KITZ Interface Unit Guide
KITZ Interface Unit Guide
         SAFETY SECTION                             7
1.       INTRODUCTION                              11
2.       HANDLING AND INSTALLATION                 11
2.1      General considerations                    11
2.2.     Electrostatic discharge (ESD)             11
2.3.     Unpacking                                 12
2.4.     Storage                                   12
3.       KITZ FEATURES                             12
4.       CONNECTION                                13
4.1      RS232 (IEC-870) connection                17
4.2      K-Bus connection                          18
5.       KITZ OPTION SWITCHES                      19
5.1      Option switch settings                    20
5.2      Data rate selection                       20
5.3      RS232 (IEC-870) frame parity              20
5.4      Time tagging of K-Bus messages            21
5.5      Modem control                             21
6.       KITZ LED INDICATIONS                      22
7.       PROTOCOL CONVERSION                       23
7.1      Message format                            23
7.2      Message validation                        23
7.3      Message time-out                          24
7.4      Conversion sequences                      24
7.5      Receive message buffering                 24
8.       KITZ ADDITIONAL FEATURES                  25
8.1      Real time clock (RTC) synchronisation     25
9.       TECHNICAL DATA                            26
9.1      Ratings – auxiliary supply                26
9.2      Burden – auxiliary supply                 26
9.3      Fuse Ratings                              26
9.4      Accuracy                                  26
9.5      Operation indicator                       26
9.6      Communication ports                       27
9.7      Message buffers                           28
9.8      High voltage withstand                    28
9.9      Environmental                             29
9.10     Mechanical tests                          29
9.10.1   Vibration IEC 255-21-1 Class I            29
9.10.2   Shock and bump IEC 255-21-2 Class I       29
9.10.3   Seismic IEC 255-21-3 Class I              29
9.11     Enclosure protection IEC529 IP20          29
10.      COMMISSIONING                             30
10.1     Commissioning preliminaries               30
10.2     Auxiliary supply tests                    31
10.3     Settings                                  32
                                          Page 5
11.    PROBLEM SOLVING                                                              32
11.1   Green supply indication led is off                                           32
11.2   Fuse blows on power-up (KITZ 101 only).                                      32
11.3   IEC 870 receive indication is off when communicating with a master station   32
11.4   K-Bus receive indication is off when communicating with a master station
       (and K relay)                                                                32
11.5   Slow communications response (many retries)                                  33
                                       Page 6
                               SAFETY SECTION
This Safety Section should be read before commencing any work on the equipment.
       *Note: The term earth used throughout the product documentation is the direct
              equivalent of the North American term ground.
                                         Page 7
Before energising the equipment it must be earthed using the protective earth
terminal, or the appropriate termination of the supply plug in the case of plug
connected equipment. Omitting or disconnecting the equipment earth may
cause a safety hazard.
The recommended minimum earth wire size is 2.5 mm2, unless otherwise stated
in the Technical Data section of the product documentation.
Before energising the equipment, the following should be checked:
   Voltage rating and polarity;
   CT circuit rating and integrity of connections;
   Protective fuse rating;
   Integrity of earth connection (where applicable)
Equipment operating conditions
The equipment should be operated within the specified electrical and
environmental limits.
Battery replacement
Where internal batteries are fitted they should be replaced with the
recommended type and be installed with the correct polarity, to avoid possible
damage to the equipment.
Insertion of modules and pcb cards
These must not be inserted into or withdrawn from equipment whilst it is
energised, since this may result in damage.
Current transformer circuits
Do not open the secondary circuit of a live CT since the high voltage produced
may be lethal to personnel and could damage insulation.
External resistors
Where external resistors are fitted to relays, these may present a risk of electric
shock or burns, if touched.
Insulation and dielectric strength testing
Insulation testing may leave capacitors charged up to a hazardous voltage.
At the end of each part of the test, the voltage should be gradually reduced to
zero, to discharge capacitors, before the test leads are disconnected.
Insertion and withdrawal of heavy current test plugs
When using a heavy current test plug, CT shorting links must be in place before
insertion or removal, to avoid potentially lethal voltages.
Fibre optic communication
Where fibre optic communication devices are fitted, these should not be viewed
directly. Optical power meters should be used to determine the operation or
signal level of the device.
