OFFICE OF THE BUILDING OFFICIAL
SPECIFICATIONS
1. ELECTRIC SERVICE SHALL BE 230V, 1-PHASE, 2-WIRE, 60 CYCLES SAN MANUEL, ISABELA
PER SECOND.
e
h 4. TYPE OF WIRING SHALL BE CONCEALED ON WALLS AND CEILING
e l m S FOR LIGHTING AND POWER LOADS SHALL BE DONE IN PVC WITH
MINIMUM SI E OF 15MM. ELECTRICAL
S
S2gh
q
5. INSTALLATION HEIGHT SHALL BE AS FOLLOWS:
g S3lmn o A) LIGHTING SWITCHES 1.4 m ABOVE FINISHED FLOOR LINE
f S n B) CONVENIENCE OUTLETS 0.3 m ABOVE FINISHED FLOOR LINE
C) PANELBOARDS (@ THE CENTER) 1.7 m ABOVE FINISHED FLOOR LINE
L E G E N D
d d S3def
b S3opq
6. SWITCHES AND CONVENIENCE OUTLETS SHALL BE RATED 10
i DN
AND 15 AMPERES RESPECTIVELY, 240 V, FLUSH TYPE. SERVICE ENTRANCE
j
c c
k C2 CIRCUIT BREAKER
7. ALL MATERIALS AND E UIPMENT TO BE USED SHALL BE BRAND NEW AND
S3ijk
APPROVED FOR THAT PURPOSE.
a a
S3abc UP
c
CIRCUIT HOMERUN
8. ALL ELECTRICAL CONDUCTORS TO BE USED SHALL BE STRANDED
COPPER AS MANUFACTURED BY PHELPS DODGE OR APPROVED E UAL.
i
j 9W PINLIGHT
b
C1 9. EFFECTIVE GROUNDING SYSTEM SHOULD BE PROVIDED IN ACCORDANCE 32W CIRCULAR
WITH THE LATEST PROVISION OF THE PHILIPPINE ELECTRICAL CODE.
FLUORESCENT LAMP
10. ALL ELECTRICAL INSTALLATION SHALL BE DONE UNDER THE DIRECT q
SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER OR MASTER 23W PINLIGHT
ELECTRICIAN.
300 VA CHANDELIER
GROUND FLOOR LIGHTING LAY OUT SECOND FLOOR LIGHTING LAY OUT 11. ALL WORKS SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION OF
THE PHILIPPINE ELECTRICAL CODE (PEC), THE RULES AND REGULATIONS OF CIRCUIT LINE
LOCAL AND NATIONAL AUTHORITIES CONCERNED WITH ENFORCEMENT OF
RULES AND REGULATIONS OF LOCAL UTILITY COMPANY
COVENIENCE OUTLET LINE
2
DUPLEX CONVENIENCE OUTLET
C5 C6 C3 C4 CH
COUNTER HEIGHT OUTLET
WP
WEATHER PROOF D.C.O.
ref ra
DESIGN ANALYSIS Ra
RANGE OUTLET
REF
REFRIGERATOR OUTLET
EMP
ELECTRIC MOTOR PUMP
AIR CONDITIONING UNIT
CIRCUIT C5 ReF Outlet @ 700 VA ACU OUTLET
CIRCUIT C1 14 LO @ 25 VA = 350 VA
I = 700 VA / 220 V = 3.18 A ONE GANG SWITCH
I = 350 VA / 220 V = 1.59 A S.
Ic = 3.18 x 1.25 = 3.98A
Ic = 1.59 x 1.25 = 2.00 A
DN USE:2- 3.5 sq. mm. THHN Cu. Wire + S2. TWO GANG SWITCH
USE: 2- 2.0 sq. mm. THHN Cu. Wire IN 15mmØ Conduit
1- 2.0 sq. mm. TW (G) IN 15 mm Conduit
15AT CB, 2P, 250V, 10KAIC
20AT CB, 2P, 250V, 10KAIC S3. THREE GANG SWITCH
CIRCUIT C2 15 LO @ 25 VA = 375 VA
CIRCUIT C6 Range Outlet @ 2000 VA
UP
DONE IN THE OFFICE OF DESIGN BY: NOTE PROJECT TITLE/LOCATION: APPROVED BY: SHEET CONTENTS: REVISION: DATE: DRAWN BY: SHEET NO.:
RESIDENCE
FOR ANY PERSON TO DUPLICATE OR TO MAKE COPIES OF AS INDICATED
ARCHITECTURAL OFFICE PTR NO.: 8809066 PRC NO.: 002894 SAID DOCUMENTS FOR USE IN THE REPETITION OF AND DATE:
DPWH
SCHEDULE OF LOADS SHORT CIRCUIT CALCULATION
OFFICE OF THE BUILDING OFFICIAL
CKT
VOLT LOADS LOAD CIRCUIT PROTECTION CONDUIT EXISTING TRANSFORMER , 100KVA / 230V ,1PHASE , % Z=1.6%
DESCRIPTION VOLTS AMPERE CURRENT WIRE SIZE AND TYPE IMPEDANCE DIAGRAM
NO. SIZE ( µPVC )
(VA) L.O. C.O. OTHERS (A) AT AF POLE
SHORT CIRCUIT CURRENT CALCULATION ( PER UNIT METHOD )
C-1 LIGHTING OUTLET 220V 350 14 1.59 15 AT 50 2 2.0MM² THHN CU 15MMØ SAN MANUEL, ISABELA
C-2 LIGHTING OUTLET 375 15 1.70 15 AT 2.0MM² THHN CU UTILITY SHORT CIRCUIT AVAILABLE , 100MVA Zs = .001
100 MVA
SERVICE ENTRANCE, 2W E base Va
lsc = x
TRANSFORMER Z base V
100 KVA ,230V ,1.6%
1.0 x 100,000
lsc = = 4063A
.107 230 V
14 mm² ( L=30m)
M
Use : 10 Kaic Circiut Breaker
SINGLE LINE DIAGRAM MCB
X "a"
@ MCB
GROUND
DONE IN THE OFFICE OF DESIGN BY: NOTE PROJECT TITLE/LOCATION: APPROVED BY: SHEET CONTENTS: REVISION: DATE: DRAWN BY: SHEET NO.:
RESIDENCE
FOR ANY PERSON TO DUPLICATE OR TO MAKE COPIES OF AS INDICATED
ARCHITECTURAL OFFICE PTR NO.: 8809066 PRC NO.: 002894 SAID DOCUMENTS FOR USE IN THE REPETITION OF AND DATE: