Ft3 Manual
Ft3 Manual
MODEL
        Fox Thermal Gas Mass Flow Meter
        Instruction Manual
        Document #104488
        Rev K
This publication must be read in its entirety before performing any operation. Failure to
 understand and follow these instructions could result in serious personal injury and/or
damage to the equipment. Should this equipment require repair or adjustment beyond
                  the procedures given herein, contact the factory at:
   Fox Thermal Instruments, Inc. (Fox Thermal) believes that the information
provided herein is accurate; however, be advised that the information contained
herein is NOT a guarantee for satisfactory results. Specifically, this information is
neither a warranty nor guarantee, expressed or implied, regarding performance,
 merchantability, fitness, or any other matter with respect to the products; nor
recommendation for the use of the product/process information in conflict with
 any patent. Please note that Fox Thermal reserves the right to change and/or
           improve the product design and specification without notice.
                                         | 3
Model FT3
Table of Contents
1. Introduction p. 6-20
b. Menu Trees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 8
c. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 17
a. Lateral Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 21
c. Installation Depth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 24
d. Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 25
e. Mounting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 27
f. Retractor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 29
a. Wiring Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 33
b. Input Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 36
c. Signal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 38
d. Alarm Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 40
e. Remote Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 43
f. Remote Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 48
   a. Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  p. 50
   b. Display Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  p. 51
c. Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 53
5. Communications p. 90-105
a. Modbus Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 90
c. HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 101
                                                                                        | 4
                                                                                                                                                   Model FT3
                                                                                                                                    Table of Contents
a. Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 106
7. Maintenance p. 112-121
b. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 116
8. Appendices p. 122-139
a. Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 122
c. Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 126
d. Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p. 135
                                                                                      | 5
Model FT3
Quick Start Guide
Use the table below as a guide while using the worksheet on the next page to record your notes.
NOTE! Please read the entire quick-start procedure before beginning installation.
4.                                                                          PIPE
      Ensure correct probe depth setting. If using 1 ½" size
      pipe, please see note on p. 24.                             CL                             FLOW
Earth Ground
5.                                                                                              TS2
                                                                                                                         Red2
                                                                                                                                   Red 1
                                                                                                                                                                                                           Earth Ground
                                                                                                                  TS3
6.
                                                                                       +7
                                                                                       IN
                                                                                                                                                                              Cable Shield
                                                                                                                                                                                     F1
                                                                                       -8                         TS4 -2 +1                                                                                                GRN
                                                                                                                  24V                                                    24V, 0.75A                                                 #6        W
                                                                                                                  RED                   2
                                                                                     5
      ordered.
                                                                                                                                                                    J2                                     BRN              BRN
                                                                                                                  YEL                   3                                                                                                #3
                                                                                                                                                                                                           WHT
                                                                                                                                  TS3
                                                                                                                                                  1       2     3
                                                                                                                                                                       TS1
                                                                                                                                            FT3                Customer PLC or DCS
7.
                                                                                                                                                  Red 1
                                                                                                                            TS2
                                                                                                                                               Red2              F1
                                                                                                                                                              +24VDC
                                                                                                             -2       +1                TS3
                                                                                                       TS4                              REMOTE Yel 3
                                                                                                                                        SENSOR 24V,0.75A
                                                                                                                    +1
                                                                                                       24V      4-20                           Wh 4                 4 to 20mA FLOW RATE
                                                                                                       OUT
                                                                                                        Electronics Enclosure
                                                                                                                                        TS4 +1 -2
                                                                                                                      -8                24V                         4 to 24V,
                                                                                                                                                                         20mA     TEMPERATURE OR
                                                                                                                                                                              0.75A
                                                                                                                                                                                    FLOW RATE
                                                                                                                                                                                                                          SENSOR
                                                                                                                                        OUT
                                                                                                                                                                    * (see important note below)
                                                                                                                                                                         J2
                                                                                                                                                                    24VDC Return
                                                                                                                                                                                                                                              R
8.
      Power on the flow meter.
                                                                                                                                                          Initializing...
9.    Check the remaining flow meter settings by accessing the meter settings eitherF1through
                                                                                        F2 F3 F4 the front panel
      of the display or by using the FT3 View™ software tool. Record the settings in the spaces given for
      items A - E on the following page.
Before powering on your meter, use this worksheet to record your notes.
After powering on your meter, check items A - E below by accessing the meter settings either through the
front panel of the meter's display or by using the FT3 View™ software tool.
A.    Which flow units have been set in
      meter? (SCFM, KG/H, etc..)
B.    Correct values for reference          Y/N              Y/N              Y/N              Y/N
      temperature and pressure?
C.    Confirm the pipe ID listed above
      same as "Pipe_id="
D.    Verify the 1st 4mA and 20mA           4mA =            4mA =            4mA =            4mA =
      meter settings                        20mA =           20mA =           20mA =           20mA =
E.    Verify the 2nd 4mA and 20mA           4mA =            4mA =            4mA =            4mA =
      meter settings                        20mA =           20mA =           20mA =           20mA =
Your Notes:
If you are experiencing any problems after completing this procedure, please call the Fox
Thermal Service Department at 831-384-4300 to review this information.
                                                                      SET PARAMETERS
                                                                    I/O FLO DSP EXIT
                                                                                                                       Display Menu, p. 12
                                                                                                                       Flow Parameter Menu 1, p. 10
                                                                        SET I/O
                                                                    COM I/O 420 EXIT
Analog Outputs
                                                                                                                                        4 mA=0 °F
                                                                                                                                        CHG                  OK
                                                          Introduction | 8
                                                                                                                                                  Model FT3
                                                                                                                                                  Introduction
         Not used
        Frequency   OUT= Not used
         HiFloAlm   NXT             OK
        LoFloAlm
       HiTempAlm
       LoTempAlm                                                   Frequency
       System Alm
                                                                                                                               Select 1 of 3
                                         High Limit Alarm                                             OUT= FREQUENCY           methods to scale
                                                                                                      NXT            OK        the frequency
                                                                                                                               output
                                                   OUT= HiFloAlm
                                                   NXT               OK
                                                                                                       FREQUENCY OUTPUT
                                                                                                      P/U U/P FEQ EXIT
                                                     HiFloAlm=500 SCFM
                                                    CHG              OK
                                                   OUT= LoFloAlm
                                                   NXT               OK                                                        MaxFlo=5678.5 SCFM
                                                                                                                               CHG             OK
                                                    LoFloAlm=100 SCFM
                                                    CHG             OK
                                                   OUT= HiTmpAlm
                                                   NXT               OK
                                                     HiTmpAlm=300° F
                                                    CHG           OK
                                                   OUT= LoTmpAlm
                                                   NXT               OK
System Alarm
                                                                    Introduction | 9
Model FT3
Introduction
                    Simulate CSV?
                    YES                   NO
                                                Diagnostic Test Menu, p. 13
                    CsvSim=0 V
                    CHG                    OK
                    ENABLE SIM?
                    YES                   NO
                     Note: simulation
                     value needs to be
                     greater than zero
                         to be taken
                      (i.e 0.0001 for a
                        value close to
                             zero)
                                                Introduction | 10
                                                                                                   Model FT3
                                                                                                     Introduction
                                             FLOW PARAMETER 2
                                            CAL SPC PRM EXIT
                                 Level 2                        Level 1
   Calibration Table                                                                             Parameters
                    Flo1 = 0.0
                    CHG PRV NXT EXIT                                       LoFloAlm=0 SCFM       Low Flow Alarm in selected
                                                                           CHG             OK    unit
           velocity in Meter/
            hour for point #1
                                                                           HiTempAlm=0 °F        High Temperature Alarm in
                                                                           CHG              OK   selected unit
                    Volt20 = 1.2479
                    CHG PRV NXT EXIT
                                                                           LoTempAlm=0 °F        Low Temperature Alarm in
                                                                           CHG              OK   selected unit
                    Flo20 = 7046.5
                    CHG PRV NXT EXIT
          Cycle through
          up to 20 settings
                                                    Introduction | 11
Model FT3
Introduction
                                                                                   DISPLAY/PASSWORD
                                                                                  DSP IR PSW EXIT
                     Display 1
                        Line 1
                                 FLo rate
                                  Total
                                            DSP1L2=Temp
                                   Elps     NXT               OK
                     Display 2    Temp
                        Line 1    Alarm
                                 FLo rate
                                  Total
                                            DSP2L1=Alarm
                                   Elps     NXT               OK
                     Display 2    Temp
                        Line 2    Alarm
                                                                   When alternate
                                 FLo rate
                                            DSP2L2=Elps            "ON", flashes
                                  Total
                                   Elps     NXT               OK   between the 2
                                  Temp                             displays
                                  Alarm
                                   On
                                   Off
                                            ALTERNATE=Off
                                            NXT               OK
                                              Introduction | 12
                                                                                                                                                           Model FT3
                                                                                                                                                               Introduction
                                                                                                       DIAGNOSTIC
                                                                                                   CALV ZRO       EXIT
                                                                                                                                                     Level 1
                                                                                                                                            VERIFY ZRO?
                                                                                                                  Display
                                                                                                                                      YES                 NO
                                                                                                                alternates
         Flow Parameter 1 Menu, p. 10                                                                            between
                                                                                                                   the 2
                                                                                                                 screens              Process Zero and
                                                                                                                                      Stable?      EXIT YES
                                                                                                         Displays “Pass” or
                                                                                                               “Fail”                 Diff=x.xxx %
                                                                                                                                        Pass              OK
                                                                      Introduction | 13
Model FT3
Introduction
Fig. 1.7: FT3 Menu Tree - Accessing Data Logger Functions from the Front Panel
                                                                      SET I/O
                                                                 INP OUT LOG EXIT
                                                       ON       Data log = ON
                                                       OFF     NXT                        OK
                       Clear Log?
                                                                                                Level 2
               YES                   NO
                                                                                Level 1
                                                             DATA LOG
                                                         CLR STR TIM EXIT                          DATA LOG
                                                                                               INT STR TIM EXIT
                                                                                          Time will
                                                                                            be set
                                                                                          when the
                                                                                          YES key is
                                                                                           pressed
                                                      Introduction | 14
                                                                                                            Model FT3
                                                                                                               Introduction
Fig. 1.8: Viewing Data Logger Records from the Front Panel
             8/10/13 09:53
             ITot = 7034691.2
                                     F1 Key                F2 Key
             8/10/13 09:53
             ITot = 7034691.2
             8/10/13 09:53
             ITot = 7034691.2
                                              Introduction | 15
Model FT3
Introduction
                                        BrShtDnCnt=0 cnt
  Bridge shutdown detection count                                Display 26
                                                                                                         Reset Total?
                                                                                                         NO                   YES
Resetting Total
                                                            Introduction | 16
                                                                                    Model FT3
                                                                                     Introduction
Welcome
Thank you for purchasing the model FT3 thermal gas mass flow meter from Fox Thermal. The FT3 is
one of the most technically advanced flow meters in the world. Extensive engineering effort has been
invested to deliver advanced features, accurate measurement performance and outstanding reliability.
This instruction manual contains the electrical and mechanical installation instructions as well as
details for programming, maintaining and troubleshooting the meter. This manual is divided into the
following sections: Introduction, Installation, Wiring, Operation, Communications,
Data Logger, Maintenance, Appendix, Definitions, and Index.
			
Theory of Operation
The model FT3 is an innovative thermal mass gas flow meter and temperature transmitter. It is
microprocessor-based and field programmable. The FT3 thermal sensor operates on the law that
gases absorb heat. A heated sensor placed in an air or gas stream transfers heat in proportion
to the stream’s mass velocity. There are two sensor elements. One sensor element detects the
gas temperature and a second element is maintained at a constant temperature above the gas
temperature. The energy transferred from the heated element is proportional to the mass flow
velocity. The FT3 flow meter maintains accurate flow measurement over a large temperature and
pressure range.
Mass Flow
The model FT3 measures mass flow; an advantage over other flow meters which measure volumetric
flow rate. Volumetric flow is incomplete because temperature and pressure are unknown and must be
measured separately. For example, the mass flow of a gas depends on its temperature and pressure.
As temperature and pressure changes, the gas volume changes but not its mass. Therefore a device
measuring mass flow is independent of temperature and pressure changes. The model FT3 provides
a direct measurement of gas flow in mass units (kg/hr, lb/hr), standard units (SCFM, SLPM) or normal
units (NM3/hr, NLPM) with no additional temperature or pressure measurements required.
Calibration Validation
Fox Thermal has developed a method to validate the calibration of the flow meter in the field. This
method is called Calibration Validation and it is made up of two distinct tests: CAL-V™ and Zero CAL-
CHECK™. The goal of Calibration Validation is to provide operators with the ability to verify that the
meter is capturing accurate data at scheduled recalibration times - or at any time - instead of sending
the meter back to the factory for recalibration.
By performing CAL-V™ in the field, operators can verify that the meter is running accurately by testing
the functionality of the sensor and its associated signal processing circuitry. This test can be done
in the pipe and in normal processing conditions. The second test, Zero CAL-CHECK™, ensures the
effectiveness and sensibility of the sensor at a "no flow" condition.
Flow Calibration
Every Fox Thermal flow meter is set to the customer's configuration at the factory using an App ID
which is generated by the on-line configurator. The App ID specifies the gas type, flow range, serial
communication and other settings in the meter. If these settings match the final customer application,
                                      Introduction | 17
Model FT3
Introduction
the meter is ready to use. The Fox Thermal Calibration Lab maintains instrument calibration data on
every flow meter. Calibration files include details on process conditions, customer gas, line size and
other information. All NIST-traceable equipment utilized for the calibration procedure is identified on
the Calibration Certificate, which is sent with every flow meter.
I/O Description
The FT3 features two galvanically isolated 4-20mA analog outputs, one isolated digital output that
can be used for pulse output or alarm, one programmable contact input, and a USB connection for
communication with a computer.
The first 4-20mA output is for flow rate. The second 4-20mA output can be configured either for
flow rate or process gas temperature. Both 4-20mA outputs can be scaled by the user. The pulse
output is programmable to represent flow rate and can be scaled for maximum flow/maximum
frequency, units-per-pulse or pulse-per-units. The maximum frequency is 100 Hz. An isolated 24VDC
output power option is provided for use with these outputs. It can supply a 42mA maximum total load
(do not use for other external devices). FT3 View™ interfaces to the USB port and is a free Fox Thermal
PC-based software program available for download on the Fox Thermal website. FT3 View™ displays
flow meter readings and permits flow meter configuration. Industry standard communication options
are available including HART or Modbus RTU (RS485). Only one of these options can be provided in a
single FT3 flow meter.
         Display Window
                                          F1   F2   F3    F4
     IR (infrared) Buttons
Push Buttons
                                      Introduction | 18
                                                                                              Model FT3
                                                                                                Introduction
                                                                        Standard I/O
       24VDC Input Power
       100-240VAC Optional                                              4-20mA Flow
Contact Input
                                      Introduction | 19
Model FT3
Installation
Installation Scope
This section describes how to install the Fox Thermal model FT3 Flow Meter and how to get started.
Installation methods will vary according to the flow meter type (insertion or inline).
