C Series
C Series
Multisignal digital panel meter, configurable to work as AC and DC voltmeter (up to 600 Vac / dc), AC and DC
ammeter (up to 5 Aac / dc), accepts process signals (mA, Vdc), thermocouples, resistive temperature probes
(Pt, Ni, PTC and NTC), resistances, potentiometers and frequency. Configurable. Standard 96 x 48 mm size
(1/8 DIN). Scalable reading with 4 digits (9999 / -1999). ‘Fast access’ function to alarm setpoints, ‘external
control’ to activate predefined functions, ‘Eco’ mode for low consumption, selectable dual scaling, 5 levels
of configurable brightness. Single universal power supply 18 to 265 Vac/dc. Optional modules for output
and control (relays, analog output, Modbus RTU). Recommended for OEM applications.
                                                                                      www.fema.es
4149r07                                                               Tel. (+34) 93.729.6004 info@fema.es
FEMA ELECTRÓNICA . Series C . C40-D
                                          -U     (18-265 Vac/dc)                -A1 (1 relay)               -A2 (1 relay)                        -NBT (no front keypad) -XXXX (customized)
                                                                                -M1 (analog output)         -(empty)                             -65 (front IP65)       -(empty)
                                                                                -S1 (Modbus RTU)                                                 -(empty)
                                                                                -(empty)
    Index
 1. Panel meter C40-D  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2            1.29 Configuration menu  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  16
   1.1 How to order .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2           1.29.1 Input signal ranges  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  16
   1.2 Front view   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3        1.29.2 Scaling  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  17
   1.3 Rear view  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3       1.29.3 Alarms  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  17
   1.4 Power connections  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3                 1.29.4 Fast access  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 18
   1.5 Signal connections  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3                1.29.5 Super fast access  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  18
   1.6 Mechanical dimensions (mm)  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3                          1.29.6 External control  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 18
   1.7 Installation and start-up  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3                  1.29.7 Menu ‘Tools’   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  19
   1.8 Technical specifications  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 4                1.29.8 Configuring the options   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  21
   1.9 Internal jumpers  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 5          1.30 Full configuration menu  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  22
   1.10 Measuring AC voltages and AC currents  .  .  .  .  .  .  .  .  . 6                              1.31 Precautions on installation  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 25
   1.11 Measuring DC voltages and DC currents  .  .  .  .  .  .  .  .  . 7                              1.32 Factory configuration  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 25
   1.12 Measuring thermocouples  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8                       1.33 Warranty   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  25
   1.13 Measuring with Pt and Ni probes  .  .  .  .  .  .  .  .  .  .  .  .  . 9                        1.34 CE declaration of conformity   .  .  .  .  .  .  .  .  .  .  .  .  .  .  25
   1.14 Measuring with NTC probes . . . . . . . . . . . . . . . 10                                    2. Output and control modules  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  26
   1.15 Measuring with PTC probes  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  10                      2.1 Modules A1 and A2 (relay output)  .  .  .  .  .  .  .  .  .  .  .  .  26
   1.16 Process measures  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11                 2.2 Module M1 (analog output)   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  26
   1.17 Measuring frequency  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 11                    2.3 Module S1 (Modbus RTU)  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 27
   1.18 Measuring resistances  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  12
                                                                                                      3. Other options   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  28
   1.19 Measuring potentiometers   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  12
                                                                                                        3.1 Option NBT  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  28
   1.20 ‘Fast access’ menu  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  13
                                                                                                        3.2 Option 65  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 28
   1.21 Scaling  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 13
                                                                                                        3.3 Option ‘customized’  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  28
   1.22 Offset reading  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 13
   1.23 ‘Eco’ mode   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  13       4. Accessories  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 29
   1.24 External control  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 13              4.1 Adapter DRA-M   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  29
   1.25 Second scaling   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  13           4.2 Adapter KA96  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 29
   1.26 To open the instrument  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  14                   4.3 Protector KIP  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  29
   1.27 How to operate the menus   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  15                      4.4 WME wall housing .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  29
   1.28 Messages and errors  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  15                4.5 THM benchtop housing  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  29
                                                                                                        4.6 Set of units (included)  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  29
2
                                                                                                            FEMA ELECTRÓNICA . Series C . C40-D
                                                                                                       5A        { 5 Aac, ±5 Adc
                                                                                                                     ~
                                                                                                       Signal    { thermocouple+,
                                                                                                                    Vac, ±Vdc, resistance, mA, pot,
                                                                                                                     ~
                                                                                                                                   Pt+, Ni+, PTC+, NTC+
                                                                                                       HV signal {
                                                                                                                    600 Vac, 200 Vac
                                                                                                                     ~         ~
                                                                                                                   ±600 Vdc, ±200 Vdc
                                                                                    48
                         Signal                           Power
               (see section 1.5)                          (see section 1.4)                                  Units
96 16 75 8
                                                                                                                                                          3
FEMA ELECTRÓNICA . Series C . C40-D
4
                                                                                                                      FEMA ELECTRÓNICA . Series C . C40-D
                                                                                                                                                                      5
FEMA ELECTRÓNICA . Series C . C40-D
     Vac ranges             Scale            Scalable           Jumper ‘S’          Jumper ‘T’          Accuracy            Max.                 Connection           Zin
              (Veff.)     by default                         (see section 1.9) (see section 1.9)          (% FS)          oversignal             (terminals)
      ~   600 Vac*           600                                    GI                                                      800 Vac                                 12 M
                                                                                                                                                  1(~ ) 4(~ )
          ~   200 Vac       200.0                                    I                                                      800 Vac                                 12 M
          ~   20 Vac        20.00           from 9999               AI                                  <0.30 %             150 Vac                                  1M
                                                                                       4-5
              ~   2 Vac     2.000            to -1999               BI                               (up to 150 Hz)         100 Vac                                 100 K
                                                                                                                                                  2(~ ) 4(~ )
      ~   200 mVac          200.0                                   CI                                                       30 Vac                                  10 K
      ~   60 mVac           60.0                                    EI                                                        3 Vac                                  1M
    Table 4 - Measuring ranges in Vac. *See section 1.34 for category of measure.
     Aac ranges             Scale            Scalable           Jumper ‘S’          Jumper ‘T’          Accuracy        Max. oversig-            Connection           Zin
              (Veff.)     by default                         (see section 1.9) (see section 1.9)          (% FS)            nal                  (terminals)
                  5 Aac     5.00                                     I                                                        7 Aac               3(~ ) 4(~ )       20 mOhm
              ~
                                            from 9999                                                   <0.50 %            (max. 7 sec.)
                                                                                       4-5
      ~   20 mAac           20.00            to -1999               DI                               (up to 150 Hz)         25 mAac               2(~ ) 4(~ )        4.7 R
    Table 5 - Measuring ranges in Aac
6
                                                                                                                 FEMA ELECTRÓNICA . Series C . C40-D
  Vdc ranges            Scale       Scalable      Jumper ‘S’         Jumper ‘T’           Accuracy         Max. oversig-          Connection      Zin
                     by default                 (see section 1.9) (see section 1.9)         (% FS)             nal                (terminals)
   ±600 Vdc              600                           G                                                       800 Vdc                          12 M
                                                                                                                                   1(+) 4(-)
   ±200 Vdc             200.0                         ---                                                      800 Vdc                          12 M
    ±20 Vdc             20.00       from 9999          A                                   <0.20 %             150 Vdc                           1M
                                                                         4-5
    ±2 Vdc              2.000        to -1999          B                                                       100 Vdc                          100 K
                                                                                                                                   2(+) 4(-)
  ±200 mVdc             200.0                          C                                                        30 Vdc                           10 K
   ±60 mVdc             60.0                           E                                   <0.25 %              3 Vdc                            1M
Table 7 - Measuring ranges in Vdc
  Adc ranges            Scale       Scalable      Jumper ‘S’         Jumper ‘T’           Accuracy         Max. oversig-          Connection      Zin
                     by default                 (see section 1.9) (see section 1.9)         (% FS)             nal                (terminals)
    ±5 Adc              ±5.00                         ---                                  <0.25 %              7 Aac              3(+) 4(-)    20 mOhm
                                    from 9999                                                                 (max. 7 sec.)
