted in the RM6 protection function depends on the
                                   following factors (among others):
                                   b operating voltage;
                                   b transformer rating;
                                   b fuse technology (manufacturer).
                                                                             CAUTION
                                    HAZARD OF MALFUNCTIONING OF THE SWITCH-FUSE COMBINATION
                                    ● Use only the fuses mentioned in the reference list.
                                    ● Replace all the fuses if one or two poles of the combination has operated
                                      (as per standard IEC 62271-105). Before replacing the fuses, take precautions, as
                                      the fuse body can be hot.
                                    Failure to follow these instructions can result in injury or equipment damage.
Dimensions of the Solefuse fuses (as per standard UTE C64-210 and IEC 60282.1)
Ø55
450 35
Dimensions of the Fusarc CF and SIBA HH Type fuses (as per standard IEC 60282.1)
                                                                               Ø
                                      Ø45
33 L 33. 27
07897073EN01-15                                                                                                                   21
Instructions for putting the RM6 into operation                                                                           RM6 - Instructions for use
Selection Table
(rating in A, use without overload at –25°C < Ө < 40° C)
22                                                                                                                                 07897073EN01-15
RM6 - Instructions for use                                         Instructions for putting the RM6 into operation
                             To remove the cover, remove the 2 screws on each side of the cover then lift it and pull
                             it towards you. The instructions are visible on the cover.
                                        INFORMATION
                                        In the case of an internal arc unit module, it is possible to disassemble the
                                        deflector to have a better accessibility.
                                        Therefore, remove the 2 screws on each side, then pull it towards you.
                             Release the plug and push the extraction handle manually to release the plug (tap with
                             the palm of your hand to detach the plug seal if necessary).
Fit the plug as far as it can go and turn it counter-clockwise to extract it.
07897073EN01-15                                                                                                         23
Instructions for putting the RM6 into operation                                                                RM6 - Instructions for use
                                                            INFORMATION
                                                            To clean the plugs, consult the preventive maintenance section.
RM6
                                                  Recover the centring devices in the bag supplied with the cubicle. Insert the fuse in the
                                                  compartment. Fit the centring device on the fuse. Insert the plug pins in the plinth
                                                  and turn clockwise.
                                                  Fix the fuse on the plug using an Allen wrench n°5 and insert the fuse in the
                                                  compartment. Tightening torque: 15 N.m.
                                                  Insert the plug and fuse assembly in the compartment. Insert the plug pins in the plinth
                                                  and turn clockwise. Press to insert the assembly in the downstream clamp.
24                                                                                                                    07897073EN01-15
RM6 - Instructions for use                                                Instructions for putting the RM6 into operation
                                                                          CAUTION
                                      Fuse blowing releases a striker that causes three-phase opening of the switch and
                                      prevents it from reclosing.
Striker pin
                                     Make sure that the handle trunnions are inserted in the plinth slots, and lock the plug
                                     manually by folding down the operating handle. Plug with fuse blowing release,
                                     used to cause three-phase opening of the switch. Press down the tipper to position it.
07897073EN01-15                                                                                                            25
Instructions for putting the RM6 into operation                   RM6 - Instructions for use
                                                      C
                                                              A
                                                                  A
                                                  B
26                                                                      07897073EN01-15
RM6 - Instructions for use       Instructions for putting the RM6 into operation
With LV Compartment
A: steel seal + steel wire
07897073EN01-15                                                              27
Instructions for putting into operation the protection relay for circuit- breaker                                             RM6 - Instructions for use
Presentation
                                                             The User-Machine Interface (UMI) on the front panel of VIP relays consists of a
                                                             display, LEDs and keys. A sealable pivoting flap can prevent access to the setting keys
                                                             by unauthorized persons.
                                                             The VIP parameters must be set correctly in order for the circuit-breaker to operate
                                                             correctly.
1: display                                                                          10 11         1
2: status LEDs
3: fault indication LEDs
4: z one for a user-customizable label with pictograms of                                                                                 2
   the fault indication LEDs
5: acknowledgement key
6: identification label                                                                                                                    3
7: sealing ring                                                                                                  Reset
                                                                                                                                           4
8: selection keys
                                                                                                                                           5
9: k ey for selecting menus and testing LEDs.
   When the VIP is not supplied with power, this key can
   also be used to start the VIP from the battery in order                                                               VIP 400
                                                                                                                         REL 59915
   to enter settings                                                                                                                       6
                                                              flap closed                                                QZ10370005
Reset
Esc
flap open
16 15 14 7 13 12
28                                                                                                                                    07897073EN01-15
RM6 - Instructions for use                                   Instructions for putting into operation the protection relay for circuit-breaker
Identification Zone
The identification zone on the front panel enables a VIP
to be identified.                                          VIP400
1: identification code
2: reference
3: supply voltage
4: serial number                                                                                                VIP 400                    1
                                                                                                                REL 59915                  2
QZ10370005 3
VIP410
                                                                                                                 VIP 410E                  1
                                                                                                                 REL 59917                 2
                                                                                            Reset                110-250 V DC
                                                                                                                                           4
                                                                                                                 100-240 V AC
                                                                                                                 QZ12039999                3
Precautions
VIP installed in a cubicle
                                                           bb Transport
                                                           VIP relays can be transported by all suitable means of transport in the usual conditions
                                                           for cubicles.
                                                           Storage conditions should be taken into consideration for a long period of transport.
                                                           bb Handling
                                                           If the cubicle is dropped, check the VIP’s condition by visual inspection and energising.
                                                           bb Storage
                                                           Schneider Electric recommends keeping the cubicle protective packaging for as long
                                                           as possible.
                                                           VIP relays, like all electronic units, must not be stored in a damp environment for more
                                                           than one month. They should be energized as quickly as possible. If this is not
                                                           possible, the cubicle reheating system must be activated.
Phase Current Sensors
                                                           VIPs operate exclusively with dual core CUa (200 A primary) and CUb (630 A primary)
                                                           current sensors.