Installation procedures must be performed using a combination of the end user’s best engineering
practices, in compliance with local codes, and with manufacturer’s recommendations.
General Precautions
The following general precautions should be observed:		
        1. Exercise care when handling the flow meter to avoid damaging the probe, sensor or
           enclosure.
        2. Close any unused conduit openings in the enclosure with plugs certified for your
           application.
        3. The enclosure cover must be closed except during configuration or during installation.
        4. Mounting FT3 in direct sunlight can cause the temperature inside the enclosure to increase
           beyond design limits, resulting in failure of LCD display and reduced component life. It
           is recommended that a sunshade be installed to avoid direct sunlight (see maximum
           enclosure operating temperature specification).
        5. Ensure the flow direction indicator points in the direction of flow.
        6. Do not install the FT3 enclosure near an igniter, igniter-controller or switching equipment.
        7. Do not install an external power supply in a cabinet containing an igniter controller or
           switching equipment.
        8. For accurate flow measurement, review flow meter placement instructions before
           installation to ensure a proper flow profile in the pipe.
        9. For safety reasons, Teflon ferrules are only appropriate for applications with pressures of 60
           psig or less. At higher pressures, use of a Teflon ferrule risks unwanted probe movement
           or ejection of the probe from the pipe. For all applications above 60 psig, the standard
           stainless steel ferrule is required.
                                        Installation | 20
                                                                                                                                     Model FT3
                                                                                                                                      Installation
             Irregular
                                                                                                                      INSERTION
             Profile                                                                                       Branch Outlet
                                               Proper         F1   F2   F3   F4
                                                                                                           (installed by
                                               Profile                                                     customer)
FLOW
                                                                                                                           INLINE
             Irregular
                                               Proper
             Profile
                                                              F1   F2   F3   F4
Profile
FLOW
8X Pipe ID 4X Pipe ID
Profile
FLOW
           NOTE!
           • Pipe ID = Inside Diameter
           • The probe diameter is ½"
           • An irregular flow profile will affect sensor accuracy
           • See FC20 Installation Instructions (PN 109193) for more information
                                               Installation | 21
Model FT3
Installation
                                                                          F1
                                                                               F2
                                                                                    F3
                                                                                         F4
                                 F1    F2   F3   F4
F1 F2 F3 F4
                                                      Installation | 22
                                                                                         Model FT3
                                                                                               Installation
       WARNING! Do not force the 0.50" sensor through the 0.531" hole. Forcing it through the
       hole can damage the probe!
6. Verify that the temporary weld of the branch fitting positions the probe window on the pipe's
   centerline.
   • Fig. 2.4 shows an incorrect welding of the branch fitting, causing the 0.50" sensor to be "off
       center".
7. Once the branch fitting is aligned properly, remove the 0.50" sensor from the branch fitting and
   finish welding. Then verify the probe is still aligned with the center of the pipe.
8. Set the depth of the flow meter (see "Fig. 2.5: Insertion Sensor Depth in Pipe" on page 24).
   • Do not tighten compression fitting until proper depth of flow meter is determined.
                                                      INCORRECT
                                                                                 BRANCH, FEMALE,
          CORRECT                   BRANCH, FEMALE,                              3/4" NPT
                                    3/4" NPT
        CENTERED
                                                         OFF CENTER
                                            PIPE                                        PIPE
                               PIPE                                        PIPE
                               CENTERLINE                                  CENTERLINE
                                             Installation | 23
Model FT3
Installation
Installation Depth
The installation depth of the sensor in the pipe is dependent on the pipe size. To get the most
accurate reading, the sensor window must be properly positioned within the pipe.
When installing the latest 45° sensor design, the end of the sensor should be 0.73" (18.5 mm) past the
center of the pipe.
When installing an original sensor design, the end of the sensor window should be 0.87" (22.1 mm)
past the center of the pipe. Reference sensor design figures on page 26.
Review Fig 2.5 below and use the following equations to calculate insertion depth. Insertion depth is
measured from the top of the compression fitting to the bottom end of the probe.
For latest 45° sensor design, Insertion depth = L +D/2 + 0.73"
For original sensor design, Insertion depth = L +D/2 + 0.87"
       CAUTION! For a 1½" pipe, do not tighten compression fitting without 0.2” distance from wall
       or damage to probe will occur.
F1 F2 F3 F4
                                                                                Compression Fitting
                                                                                (Supplied by Fox)
                                                                                Branch Fitting,
                                                                                3/4" NPT Female
                                                                                (Supplied by
                                                    “L”                         Customer)
INSERTION DEPTH
“D/2”
CL
“D”
                                                    Installation | 24
                                                                                          Model FT3
                                                                                           Installation
TOP VIEW
FLOW
-2°
FRONT VIEW
F1 F2 F3 F4
Pipe
FLOW
      NOTE! Some flow meters are shipped with the sensor elements that are offset (see Fig. 2.7).
      Others are shipped with sensors that have equal length elements (see Fig. 2.8). The sensor
      type supplied was selected at the factory to be the best suited for your application. Follow the
      appropriate sensor orientation instructions.
                                                Installation | 25
Model FT3
Installation
+2°
                                              FLOW
                                                     -2°
FLOW
FLOW FLOW
FLOW FLOW
                                        Installation | 26
                                                                                     Model FT3
                                                                                        Installation
          NOTE! Before removing a probe with compression fitting, mark the tube at the back of the
          nut, and mark a line along the nut and fitting body. Use these marks when reinstalling the
          probe. Reference the instructions on p. 28.
          NOTE! When installing a probe with compression fitting that has been tightened previously,
          use the instructions on Page 28.
          CAUTION! Once the compression fitting is locked onto the probe, the probe can be
          removed or rotated, but the insertion depth is locked in place.
          CAUTION! For a 1½" pipe, do not tighten compression fitting without 0.2” distance from
          wall or damage to probe will occur.
          CAUTION! If the stainless steel or Teflon ferrules are not properly tightened, and/or the
          recommended pressure is exceeded, the ferrules can slip on the stainless steel tubing
          causing damage to the meter or bodily harm.
                                        Installation | 27
Model FT3
Installation
Mounting Instructions - Compression Fittings (Inline and Insertion Meters Previously Installed)
In cases where a compression fitting has already been swaged in an inline flow body or an insertion
meter, use the following procedure.
    • Carefully insert the probe with swaged ferrules into the fitting until the front ferrule seats
       against the fitting (see Fig. 2.10).
    • Verify that the probe is installed the correct depth in the pipe (refer to Fig. 2.5).
    • Rotate the nut with a wrench until the probe and nut are in their previously marked positions,
       or you feel a significant increase in resistance (see Fig. 2.10).
    • Tighten the nut slightly (approximately 1/8 turn).
                                        Installation | 28
                                                                                       Model FT3
                                                                                          Installation
1. Remove meter probe from retractor assembly and leave the ball valve open.
2. Install the valve assembly on the pipe, by tightening the Hex Nipple with a 1-1/16" wrench.
  COMPRESSION
       FITTING                                                             RETRACTOR
HEX NIPPLE
       RETAINING
            RING                                                              BRANCH WELD FITTING,
                                                                              3/4" NPT, 316 SST
                                        Installation | 29
Model FT3
Installation
3. Carefully slide the probe through the retractor assembly and through the hole to see if there is
   interference by touching the pipe wall with the end of the probe on the far side or until the probe
   cannot go deeper. Remove the probe. Remove the retractor and rework the hole, if required.
METER
RETRACTOR
4. The installation depth of the sensor in the pipe is dependent on the pipe size. To get the most
   accurate reading, the sensor window must be properly positioned within the pipe.
   When installing the latest 45° sensor design, the end sensor should be 0.73" (18.5 mm) past the
   center of the pipe.
   When installing an original sensor design, the end of the sensor window should be 0.87" (22.1
   mm) past the center of the pipe. Reference sensor design figures on page 26.
                                         Installation | 30
                                                                                            Model FT3
                                                                                             Installation
   Review Fig 2.13 below and use the following equations to calculate insertion depth. Insertion
   depth is measured from the top of the compression fitting to the bottom end of the probe.
   For latest 45° sensor design, Insertion Depth = L + D/2 + 0.73"
   For original sensor design, Insertion Depth = L +D/2 + 0.87"
        CAUTION! For a 1½" pipe, do not tighten compression fitting without 0.2” distance from wall
        or damage to probe will occur.
5. The Retractor Clearance table of Fig. 2.13 lists the space required to remove the meter from the
   retractor. Use the model code of your meter to determine the dimension.
                                                                                  "RC"
                                                                                RETRACTOR
                                                                                CLEARANCE
                                                              MARK ON
                                                              PROBE
                                                                          "L"
                                                                                INSERTION
          BRANCH WELD FITTING,                                                    DEPTH
             3/4" NPT, 316 SST
                                                                      "D/2"
                                    "D"
                                                 RETRACTOR CLEARANCE
                                          CODE         "RC" DIMENSION
                                           15R         27.3" (69.4 CM)
                                           18R         30.3" (77.0 CM)
                                           24R         36.3" (92.2 CM)
                                           30R         42.3" (107.4 CM)
                                           36R         48.3" (122.7 CM)
                                                 Installation | 31
Model FT3
Installation
6. Insert probe back into the retractor to the depth mark and hand-tighten the compression fitting.
7. Verify that flow direction indicator is in line with pipe and in the direction of flow.
                                                                   FLOW DIRECTION
                                                                   ARROW
                 NUT
                                                                   COMPRESSION
                                                                   FITTING
        NOTE! For instructions on how to properly remove and replace the meter from a retractor, please
        refer to "Instructions for Removing and Inserting the Meter from a Pressurized Pipe using the
        Retractor" on page 113.
                                          Installation | 32
                                                                                                           Model FT3
                                                                                                                            Wiring
Wiring Instructions
To wire the FT3 connect the power and signal wires to the terminal blocks according to the label and
instructions on the following pages.
Earth Ground
F1 F2 F3 F4
                                                                                     Red 1
                                                                        TS2
                                                                                     Red2
                                                                              TS3
                                                                  +1          REMOTE Yel 3
                                                              4-20            SENSOR Wh 4
                                                             FLOW
                                                                   -2                Wh 5
                                                                  +3
       Display front                                          4-20
                                                               #2                                      1   2      3
          panel                                                    -4
                                                                                                                      TS1
                                                                  +5
                                                              PULSE
                                                              /ALM
                                                                   -6
                                                                  +7                                              F1
                                                                  IN          TS4 -2 +1
                                                                  -8          24V                    24V, 0.75A
                                                                              OUT
J2
USB port
Wire the FT3 by opening the rear enclosure cover, bringing customer supplied wires in through
the conduit openings and connecting to the terminal blocks. The FT3 has two conduit openings to
maintain separation between AC input power and output signal wiring (see Fig. 3.4 on Page 37 for
more information). To eliminate the possibility of noise interference, use a separate conduit for AC
power and cut all wires short for a minimum service loop.
                                              Wiring | 33
Model FT3
Wiring
Wiring Precautions
      WARNING! 
       • DO NOT OPEN THE ENCLOSURE WHEN ENERGIZED OR AN EXPLOSIVE ATMOSPHERE IS
         PRESENT.
        • All plumbing and electrical installations of flow meters must be in compliance with local
          codes, the end user’s best engineering practices, and manufacturer’s recommendations.
        • Connect earth ground to a chassis ground screw on the inside of FT3 enclosure.
        • An external power disconnect and 16A over-current protection are required for the AC and
          DC powered FT3.
        • Do not install the FT3 enclosure near an igniter, igniter-controller or switching equipment.
        • Do not install an external power supply in a cabinet containing an igniter controller or
          switching equipment.
        • This flow meter contains components that can be damaged by static electricity. You must
          discharge yourself by touching a grounded steel pipe or other grounded steel material prior
          to working inside this flow meter.
        • For the remote sensor option, the serial number of the electronics enclosure must match
          the remote sensor probe.
        • Close any unused conduit openings using suitably certified plugs
Power Wiring
For power wiring, use stranded copper wire, 16 to 20 gauge. If an external 24VDC power source is
used, twisted pair shielded cable is recommended. Supply connection wiring must be rated for at
least 90°C.
Grounding
The enclosure must be properly grounded with a quality earth ground. 16 gauge, stranded wire is
recommended. For US and Canada installation, the internal ground terminal on the enclosure must be
used. Use of the external ground terminal is optional.
Signal Wiring
For signal wiring, the recommended wire gauge is 18 to 22 AWG. Always use twisted pair shielded
cable. The cable shield should not be connected at the flow meter, it should be connected at the
power supply AC ground terminal or instrumentation AC ground. Do not route the power and signal
wires in the same conduit. Power wires must enter left-hand conduit entry. Signal and remote sensor
(where applicable) must enter right-hand conduit entry.
                                           Wiring | 34
                                                                                    Model FT3
                                                                                             Wiring
        NOTE! Serial Numbers: If you have more than one meter, you must ensure that the serial
        numbers of the probe/remote enclosure, electronics enclosure, and flow body match one
        another. These items have been manufactured and claibrated to operate as a unit and connot
        be mismatched.
For remote sensor wiring, five wire shielded cable is required, the recommended wire gauge is 18
AWG. Use Belden number 5306FE or similar type of cable, depending on environment or temperature
requirements of the application. Make sure that the cable length does not exceed 100 feet and the
wire resistance does not exceed one ohm. Connect the cable shield at the remote enclosure end. Do
not connect the shield at the electronics enclosure.
Installation Wiring
Obtain the correct length for the FT3 power and signal wires using one of these methods:
   • Trim the wires to extend 2.5 inches out of the enclosure after the conduit and wires are routed to
     the FT3 (preferred method).
   • Trim the wires to extend 6 inches from the end of the conduit before it is attached to the FT3.
                          Input
                                                                   Signal Wiring,
                          Power
                                                                   Serial Communication
        3x 3/4 inch NPT Female                                     Remote Sensor Wiring (option)
                                               F1   F2   F3   F4
                                          Wiring | 35
Model FT3
Wiring
The enclosure must be properly grounded with a quality earth ground. Sixteen (16) gauge, stranded
wire, is recommended for power and earth ground.
For US and Canada Zones installations, the internal ground terminal on the enclosure must be used.
Use of the external ground terminal is optional.
Earth Ground
                                     Red 1
                        TS2                                                 Earth Ground
                                     Red2
                              TS3
                              REMOTE Yel 3
              4-20
                  +1
                              SENSOR Wh 4
                                                                            24V Return
             FLOW
                   -2
                 +3
                                     Wh 5                                   +24VDC
             4-20
              #2                                       1   2      3
                  -4
                                                                      TS1
                 +5
              PULSE
              /ALM
                  -6
                 +7                                               F1
                 IN           TS4 -2 +1
                 -8           24V                    24V, 0.75A
                              OUT
J2
                                             Wiring | 36
                                                                                           Model FT3
                                                                                               Wiring
The enclosure must be properly grounded with a quality earth ground. Sixteen (16) gauge, stranded
wire, is recommended.
For US and Canada Zones installations, the internal ground terminal on the enclosure must be used.
Use of the external ground terminal is optional.