                                  Page 8
  Decommissioning and Disposal
Decommissioning: The auxiliary supply circuit in the relay may include
                 capacitors across the supply or to earth. To avoid electric
                 shock or energy hazards, after completely isolating the
                 supplies to the relay (both poles of any dc supply), the
                 capacitors should be safely discharged via the external
                 terminals prior to decommissioning.
Disposal:          It is recommended that incineration and disposal to water
                   courses is avoided. The product should be disposed of in a
                   safe manner. Any products containing batteries should have
                   them removed before disposal, taking precautions to avoid
                   short circuits. Particular regulations within the country of
                   operation, may apply to the disposal of lithium batteries.
                               Page 9
Technical Specifications
Protective fuse rating
Refer to Section 9. Technical Data, item 9.3 Fuse Ratings.
                               Page 10
Section 1.    INTRODUCTION
                                         Page 11
        If you are making measurements on the internal electronic circuitry of an
        equipment in service, it is preferable that you are earthed to the case with a
        conductive wrist strap. Wrist straps should have a resistance to ground between
        500k-10M ohms. If a wrist strap is not available, you should maintain regular
        contact with the case to prevent a build-up of static. Instrumentation which may
        be used for making measurements should be earthed to the case whenever
        possible.
        More information on safe working procedures for all electronic equipment can
        be found in BS 5783 and IEC 147-OF. It is strongly recommended that detailed
        investigations on electronic circuitry, or modification work, should be carried out
        in a Special Handling Area such as described in the above-mentioned BS and
        IEC documents.
2.3.    Unpacking
        Care must be taken when unpacking and installing the unit to prevent damage.
2.4.    Storage
        If the KITZ unit is not to be installed immediately upon receipt it should be stored
        in a place free from dust and moisture in the original carton. Where de-
        humidifier bags have been included in the packing they should be retained.
        The action of the de-humidifier crystals will be impaired if the bag has been
        exposed to ambient conditions and may be restored by gently heating the bag
        for about an hour, prior to replacing it in the carton.
        Dust which collects on a carton may, on subsequent unpacking, find its way into
        the unit; in damp conditions the carton and packing may become impregnated
        with moisture and the de-humidifier will lose its efficiency.
        Storage temperature –25°C to +70°C.
                                        Page 12
                                                                                                                                                                                                                                               Section 4.
                                                                   Connection to K-Bus
                                                                                                              K-Bus to IEC 870 interface
                                                                                                              (KITZ 101)
                                                                                                                                                                                                                                               CONNECTION
Page 13
                                                                                                     US   2
                                                                                                   KB
                                                                                                     1
                                     PC
                                                                                                                                             Mains cable
                                                                                                                          RS232 link
                                                                                                                          serial port
                                                                                     K-Bus
                                                                              to terminals 1 & 2
                                                                                   screen to
                                                                                                                                  US    2
                                                                                                                                KB
                                                                                                                                   1
                                          K Range relays
                                                                                                                             Detail of earth link
                                                                                                                             & external resistor when fitted
                                                                                                                                                               A typical application connection arrangement for the KITZ 101 is shown below:
Page 14
                                                                                                          US   2
                                                                                                       KB
                                                                                                          1
                                           PC
                                                                                                                         RS232 link                 Auxiliary supply
                                                                                                                         serial port
                                                                                         K-Bus
                                                                                  to terminals 1 & 2
                                                                                       screen to
                                                                                                                                         US     2
                                                                                                                                       KB
                                                                                                                                            1
                                                K Range relays
                                                                                                                                  Detail of earth link
                                                                                                                                  & external resistor when fitted
Page 15
                                      internally connected                                                  assemblies FT 0113 001 supplied with
                                                                                                            K-Bus/IEC870 interface
                                                       IBM or compatible PC
                                                   (for pin assignment numbers
                                                            see table 1)
                                                                                                                                                   A schematic representation of a typical application connection arrangement is
          Figure 2a: KITZ 101 IEC-870 (RS232) port to PC serial port connections.
                                                                                      Typical      Typical                               Typical
                                                                                     K Range      K Range                               K Range
                                                                                       Relay        Relay                                 Relay
                                                KITZ 102
                                         K-Bus/IEC870 Interface
                Auxiliary supply
                      dc voltage
                                                                * 150R              Terminals
                                                            2            1                54          54                                 54 * 150R
                                      2 TX
                                      3 RX
                                      7 Signal ground                                    56           56                                 56
                                      1 Protective ground
                                                                                    Screen Link
                                           All     points are                                                * 2 off externally mounted resistor
Page 16
                                         internally connected                                                  assemblies FT 0113 001 supplied with
                                                                                                               K-Bus/IEC870 interface
                                                          IBM or compatible PC
                                                      (for pin assignment numbers
                                                               see table 1)
          Figure 2b: KITZ 102 IEC-870 (RS232) port to PC serial port connections.