                                                           These sensors provide:
                                                           bb the VIP power supply,
                                                           bb metering of all 3 phase currents and the earth fault current.
                                                           The use of dedicated sensors means that the complete protection chain performance
                                                           (sensor, VIP, Mitop trip unit) can be guaranteed.
                                                           It is very easy to connect VIP relays to the CUa or CUb sensors by means of 2
                                                           prewired connectors from the sensors:
                                                           bb 1 x 9-pin SUBD connector for metering the phase and earth fault currents,
                                                           bb 1 x 6-pin lockable connector for the VIP power supply.
                                                           The CUa and CUb current sensors consist of 2 windings per phase:
                                                           bb one winding providing the VIP power supply,
                                                           bb the other winding enabling the VIP to measure the phase currents.
                                                           The earth fault current is measured by taking the sum of the 3 phase currents inside
                                                           the sensor.
07897073EN01-15                                                                                                                                   29
Instructions for putting into operation the protection relay for circuit- breaker                                    RM6 - Instructions for use
                                                                                                     E
                                                                                                                I1
                                                                                                                I2
                                                                  1
                                                                                                                I3
Io
Connection precautions
                                                                                                 DANGER
                                                          HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
                                                          ● Never leave the current sensor secondary in open circuit.
                                                           The high voltage that would result from opening the circuit is dangerous for the
                                                           operator and for the equipment.
                                                          ● Never disconnect the VIP protection relay current sensor connectors unless the
                                                            MV circuit-breaker is in the open position and completely isolated.
                                                          ● Wear insulating gloves to avoid any contact with a conductor that has accidentally
                                                            been energized.
                                                          ● Wear personal protective equipment in compliance with current regulations.
                                                          ● Screw tight all terminals, even those not in use.
                                                          Failure to follow these instructions will result in death or serious injury.
30                                                                                                                          07897073EN01-15
RM6 - Instructions for use                                       Instructions for putting into operation the protection relay for circuit-breaker
                                                              The VIP protection relay is connected to the Mitop trip unit with a 2-pin prewired
                                                              connector from the Mitop trip unit. Connect the lockable 2-pin connector to the VIP.
Earthing
                                                                                                 WARNING
                                                                HAZARD OF ELECTRIC SHOCK
                                                                Connect the VIP to earth. Check the integrity of protective conductor connection
                                                                before carrying out any other actions.
                                                                Failure to follow these instructions can result in death, serious injury, or
                                                                equipment damage.
Status LEDs
The status LEDs provide information about the VIP general status:
07897073EN01-15                                                                                                                                        31
Instructions for putting into operation the protection relay for circuit- breaker                                      RM6 - Instructions for use
                                                         After a trip, the fault indication LEDs are powered by the battery embedded in the VIP
                                                         or by the VIP410 auxiliary power supply.
                                                         Fault indication by the LEDs can be stopped:
                                                         bb by pressing the Reset key,
                                                         bb automatically by the reappearance of a current in the network higher than the
                                                         pick-up current,
                                                         bb automatically after 24 hours,
                                                         bb by remote control order via the communication (VIP410).
                                                         For the first 3 LEDs, faster flashing may occur before the protection trips, to indicate
                                                         the following information:
                                                               pictogram                                    overshoot
                                                                                Overshoot of the instantaneous set point for phase
                                                                                overcurrent protection (I> or I>> or I>>> pickup outputs)
                                                                                Overshoot of the instantaneous set point for earth fault
                                                                                protection (Io> or Io>> pick-up outputs)
                                                                                Overshoot of the alarm set point for thermal overload
                                                                                protection
Note
                                                         In custom mode, the protection set points may not be assigned to the Mitop trip unit
                                                         output. In this case, the fault indication LED may be active, without being
                                                         associated with the circuit-breaker trip. Depending on the application, this
                                                         can indicate the presence of a fault without tripping the circuit-breaker. The fault
                                                         indication LED pictograms can be customized by sticking a label to the right of the
                                                         LEDs.
Display
       Io                                                The display is an LCD unit.
                                                         It is only back-lit on the VIP410, when the auxiliary power supply is present.
       0.1 A                                             Each VIP function is presented in a screen consisting of the following items:
                                                         bb 1st line: symbols for electrical values or function name
                                                         bb 2nd line: displays the values of measurements or parameters associated with the
                                                         function
                                                         bb a menu pointer, on the left, points to the pictogram of the selected menu.
Menu Organization
                                                         All the data available in the VIP relay is divided between 3 menus:
                                                         bb the metering menu        contains the current measurements, peak demand currents,
                                                         load history, event records, fault trip counter and the breaking current history.
                                                         bb the protection menu       contains the essential settings for setting up the protection
                                                         functions.
                                                         bb the parameters menu         contains the parameters that are used to adapt VIP
                                                         operation to particular applications. When a VIP is new, all the parameters in this menu
                                                         have a default value. The protection functions are operational even with the
                                                         parameters menu default values.
32                                                                                                                           07897073EN01-15
RM6 - Instructions for use          Instructions for putting into operation the protection relay for circuit-breaker
Default Screen
                                  A default screen is displayed automatically 3 minutes after the last keystroke.
                                  This default screen is the screen displaying the phase currents.
Integral Battery
                                  The VIP has an integral battery. It is used to:
                                  bb activate the user-machine interface in order to enter settings when the VIP is not
                                  supplied with power.
                                  bb illuminate the fault indication LEDs when the VIP is no longer supplied with power
                                  after giving the opening order to the circuit-breaker.
                                  bb power the internal calendar.
                                  When the VIP is not supplied with power:
                                  Pressing and holding down the key          activates battery-powered operation of the
                                  user-machine interface. It is then possible to access the menus in order to enter
                                  settings. In this case, the display turns off automatically after 3 minutes of inactivity on
                                  the keypad.
                                  bb The protection functions are activated automatically if the current reappears. The
                                  integral battery plays no part in operating the protection functions. The protection
                                  functions work even when there is no battery.
                                  NOTE:
                                  bb in battery operation mode, the VIP processor runs with a reduced clock frequency to
                                  ensure the battery life is maintained. As a result, the user-machine interface may be
                                  slower to react.