Earth Ground
                                      Red 1
                         TS2
                                      Red2                                  Earth Ground
                               TS3
                               REMOTE Yel 3
               4-20
                   +1
                               SENSOR Wh 4
                                                                            AC (L)
              FLOW
                    -2
                  +3
                                      Wh 5                                  AC (N)
              4-20
               #2                                      1   2      3
                   -4
                                                                      TS1
                  +5
               PULSE
                   -6
                  +7                                              F1
                  IN           TS4 -2 +1
                  -8           24V                   24V, 0.75A
                               OUT
J2
                                              Wiring | 37
Model FT3
Wiring
      CAUTION! When using the 4-20mA output to control equipment in a failsafe application, see
      the wiring configuration on p. 40.
        NOTE!
        • When using a 12 volt power supply, the load resistor on the 4-20mA output must be
          125 ohms or less to operate properly.
        •   When using 24 volt power, the load resistor is typically 250 ohms. A 250 ohm resistor in
            the 4-20mA circuit will result in a 1 to 5 volt signal to the PLC or DCS.
        •   When using a 24 volt power supply, the load resistor on the 4-20mA output must be
            600 ohms or less.
        •   Some PLC and DCS equipment have built in load resistors, please refer to the technical
            manuals of such equipment.
                                             Wiring | 38
                                                                                   Model FT3
                                                                                            Wiring
      CAUTION! When using the 4-20mA output to control equipment in a failsafe application, see
      the wiring configuration on p. 40.
Fig. 3.6: 4-20mA Output Wiring for Loop Power Provided by FT3
        NOTE!
        • This wiring option is only available with the isolated 24V output power option.
        •   When using a 12 volt power supply, the load resistor on the 4-20mA output must be
            125 ohms or less to operate properly.
        •   When using 24 volt power, the load resistor is typically 250 ohms. A 250 ohm resistor in
            the 4-20mA circuit will result in a 1 to 5 volt signal to the PLC or DCS.
        •   When using a 24 volt power supply, the load resistor on the 4-20mA output must be
            600 ohms or less.
        •   Some PLC and DCS equipment have built in load resistors, please refer to the technical
            manuals of such equipment.
                                                    Wiring | 39
Model FT3
Wiring
      CAUTION! Configure the FT3 with the following setup when using the 4-20mA output to
      control equipment in a failsafe application.
The System Alarm output is designed to allow current to flow during normal operation and interrupts
current when power to the meter is lost or in a System Alarm condition.
In the 4-20mA Failsafe Wiring configuration of Fig. 3.7, the 4-20mA signal goes to 0mA if power to
the FT3 is lost or a System Alarm occurs.
Fig. 3.7: 4-20mA Failsafe Wiring and Range of 4-20mA Output for NAMUR Alarm
                                                                         NAMUR
                                                                          Range
                               FT3            Customer PLC or DCS         Alarm                         21 mA
                                                                                                        20 mA
                                     Red 1
                                                                                     Normal Operation
                        TS2
                                     Red2    +24VDC
                                                                          Working Range
                              TS3
                  +1          REMOTE Yel 3
              4-20            SENSOR Wh 4
             FLOW
                   -2                Wh 5
                 +3
             4-20
              #2 -4                                    1   2   3
                                                                   TS1
                 +5
              PULSE
              /ALM
                 -6
                                                4 to 20mA FLOW RATE                                     4 mA
                 +7                                         F1
                 IN           TS4 +1 -2                                                                 3.6 mA
                 -8           24V               24VDC
                                                   24V, Return
                                                        0.75A
                                                                         NAMUR
                              OUT
                                                                          Range
                                                                          Alarm
J2
0 mA
                                                 Wiring | 40
                                                                                                    Model FT3
                                                                                                        Wiring
J1
        NOTE!
        • The FT3 Pulse/Alarm output is typically used to drive digital circuitry or solid-
          state relays. The output of a solid state relay may, in turn, operate loads such as
          electromechanical relays or alarm indicators.
        •   The maximum load current of the Pulse/Alarm output is 20mA. Choose a load
            resistance that provides approximately 10mA with the power supply operating voltage.
        •   When the output is configured for Alarm and an alarm is not active, the output
            will be on (0 volts output). When an alarm is active, the output will be off
            (24 volts output).
                                                   Wiring | 41
Model FT3
Wiring
J1
        CAUTION!
        Do not exceed 42 mA total load on the 24V Output TS4 (ie including 4-20mA outputs).
        NOTE!
        • This wiring option is only available with the isolated 24V output power option.
        •   The FT3 Pulse/Alarm output is typically used to drive digital circuitry or solid-
            state relays. The output of a solid state relay may, in turn, operate loads such as
            electromechanical relays or alarm indicators.
        •   The maximum load current of the Pulse/Alarm output is 20mA. Choose a load
            resistance that provides approximately 10mA with the power supply operating voltage.
        •   When the output is configured for Alarm and an alarm is not active, the output
            will be on (0 volts output). When an alarm is active, the output will be off
            (24 volts output).
                                                    Wiring | 42
                                                                                  Model FT3
                                                                                           Wiring
When the 2 gas curve option is ordered, the switch can be used to switch between curves.
J1
                                         Wiring | 43
Model FT3
Wiring
The Tx/Rx+ signal connects to pin 1, Tx/Rx- connects to pin 2 and communication common to pin 3,
and the cable shield to pin 4 as shown in Fig. 3.11.
Termination Resistor
Connect a termination resistor across the receive/transmit signals of the last device on the RS485
communication line. To connect the 121 ohm termination resistor on the FT3, set JP1 to the TERM
position.
Disconnect the termination resistor on all other external RS485 devices. The termination resistor of
the FT3 is disconnected by setting JP1 to the NC (Not Connected) position.
                        Tx/Rx (+)
                        Tx/Rx (-)
          Communication Common
                    Cable Shield
        NOTE!
         • JP1 jumper will either be in the NC (Not Connected) or TERM (terminated) position. It
            should be in the terminated position on the last meter in the series.
                                                     Wiring | 44
                                                                             Model FT3
                                                                                     Wiring
                                       Wiring | 45
Model FT3
Wiring
Fig. 3.13: HART 4-20mA Output Wiring, Loop Power Provided by FT3
                                         Wiring | 46
                                                                                 Model FT3
                                                                                         Wiring
A handheld HART communicator can be connected to test points TP1 (+) and TP2 (-) with clip leads or
to the 4-20mA terminal block.
                                         Wiring | 47
Model FT3
Wiring
Remote Wiring
Remote wiring is only necessary when the remote sensor option has been ordered.
           Input
           Power
                           F1   F2   F3   F4
Five wire shielded cable required. The shielded cable should be run through a separate grounded
steel conduit (no other cables or wires in the conduit). If you are using your own cable, make sure
that the cable length does not exceed 100 feet and has a wire resistance that does not exceed one
ohm (18 AWG recommended).
         NOTE! Do not connect the cable shield at the electronics enclosure end. Connect the cable
         shield at the remote sensor terminal.
         NOTE! The enclosures must be properly grounded with a quality earth ground. 16 gauge,
         stranded wire is recommended.
Use an extension cable to connect the terminals of the remote sensor enclosure to connector TS3
located behind the rear cap of the electronics enclosure as shown in Fig. 3.16 and Table 3.1 on the
following page.
       NOTE! Serial numbers: If you have more than one meter, you must ensure that the serial
       numbers of the probe/remote enclosure, electronics enclosure, and flow body match one
       another. These items have been manufactured and calibrated to operate as a unit and cannot
       be mismatched.
                                               Wiring | 48
                                                                                                                                               Model FT3
                                                                                                                                                         Wiring
                                                                                                   Shield                                      BLK
                                                                                                                 #4                  #2
                   RED             2
  5
                             TS3
                                            1   2   3
                                                             TS1
                                                        F1
              -2    +1
        TS4
        24V                                 24V,0.75A
        OUT
                                                                                                                                           Black Dot Denotes Pin #1
                                       J2
Sensor Wires
Remote Enclosure
        NOTE! Wire colors listed here represent the wire colors of cables supplied by Fox Thermal.
        Colors may vary if customer is supplying their own cable.
                         1                                                Red                  1                                    Red
                         2                                               Black                 2                                    Red
                         3                                               Brown                 3                                   Yellow
        No Connection                                                    Shield                4                                   Green
                         4                                               White                 5                                   White
                         5                                               Green                 6                                   White
                                                                                  Wiring | 49
Model FT3
Operation
Start Up Sequence
The program automatically enters the Run/Measure mode after power up. The screen will show the
software version of the FT3 during power up.
USB Interface
The USB interface is a standard feature which allows communication with a PC to monitor readings
and configure settings. FT3 View™, is a free application program from Fox Thermal that connects to
the USB interface and allows data monitoring, configuration setting, data logging to Excel, and an
option to save and recall FT3 configuration data.
The FT3 display is a 2 line x 16 character display with 4 mechanical buttons and 4 IR (infrared) keys.
The mechanical buttons of the configuration panel can be accessed by removing the FT3 cap. Be sure
to replace the cap after you are done configuring the FT3.
The IR keys and mechanical buttons perform the same function, but the IR keys can be used without
opening the cover. The IR keys can be calibrated for better operation in the field or disabled (p. 89)
when the meter is used in snow or ice in order to avoid false key detection.
                   Display Window
                                                              F1    F2    F3    F4
               IR (infrared) Buttons
Push Buttons
                                        Operation | 50
                                                                                         Model FT3
                                                                                          Operation
Pressing the F1 and F2 keys at the same time enters the Log Menu and Engineering Menu screens.
Pressing the F3 and F4 keys at the same time brings up the Reset Total screen prompt.
F1 F2
F1 F2
                                                        (Fixed screen)
        Display #4          Set Parameter?
                            No                    Yes
F2 F4
                                            Operation | 51
Model FT3
Operation
There are nineteen (19) screens (10 - 28) to view meter data:
Screen 10 - Flow rate measured by the meter, CSV of the sensor measurement circuit.
Screen 11 - Average CSV of the sensor measurement circuit, velocity flow in user-selected unit.
Screen 12 - Sensor filtered average voltage, velocity in meter/hour.
Screen 13 - TSI average count, TSV average count.
Screen 14 - TSI in volts, TSV in volts.
Screen 15 - TSI current in Amp, TSI resistance in ohm.
Screen 16 - RTD9 count, gas temperature in degrees C.
Screen 17 - Channel 1 4-20mA current loop count, channel 2 4-20mA current loop count.
Screen 18 - Frequency output count, active alarm codes.
Screen 19 - High and low flow alarm settings.
Screen 20 - High and low temperature alarm settings.
Screen 21 - Elapsed time of meter operation and the status in hexadecimal.
Screen 22 - FT3 electronics firmware version, optional display firmware version.
Screen 23 - Total number of power cycles, number of errors in total flow measurement.
Screen 24 - TSI resistance in ohm, RTD9 resistance in Ohm.
Screen 25 - Most recent CAL-V™ value, CAL-V™ last verify value.
Screen 26 - Bridge shutdown detection count.
Screen 27 - Zero CAL-CHECK™ pipe reference value, most recent Zero CAL-CHECK™ test difference.
Screen 28 - Zero CAL-CHECK™ bottle reference value, most recent Zero CAL-CHECK™ test difference.
                                        Operation | 52
                                                                                     Model FT3
                                                                                        Operation
      VALUE = 0.91234
      CHG			               OK
F1 F2 F3 F4
Press CHG (F1) key to change the value, OK (F4) to accept the value.
      VALUE = 0.91234
      UP    DN      NXT    OK
F1 F2 F3 F4
Press the UP (F1) or DN (F2) key to select a new digit or character, the cursor points to the selected
digit. Press NXT (F3) to select the next digit and OK (F4) to accept the entry.
F1 F2 F3 F4
Press NXT (F1) key repeatedly until the correct selection is made and OK (F4) key to accept the entry.
        SET PARAMETERS ?
      No                   Yes
F1 F2 F3 F4
Press YES (F4) and the following screen will prompt user to enter password:
      PASWD:_
      UP    DN     NXT     OK
F1 F2 F3 F4
Enter the correct password, then follow the instructions for changing a value as specified above. The
default Level 1 password is “1234”.
                                        Operation | 53
Model FT3
Operation
If the wrong password is entered, the message “Wrong Password” will display and then return to the
programming entry screen.
           SET PARAMETERS
     I/O      FLO   DSP   EXIT
F1 F2 F3 F4
This is the screen for the programming mode. Press EXIT (F4) repeatedly until “Normal Mode” is
seen briefly to exit the programming mode.
        SET          I/O
     COM    I/O     420      EXIT
F1 F2 F3 F4
In this screen press 420 (F3) (screen appearance may vary according to options).
         SET  4-20         mA
      CH1 CH2                EXIT
F1 F2 F3 F4
     20 mA = 3500 SCFM
     CHG                     OK
F1 F2 F3 F4
Enter the value for the 20mA and press OK (F4) key to accept the setting.
       NOTE! When the flow rate exceeds the programmed value for the 20mA set point, the analog
       output will stay at 20mA and an alarm code will be generated.
                                        Operation | 54
                                                                                     Model FT3
                                                                                            Operation
     4 mA = 0 SCFM
     CHG                    OK
F1 F2 F3 F4
The following menu item allows the user to select an alarm level on the 4-20mA output when a
serious issue is detected that is preventing the calculation of a correct flow value
The options are:
  • mA Fault=3.6 mA (Force the 4-20mA signal to 3.6mA on alarm)
  • mA Fault=21 mA (Force the 4-20mA signal to 21mA on alarm)
  • mA Fault=Not use (4-20mA signal alarm fault not used)
        CAUTION! When using the 4-20mA output to control equipment in a failsafe application, use
        the wiring configuration and set the Pulse/Alarm Output to System alarm as shown in "Alarm
        Output" on p. 58.
After setting the 4mA output value, choose the mA fault value:
F1 F2 F3 F4
The following events will set the output to 3.6mA or 21mA if the alarm level is selected:
 • Sensor resistance above high limit
 • Bridge Shutdown
When the 4-20mA output is wired through the System Alarm, the following cause the output to go to
0mA:
 • Power to the Microprocessor is lost
 • Sensor or electronics failure
                                          Operation | 55
Model FT3
Operation
To exit the programming mode, press (F4) repeatedly until Normal Mode is seen.
Select CH2 (F2) to program channel 2. Channel 2 is programmable for flow (CH2=Flow) or
temperature (CH2=Temp).
      CH2 = Temp
      NXT                  OK
F1 F2 F3 F4
Press NXT (F1) to select Flow or Temperature and then press OK (F4).
      20 mA = 300 º F
      CHG                  OK
F1 F2 F3 F4
Enter the value for the 20mA and press OK (F4) key to accept the setting.
     4 mA = 10 º F
     CHG                   OK
F1 F2 F3 F4
Press (F4) repeatedly until “Normal Mode” is seen briefly to exit the programming mode.
Pulse/Alarm Output
From the SET PARAMETERS menu, press I/O (F1), then I/O (F2).