                                                                         4-5
  ±20 mAdc             ±20.00        to -1999          D                                   <0.15 %            25 mAdc              2(+) 4(-)     4.7 R
Table 8 - Measuring ranges in Adc
                                                                                                                                                           7
FEMA ELECTRÓNICA . Series C . C40-D
                                                                                                                                            tc -
                                                                                                                                            tc +
                                                                               -100 / 1350 ºC
        Thermocouple K
                                                                               (-148 / 2462 ºF)
                                                                               -100 / 1200 ºC
        Thermocouple J
                                                                               (-148 / 2192 ºF)
                                                                               -100 / 1000 ºC
        Thermocouple E                      E
                                                                               (-148 / 1832 ºF)
                                                                               -100 / 1300 ºC
        Thermocouple N
                                                                               (-148 / 2372 ºF)
                                                              4-5                                                                    <3 º
                                                                                -100 / 900 ºC
        Thermocouple L
                                                                               (-148 / 1652 ºF)
                                                                                                           2 (tc +)
                                                                                                           4 (tc -)
                                                                                 0 / 1768 ºC
        Thermocouple R
                                                                                (32 / 3214 ºF)
                                                                                 0 / 1768 ºC
        Thermocouple S                     EJ
                                                                                (32 / 3214 ºF)
                                                                                -100 / 400 ºC
        Thermocouple T
                                                                                (-148 / 752 ºF)
                                                                                 0 / 2300 ºC
        Thermocouple C                      E
                                                                                (32 / 4172 ºF)
                                                                                                                                     <5 º
                                                                                700 / 1820 ºC
        Thermocouple B                     EJ
                                                                               (1292 / 3308 ºF)
8
                                                                                                                    FEMA ELECTRÓNICA . Series C . C40-D
       Sensor                 Jumper ‘S’                  Jumper ‘T’        Range in ºC             Total error          Connection         Current at
                           (see section 1.9)            (see section 1.9)       (in ºF)                                  (terminals)         sensor
                                                                                                                             2 (Pt+)
                                                                            -200 / 700 ºC
   Pt100 3 wires                 FHJ                          5-6                                                            4 (Pt -)        < 900 uA
                                                                            (-328 / 1292 ºF)
                                                                                                                             5 (sense)
                                                                            -200 / 700 ºC
   Pt100 2 wires                  FH
                                                                            (-328 / 1292 ºF)
                                                                            -150 / 630 ºC
        Pt500                      F                                                                                                          < 90 uA
                                                                            (-238 / 1166 ºF)
                                                                             -60 / 120 ºC
       Ni200                      FH                                                                                                         < 900 uA
                                                                             (-76 / 248 ºF)
                                                                             -60 / 180 ºC
       Ni1000                      F                                                                                                          < 90 uA
                                                                             (-76 / 356 ºF)
                                                                                                                                                          9
FEMA ELECTRÓNICA . Series C . C40-D
 Different NTC probes can be used, by configuring the instrument for                        • Start-up, connections and jumpers
 different values of ‘R25’ and ‘beta’. The instrument measures resis-                       For instrument start-up follow the steps listed at section 1.7. Signal
 tance from 100 R up to 1 MOhm. Use ‘Table 12’ to write down values                         connections are indicated at section 1.5. Location for internal jump-
 for your NTC.                                                                              ers is indicated at section 1.9.
 • Parameters ‘R25’ and ‘Beta’                                                              See below connections for NTC probe :
 The instrument accepts values of ‘beta’ between 2500 and 5500, and
 values of R25 between 1.0 K and 200.0 K
                                                                                                                    1 2 3 4 5
 • Resolution and units
 The temperature resolution using NTC temperature probes is con-
 figurable to 1º or 0.1º. Reading can be configured in ºC (degrees Cel-
 sius) or ºF (degrees Fahrenheit).