                                  bb during a setting operation with the VIP powered by its internal battery alone, the
                                  clock display is not refreshed on screen. However the internal clock increments
                                  normally.
07897073EN01-15                                                                                                             33
Instructions for putting into operation the protection relay for circuit- breaker                                   RM6 - Instructions for use
Reset
                                                                                                  400
                                                                                              VIP 59915
                                                                                              REL
                                                                                                        05
                                                                                                    3700
                                                                                              QZ10
Battery Recycling
                                                                                                             WARNING
                                                          HAZARD OF EXPLOSION
                                                          ● Do not recharge the battery.
                                                          ● Do not short circuit the battery.
                                                          ● Do not crush the battery.
                                                          ● Do not disassemble the battery.
                                                          ● Do not heat the battery above 100°C (212°F).
                                                          ● Do not throw the battery into fire or water.
                                                          Failure to follow these instructions can result in death, serious injury,
                                                          or equipment damage.
Battery Characteristics
                                                         b   1/2 AA 3.6 V lithium battery
                                                         b   Model: LS14250 from SAFT
                                                         b   Storage conditions: as defined in EN 60086-4
                                                         b   Do not use rechargeable batteries or other types of battery
Replacement Procedure
                                                         When depleted, the battery is replaced as follows:
                                                         b 1: Insert a battery with the above characteristics, respecting the polarity
                                                         (+ facing up).
                                                         b 2: Re-close the battery compartment.
                                                         b 3: Replace the cover shielding the battery compartment.
                                                         b 4: Test the battery by pressing the Reset key for 2 to 3 seconds: the LEDs must
                                                         remain on clearly without fading for the whole time the key is pressed.
                                                         b 5: Reset the VIP time if necessary.
                                                         b 6: Close the settings protective flap.
Cleaning Product
                                                         To clean the product (especially when dusting), simply use a damp cloth.
34                                                                                                                         07897073EN01-15
RM6 - Instructions for use     Instructions for putting into operation the protection relay for circuit-breaker
Battery Module
                             The pocket battery module should only be used during maintenance or commissioning
                             by qualified personnel and must never be left permanently connected to a running VIP.
LV434206
07897073EN01-15                                                                                                     35
Instructions for putting into operation the protection relay for circuit- breaker                                     RM6 - Instructions for use
VIP40 / VIP45
                                                         NOTE: The VIP40 / VIP45 protection relay does not apply to the RM6 Connected
Presentation                                             Advanced unit.
                                                         The user-machine Interface (UMI) on the front panel of VIP relays consists of a display,
                                                         LEDs and keys. A sealable pivoting flap can prevent access to the setting keys by
                                                         unauthorized persons.
1: display                                                                      1
2: lugs for opening the transparent protective flap
3: transparent protective flap
4: Imax. peak demand display button                                                                                       7
5: sealing ring                                                                                                           8
6: Test/Reset button                                                                                                      9
7: status LED
8: space for a user-customizable label
9: trip fault indication LED
10: identification label                                  2
11: symbol indicating that it is necessary to read
     the manual                                           3
12: battery
                                                                                                                         10
4 5 6 11
12
Identification Label
                                                         The identification label on the front panel is used to identify the VIP:
                                                         bb product name
                                                         bb product reference
                                                         bb serial number
Display
                                                         The display is an LCD unit.
                                                         During operation, the display indicates the value of the current on each phase in
                                                         succession. Each phase remains displayed for 3 seconds before automatically
                                                         changing to the next. The display is in amps, on three digits.
                                                         If the phase current is less than the pick-up current, consult the reference
                                                         NRJED311207EN. The VIP is not activated and the display is off.
36                                                                                                                            07897073EN01-15
RM6 - Instructions for use                   Instructions for putting into operation the protection relay for circuit-breaker
Test/Reset button
                                           After a trip, pressing this button stops the flashing trip indication. This button can also
                                           be used to:
                                           bb test the built-in battery. When pressing the Test/Reset button, the fault indication
                                           LED lights up immediately to indicate that the battery is OK.
                                           bb perform the “lamp test” if the relay is supplied with power. Pressing the Test/Reset
                                           button for 5 seconds causes all the display segments and the            status LED to light
                                           up, and displays the software version number.
                                           The VIP built-in battery only supplies power to the fault indication LED and displays the
                                           type of fault. It has no role in operating the protection functions.
                                           The symbol        indicates that it is necessary to read the VIP reference manual
                                           before working on the product.
07897073EN01-15                                                                                                                      37
Instructions for putting into operation the protection relay for circuit- breaker                                   RM6 - Instructions for use
VIP40/45 Settings
Front Panel                                              When the protective flap is opened, you can enter the protection settings by means of
                                                         the rotary switches. To do this, use a 3 mm flat blade screwdriver.
                                                                                                                    5
                                                              1
2 4
                                                                                              3
1: phase overcurrent protection adjustment dial
2: setting range selector switch
3: earth fault protection set point adjustment dial      VIP45
4: earth fault protection time delay adjustment dial
5: advanced settings protective cover
6: connection port for the pocket battery module
7: Trip test button
                                                                                                                    7
                                                              1
2 6
3 4 5
Advanced Settings
                                                         To access the advanced settings, remove the advanced settings protective cover.
                                                         Both settings can be entered using a single selector switch:
                                                         bb discrimination with the LV CB
                                                         bb earth fault protection inrush current delay
38                                                                                                                          07897073EN01-15
RM6 - Instructions for use           Instructions for putting into operation the protection relay for circuit-breaker
Frequency
                                   The network frequency (50 Hz or 60 Hz) is a parameter that must be known for
                                   operation of the VIP40 and VIP45 signal processing algorithms.They therefore have
                                   an automatic frequency recognition system.
                                   The recognized value (50 Hz or 60 Hz) is stored and the VIP works permanently with
                                   this value.
                                   This stored value is used each time the VIP starts.