            SET      I/O
      INP    OUT           EXIT
F1 F2 F3 F4
Press OUT (F2) to select output. The following screen will show:
     OUT = Frequency
     NXT                   OK
F1 F2 F3 F4
Press NEXT (F1) to cycle through output options until you have the selection for "OUT=Frequency"
and press OK (F4).
                                          Operation | 56
                                                                                      Model FT3
                                                                                           Operation
     FREQUENCY OUTPUT
      P/U   U/P   FEQ      EXIT
F1 F2 F3 F4
Use P/U (F1) to enter pulse per unit, U/P (F2) for unit per pulse or FEQ (F3) to enter the flow and
maximum frequency to scale the frequency output.
        NOTE! When data is entered with any of the three described methods, the other values will
        be re-calculated according to the settings.
     PLS/UNT = 2
     CHG                    OK
F1 F2 F3 F4
Press CHG (F1) to change the setting and then OK (F4) to accept entry. The value entered is in pulse
per selected flow unit total (for example, 2 pulses per SCF).
      UNT/PLS = 0.5
      CHG                  OK
F1 F2 F3 F4
Press CHG (F1) to change the setting and then OK (F4) to accept entry.
The value entered is in unit per pulse (for example. 0.5 flow unit total per pulse)
                                          Operation | 57
Model FT3
Operation
     MaxFreq=100 Hz
     CHG                     OK
F1 F2 F3 F4
     MaxFlo=5000 SCFM
     CHG                     OK
F1 F2 F3 F4
        NOTE! If the flow rate exceeds the maximum pulse rate (frequency), the output will stay at
        100 Hz and the FT3 will issue an alarm code.
Alarm Output
To program the Alarm output, press I/O (F1) key from the SET PARAMETERS menu. Then select I/O
(F2) and the screen will show:
            SET       I/O
      INP    OUT             EXIT
F1 F2 F3 F4
     OUT = HiFloAlm
     NXT                     OK
F1 F2 F3 F4
Then press NXT (F1) to select the correct alarm and press OK (F4).
      Selections are:
           Not used
           Frequency
           HiFloAlm = High Flow Alarm
           LoFloAlm = Low Flow Alarm
           HiTempAlm = High Temperature Alarm
           LoTempAlm = Low Temperature Alarm
           System Alm = System Alarm
                                      Operation | 58
                                                                                    Model FT3
                                                                                        Operation
When the output is set to Alarm and there is no alarm condition, the output will be on (0 volts). When
an alarm is active, the output is turned off (24 volts).
     HiFloAlm=500 SCFM
     CHG                   OK
F1 F2 F3 F4
Enter the value for the limit by pressing CHG (F1) and then OK (F4). A value of 0 disables the alarm.
        NOTE! There is only one output to operate as a pulse output or an alarm output. Both
        cannot operate at the same time.
           INP=Not Used
     NXT                   OK
F1 F2 F3 F4
Press NXT (F1) until the correct selection is shown and then press OK (F4) to accept the setting.
       Selections are:
           Not used
           Tot Reset = Reset the totalizer
           Switch Crv = Switch between calibration curve 1 and curve 2 (only if 2 gas curve ordered)
                                       Operation | 59
Model FT3
Operation
      SWITCH TO CRV 1?
       NO                  YES
F1 F2 F3 F4
     PASSWORD:_
      UP  DN    NXT        OK
F1 F2 F3 F4
After entering a valid password, a brief confirmation message will be displayed for 1 second:
SWITCH TO CRV 1
F1 F2 F3 F4
     INP=SWITCH CRV
      NXT                  OK
F1 F2 F3 F4
        NOTE! Helpful hint: From normal display mode, press F4 to view the current gas curve
        selection.
                                        Operation | 60
                                                                                     Model FT3
                                                                                         Operation
Two totalizers (Total 1 and Total 2) and two elapsed time counters are available on the display and
through the USB serial communication. The reset function will reset all totalizers and elapsed time
counter to zero.
In the event of a power failure, the software will remember the last curve in use. Upon powering up
again, the FT3 unit will continue to use that curve.
Switching between gas curves will require a password unless the password is set to "0", which disables
it. The calibration certificates for order with 2 gas curves will identify which gas is Gas 1 and Gas 2.
When measuring in mass units, a density value must be entered for each gas curve.
      DNS1 = 0.9876
      CHG                  OK
F1 F2 F3 F4
DNS1 is the density associated with curve 1. Change it as needed and press OK (F4).
     DNS2 = 1.2876
     CHG                   OK
F1 F2 F3 F4
DNS2 is the density associated with curve 1. Change it as needed and press OK (F4).
     20mA = 500SCFM
     CHG                   OK
F1 F2 F3 F4
20mA is the upper limit associated with curve 1. Change it as needed and press OK (F4).
                                        Operation | 61
Model FT3
Operation
     4mA = 0
     CHG                   OK
F1 F2 F3 F4
4mA is the lower limit associated with curve 1. Change it as needed and press OK (F4).
     20 maCv2=450 SCFM
     CHG               OK
F1 F2 F3 F4
20 maCv2 is the upper limit associated with curve 2. Change it as needed and press OK (F4).
    4 maCv2=0
    CHG                    OK
F1 F2 F3 F4
4 maCv2 is the lower limit associated with curve 2. Change it as needed and press OK (F4).
             SET I/O
     COM     I/O     420   EXIT
F1 F2 F3 F4
     Comm=Modbus
     NXT                   OK
F1 F2 F3 F4
                                       Operation | 62
                                                                                   Model FT3
                                                                                       Operation
Display Setup
There are four display screens that you can cycle through in normal operating mode (see Fig. 4.2 on
p. 51). Two of the four display screens are fixed and cannot be changed (Display 3 and Display 4).
The other two screens are programmable to show the information that you prefer.
           Display #1			                          Display #2
      DSP1L1                        DSP2L1
      DSP1L2                        DSP2L2
F1 F2 F3 F4 F1 F2 F3 F4
      Selections are:
             DSP1L1 = Display 1, Line 1
             DSP1L2 = Display 1, Line 2
             DSP2L1 = Display 2, Line 1
             DSP2L2 = Display 2, Line 2
     DISPLAY/PASSWORD
     DSP     IR   PSW       EXIT
F1 F2 F3 F4
F1 F2 F3 F4
     ALTERNATE = Off
     NXT                    OK
F1 F2 F3 F4
                                          Operation | 63
Model FT3
Operation
This menu allows you to alternate between menu display 1 and 2 every few seconds.
      Selections are: On or Off
Press OK (F4) to accept selection. Press EXIT (F4) repeatedly until “Normal Mode” is seen briefly to
exit the programming mode.
Password
There are two user level passwords, only Level 1 is programmable and gives access to all the normal
settings. The second password is used to allow access to calibration settings.
Default Level 1 password is “1234”, and Level 2 password is “9111”. The Level 1 programmable
password can be disabled by setting it to “0”.
From the SET PARAMETERS menu press DSP (F3) to select the DISPLAY menu.
      DISPLAY/PASSWORD
      DSP     IR   PSW    EXIT
F1 F2 F3 F4
     PASSWD = 1234
     CHG                  OK
F1 F2 F3 F4
Press OK (F4) to accept new data and exit programming by pressing EXIT (F4) key repeatedly until
out of the programming mode.
Units Settings
This menu is used to set the units for mass flow, temperature, and pressure as well as the setting
of reference temperature and reference pressure. These values will be set at Fox Thermal using
information supplied by the customer. These values can be changed to match a new application. The
units setting is accessed from the SET PARAMETERS menu. To access the Unit Settings Menu:
                                         Operation | 64
                                                                                       Model FT3
                                                                                          Operation
            SET PARAMETERS
     I/O      FLO    DSP   EXIT
F1 F2 F3 F4
        FLOW PARAMETERS 1
      DGN UNT     PRM     EXIT
F1 F2 F3 F4
     FLO = SCFM
     NXT                     OK
      F1       F2     F3      F4
                               				
Press NXT (F1) to change selection and OK (F4) to accept.
Flow Units
   Selections for flow units are:
       SCFM             KG/M              LBS/D           SM3/H           MSCFD (MCFD)
       SCFH                KG/S           NLPH            SM3/D           MMSCFD (MMCFD)
       NM3/H               LBS/H          NLPM            NM3/D           MCFD (MSCFD)
       NM3/M               LBS/M          NLPS            SLPM            MMSCFM (MMCFM)
       KG/H                LBS/S          SM3/M           SCFD            MT/H
       SMPS                NMPS           SFPM
NOTE! The totalizer must be reset immediately after changing the flow units setting.
           NOTE! The totalizer (total flow measured) will roll over when reaching a certain value. The
           maximum value is dependent on the flow units selected (see Totalizer Rollover p. 74).
           WARNING! The FT3 re-calculates area, 4 and 20mA values, maximum flow for the pulse
           output and zero flow cutoff when changing flow units except for velocity units. When going
           to or from velocity units, the FT3 will not recalculate these values and these values must be
           re-entered manually.
                                          Operation | 65
Model FT3
Operation
Temperature Units
After pressing OK (F4) to accept the Flow unit the display will prompt for the temperature unit
setting:
F1 F2 F3 F4
Reference Temperature
After pressing OK (F4) to accept the temperature unit setting, the display will prompt for temperature
reference in selected unit.
     TmpRef = 60 °F
     CHG                   OK
F1 F2 F3 F4
Pressure Units
After pressing OK (F4) to accept the reference temperature, the display will prompt for the reference
pressure unit selection:
F1 F2 F3 F4
Reference Pressure
After the pressure unit selection is made, the display will show a menu to enter the reference pressure:
     PresRef= 14.7
     CHG                   OK
F1 F2 F3 F4
                                        Operation | 66
                                                                                    Model FT3
                                                                                        Operation
        NOTE! The parameters in this menu are set to the customer specifications at the factory. They
        should only be changed when changing the application of the flow meter.
            SET PARAMETERS
      I/O     FLO    DSP   EXIT
F1 F2 F3 F4
The FLOW PARAMETER 1 menu is accessed from the SET PARAMETERS menu by pressing FLO (F2):
        FLOW PARAMETER 1
     DGN   UNT   PRM EXIT
F1 F2 F3 F4
         FLOW PARAMETER 2
      CAL   SPC   PRM    EXIT
F1 F2 F3 F4
        NOTE! The CAL and SPC function key will only appear and be accessible from a Level 2
        password.
Then press PRM (F3). This will move into settings for flow cutoff, pipe diameter, and filter value.
These settings will be followed by the high and low alarm settings for flow rate and/or temperature.
F1 F2 F3 F4
Enter the value for the flow cutoff and then press OK (F4). When the flow rate falls below the flow
cutoff, the flow meter will display a flow value of zero.
                                       Operation | 67
Model FT3
Operation
Pipe Area
Enter the pipe area in square meters or square feet and then press OK (F4). Use square meter for
metric flow unit selection.
F1 F2 F3 F4
Filter Value
The filter value is entered in seconds. The allowable time constant range is 0.8 to 10 seconds. The
filter time interval is proportional to the dampening.
The filter value is also referred to as a dampening factor and is used to quiet the readings. The filter
value is an exponential filter that dampens the noise and is used as follows:
        Flow Value = (FA * new value) + (FB * average)
           Where FA = filter value, FA + FB is equal to 1.0
A lower filter value will increase dampening of the flow rate and smooth the reading. A lower filter
value will also slow the meter's response. For example, if we enter a filter of 0.8, the weight ratio for
the new average is:
        New average = (80% new sample) + (20% last average)
          Filter range is 0.01 to 1.0, 0.01 being a high filter value and 1.0 = no filter.
F1 F2 F3 F4
                                               Operation | 68
                                                                                    Model FT3
                                                                                        Operation
To set the parameters for a high flow rate alarm, press CHG (F1):
F1 F2 F3 F4
To set the parameters for a low flow rate alarm, press CHG (F1):
F1 F2 F3 F4
To set the parameters for a high temperature alarm, press CHG (F1):
     HiTmpAlm = 200 F
     CHG                   OK
F1 F2 F3 F4
                                        Operation | 69
Model FT3
Operation
To set the parameters for a high temperature alarm, press CHG (F1):
     LoTmpAlm = 20 F
     CHG                   OK
F1 F2 F3 F4
Simulation
This menu allows for simulation of flow rate and temperature. It should only be used for testing
and demonstration purposes. Make sure to return all of these simulation values to zero, before
returning to the normal mode of operation.
        CAUTION! If the 4-20mA and/or the pulse/alarm outputs are connected to controllers, set
        the controllers to “manual” to ensure that the simulated signals do not cause false controller
        action.
The DIAGNOSTIC menu used for Simulation is accessible from the SET PARAMETERS menu by
pressing FLO (F2):
        FLOW PARAMETER 1
     DGN   UNT   PRM     EXIT
F1 F2 F3 F4
F1 F2 F3 F4
F1 F2 F3 F4
                                       Operation | 70
                                                                                  Model FT3
                                                                                     Operation
F1 F2 F3 F4
F1 F2 F3 F4
F1 F2 F3 F4
F1 F2 F3 F4
F1 F2 F3 F4
        NOTE! This value is used to simulate the Current Sense Voltage (CSV) and should be set to
        zero for normal mode.
                                          Operation | 71
Model FT3
Operation
      ENABLE SIM?
      YES                   NO
F1 F2 F3 F4
Press YES (F1) to start the simulation mode, otherwise press NO (F4). Upon pressing either key, the
program will return to the FLOW PARAMETER 1 screen.
Calibration Parameters
This menu allows changing the factory calibrated setting of the flow meter and is accessible with a
Level 2 password. Calibration parameter values are set for temperature and pressure at 0 degree C
and 760 mmHg. These settings should normally never be changed except by Fox Thermal personnel
at the factory.
This calibration menu is entered from the SET PARAMETERS menu by pressing FLO, PRM, and CAL.
     FLOW PARAMETER 2
     CAL SPC    PRM EXIT
F1 F2 F3 F4
              CAL TABLE
     TB1      ---  ---      EXIT
F1 F2 F3 F4
     Volt1 = 0.92367
     CHG     PRV NXT        EXIT
F1 F2 F3 F4
     Flo1 = 0
     CHG PRV         NXT    EXIT
F1 F2 F3 F4
Use the CHG (F1) key to change the entry, PRV (F2) to move to the previous entry, NXT (F3) to move
to the next entry and EXIT (F4) to return.
                                         Operation | 72
                                                                                         Model FT3
                                                                                           Operation
Pressing the NXT (F3) key will show the data point voltage and then mass velocity and then go to the
next data point. The number after Volt (i.e., Volt1) or Flo (i.e., Flo1) indicated the data point number.
The calibration table can hold up to 20 data pair points. Each data point has a voltage and mass
velocity associated with it.
K Factor
The K Factor allows the user to adjust the meter’s calibration. The flow meter increases the calculated
flow rate by the K Factor. This results in a direct scaling of the meter’s output across the entire full
range.
The K Factor parameter is accessed from the FLOW PARAMETER 2 menu by entering a Level 2
password “9111” and pressing the SPC key (F2).
         FLOW PARAMETER 2
      CAL   SPC   PRM EXIT
F1 F2 F3 F4
     K fact=0%
     CHG                    OK
F1 F2 F3 F4
Press CHG (F1). Add the correction factor and press OK (F4).