                                                                                                                                ntc -
                                                                                                                                ntc +
       NTC ‘R25’*        Jumper ‘S’          Jumper ‘T’          Range        Accuracy Connection           Beta*           Range                   NTC probe
      (configurable)   (see section 1.9) (see section 1.9) of measure (% of reading) (terminals) (configurable)          of measure         Temp.       R25     Beta
                                                                                                                             100 R
                                                                from -60 ºC    <1.5% of 2 (NTC +)
          10K                 FK                 4-5                                                         3500
                                                                 to 150 ºC     reading 4 (NTC -)
                                                                                                                              1 MR
Table 13 - *‘Beta’ is configurable from 2000 to 5500. ‘R25’ is configurable from 1.0 K up to 200.0 K. Table 12 - Data from NTC datasheet
                KTY81-220
 KTY 220                             FHK
                KTY82-220
                                                                                                                                ptc -
 Table 14 - Ranges of temperature for PTC probes                                                                                ptc +
10
                                                                                                                 FEMA ELECTRÓNICA . Series C . C40-D
             Ranges                   Scale          Scalable      Jumper ‘S’       Jumper ‘T’        Accuracy           Max.       Connection         Zin
         of measure                 by default                  (see section 1.9) (see section 1.9)    (% FS)          oversignal   (terminals)
                  passive                                                                                                           2 (signal)
                                                                                        1-2                                         5 (Vexc)
                (needs Vexc.)
  4/20 mA                                                              D                               <0.15 %          25 mA                       4.7 Ohm
                   active                                                               4-5                                         2 (mA+)
                                                     de 9999                                                                        4 (mA-)
                  passive           0/100.0                                                                                         2 (+Vdc)
                                                     a -1999                            1-2                                         4 (comm.)
  0/10 Vdc      (needs Vexc.)                                          A                               <0.20 %          25 Vdc      5 (Vexc)           1M
                   active                                                               4-5                                         2 (+Vdc)
                                                                                                                                    4 (comm.)
Table 15 - Ranges of measure for process signals
                                                                                                                                                              11
FEMA ELECTRÓNICA . Series C . C40-D
 • Response times
 The response time to a signal step is 300 mSeconds, independent of                                                                         Pot+ (5 Vdc)
 the signal range selected.                                                                                                                 Pot- (comm.)
 • Terminal 5 ‘multifunction’ - ‘Vexc’                                                                                                      Signal
 To measure potentiometer signals, set internal jumper ‘T’ at position
 2-3 (see section 1.9). Terminal 5 will be assigned to a +5 Vdc excita-
 tion voltage for the potentiometer.
12
                                                                                                              FEMA ELECTRÓNICA . Series C . C40-D
                                                                                                                                                                   13
FEMA ELECTRÓNICA . Series C . C40-D
     To open the housing and access the internal circuits, use a flat screw-
     driver to unlock clips ‘D’, ‘C’, ‘B’ and ‘A’, in this order. Remove the
     front filter. Let the inside of the instrument slide out of the housing.
     To reinsert the instrument make sure that all modules are correctly
     connected to the pins on the display module. Place all the set into
     the housing, assuring that the modules correctly fit into the internal
     guiding slides of the housing. Once introduced, place again the front
     filter at cover ‘X’, and then insert clips ‘A’, ‘B’, ‘C’ and ‘D’, in this order.
                                                                                                                                           C
                                                                                             X
                                                                                                                            A
                                                                                                 Risk of electric shock. Removing the front cover will
                                                                                                 grant access to the internal circuits. Disconnect the in-
                                                                                                 put signal to prevent electric shock to the operator. Op-
                                                                                                 eration must be performed by qualified personnel only.
                                                                                                 Observe precautions for handling ESD (electrostatic dis-
                                                                                                 charge) sensitive devices
Optional modules
                                                                                                          Opt.2
                                                                   Opt.1
Motherboard
Housing
14
                                                                                                                    FEMA ELECTRÓNICA . Series C . C40-D
Key SQ (<) - press the SQ (<) key for 1 second to access the ‘con-            ‘d.udr’            display underrange (‘d.udr’) / overrange (‘d.ovr’). The
figuration menu’. Inside the menu, the SQ (<) key functions as a              ‘d.oVr’            instrument already displays the minimum / maximum
‘ENTER’ key. It selects and accesses the menu option currently dis-                              value possible (9999 / -1999).
played. At menus with numerical value entries, it validates the num-          ‘Err.1’            incorrect password.
ber displayed.
                                                                              Table 19 - Messages and error codes
Key UP (5) - the UP (5) key gives access to the ‘fast access’ menu.