4.1     RS232 (IEC-870) connection
4.1.1   Recommended cable
        A standard PC serial port interface cable (with the connections listed in Table 1)
        should be used. It is essential that the cable screen is earthed at one end to
        ensure adequate screening. The connectors should be screw-locked to the KITZ
        and the PC.
4.1.2   Cable length
        The maximum recommended length of cable from the IEC-870 Communications
        port is 15 metres (50 feet) or 2500 pF total cable capacitance. For longer
        distance communication on the IEC-870 port an external RS485 interface may
        be required.
4.1.3   Data rates
        The maximum data communication rate specified in the RS232-c standard is
        20 kbits/s. The KITZ unit will support faster communication data rates (up to
        115.2 kbits/s) for use with development tools such as K-Spy.
        The following table shows the connections required to interface a KITZ to a user
        PC serial data port. These connections are for guidance only and reference
        should be made to the PC user manual.
        Note that the terms “Receive Data” and “Transmit Data” (in Tables 1 and 2)
        refer to the named connector and not to a nominated end.
                                       Page 17
        The following table lists the complete (Modem Control) pin functions of the
        KITZ and the PC:
                                        Page 18
4.2.5   Maximum cable (spur) length
        The maximum cable length is 1000m.
4.2.6   Maximum slave devices per spur
        The maximum number of devices per spur is 32.
                                  K-Bus                 No
                           SCN      1     2             Vx   V~
Figure 3a: KITZ 101 front plate layout and rear connections.
                                                                               0
                                                                                   01234567
                                  K-Bus             No
                            SCN     1     2         Vx       V
                                                                                     AUXILIARY SUPPLY
                                                                                        VOLTAGE
Figure 3b: KITZ 102 front plate layout and rear connections.
                                              Page 19
5.1   Option switch settings
      The option switches on the KITZ front plate allow the user to configure the KITZ to
      suit the application requirements.
      The following table lists the KITZ option switch functions.
                                         Page 20
      The normal operational mode of the KITZ unit uses the 11 bit frame format.
      However, some equipment to which the KITZ unit is to be interfaced can only
      support the 10 bit frame format (eg. most modems).
      The use of the 10 bit frame format will result in a less secure communications
      protocol which does not meet the IEC-870 - 5 FT 1.2 requirements.
5.4   Time tagging of K-Bus messages
      The fifth switch (switch 4) appends an IEC-870 format time tag (using the KITZ
      RTC‘s current time) to a received K-Bus message.
      The KITZ Interface unit will insert an IEC-870 format time tag into a converted
      IEC-870 courier message if all of the following conditions apply:
      1) Switch 4 (fifth from left is set).
      2) The message contains a millisecond timer count (DTL Type 38h - 3Bh).
      3) The message contains a courier status byte (or bytes) (DTL Type 5Ch - 5Fh).
      4) An IEC-870 time tag (DTL Type 3Ch - 3Fh) is not already contained before
         the status byte within the message.
      The IEC-870 time tag will be added after the millisecond count.
      The time tag format is shown below.
      The IEC-870 time tag value is the time of reception of the first byte of the K-Bus
      message.
      If switch 4 is not set, the millisecond counter of the relay reply will be adjusted to
      take account of protocol conversion delays.
5.5   Modem control
      The Modem Set-up and Modem Present switches control the KITZ unit mode of
      operation when connected to a modem. This is shown in the following table:
        The K-Bus frame is based upon the ISO High level Data Link Control (HDLC)
        protocol. This is a bit-oriented protocol and eliminates much of the control
        overhead associated with byte-oriented protocols. The information field of the
        HDLC frame is totally transparent and the information can take on any form and
        contain any binary bit combination.
        The IEC-870 Message format as used by a PC-based K Range master station is
        shown below:
        For further details of the IEC-870 - 5 FT1.2 message format see the appropriate
        IEC specification.
7.2     Message validation
        Message validation takes place during and after message reception.
7.2.1   K-Bus message validation
        The framing of the K-Bus message must be correct (HDLC Start and Stop flags
        present).
        At the end of a frame:
        a)      CRC (HDLC)
        b)      Data overrun
        c)      Residue (HDLC information field is an exact number of bytes)
        d)      Correct message length (matches received message data)
        During a frame:
        a)      Character time-out
        b)      Receive Buffer overflow
        c)      Message is too long
7.2.2   IEC message validation
        The framing of the message must be correct for IEC-870 - 5 FT1.2.
        At the start of a frame:
        a)      A correct header frame must be present (2 Starts + matching lengths).
                                             Page 23
        b)   A time of greater than 33 bit transmissions (at current baud rate) must have
             elapsed since the last erroneous message
        At the end of a frame:
        a)   Checksum is correct
        b)   A STOP character must be present.
        During a frame:
        a)   Framing error
        b)   Overrun error
        c)   Character parity (if enabled)
        d)   Character time-out
        e)   Receive Buffer overflow
        f)   Message is too long
7.3     Message time-out
        The KITZ unit uses timers to speed-up re-initialisation of message reception and
        transmission when a message timing error occurs (on the K-Bus or IEC-870 port).
7.3.1   K-Bus timers
        The received K-Bus message is checked for character gaps. The timer value is
        2ms between characters.
        The transmitted K-Bus message cannot take greater than 500ms to transmit.
7.3.2   RS232 (IEC-870) timers
        These timer values are dependent on the data rate used (the data rate switch
        position determines the timer value used).
        The received IEC-870 message is checked for character gaps within the
        message. The maximum gap allowable is 33 bits (at current data rate).
        The transmitted IEC-870 message is not allowed to take greater than a
        5,500 bit time period (at current data rate) to transmit.
        Note: IEC-870 - 5 FT1.2 states that data transmitted in this format should not
              have inter-character gaps. The KITZ unit transmits using this format, but
              the receiver allows gaps as mentioned above. The 3 byte (33 bit) delay
              after message error is adhered to.
7.4     Conversion sequences
        When a valid message is received on one channel (either K-Bus or IEC-870),
        the following operation occurs:
        (1) the other channels receiver is disabled.
        (2) the message is converted (IEC-870 to K-Bus or K-Bus to IEC-870).
        (3) the message is transmitted on the other channel.
        (4) the other channels receiver is re-enabled.
7.5     Receive message buffering
        Under normal operating conditions the KITZ unit will not need to buffer received
        messages because the master station will send a message and then wait for a
                                        Page 24
        reply. However, if direct conversion is required message buffering will be
        inevitable. If the received message data rate is higher than the transmitted data
        rate, multiple message buffering (and eventual overflow) will occur. If the
        received message data rate is lower than (or equal to) the transmitted data, only
        one incoming message will have to be buffered while the previous message is
        being transmitted.
        The KITZ unit is capable of buffering up to 2048 bytes of message data (but not
        exceeding 64 individual messages) on one channel while transmitting data on
        the other channel. After this limit has been reached, received messages will be
        ignored until space is available in the internal buffer (ie. a complete message has
        been transmitted).
        When multiple buffering of received messages occurs, the messages will be
        converted and transmitted in the order in which they were received. The other
        channel’s receiver will not be re-enabled until after all valid messages have been
        converted and transmitted.
         Command Command IEC TIME Extended Milli-         Minutes Hour    Day    Month Year
         DTL     Set IEC          Length   seconds.
                 Time    DTL
                 (RTC)   (EXT)
         05        45        3C       07        0 - 59999 0 - 59   0 - 23 1 - 31 1 - 12 0 - 99
        The protocol converter will check the incoming IEC-870 message for a
        synchronise RTC (real time clock) command sequence and if found sets the RTC
        to the specified time.
        The ‘Synchronise RTC’ command must be the only command after the IEC control
        byte within the message, otherwise normal protocol conversion occurs.
        The RTC setting value sent by the master station should correspond to the start of
        the transmitted message (to the KITZ unit).
        If time-tagging of K-Bus messages is not required, the RTC need not be
        synchronised.