Restore Database
In case of user error, the ability to restore the meter to the original factory settings can be achieved in
this menu. The display will show:
      RESTORE DATABASE?
      YES                   NO
F1 F2 F3 F4
Press YES (F1) ONLY if you want to restore your database to the initial factory setting that the meter
was shipped with. All current user-entered settings will be overwritten. The green LP3 LED will flash at
a faster pace until the recall is performed. The "RESET CRC" screen will follow "RESTORE DATABASE".
Upon pressing NO (F4), an option to reset the NVRAM CRC will follow.
                                          Operation | 73
Model FT3
Operation
Reset CRC
If the NVRAM CRC check fails (Error Code 36), the programmed settings values will need to be verified
and corrected before clearing the error. Call Fox Thermal Customer Service if you need assistance.
         RESET CRC?
         YES                   NO
F1 F2 F3 F4
Press YES (F1) ONLY if you want to reset the CRC and generate a new CRC value.
         RESET TOTAL ?
         NO                   YES
F1 F2 F3 F4
Press YES (F4) and enter password to reset total and elapsed time. Press NO (F1) to cancel.
Totalizer Rollover: The FT3 has an automatic roll-over function. The total flow count of the FT3 will
roll over after 99,999,999,999. Except for:
        MSCFD: 		            999,999,999
        MMSCFM: 		           9,999,999
        MMSCFD: 		           999,999
Calibration Validation
Operators can verify the meter is running accurately in the field by performing two simple tests.
The first test, CAL-V™, tests the functionality of the sensor and its associated signal processing
circuitry and can be done in the pipe and in normal processing conditions.
The second test, Zero CAL-CHECK™, ensures the repeatability and cleanliness of the sensor and can be
performed in two ways: In situ or Out of Pipe. See Fig. 4.4 to understand Calibration Validation with
these two tests.
                                         Operation | 74
                                                                                               Model FT3
                                                                                                   Operation
Fox Thermal has developed Calibration Validation, using the CAL-V™ and Zero CAL-CHECK™ tests to
help our customers avoid sending the meter back for annual or biennial re-calibrations.
During the CAL-V™ calibration validation test, the microprocessor adjusts current to the
sensor elements and determines the resulting electrical characteristics. Data within established
tolerances confirms the meter is accurate.
         NOTE! If the CAL-V™ test is performed using the Fox Thermal FT3 View™ Software, at the
         completion of the test, a CAL-V™ Certificate may be printed for a record of the test. This
         certificate will display a pass/fail result.
                                            Operation | 75
Model FT3
Operation
       FLOW PARAMETER 1
     DGN   UNT   PRM    EXIT
F1 F2 F3 F4
                DIAGNOSTIC
     SIM        TST             EXIT
F1 F2 F3 F4
                DIAGNOSTIC
     CALV        ZRO            EXIT
F1 F2 F3 F4
                 CAL-V
      VER                       EXIT
F1 F2 F3 F4
Press VER (F1) to get to the go to zero screen. The display will show:
      Flo: Go to Zero
      NXT               EXIT    OK
F1 F2 F3 F4
To select what the flow output will do during a CAL-V™, choose from these options:
   • Go to Zero: Flow output will be zero during the test (i.e. 4mA)
   • Hold Value: Flow will hold last value during the test
NOTE! The FT3 will stop measuring flow when performing this test.
     Take Control
     off-line            EXIT   OK
F1 F2 F3 F4
                                          Operation | 76
                                                                                         Model FT3
                                                                                             Operation
        WARNING! If you are using closed loop control, the system needs to be taken off-line during
        the test.
F1 F2 F3 F4 F1 F2 F3 F4
This test will take up to 4 minutes (less time if there is flow) and will show the Cal value changing as
the power to the sensor is adjusted. The T=xxx is a count down timer indicating how much time is left
to finish the test. A “Please Wait” message will be flashing on and off on line 2 during this test.
If a "Fail" result is displayed after repeating the test, please call Fox Thermal Service at (831) 384-4300
for assistance.
       CAL-V = 0.251
       Pass                   OK
F1 F2 F3 F4
        CAUTION!
        • The CAL-V™ test is valid for checking the calibration accuracy of flow meters installed in the
          applications for which it was calibrated including the gas/gas mixture, calibration range, and
          pipe size shown on the calibration certificate.
        • For applications with temperature exceeding 250°F (121°C), CAL-V™ test results may vary.
        • Periodic inspection for damage and cleaning of the sensor elements is required.
                                          Operation | 77
Model FT3
Operation
takes less than 5 minutes to complete. At the conclusion of the test, a Pass or Fail message will be
displayed. Press F4 at the conclusion of the test to return to normal measuring mode or to terminate
the test.
		
There are a few ways that Zero CAL-CHECK™ is different than CAL-V™:
• The Zero CAL-CHECK™ test must be performed at a "no flow" condition (ie zero flow)
• If the Zero CAL-CHECK™ test is to be performed in the pipe, the field baseline must be set before
   an actual test can be performed (see "Setting Field Baseline for In Situ Zero CAL-CHECK™ Tests" on
   p. 79).
• If the Zero CAL-CHECK™ test is to be performed out of the pipe, the meter must be set upside-
   down (probe pointing up) and the PVC sensor protector that the meter was shipped with must be
   placed back over the sensor to achieve the factory baseline that the meter has been set with.
With this configuration, the meter must be removed from the process, the test performed, and then
the meter returned to the process after testing has been completed.
Due to the high sensitivity of the PowerPro™ sensor, it is necessary to isolate the sensor once the
meter has been removed from the pipe. Therefore, Fox Thermal provides a sensor cover when the
meter is shipped to the customer. An alternative to the sensor cover is to use a bottle or other closed
container in order to isolate the sensor and achieve the "no flow" condition necessary to perform the
Zero CAL-CHECK™ test.
                                         Operation | 78
                                                                                       Model FT3
                                                                                           Operation
Fig. 4.5: Fox Thermal-Supplied PVC Sensor Protector vs. Plastic Bottle
       NOTE! If you need information on the installation of the Fox Thermal retractor, refer to
       "Installation of a New Retractor Assembly" on page 29.
                                         Operation | 79
Model FT3
Operation
F1 F2 F3 F4
     PAGE 10                            Operation | 80
                                                                                     Model FT3
                                                                                        Operation
        WARNING! SYSTEM MAY BE UNDER HIGH PRESSURE. Do not attempt to remove meters
        from a pipe pressurized above 60 psig without first relieving pressure in the pipe.
        WARNING! When removing the flow meter, be sure to hold the electronics enclosure firmly
        by hand before unscrewing the compression fitting nut. Failure to do this will allow the
        pressure in the pipe to suddenly and rapidly force the meter from the pipe potentially causing
        serious injury. The meter could also be damaged resulting in a loss of gas from the pipe. The
        force required to hold the meter will be 0.20 times the pipe pressure. If you are unsure of your
        ability to hold the meter for any reason, do not loosen the compression fitting nut.
Loosen the compression nut of the compression fitting using two 7/8" wrenches. Once loosened, the
probe will be able to slide out (see Fig. 4.8 below).
                                                                ch
                                                              en
                                                            wr
                                                         8”
                                                       7/
Compression Nut
                  Adjacent Hex
                                         13
                                            /16
                                               ”w
                                                 ren
                                                ch
With one hand supporting the meter, slide the probe up through the retractor until the internal stop
makes contact. Close the valve shut-off handle by turning the lever 90˚clockwise to isolate the sensor
within the chamber of the retractor (see figure 4.9).
                                        Operation | 81
Model FT3
Operation
F1 F2 F3 F4
             Lift to unlock
             handle
                                                                                   PROBE INSIDE
                                                                                   RETRACTOR
                                                           PAGE 12
After diagnostic procedure is complete, the probe must be reinserting into the pipe to begin
monitoring flow again. When the test has been completed, carefully open shut-off valve, slide the
meter down until the ferrules rest in the fitting, and tighten the compression fitting nut on the fitting
to seal the probe in the stream.
                                             Operation | 82
                                                                                       Model FT3
                                                                                          Operation
When the sensor is isolated in zero flow, the FT3 meter is ready to either perform the Zero CAL-
CHECK™ test or set the field baseline for future tests.
             SET PARAMETERS
       I/O     FLO    DSP   EXIT
F1 F2 F3 F4
      FLOW PARAMETER 1
      DGN UNT PRM           EXIT
F1 F2 F3 F4
              DIAGNOSTIC
      SIM     TEST          EXIT
F1 F2 F3 F4
              DIAGNOSTIC
     CALV     ZRO           EXIT
F1 F2 F3 F4
                                         Operation | 83
Model FT3
Operation
F1 F2 F3 F4
F1 F2 F3 F4
F1 F2 F3 F4
F1 F2 F3 F4
        NOTE! At this point, you must make sure that there is a no flow condition in the pipe (see
        "Techniques for Achieving Zero Flow - In the Pipe" on p. 78). Also be sure that the meter
        will be stable for the duration of the setting process.
If there is no flow and the meter is stable, press YES (F4). The display will show:
F1 F2 F3 F4
As the meter is setting the field baseline, the meter will display the reference value for the Zero
baseline (ZR=xx.xxxx) and a countdown timer (T=xx) to approximate the time until the completion of
the set. Depending on the meter configuration, the set may take between 5-15 minutes to complete.
        NOTE! Do not interrupt the set by touching the meter or changing conditions in the pipe.
        Changing the meter setup may affect the accuracy of the baseline.
                                         Operation | 84
                                                                                   Model FT3
                                                                                      Operation
     Ref=x.xxxx
                            OK
F1 F2 F3 F4
The meter may now perform Zero CAL-CHECK™ tests at the field baseline at any time.
     FLOW PARAMETER 1
     DGN UNT PRM EXIT
F1 F2 F3 F4
             DIAGNOSTIC
      SIM    TST        EXIT
F1 F2 F3 F4
             DIAGNOSTIC
     CALV    ZRO        EXIT
F1 F2 F3 F4
If performing the test in the pipe, a "no flow" condition must be met. If performing the test in
the pipe, a "no flow" condition must be created. If performing out of the pipe, the meter must be
removed and the sensor covered by a bottle or the PVC sensor protector.
F1 F2 F3 F4
                                         Operation | 85
Model FT3
Operation
Press PIP (F1) to choose to perform the test in the pipe. The display will show:
F1 F2 F3 F4
             VERIFY ZRO?
      YES                   NO
F1 F2 F3 F4
F1 F2 F3 F4
        WARNING! If you are using "Pipe" test, you must verify that there is a no flow condition
        before proceeding. If you are performing the test in a bottle, be sure to isolate the sensor in a
        bottle - any air movement (even from a fan) can result in a false "fail" result.
Once process is stable, press YES (F4) key to begin the Zero CAL-CHECK™.
     Verifying ZRO
     Diff = xx.xx         T=xx
F1 F2 F3 F4
This test will take less than 5 minutes. The T=xx is a count down timer indicating how much time is
left to finish the test.
                                        Operation | 86
                                                                                    Model FT3
                                                                                       Operation
     Diff=x.xxx %
      Passed                OK
F1 F2 F3 F4
Upon test completion, the final percentage value will be displayed along with a Pass/Fail message.
Press FLO (F2) from the SET PARAMETERS menu. The display will show:
      FLOW PARAMETER 1
      DGN UNT     PRM      EXIT
F1 F2 F3 F4
          DIAGNOSTIC
      SIM   TST            EXIT
F1 F2 F3 F4
             DIAGNOSTIC
      CALV     ZRO          EXIT
F1 F2 F3 F4
F1 F2 F3 F4
                                         Operation | 87
Model FT3
Operation
Press BTL (F2) to choose to perform the test out of the pipe. The display will show:
F1 F2 F3 F4
              VERIFY ZRO?
      YES                    NO
F1 F2 F3 F4
F1 F2 F3 F4
        WARNING! You must verify that there is a no flow condition before proceeding. Be sure to
        isolate the sensor completely - any air movement (even from a fan) can result in a false "Fail"
        result.
Once process is stable, press YES (F4) key to begin the Zero CAL-CHECK™.
F1 F2 F3 F4 F1 F2 F3 F4
This test will take less than 5 minutes. The display will alternate between the standard deviation
measurement value and the T=xx count down timer indicating how much time is left to finish the test.
      Diff=x.xxx %
      Passed                 OK
F1 F2 F3 F4
Upon test completion, the final value will be displayed along with a Pass/Fail message.
                                         Operation | 88
                                                                                      Model FT3
                                                                                         Operation
     IR KEY= Enabled
     NXT                   OK
F1 F2 F3 F4
        NOTE! After selecting “Disable” and pressing OK (F4), the IR keys will no longer operate. It
        will be necessary from now on to open the cover and operate the configuration panel using
        the mechanical push buttons. To return to the normal display mode, use the mechanical
        buttons to enable the IR keys.
        NOTE! The IR keys are disabled for 1 minute when a mechanical key is used, to prevent
        accidentally activating the IR keys.
        NOTE! Your finger must activate each key approximately 0.1” to .5” from the surface of the
        glass.
To begin the IR key calibration process, turn off power to the FT3 and then turn on power while
placing your fingers on the (F3) and (F4) IR keys at the same time. Activate IR key (F1) to confirm to
begin the IR key calibration. Hold your finger over IR key (F1). In 10 seconds the power level of the IR
key (F1) will be displayed and automatically increase until activation is detected. This will be repeated
for calibration of the (F2), (F3) and (F4) keys.
To check the calibration values of the IR keys, turn off power to the FT3, then turn on power to the FT3
while placing your finger on the (F1) IR key. The display will show the values (example here):
IR = 3,3,3,3
F1 F2 F3 F4
                                         Operation | 89
Model FT3
Communications
Modbus Protocol
Modbus Protocol is an application layer messaging protocol that provides client/sever
communications between devices. Modbus is a request/reply protocol and offers services specified by
function codes.
The size of the Modbus Protocol Data Unit is limited by the size constraint inherited from the first
Modbus implementation on Serial Line network (max. RS485 Application Data Unit = 256 bytes).
Therefore, Modbus PDU for serial line communication = 256 – Server address (1 byte) – CRC (2 bytes)
= 253 bytes.
RS485 ADU = 253 + Server address (1 byte) + CRC (2 bytes) = 256 bytes.
Command Request:
  <Meter Address> <Function code> <Register start address high> <Register start address low>
  <Register count high> <Register count low> <CRC high> <CRC low>
Command Response:
  <Meter Address> <Function code> <Data byte count> <Data register high> <Data register
  low> ... <Data register high> <Data register low> <CRC high> <CRC low>
NOTE! The data shown in brackets < > represents one byte of data.
Modbus Indicators
Orange LED indicator LP2 blinks when Modbus signals are received and yellow LP1 blinks when
Modbus signals are transmitted. The LEDs are located on the Modbus communication board next to
the wiring connections.