Inside the menus, it moves vertically through the different menu op-
tions. At menus with numerical value entries, it modifies the digit
selected by increasing its value to 0, 1, 2, 3, 4, 5, 6, 7, 8, 9.
Key LE (3) - inside the menus, the LE (3) key functions as the ‘ES-
CAPE’ key. It leaves the selected menu, and eventually, will leave the
whole menu. When leaving the ‘configuration menu’ with the LE (3)
key, the changed parameters are activated. At menus with numeri-
cal value entries, the LE (3) key allows to select the active digit. To
modify the value of the selected digit use the UP (5) key.
Menu ‘rollback’
After 30 seconds without interaction from the operator, the instru-
ment will rollback and leave the ‘configuration menu’ or the ‘fast ac-
cess’ menu. All changes will be discarded.
                                                                                                                                                            15
FEMA ELECTRÓNICA . Series C . C40-D
                                                      20 Vac range                • ‘AC signals’ (‘Ac’) - select a range between 600 Vac, 200 Vac,
                                                                                  20 Vac, 2 Vac, 200 mVac, 60 mVac, 5 Aac and 20 mAac. The AC mea-
                                                      2 Vac range
                                                                                  sure ranges provide ‘True RMS’ reading.
                                                      200 mVac range
                                                      60 mVac shunt range         • ‘DC signals’ (‘dc’) - select a range between ±600 Vdc, ±200 Vdc,
                                                                                  ±20 Vdc, ±2 Vdc, ±200 mVdc, ±60 mVdc, ±5 Adc and ±20 mAdc. Dc
                                                      5 Aac range                 measures are bipolar.
                                                      20 mAac range
                                                      ±200 mVdc range             • ‘RTD probes’ (‘rtd’) - the ‘rtd’ menu offers temperature resis-
                                                                                  tive probes type Pt (platinum) and Ni (Nickel). Select the type of
                                                      ±60 mVdc shunt range        probe from the available options Pt100 3 wire, Pt100 2 wire, Pt500,
                                                                                  Pt1000, Ni100, Ni200 and Ni1000. For measures with 2 wires, a
                                                      ±5 Adc range
                                                                                  manual compensation for the wire resistance error is available us-
                                                      ±20 mAdc range              ing parameter ‘Offset reading’ (‘oFFS’) (see section 1.22).
                                                                                  • ‘NTC probes’ (‘ntc’) - select the ‘ntc’ menu to configure the input
                                                                                  for NTC probes. To correctly configure the measure for NTC, two pa-
                                                      4/20 mA range
                                                                                  rameters need to be defined : first the resistance of the NTC probe
                       Process                                                    at 25º (‘r.25’) and parameter ‘beta’ (‘bEtA’). The instrument accepts
                                                      0/10 Vdc range
                                                                                  beta values between 2000 and 5500, and values of R25 between
                                                                                  1.0 K and 200.0 K. For more information on NTC measures see sec-
                                                      thermocouple K              tion 1.14.
                    Thermocouples
                                                      thermocouple J
                                                                                  • ‘PTC probes’ (‘Ptc’) - select the ‘ptc’ menu to configure the input
                                                      thermocouple E              for PTC probes. Select K121 for PTC probes from the KTY-121 family
                                                                                  (KTY81-121 and KTY82-121). Select K220 for PTC probes from the
                                                      thermocouple N
                                                                                  KTY-210 family (KTY81-210 and KTY82-210) and KTY-220 (KTY81-
                                                      thermocouple L
                                                                                  220 and KTY82-220). For more information on PTC probes see sec-
                                                                                  tion 1.15.
                                                      thermocouple R
thermocouple S
thermocouple B
thermocouple T
thermocouple C
16
                                                                                     FEMA ELECTRÓNICA . Series C . C40-D
                                              res. at
                                               25º
                                                        1.29.2 Scaling
             NTC probes
                                              beta      Scale the reading at the ‘Scaling’ (‘ScAL’) menu. Temperature ranges
                                                        (thermocouples, Pt and Ni probes, NTC and PTC probes) have direct
                                                        temperature indication and are not scalable.
                            KTY 121 family
             PTC probes                                 To configure the scaling, enter the ‘Decimal point’ (‘dP’) parameter
                            KTY 210 and 220 family      and select the desired position for the decimal point, using key ‘LE’
                                                        (3).
