DESIGN OF PILE AND PILE CAP (4 GROUP) OF 800 CUM.
OHR FOR
BADURIA MUNICIPALITY,ZONE-V, DISTRICT- NORTH 24 PGS.
DESIGN OF PILE:
Design Data:
1.Total DL when Full = 16300 KN
2. Base Shear = 600 KN
3. Seismic Moment = 14840 KN-m
4. No. of Column = 10 Nos.
4a. Diameter of Column = 600 mm
4b. Size of Pedestal = 800 mm Sq. Shape
5. Radius of Column Assembly = 5.125 m
6. M.I. of Column Configuration = 37.132 M4
7. M.I Per Column C/S Area = 131.328 M2
7. Load on column:
(a) Load due to vertical load 1630.00 KN
(b) Load due to moment 579.12 KN
8.Load on farthest Column:
a) Maximum Vertical Load 2209 KN
b) Minimum Vertical Load 1051 KN
c) Horizontal Load 60 KN
Max. Vertical Load on each Column 2209 KN (Compressive)
Min. Vertical Load on each Column 1051 KN (Compressive)
Horizontal Load on each Column 60 KN (Lateral)
Pile Data (As per Soil Investigation Report & Annexure-II ):
Diameter of Pile 500 mm
Safe Vertical Load Capacity 630 KN
Safe Pull-out Capacity 541 KN
Safe Lateral Load Capacity 26.0 KN
Shaft Length 28 m
Cut-Off length 2m
L1 0m
Depth of Fixity of Pile, Lf 5.679 m
Considering Seismic effect, the vertical capacity of Pile can be
increased by 25%. (for Ncorrected>10) *0.85 (GRP.EFFICIENCY)
Max. Vertical Load Capacity 669.38 KN
Lateral Load Carrying Capacity 25.13 KN
Design of RCC Pile:
Considering
Clear Cover 50 mm
Dia of bar 16 mm
Grade of Concrete M- 25
Grade of Steel Fe- 500
Max. Vertical Load on Column:
Vertical Load (Seismic) 2209 KN
Pile Cap & Overburden Load 161.82 KN
Max. Vertical Load on Column 2371 KN
PG-12