                                       Page 25
Section 9.      TECHNICAL DATA
Nominal Operative
             KITZ 101
             110/240V ac                       87 – 265V ac 50/60Hz
             KITZ 102
             24/125V ac/dc                     19 –150V dc
                                               50 –133V ac 50/60Hz
             48/250V ac/dc                     33 – 300V dc
                                               87 – 265V ac 50/60Hz
                                        Page 26
9.6     Communication ports
9.6.1   K-Bus port
        Language:                                           COURIER
        Transmission:                                       Synchronous - RS485 voltage levels
        Transmission Coding:                                Biphase space
                                                            (Differential Manchester)
        Frame Format:                                       HDLC
        Baud Rate:                                          64k/bit per second
        K-Bus Cable:                                        Screened twisted pair
        K-Bus cable length:                                 1000m of cable (maximum)
        K-Bus Loading:                                      32 units (multi-drop system)
        Isolation:                                          2kV rms for one minute
        Voltage signals
        (Based on RS485 differential voltage level):
        Unloaded driver differential output:                ±5V
        Receiver input sensitivity:                         ±200mV
                              RS485
                              Driver/Receiver                      1:1
                              Pair                                 Isolating
                                                                   Transformer
                 TxD
Tx/Rx 15V
RxD
                                                                                  Transient
                                                                                 Suppressor
                                                    7V5            7V5
                                          Interference
                                          Suppressor
                                          Zener diodes
                                                          Ground
                                                Page 27
9.6.2   IEC-870 (RS232) port
        Language:                                  COURIER
        Transmission:                              Asynchronous - RS232 voltage levels
        Transmission coding:                       NRZ
        Frame format (switch 3 = position 0):      Asynchronous - 11 bit
                                                   (1 start bit, 8 data bits, 1 parity (even)
                                                   1 stop bit)
        Frame format (switch 3 = position 1):      Asynchronous - 10 bit
                                                   (1 start bit, 8 data bits, no parity,
                                                   1 stop bit)
        Baud rate:                                 1200 to 115200 bits per second
        RS232 cable:                               RS232 serial interface lead
        RS232 cable length:                        15m of cable (maximum)
                                                   (or 2500pF total cable capacitance)
        RS232 Loading:                             2 units (point to point system)
9.7     Message buffers
        K-Bus
        Receive Data Buffer Size:                  2048 bytes or 64 messages
        IEC-870
        Receive Data Buffer Size:                  2048 bytes or 64 messages
9.8     High voltage withstand
        The high voltage withstand tests can be performed on the following independent
        circuits:
        Auxiliary supply
        K-Bus communication port
        The IEC 870 port is earthed locally and should not be tested for high voltage
        withstand. It is protected by the cable screen.
9.8.1   Dielectric test (Insulation) IEC 255-5, BS 5992-3
        2.0kV rms for one minute between all terminals wired together and case earth.
        2.0kV rms for one minute between terminals of independent circuits.
9.8.2   High voltage impulse IEC255-5, BS 5992-3
        5kV peak, 1.2/50µs, 0.5J between all terminals of independent circuits and
        terminals of independent circuits to case earth.
        0kV peak on IEC-870 port
9.8.3   High frequency disturbance IEC255-22-1, BS 142-1.4.1
        Class III 2.5kV peak between independent circuits and independent circuits
        to case.
        Class III 1.0kV between terminals of same circuit
        0kV peak on IEC-870 port
                                       Page 28
9.8.4    Electrical fast transient IEC255-22-4, BS 142-1.4.4, IEC 801-4
         Auxiliary supply                           Class III 2kV
         K-Bus communication port                   Class III 2 kV – capacitive coupling
         IEC-870 Port                               None
9.8.5    Electrostatic discharge IEC 255-22-2, IEC 801-2
         Class II 4kV – point contact discharge.
         Note: The IEC-870 port will not withstand electrostatic discharges (air or
               contact).
9.9      Environmental
9.9.1    Temperature IEC 68-2-1, BS 2011 Part 2.1A & IEC 68-2-2, BS 2011 Part 2.1B
         Storage and transit:                       –25°C to +70°C
         Operating:                                 –25°C to +55°C
9.9.2    Humidity IEC68-2-3, BS 2011 Part 2.1 Ca
         56 days at 93% relative humidity and +40°C
9.10     Mechanical tests
9.10.1   Vibration IEC 255-21-1 Class I
9.10.2   Shock and bump IEC 255-21-2 Class I
9.10.3   Seismic IEC 255-21-3 Class I
9.11     Enclosure protection IEC529 IP20
9.12     Battery
         Replacement
         See Section 11. Problem Solving.