                            range 0 to 5 K              Then configure at the ‘Display Low’ (‘d.Lo’) parameter the reading
             Resistance                                 value associated to the low signal range and configure at the ‘Display
                            range 0 to 50 K
                                                        High’ (‘d.Hi’) parameter the reading value for the high signal range.
                                                        For more information see section 1.21.
            Potentiometer
Frequency
                                                        1.29.3 Alarms
                                                        The instrument has 2 independent and configurable alarms.
  Scaling   Decimal point
                                                        Control the independent activation of relays A1 installed (optionally)
                                                        at slots 1 and 2 (see section 2.1) from menu entries ‘Alarm 1’ (‘ALr1’)
             Display Low                                and ‘Alarm 2’ (‘ALr2’). Alarms control also the activation of front leds
                                                        ‘1’ and ‘2’ located as indicated at section 1.2.
                                                        To configure the alarms, enter at the alarm menu (‘ALr1’, or ‘ALr2’)
            Display High                                and configure the following parameters :
                                                         • at the ‘Alarm type’ (‘TypE’) parameter select alarm as as a max-
                                                         imum type alarm (‘MAX’) or a minimum type alarm (‘MIn’). The
                                                         maximum type alarm (or minimum type) activates when the dis-
                                                         play value is higher (or lower) than the setpoint value.
 Alarm 1     Alarm type
                                                         • at the ‘Setpoint’ (‘SEt’) parameter enter the value for the alarm
                                                         activation point. This parameter is eligible for configuration through
                                                         the ‘Fast access’ menu (see section 1.20).
              Setpoint
                                                         • configure the hysteresis value at ‘Hysteresis’ (‘hySt’). The hys-
                                                         teresis applies to the deactivation process of the alarm. The alarm
             Hysteresis                                  deactivates when the reading has passed the setpoint value plus
                                                         the hysteresis value. Hysteresis helps to avoid repetitive switching
                                                         of the alarm relays, due to fluctuating input signals around the set-
                                                         point.
                                                                                                                              17
FEMA ELECTRÓNICA . Series C . C40-D
                        Setpoint
                                       The ‘Key UP (Fast access)’ (‘K.uP’) menu allows to select which func-
                                       tions will be accessible when pressing the front key ‘UP’ (5). Select
                                       ‘on’ to activate each function.
                       Hystereses       • the ‘Setpoint 1’ (‘ALr1’) function allows to visualize and modify
                                        the setpoint value of alarm 1.
                                        • the ‘Setpoint 2’ (‘ALr2’) function allows to visualize and modify
                                        the setpoint value of alarm 2.
        Key UP         Setpoint 1
     (fast access)
                                        •the ‘Memory of maximum’ (‘MAX’) or ‘Memory of minimum’
                                        (‘MIn’) allows to visualize the memory of maximum and minimum
                                        reading. The memory resets when the instrument restarts (power
                       Setpoint 2
                                        off-on cycle, or when leaving the configuration menu with a change
                                        to be applied).
                     Memory of max.     • the ‘Tare function’ (‘tArE’) allows to visualize the actual tare value.
                     Memory of min.
                                       1.29.5 Super fast access
                                       If only a single function is selected for the ‘fast access’ menu, press-
                     ‘Tare’ function   ing the the ‘UP’ (5) key will shortly display the function name and
                                       then automatically jump to the function value.
18
                                                                                                    FEMA ELECTRÓNICA . Series C . C40-D
                               relay
                                                                       1.29.7 Menu ‘Tools’
                                           the parameter ‘420’ gives
                                                                       The ‘Tools’ (‘tooL’) menu contains multiple configuration options of
                                           access to the calibration   the instrument.
                           analog output   menu for the analog out-
                                           put. See section 2.2 for       • select at the ‘Option 1’ (‘out.1’) parameter the module type
                                           more information.              installed at the ‘Opt.1’ (see section 2) slot. Select ‘relay’ (‘rELE’)
                           Modbus RTU
                                                                          for the relay output module ‘A1’. Select ‘analog output’ (‘420’)
                                                                          for the analog output module ‘M1’. Select ‘Modbus RTU’ (‘r.485’)
                                                                          for the Modbus RTU serial output module ‘S1’.