                                   For the VIP to recognize the network frequency and store it, it has to detect a current
                                   on phase 1 for a minimum period of 5 seconds in the range 50 Hz +/- 2 Hz or
                                   60 Hz +/- 2 Hz.
                                   This detection happens when the VIP starts.
07897073EN01-15                                                                                                          39
Instructions for putting into operation the protection relay for circuit- breaker           RM6 - Instructions for use
Operating Instructions
Operating and Viewing Cubicle Condition
Description
A: earthing switch operating shaft                                                  A   E
B: switch function operating shaft
C: fuse-switch combination function operating shaft
D: position indicator
E: fuse-switch combination function opening pushbutton
                                                         D
F: padlocking handle
                                                         B
                                                                                                                    C
40                                                                                                07897073EN01-15
                                      -100 mbar       Filling     +500 mbar
RM6 - Instructions for use                           pressure                                 Operating instructions
                                                      0.2 bar
                                                     +40°
                                                     +20°
                                                      0°
-25°
b If the needle is in the green zone, RM6 unit can be operated normally.
                                                       +40°
                                                       +20°
                                                        0°
-25°
b If the needle is in the red zone, the RM6 pressure is too low to operate.
                                                                       WARNING
                                HAZARD OF ELECTRIC
                                             +40°
                                                   SHOCK, EXPLOSION, OR ARC FLASH
                                ● DO NOT make any
                                               +20°operation on RM6.
                                                  0° Schneider Electric service center.
                                ● Contact immediately
                                                   -25° instructions could result in death or serious injury.
                                Failure to follow these
07897073EN01-15                                                                                                       41
Operating instructions                                                                              RM6 - Instructions for use
Pressure Check
Press the "DENSITY CHECK" button.
The LCD screen displays:
                                          b Case 1: OK
                                          The RM6 unit is in normal operational status (ready for energizing).
                                          b Case 2: LOW / OK
                                          The RM6 unit is in degraded operational status.
                                          Replacement need to be planned.
                                          Can stay energized and can be operated.
                                                                            WARNING
                                           HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                           If the LCD screen of the pressure switch displays VERY LOW / NOT OK:
                                           ● Do not make any operation on RM6.
                                           ● Contact immediately Schneider Electric service center.
                                           Failure to follow these instructions can result in death or serious injury.
42                                                                                                          07897073EN01-15
RM6 - Instructions for use                                                                         Operating instructions
Operating Service
Closing a Switch
Initial state:
b switch open
b earthing switch open
                                   Lift the operating shaft protective cover. Activate the switch operating mechanism to
                                   the right. The indicator moves to the closed position, and access to the earthing switch
                                   operating shaft is blocked.
Opening a Switch
Initial state:
b switch closed
b earthing switch open
                                   Activate the switch operating mechanism to the left. The indicator moves to the open
                                   position, and access to the earthing switch operating shaft is released.
                                   Lift the operating shaft protective cover. Move aside the pallet with the end of the lever,
                                   then activate the earthing switch operating mechanism to the right. The indicator
                                   moves to the earth position and access to the main switch operating shaft is blocked.
                                                                       CAUTION
                                    HAZARD OF EQUIPMENT AGEING
                                    Do not close the earthing switch when the incoming line is powered on.
                                    Failure to follow these instructions can result in injury or equipment damage.
07897073EN01-15                                                                                                            43
Operating instructions                                                                             RM6 - Instructions for use
                                        Move aside the pallet with the end of the lever, then activate the switch operating
                                        mechanism to the left. The indicator moves to the open position, and access to the
                                        switch or circuit-breaker operating shaft is released.
                                        Lift the operating shaft protective cover. Activate the switch operating mechanism to
                                        the right. The indicator moves to the closed position, and access to the earthing switch
                                        is blocked.
                                                                           CAUTION
                                         HAZARD OF EQUIPMENT AGEING
                                         Energize the undervoltage coil before operating the switch.
                                         Failure to follow these instructions can result in injury or equipment damage.
Initial state:
b circuit-breaker or fuse-switch open
b earthing switch open
Operating Safety
44                                                                                                          07897073EN01-15
RM6 - Instructions for use                                                                        Operating instructions
Key-locking (optional)
                                    The switches and the circuit-breaker are locked in the open position. The earthing
                                    switches are locked in position:
                                    bb open
                                    bb open/closed
                                    There are various possible locking diagrams.
                                    bb network switch and network outgoing circuit-breaker:
                                    □□ semi-crossed locking
                                    □□ crossed locking
                                    bb transformer feeder:
                                    □□ RM6 / transformer
                                    □□ RM6 / low voltage
                                    □□ RM6 / transformer / low voltage
Padlocking
Operating Shaft Padlocking Handle
                                    Switch and earthing switch with a degree of protection IP3X, fit a padlock
                                    6 mm < handle diameter < 8 mm.
07897073EN01-15                                                                                                          45
Operating instructions                                                                                           RM6 - Instructions for use
                                                           Fit the padlock on the opening pushbutton 6 mm < handle diameter < 8 mm.
                                                           A: fuse-switch combined function or circuit-breaker opening pushbutton.
Motorization Lock
B: circuit-breaker motorized                                                                                                          B
C: position of the switch
                                                                                                                     VERSION NEUTRALISEE
                                                                                                                    NEUTRALIZED VERSION
                                                                                     ON
                                                                                                              OFF
                                                                                                    C
OFF
Padlocking the Operating Shafts of the Switch with the Operating Mechanism Front Plate
Removed
Fit a padlock 6 mm < handle diameter < 8 mm in one of
the 2 marked holes.
Padlocking the Operating Shafts of the Circuit-Breaker with the Operating Mechanism
Front Plate Removed
                                                                                                                             A
Fit a padlock 6 mm < handle diameter < 8 mm in one of
the 2 marked holes.