         Disposal
         The battery should be removed from the unit and have any connection leads
         removed before disposal, taking precautions to avoid short circuits. Particular
         regulations within the country of operation may apply to the disposal of lithium
         batteries.
                                          Page 29
9.13       Model numbers
                                                  KITZ 10           X   X                AE
            Power supply
            AC only                                         1
            AC/DC                                           2
            Mounting arrangement
            Desk top                                                    X
            Back of panel                                               Y
            Auxiliary supply
            24/125V dc or 110/125V ac                                                2
            48/250V dc or 110/240V ac                                                5
Nominal Operative
            KITZ 101
            110/240V ac                             87 – 265V ac 50/60Hz
            KITZ 102
            24/125V ac/dc                           19 –150V dc
                                                    50 –133V ac 50/60Hz
            48/250V ac/dc                           33 – 300V dc
                                                    87 – 265V ac 50/60Hz
                                           Page 31
10.3   Settings
       When the KITZ interface unit is used to allow a PC (running master station
       software) to communicate with K Range relays (ie. normal operation), the
       following applies:
       Check baud rate (option switches 0-2) setting on the IEC-870 (RS232) port
       corresponds to the data communication rate of the master station. The standard
       setting is 9600 bps and the following option switch position apply:
       Option Switch 0 is set to 1 (Up)
       Option Switch 1 is set to 1 (Up)
       Option Switch 2 is set to 0 (Down)
       Option Switch 3 (RS232 (IEC870) frame format) should be set to the 0 (Down)
       position.
       Option Switch 4 (Add IEC time-tag) should be set to the 1 (Up) position.
       Option Switches 5 and 6 (Modem Present and Modem Set-up) should be set to
       the 0 (Down) position.
       Option Switch 7 (reserved) should be set to the 0 (Down) position.
       The option switch settings are applied at power-up.
       If changes are made to the settings, the auxiliary supply must be switched off.
       The unit is re-energised after at least 5 seconds.
       Common operational faults are listed in this section. The solutions offered are for
       guidance only.
11.1   Green supply indication led is off
       Check correct auxiliary supply is present (ie. no supply).
       Check fuse.
11.2   Fuse blows on power-up (KITZ 101 only).
       Check that excessive auxiliary supply voltage is not being used.
11.3   IEC 870 receive indication is off when communicating with a master station
       Check data rate selection for IEC-870 (RS232) port is identical to that of the
       master station.
       Power-down the unit and then power-up the unit to guarrantee the switch settings.
       Check master station is polling for data.
11.4   K-Bus receive indication is off when communicating with a master station
       (and K relay)
       Relay is not communicating (incorrect address/not configured etc.): refer to the
       appropriate K Range service manual.
                                       Page 32
       Incorrect connection and/or termination resistor fitted to K-Bus of wrong value or
       missing altogether.
11.5   Slow communications response (many retries)
       No termination resistor fitted to K-Bus, or incorrect value.
11.6   Real time clock corruption
       The battery within the KITZ 101, 102 is provided to maintain the real time clock
       to the correct time following an interruption of the ac/dc voltage supply to the
       unit. Corruption of the real time clock can occur if the voltage across the battery
       drops below the accepted minimum level and an interruption in power supply
       takes place. This may be evident by invalid real time clock data within the
       Courier response message of the slave devices connected to the unit. The voltage
       across the battery should be measured with the supply voltage removed and if
       found to be less than 3.5V, the unit should be returned to GEC ALSTHOM T&D
       Protection & Control Limited for replacement of the battery.
                                       Page 33
                                          216.0
205.0
                                                                                    V~
                                                                                                             163.0
                                                                            No
                                                                            Vx      2
                                                                            K-Bus
                                                                                    1
                                                                                    SCN
       65.5    57.5
216.0
                                          205.0
                                          179.0
                                                                                          AUXILIARY SUPPLY
                                                                                             VOLTAGE
       181.0
                                                                                    V
               174.0                                                                                         163.0
                                                                             No
                                                                             Vx     2
                                                                            K-Bus
                                                                                    1
                                                                                    SCN
                                4 (Typ)
                                                                    4 off mounting lugs
57.5
                                                   Page 34
Page 35
                        GEC ALSTHOM T&D PROTECTION & CONTROL LIMITED
                              St Leonards Works, Stafford ST17 4LX, England
                 Tel: 44 (0) 1785 223251 Telex: 36240 Fax: 44 (0) 1785 212232