                                                                          Note : the parameter ‘420’ gives access to the calibration menu
                                                                          for the analog output module. See section 2.2 for more informa-
              Steps
                                                                          tion about this menu and the calibration.
                                                                                                                                              19
FEMA ELECTRÓNICA . Series C . C40-D
               ‘Eco’ mode                     5 to 255 seconds             - after the configured time is over, without interaction from
                                                                           the operator, the display powers off the reading. It will not
                                                                           power off if the instrument is into ‘configuration menu’ or in
                                                                           ‘fast access’ menu or there is an active alarm.
                                                                           - the instrument will power on the display when an alarm acti-
                                                                           vates (either alarm 1 or 2) and will remain on if alarm remains
                                                                           active.
                                                                           - the instrument will power on the display if the operator
                                                                           press any front key.
                                              1º resolution             • at the ‘Temperature resolution’ (‘t.rES’) menu select the reso-
              Temperature                                               lution to 1º or 0.1º. This resolution applies to temperature probes
               resolution                     0.1º resolution
                                                                        Pt100, Pt500, Pt100, Ni100, Ni200, Ni1000, PTC and NTC. For
                                                                        thermocouple probes resolution is fixed to 1º.
                                              Degrees Celsius
                                                                        • at the ‘Degrees’ (‘dEG’) menu select the temperature values to
                Degrees
                                              Degrees Fahrenheit        be read in ºC (degrees Celsius) or in ºF (degrees Fahrenheit).
                                                                        • at the ‘Alpha’ (‘ALPh’) menu select the value for the alpha pa-
                                              Alpha 0.0385              rameter to ‘0.0385’ o ‘0.0390’. This parameter affects to Pt probes
                 Alpha                                                  (Pt100, Pt500, Pt1000) and it depends on the probe.
                                              Alpha 0.0390
                                                                        • at the ‘Cold junction’ (‘cJc’) menu select ‘on’ to activate the
                                                                        thermocouple cold junction compensation. Select ‘off’ to deac-
                                              Thermocouple cold         tivate.
                                              junction compensation
              Cold junction
                                              ‘on’ or ‘off’             • the ‘AC deadband’ (‘d.bnd’) parameter applies only to AC mea-
                                                                        suring ranges. The True RMS measures deal with a considerable
                                                                        noise when signal is near to 0. This parameter allows to set a
                                              Deadband for AC signals
                                                                        value between 0 and 100 (by default is 20) to empirically set the
              ‘AC deadband’
                                                                        signal level at which reading will be forced to 0, when signal is
                                                                        below that level.
                                              Minimum
                                                                        • at the ‘Brightness’ (‘LIGh’) menu select between 5 levels of
               Brightness                                               brightness intensity for the display. It adapts the instrument to
                                                                        environments with higher or lower brightness is needed or to
                                              Standard                  adapt the intensity to other meters in the area.
                                                                        • the ‘Version’ (‘VEr’) menu informs about the firmware version
                                                                        installed on the instrument.
                                              Maximum                   • at the ‘Password’ (‘PASS’) menu select a 4 digit code to block
                                                                        access to the ‘configuration menu’. Use the ‘Password’ function
                                                                        to prevent modifications on the instrument configuration. To ac-
                 Version                                                tivate the ‘Password’ select ‘on’ and enter the numerical code.
                                                                        The code will be requested when trying to access the ‘configura-
                                                                        tion menu’. The ‘fast access’ menu is not blocked by the ‘Pass-
               Password                                                 word’.
20
                                                                                  FEMA ELECTRÓNICA . Series C . C40-D
                                                                                                                            21
FEMA ELECTRÓNICA . Series C . C40-D
                                                    5 Aac range
                                                                                                                               res.