46                                                                                                                       07897073EN01-15
RM6 - Instructions for use                                                                                          Operating instructions
L1 L2 L3
LV COMPARTMENT
MV COMPARTMENT
07897073EN01-15                                                                                                                            47
Operating instructions                                                                                    RM6 - Instructions for use
MV COMPARTMENT LV COMPARTMENT
     L3 L2 L1
                                                                      SC150
                S1                                      1       1
                                                                      L1
           S1   S2                                      2       2
                                                                      L2
      S1 S2                                             3       3
                                                                         CT
                                                                      L3 SW1-4
      S2                                                4       4
                                                                      Com I
                                                        5       5
                                                                      Com I0
                                                        6       6
                                                                      I0
                                                                                                                1    2   3    4   5   6
CT 0,5 Coil
already installed                                                       Additional cables                                    SC150 / RTU
LV COMPARTMENT
                                                                                     DANGER
                                                  HAZARD OF ELECTRIC SHOCK
                                                  The CT 0.5 Coil cable must always be connected to bridges or SC150 / RTU when
                                                  the cubicle is energized.
                                                  Failure to follow these instructions will result in death or serious injury.
48                                                                                                                  07897073EN01-15
RM6 - Instructions for use                                                                               Operating instructions
MV COMPARTMENT LV COMPARTMENT
   L3 L2 L1
                                                                 SC150
                 S1                               1       1
                                                                 L1
          S1     S2                               2       2
                                                                 L2
     S1 S2                                        3       3
                                                                    CT
                                                                 L3 SW1-4
    S2                                            4       4
                                                                 Com I
                                                  5        5
                                                                 Com I0
                                                  6       6
                                                                 I0
                                                                                                            1   2   3    4   5   6
Split coil
not provided in the kit                                            Additional cables                                    SC150 / RTU
LV COMPARTMENT
MV COMPARTMENT
07897073EN01-15                                                                                                                      49
Operating instructions                                                                         RM6 - Instructions for use
                                                                    NOTICE
                                     HAZARD OF EQUIPMENT DAMAGE
                                     DO NOT remove the pre-cut part directly on the cubicle.
                                     Failure to follow these instructions can result in equipment damage.
                                             INFORMATION
                                             Remove only the necessary pre-cut part, depending on the width of
                                             the LV cabinet.
50                                                                                                   07897073EN01-15
RM6 - Instructions for use                                                                Operating instructions
                                                               CAUTION
                              HAZARD OF CUT
                              ● Be careful, the edges of the cut can be sharp.
                              ● Apply appropriate Personal Protective Equipment (PPE) and follow safe work
                                practices.
                              Failure to follow these instructions can result in injury or equipment damage
07897073EN01-15                                                                                               51
Operating instructions                                                                                                                          RM6 - Instructions for use
                                                                               If it is impossible to install the CL110 sensors on the left function of the RMU,
               RM6 – CL110 sensors                                             they can be installed on the right function.
                                                                                                                     Label Size : 90 x 114 mm
               Label size 90 x 114 mm                                                                                Scale 1
               Scale 1                                                                                                                              C
CL110 kit reference: MFR57685
A: Positioning label                                                      A
B: CL110 sensor n°1
C: CL110 sensor n°2 in its support
                                                                                                        DANGER
                                                                                               HAZARD OF ELECTRIC SHOCK,
                                                                                               EXPLOSION, OR ARC FLASH
                                                                                               Keep the environmental monitoring
                                                                                               sensors only in the position defined.
                                                                                               Failure to follow these instructions
                                                                                               will result in death or serious injury.
52                                                                                                                                                    07897073EN01-15
RM6 - Instructions for use                                        Operating instructions
                                                           65±5
                                                   400±5
                                                   10±5
07897073EN01-15                                                                      53
Operating instructions                                                                                   RM6 - Instructions for use
24 25 26
Flooding Option
Installation Diagram
                                              Connection to HUA250 module on connector 10.
                                              Digital inputs 1: Common (+24VDC) n°1 / Digital input 4.
DI T300
                                                                         14       A2
                                              Common Pin 1
                                              HU250
                                                                                                    BU/3
                                                                        12-24V
                                                                       RSL Relay
                                                                                                0V                        Sensor
54                                                                                                             07897073EN01-15
RM6 - Instructions for use                                                                           Operating instructions
10-15 mm
07897073EN01-15                                                                                                             55
Operating instructions                                                                                   RM6 - Instructions for use
Relay
10
10
56                                                                                                              07897073EN01-15
RM6 - Instructions for use                                                                                               Operating instructions
Overcurrent Indicator
                                                          NOTE: The overcurent indicator does not apply to the RM6 Connected Advanced unit.
1 2
Operation
                                                          If the reaction current exceeds the pre-set threshold, the indicator sends an optical
                                                          signal on the faulty phase. The signal remains visible until it is manually reset.
                                                          1: Threshold overshoot optical signal, one for each phase.
                                                          2: Rotary resetting and operating test button (turn quickly).
                                                          1                                                       3
                                                                                                                  2
Operation
                                                          If the reaction current exceeds the pre-set threshold, the indicator sends an optical
                                                          signal on the faulty phase. The signal remains visible for a time that can be pre-set.
                                                          2 hours or 4 hours.
                                                          Manual resetting is possible.
                                                          1: Threshold overshoot optical signal, one for each phase.
                                                          2: Time during which the signal remains visible.
                                                              Resetting is automatic.
                                                          3: Resetting and operating test pushbutton.
07897073EN01-15                                                                                                                                    57
Operating instructions                                                              RM6 - Instructions for use
                           The Flair 21D, 22D and 23DM fault passage indicator is self-powered by the
                           measurement sensors. A minimum 2 A current is required in the MV cable to start up
                           the Flair 21D display, an energy storage guarantees a 4-hour minimum autonomy.
                           The Flair devices have an output contact for interfacing with a SCADA system.
                            Flair 22D/23DM can be connected to a voltage presence indicating system (VPIS)
                           provided with a voltage output (VPIS-VO). In this case, for greater reliability, fault
                           detection is confirmed by voltage absence without taking into account the current.
                           Flair 23DM has to be supplied from 24 Vdc to 48 Vdc for a permanent display operating
                           and for the outdoor lamp supply (with a single zero sequence CT, self powering is
                           not possible).