                                  Communications | 90
                                                                                        Model FT3
                                                                                Communications
Request:
   <Meter Address> <Command code=03> <Register start address high> <Register start address
   low> <Register count high> <Register count low> <CRC high> <CRC low>
Response:
   <Meter Address> <Command code=03> <Byte count> <Data high><Data low> ... <Data
   high><Data low> <CRC high> <CRC low>
Example: Request data register at starting address 0x0000 and specifying 1 register
Response:
   <0x01> <0x03> <0x02> <xx> <xx> <CRC high> <CRC low>
*To get the actual value of registers 40011-40013, divide the presented value by 10 or 100.
                                       Communications | 91
Model FT3
Communications
                                       Communications | 92
                                                                                       Model FT3
                                                                                 Communications
          NOTES!
        • In the table, LSW means Least Significant Word, and MSW means Most Significant Word.
          In this case a “word” is one 16-bit Modbus register. A 32-bit float or 32-bit integer is
          stored in a pair of Modbus registers. When a register is designated as “32-bit int LSW”, it
          means that bits 0-15 of the variable are in that register. A register designated as MSW has
          bits 16-31 of the variable. For instance, the flow total can be read as a 32-bit integer from
          registers 40003 (LSW) and 40004 (MSW). If the flow total is 0x12345678, then register
          40003 will hold 0x5678, and register 40004 will hold 0x1234.
        • 32-bit floating point values are defined by the IEEE 754 standard: https://ieeexplore.ieee.
          org/document/8766229
        • Refer also to Wikipedia: https://en.wikipedia.org/wiki/Single-precision_floating-point_
          format
Example:
Request data register at starting address 0x0000 and specifying only 1 register:
<0x01> <0x03> <0x00> <0x00> <0x00> <0x01> <0x0a> <0x84>
Command Response
<0x01> <0x03> <0x02> <xx> <xx> <CRC high> <CRC low>
Where xx is the data register value.
                                       Communications | 93
Model FT3
Communications
Request:
   <Meter Address> <Command code=04> <Register address =0> <Register address =0> <Register
   count =0> <Register count =1> <CRC high> <CRC low>
Response:
   <Meter Address> <Command code=04> <Byte count =2> <Status High><Status Low> <CRC
   high> <CRC low>
Table 5.2: Status Bits Definitions for Command 04, Modbus Address 30001
    Bit     Definition                                                Comment
     0      Power up indication                                       Cleared when out of the power up sequence
     1      Flow rate reached high limit threshold                    Set limit to zero to disable
     2      Flow rate reached low limit threshold                     Set limit to zero to disable
     3      Temperature reached high limit threshold                  Set limit to zero to disable
     4      Temperature reached low limit threshold                   Set limit to zero to disable
     5      Sensor reading is out of range                            Check sensor wiring
     6      Velocity flow rate outside of calibration table           Check sensor wiring
     7      Incorrect Settings                                        Check settings
     8      In simulation mode                                        Set simulation value to 0 to disable
     9      Pulse output is out of range                              Check pulse output settings
     10     Analog CH1 4-20mA is out of range                         Check analog output settings
     11     Analog CH2 4-20mA is out of range                         Check analog output settings
     12     Anybus error                                              Replace display board
     13     Bridge Shut Down                                          Check sensor wiring
     14     CRC error                                                 Check parameters and reset CRC
     15     Error in Total                                            Reset total to clear alarm
Table 5.3: Status 2 Bits Definitions for Command 04, Modbus Address 30002
    Bit     Definition
     0      CAL-V in progress
     1      ADC12<> ADC24 too far apart, internal calibration out of range
     2      CAL-V Diff out of range
     3      Curve #2 Selected (for 2 gas curves only)
     4      Zero Check failed
     5      CAL-V/Zero Check aborted
                                           Communications | 94
                                                                                   Model FT3
                                                                             Communications
Request:
   <Meter Address> <Command code=06> <Register address high=0x00> <Register address
   low=0x0a> <Register data high=0x00> <Register data low =0x02> <CRC high> <CRC low>
Response:
   <Meter Address> <Command code=06> <Register address =0x00> <Register address =0x0a>
   <Register data=0x00> <Register data =0x02> <CRC high> <CRC low>
Reset Total:
   Address = 40011, data = 0x02
   This command is used to clear the Totalizer and elapsed time registers
24 hours Event:
   Address=40011, data = 182 (0xB6)
   This command generates a 24 hours event, the same way as when the 24 hours counter rolls over.
   This may be useful to record total over a shorter period.
CAL-V Verify:
  Address=40011, data = 161 (0xA1)
   This command initiates a "CAL_V Verify". This operation may take 4 minutes to complete and
   will stop the meter from calculating flow. The Status2 bit D0 may be monitored to check for
   completion.
   This command initiates a "Zero Check In-Pipe Verify". This operation does not affect flow
   calculations. The register 40069 may be monitored to check for completion.
                                  Communications | 95
Model FT3
Communications
   This command initiates a "Zero Check In-Bottle Verify". This operation does not affect flow
   calculations. The register 40069 may be monitored to check for completion.
   This command initiates a command to switch to gas curve 1 when configured for 2 gas curves.
   Make sure that the input contact is not programmed for curve switching
   This command initiates a command to switch to gas curve 2 when configured for 2 gas curves.
   Make sure that the input contact is not programmed for curve switching.
Request:
<Meter Address> <Function code=06> <Register address high=0x00> <Register address low=0xd5>
<Register data high=0x00> <Register data low =0xx> <CRC high> <CRC low>
Response:
<Meter Address> <Function code=06> <Register address =0x00> <Register address =0xd5>
<Register data=0x00> <Register data =0xx> <CRC high> <CRC low>
       NOTE! The Record Number is an unsigned integer (0-65535) that is incremented every time a
       new record is stored and is not the same as the request record number (0-30).
                                  Communications | 96
                                                                                        Model FT3
                                                                                Communications
Example:
Request:
Request data register at starting address 40200 and specifying 9 register to read the complete record
Response:
Clear Data Log (command 06, Preset Register, Modbus Address 40213)
This command is used to clear all records in the log.
Address register = 40213
Data = 0x57.
Request:
<Meter Address> <Function code=06> <Register address high=0x00> <Register address low=0xd4>
<Register data high=0x00> <Register data low =0x57> <CRC high> <CRC low>
Response:
<Meter Address> <Function code=06> <Register address =0x00> <Register address =0xd4>
<Register data=0x00> <Register data =0x57> <CRC high> <CRC low>
                                      Communications | 97
Model FT3
Communications
Since the Modbus register data is sent most significant byte first and the registers are sent lowest
numbered first, a floating point value will look like this in the data stream:
                                      Communications | 98
                                                                                   Model FT3
                                                                            Communications
Modbus Parameters
To program the communication parameters, start at the SET PARAMETERS menu:
            SET PARAMETERS
      I/O     FLO    DSP   EXIT
F1 F2 F3 F4
               SET I/O
     COM      I/O      420   EXIT
F1 F2 F3 F4
     Comm=Modbus
     NXT                      OK
F1 F2 F3 F4
Press NXT (F1) repeatedly until Modbus is selected as shown and then press OK (F4) to accept the
setting.
     Baud=9600
     NXT                     OK
F1 F2 F3 F4
Press NXT (F1) repeatedly until the correct selection is shown then press OK (F4) to accept the
setting.
Selections are:    115200		              9600
			76800			4800
			57600			2400
			38400			1200
			                19200		
					
                                    Communications | 99
Model FT3
Communications
     Parity=EVEN
     NXT                  OK
F1 F2 F3 F4
Press NXT (F1) repeatedly until the correct selection is shown and then press OK (F4) to accept the
setting.
     Address=02
     CHG                   OK
F1 F2 F3 F4
Press CHG (F1) to change the address and then press OK (F4) to accept the setting.
NOTE! Power cycle is required for the new settings to take effect.
                                 Communications | 100
                                                                                        Model FT3
                                                                                  Communications
Purpose
This specification provides a complete description of this Field Device from a HART Communication
perspective. The specification is designed to be a technical reference for HART capable Host
Application Developers, System Integrators and knowledgeable End Users. It also provides
functional specifications (e.g., commands and performance requirements) used during development,
maintenance and testing. This document assumes the reader is familiar with HART Protocol
requirements and terminology.
References
HART Smart Communications Protocol Specification. HCF_SPEC-12.
Device Identification
Manufacture ID Code: 24635 (603b hex) Device Type Code: 57583 (E0EF Hex)
Physical Layers
                           FSK
Supported:
Physical Device            Transmitter, DC-isolated Bus
Category:                  Device
Product Overview
The FT3 HART communication option can be monitored and configured using a HART master device
or a hand-held communicator.
                                     Communications | 101
Model FT3
Communications
Channel 2 of the 4-20mA output may be configured for flow or temperature values when using HART.
HART Indicators
Green LED indicator LP3 cycles on and off to indicate that the FT3 is operating. Orange LED indicator
LP2 blinks when HART signals are received and Yellow LP1 blinks when HART signals are transmitted.
The LEDs are located on the HART communication board next to the wiring connections.
The orange LED indicator LP2 will be on continuously when HART communication is enabled and the
4-20mA wiring is not connected.
HART Parameters
To program the communication parameters, press I/O (F1) key from the SET PARAMETERS menu.
           SET PARAMETERS
     I/O     FLO    DSP   EXIT
F1 F2 F3 F4
              SET I/O
     COM    PUL     420      EXIT
F1 F2 F3 F4
     Comm=HART
     NXT                  OK
F1 F2 F3 F4
Press NXT (F1) until HART is selected as shown and then press OK (F4) to accept the setting.
                                    Communications | 102
                                                                                           Model FT3
                                                                                   Communications
NOTE! Power cycle is required for the new settings to take effect.
Device Variables
This device does not expose any Device Variables.
Dynamic Variables
Four Dynamic Variables are implemented.
        Variable                   Meaning                    Units
        PV                         Flow Rate                  In Selected Units
        SV                         Total                      In Selected Units
        TV                         Temperature                In Selected Units
        QV                         Elapsed Time               In Hours
Status Information
Device Status
Bit 4 ("More Status Available") is set when any failure is detected. Command #48 provides additional
detail.
                                    Communications | 103
Model FT3
Communications
                                 Communications | 104
                                                                                  Model FT3
                                                                           Communications
Modes
Fixed current mode is implemented, using Command 40. This mode is cleared by power loss or reset.
Damping
Damping is standard, affecting only the PV and the loop current signal.
Capability Checklist
                                  Communications | 105
Model FT3
Data Logger
This section of the manual contains the operation instructions for the FT3 data logger. The FT3 data
logger supports 31 records with a start/sync time of midnight set as a default. When the number of
samples exceeds 31, the oldest data will be overwritten. Only the most recent 31 records are kept.
          SET PARAMETERS
       I/O    FLO  DSP EXIT
F1 F2 F3 F4
              SET I/O
      COM     I/O   420   EXIT
F1 F2 F3 F4
            SET I/O
      INP   OUT    LOG      EXIT
F1 F2 F3 F4
       NOTE! If the hardware does not detect a real time clock, the LOG menu key will not be
       displayed.
            Data log = ON
      NXT                    OK
F1 F2 F3 F4
The default is set with the data logger enabled, press F1 (NXT) to turn the data logger ON or OFF
(the default is ON).
             DATA LOG
      CLR   STR    TIM      EXIT
F1 F2 F3 F4
            DATA LOG
     CLR    STR    TIM      EXIT
F1 F2 F3 F4
F1 F2 F3 F4
For example:
A settting of "day=00, hour=00, minute=00" will reload the interval every day at midnight.
From the data log menu, press F2 (STR). The screen will show:
           Start Time = ON
     NXT                     OK
F1 F2 F3 F4
Press F1 (NXT) to turn ON or OFF the Start/Sync Time and then press F4 (OK):
      Day Start = 0
      CHG                    OK
F1 F2 F3 F4
Press F4 (OK).
     Hour Start = 0
     CHG                     OK
F1 F2 F3 F4
Set the hour for which you want to start/sync time. When the Hour Start is set to zero, the default will
be for midnight. Press F4 (OK).
      Min Start = 0
      CHG                    OK
F1 F2 F3 F4
Set the minute for which you want to start/sync time. Press F4 (OK).
F1 F2 F3 F4
NOTE! Make sure that the specified time has not been reached yet.
             Date/Time
     SET     VIEW          EXIT
F1 F2 F3 F4
Press F1 (SET):
     Year Set = 13
     CHG                   OK
F1 F2 F3 F4
     Month Set = 10
     CHG                    OK
F1 F2 F3 F4
     Day Set = 28
     CHG                    OK
F1 F2 F3 F4
     Hour Set = 13
     CHG                    OK
F1 F2 F3 F4
     Min Set = 45
     CHG                   OK
F1 F2 F3 F4
     Sec Set = 55
     CHG                   OK
F1 F2 F3 F4
      Sec Date/Time
      YES                  NO
F1 F2 F3 F4
        NOTE! All real time clocks on FT3 data loggers are set to a default of California's Pacific
        Standard Time. To sync the real time clock to your local time exactly, set the time slightly
        ahead of your local, current time and wait for the current time to reach the set value before
        pressing the F1 (YES) key to set the time.
            Date/Time
        10/28/13 13:45:55
      F1      F2      F3   F4
The current real time is displayed on line 2 and is updated every second. Press F4 to exit.
NOTE! The seconds will only be displayed if there is enough room available to do so.
F1 F2 F3 F4
NOTE! Record #1 is the most recent interval total, record #31 is the oldest.
This display screen will appear for only 1 second and will then show:
      10/07/13       15:54
      ITOT= 152345.3
F1 F2 F3 F4
The Date and Time is displayed on line 1 and the interval total on line 2. The interval total is based on
the flow units selected in the meter (total mass flow or total volumetric flow).
Pressing F2 will display the next record, F1 will display the previous record.
PRECAUTIONS
      WARNING! BEFORE ATTEMPTING ANY MAINTENANCE, TAKE THE NECESSARY SAFETY
      PRECAUTIONS BEFORE REMOVING THE PROBE FROM THE DUCT (EXAMPLE: PURGE
      LINES OF TOXIC AND/OR EXPLOSIVE GAS, DEPRESSURIZE, ETC...).
        WARNING! EXPLOSION HAZARD. DO NOT REMOVE OR REPLACE COMPONENTS
        OR FUSES UNLESS POWER HAS BEEN SWITCHED OFF WHEN A FLAMMABLE OR
        COMBUSTIBLE ATMOSPHERE IS PRESENT.
        WARNING! EXPLOSION HAZARD. DO NOT DISCONNECT EQUIPMENT WHEN A
        FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.
Access to Electronics
Accessing electronics is not normally required for maintenance purposes. If a loose connection is
suspected, unscrew the rear cap of the meter to access the wiring terminations.
Fuse Replacement
       WARNING! Turn input power OFF before removing or installing a fuse. Use only
       recommended fuse replacements.
Verify the fuse is defective by measuring it with an ohm Meter (two replacement fuses are provided
with each unit). Replacement fuse is Littelfuse part number 0454.750MR.