                                                    20 mAac range                                                              at 25º
                                                                                              NTC probes
                                                                                                                               beta
                                                    ±5 Adc range
                                                                                              Frequency
                                                    ±20 mAdc range
                                                    4/20 mA range
                                                                                   Scaling   Decimal point
                     Process
                                                    0/10 Vdc range
                                                                                              Display Low
                                                    thermocouple K
                  Thermocouples
                                                    thermocouple J                           Display High
thermocouple E
                                                    thermocouple N
                                                                                   Alarm 1    Alarm type
                                                    thermocouple L
                                                    thermocouple R
                                                                                               Setpoint
                                                    thermocouple S
                                                    thermocouple B
                                                                                              Hysteresis
                                                    thermocouple T
thermocouple C
22
                                                             FEMA ELECTRÓNICA . Series C . C40-D
                                                                     relay
                      Setpoint
                                                                                 the parameter ‘420’ gives
                                                                                 access to the calibration
                                                                 analog output   menu for the analog out-
                     Hysteresis                                                  put. See section 2.2 for
                                                                                 more information.
                                                                 Modbus RTU
     Key UP          Setpoint 1
  (fast access)
                                                   Steps
                     Setpoint 2
Memory of max.
Memory of min.
Function ‘tare’
Offset reading
Memory of max.
                                                                  Display Low
                    Display hold
                                                                 Display High
                   Function ‘tare’
                   Decimal point 0
                                                ‘Eco’ mode                       5 to 255 seconds
                   Decimal point 1
                                                                                 1º resolution
                                               Temperature
                   Decimal point 2              resolution                       0.1º resolution
                                                                                 degrees Celsius
                   Decimal point 3
                                                  Degrees
                                                                                 degrees Fahrenheit
Second scaling
                                                                                                       23
FEMA ELECTRÓNICA . Series C . C40-D
                                                       Alpha 385
                       Alpha
                                                       Alpha 390
                                                       Thermocouple cold
                                                       junction compensation
                    Cold junction
                                                       ‘on’ or ‘off’
                                                       Deadband fo AC signals
                    ‘AC deadband’
                                                        Minimum
                     Brightness
Standard
Maximum
Version
Password
Factory reset
Speed Kbps
Format
24
                                                                                                                                FEMA ELECTRÓNICA . Series C . C40-D
                                                                                                                                                                             25
FEMA ELECTRÓNICA . Series C . C40-D
 Type of relay		             3 contact relay (NC, NO, common)               Output signal		              4/20 mA (active and passive)
 Current maximum             8 A per relay (resistive load)                 Active output		 connect terminal A (+15 Vdc) and B (mA)
 Voltage maximum             250 Vac continuous                             			RL <350 R
 when switching power lines, with overvoltage category 3, maximum switch-
 ing voltage is 150Veff to comply with CE safety requirements.              Passive output		 connect terminal C (GND) and B (mA)
                                                                            			RL < 700 R
 Isolation			                3500 Veff
                                                                            Accuracy		                   <0.5% FS
 Type of terminal		          plug-in screw terminal, pitch 5.08 mm
 Slots allowed		             Opt.1 for A1 module                            Response time		              <100 mSeg. + meter response time
 			                         Opt.2 for A2 module                            Isolation			                 1000 Vdc
                                                                            Slots allowed		              Opt.1
                               Opt.2               Opt.1                                                                       Opt.1
                                           Com.               Com.                                                                         Vexc
                                           NO                 NO                                                                           4/20 mA
                                           NC                 NC                                                                           Common
G H I A B C A B C
26
                                                                                                        FEMA ELECTRÓNICA . Series C . C40-D
                                                                                    Terminal B           B
                         analog output   Do not calibrate                           Terminal A           A
                                                                                    Terminal G           GND
                                            Calibrate
Modbus RTU
                                                                                                                                                  27
FEMA ELECTRÓNICA . Series C . C40-D
 3. Other options
     3.1 Option NBT
     Instruments without front key-
     pad. To configure the instrument,
     remove the meter from the panel
     and remove the front filter. Inter-
     nal press buttons for configuration
     are accessible. Optionally, request
     the instrument preconfigured
     from factory.
                                           Without front keypad
3.2 Option 65
28
                                                                     FEMA ELECTRÓNICA . Series C . C40-D
4. Accessories
4.1 Adapter DRA-M                   4.4 WME wall housing
Adapter for DIN rail mount, for     Wall mount housing. Together
Series C                            with the KIP protector, offers a
                                    full IP65 protection. For Series C
                                    of panel meters.
                                                                                                     29
FEMA ELECTRÓNICA . Series C . C40-D
Notes