58                                                                                         07897073EN01-15
RM6 - Instructions for use                                                                        Operating instructions
Maximeter Mode
                               To access the maximeter function, press once the “Imax.” button.
                               For each phase, an indication of the maximum load currents since the last reset is
                               displayed.
                               Example:
                               for a maximum current of 500 A in phase 1:            then          ,
                               followed by L2 and L3.
                               Event B
                               The line current disappears (or absence of U with VPIS-VO option, on Flair
                               22D/23DM).
                               Fault indication is active when A is followed by B within a lapse of time of less than
                               70 s.
                               For these 2 types of faults, the indicator lamp remains flashing until it is reset (Reset),
                               which can be achieved by:
                               bb current recovery > 70 s, configurable time delay on Flair 22D/23DM (Reset active if
                               “Automatic reset” is not on “OFF”);
                               bb U recovery, if VPIS-VO option on Flair 22D/23DM (Reset active if “Automatic reset”
                               is not on “OFF”);
                               bb end of the time delay, (4 hours on Flair 21D, configurable on Flair 22D/23DM);
                               bb a press on external Reset;
                               bb manual actuation of the “Test/Reset” button.
Maintenance
                               bb The Flair 21D fault passage indicator requires no maintenance (no electric cells or
                               batteries to be changed regularly).
                               bb The lithium battery of the Flair 22D indicator should be changed about every
                               15 years (For the battery replacement process, call your sales representative
                               who will put you in contact with the closest Schneider Electric group service
                               centre. You can log on to: www.schneider-electric.com).
                               bb The lithium battery of the BVP option (external indicator unit with incorporated
                               battery) is to be changed every 15 years.
07897073EN01-15                                                                                                         59
Operating instructions                                                                          RM6 - Instructions for use
Settings
                                    The Flair devices (>2010) are a fault passage indicator without settings (automatic
                                    mode).
                                    However, it is possible to perform specific override settings.
                                    In manual mode, settings are made:
                                    bb using the 3 buttons located under the display (Flair 22D/23DM),
                                    bb by micro-switches (drawing opposite) (Flair 21D). The changes are taken into
                                    account after a press on the “Test/Reset” button.
In AUTO mode I>; I0>, the manual settings are not active.
Test Mode
                                    bb A press on the “Test/Reset” button activates Test mode.
                                    bb The indicator lamp      flashes, and the BVP and the “OUT” output are activated
                                    until the end of the test.
                                    bb The display successively shows:           and          and          (software
                                    version).
                                    bb Then, all parameters followed by their values scroll and the indicator returns to
                                    mode ammeter 10 s after displaying the last value (pressing “Test/Reset” to return
                                    immediately to the ammeter mode).
Setting Parameter Scrolling Sequence in Test Mode for Flair 21D (automatic on test mode)
                                    Setting of        Network     Imax threshold      Zero sequence         Timer reset
                                    automatic fault   frequency   “I>”                threshold “Io>“
                                    detection (*)                 (OverCurrent) (A)   (Earth Fault) (A)
Ammeter mode
                                                                                                                     10 s or
                                                                                                                   “Test/Rest”
                                    When “Auto” is “ON”, Flair 21D uses the following values for fault detection:
                                    bb frequency = self-detection
                                    bb zero sequence threshold = automatic fault detection for any fault > 20 A
                                    bb Imax threshold = automatic fault detection for any fault > 200 A
                                    bb acknowledge time = 40 ms
                                    bb Inrush = 3 s
                                    bb CT type = CT1 ( can be changed to CT2 by actualing the buttoms)
                                    bb Automatic reset = 70 s (if automatic reset =on)
                                    bb Timer reset = 4h
60                                                                                                        07897073EN01-15
RM6 - Instructions for use                                                                                                    Operating instructions
CT type or
                                                         Acknowledge time                                          to
                                                         (Fault duration) (ms)
Inrush (s) or
Fault VALidation or or
10 s Ampermeter Mode
07897073EN01-15                                                                                                                                     61
Operating instructions                                                                                                   RM6 - Instructions for use
Connection
Connection of CTs to the 3 MV cables
bb Cable length: 3 m max.
                                                                                                                                        BVP :
bb Cross section: max. 1.5 mm2                                                                                                          External indicator
bb CTR2200: mounting without common point (6 wires)                                                                                     unit with
bb MF1: mounting with or without common point (4 or 6                                                                                   incorporated battery
wires)                                                                                             CTs connection
                                                                                                     Common
                                                                                                       point
                                                                                                                                 BVE:
                                                                                                                                 External indicator
                                                                                                                                 unit
                                                                                                                                  SCADA
                                                                                                                                  output
VPIS-Vo
                                                                                                   Common
                                                                                                     point
Type C mouting ’single zero sequence CT’possible only with flair 23DV
62                                                                                                                                  07897073EN01-15
RM6 - Instructions for use                                                                                          Operating instructions
Ammeter
                                                NOTE: The Amp 21D ammeter does not apply to the RM6 Connected Advanced unit.
                                                The Amp 21D is an ammeter, for cubicle, automatic and self-powered. The Amp 21D
                                                comes into operation whenever the current is greater than 3 A on the network.
Test
                                                  L1
                                                                                                               Test button
                                                  L2
                                                                                A
                                                                                        I max.
                                                  L3
                                                                                                               I max. button
                                                                                                 Easergy
                                                                                                 Amp21D
                                                                                                 EMS58401
Standard Operating
Measuring mode
                                                Equipment’s standard operating mode.
                                                The AMP 21D ammeter displays in succession, by scrolling, the currents on phases
                                                L1, L2 and L3, and saves to memory the maximum values.
CURRENT
Maximeter mode
                                                A press on the “I max.” button activates the Maximeter mode. This mode allows display
                                                of the I maximum values occurring on the 3 network phases since the previous
                                                initialization.
PRESS                                                                                                                           Measuring
on I max                                                                                                                        mode
               Max.L1        Max. value L1    Max.L2         Max. value L2           Max.L3                  Max. value L3
                                                At the end of the maximeters’display cycle, the Amp 21D automatically returns to
                                                Measuring mode. The maximeter is reset by simultaneously pressing the “Test” and “I
                                                max.” buttons.