Sensor Cleaning
The sensor is insensitive to small amounts of residue, but continued use in dirty environments will
require periodic cleaning. To inspect the sensor, remove power from electronics and remove the unit
from the pipe or duct, exposing the sensor elements. If they are visibly dirty, clean them with water or
alcohol (ethanol) using an appropriate brush until they appear clean again. Even though the sensor
elements are rugged, avoid touching them with any solid object and use a light touch while cleaning
them.
                                    Maintenance | 112
                                                                                  Model FT3
                                                                                  Maintenance
Instructions for Removing and Inserting the Meter from a Pressurized Pipe using the Retractor
       WARNING! Possible injury or damage to equipment may occur if the retractor is not used
       correctly. Please read the following instructions carefully prior to using the retractor.
       CAUTION! Never remove the compression fitting without first closing the ball valve and
       bleeding off pressure inside of the retractor.
       WARNING! When working with the retractor, do not stand or position any part of your body
       in the path of the flow meter. An injury may occur if the probe is forced outward by system
       pressure.
        NOTE! At 125 psig of max system pressure, the probe will have approximately 25 lbs. of force
        pushing it out.
2. Loosen the compression fitting nut using two 7/8" wrenches.
3. With one hand supporting the meter, unscrew the compression nut and slide the probe out of the
   retractor until the internal stop halts the travel of the probe.
4. Close the ball valve all the way.
Fig. 7.1: Close Up of Compression Nut and Compression Fitting for Retractor
                                                   Compression Nut,
                                                   7/8" Wrench
                                                   Compression Fitting,
                                                   7/8" Wrench
                                       Maintenance | 113
Model FT3
Maintenance
Compression Nut
Compression Fitting
Nipple
Ball Valve
                                       Maintenance | 114
                                                                                    Model FT3
                                                                                   Maintenance
9. Carefully slide the probe out of the retractor along with the fitting while supporting the meter as
   it comes out. Be careful while handling the meter so the sensor does not get damaged.
How to Insert the Probe into the Flow Stream (Valve closed, System Pressurized)
        WARNING! Never stand where your body or any part of it is in front of the meter. An injury
        may occur if the probe is forced outward by the system pressure.
1. Apply a thin film of anti-seize compound on the compression fitting threads, if needed.
2. Push the probe into the retractor and tighten the compression nut by hand. Align the probe with
   the flow by rotating the probe until the flow direction arrow on the probe fitting is aligned with
   the centerline of the pipe, and points in the direction of flow (see Fig. 7.3).
3. Tighten the compression nut onto the compression fitting using a 7/8” wrench on the nut and a
   7/8” wrench on the fitting.
4. Pressurize the system and check the retractor for leaks. Tighten any of the fittings that may need
   it or seal any leaks that require it.
5. The system may be wired at this point. Refer to the wiring section of this manual for wiring
   instructions for the electronics enclosure. Power may be applied only after the meter has been
   properly wired according to the manual, and it is safe to do so.
                                    Maintenance | 115
Model FT3
Troubleshooting
Troubleshooting
       CAUTION! The electronics and sensor supplied by Fox Thermal are calibrated as a single
       precision mass flow meter. Interchanging sensors will decrease the accuracy of the flow
       meter. If you experience any problem with your model FT3 flow meter, call Fox Thermal
       Customer Service Department, Technical Assistance at (831) 384-4300.
    Problem             Possible Cause(s)                           Action(s)
Meter keeps        1. Power supply             1. Measure power supply voltage to verify it is
power cycling      2. Malfunction in flow         stable and within operating range (refer to
                      meter                       power supply specs on p. 124).
                   3. Electromagnetic          2. Check meter power cycles.
                      Interference (EMI)       3. Press and release F1 and F2 at the same time;
                                                  the display will enter Engineering screens.
                                               4. Press F1 to get to screen #23; record power
                                                  cycle value.
                                               5. Press F4 to return to normal operation; monitor
                                                  meter until problem returns.
                                               6. Return to screen #23 to see if power cycles
                                                  have increased; microprocessor is resetting due
                                                  to EMI electrical noise entering the meter.
                                               7. Check Power input and output cables
                                                  grounding and routing.
                                               8. Return flow meter to Fox Thermal for repair
                                                  (refer to p. 136 for shipping instructions).
Flow measurement 1. Very turbulent flow        1. Increase dampening (see filter settings in "Flow
is erratic or    2. Sensor dirty                  Parameters" on p. 67)
fluctuating      3. Sensor broken              2. Clean sensor (Refer to Maintenance section, p.
                 4. Probe not mounted             112)
                    securely                   3. Return flow meter to Fox Thermal for repair
                 5. Malfunction in flow           (Refer to p. 136 for shipping instructions)
                    meter                      4. Remount probe (see Installation section, p.
                 6. Meter installed               21); must be mounted securely without
                    incorrectly                   vibration. If vibration persists, choose a new
                                                  mounting location without vibration.
                                               5. Return flow meter to Fox Thermal for repair
                                                  (Refer to p. 136 for shipping instructions)
                                               6. Re-install meter according to instructions (Refer
                                                  to installation section, p. 21)
                                Troubleshooting | 116
                                                                                    Model FT3
                                                                              Troubleshooting
Unit will not       1. No power input          1. Check for correct power supply voltage at TS1
power-up            2. Bad fuse                   on main board.
                                               2. Check fuse (F1) located next to TS1 on main
                                                  board.
Meter does not read Calibration table may be   1. Check the calibration table for a corrupted location.
up to full scale    corrupted                  2. Enter the password 9111.
                                               3. From the Flow Parameters 2 menu screen, select
                                                  CAL (F1)
                                               4. Select NXT (F1) to cycle through calibration table
                                                  to verify entries match the calibration certificate.
                                               5. Check for CRC error code.
                                  Troubleshooting | 117
Model FT3
Troubleshooting
Installation Problems
The following is a summary listing of problems that may be encountered with the installation of the
FT3 thermal mass flow meter.
1. Improper wiring connections.
   Refer to Fig. 3.1 to 3.16 and "Wiring Precautions" in Wiring section (p. 33 to p. 49) for further
   guidance.
2. Inadequate power source.
   For FT3 models specified for 24VDC operation, the input voltage must be 24VDC ±10%. A
   20 Watt power supply or greater is recommended for powering the FT3 to ensure it operates
   properly under all temperature ventilation, and power on conditions. If the voltage supplied
   at the input terminals of the FT3 is not within the range of 21.6VDC to 26.4VDC, a variety of
   problems can occur including a dim display, inaccurate flow readings or faulty 4-20mA, pulse and
   communication interface.
3. Flow measurement seems inaccurate.
   • Check to ensure that the flow meter is installed so that the Flow Direction Indicator is pointing
      in the direction of flow. Refer to Fig. 2.6 (p. 25). If not, change orientation of meter.
   • Check that the insertion depth of the sensor/probe is correct. The end of the probe should be
      adjusted as per Fig. 2.5 (p. 24).
   • Ensure that there are a minimum of fifteen diameters of straight pipe upstream of the sensor
      and ten diameters downstream. If complex flow disturbances are upstream of the sensor,
      extension of the straight pipe may be required to ensure accurate flow measurement. Contact
      Fox Thermal for assistance.
   • Ensure that pipe inside diameter in the meter matches data on the Fox Thermal Calibration
      Certificate. The pipe inside diameter is programmed into the flow meter through the front
      panel (see Flow Parameters, p. 67).
4. Erratic flow reading (especially a flow reading spiking high).
   This may be a symptom of moisture in the flow stream. Fox Thermal flow meters are designed
   to work in relatively dry gas applications only. Contact Fox Thermal to discuss resolutions to this
   problem.
5. Flow meter is not responding to flow.
   • Check to ensure adequate power is supplied to the flow meter. If things appear to be correct,
      perform this functional test before calling Fox Thermal. Carefully remove the probe and sensor
      from the pipe. For those flow meters with a display - and if the display is reading zero - blow
      on the sensor to see if a response occurs. If nothing happens, take a damp rag or sponge and
      place it in contact with the sensor. A reading should occur. Contact Fox Thermal Customer
      Service with this information.
6. Display and/or 4-20mA signal reading above zero flow when no flow is occurring in the pipe.
   If the reading is less than 5% of full scale, it is likely this is a normal condition caused by
   convection flow created by the heated sensor. It does not mean that the zero of the instrument is
   improperly set. The Fox Thermal sensor is extremely sensitive to gas flow and can even read the
   small flow caused by convection. If this is an unacceptable condition, please contact Fox Thermal
   Customer Service for alternatives.
7. Mismatched serial numbers.
   If you have more than one meter, you must ensure that the serial numbers of meter, remote, and/
   or flow body match one another. These items have been manufactured and calibrated to operate
   as a unit and cannot be mismatched.
                                   Troubleshooting | 118
                                                                                       Model FT3
                                                                                Troubleshooting
Troubleshooting CAL-V™
If the FT3 meter fails a CAL-V™ Calibration Validation test, follow the steps below:
                                   Troubleshooting | 119
Model FT3
Troubleshooting
Alarm Codes
Alarm
            Reason                                          Action
Code
  13  Flow rate above       Refer to the PARAMETER MENU 2 section on p. 67 of this Manual to
      high limits           verify limit is within range. Check ALM = HiFloAlm under PRM.
  14  Flow rate below       Refer to the PARAMETER MENU 2 section on p. 67 of this Manual to
      low limits            verify limit is within range. Check ALM = LoFloAlm under PRM.
  15  Temperature           Refer to the PARAMETER MENU 2 section on p. 67 of this Manual to
      above high limits     verify limit is within range. Check ALM=HiTempAlm under PRM.
  16  Temperature           Refer to the PARAMETER MENU 2 section on p. 67 of this Manual to
      below low limits      verify limit is within range. Check ALM = LoTempAlm
  22  Sensor out of         Refer to the ENGINEERING DISPLAY MENU on p. 16 of this Manual
      range                 and the Fox Thermal factory Calibration Certificate to check CSV
                            voltage. Compare Display 10 value to Calibration Certificate CSV
                            voltage and verify it's within range.
  23   Velocity out of      Refer to the ENGINEERING DISPLAY MENU on p. 16 of this Manual
       calibration table    and the Fox Thermal factory Calibration Certificate to check CSV
       range                voltage. Compare Display 10 value to Calibration Certificate CSV
                            voltage and verify it's within range.
  24   Check settings       One or more internal settings are corrupted or out of spec. Contact Fox
                            Thermal Service for instructions to verify settings.
  25   Simulation mode      Meter is in Simulation Mode. Refer to the PARAMETER MENU 1 section
                            on p. 70 of this Manual. Use the SIM Section under Diagnostics to
                            return to normal operation.
  26   Frequency output     Refer to the DIGITAL OUTPUT MENU on p. 56 of this Manual. Verify
       over range           the Frequency Output settings are within limits.
  32   4-20mA for flow      Refer to the MAIN MENU on p. 54 of this Manual. Use the Set I/O
       rate is out of       section to verify range limits under FLO Set 4-20mA.
       range
  33   4-20mA for           Refer to p. 54 of this Manual. Use the Set I/O section to verify
       temperature is out   range limits under FLO Set 4-20mA. Channel #2 can be set for flow or
       of range             temperature.
  34   Busy                 Meter is recalculating new parameters.
  35   Sensor Bridge        The FT3 sensor readings are not correct. Check the sensor wiring to the
       Shutdown             FT3 electronic enclosure and remote enclosure..
  36   Database CRC         Refer to the PARAMETER MENU 2 section on p. 74 of this Manual to
       Error                reset CRC. Use SPC section of menu to reset CRC. Contact Fox Thermal
                            Service Department for possible causes.
                                Troubleshooting | 120
                                                                                 Model FT3
                                                                           Troubleshooting
Alarm
            Reason                                        Action
Code
  37  Totalizer Error     See "Reset the Total and Elapsed Time" on p. 74 for steps to clear
      Detected            Error Code. Contact Fox Thermal for possible causes.
  38  CAL-V™ in           Wait until the CAL-V™ or Cal Set is finished.
      progress
  39  ADC12 versus      The tolerance between the 2 analog to digital converters is out of
      ADC24 too far     specification. Recalling manufacture default parameters using the
                        Restore Database command on p. 11 may correct the problem.
  40   CAL-V™ Diff Fail The CAL-V™ Diff Failed. Check sensor wiring and verify that the
                        sensor's resistance is correct. Call Tech Support.
  41   Zero CAL-CHECK™ Allow meter to stabilize for 15 minutes and perform the test again. If
       Fail             another "Fail" test results, call Tech Support.
                               Troubleshooting | 121
Model FT3
Appendix
Performance Specs
Flow Accuracy:
  ±1% of reading ±0.2% of full scale
   Accuracy specification applies to customer's selected flow range
   Maximum range: 15 to 60,000 SFPM (0.07 to 280 NMPS)
   Minimum range: 15 to 500 SFPM (0.07 to 2.4 NMPS)
   Straight, unobstructed pipe requirement
       Insertion Meters: 15 diameters upstream; 10 downstream
       Inline Meters (1/2" size): 6" (152mm) upstream and downstream
       Inline Meters (all other sizes): 8 diameters upstream; 4 downstream
Operating Specs
Units of Measurement (field selectable):
  SCFM, SCFH, NMPS, NM3/M, NM3/H, NM3/D, NLPS, NLPM, NLPH, SCFD, MSCFD, MMSCFD,
  MMSCFM, SMPS, SM3/D, SM3/H, SM3/M, LB/S, LB/M, LB/H, LB/D, KG/S, KG/M, KG/H, SLPM, SFPM,
  MT/H, MCFD
                                          Appendix | 122
                                                                                                         Model FT3
                                                                                                              Appendix
  NOTE! To determine if the FT3 will operate accurately in other pipe sizes, divide the maximum flow rate by the pipe area.
  The application is acceptable if the resulting velocity is within the velocity range above. Check Fox Thermal website for
  velocity calculator.
  NOTE! Standard conditions of air at 70°F and one atmosphere. Consult factory for other gases and for flow ranges above
  those listed. Inline meters above 2,500 SCFM (7,900 NM3/H) air may require third party calibration. Contact Fox Thermal.
                                                Appendix | 123
Model FT3
Appendix
Inputs/Outputs:
  4-20mA Channel 1:
   • Standard isolated 4-20mA output configured to indicate flow; fault indication per NAMUR
      NE43.
  4-20mA Channel 2:
   • Standard isolated 4-20mA output configured to indicate either flow or temperature; fault
      indication per NAMUR NE43.
  Pulse/Alarm:
   • Isolated open collector output rated for 5 to 24VDC, 20mA maximum load, 0 to 100Hz (the
      pulse output can be configured to either transmit a 0 to 100Hz signal proportional to flow
      rate or an on/off alarm).
  Remote Switch Input:
   • Can be configured to reset the flow totalizer and elapsed time.
  Serial Communication
   • Isolated Modbus RTU (RS485) option
   • Isolated HART communication option
  USB Communication:
   • Isolated USB 2.0 for interfacing with a laptop or computer is standard.
   • FT3 View™: A free PC-based software tool that provides complete configuration, remote
      process monitoring, and data logging functions through USB communication.