Test mode
                                                                                       Press on
                                                                                        Test
                                                Choice of CT type:
                                                bb the CT1 option corresponds to ( ref.59925) phase CTs;
                                                bb the CT2 option corresponds to ( ref.59963) phase CTs;
                                                bb factory setting: CT1.
07897073EN01-15                                                                                                                        63
Operating instructions                                                                 RM6 - Instructions for use
CT connection
                          Assembly
                          6 wires
                                                               Common
                          CTR2200 or MF1                       point                                   Assembly
                                                                                                       4 wires
                          phase CTs
                                                                                                       MF1 phase CTs
64                                                                                              07897073EN01-15
RM6 - Instructions for use                                                                                                  Operating instructions
Operation
                                                              Calibration
                                                              At power up, the VD23 automatically detects voltage presence and the network
                                                              frequency, and then performs self-calibration.
                                                                         : calibration performed
                                                              Measuring mode
                                                              3 seconds after calibration, the VD23 displays, by scrolling, the percentages of the
                                                              nominal voltage detected on each phase.
3s 3s 3s 3s
Detection Sequence
Configuration: voltages V1,V2,V3, direct mode
R1: terminal      = relay rest position: voltage loss on at                                          threshold paramater
least one of the phases
R2: terminal      = relay rest position: voltage presence
on at least one of the phases
A configurable time delay is applied for control of R1
and R2:
T12 = time delay for R1 changeover upon voltage loss
T11 = time delay for R1 changeover upon voltage
recovery
T21 = time delay for R2 changeover upon voltage loss
T22 = time delay for R2 changeover upon voltage
recovery
                                                                 Indicator
                                                                 Indicator
07897073EN01-15                                                                                                                                      65
Operating instructions                                                                                                          RM6 - Instructions for use
ou
                      3 4 5 6
       SW 1                                 V1+V2+V3+V0
                                            V1.V2.V3.V0
       SW 2
                                   R1
VD23
                                                                      3 4 5 6                                       3 4 5 6
       SW 1                                                                                     U12+U13+U23                                U12+U13+U23
                                                                                                U12.U13.U23.                               U12.U13.U23.
       SW 2
                                                                                       R1
66                                                                                                                                      07897073EN01-15
RM6 - Instructions for use                                                                        Operating instructions
                                   Open the switch and close the earthing switch. To remove an access panel, remove
                                   the 2 upper screws, lift and pull towards you.
                                                                         DANGER
                                    HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                    ● The complete switchboard (all the RM6 connected together) must be
                                      de-energized to connect O or T function.
                                    ● Open all switches connected to the busbar.
                                    ● Close all associated earthing switches.
                                    Failure to follow these instructions will result in death or serious injury.
                                   Optionally
                                   Switch and circuit-breaker closing is inhibited if the access panel is removed.
07897073EN01-15                                                                                                            67
Operating instructions                                                                     RM6 - Instructions for use
                                                                       DANGER
                                   HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                                   ● Before any intervention inside the DE-Mt cubicle, be sure all upstream
                                     connection(s) are locked-out in OPEN position.
                                   ● Before any intervention inside the DE-Mt cubicle, be sure all downstream
                                     connection(s) are locked-out in OPEN position.
                                   ● Before any intervention inside the DE-Mt cubicle, be sure the 3 busbars are
                                     grounded, via a temporary connection or via an earthing switch (upstream or
                                     downstream).
                                   Failure to follow these instructions will result in death or serious injury.
                                        Optional:
                                   a key lock exists
                                      (example B)
68                                                                                                07897073EN01-15
RM6 - Instructions for use                                                                      Preventive maintenance
Preventive Maintenance
Standard Operating Conditions
Maintenance Summary Table
                                    description                   operation                     material
                                    panelling                     cleaning                      cloth
                                    earthing covers               cleaning                      sponge, clear water
Panelling
                                   Schneider Electric draws your attention to the risk of using high-pressure cleaning
                                   processes.
                                   Schneider Electric cannot therefore guarantee the reliability of equipment that has
                                   been cleaned in this manner, even if cleaning has been followed by lubrication.
                                   The main drawbacks of this process are:
                                   b deterioration due to jet pressure and impossibility of relubricating the inaccessible
                                     fixing points.
                                   b risk of overheating due to presence of solvent on the contact zones.
                                   b elimination of special protections.
Earthing Covers
                                   This operation can be performed in event of excessive soiling.
                                   Clean using a sponge and clear water. Do not use alcohol or other solvents to clean.
07897073EN01-15                                                                                                          69
Preventive maintenance                                                                                                                 RM6 - Instructions for use
Illustration for an RM6 Connected Advanced unit: Illustration for an RM6 unit:
1 1
                                 Res
                                       et
                                                                                                                                                  3
              L1
                   L2
                                                                                2                                                     3
                        L3
L1
                                                                   3                                                          4
                                                 L2
L3
L2
L3
                                                                                                                    5
                                                           4
                             5
70                                                                                                                                             07897073EN01-15
RM6 - Instructions for use                                                                   Corrective maintenance
Corrective Maintenance
Foreword
                                The corrective maintenance operations enable replacement of subassemblies.
                                The operations listed in the following summarising table can be performed by the
                                customer or by Schneider Electric after-sales representatives.
                                After each operation, perform the electrical tests according to current standards.
07897073EN01-15                                                                                                      71
Corrective maintenance                                                                  RM6 - Instructions for use
  B       Replacing a Fuse
                             Standard IEC 252 paragraph 23.2 recommends replacement of the 3 HV fuses after
                             blowing of one of the fuses.
Removal
                             Before performing the following operations, check that the earthing switch is closed.
                             To remove the cover, remove the 2 screws on each side of the cover then lift it and pull
                             it towards you. The instructions are visible on the cover.
                                       INFORMATION
                                       In the case of an internal arc station, it is possible to disassemble the
                                       deflector to have a better accessibility.