Physical Specs
Sensor material:
  316 stainless steel, Hastelloy C276 optional
Enclosure:
  NEMA 4X (IP67), aluminum, dual ¾” FNPT conduit entries. Cabling to remote enclosure: 5-conductor,
  18 AWG, twisted, shielded, 100 feet maximum.
                                       Appendix | 124
                                                                                               Model FT3
                                                                                                    Appendix
Agency Approvals
CE: Approved
  EMC Directive; 2014/30/EU
  Electrical Equipment for Measurement, Control and Lab Use: EN61326-1:2013
  Low Voltage Directive (LVD): 2014/35/EU
  Product Safety Testing: EN 61010-1: 2010
  Pressure Equipment Directive: 2014/68/EU
  Weld Testing: EN ISO 15614-1 and EN ISO 9606-1, ASME B31.3
FM and FMc: Approved
  Class I, Division 1, Groups B,C,D;
  Class II, Division 1, Groups E,F,G;
  Class III, Division 1; T3C, Ta = - 40˚C to +70˚C;
  Class 1, Zone 1, AEx/Ex d IIB + H2 (T6, T4, or T1*); Ta= -20˚C to +70˚C; Type 4X (IP67)
ATEX (FM12ATEX0034X): Approved
  II 2 G Ex db IIB + H2 (T6, T4, or T1*) Gb Ta = - 20˚C to +70˚C; IP67
  II 2 D Ex tb IIIC (T85˚C, T135˚C, or T450˚C*) Db Ta = - 20˚C to +70˚C; IP67
IECEx (IECEx FMG 12.0010X): Approved
  Ex db IIB + H2 (T6, T4, or T1*) Gb Ta = - 20˚C to +70˚C; IP67
  Ex tb IIIC (T85˚C or T135˚C*) Db Ta = - 20˚C to +70˚C; IP67**
  ATEX and IECEx Standards:
  EN 60079-0 		               EN 60079-31			             IEC 60079-0		        IEC 60079-31
  EN 60079-1		                EN 60529 +A1 		            IEC 60079-1		        IEC 60529
  					
Model Code                             Temp. Code Marking - Zones (Gas)       Temp. Code Marking - Zones (Dust)
Enclosure           Sensor Type        Main Enclosure      Remote Enclosure   Main Enclosure      Remote
                                                                                                  Enclosure**
E1                  ST                 T4                  N/A                135°C               N/A
E2                  ST                 T4                  N/A                135°C               N/A
E3                  ST                 T6                  T4                 85°C                135°C**
E4                  ST                 T6                  T4                 85°C                135°C**
E3                  HT                 T6                  T1                 85°C                450°C**
E4                  HT                 T6                  T1                 85°C                450°C**
*Temperature code ratings for Zones are dependent on external process temperature factors and equipment enclosure
configuration. See the table above for specific temperature code ratings.
**The IECEx dust rating does not apply to the Remote Enclosure.
                                            Appendix | 125
Model FT3
Appendix
                                                               8.1
                                                              (20.6)
                               4.6                                      3.9
                              (11.7)                                   (9.9)
                  6.5
                 (16.5)
                                       10.75±.13
                                       (27.3 ±.33)
                  “LL”
                                         Appendix | 126
                                                                                                        Model FT3
                                                                                                          Appendix
                                                                                                                            5.9
 5.2                                                                                                                       (15.0)
(13.2)
                           2X 3/4” NPT,
                             FEMALE
                                                                                                                      10.75±.13
                                                                                                                      (27.3 ±.33)
                                                                                                 “LL”
                                                   Appendix | 127
Model FT3
Appendix
                                                                                                       SIDE VIEW
                   BRACKET
             2x U-BOLT
               W/NUT                                                JAM NUT
                                                                      SEE ADAPTER
                                                                      DETAIL
                                                                                              PROJECTIONS
                                                                   ADAPTER
                             Ø2.38             4x
                                             WASHER
                           2 IN. PIPE
                                                                                                       THREADS
                                                                                      ADAPTER DETAIL
F1 F2 F3 F4
4x Ø.344 2.81
2.81
                                                                         MOUNTING
                                                                         HOLE DETAIL
                                                            Appendix | 128
                                                                                                        Model FT3
                                                                                                             Appendix
                                                                                                8.1
                                                                                               (20.6)
                                             4.6
                                            (11.7)                                     4.3
                                                                                      (10.9)
                            Input                            Signal
                            Power                            Wiring
(13.2)
“HH”
“LL”
FLOW CL
                 Probe Size           Probe Size             Dimension “LL” ± .10              Dimension "HH" ± .10
                [model code]           [inches]              [inches / millimeters]             [inches / millimeters]
                          06IE                    6"                  6.0" (152mm)                      12.9" (318mm)
                          09I                     9"                  9.0" (229mm)                      15.5" (394mm)
                          12I                    12"                  12.0" (305mm)                     18.5" (470mm)
                          15I                    15"                  15.0" (381mm)                     21.5" (546mm)
                          18I                    18"                  18.0" (457mm)                     24.5" (622mm)
                          24I                    24"                  24.0" (610mm)                     30.5" (775mm)
                          30I                    30"                  30.0" (762mm)                     36.5" (927mm)
                          36I                    36"                  36.0" (914mm)                     42.5" (1080mm)
                                                      Appendix | 129
Model FT3
Appendix
                                                                                                                  3.6
                                                                                                                 (9.1)
                                                                                                         4.4
                                                                                                        (11.2)
                                                                                                              2.0
                                           4.6                                                               (5.1)
                                          (11.7)
                             Input
                                                                                                                          4.5
                             Power
                                                                                                                         (11.4)
                      2x 3/4 inch
            5.2
                      NPT Female     F1    F2   F3   F4
                                                                       Remote Cable, 5 Conductor,
           (13.2)                                                      Shielded, 100ft (30.48m) Max.
                                                                                                                                         “HH”
“LL”
FLOW CL
Table 8.5: Insertion Remote Meter with 316 stainless steel probe
            Probe Size               Probe Size                   Dimension “LL” ± .10                 Dimension “HH” ± .10
          [model code]                          [inches]          [inches / millimeters]               [inches / millimeters]
                    06IE                                  6"            6.0" (152mm)                                 11.9" (302mm)
                    09I                                   9"            9.0" (229mm)                                 14.9" (379mm)
                    12I                                   12"          12.0" (305mm)                                 17.9" (455mm)
                    15I                                   15"          15.0" (381mm)                                 20.9" (531mm)
                    18I                                   18"          18.0" (457mm)                                 23.9" (607mm)
                    24I                                   24"          24.0" (610mm)                                 29.9" (760mm)
                    30I                                   30"          30.0" (762mm)                                 35.9" (912mm)
                    36I                                   36"          36.0" (914mm)                              41.9" (1064mm)
                                                           Appendix | 130
                                                                                                                        Model FT3
                                                                                                                             Appendix
Fig. 8.6: Inline Meter with Flow Body and NPT End Connections Dimensions
                                                                                                           8.1
                                                                                                          (20.6)
                                                     4.6
                                                    (11.7)                                        4.3
                                                                                                 (10.9)
                                 Input                              Signal
                                 Power                              Wiring
“H”
CL
“L”
Table 8.6: Inline Meter with Flow Body and NPT End Connections
              Body Size                        Body Size                Dimension “L” ± .10                        Dimension “H” ± .10
             [model code]                       [inches]                     [inches]                              [inches / millimeters]
                     05P *                               0.50"                             12"                         10.5" (267mm)
                    075P *                               0.75"                             12"                         10.5" (267mm)
                     10P *                               1.00"                             12"                         10.5" (267mm)
                     125P *                              1.25"                             12"                         10.5" (267mm)
                     15P *                               1.50"                             12"                         10.5" (267mm)
                    20P **                               2.00"                             12"                         10.5" (267mm)
                    25P **                               2.25"                             18"                         10.6" (269mm)
                    30P **                               3.00"                             18"                         12.5" (318mm)
                                                              Appendix | 131
Model FT3
Appendix
Fig 8.7: Inline Remote Meter with Flow Body and NPT End Connections Dimensions
                                                                                                            3.6
                                                                                                           (9.1)
                                                                                                4.4
                                                                                               (11.2)
                                                                                                         2.0
                                       4.6                                                              (5.1)
                                      (11.7)
                Input
                                                                                                                    4.5
                Power
                                                                                                                   (11.4)
CL
“L”
Table 8.7: Inline Remote Meter with Flow Body and NPT End Connections
                 Body Size                           Body Size      Dimension “L” ± .10                         Dimension “HH” ± .10
                [model code]                          [inches]                   [inches]                       [inches / millimeters]
                        05P *                           0.50"                          12"                                  10.5" (267mm)
                        075P *                          0.75"                          12"                                  10.5" (267mm)
                        10P *                           1.00"                          12"                                  10.5" (267mm)
                        125P *                          1.25"                          12"                                  10.5" (267mm)
                        15P *                           1.50"                          12"                                  10.5" (267mm)
                        20P **                          2.00"                          12"                                  10.5" (267mm)
                        25P **                          2.50"                          18"                                  10.6" (269mm)
                        30P **                          3.00"                          18"                                  12.5" (318mm)
                                                          Appendix | 132
                                                                                                                                            Model FT3
                                                                                                                                                Appendix
Fig. 8.8: Inline Meter with Flow Body and 150 lb. RF Flange End Connections Dimensions
                                                                                                           8.1
                                                                                                          (20.6)
                                                                                          4.3
                                            4.6
                                           (11.7)                                        (10.9)
                                      F1   F2    F3   F4           5.2
                                                                  (13.2)
“H”
CL
“L”
Table 8.8: Inline Meter with Flow Body and 150 lb. RF Flange End Connections Dimensions
                   Body Size                               Body Size            Dimension “L” ± .10                            Dimension “H” ± .10
               [model code]                                 [inches]                 [inches]                                  [inches / millimeters]
                          05F *                               0.50"                     12"                                                 10.5" (267mm)
                         075F *                               0.75"                     12"                                                 10.5" (267mm)
                          10F *                               1.00"                     12"                                                 10.5" (267mm)
                         125F *                               1.25"                     12"                                                 10.5" (267mm)
                          15F *                               1.50"                     12"                                                 10.5" (267mm)
                         20F **                               2.00"                     12"                                                 10.5" (267mm)
                         25F **                               2.50"                     18"                                                 10.6" (269mm)
                         30F **                               3.00"                     18"                                                 12.5" (318mm)
                         40F **                               4.00"                     18"                                                 12.5" (318mm)
                         60F **                               6.00"                     24"                                                 12.5" (318mm)
                                                                Appendix | 133
Model FT3
Appendix
Fig 8.9: Inline Remote Meter with Flow Body and 150 lb. RF Flange End Connections Dimensions
                                                                                                       3.6
                                                                                                      (9.1)
                                                                                           4.4
                                                                                          (11.2)
                                                                                                    2.0
                                                                                                   (5.1)
                                   4.6
                                  (11.7)
                                                                                                               4.5
          2X 3/4 " NPT,
                                                                                                              (11.4)
          Female
        5.2
                                                             Remote Cable, 5 Conductor,
                             F1   F2   F3   F4
       (13.2)
                                                             Shielded, 100FT Max.
                                                                                                                           “HH”
CL
“L”
Table 8.9: Inline Remote Meter with Flow Body and 150 lb. RF Flange End Connections Dimensions
             Body Size                           Body Size   Dimension “L” ± .10           Dimension “HH” ± .10
            [model code]                          [inches]        [inches]                  [inches / millimeters]
                    05F *                          0.50"                      12"                          10.5" (267mm)
                   075F *                          0.75"                      12"                          10.5" (267mm)
                    10F *                          1.00"                      12"                          10.5" (267mm)
                   125F *                          1.25"                      12"                          10.5" (267mm)
                    15F *                          1.50"                      12"                          10.5" (267mm)
                    20F **                         2.00"                      12"                          10.5" (267mm)
                    25F **                         2.50"                      18"                          10.6" (269mm)
                    30F **                         3.00"                      18"                          12.5" (318mm)
                    40F **                         4.00"                      18"                          12.5" (318mm)
                    60F **                         6.00"                      24"                          12.5" (318mm)
                                                     Appendix | 134
                                                                                     Model FT3
                                                                                         Appendix
Fox Thermal warrants that for a period of one year following the date of original shipment of Fox’s
products that the product will conform to Fox’s standard written specifications applicable to such
product and will be free from defects in workmanship. For more details, view the Limited Warranty
section in the Terms and Conditions of Sale. Find that document at this link:
https://www.foxthermal.com/pdf/terms-and-conditions.pdf
Fox warrants that consumable materials, supplied by Fox either as part of an instrument or system, or
separately, will be free from defects in material and workmanship at the time of shipment. A list of key
consumables and expected lifetimes may be found in the applicable Seller equipment operation and
maintenance manual.
For more details about Fox’s warranty statement and exclusions, please download the Terms and
Conditions of Sale document. Find that document at this link:
https://www.foxthermal.com/pdf/terms-and-conditions.pdf
                                       Appendix | 135
Model FT3
Appendix
If it becomes necessary to return a Fox Thermal flow meter for service or recalibration, please follow
these steps:
1. A Return Material Authorization (RMA) Number must be obtained from the Fox Thermal Customer
   Service Department prior to returning any Fox Thermal meter(s).
2. Please have your meter’s serial number(s) available.
3. Read and complete the Fox Thermal RMA Customer Information Form. Be sure to initial the
   decontamination statement as well as provide complete return shipping instructions (we cannot
   deliver to post office boxes).
4. The entire flow meter must be returned, including all electronics (unless specifically instructed
   to do otherwise). ALL serial numbers must match their corresponding meters. This is especially
   necessary when returning flow body models.
5. Clean and decontaminate all wetted parts before returning to Fox Thermal.
6. Ship the meter to the following address:
   Fox Thermal Instruments, Inc.
   399 Reservation Road
   Marina, CA 93933
   Attn: Service Dept.
   [RMA Number]
         NOTE! Be sure to review all of the information on the Customer Information Form before
         sending your meter to the Fox Thermal Customer Service Department. The Fox Thermal
         Shipping/Receiving Department cannot accept meters that have not been prepared
         appropriately.
If you have already shipped your meter to Fox Thermal for servicing and would like to check the
status of your meter, please fill out our online Service Order Status form located at www.foxthermal.
com and you will hear from a Customer Service Rep within 1 business day of your requested update.
                                         Appendix | 136
                                                                                 Model FT3
                                                                                      Appendix
                                          Appendix | 137
Model FT3
Appendix
Index
                                               Appendix | 138
Appendix | 139
           Wiring                                         Definition of Terms
           Indicates compliance with the WEEE Directive. Please dispose of the product in
           accordance with local regulations and conventions.
           Indicates compliance with the applicable European Union Directives for Safety LVD
           (Low Voltage Directive), EMC (Electromagnetic Compatibility Directive), and PED
           (Pressure Equipment Directive).
IP67       Enclosure Protection Classification per IEC 60529: Protected against the ingress of
           dust and Immersion.
SALES@FOXTHERMAL.COM                                                                      Phone
                                                                                    831.384.4300
Address
399 Reservation Road                                                                  Worldwide
Marina, CA 93933 USA                                                              foxthermal.com