                                       Therefore, remove the 2 screws on each side, then pull it towards you.
                             Release the plug and push the extraction handle manually to unlock the plug (tap with
                             the palm of your hand to separate the seal from the plug if necessary). Move the plug
                             up to the limit stop, swivel it towards the left to remove it.
72                                                                                              07897073EN01-15
RM6 - Instructions for use                                                                       Corrective maintenance
Recover the centring device at the top of the fuse. Extract the fuse.
                                  Loosen the fuse using an Allen wrench n°5. Let the plug hang down from its supporting
                                  string.
                                  If the fuse plugs are dirty, clean the conical surface using silicon oil. Then wipe it down
                                  with a clean cloth to dry it.
                                  Talc the clean surface with natural talc to avoid clinging between the plug and fuse
                                  compartment. The surface must appear smooth without lumps.
07897073EN01-15                                                                                                            73
Corrective maintenance                                                                     RM6 - Instructions for use
                              Insert the fuse in the compartment. Fit the centring device on the fuse. Insert the plug
                              pins in the plinth and turn clockwise.
Striker pin
                              The end of the fuse equipped with the striker is marked. The technical data and
                              mounting direction of the fuse are printed on the body (striker facing upwards).
                              Fix the fuse on the plug using an Allen wrench n°5 and insert the fuse in the
                              compartment. Tightening torque: 15 N.m
                              Insert the plug and fuse assembly in the compartment. Insert the plug pins in the plinth
                              and turn clockwise.
74                                                                                                07897073EN01-15
RM6 - Instructions for use                                                                Corrective maintenance
                             Make sure that the handle trunnions are inserted in the plinth slots and lock the plug.
                             Never use the operating lever to lock the plug.
                             For replacement of a fuse that has struck, press the switch to put it back in position.
07897073EN01-15                                                                                                    75
Corrective maintenance                                                                                                                                              RM6 - Instructions for use
                                                                                                                              3
                                                                                                     1
                               1 - Unscrew the 2 screws of the fuse compartment cover then remove it by pulling it
                               towards you.
                               2 - Remove the LV connection access trunking (6 screws HM6x16).
                               3 - Remove the mimic panel front plate (4 screws HM6x16).
                                                                                                                                                                                                                              SF6 DENSITY
                                                                                                                                                                                                                       ELECTRONSYSTEM
                                                                                                                        OFF
                                                                                                                                                                                                                            DO NOT
                                             OK
ON
OK
ON
OK
ON
                                                                                                                                                                                                                           OPERATE
                                                                                                                                                                                                             GLI/LCD
                                                                                                                                                                                                                         VERY LOW
                                                             L1   L2   L3                                                     L1   L2   L3                                   L1   L2   L3                                NOT   OK
                                                                                                                                                                                                                       TEST          DENSITY CHECK
Reset
                                                                                                                              L3
                                              L1        L2                         L3   L1               L2                                               L1            L2                              L3
76                                                                                                                                                                                     07897073EN01-15
RM6 - Instructions for use                                                              Corrective maintenance
                             Remove the 3 nuts fixing the motor support. Disconnect the motor supply wiring.
                             Remove the motor support by pulling it backwards.
Fitting
                             Fit the new motor in the opposite order to removal.
                             Tightening torque: 28 N.m.
                             Fit the trunking and the cover.
07897073EN01-15                                                                                                77
Corrective maintenance                                                                        RM6 - Instructions for use
Access to subassembly
using switch function
Example: for an IPI substation.
bb Open switch
bb Closed earthing switch
                                                                                   3
                                                                         1
78                                                                                                       07897073EN01-15
RM6 - Instructions for use                                                                        Corrective maintenance
Recover the 2 relays, then the 2 fuses on the front plate to be replaced.
RO3
                                     Using a wire cutter, locate the diodes and the jumper cable to be eliminated
                                     (6 anchoring points). The components cannot be reused.
07897073EN01-15                                                                                                             79
Corrective maintenance                                                                         RM6 - Instructions for use
                                      Reassemble the 2 relays C, then the 2 fuses B. Install the new front plate.
                                      Reconnect the wiring at the printed-circuit terminal block and customer power supply
                                      level A.
80                                                                                                    07897073EN01-15
RM6 - Instructions for use                                                                     Corrective maintenance
                                                                                                         S1
                                                    A
                                   Remove the position indicator A. Remove interlocking B (elastic ring and spring).
                                   Remove contact support S1 without disconnecting the wiring.
                                                                                  S2      S3    S41     S5
                                                  S3
                                   Remove contact S3 without disconnecting the wiring. Remove the contact support
                                   S2, S4, S5, S6 and S7 without disconnecting the wiring.
13 Nm
S1
                                   Fit contacts S1 to S7 to replace the former contacts. Fit the position indicator and
                                   interlocking. Disconnect the contact wiring S1 disassembled, and connect it to the new
                                   contact. Repeat this operation for all the contacts (S2 to S7).
07897073EN01-15                                                                                                        81
Corrective maintenance                                                                     RM6 - Instructions for use
SF6 characteristics                The mass of SF6 is mentioned on a specific label stuck near the filling point.
                                   GWP (Global Warming Potential) of SF6 = 22800, 1 kg of SF6 is equivalent to ~23 tons
                                   of CO2.
Process at end-of-life
                                   Prior to disposal of the equipment at end-of-life, the SF6 gas must be recovered in
                                   order for it to be recycled, reclaimed or destroyed.
                                   In any case SF6 must not be released to the atmosphere.
                                   According to European regulation (EU 517/2004), people recovering SF6 from this
                                   equipment must be certified.
                                   The minimum SF6 recovery vacuum pressure must be < 20 mbar.
                                   The SF6 recovered must be weighed. The mass of SF6 recovered must be the mass
                                   indicated on the label.
                                   Schneider Electric offers a complete service to dismantle and recycle Medium Voltage
                                   equipment and SF6 gas at end-of-life. This service is compliant with IEC 62271-4 and
                                   conforms to local regulations.